Daikin Airconditioning UK Ltd
p . 0 2
Daikin Europe N.V.
Daikin has a worldwide reputation based on over 70 years’ experience in the successful manufacture of high quality air conditioning equipment for industrial, commercial and residential use.
Environmental Awareness
Air conditioning and the environment
Air conditioning systems bring a significant level of indoor comfort to our working and living conditions regardless of outdoor temperature. With the advent of climate change and increasing global awareness of the need to reduce the burdens on the environment, Daikin has invested heavily in developing increasingly efficient systems. Daikin’s highly successful technological results are incorporated in the latest heating and cooling systems designed specifically, in all aspects, to limit their impact on our environment.
Enhanced Capital Allowances
The Enhanced Capital Allowance scheme (ECA) was introduced to encourage firms to make energy saving investments in efficient technology. Under this scheme, expenditure on technologies and products on the
Energy Technology List (ETL) can qualify for 100% first year tax allowances.
The ETL is dynamic, with new products and technologies being added as and when they are approved.
Daikin now have over 300 products listed under 3 technology categories. Extensive listings of all qualifying products can be found on www.eca.gov.uk/etl.
Investments in heat pumps and packaged chillers can only qualify for ECAs if the unit or system is named on the ETL. Eligible products are required to meet performance criteria for both heating and cooling.
The qualifying criteria for heat pump systems, including VRV, is that the minimum energy efficiency meets COP greater than 3.4 and EER greater than 3.0 (Energy Label B). As you will see in this brochure,
Daikin VRV exceeds these criteria.
Part L of the Building Regulations
As part of the European Community’s aim to reduce Global Warming emissions a directive known as Energy
Performance in Buildings Directive (EPBD) was made effective.
In the UK we amended Part L of our building regulations to comply with this directive, which became law in April 2006. It is split between domestic (L1A / L1B) and non-domestic (L2A / L2B) buildings. It applies to new building design (sections A) and refurbishments (sections B).
Air conditioning is measured by Seasonal Energy Efficiency Ratio (SEER) and Seasonal Coefficient of
Performance (SCoP) for cooling and heating respectively. The default levels in the Government calculating tool (SBEM) is SEER 3.5 and SCoP 2.2 for VRV.
Daikin VRVIII exceeds that with typical SEERs averaging over 5 and SCoPs over 3. This ensures that the designer can keep the carbon footprint as small as possible and due to VRVIII’s high efficiency, lower running costs are a welcome benefit to the end user.
p . 0 3 c o n t e n t s
Table of Contents
I
NTRODUCTION
4
F
EATURES
10
1. Wide Application Range
2. Environmental Awareness
3. Installation & Maintenance Friendly Design
10
20
23
O
UTDOOR UNITS
28
1. VRVIII
2. VRV-WII
3. Accessories
28
38
40
I
NDOOR UNITS
42
1. Features
2. Specifications
42
49
V
ENTILATION
62
1. HRV - Heat Reclaim Ventilation
2. FXMQ-MFV1 - Outdoor Air Processing Unit
62
64
3. VRV+EXV-kit - VRV Air Handling Applications 65
U
SER
F
RIENDLY
C
ONTROL
S
YSTEMS
66
1. Individual Control Systems
2. Centralised Control Systems
3. Network Solutions
4. Accessories
66
68
69
74
p . 0 4
The History of VRV Systems
• 1987
The original VRV air conditioning system developed by Daikin
Industries Ltd. in 1982 is introduced into Europe in
VRV standard format. VRV D series can supply conditioned air from up to 4 indoor units connected to a single outdoor unit.
• 1991
A further step forward is taken in 1991 with the introduction of the VRV heat recovery system, offering simultaneous cooling and heating from different indoor units on the same refrigeration circuit.
• 1994
Consistent high quality and efficiency lead to the wide-spread acceptance of the VRV concept and Daikin becomes the first Japanese air conditioning manufacturer to be awarded the ISO9001 certification. Daikin applies yet another quantum leap to VRV technology: the VRV
Inverter-H series, operate up to 16 indoor units from just
1 outdoor unit.
• 1990
The end of the year sees the launch of the new
VRV Inverter G series with the facility to operate up to 8 indoor units from a single outdoor unit. Inverter capacity control greatly increases system flexibility and efficiency.
• 1992
Continuous improvements to energy efficiency and system flexibility lead to the development of the advanced Hi-VRV in which fresh air supply (HRV) and computerised management
(DACMS) are integrated with the VRV.
• 1998
In anticipation of phase out dates for all CFC based equipment, Daikin Europe steps up the production of
VRV air conditioning units using R-407C.
Daikin Europe celebrates its 25 th
anniversary with the award of an ISO14001 environmental certificate and the introduction of VRV
Inverter K series with R-407C, in cooling only or heat pump format. As many as 16 indoor units can be connected to
1 single outdoor unit.
p . 0 5
• 1999
The VRV Plus series using R-22 has been designed around leading edge technologies to accommodate high capacity air conditioning networks of up to
30 indoor units from a single refrigerant circuit.
Another step forward has been taken with the launch of the VRV heat recovery series using R-407C and connecting up to 16 indoor units to 1 single outdoor unit.
• 2001
The latest addition to the VRV Plus series is the VRV Plus heat recovery series using
R-407C. Up to 32 indoor units can be connected to a single refrigerant circuit.
• 2003
Daikin introduces the
VRVII, the world’s first R-410A operated variable refrigerant flow system. Available in cooling only, heat pump and heat recovery versions, the system, which represents a considerable advance over earlier VRV systems, demonstrates Daikin’s innovative application of new technology.
No less than 40 indoor units in heat recovery as well as heat pump format can be connected to a single refrigerant circuit.
• 2005
Daikin has extended the operational scope of its acclaimed VRVII inverter driven dx air conditioning system, with a new watercooled version, VRV-
WII. Available in 10, 20 and 30HP models, the system operates on
R-410A refrigerant and is available in both heat pump and heat recovery versions.
• 2000
Because of the growing needs of large-capacity systems Daikin Europe introduces the VRV Plus series using R-407C, in heat pump format. Up to 32 indoor units can be connected to a single refrigerant circuit.
• 2002
Daikin launches the new πVRV series – an energy saving series with high COP levels and flexible design characteristics, using
R-407C.
• 2004
The introduction of the
VRVII-S series extends
VRV operating scope into the light commercial sectors.
Available in 4, 5 and
6HP capacities, the system is designed for installation in up to
9 rooms.
• 2006 - 2007
Daikin has announced the third generation of its much acclaimed
VRV range with the extensively re engineered VRVIII.
Available in heat pump cooling only and heat recovery versions, VRVIII incorporates all the best features of earlier
VRV systems. However, it also possesses a considerable number of new design, installation and maintenance refinements.
H i - V R V p . 0 6
What is ?
In recent years, design styles for intelligent buildings such as hotels, banks and offices etc. have increasingly featured large areas of glazing with attendant high solar heat gains that can only be dissipated by means of air conditioning. Not surprisingly therefore, air conditioning has grown in importance and is now widely accepted as an integral component of most modern architectural concepts.
The increasing use of electronic office equipment raises thermal loadings still further to a point whereby, even in winter, internal temperatures can reach uncomfortable levels. The demand for cooling or heating can also vary considerably through-out the day depending on the number and occupation of personnel on the premises. But end users have come to expect far more than just cooling and heating from their air conditioning.
The ideal modern system must be energy efficient, easy to install, flexible, reliable and user friendly. Fresh air must be supplied without increasing energy consumption and the role of central management facilities should also be considered in this respect for medium to large sized buildings. The Daikin
Hi-VRV system meets all these demands.
AIR CONDITIONING
NETWORK SOLUTION
VENTILATION CONTROL AND
MANAGEMENT
The innovative Hi-VRV selection programme, Daikin’s flag ship software package, enables you to exploit the system’s possibilities to the max and guarantees the end user a perfect service. From now on you can fully plan your Daikin air-conditioning project on a step-by-step basis without difficulty.
p . 0 7
• H
EAT
R
ECLAIM
V
ENTILATION
Heat and humidity are exchanged between supply and exhaust air, which
• brings outdoor air close to indoor air conditions
• recovers energy loss
• realises considerable reduction of air conditioning capacity
• V
ARIABLE
R
EFRIGERANT
V
OLUME
• available in cooling only, heat pump and heat recovery formats.
• a rapid response system in which up to
64 indoor units can operate on the same refrigerant circuit.
• an inverter driven compressor enables the output of the outdoor unit to be modulated in accordance with the cooling/heating demand of the zone which it controls.
NETWORK SOLUTION
The ideal solution for control and management of up to 2,000 indoor units.
Allows detailed and easy monitoring and operation of VRV systems
(maximum 2 x 64 control groups).
The ideal solution for control and management of maximum 1,024 VRV indoor units.
Open network integration of VRV monitoring and control functions into
LonWorks® networks.
Integrated control system for seamless connection between VRV and BMS systems.
p . 0 8
The VRV Systems
VRVIII I
NVERTER
C
OOLING
O
NLY
• For cooling operation from one system
• Up to 29 indoor units can be operated from a single outdoor unit without the need for an additional adapter PCB.
