Carrier GAS FURNACE 58MTA User`s manual

58MXA
4-Way Multipoise Fixed-Capacity
Direct-Vent Condensing Gas Furnace
Visit www.carrier.com
Service and Maintenance Instructions
For Sizes 040-140, Series 160
ELECTRICAL SHOCK, FIRE, OR EXPLOSION HAZARD
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death, or property damage.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
- Before servicing, disconnect all electrical power to furnace.
- When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
- Verify proper operation after servicing.
A93040
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools, and
equipment. If you do not possess these, do not attempt to
perform any maintenance on this equipment other than those
procedures recommended in the User’s Manual. FAILURE
TO FOLLOW THIS WARNING COULD RESULT IN
POSSIBLE DAMAGE TO THIS EQUIPMENT, SERIOUS
PERSONAL INJURY, OR DEATH.
®
®
•••••
Never store anything on, near, or in contact with the furnace,
such as:
1. Spray or aerosol cans, rags, brooms, dust mops, vacuum
cleaners, or other cleaning tools.
2. Soap powders, bleaches, waxes or other cleaning compounds, plastic or plastic containers, gasoline, kerosene,
cigarette lighter fluid, dry cleaning fluids, or other volatile
fluids.
3. Paint thinners and other painting compounds, paper bags,
or other paper products.
Failure to follow this warning can cause corrosion of the heat
exchanger, fire, personal injury, or death.
U L T R A
G A S
•••••
H I G H
•••••
C Y
E F F I C I E N
C E
F U R N A N
NOTE: Read the entire instruction manual before starting the
installation.
This symbol → indicates a change since the last issue.
TABLE OF CONTENTS
SAFETY CONSIDERATIONS .....................................................2
GENERAL......................................................................................2
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS........2
CARE AND MAINTENANCE.....................................................2
Cleaning and/or Replacing Air Filter.......................................3
Blower Motor and Wheel Maintenance...................................3
Cleaning Burners ......................................................................4
Cleaning Heat Exchangers........................................................5
Primary Heat Exchangers ......................................................5
Secondary Heat Exchangers ..................................................6
Flushing Collector Box and Drainage System ........................6
A93007
Fig. 1—Multipoise Furnace in Upflow Orientation
Servicing Hot Surface Igniter...................................................7
Electrical Controls and Wiring.................................................8
Checking Heat Tape Operation (If Applicable) ....................10
Winterizing..............................................................................10
WIRING DIAGRAM...................................................................11
TROUBLESHOOTING ...............................................................11
Status Codes............................................................................11
Component Tests ....................................................................11
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
PC 101
Catalog No. 535-80099
Printed in U.S.A.
Form 58MXA-9SM
Pg 1
11-02
Replaces: 58MXA-8SM
Tab 6a 8a
AIRFLOW
ie
rr
r Cor pora
UPFLOW
ti
on
Ca
EFFICIENCY
RATING
CERTIFIED
®
I
IR
REG
ST
I
SO
M
CERTIFIED
900
HORIZONTAL
RIGHT
HORIZONTAL
LEFT
E R E D F8 3
1 #A28
DOWNFLOW
AIRFLOW
REGISTERED QUALITY SYSTEM
AIRFLOW
AIRFLOW
SAFETY CONSIDERATIONS
A93041
Recognize safety information. This is the safety-alert symbol .
When you see this symbol on the furnace and in instructions or
manuals, be alert to the potential for personal injury.
Fig. 2—Multipoise Orientation
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing to
protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools
which are held during the procedure. These precautions will
help to avoid exposing the control to electrostatic discharge
by putting the furnace, the control, and the person at the same
electrostatic potential.
Installing and servicing heating equipment can be hazardous due to
gas and electrical components. Only trained and qualified
service agency personnel should install, repair, or service
heating equipment. Untrained personnel can perform basic
maintenance functions described in User’s Information
Manual such as cleaning and replacing air filters. All other
operations must be performed by trained and qualified service
agency personnel. When working on heating equipment, observe
precautions in the literature, on tags, and on labels attached to or
shipped with the unit and other safety precautions that may apply.
1. Disconnect all power to the furnace. DO NOT TOUCH THE
CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
2. Firmly touch a clean, unpainted, metal surface of the furnace
chassis which is close to the control. Tools held in a person’s
hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the
control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example; DO
NOT move or shuffle your feet, DO NOT touch ungrounded
objects, etc.).
→ Follow
all safety codes including the National Fuel Gas Code
(NFGC) NFPA 54-2002/ANSI Z223.1-2002 in the U.S.A.; National Standard of Canada, Natural Gas and Propane Installation
Code CSA B149.1-00 (NSCNGPIC) in Canada; and the Installation Standards, Warm Air Heating and Air Conditioning Systems
(NFPA 90B) ANSI/NFPA 90B. Wear safety glasses and work
gloves. Have a fire extinguisher available during start-up and
adjustment procedures and service calls.
4. If you touch ungrounded objects (recharge your body with
static electricity), firmly touch furnace again before touching
control or wires.
5. Use this procedure for installed and uninstalled (ungrounded)
furnaces.
6. Before removing a new control from its container, discharge
your body’s electrostatic charge to ground to protect the
control from damage. If the control is to be installed in a
furnace, follow items 1 through 5 before bringing the control
or yourself into contact with the furnace. Put all used AND
new controls into containers before touching ungrounded
objects.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous
operation.
GENERAL
7. An ESD service kit (available from commercial sources) may
also be used to prevent ESD damage.
These instructions are written as if the furnace is installed in an
upflow application. An upflow furnace application is where the
blower is located below the combustion and controls section of the
furnace, and conditioned air is discharged upward. Since this
furnace can be installed in any of the 4 positions shown in Fig. 2,
you may need to revise your orientation to component location
accordingly.
CARE AND MAINTENANCE
For continuing high performance and to minimize possible furnace
failure, it is essential that maintenance be performed annually on
this equipment. Consult your local dealer for proper maintenance
and maintenance contract availability.
2
WASHABLE
FILTER
IN FURNACE
FILTER
RETAINER
WASHABLE
FILTER
FILTER
SUPPORT
FILTER
RETAINER
WASHABLE FILTER OR
DISPOSABLE MEDIA
FILTER IN FILTER CABINET
WASHABLE FILTER OR
DISPOSABLE MEDIA FILTER
IN FILTER CABINET
Fig. 4—Filter Installed for Side Inlet
Fig. 3—Bottom Filter Arrangement
A00233
A00232
To clean or replace filters, proceed as follows:
If filter is installed in filter cabinet adjacent to furnace:
Turn off the gas and electrical supplies to the unit before
performing any maintenance or service. Follow the operating
instructions on the label attached to the furnace. Failure to
follow this warning could result in personal injury or death.