• The line-up of 5, 8, 10, 12, 16, 18hp models is ideally suited to applications in smaller facilities and minor expansions and upgrades.
VRVIII I
NVERTER
H
EAT
P
UMP
• For either cooling or heating operation from one system
• Up to 64 indoor units can be operated from a single outdoor unit without the need for an additional adapter PCB.
• An extensive capacity range starting at 5hp, then from 8hp to 54hp in 2hp increments meets all customer requirements concerning small to large buildings, whether new or existing
VRVIII I
NVERTER
H
EAT
R
ECOVERY
• For simultaneous cooling and heating operation from one system
• Up to 64 indoor units can be operated from a single outdoor unit in VRVIII heat recovery format.
• Extensive capacity range from 8hp to 48hp in
2hp increments for VRVIII, meets all customer requirements concerning small to large buildings, whether new or existing.
• Heat recovery is achieved by diverting exhaust heat from indoor units in cooling mode to areas requiring heating.
• The BS unit switches the system between cooling and heating modes.
V R V s y s t e m s p . 0 9
VRV-WII I
NVERTER
H
EAT
P
UMP
• For either cooling or heating operation from one system
• Up to 32 indoor units can be operated from a
VRV-WII outdoor unit without the need for an additional adapter PCB.
• Availble in 10, 20 and 30 HP models
VRV-WII I
NVERTER
H
EAT
R
ECOVERY
• For simultaneous cooling and heating operation from one system
• Up to 32 indoor units can be executed from a
VRV-WII outdoor unit without the need for an additional adapter PCB
• Availble in 10, 20 and 30 HP models
• Heat recovery is achieved by diverting exhaust heat from indoor units in cooling mode to areas requiring heating.
• The BS unit switches the system between cooling and heating modes.
Features
1. W
IDE
A
PPLICATION
R
ANGE
1
VRVIII Cooling Only/Heat Pump Outdoor Unit Range
5HP 8,10,12HP p . 1 0
14,16,18HP
VRVIII cooling only
RXQ5P
RXQ10P
RXQ12P
VRVIII heat pump
RXYQ5P
RXYQ10P
RXYQ12P
N° of outdoor units*
1
1
1
N° of compressors*
1
2
2
Maximum n° of connectable indoor units
8
16
19
Minimum capacity index
- 50%
62.5
125
150
Maximum ** capacity index - 130%
162.5
Capacity steps
18
325
390
37
37
RXQ16PA RXYQ16PA 1 3 26 200 520 51
-
-
-
-
-
-
-
-
RXYQ20P
RXYQ22P
2
2
3
4
32
35
250
275
650
715
35
36
RXYQ24P 2 4 39 300 780 40
- RXYQ26P 2 4 42 325 845 40
RXYQ28P 2 5 45 350 910 45
-
-
-
-
-
-
-
* Based on optimised footprint combinations.
RXYQ30P
RXYQ32P
RXYQ34P
RXYQ36P
RXYQ38P
RXYQ40P
RXYQ42P
RXYQ44P
RXYQ46P
RXYQ48P
RXYQ50P
RXYQ52P
RXYQ54P
** Please contact your local Daikin dealer for more information.
3
3
3
2
2
2
2
3
3
3
3
3
3
5
6
6
6
6
7
7
7
8
8
9
9
9
49
52
55
58
61
64
64
64
64
64
64
64
64
375
400
425
450
475
500
525
550
575
600
625
650
675
975
1,040
1,105
1,170
1,235
1,300
1,365
1,430
1,495
1,560
1,625
1,690
1,755
45
46
50
50
41
46
46
46
66
66
56
56
56
O u t d o o r u n i t p . 1 1
8,10,12HP 14,16HP
2
VRVIII Heat Recovery
Outdoor Unit Range
VRV III heat recovery
REYQ8P
REYQ10P
REYQ12P
REYQ14P
REYQ16P
REYQ18P
REYQ20P
REYQ22P
REYQ24P
REYQ26P
REYQ28P
REYQ30P
REYQ32P
REYQ34P
REYQ36P
REYQ38P
REYQ40P
REYQ42P
REYQ44P
REYQ46P
REYQ48P
N° of outdoor units
1
1
1
1
1
2
2
2
2
2
2
2
2
3
3
3
3
3
3
3
3
N° of compressors
2
2
2
2
2
3
3
4
4
5
5
6
6
6
6
7
8
8
8
9
9
Maximum n° of connectable indoor units
13
16
19
22
26
29
32
35
39
42
45
48
52
55
58
61
64
64
64
64
64
Minimum capacity index - 50%
100
125
150
175
200
225
250
275
300
325
350
375
400
425
450
475
500
525
550
575
600
Maximum capacity index - 130%
260
325
390
455
520
585
650
715
780
845
910
975
1,040
1,105
1,170
1,235
1,300
1,365
1,430
1,495
1,560
Capacity steps
36
41
46
36
38
41
41
46
46
51
41
46
51
31
38
26
31
37
26
30
37
10HP
3
VRV-WII Outdoor Unit Range
VRV-WII heat pump
VRV-WII heat recovery
RWEYQ10M
RWEYQ20M
RWEYQ30M
N° of outdoor units*
N° of compressors
Maximum n° of connectable indoor units
Minimum capacity index - 50%
Maximum capacity index - 130%
Capacity steps
1 1 16 125 325 22
2 2 20 250 650 32
3 3 32 375 975 37
4
Indoor Unit Capacity Index
Model
Capacity index eg. Selected indoor units: FXCQ25 + FXFQ100 + FXMQ200 + FXSQ40
Connection ratio: 25 + 100 + 200 + 40 = 365
9 possible outdoor unit REYQ12P
20 25 32 40 50 63 71 80 100 125 200 250
20 25 31.5 40 50 62.5 71 80 100 125 200 250
W i d e A p p l i c a t i o n R a n g e p . 1 2
5
Wide Range of Indoor Units
VRV air conditioning brings summer freshness and winter warmth to offices, hotels, department stores and many other commercial premises. It enhances the indoor environment and creates a basis for increased business prosperity and whatever the air conditioning requirement, a Daikin indoor unit will provide the answer. VRV air conditioning can be supplied via 13 different indoor unit models in a total of 75 variations.
Cassette type unit
Concealed ceiling unit
Floor standing unit
p . 1 3
Indoor units
Roundflow ceiling mounted cassette
4-way blow ceiling mounted cassette
2-way blow ceiling mounted cassette
Ceiling mounted corner cassette
Small concealed ceiling unit
Slim concealed ceiling unit
Concealed ceiling unit
Large concealed ceiling unit
Wall mounted unit
Ceiling suspended unit
4-way blow ceiling suspended unit
Floor standing unit
Concealed floor standing unit
FXFQ
FXZQ
FXCQ
FXKQ
FXDQ
FXDQ
FXSQ
FXMQ
FXAQ
FXHQ
FXUQ
FXLQ
FXNQ
20 25
✘ ✘
✘ ✘
✘ ✘
✘
✘
✘
✘
✘
✘
✘
✘
✘
✘
✘
✘
✘
32
✘
✘
✘
✘
✘
✘
✘
✘
✘
✘
50
✘
✘
✘
✘
✘
✘
✘
✘
✘
40
✘
✘
✘
✘
✘
✘
✘
✘
✘
✘
71
✘
63
✘
✘
✘
✘
✘
✘
✘
✘
✘
✘
80
✘
✘
✘
✘
100
✘
125
✘
200 250
✘
✘
✘
✘
✘
✘
✘
✘
✘ ✘
Concealed floor standing unit
Ceiling suspended unit
Wall mounted unit
W i d e A p p l i c a t i o n R a n g e p . 1 4
Daikin offers a variety of solutions for the provision of fresh air ventilation to offices, hotels, stores and other commercial outlets – each one complementary to and as flexible as the VRV system itself.
HRV - H
EAT
R
ECLAIM
V
ENTILATION
9
Heat and humidity are exchanged between supply and exhaust air, which
• brings outdoor air close to indoor air conditions
• recovers energy loss
• realises considerable reduction of air conditioning capacity
9
The heat exchanger modulates the humidity and temperature of incoming fresh air to match indoor conditions.
9 The balance achieved between indoor and outdoor ambients, enables the cooling/heating load placed on the air conditioning system to be reduced. (Heat and humidity are exchanged)
9
Most energy saving solution as smaller indoor units can be selected:
• Size down of indoor units down to 40 %
• Payback total VAM system: ±2.5 years*
*conditions:
- outside cooling conditions: 30°C / outside heating conditions: - 8°C
- Inside cooling conditions: 24°C / inside heating conditions: 22°C
- Ventilation per room: 150m3/h
9 Ideal modular concept to cope with the fresh air requirements
FXMQ-MFV1 – O
UTDOOR
A
IR
P
ROCESSING
U
NIT
9
100% fresh air intake possible
9 Leaves maximum floor and wall space for furniture, decorations and fittings
9 Operation range: -5°C to 43°C
9
225 Pa external static pressure allows extensive ductwork runs and flexible application: ideal for use in large areas
9 Drain pump kit available as accessory
VRV+EXV-
KIT
- VRV A
IR
H
ANDLING
A
PPLICATIONS
9
Inverter controlled units
9
Large capacity range (from 5HP to 18HP)
9 Cooling only
9 Control z: control of air temperature (suction temperature, room temperature) via Daikin control (no DDC controller needed)
9
Large range of expansion valve kits available
9 Drain pump kit available as accessory
p . 1 5
7
Extended Piping Length
VRVIII
VRVIII offers an extended piping length of 165m (190m equivalent piping length) with a total system piping length of 1,000m.
In case the outdoor unit is located above the indoor unit the height difference is 50m standard. It can be extended to 90m*
In case the outdoor unit is located below the indoor unit, the height difference is 40m standard. Height differences up to maximum 90m are possible*.
length
Equivalent piping length
190 m
After the first branch, the longest piping length can be a maximum of 90m provided that the difference between the longest piping length and the shortest piping length is a maximum of 40m.
* For more information, please contact your local Daikin dealer.
VRV-WII
The water-cooled VRV-WII uses water as its heat source and since there are no limitations on water piping length, is eminently suitable for application to tall multi storey or large buildings. Considerable flexibility is available within the refrigerant circuit since up to 120m actual piping length and 50m* (if the VRV-WII is above the indoor units) in height can exist between the VRV-WII and indoor units.
Water piping does not intrude on the occupied spaces, so there are no leakage problems.
* 40m if the VRV-WII is below the indoor units.
Actual piping length between the VRV-WII and indoor units: 120m
(Equivalent piping length: 140m)
(Total piping length: 300m)
Water piping
Refrigerant piping
Level difference between indoor units: 15m
Indoor installation
VRV-WII
Water piping length depends on the heat source equipment length
Equivalent piping length
140 m
W i d e A p p l i c a t i o n R a n g e p . 1 6
8
Super Silent Mode
Step 1
Step 2
50dB
45dB
5HP 8HP 10HP 12HP 14HP 16HP 18HP
14.7 19.9 19.9 20.9 19.9 20.1 20.2
100% 98% 78% 69% 55% 49% 44%
11.9 15.1 15.1 15.6 15.5 15.6 15.6
93% 74% 59% 51% 43% 38% 34%
Step 1 fixes the operating sound value at 50dBA. When the sound level of an 8HP outdoor unit is fixed at
50dBA it will operate at 98 % of its nominal capacity. Step 2 fixes the operating sound value at 45dBA. When the sound level of the same 8HP outdoor unit is fixed at 45dBA it will operate at 74 % of its nominal capacity.
For some applications the operating sound level of the outdoor unit might be too high. VRVIII super silent mode however, allows the sound level to be fixed in order to avoid noise pollution.
9
VRV-WII
The adoption of a new water heat exchanger and optimization of the refrigerant control circuit has resulted in the industry’s most compact and lightweight design. The unit weight of 150kg and height of 1,000mm makes installation easy. Stacked configuration is also possible, contributing further to space savings.
Stacked configuration is possible.
Ceiling height
3,200mm or higher
100-300mm
Floor level
In the event of a compressor malfunction, the remotely controlled or field set back-up function in the outdoor unit in question (and also between different outdoor units) will allow emergency operation of another compressor in order to maintain 8 hour maximum interim capacity.
p . 1 7
11
Year Round Cooling and/or Heating
9 Designed to provide simultaneous year round cooling and/or heating, VRV heat recovery systems are modular in concept and are therefore, ideal for use in rooms or zones that generate varying thermal loads according to building orientation or local hot or cold spots.
9 It is possible for the same meeting room to give rise to differing thermal loads depending on the time of day, number of occupants present, location and usage pattern of lighting and electronic office equipment.
9 The colder it is outside, the warmer it needs to be indoors, which means that the capacity of the air-cooled outdoor unit drops. Water-cooled air conditioners are not subject to this problem. The boiler ensures that sufficient enough additional heat is always available indoors.
The new VRVIII Heat Recovery system improves on delivered heating capacity compared to other systems on the market, through changes in operation during defrost. As each system comprises at least 2 heat exchangers in the outdoor unit, the system will defrost these alternatively.
This results in continuous heating at the indoor unit even during the defrost cycle. Where other VRF systems stop operating, VRVIII continues in heating to maintain comfort.
Defrost
Continuous heating during defrost
Liquid pipe
High/Low Pressure Gas Pipe
Suction gas type
BS unit
Heating
W i d e A p p l i c a t i o n R a n g e p . 1 8
12
Anti Corrosion Treatment
Special anti corrosion treatment of the heat exchanger provides 5 to 6 times greater resistance against acid rain and salt corrosion. The provision of rust proof steel sheet on the underside of the unit gives additional protection.
Improvement in corrosion resistance
Heat exchanger
An anti-corrosion heat exchanger cutaway view
Hydrophilic film
Aluminium
Corrosion-resistant
Acrylic resin
Corrosion resistance rating
Salt corrosion
Acid rain
Non-treated
1
1
5 to 6
5 to 6
Performed tests :
VDA Wechseltest contents of 1 cycle (7 days):
9
24 hours salt spray test SS DIN 50021
9
96 hours humidity cycle test KFW DIN 50017
9 48 hours room temperature & room humidity testing period : 5 cycles
8
6
4
2
0
1 2 3 4 5
Cycle
Kesternich test (SO2)
9 contents of 1 cycle (48 hours) according to DIN50018 (0.21)
9 testing period : 40 cycles
Bare aluminium
DAIKIN P.E.
7
6
5
4
3
10
9
8
2
1
0
1 2 3 4 5
Cycle
6 10 20 30 40
p . 1 9
VRVIII
Standard operation down to -20°C outdoor ambient temperature. Advanced PI control of the outdoor unit enables VRVIII series to operate at outdoor ambients down to -5°C in cooling mode and down to -20°C in heating mode.
50
40
Cooling 43°CDB
-10
-15
10
-5
30
20
-5°CDB
Heating 15.5°CWB
-20
-20°CWB
VRVIII cooling only / heat pump
10
-5
-10
-15
-20
50
40
30
20
Cooling 43°CDB
-5°CDB
Cooling & Heating
15.5°CWB
-5°CWB
Heating
15.5°CWB
VRVIII heat recovery
-20°CWB
VRV-WII
Wide operation range of the water-cooled units between
10°C & 45°C, both in cooling and heating.
30
20
10
0
50
40
Cooling
45°
10°C 10°C
VRV-WII heat pump / heat recovery
Heating
45°C
14
Low Operation Sound Level
9
Continuous research by Daikin into reducing operation sound levels has resulted in the development of a purpose designed inverter scroll compressor and fan.
9
Daikin indoor units have very low sound operation levels, down to 25dB(A)
dB(A)
0
20
40
60
80
100
120
Treshold hearing
Extremely soft
Very soft
Moderately loud
Very loud
Threshold of feeling
Sound
-
Rustling leaves
Quiet room
Normal conversation
City traffic noise
Jet taking off
9
D
AIKIN INDOOR UNIT
E n v i r o n m e n t a l C o n s c i o u s n e s s p . 2 0
2. E
NVIRONMENTAL
A
WARENESS
Option 1: Compact Combinations
Compact combinations from 5HP to 54HP provide the smallest footprint
HP
8
16 18 20
1
22 24 26
1
28 30 32 34
10 1 1
12 1 1 2 1
14 1
16 1
36
18 1 1 1 1 1 1 2
EER/COP Values
HP
EER
COP
16 18 20 22 24 26 28 30 32 34 36
3.17 3.02 3.68 3.62 3.49 3.28 3.26 3.20 3.11 3.09 3.02
3.88 3.69 4.08 4.04 3.47 3.84 3.83 3.81 3.83 3.79 3.69
Option 2: High EER/COP Combinations
High EER/COP combinations provide the most energy efficient outdoor units from 16HP to 36HP
HP
8
10
12
16 18 20
2 1
22 24 26 28 30 32 34
1 2 1 1 2 3 1
36
2 2 3
9
30 %
RISE
Optimised EER/COP Values
HP
EER
COP
16 18 20 22 24 26 28 30 32 34 36
4.04 3.88 3.78 3.62 4.02 3.94 3.84 3.77 3.60 3.56 3.49
4.27 4.15 4.09 4.04 3.97 4.20 4.13 4.09 4.05 4.02 3.99
2
Smaller Refrigerant Charge
Compared to previous series VRVIII has the smallest refrigerant amount in the system.
10HP
Refrigerant charge
R-22 VRV-K
13.5 kg
100 %
R-407C VRV-K
11.2 kg
83 %
R-410A VRVII
8.6 kg
63.7 %
R-410A VRVIII
8.4 kg
62.2 %
9
37.8 %
REDUCTION
3
Improved Refrigerant Containment
All flange and flare connections in the VRIII condensing units and branch selector boxes have been replaced by brazing connections to ensure improved refrigerant containment.