1. Turn off electrical supply to furnace.
2. Remove filter cabinet door.
3. Slide filter out of cabinet.
4. If equipped with permanent, washable filter, clean filter by
spraying cold tap water through filter in opposite direction of
airflow. Rinse filter and let dry. Oiling or coating of the filter
is not recommended.
The minimum maintenance that should be performed on this
equipment is as follows:
1. Check and clean or replace air filter each month as needed.
2. Check blower motor and wheel for cleanliness annually.
5. If equipped with factory specified disposable media filter,
replace only with a factory-authorized filter of the same size.
3. Check electrical connections for tightness and controls for
proper operation each heating season. Service as necessary.
6. Slide filter into cabinet.
4. Check for proper condensate drainage. Clean as necessary.
7. Replace filter cabinet door.
5. Check for blockages in combustion-air and vent pipes annually.
8. Turn on electrical supply to furnace.
If filter is installed in furnace blower compartment:
6. Check burners for cleanliness annually.
1. Turn off electrical supply to furnace.
2. Remove main furnace door and blower access panel.
→
3. Release filter retainer wire. (See Fig. 3 or 4.)
Be careful of sharp metal edges, etc. Use care and wear
protective clothing, safety glasses, and gloves when removing
parts. Failure to follow this caution could result in personal
injury.
4. Slide filter out of furnace.
5. Furnaces are equipped with permanent, washable filter(s).
Clean filter by spraying cold tap water through filter in
opposite direction of airflow.
Step 1—Cleaning and/or Replacing Air Filter
6. Rinse filter and let dry. Oiling or coating filter is not
recommended.
The air filter arrangement may vary depending on the application
or orientation. Filter could be located in furnace blower compartment or in the filter cabinet, but not in both.
7. Slide filter into furnace.
8. Recapture filter retainer wire.
9. Replace blower access panel and main furnace door.
Never operate unit without a filter or with the blower access
panel removed. Failure to follow this warning could result in
a fire or personal injury.
10. Turn on electrical supply to furnace.
Step 2—Blower Motor and Wheel Maintenance
To ensure long life, economy, and high efficiency, clean accumulated dirt and grease from blower wheel and motor annually.
The inducer and blower motors are pre-lubricated and require no
additional lubrication. These motors can be identified by the
absence of oil ports on each end of the motor.
Operating a unit without a filter or with the blower access
door removed could cause damage to the furnace blower
motor. Dust and lint on internal parts of furnace can cause a
loss of efficiency.
The following items should be performed by a qualified service
technician.
NOTE: If the filter has an airflow direction arrow, the arrow must
point toward the blower.
3
(1.) Connect 1 tube (blue or blue and white striped) from
collector box.
Clean blower motor and wheel as follows:
1. Turn off electrical supply to furnace.
(2.) Connect 1 tube (violet or unmarked) from inducer
housing.
2. Remove main furnace door and blower access panel.
3. Disconnect blower motor wires from furnace control.
Field thermostat connections may need to be disconnected
depending on their length and routing.
(3.) Connect 1 tube (relief port, green or pink) from
collector box.
c. Connect field drain to condensate trap.
4. Remove control box mounting screws and position control
box, transformer, and door switch assembly to right side of
furnace casing.
13. Reconnect wires.
Refer to furnace wiring diagram, and connect thermostat leads
if previously disconnected. (See Fig. 15.)
5. If condensate trap is located in left- or right-hand side of
furnace casing, proceed to item 6, otherwise remove trap and
tubing as described below (See Fig. 8, top left):
NOTE: Refer to Table 1 for motor speed lead reconnection if
leads were not identified before disconnection.
a. Disconnect field drain connection from condensate trap.
b. Disconnect drain and relief port tubes from condensate
trap.
Heating speed selection MUST be adjusted to provide proper
temperature rise as specified on the rating plate. Failure to
adjust the heating speed may shorten heat exchanger life.
c. Remove condensate trap from blower shelf.
6. Remove screws securing blower assembly to blower shelf and
slide blower assembly out of furnace.
7. Clean blower wheel and motor by using a vacuum with soft
brush attachment. Be careful not to disturb balance weights
(clips) on blower wheel vanes. Do not bend wheel or blades as
balance will be affected.
Table 1—Speed Selection
8. If greasy residue is present on blower wheel, remove wheel
from the blower housing and wash it with an appropriate
degreaser. To remove wheel:
a. Mark blower wheel location on shaft before disassembly to
ensure proper reassembly.
COLOR
SPEED
Black
Yellow (When Present)
Blue
Red
White
High
Medium High
Medium Low
Low
Common
FACTORY
ATTACHED TO
Cool
Spare
Heat
Fan
Com
b. Loosen setscrew holding blower wheel on motor shaft.
NOTE: Mark blower mounting arms and blower housing so each
arm is positioned at the same hole location during reassembly.
Blower access door switch opens 115-v power to furnace
control. No component operation can occur. Caution must be
taken when manually closing this switch for service purposes.
Failure to follow this warning could result in personal injury
or death.
c. Mark blower wheel orientation and cutoff plate location to
ensure proper reassembly.
d. Remove screws securing cutoff plate and remove cutoff
plate from housing.
e. Remove bolts holding motor mounts to blower housing and
slide motor and mounts out of housing. Disconnect capcitor
and ground wire attached to blower housing before removing motor. Motor mounts need not be removed from motor.
14. Turn on electrical supply. Manually close blower access door
switch. Use a piece of tape to hold switch closed. Check for
proper rotation and speed changes by performing a component
self-test as shown at the bottom of Service Label. (See Fig.
16.)
f. Remove blower wheel from housing.
15. If furnace is operating properly remove tape to release blower
access door switch, replace blower access door, and replace
main furnace door.
The blower wheel should not be dropped or bent as balance
will be affected.
Step 3—Cleaning Burners
The following items should be performed by a qualified service
technician. If the burners develop an accumulation of light dirt or
dust, they may be cleaned by using the following procedure:
g. Clean wheel per instructions on degreaser cleaner. Do not
get degreaser in the motor.
9. Reassemble motor and blower wheel by reversing items 8b
through 8f. Ensure wheel is positioned for proper rotation.
Tighten set-screw to 140-160 in.-lb torque.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
10. Reinstall blower assembly in furnace.
3. Remove burner box cover.
11. Reinstall control box, transformer, and door switch assembly
on blower shelf.
4. Using backup wrench, disconnect gas supply pipe from gas
valve.
12. Reinstall condensate trap and tubing if previously removed.
a. Reinstall condensate trap in hole in blower shelf.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous
operation.
b. Connect condensate trap drain tubes. See Fig. 8 or tubing
diagram on main furnace door for proper tube location.
NOTE: Ensure tubes are not kinked or pinched, as this will affect
operation.
5. Remove wires from gas valve. Note location for reassembly.
4
6. Remove burner box pressure tube from gas valve regulator
fitting.
7. Remove screws that secure manifold to burner box. (See Fig.
5.)
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in
serious injury, death, or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the
detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury, or
loss of life.
CELL
PANEL
MANIFOLD
MOUNTING
SCREW
18. Check for gas leaks.
19. Replace main furnace door.
Step 4—Cleaning Heat Exchangers
The following items should be performed by a qualified service
technician.
PRIMARY HEAT EXCHANGERS
If the heat exchangers get an accumulation of light dirt or dust on
the inside, they may be cleaned by the following procedure:
MANIFOLD
NOTE: If the heat exchangers get a heavy accumulation of soot
and carbon, both the primary and secondary heat exchangers
should be replaced rather than trying to clean them thoroughly due
to their intricate design. A build-up of soot and carbon indicates
that a problem exists which needs to be corrected, such as
improper adjustment of manifold pressure, insufficient or poor
quality combustion air, improper vent termination, incorrect size
or damaged manifold orifice(s), improper gas, or a restricted heat
exchanger (primary or secondary). Action must be taken to correct
the problem.
GAS VALVE
REGULATOR
FITTING
GAS VALVE
A96304
Fig. 5—Burner Box Assembly
NOTE: Do not remove burner box from cell panel.
8. Remove manifold, orifices, and gas valve as 1 assembly.
9. Remove screws attaching burner assembly in burner box.
10. Remove burner assembly from burner box.
NOTE: All burners are attached to burner bracket and can be
removed as 1 assembly.
11. Clean burners with soft brush and vacuum.
12. Reinstall manifold, orifice, and gas valve assembly in burner
box. Ensure manifold seal grommet is installed properly and
burners fit over orifices.
13. Reconnect wires to gas valve. Refer to furnace wiring diagram
for proper wire location.
14. Reinstall burner box pressure tube to gas valve regulator
fitting.
15. Reinstall gas supply pipe to furnace gas control valve using
backup wrench on gas valve to prevent rotation and improper
orientation.
NOTE: Use propane gas resistant pipe dope to prevent gas leaks.
DO NOT use Teflon tape.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous
operation.
3. Disconnect wires or connectors to flame rollout switch, gas
valve, igniter, and flame sensor.
4. Disconnect combustion-air intake pipe from intake housing.
5. Remove the pressure switch tube from intake housing.
6. Remove screws attaching intake housing to burner box, and
rotate intake housing away from burner box for removal.
7. Using backup wrench, disconnect gas supply pipe from gas
valve.
8. Disconnect pressure tubing from gas valve.
Gas valve switch MUST be facing forward or tilted upward.
Failure to follow this warning could result in property
damage, personal injury, or death.
9. Remove 2 screws attaching top filler panel and rotate upwards
to gain access to screws attaching burner box to cell panel.
10. Remove screws attaching burner box to cell panel. (See Fig.
5.)
16. Replace burner box cover.
17. Turn on gas and electrical supplies to furnace.
NOTE: Burner box cover, manifold, gas valve, and burner
assembly should be removed as 1 assembly.
11. Clean heat exchanger openings with a vacuum and a soft
brush. (See Fig. 6.)
NOTE: After cleaning, inspect the heat exchangers to ensure they
are free of all foreign objects that may restrict flow of combustion
products.
12. Reverse items 4 through 10 for reassembly.
5
16. Check furnace operation through 2 complete heat operating
cycles. Look through sight glass in burner enclosure to check
burners. Burner flames should be clear blue, almost transparent. (See Fig. 9.)
PRIMARY HX
INLET OPENINGS
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in
serious injury, death, or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the
detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury, or
loss of life.
17. Check for gas leaks.
18. Replace main furnace door.
SECONDARY HEAT EXCHANGERS
A96305
NOTE: The condensing side (inside) of the secondary heat
exchangers CANNOT be serviced or inspected. A small number of
bottom outlet openings can be inspected by removing the inducer
assembly. See Flushing Collector Box and Drainage System
section for details on removing inducer assembly.
Fig. 6—Cleaning Inlet Openings of Primary Heat
Exchangers
Step 5—Flushing Collector Box and Drainage System
The ground wire from the gas valve MUST be attached to the
burner box attachment screw. Failure to attach this ground
wire to an adequate casing ground will cause the furnace
control to lock out.
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect inducer motor and pressure switch wires or
connectors.
NOTE: Be sure burner box gasket is installed between burner box
and cell panel. (See Fig. 5.) If gasket is damaged, replace it.
4. Disconnect pressure switch tubes.
5. Disconnect vent pipe from inducer housing outlet by loosening coupling clamp on inducer outlet.
NOTE: Inspect combustion-air intake housing. If foamed gasket
was removed, check for any damage. If gasket is damaged in any
way, it must be repaired. To repair, remove damaged gasket
section, apply sealant releasing agent such as PAM cooking spray
or equivalent (must not contain corn or canola oil, aromatic or
halogenated hydrocarbons or inadequate seal may occur) to burner
box and apply a small bead of G.E. RTV 162, G.E. RTV 6702, or
Dow-Corning RTV 738 sealant to edge of combustion-air intake
housing. (See Fig. 7.)
6. Disconnect drain tube from inducer housing. (See Fig. 8.)
7. Remove inducer housing assembly by removing 4 bolts
attaching assembly to cell panel.
8. Flush inside of collector box with water until discharge from
condensate trap is clean and runs freely.
NOTE: Ensure the drain tube disconnected from the inducer
housing is higher than the collector box opening or water will flow
out tube.
9. Inspect inside area of collector box for any pieces of foreign
materials and remove if present.
RTV
DO NOT use wire brush or other sharp object to inspect or
dislodge materials in secondary heat exchangers as failure of
the secondary heat exchanger will occur. Flush with water
only.
PAM
10. Reassemble inducer assembly by reversing items 5 through 7.
Tighten the vent coupling clamp screw(s) to 15 in.-lb of
torque.
A93087
Fig. 7—Combustion-Air Intake Housing Gasket
Repair
NOTE: If seal between the inducer housing and the collector box
is damaged in any way, it must be repaired. To repair, apply
sealant releasing agent such as PAM cooking spray or equivalent
(must not contain corn or canola oil, aromatic or halogenated
hydrocarbons which can cause an inadequate seal to occur) to
inducer housing. (See Fig. 10.) Apply a small bead of G.E. RTV
162, G.E. RTV 6702, or Dow-Corning RTV 738 sealant to groove
in collector box.