VRVIII H/R
Brazed joint
Outdoor unit
Shutoff valve
Liquid pipe
High/low pressure gas pipe
Suction gas pipe
Equalizing pressure pipe
Brazed joints
p . 2 1
4
Refrigerant Containment Check
The refrigerant volume of the complete system is calculated from the following data:
• outdoor temperature
• reference system temperatures
• reference pressure temperatures
• refrigerant density
• types and number of indoor units
When activating the refrigerant containment check, the unit switches into cooling mode and duplicates certain reference conditions based on memory data. The result indicates whether or not refrigerant leakage has occurred.
5
Restriction of Hazardous Substances in electrical and electronic equipment (2002/95/EC)
Hazardous substances include Lead (Pb), Cadmium (Cd), Hexavalent Chromium (Cr6+), Mercury (Hg),
Polybrominated biphenyls (PBB), Polybrominated diphenylether (PBDE).
Although RoHS regulations are only applicable to small and large household equipment, Daikin environmental policy nevertheless ensures that VRVIII will be totally in line with RoHS.
6
The linear VRV system makes use of a variable Proportional Integral (PI) control system which uses refrigerant pressure sensors to give added control over inverter and ON/OFF control compressors in order to abbreviate control steps into smaller units to provide precise control in both small and larger areas. This in turn enables individual control of up to 60 indoor units of different capacity and type at a ratio of 50~200 % in comparison with outdoor units capacity. 5 HP outdoor units use inverter control compressors only.VRV systems have low running costs because it permits each zone to be controlled individually. That is, only those rooms that require air conditioning will be heated or cooled, while the system can be shut down completely in rooms where no air conditioning is required.
5HP/14kW OUTDOOR UNIT 8HP/22.4kW OUTDOOR UNIT
100% 100%
100%
10HP/28kW OUTDOOR UNIT
12HP/33.5kW OUTDOOR UNIT
14%
Large
1
2
37 Steps
Load
1
Small
18 Steps
1
24%
Large
Load
100%
14HP/40.0kW OUTDOOR UNIT
16HP/44.5kW OUTDOOR UNIT
Small
1
3
1
10%
Large
2 2
Load
51 Steps
1
Small
24 Steps
1
19%
Large
Load
Small
100%
18HP/44.5kW OUTDOOR UNIT
1
3
1
9%
Large
2 2
Load
55 Steps
1
Small
E n v i r o n m e n t a l C o n s c i o u s n e s s p . 2 2
7
Smart Control Brings Comfort
An electronic expansion valve, using PID control, continuously adjusts the refrigerant volume in respond to load variations of the indoor units. The VRV system thus maintains comfortable room temperatures at a virtually constant level, without the temperature variations typical of conventional ON/OFF control systems.
Cooling
VRV SERIES (DAIKIN PID Controls)
ON/OFF controlled air conditioner (2.5HP)
Slow start-up
Time
Note: the graph shows the data, measured in a test room assuming actual heating load.
The thermostat can control stable room temperature at ± 0.5°C from set point.
Set point
Non inverter AC
Inverter AC
Keeps temperature stable
Start-up time reduced by about 1/3
Repeats hot and cold cycles
Large temperature difference
Smaller temperature difference
8
Less Frequent Start/Stop Cycle
9 the technique adopted by Daikin, of regulating the capacity using multiple compressors clearly results in minimum switching losses and power surges because of the overlap in capacity and frequency
9 since Daikin utilises small 5HP inverter compressors, the influence of harmonics is less than that generated by a single large compressor
9 the use of multiple compressors by Daikin also ensures a 50 % standby facility
9 smaller compressors are cheaper and faster to replace
30
50%
60%
55%
65%
116 30+on 116+on
Frequency
9
Refrigerant Recovery Function
The refrigerant recovery function enables all expansion valves to be opened. In this way the refrigerant can be drained from the piping system.
p . 2 3
3. I
NSTALLATION
& M
AINTENANCE
F
RIENDLY
D
ESIGN
1
Automatic Charge Function
Conventional Way:
1. calculation of additional refrigerant charging volume
2. charging the unit with additional refrigerant
3. measuring the weight of the cylinder
4. judgment based on pressure (test operation)
VRVIII
With VRVIII however, these 4 steps are omitted since VRVIII unit can be charged with the necessary amount of refrigerant automatically via a push button on the PCB. Automatic charging will cease once the appropriate amount of refrigerant has been transferred.
If temperature drops below 20°C manual charging is necessary. After having switched to heating and once the indoor temperature rises above 20°C, push the auto charge button to activate auto charge function. Refrigerant containment is only available after performing the automatic charge function.
32°C
Indoor temperature
20°C
Automatic charge function
Manual charge
0°C 43°C
Outdoor temperature
2
When refrigerant charging has ceased, pushing the test operation button on the PCB will initiate a check on the wiring, shut off valves, sensors and refrigerant volume. This test ceases automatically when completed.
3
Self Diagnostic Function
This function operated via push button on the PCB, speeds up troubleshooting and should be used for start-up and maintenance.
Disconnected thermistors, faulty solenoid valves or motor operated valves, compressor malfunctions, communication errors, etc can be diagnosed quickly.
I n s t a l l a t i o n & M a i n t a n c e F r i e n d l y D e s i g n p . 2 4
The cyclical start-up sequence of multiple outdoor units systems equalized compressor duty and extends operating life
5
Short Installation Time
Thanks to small refrigerant pipes and REFNET piping options, the VRV piping system can be installed very easily and quickly.
Installation of the VRV system can also be implemented floor by floor, so that sections of the building can be put into use very quickly, or enabling the air conditioning system to be commissioned and operated in stages, rather than on final completion of the project.
6
Modular & Lightweight
Modular design enables units to be joined together in rows with an outstanding degree of uniformity.
The design of the outdoor units is sufficiently compact to allow them to be taken up to the top of a building in a commercial elevator, overcoming site transportation problem, particularly when outdoor units need to be installed on each floor.
7
No structural reinforcement necessary
Thanks to the lightweight and vibration-free construction of the outdoor units, floors do not need to be reinforced, reducing the overall cost of the building.
p . 2 5
Reduced piping diameters
Use of high efficiency R-410A enables the VRVIII to operate on a smaller refrigerant charge to be used, leading to a reduction in liquid and gas pipe diameters.
Reduced piping costs thanks to modular design
Smaller diameter liquid and gas piping contributes to a reduction in installation space and installation costs.
4-way Piping Connection
VRV series not only offer the possibility to run piping from the front, but also from the left, right or bottom, thus providing greater freedom of layout.
Non Modular VRF System
Outdoor unit Max. 16 indoor units
Left
Front
Bottom
Right
Around 30% reduction in installation costs for refrigerant piping.
VRVIII System
Outdoor unit
Max. 64 indoor units
VRV-WII System
R-410A
Max. 32 indoor units
H2O
p . 2 6
9
Unified REFNET piping
The unified Daikin REFNET piping system is especially designed for simple installation
The use of REFNET piping in combination with electronic expansion valves, results in a dramatic reduction in imbalance in refrigerant flowing between indoor units, despite the small diameter of the piping.
REFNET joints and headers (both accessories) can cut down on installation work and increase system reliability.
Compared to regular T-joints, where refrigerant distribution is far from optimal, the Daikin REFNET joints have specifically been designed to optimise refrigerant flow.
REFNET joint
REFNET header
REFNET joint
Attached insulators for REFNET joint
Attached insulators for REFNET header
T-joint
10
Up to 3 outdoor units can be connected to 1 power supply and can be turned on sequentially. This allows the number of breakers and their capacities to remain small and simplifies wiring (for models of 10Hp or less).
11
Cross Wiring Check
The cross wiring check facility available on the VRV is the first of its type in the industry to warn operatives of connection errors in inter unit wiring and piping. This function identifies and alerts system errors by means of on/off LEDs on the outdoor unit’s PC boards.
12
A simple 2-wire non-shielded multiplex transmission system links each outdoor unit to multiple indoor units using one 2-core wire, thus simplifying the wiring operation.
Furthermore, outdoor units have power connection outlets on side and front, resulting in easier installation and maintenance and saving space when rows of units are connected together.
13
“Super Wiring” System
A Super Wiring system is used to enable the shared use of wiring between indoor units, outdoor units and the centralised remote control.
This system makes it easy for the user to retrofit the existing system with a centralised remote control, simply by connecting it to the outdoor units.
Thanks to a non polarity wiring system, incorrect connections become impossible and installation time is reduced.
I n s t a l l a t i o n & M a i n t a n c e F r i e n d l y D e s i g n p . 2 7
Wiring can be fed from the front panel, both left and right side panels and bottom panel of the outdoor unit.
Left
Right
Front
Bottom
15
Auto Address Setting Function
Allows wiring between indoor and outdoor units, as well as group control wiring of multiple indoor units, to be performed without the bothersome task of manually setting each address.
p . 2 8
Outdoor Units
1. VRVIII
1
1
Reluctance Brushless DC Compressor
9 The reluctance brushless DC motor provides significant increases in efficiency compared to conventional
AC inverter motors, simultaneously using 2 different forms of torque (normal and reluctance torque) to produce extra power from small electric currents.
9
The motor comprises powerful neodymium magnets, that create the reluctance torque. These magnets are approximately 12 times stronger than ferrite magnets and make a major contribution to its energy saving characteristics.