13. Refer to furnace wiring diagram and reconnect wires to flame
rollout switch, gas valve, igniter, and flame sensor.
14. Reconnect pressure switch tubes to gas valve and intake
housing. Refer to tube routing label on main furnace door for
proper tube location. Be sure tubes are not kinked. (See Fig.
8.)
11. Refer to furnace wiring diagram and reconnect wires to
inducer motor and pressure switches or connectors.
15. Turn on gas and electrical supplies to furnace.
6
TUBE ROUTING
Furnace is shipped from factory in upflow configuration. Pressure tube and drain tube routing MUST match the diagrams below.
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
(Blower access panel removed)
CAP
CAP
COLLECTOR BOX TUBE
(PINK)
PLUG
COLLECTOR BOX TUBE
(GREEN)
COLLECTOR BOX TUBE (GREEN)
CONDENSATE TRAP
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE COUPLING
(RIGHT DRAIN OPTION)
CONDENSATE TRAP
INDUCER HOUSING DRAIN TUBE
(VIOLET)
FIELD-INSTALLED
FACTORY-SUPPLIED 1/2-IN.
CPVC STREET ELBOWS (2)
FOR LEFT DRAIN OPTION
FIELD-INSTALLED FACTORY-SUPPLIED
DRAIN TUBE
Condensate Trap on
RIGHT Side
Tube location when used in DOWNFLOW application
PLUG
COLLECTOR BOX
DRAIN TUBE (BLUE)
PLUGGED END
CAP
CAP
COLLECTOR BOX TUBE
(PINK)
PLUG
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
COLLECTOR BOX TUBE
(GREEN)
INDUCER HOUSING DRAIN
TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX EXTENSION TUBE
BURNER ENCLOSURE PRESSURE
REFERENCE TUBE ASSEMBLY
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE TRAP
DRAIN TUBE COUPLING
COLLECTOR BOX
TUBE (PINK)
BURNER ENCLOSURE PRESSURE
REFERENCE TUBE ASSEMBLY
DRAIN TUBES ROUTED IN
FRONT OF GAS VALVE
INDUCER HOUSING DRAIN TUBE (VIOLET)
Tube location when used on
HORIZONTAL - LEFT application
COLLECTOR BOX DRAIN TUBE
(BLUE)
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
CAP
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
COLLECTOR BOX
EXTENSION TUBE
DRAIN TUBE
COUPLING
COLLECTOR BOX
EXTENSION DRAIN TUBE
COLLECTOR BOX EXTENSION TUBE
COLLECTOR BOX TUBE (PINK)
AUXILIARY "J" BOX RELOCATED HERE
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE)
CONDENSATE TRAP
GAS VALVE
PLUG
COLLECTOR BOX
TUBE (GREEN)
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
CONDENSATE TRAP
Tube location when used on
HORIZONTAL - RIGHT application
PLUG
COLLECTOR BOX EXTENSION DRAIN TUBE
COLLECTOR BOX DRAIN TUBE
(BLUE)
COLLECTOR BOX DRAIN
TUBE
(BLUE & WHITE STRIPED)
COLLECTOR BOX
TUBE (GREEN)
NOTE:
COLLECTOR BOX DRAIN TUBE
(BLUE & WHITE STRIPED)
COLLECTOR BOX DRAIN TUBE
(BLUE)
COLLECTOR BOX DRAIN TUBE
(BLUE)
FIELD-INSTALLED
FACTORY-SUPPLIED DRAIN TUBE
COUPLING (LEFT DRAIN OPTION)
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
PLUG
COLLECTOR BOX TUBE
(PINK)
COLLECTOR BOX DRAIN
TUBE
(BLUE & WHITE STRIPED)
INDUCER HOUSING (MOLDED) DRAIN TUBE
(BEHIND COLLECTOR BOX DRAIN TUBE)
Condensate Trap on
LEFT Side
Condensate Trap on LEFT
Side Optional
Tube location when used in UPFLOW application
Condensate Trap; Factory Installed
in Blower Shelf
BURNER ENCLOSURE
PRESSURE REFERENCE
TUBE ASSEMBLY
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX TUBE (PINK)
RELOCATE TUBE BETWEEN BLOWER
SHELF AND INDUCER HOUSING FOR
040,060, AND 080 HEATING INPUT
FURNACES
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
CONDENSATE TRAP
INDUCER HOUSING DRAIN TUBE (VIOLET)
1. All tubing must be connected securely and routed to avoid kinks and traps.
2. Pressure tubing must always slope away from pressure switch to collector box connection as shown.
3. HORIZONTAL-LEFT installations require the collector box pressure tube to be relocated between the inducer housing and the blower shelf to
prevent a trap. Refer to the Installation Instructions for further details.
324999-201 REV. C
A00308
Fig. 8—Furnace Pressure and Drain Tubing Diagram
12. Reconnect pressure tubes to pressure switch. See diagram on
main furnace door for proper location of tubes. Be sure tubes
are not kinked. (See Fig. 8.)
13. Turn on gas and electrical supplies to furnace.
14. Check furnace operation through 2 complete heat operating
cycles. Check area below inducer housing, vent pipe, and
condensate trap to ensure no condensate leaks occur. If leaks
are found, correct the problem.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result in
serious injury, death, or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the
detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury, or
loss of life.
15. Check for gas leaks.
16. Replace main furnace door.
Step 6—Servicing Hot Surface Igniter
The igniter does NOT require annual inspection. Check igniter
resistance before removal.
7
1. Turn off gas and electrical supplies to furnace.
2. Remove main furnace door.
3. Disconnect igniter wire connection.
4. Check igniter resistance.
a. Using an ohm meter, check resistance across both igniter
leads in connector.
PAM
RTV
b. Cold reading should be between 45 ohms and 90 ohms.
c. If ohm reading is higher than 110 ohms, igniter is cracked
and must be replaced.
5. Remove igniter assembly.
Allow igniter to cool before removal. Normal operating
temperatures exceed 2000°F.
a. Do not remove igniter from bracket while assembly is in
furnace. Using a 1/4 in. nutdriver, remove screw securing
bracket and igniter assembly to bottom of burner box. The
screw in the bracket is always located toward outside of
burner box. The screw may be hidden by inlet box or inlet
pipe, but can be removed without removing either. After
removing screw, slide igniter and bracket toward outside of
burner box and pull straight out.
A93081
Fig. 10—Gasket on Collector Box
9. Verify igniter operation by initiating furnace control board
self-test feature or by cycling thermostat.
10. Replace main furnace door.
Step 7—Electrical Controls and Wiring
The igniter is fragile. DO NOT allow it to hit the side of the
burner box opening while removing or replacing it.
b. Inspect igniter for a white area indicating a crack may be
present. If found, replace igniter.