9
High thrust mechanism (VRVIII cooling only/heat pump)
By introducing high pressure oil, the reactive force from the fixed scroll is added to the internal force, thereby reducing thrust losses. This results in improved efficiency and suppressed sound level
Ferrite magnet
Neodymium magnet
2
Sine Wave DC Inverter
Optimizing the sine wave curve, results in smoother motor rotation and improved motor efficiency.
3
DC Fan Motor
The use of a DC fan motor offers substantial improvements in operating efficiency compared to conventional
AC motors, especially during low speed rotation.
DC fan motor structure
60
40
20
100
DC motor efficiency
(comparison with a conventional AC motor)
80
AC motor
0
200 300 400 500 600 700 800 900 1000
Motor speed (rpm)
O u t d o o r U n i t s p . 2 9
4
5
3
2
1
4
Dual DC Fans
• Maximum 10% increase in airflow (16 HP) due to dual
DC fans
• Increased output and reduced pressure loss together with increased external static pressure and reduced rated fan input.
10 HP: 3 blades, ø700
--> 4 blades, ø680 blade area increased by 25%, uneven pitch: No NZ noise
18 HP: ø700 --> ø540 x 2 blade area increased by 20%, sound reduced by 0.7 dB
9 9
Fans optimized for their casings
(increased air flow without sound increase)
10
8.1
5
3.2
3.8
1.3
0
4.9
2.5
VRVII VRVIII
Substantial reduction in pressure loss
Three-dimensional integrated woven soft steel grilles with plastic coating
• High strength (withstands weight of 60 kg)
• Increased outflow area opening ratio
Increased heat exchange area
• Increase in heat exchange effectiveness
5
e-Pass Heat Exchanger
Optimization of the path layout of the heat exchanger prevents heat transferring from the overheated gas section towards the sub cooled liquid section - a more efficient use of the heat exchanger.
Current Model HD Type
OUT 45°C
IN 85°C
27°C
IN 85°C
27°C
55°C
55°C
37°C
27°C
27°C
55°C
50°C
27°C
27°C
SAÍDA 45°C
In cooling mode, the heat exchanger of the condensor is improved.
This means an improvement of COP by 3%.
OUT 45°C
43°C
60°C
55°C
6
i-Demand Function
The newly introduced current sensor minimizes the difference between the actual power consumption and the predefined power consumption.
8:00 12:00
Time
p . 3 0
2
VRVIII COOLING ONLY
RXQ-P(A)
Nominal capacity
COP
Capacity range
Power input (nominal)
Max n° of indoor units to be connected
Indoor index connection minimum maximum
Casing colour material width depth kW
HP kW mm mm
Fan type air Flow Rate (nominal at 230V) m
3
/min external static pressure (MAX) Pa
Compressor type
Operation range minimum maximum
Sound level (nominal)
°CDB
°CDB sound power dBA sound pressure dBA
Refrigerant type
Refrigerant Oil
Piping Connections charge control type charged volume liquid gas heat insulation kg l type diameter (OD) mm type diameter (OD) mm
Capacity control method
Capacity control [%]
Safety devices
Power supply name phase frequency voltage
Hz
V
RXQ5P7W1B RXQ8P7W1B RXQ10P7W1B RXQ12P7W1B RXQ14P7W1BA RXQ16P7W1BA RXQ18P7W1BA
14.0
3.98
5
3.52
8
62.5
162.5
1,680
635
765
157
95
-5.0
43.0
72
54
6.2
1.7
9.52
15.9
~ 100
W1
3N~
50
400
22.4
4.03
8
5.56
13
100
260
1,680
930
765
185
171
-5.0
43.0
78
57
7.7
28.0
3.77
10
7.42
16
125
325
33.5
3.48
12
9.62
19
150
390
1,680
930
765
238
Daikin White
Painted galvanised steel
1,680
930
765
238
Propeller
196 185
-5.0
43.0
78Pa in high static pressure
Hermetically sealed scroll compressor
-5.0
43.0
78
58
8.4
80
60
R-410A
8.6
Notes
Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are measured in a semi-anechoic room.
40.0
3.23
14
12.4
23
175
455
1,680
1,240
765
314
233
-5.0
43.0
80
60
11.3
2.1
9.52
19.1
3.9
Expansion valve (electronic type)
Synthetic (ether) oil
3.9
Braze connection
9.52
22.2
12.7
Braze connection
28.6
Both liquid and gas pipes
5.7
12.7
28.6
~ 100 ~ 100
Inverter controlled
~ 100 ~ 100
HPS, fan motor driver overload protector, overcurrent relay, inverter overload protector, PC board fuse
W1 W1 W1 W1
3N~
50
400
3N~
50
400
3N~
50
400
3N~
50
400
45.0
3.17
16
14.2
26
200
520
1,680
1,240
765
314
233
-5.0
43.0
80
60
11.5
5.7
12.7
28.6
~ 100
W1
3N~
50
400
49.0
3.02
18
16.2
29
225
585
1,680
1,240
765
322
239
-5.0
43.0
83
63
11.7
5.8
15.9
28.6
~ 100
W1
3N~
50
400
O u t d o o r U n i t s p . 3 1
3
VRVIII HEAT PUMP - SMALL FOOTPRINT COMBINATION
RXYQ-P(A)
Nominal capacity
Capacity range cooling heating heating
Max n° of indoor units to be connected
Indoor index connection minimum maximum
COP cooling heating
Power input (nominal) cooling
Casing colour material mm mm kg kW kW
14.0
16.0
3.98
HP kW
4.00
5 kW
3.52
4.00
8
62.5
162.5
1,680
635
765
159 width depth
Weight unit
Fan type air flow rate cooling
(nominal at 230V) heating external static pressure (MAX) Pa m
3
/min 95 m
3
/min 95
Compressor type
Operation range cooling minimum °CDB -5.0 maximum °CDB 43.0 heating minimum °CWB -20.0
Sound level (nominal) cooling maximum °CWB sound power dBA sound pressure dBA
15.0
72
54
Refrigerant type charge control kg 6.2
Refrigerant Oil
Piping Connections type liquid charged Volume gas heat insulation max. total length l type diameter (OD) mm type diameter (OD) mm m
1.7
9.52
15.9
1,000
~ 100
Hz
V
W1
3N~
50
400
RXYQ5P7W1B RXYQ8P7W1B RXYQ10P7W1B RXYQ12P7W1B RXYQ14P7W1BA RXYQ16P7W1BA RXYQ18P7W1BA
22.4
25.0
4.03
4.27
8
5.56
5.86
13
100
260
1,680
930
765
187
171
171
28.0
31.5
3.77
4.09
10
7.42
7.70
33.5
37.5
3.48
3.97
12
9.62
9.44
16
125
325
19
150
390
Daikin White
1,680
930
765
240
Painted galvanised steel
1,680
930
765
185
185
-5.0
43.0
240
Propeller
196
196
78Pa in high static pressure
Hermetically sealed scroll compressor
-5.0
43.0
40.0
45.0
3.23
3.98
14
12.4
11.30
23
175
455
1,680
1,240
765
316
233
233
-5.0
43.0
-20.0
15.0
78
57
7.7
2.1
9.52
-20.0
15.0
78
58
8.4
R-410A
8.6
Expansion valve (electronic type)
Synthetic (ether) oil
3.9
-20.0
15.0
80
60
9.52
3.9
Braze connection
12.7
Braze connection
-5.0
43.0
-20.0
15.0
80
60
11.3
5.7
12.7
19.1
1,000
22.2
1,000
28.6
Both liquid and gas pipes
1,000
Reversed cycle
28.6
1,000
Sensor for outdoor heat exchanger temperature
Inverter controlled
~ 100 ~ 100 ~ 100 ~ 100
HPS, fan motor driver overload protector, overcurrent relay, inverter overload protector, PC board fuse
W1
3N~
W1
3N~
W1
3N~
W1
3N~
50
400
50
400
50
400
50
400
45.0
50.0
3.17
3.88
16
14.2
12.90
26
200
520
1,680
1,240
765
316
233
233
-5.0
43.0
-20.0
15.0
80
60
11.5
5.7
12.7
28.6
1,000
~ 100
W1
3N~
50
400
49.0
56.5
3.02
3.69
18
16.2
15.30
29
225
585
1,680
1,240
765
324
239
239
-5.0
43.0
-20.0
15.0
83
63
11.7
5.8
15.9
28.6
1,000
~ 100
W1
3N~
50
400
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound power level is an absolute value that a sound source generates.
Sound pressure level is a relative value, depending on the distance and acoustic environment.
Sound values are measured in a semi-anechoic room.