There may be more than 1 electrical supply to the unit. Check
accessories and cooling unit for additional electrical supplies.
NOTE: A small crack cannot be seen on a new igniter. After a
period of operation, a white area will be visible around the crack.
The electrical ground and polarity for 115-v wiring must be
maintained properly. Refer to Fig. 11 for field wiring information
and to Fig. 15 for unit wiring information.
NOTE: If the polarity is not correct, the STATUS LED on the
furnace control will flash rapidly and prevent the furnace from
operating. The control system also requires an earth ground for
proper operation of the furnace control and flame sensor.
The 24-v circuit contains an automotive-type, 3-amp fuse located
on the control center. (See Fig. 12.) Any direct shorts of the 24-v
wiring during installation, service, or maintenance will cause this
fuse to blow. If fuse replacement is required, use ONLY a fuse of
identical size (3-amp). The control LED will flash status code 24
when fuse needs to be replaced.
With power to the unit disconnected, check all electrical connections for tightness. Tighten all screws on electrical connections. If
any smoky or burned connections are found, disassemble the
connection, clean all parts, strip wire, and reassemble properly and
securely.
Reconnect electrical supply to unit and observe unit through 1
complete operating cycle for proper operation.
c. If replacement is required, replace igniter on igniter bracket
external to furnace to avoid damage as the silicon portion is
very brittle and will easily crack or shatter.
d. To remove igniter from igniter bracket, remove screw
holding igniter ceramic block to bracket and pull ceramic
block out of bracket.
6. To replace igniter/igniter assembly, reverse items 5a through
5d.
;;
;;
7. Reconnect igniter wire connection.
8. Turn on gas and electrical supplies to furnace.
BURNER FLAME
BURNER
MANIFOLD
A89020
Fig. 9—Burner Flame
8
FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING
NOTE 2
W
FIVE WIRE
THREE-WIRE
HEATING-ONLY
C
R
G
Y
THERMOSTAT
TERMINALS
FIELD-SUPPLIED
DISCONNECT
208/230- OR
460-V
THREE
PHASE
BLOWER DOOR SWITCH
BLK
BLK
WHT
WHT
W
GND
C
O
N
T
R
O
L
GND
115-V FIELDSUPPLIED
DISCONNECT
AUXILIARY
J-BOX
R
208/230-V
SINGLE
PHASE
G
COM
GND
NOTE 1
CONDENSING
UNIT
Y/Y2
TWO
WIRE
24-V
TERMINAL
BLOCK
FURNACE
NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
A99440
Fig. 11—Field Wiring
TWINNING AND/OR
COMPONENT TEST
TERMINAL
BLOWER OFF-DELAY
BLOWER OFF-DELAY
DHUM
120 180
90 150
Y1
HUMIDIFIER TERMINAL
(24-VAC 0.5 AMP MAX.)
G
TEST/TWIN
TRANSFORMER 24-VAC
CONNECTIONS
PLT
COM W/W1 Y/Y2
24V
24-V THERMOSTAT
TERMINALS
R
HUM
0.5 AMP@24VAC
NUETRAL BLW
STATUS CODE LED
3-AMP FUSE
FUSE 3-AMP
EAC-2
L2
PL1-LOW VOLTAGE MAIN
HARNESS CONNECTOR
1
115-VAC(L2)NEUTRAL
CONNECTIONS
SEC-2 SEC-1
PLT
LED OPERATION &
DIAGNOSTIC LIGHT
COOL
FAN
SPARE-1 SPARE-2
SPARE-1
BLOWER SPEED
SELECTION TERMINALS
SPARE-2
1-AMP@
EAC-1 115VAC
FAN
L1
HEAT
COOL
HEAT
PR-1
PL2
1
115 VAC (L1) LINE
VOLTAGE CONNECTION
PL2-HOT SURFACE
IGNITER & INDUCER
MOTOR CONNECTOR
EAC-1 TERMINAL
(115-VAC 1.0 AMP MAX.)
A02142
Fig. 12—Control Center
9
32°F MINIMUM INSTALLED
AMBIENT OR FREEZE
PROTECTION REQUIRED
A93058
Fig. 13—Winterizing the Furnace
Step 8—Checking Heat Tape Operation (If Applicable)
If this furnace is to be operated in an unconditioned space
where the ambient temperatures may be 32°F or lower, freeze
protection measures must be taken. (See Fig. 13.) See
CONDENSATE DRAIN PROTECTION section of Installation, Start-Up, and Operating Instructions.
In applications where the ambient temperature around the furnace
is 32°F or lower, freeze protection measures are required. If heat
tape has been applied, check to ensure it will operate when low
temperatures are present.
NOTE: Heat tape, when used, should be wrapped around the
condensate drain trap and drain line. There is no need to use heat
tape within the furnace casing. Most heat tapes are temperature
activated, and it is not practical to verify the actual heating of the
tape. Check the following:
A99119
Fig. 15—Funnel in Drain and Antifreeze Running
Through Trap
1. Check for signs of physical damage to heat tape such as nicks,
cuts, abrasions, gnawing by animals, etc.
2. Check for discolored heat tape insulation. If any damage or
discolored insulation is evident, replace heat tape.
3. Check that heat tape power supply circuit is on.
Step 9—Winterizing
Freezing condensate left in the furnace will damage the
equipment.
If the furnace will be off for an extended period of time in a
structure where the temperature will drop to 32°F or below,
winterize as follows:
1. Turn off electrical supply to furnace.
2. Remove main furnace door.
3. Disconnect cap from unused drain tap on inducer housing.
(See Fig. 13.)
4. Connect field-supplied 1/2-in. I.D. tube to upper inducer
housing drain connection.
Do not use ethylene glycol (Prestone II antifreeze/coolant or
equivalent automotive type). Failure of plastic components
will occur.
Fig. 14—Inducer Housing Drain Cap
5. Insert funnel in tube and pour up to 1 quart antifreeze,
propylene glycol (RV, swimming pool antifreeze, or equivalent) into funnel until it is visible at point where condensate
enters open drain. (See Fig. 14.)
A99118
10
6. Reconnect drain cap to inducer housing.
→ Record the code. After the last code is displayed the control will
perform the component test, and then return to normal standby
mode.
7. Replace main furnace door.
8. Propylene glycol need not be removed before restarting
furnace.
COMPONENT TEST
WIRING DIAGRAM
See Fig. 16 for Wiring Diagram.
TROUBLESHOOTING
Use the Troubleshooting Guide, the status code LED on the
cotntrol and the Component Test to isolate furnace operation
problems.
Blower access panel door switch opens 115-v power to
control board. No component operation can occur. Caution
must be taken when manually closing this switch for service
purposes. Failure to follow this warning could result in
electrical shock, personal injury, or death.
STATUS CODES
For an explanation of status codes, refer to service label located on
back of main furnace door or Fig. 17 and the Troubleshooting
Guide. The stored status code will NOT be erased from the control
memory if 115- or 24-v power is interrupted.
Use the Component Test to check furnace components for proper
operation. To initiate the component self-test sequence, shut off
the room thermostat or disconnect the ″R″ thermostat lead. Briefly
(approximately 2 sec) short the TWIN/TEST terminal to the COM
24V terminal. The status LED will turn off. The test sequence will
be as follows:
NOTE: Removing the blower access door will open the blower
access door switch and terminate 115-v power to the control.
To read current status code, remove main furnace door. The status
code LED can be viewed through the sight glass on the blower
access door.
1. LED flashes last status code, or code 11, 4 times. Record this
status code for further troubleshooting.
2. The inducer will start and continue to run until test is over.
NOTE: NO thermostat signals may be present at control and all
blower off delays must be completed to view previous codes.
→
3. Hot surface igniter (HSI) is energized for 15 sec, then
de-energized.
4. Blower operates on continuous FAN speed for 10 sec, then
turns off.
Make sure limit switch or flame rollout switch wire does not
contact any metal component, such as gas valve. If wire is
shorted, 3-amp fuse on furnace control will blow.
5. The blower motor operates on HEATING speed for 10 sec,
then turns off.
6. The blower motor operates on COOLING speed for 10 sec,
then turns off.
To retrieve previous codes, remove 1 of the red main limit or flame
rollout switch wires for 1 to 4 sec until the LED light goes out, then
reconnect it. (Do not leave red wire disconnected for longer
periods of time as the control will assume an overtemperature
condition exists and will respond with blower operation.) This
places the control in the status recall mode and displays the last
code stored in memory.
7. Inducer turns off.
8. The gas valve and humidifier terminal HUM are not energized
for safety reasons.
11
BLOWER OFF DELAY
JUMPER SELECT
PRINTED CIRCIUT BOARD
Y1
TO 115VAC FIELD DISCONNECT
NOTE #2
(WHEN USED)
LGPS
PRS
PCB
L2
L1
LO
MED LO
MED HI
HI
SPARE-1
NOTE #10
OL
HI/LO
COOL
ILK
120
150
Y/Y2
TEST/TWIN
HEAT
YEL
180
BLU
RED
LS
FRS
C
GRN/YEL
NOTE #3
HUM
RED
FU1
NOTE #6
FAN
BLWR
GV
M
RED
ORN
R
L1
BLU
J1
EAC-1
HSIR
1 2 3 4 5 6 7 8 9 10 11
RED
RED
WHT
RED
GRN/YEL
PL2
BHT/CLR
COOL
BFANR
BLWR
2
SPARE 2
EAC-1
NOTE #10
IDM
PL3
2
1
CAP -1
JB
START
WHT
BLK
BLK
BRN
FRS
6
LS
8
NEUTRAL
FU2
2
W
PL1
LGPS
(WHEN USED)
NOTE #11
PRS
4
GVR-1
Y/Y2
L1
RED (LO)
BLU
(MED LO)
SEC-2
R
FUSED OR CIRCUIT BREAKER
DISCONNECT SWITCH (WHEN REQ’D)
NOTE #2
WHT
CAP - 2
2
HUM
WHT
BRN
3
GVR-2
BLK
GRN/YEL
1
PL4
SEC-1
WHT
PRINTED CIRCIUT BOARD
WHT (COM)
AUX
F U 1 NOTE #6
BLK
BLK
BLWM
OL
AUX
PR1
BLK (HI)
YEL
(MED HI)
M
WHT
BLK
BLK
SPARE 1
WHT
(COM)
2
L1
M
TEST/TWIN
BRN
OL
FAN
HEAT
WHT
GRN/YEL
1
IDM
OL
115VAC
24VAC
BRN
3
1
HSI
2
TRAN
CAP -2
PL4
FSE
PL3
L2
EAC-2
BLWM
WHT
WHT
GRN/YEL
YEL
WHT
PL1
PR1
HSI
NOTE #8
BLW
NEUTRAL
L2
2
PL2
BLK
TRAN
LED 1
BLU
1
1
IDR
WHT
START
COM
GRN/YEL
SEC-1
CAP-1
FAN
NOTE #11
G
Com
24V
W
EAC-2
EQUIPMENT GROUND
ORN
90
DHUM
SEC-2
SCHEMATIC DIAGRAM
(NATURAL GAS & PROPANE)
GND
10
M
GV
CPU
ILK
GND
DHUM
C
5
NOTE #3
Y1
L
E
G
E
N
D
BFANR
BHT/CLR
BLWR
BLWM
CAP 1, 2
CPU
EAC-1
EAC-2
FRS
FSE
FU 1
FU 2
GND
GV
GVR 1, 2
HSI
HSIR
HUM
IDM
IDR
ILK
J1
JB
LED
LGPS
LS
CONTINUOUS-FAN SELECT RELAY, SPDT
BLOWER MOTOR SPEED CHANGE RELAY, SPDT
BLOWER MOTOR RELAY, SPST-(N.O.)
BLOWER MOTOR, PERMANENT-SPLIT-CAPACITOR
CAPACITOR
MICROPROCESSOR AND CIRCUITRY
ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.0 AMP MAX.)
ELECTRONIC AIR CLEANER CONNECTION (COMMON)
FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.)
FLAME-PROVING ELECTRODE
FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED
FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE
(FIELD INSTALLED & SUPPLIED)
EQUIPMENT GROUND
GAS VALVE-REDUNDANT
GAS VALVE RELAY, DPST-(N.O.)
HOT SURFACE IGNITER (115 VAC)
HOT SURFACE IGNITER RELAY, SPST-(N.O.)
24VAC HUMIDIFIER CONNECTION (0.5 AMP. MAX.)
INDUCED DRAFT MOTOR, PSC
INDUCED DRAFT MOTOR RELAY, SPST-(N.O.)
BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.)
BLOWER - OFF DELAY JUMPER SELECTOR
JUNCTION BOX
LIGHT-EMITTING DIODE FOR STATUS CODES - AMBER
LOW GAS PRESSURE SWITCH, SPST-(N.O.)
LIMIT SWITCH, AUTO-RESET, SPST (N.C.)
OL
PCB
PL1
PL2
PL3
PL4
PRS
TEST/TWIN
TRAN
AUTO-RESET INTERNAL MOTOR OVERLOAD
TEMPERATURE SWITCH (N.C.)