O u t d o o r U n i t s p . 3 2
4
VRVIII HEAT PUMP - SMALL FOOTPRINT COMBINATION
Combination RXYQ8P7W1B
RXYQ10P7W1B
RXYQ12P7W1B
RXYQ14P7W1BA
RXYQ16P7W1BA
Nominal capacity
RXYQ18P7W1BA cooling heating
COP cooling
Capacity range heating
Power input (nominal) cooling heating kW kW
HP kW kW
Max n° of indoor units to be connected
Indoor index connection minimum maximum
Casing colour material
Fan type air flow rate cooling m 3 /min
(nominal at 230V) heating m
3
/min
External static pressure (MAX) Pa
Compressor type
Operation range cooling minimum °CDB maximum °CDB heating
Refrigerant type charge minimum maximum control
Maximum total refrigerant charge in the system
Refrigerant Oil type charged volume l
°CWB
°CWB kg kg
Piping Connections
Defrost method
Defrost control liquid gas heat insulation max. total length type diameter (OD) mm type diameter (OD) mm m
Capacity control method
Capacity control [%]
Safety devices
Power supply name phase frequency voltage
Hz
V
RXYQ-P RXYQ20P7W1B RXYQ22P7W1B RXYQ24P7W1B RXYQ26P7W1B RXYQ28P7W1B RXYQ30P7W1B RXYQ32P7W1B RXYQ34P7W1B RXYQ36P7W1B
1
1
55.9
62.5
3.68
4.08
20
15.2
15.3
32
250
650
Propeller
171 + 196
171 + 196
-5.0
43.0
-20.0
15.0
R-410A
7.7 + 8.6
2.1 + 3.9
15.9
28.6
1,000
~ 100
W1
3N~
50
400
1
1
61.5
69.0
3.62
4.04
22
17.0
17.1
35
275
715
Propeller
185 + 196
185 + 196
-5.0
43.0
-20.0
15.0
R-410A
8.4 + 8.6
3.9 + 3.9
15.9
28.6
1,000
~ 100
W1
3N~
50
400
2
67.0
75.0
3.49
3.97
24
19.2
18.9
39
300
780
Propeller
196 + 196
196 + 196
-5.0
43.0
-20.0
15.0
R-410A
8.6 + 8.6
3.9 + 3.9
15.9
34.9
1,000
~ 100
W1
3N~
50
400
1
1
71.4
81.5
3.28
3.84
26
1
1
77.0
88.0
3.26
3.83
28
21.8
21.2
42
325
845
23.6
23.0
45
350
25.8
24.7
49
375
975 910
Daikin White
Propeller
171 + 239
171 + 239
Painted galvanised steel
Propeller
185 + 239
185 + 239
78Pa in high static pressure
Hermetically sealed scroll compressor
Propeller
196 + 239
196 + 239
1
1
82.5
94.0
3.20
3.81
30
1
1
89.0
102.0
3.11
3.83
32
28.6
26.6
52
400
1,040
Propeller
233 + 239
233 + 239
1
1
94.0
107.0
3.09
3.79
34
30.4
28.2
55
425
1,105
Propeller
233 + 239
233 + 239
-5.0
43.0
-20.0
15.0
-5.0
43.0
-20.0
15.0
-5.0
43.0
-20.0
15.0
R-410A
7.7 + 11.7
R-410A
8.4 + 11.7
R-410A
8.6 + 11.7
Expansion valve (electronic type)
Less than 100 (calculated charge less than 95)
2.1 + 5.8
19.1
Synthetic (ether) oil
3.9 + 5.8
Braze connection
19.1
3.9 + 5.8
19.1
34.9
Braze connection
34.9
Both liquid and gas pipes
1,000 1,000
34.9
1,000
Reversed cycle
Sensor for outdoor heat exchanger temperature
-5.0
43.0
-20.0
15.0
R-410A
11.3 + 11.7
5.7 + 5.8
19.1
34.9
1,000
-5.0
43.0
-20.0
15.0
R-410A
11.5 + 11.7
5.7 + 5.8
19.1
34.9
1,000
~ 100
Inverter controlled
~ 100 ~ 100 ~ 100 ~ 100
HPS, fan motor driver overload protector, overcurrent relay, inverter overload protector, PC board fuse
W1
3N~
50
400
W1
3N~
50
400
W1
3N~
50
400
W1
3N~
50
400
W1
3N~
50
400
32.4
30.6
58
450
1,170
2
98.0
113.0
3.02
3.69
36
Propeller
239 + 239
239 + 239
-5.0
43.0
-20.0
15.0
R-410A
11.7 + 11.7
5.8 + 5.8
19.1
41.3
1,000
~ 100
W1
3N~
50
400
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent systems, each containing less than 95 kg refrigerant charge. For factory charge, refer to the namplate of the unit.
p . 3 3
RXYQ-P
Combination RXYQ8P7W1B
RXYQ10P7W1B
RXYQ12P7W1B
RXYQ14P7W1BA
RXYQ16P7W1BA
Nominal capacity
RXYQ18P7W1BA cooling heating
COP cooling
Capacity range heating
Power input (nominal) cooling heating kW kW
HP kW kW
Max n° of indoor units to be connected
Indoor index connection minimum maximum
Casing colour material
Fan type air flow rate cooling m 3 /min
(nominal at 230V) heating m
3
/min external static pressure (MAX) Pa
Compressor type
Operation range cooling minimum °CDB maximum °CDB heating
Refrigerant type charge minimum maximum °CWB control
Maximum total refrigerant charge in the system
Refrigerant Oil type charged Volume l
°CWB kg kg
Piping Connections
Defrost method
Defrost control liquid gas heat Insulation max. total length type diameter (OD) mm type diameter (OD) mm m
Capacity control method
Capacity control [%]
Safety devices
Power supply name phase frequency voltage
Hz
V
RXYQ38P7W1B RXYQ40P7W1B RXYQ42P7W1B RXYQ44P7W1B RXYQ46P7W1B RXYQ48P7W1B RXYQ50P7W1B RXYQ52P7W1B RXYQ54P7W1B
1 1
1 1
1 1 2 1
1
1
1 1 1 2 2 2 2 2 3
105.0 111.0 116.0 120.0 126.0 132.0 138.0 143.0 147.0
119.0 126.0 132.0 138.0 145.0 151.0 158.0 163.0 170.0
3.34 3.34 3.28 3.16 3.17 3.14 3.08 3.07 3.02
3.89 3.89 3.86 3.78 3.79 3.78 3.77 3.75 3.70
38 40 42 44 46 48 50 52 54
31.4 33.2 35.4 38.0 39.8 42.0 44.8 46.6 48.6
30.6 32.4 34.2 36.5 38.3 40.0 41.9 43.5 45.9
61 64 64 64 64 64 64 64 64
475 500 525 550 575 600 625 650 675
1,235 1,300 1,365 1,430 1,495 1,560 1,625 1,690 1,755
Daikin White
Painted galvanised steel
Propeller
171 + 196 + 239 185 + 196 + 239 196 + 196 + 239 171 + 239 + 239 185 + 239 + 239 196 + 239 + 239 233 + 239 + 239 233 + 239 + 239 239 + 239 + 239
171 + 196 + 239 185 + 196 + 239 196 + 196 + 239 171 + 239 + 239 185 + 239 + 239 196 + 239 + 239 233 + 239 + 239 233 + 239 + 239 239 + 239 + 239
78 Pa in high static pressure
Hermetically sealed scroll compressor
-5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0 -5.0
43.0 43.0 43.0 43.0 43.0 43.0 43.0 43.0 43.0
-20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0 -20.0
15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0 15.0
R-410A
7.7 + 8.6 + 11.7 8.4 + 8.6 + 11.7 8.6 + 8.6 + 11.7 7.7 + 11.7 + 11.7 8.4 + 11.7 + 11.7 8.6 + 11.7 + 11.7 11.3 + 11.7 + 11.7 11.5 + 11.7 + 11.7 11.7 + 11.7 + 11.7
Expansion valve (electronic type)
Less than 100 (calculated charge less than 95)
Synthetic (ether) oil
2.9 + 3.9 + 5.8 3.9 + 3.9 + 5.8 3.9 + 3.9 + 5.8 2.1 + 5.8 + 5.8 3.9 + 5.8 + 5.8 3.9 + 5.8 + 5.8 5.7 + 5.8 + 5.8 5.7 + 5.8 + 5.8 5.8 + 5.8 + 5.8
Braze connection
19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1
Braze connection
41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3 41.3
Both liquid and gas pipes
1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000 1,000
~ 100 ~ 100
Sensor for outdoor heat exchanger temperature
~ 100 ~ 100
Inverter controlled
~ 100 ~ 100 ~ 100
HPS, fan motor driver overload protector, overcurrent relay, inverter overload protector, PC board fuse
~ 100 ~ 100
W1 W1 W1 W1 W1 W1 W1 W1 W1
3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~ 3N~
50 50 50 50 50 50 50 50 50
400 400 400 400 400 400 400 400 400
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent systems, each containing less than 95 kg refrigerant charge. For factory charge, refer to the namplate of the unit.