PRINTED CIRCUIT BOARD CONTROL
11-CIRCUIT PCB CONNECTOR
2-CIRCUIT CONNECTOR
2-CIRCUIT HSI, CONNECTOR
3-CIRCUIT IDM EXTENSION CONNECTOR
PRESSURE SWITCH, SPST-(N.O.)
COMPONENT TEST & TWIN TERMINAL
TRANSFORMER-115VAC/24VAC
JUNCTION
UNMARKED TERMINAL
PCB CONTROL TERMINAL
FACTORY WIRING (115VAC)
FACTORY WIRING (24VAC)
FIELD WIRING (115VAC)
1
G
COM
NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
FIELD WIRING (24VAC)
CONDUCTOR ON CONTROL PCB
FIELD WIRING SCREW TERMINAL
10.
11.
12.
FIELD EARTH GROUND
EQUIPMENT GROUND
FIELD SPLICE
13.
14.
9
FSE
7
PCB
NOTE #5
3
11
If any of the original equipment wire is replaced use wire rated for 105°C.
Use only copper wire between the disconnect switch and the furnace junction box (JB).
This wire must be connected to furnace sheet metal for control to prove flame.
Symbols are electrical representation only.
Solid lines inside PCB are printed circuit board conductors and are not included in legend.
Replace only with a 3 amp fuse.
Inducer (IDM) and blower (BLWM) motors contain internal auto-reset thermal overload switches (OL).
Neutral connections are interchangeable within the NEUTRAL connector block.
Blower motor speed selections are for average conditions, see installation instructions for details on
optimum speed selection.
YELLOW lead not on all motors.
Factory connected when LGPS is not used.
Ignition-lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will
auto-reset after three hours.
Blower-on delay: gas heating 60 seconds, cooling or heat pump 2 seconds.
Blower-off delay: gas heating selections are 90, 120, 150 or 180 seconds, cooling or heat pump
90 seconds or 5 seconds when dehumidify call is active.
326796-101 REV. A
PLUG RECEPTACLE
Fig. 16—Wiring Diagram
A02157
12
SERVICE
If status code recall is needed, briefly remove then reconnect one main limit wire to display
stored status code. On RED LED boards do not remove power or blower door before initiating status code recall. After one status code recall is completed component test will occur.
LED CODE
STATUS
CONTINUOUS OFF - Check for 115VAC at L1 & L2, & 24VAC at SEC-1 & SEC-2.
CONTINUOUS ON - Control has 24VAC power.
RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned,
refer to twinning kit instructions.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST
DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY
THE NUMBER OF LONG FLASHES.
11 NO PREVIOUS CODE - Stored status code is erased automatically after 72
hours. On RED LED boards stored status codes can also be erased when power
(115 VAC or 24 VAC) to control is interrupted.
12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for 90
seconds, if unit is powered up during a call for heat (R-W closed) or R-W opens
during blower on-delay.
13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if the limit or flame rollout switch is
open longer than 3 minutes.
- Control will auto reset after three hours.
- Refer to #33.
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.
21 GAS HEATING LOCKOUT - Control will NOT auto reset.
Check for: - Mis-wired gas valve
-Defective control (valve relay)
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is
de-energized. Inducer will run until fault is cleared. Check for:
- Leaky gas valve
- Stuck-open gas valve
23 PRESSURE SWITCH DID NOT OPEN Check for:
- Obstructed pressure tubing.
- Pressure switch stuck closed.
24 SECONDARY VOLTAGE FUSE IS OPEN Check for:
- Short circuit in secondary voltage (24VAC) wiring.
31 PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than
five minutes, inducer shuts off for 15 minutes before retry. Check for:
- Excessive wind - Proper vent sizing
- Defective inducer motor
- Low inducer voltage (115VAC)
- Defective pressure switch
- Inadequate combustion air supply
- Restricted vent
- Disconnected or obstructed pressure tubing
- Low inlet gas pressure (if LGPS used)
If it opens during blower on-delay period, blower will come on for the selected
blower off-delay.
33 LIMIT CIRCUIT FAULT - Indicates a limit, or flame rollout is open. Blower will
run for 4 minutes or until open switch remakes whichever is longer. If open
longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes
status code #33 continues to flash until blower shuts off. Flame rollout switch
requires manual reset. Check for: - Restricted vent
- Proper vent sizing
- Loose blower wheel
- Excessive wind
- Dirty filter or restricted duct system.
- Defective blower motor or capacitor. - Defective switch or connections.
- Inadequate combustion air supply (Flame Roll-out Switch open).
34 IGNITION PROVING FAILURE - Control will try three more times before lockout
#14 occurs. If flame signal lost during blower on-delay period, blower will come
on for the selected blower off-delay. Check for: - Control ground continuity
- Flame sensor must not be grounded
- Oxide buildup on flame sensor (clean with fine steel wool).
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal).
- Gas valve defective or gas valve turned off
- Manual valve shut-off
- Defective Hot Surface Ignitor
- Low inlet gas pressure
- Inadequate flame carryover or rough ignition
- Green/Yellow wire MUST be connected to furnace sheet metal
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;
- Gas valve relay stuck open
- Flame sense circuit failure
- Software check error
Reset power to clear lockout. Replace control if status code repeats.
COMPONENT TEST
To initiate the component test sequence, shut OFF the room thermostat or disconnect
the "R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal. Status LED will flash code and then turn ON the inducer motor. The inducer
motor will run for the entire component test. The hot surface ignitor, blower motor
FAN speed (AMBER LED boards only) blower motor HEAT speed, and blower motor
COOL speed will be turned ON for 10-15 seconds each. Gas Valve and Humidifier
will not be turned on.
327884-101 REV. B
A02270
→ Fig. 17—Service Label
13
14
YES
Go to section below for the status code that
was flashed.
Determine status code. The status code is a
2 digit number with the first digit determined
by the number of short flashes and the second
digit by the number of long flashes?
YES
Is LED status light blinking ON/OFF slowly
with a combination of short and long flashes?
NO
Is LED status light blinking rapidly without a
pause?
Is LED status light on?
START
YES
NO
YES
NO
NO
YES
Replace furnace control.
Run system through a heating or cooling cycle
to check operation. Status codes are erased
after 72 hours. On RED LED boards stored
status codes can also be erased whenever
(115V or 24V) is interrupted.
YES
Does the control respond to W, Y1 (if present),
Y/Y2, and G (24V) thermostat signals?
To recall status code briefly remove and reconnect one RED wire from the Limit
Switch or Flame Rollout switch to display stored status code. On RED LED
control do not remove power or blower access panel before initiating status
code recall. You can also recall the previous status code by momentarily shorting
the TEST/TWIN terminal to Com24V terminal until the LED goes out. LED will
flash the previous status code or status code #11 (1 short and 1 long flash) if
there was no previous code. After the control repeats the code 4 times, the
control will go through a brief component test sequence. The inducer will start
and run for the entire component test. The HSI, blower motor FAN speed
(AMBER LED boards only) HEAT speed, and COOL speed will run for 10 – 15
seconds each. Gas valve and humidifier will not be turned on.