O u t d o o r U n i t s p . 3 4
5
VRVIII HEAT PUMP - HIGH COP COMBINATION
RXYQ-P RXYQ16P7W1B RXYQ18P7W1B RXYQ20P7W1B
Combination RXYQ8P7W1B
Nominal capacity
RXYQ10P7W1B
RXYQ12P7W1B cooling heating kW kW
COP cooling heating
Capacity range
Power input (nominal) cooling heating
Max n° of indoor units to be connected
Indoor index connection minimum maximum
HP kW kW
Casing colour material
Fan type air flow rate cooling
(nominal at 230V) heating external static pressure (MAX) Pa m
3
/min m
3
/min
Compressor type
Operation range cooling minimum °CDB maximum °CDB heating charge control minimum °CWB maximum °CWB
Refrigerant type kg kg Maximum total refrigerant charge in the system
Refrigerant Oil type
Piping Connections charged Volume liquid type l
2
44.8
50.0
4.04
4.27
16
11.1
11.7
26
200
520
171 + 171
171 + 171
-5.0
43.0
-20.0
15.0
7.7 + 7.7
2.1 + 2.1
1
1 2
50.4
56.5
3.88
4.15
18
13.0
13.6
56.0
63.0
3.78
4.09
20
14.8
15.4
29 32
225 250
585 650
171 + 185
171 + 185
78Pa in high static pressure
Hermetically sealed scroll compressor
-5.0
43.0
-20.0
15.0
2.1 + 3.9
Painted galvanised steel
Propeller
185 + 185
185 + 185
-5.0
43.0
-20.0
15.0
7.7 + 8.4
R-410A
8.4 + 8.4
Expansion valve (electronic type)
Less than 100 (calculated charge less than 95)
Synthetic (ether) oil
3.9 + 3.9 gas diameter (OD) mm type
12.7 15.9 15.9 diameter (OD) mm 28.6 28.6 28.6 heat insulation Both liquid and gas pipes
Defrost method
Defrost control max. total length m 1,000 1,000 1,000
Sensor for outdoor heat exchanger temperature
Capacity control method controlled
Capacity control [%]
Safety devices
Power supply name
~ 100
W1
~ 100 ~ 100
HPS, fan motor driver overload protector, overcurrent relay, inverter overload protector, PC board fuse
W1 W1 phase 3N~ 3N~ 3N~ frequency voltage
Hz
V
50
400
50
400
50
400
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent systems, each containing less than 95 kg refrigerant charge. For factory charge, refer to the namplate of the unit.
RXYQ22P7W1B
4.04
22
17.0
17.1
35
275
715
1
1
61.5
69.0
3.62
185 + 185
185 + 185
-5.0
43.0
-20.0
15.0
8.4 + 8.6
3.9 + 3.9
15.9
28.6
1,000
~ 100
W1
3N~
50
400
p . 3 5
Combination RXYQ8P7W1B
RXYQ10P7W1B
Nominal capacity
RXYQ12P7W1B cooling heating
COP cooling heating
Capacity range
Power input (nominal) cooling heating
Max n° of indoor units to be connected
Indoor index connection minimum maximum kW kW
HP kW kW
Casing colour material
Fan type air flow rate cooling
(nominal at 230V) heating external static pressure (MAX) Pa m
3
/min m
3
/min
Compressor type
Operation range cooling minimum °CDB maximum °CDB heating charge control minimum °CWB maximum °CWB
Refrigerant type kg
Maximum total refrigerant charge in the system
Refrigerant Oil type
Piping Connections charged volume liquid gas type l kg diameter (OD) mm type
Defrost method diameter (OD) mm heat insulation max. total length m
Defrost control
Capacity control method
Capacity control [%]
Safety devices
Power supply name phase frequency voltage
Hz
V
RXYQ-P RXYQ24P7W1B RXYQ26P7W1B RXYQ28P7W1B RXYQ30P7W1B RXYQ32P7W1B RXYQ34P7W1B RXYQ36P7W1B
3
67.2
75.0
4.02
3.97
24
16.7
2
1
72.8
81.5
3.94
4.20
26
18.5
1
2
78.4
88.0
3.84
4.13
28
20.4
3
84.0
94.5
3.77
4.09
30
22.3
1
2
89.4
100.0
3.60
4.05
32
24.8
1
2
95.0
107.0
3.56
4.02
34
26.7
18.9 19.4 21.3 23.1 24.7 26.6 28.3
39 42 45 48 52 55 58
300
780
325
845
350
910
375
975
400
1,040
425
1,105
450
1,170
3
101.0
113.0
3.49
3.99
36
28.9
Propeller
171 + 171 + 171
171 + 171 + 171
-5.0
43.0
-20.0
15.0
7.7 + 7.7 + 7.7
2.1 + 2.1 + 2.1
15.9
34.9
1,000
~ 100
W1
3N~
50
400
Propeller
171 + 171 + 185
171 + 171 + 185
-5.0
43.0
-20.0
15.0
7.7 + 7.7 + 8.4
2.1 + 2.1 + 3.9
19.1
34.9
1,000
Propeller
171 + 185 + 185
171 + 185 + 185
Daikin White
Painted galvanised steel
Propeller
185 + 185 + 185
185 + 185 + 185
78Pa in high static pressure
Hermetically sealed scroll compressor
-5.0 -5.0
43.0
-20.0
43.0
-20.0
Propeller
171 + 196 + 196
171 + 196 + 196
-5.0
43.0
15.0
7.7 + 8.4 + 8.4
15.0
R-410A
8.6 + 8.6 + 8.6
Expansion valve (electronic type)
-20.0
15.0
7.7 + 8.6 + 8.6
Less than 100 (calculated charge less than 95)
Synthetic (ether) oil
2.1 + 3.9 + 3.9 3.9 + 3.9 + 3.9 2.1 + 3.9 + 3.9
19.1 19.1
34.9
1,000
34.9
Both liquid and gas pipes
1,000
Reversed cycle
19.1
34.9
1,000
~ 100
W1
3N~
50
400
Sensor for outdoor heat exchanger temperature
Inverter controlled
~ 100 ~ 100 ~ 100
HPS, fan motor driver overload protector, overcurrent relay, inverter overload protector, PC board fuse
W1
3N~
50
400
W1
3N~
50
400
W1
3N~
50
400
Propeller
185 + 196 + 196
185 + 196 + 196
-5.0
43.0
-20.0
15.0
8.4 + 8.6 + 8.6
3.9 + 3.9 + 3.9
19.1
34.9
1,000
~ 100
W1
3N~
50
400
Propeller
196 + 196 + 196
196 + 196 + 196
-5.0
43.0
-20.0
15.0
8.6 + 8.6 + 8.6
3.9 + 3.9 + 3.9
19.1
41.3
1,000
~ 100
W1
3N~
50
400
Notes: Nominal cooling capacities are based on : indoor temperature : 27°CDB, 19°CWB, outdoor temperature : 35°CDB, equivalent refrigerant piping : 7.5m, level difference : 0m.
Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 7.5m, level difference : 0m
Sound level of a multi system is determined by the individual outdoor unit and installation condition
The refrigerant charge of the system must be less than 100 kg. This means that in case the calculated refrigerant charge is equal to or more than 95 kg, you must divide your multiple outdoor system into smaller independent systems, each containing less than 95 kg refrigerant charge. For factory charge, refer to the namplate of the unit.