Replace transformer.
Check for correct line voltage polarity. If units
are twinned, check for proper low-voltage
(24V) transformer phasing.
Was there a previous status code
other than #11?
YES
Is there 115V going to switch?
Is door switch closed?
Replace door switch.
NO
NO
Replace furnace control.
YES
Is there 24V at SEC-1 and SEC-2?
YES
Is there 115V at L1 and L2?
TROUBLESHOOTING GUIDE
YES
NO
NO
NO
YES
The thermostat is not compatible with the
furnace control. Either install a ballast resistor,
connect the Com24V thermostat terminal to
the thermostat, or replace the thermostat.
NO
Does the problem repeat when using
a jumper wire?
Disconnect all the thermostat wires from the
furnace control.
YES
Is 24V present at W, Y1 (if present), Y/Y2 or
G thermostat terminals on the furnace control?
NO
Check room thermostat or
interconnecting cable.
Close circuit breaker and go back to START.
Check for continuity in wire from circuit breaker
to furnace.
Is circuit breaker closed?
Close door switch and go back to START.
A02204a
NO
15
24 SECONDARY VOLTAGE FUSE IS OPEN
Check for:
- Short circuit in secondary voltage (24V)
wiring including thermostat leads.
Disconnect thermostat leads to isolate
short circuit.
23 PRESSURE SWITCH DID NOT OPEN
Check for:
- Obstructed pressure tube.
- Pressure switch stuck closed.
22 ABNORMAL FLAME-PROVING SIGNAL
Flame is proved while gas valve is deenergized. Inducer will run until fault is
cleared. Check for:
- Stuck open or leaky gas valve.
21 GAS HEATING LOCKOUT – Turn off
power and wait 5 minutes to retry.
Check for:
- Stuck closed gas valve relay on control.
- Miswire or short to gas valve wire.
14 IGNITION LOCKOUT – System failed to
ignite gas and prove flame in 4 attempts.
Control will auto-reset after 3 hours.
See status code 34.
13 LIMIT CIRCUIT LOCKOUT – Lockout
occurs if the limit or flame rollout switch is
open longer than 3 minutes. Control will
auto-reset after 3 hours. See code 33.
12 BLOWER ON AFTER POWER UP –
(115V OR 24V) – Normal operation.
Blower runs for 90 seconds, if unit is
powered up during a call for heat (R-W
closed) or when (R-W opens) during the
blower on-delay period.
11 NO PREVIOUS CODE – Stored codes
are erased after 72 hours. On RED LED
boards stored status codes can also be
erased whenever power (115V or 24V)
is interrupted. Run system through a
heating or cooling cycle to check system.
34 IGNITION PROVING FAILURE – If flame
is not sensed during the trial for ignition
period, the control will repeat the ignition
NO
sequence 3 more times before lockout
#14 occurs. If flame signal is lost during
YES
the blower on-delay period, blower will
come on for the selected blower off-delay.
Check the following items first before
proceeding to the next step.
- Gas valve turned off.
- Manual shut-off valve.
- Green/Yellow wire MUST be connected
to furnace sheet metal.
- Flame sensor must not be grounded.
To determine whether the problem is in
the gas valve, igniter, or flame sensor the
system can be operated in the component
test mode to check the igniter. First
remove the R thermostat connection from
the control and initiate the component
test sequence. Does the igniter glow
orange/white by the end of the 15 second
warm-up period?
33 LIMIT CIRCUIT FAULT – Indicates the
limit or flame rollout switch is open. Blower
will run for 4 minutes or until open switch
remakes whichever is longer. If open
longer than 3 minutes, code changes to
lockout #13. If open less than 3 min.
status code #33 continues to flash until
blower shuts off. Flame rollout switch
requires manual reset. Check for:
- Dirty filter or restricted duct system.
- Loose blower wheel.
- Defective switch or connections.
- Defective blower motor or capacitor.
- Inadequate combustion air supply
(flame rollout switch open).
- Restricted vent.
- Proper vent sizing.
- Excessive wind.
- Blower motor on incorrect speed tap.
- Input rate to furnace set too high.
31 PRESSURE SWITCH DID NOT CLOSE
OR REOPENED – If open longer than 5
minutes, inducer shuts off for 15 minutes
before retry. If opens during blower ondelay period, blower will come on for the
selected blower off-delay. Check for:
- Proper vent sizing.
- Low inducer voltage (115V).
- Low inlet gas pressure (if LGPS used).
- Inadequate combustion air supply.
- Disconnected or obstructed pressure
tubing.
- Defective inducer motor.
- Defective pressure switch.
- Excessive wind.
- Restricted vent.
Fixed.
YES
Will main burners ignite and stay on?
YES
Is current near typical value?
Clean flame sensor with fine steel wool and
recheck current. Nominal current is 4.0 to 6.0
microamps.
YES
Repeat call for heat and check flame sensor
current during trial for ignition period. Is the
DC microamps below 0.5?
NO
Do the main burners stay on?
YES
Do the main burners ignite?
YES
Does gas valve open and allow gas to flow?
YES
Reconnect the R thermostat lead and set
thermostat to call for heat. Connect voltmeter
across gas valve connections. Does gas valve
receive 24V?
Unplug igniter harness from control and initiate
another component test sequence. Check
for 115V between pin 1 and NEUTRAL-L2 on
the control. Was 115V present for the 15
second period?
NO
NO
NO
YES
NO
NO
NO
YES
NO
Replace furnace control.
Replace electrode.
A02204b
Check connections and retry. If current is
near typical value (4.0-6.0 nominal) and
burners will not stay on, replace control.
Allow blower to come on and repeat test to
check for intermittent operation.
Check for:
- Inadequate flame carryover or rough
ignition.
- Low inlet gas pressure.
- Proper firing rate.
- Check for air leakage around igniter bracket.
Check that all gas valves are turned on.
Replace valve.
Check connections. If OK, replace control.
Check for continuity in the harness and igniter.
Replace defective component.
Replace furnace control.
45 CONTROL CIRCUITRY LOCKOUT
Auto-reset after 1 hour lockout due to:
Flame circuit failure.
- Gas valve relay stuck open.
Software check error.
Reset power to clear lockout. Replace
control if code repeats.
Copyright 2002 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231
58mxa9sm
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6a 8a
PC 101
Catalog No. 535-80099
Printed in U.S.A.
Form 58MXA-9SM
Pg 16
11-02
Replaces: 58MXA-8SM