V R V I I I p . 3 6
6
VRVIII HEAT RECOVERY
REYQ-P 8 10 12 14 16 18 20 22 24 26 28
Modules REMQ8P
REMQ10P
REMQ12P
REMQ14P
REMQ16P
Number of outdoor units
Equivalent horsepower
Capacity
Nominal input cooling heating cooling heating
EER
COP cooling heating
Max. number of connectable indoor units
Minimum capacity index
HP kW kW kW kW
Maximum capacity index - 130 %
Capacity steps
Dimensions height width
Weight
Casing
Colour depth mm mm mm kg
Sound pressure level
Sound power level
Fan type air flow rate
Refrigerant
Refrigerant oil name charge control type dB(A) dB(A) kg
Compressor charge type l starting method
Piping connections liquid gas mm mm discharge gas mm pressure equalizer tube mm
Operation range cooling °CDB
Power supply heating
Safety devices
*Information was not available at time of publication
°CWB
W1
1
1
1
1 1
1 1 1 1 1 2 2 2 2 2 2
8 10 12 14 16 18 20 22 24 26 28
22.4 28 33.5 40 45 50.4 55.9 61.5 67.0 73.0 78.5
25 31.5 37.5 45 50 56.5 62.5 69 75 81.5 87.5
4.10
4.30
3.95
4.27
3.69
4.20
3.51
4.10
3.19
3.90
3.88
4.15
3.68
4.08
3.61
4.03
3.49
3.97
3.38
3.96
3.3
3.92
13 16 19 22 26 29 32 35 39 42 45
100 125 150 175 200 225 250 275 300 325 350
260 325 390 455 520 585 650 715 780 845 910
30 37 37 26 26 31 31 38 38 41 41
1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680
1,300 1,300 1,300 1,300 1,300 930 + 930 930 + 930 930 + 930 930 + 930 930 + 1,240 930 + 1,240
765 765 765 765 765 765 765 765 765 765 765
331 331 331 339 339 204 + 254 204 + 254 254 + 254 254 + 254 254 + 334 254 + 334 painted galvanised steel ivory white
58 58 60 62 63 61 62 62 63 62 63
* * * * * 81.0 82.0 82.0 83.0 82.0 83.0
190 190 210 235 240 propeller fan
180 + 185 180 + 200 185 + 200 200 + 200 185 + 230 200 + 230
10.3 10.6 10.8 11.1 11.1
R-410A
8.2 + 9.0 electronic expansion valve synthetic ether oil
8.2 + 9.1 9.0 + 9.1 9.1 + 9.1 9.0 + 11.7 9.1 + 11.7
* * * * * 8.2 hermetically sealed scroll compressor
8.4 10.4 10.6 12.6 12.8
soft start
9.52 9.52 12.7 12.7 12.7 15.9 15.9 15.9 15.9 19.1 19.1
19.1 22.2 28.6 28.6 28.6 28.6 28.6 28.6 34.9 34.9 34.9
15.9 19.1 19.1 22.2 22.2 22.2 28.6 28.6 28.6 28.6 28.6
none
-5 ~ 43 none
-5 ~ 43 none
-5 ~ 43
-20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 none
-5 ~ 43 none
-5 ~ 43
-20 ~ 15.5 -20 ~ 15.5
19.1
-5 ~ 43
-20 ~ 15.5
3~, 50Hz, 380-415V
19.1
-5 ~ 43
19.1
-5 ~ 43
-20 ~ 15.5 -20 ~ 15.5
19.1
-5 ~ 43
-20 ~ 15.5
19.1
-5 ~ 43
19.1
-5 ~ 43
-20 ~ 15.5 -20 ~ 15.5
HPS, fan motor overcurrent protector, inverter overload protector, overcurrent relay, PC board fuse
O u t d o o r U n i t s p . 3 7
REYQ-P 30 32 34 36 38 40 42 44 46 48
Modules REMQ8P 1 1
REMQ10P
REMQ12P
1 1 1
1 1 2 1
REMQ14P 1 1
REMQ16P 1 2 1 1 1 1 2 2 2 3
Number of outdoor units
Equivalent horsepower HP
2 2 3 3 3 3 3 3 3 3
30 32 34 36 38 40 42 44 46 48
Capacity cooling kW 85.0 90.0 95.4 101.0 107.0 112.0 118.0 124.0 130.0 135.0
heating kW 95 100 107 113 119 125 132 138 145 150
Nominal input cooling heating kW kW
26.6
24.2
28.4
25.8
27.2
26.5
29.4
28.2
31.2
30.0
33.4
31.8
35.8
33.5
38.0
35.2
40.8
37.1
42.6
38.7
EER cooling 3.2 3.17 3.51 3.43 3.43 3.35 3.3 3.26 3.19 3.17
COP heating 3.93 3.88 4.04 4.01 3.97 3.93 3.94 3.92 3.91 3.88
Max. number of connectable indoor units
Minimum capacity index
48 52 55 58 61 64 64 64 64 64
375 400 425 450 475 500 525 550 575 600
Maximum capacity index - 130 % 975 1,040 1,105 1,170 1,235 1,300 1,365 1,430 1,495 1,560
Capacity steps 46 46 36 36 41 41 46 46 51 51
Dimensions height width mm mm
1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680 1,680
1,240 + 1,240 1,240 + 1,240 930 + 930 + 1,240 930 + 930 + 1,240 930 + 930 + 1,240 930 + 930 + 1,240 930 + 1,240 + 1,240 930 + 1,240 + 1,240 1,240 + 1,240 + 1,240 1,240 + 1,240 + 1,240 depth mm 765 765 765 765 765 765 765 765 765 765
Weight kg 334 + 334 334 + 334 204 + 254 + 334 204 + 254 + 334 254 + 254 + 334 254 + 254 + 334 254 + 334 + 334 254 + 334 + 334 334 + 334 + 334 334 + 334 + 334
Casing
Colour painted galvanised steel
Sound pressure level dB(A) 63 63 63 64 64 65 64 65 65 65
Sound power level dB(A) 83.0 83.0 83.0 84.0 84.0 85.0 84.0 85.0 85.0 85.0
Fan type air flow rate 230 + 230 230 + 230 180 + 185 + 230 180 + 200 + 230 185 + 200 + 230 200 + 200 + 230 185 + 230 + 230 200 + 230 + 230 230 + 230 + 230 230 + 230 + 230
Refrigerant name R-410A charge kg 11.7 + 11.7 11.7 + 11.7 8.2 + 9.0 + 11.7 8.2 + 9.1 + 11.7 9.0 + 9.1 + 11.7 9.1 + 9.1 + 11.7 9.0 + 11.7 + 11.7 9.1 + 11.7 + 11.7 11.7 + 11.7 + 11.7 11.7 + 11.7 + 11.7
Refrigerant oil control type electronic expansion valve synthetic ether oil charge l 14.9 15.0 15.7 15.9 17.9 18.1 20.1 20.3
Compressor type hermetically sealed scroll compressor starting method
Piping connections liquid mm 19.1 19.1 19.1 19.1 19.1 19.1 19.1 19.1 gas mm 34.9 34.9 34.9 41.3 41.3 41.3 41.3 41.3 discharge gas mm 28.6 28.6 28.6 28.6 34.9 34.9 34.9 34.9 pressure equalizer tube mm
Operation range cooling °CDB
19.1
-5 ~ 43
19.1
-5 ~ 43
19.1
-5 ~ 43
19.1
-5 ~ 43
19.1
-5 ~ 43
19.1
-5 ~ 43
19.1
-5 ~ 43 heating °CWB -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5 -20 ~ 15.5
Power supply W1 3~, 50Hz, 380-415V
Safety devices HPS, fan motor overcurrent protector, inverter overload protector, overcurrent relay, PC board fuse
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m • level difference: 0m
• Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB/6°CWB • equivalent refrigerant piping: 7.5m • level difference: 0m
19.1
-5 ~ 43
-20 ~ 15.5
22.4
19.1
41.3
34.9
19.1
-5 ~ 43
-20 ~ 15.5
22.5
19.1
41.3
34.9
19.1
-5 ~ 43
-20 ~ 15.5
p . 3 8
2. VRV-WII
1
VRV-WII Technology
1
Reluctance Brushless DC Compressor
9
The reluctance brushless DC motor provides significant increases in efficiency compared to conventional AC inverter motors, simultaneously using 2 different forms of torque (normal and reluctance torque) to produce extra power from small electric currents.
9
High thrust mechanism
By introducing high pressure oil, the reactive force from the fixed scroll is added to the internal force, thereby reducing thrust losses.
This results in improved efficiency and suppressed sound level
9 The motor comprises powerful neodymium magnets, that create the reluctance torque.
These magnets are approximately 12 times stronger than ferrite magnets and make a major contribution to its energy saving characteristics.
Ferrite magnet
Neodymium magnet
Iron
Low pressure side
Neodymium
Magnet
S N
S
N
N
S
N S
N
S
Suction
Scroll
Discharge
Rotating
Stator
Field
“Normal” torque
Reluctance torque
High pressure side
Reluctance
DC Motor
2
Sine Wave DC Inverter
Optimizing the sine wave curve, results in smoother motor rotation and improved motor efficiency.
3
i-Demand Function
The newly introduced current sensor minimizes the difference between the actual power consumption and the predefined power consumption.
16:00
Time
p . 3 9
O u t d o o r U n i t s
2
VRV-WII HEAT PUMP / HEAT RECOVERY
HEAT PUMP HEAT RECOVERY
VRV-WII RWEYQ10M RWEYQ20M RWEYQ30M RWEYQ10M RWEYQ20M RWEYQ30M
Nominal cooling capacity
Nominal heating capacity
Capacity range
Power input (nominal)
COP
Max n° of indoor units to be connected
Minimum capacity index
Maximum capacity index
Power supply
Dimensions height
Weight width depth
Colour
Sound pressure levels
Sound power levels
Fan type cooling heating cooling heating
Refrigerant
Refrigerant Oil
Compressor
Piping Connections
Safety devices air flow rate (nominal) name charge control type charged volume quantity type starting method liquid discharge gas gas l kW kW
HP kW kW
Y1 mm mm mm kg dBA dBA m kg
3 mm mm mm
/min
26.70 53.40 80.10 26.70 53.40 80.10
31.50 63.00 94.50 31.50 63.00 94.50
10 20 30 10 20 30
6.03 12.10 18.10 6.03 12.10 18.10
6.05 12.10 18.20 6.05 12.10 18.20
4.43 4.41 4.43 4.43 4.41 4.43
5.21 5.21 5.19 5.21 5.21 5.19
16 20 32 16 20 32
125 250 375 125 250 375
325 650 975 325 650 975
1,000
780
550
150
3~, 50Hz, 380-415V
*
*
*
Ivory white (5Y7,5/1)
*
*
*
150+150 150+150+150
1,000
780
550
150
3~, 50Hz, 380-415V
*
*
*
*
*
*
150+150 150+150+150
Ivory white (5Y7,5/1)
51.0 54.0 56.0 51.0 54.0 56.0
** ** ** ** ** **
-
** ** ** ** ** **
** ** ** ** ** **
5.2
** ** ** ** ** **
1 2 3 1 2 3
9.52 (flare)
22.2 (brazing)
R-410A
5.2+5.2
Expansion valve (electronic type)
Synthetic (ether) oil
Hermetically sealed scroll compressor
Soft start
15.9 (flare)
28.6 (brazing)
-
HPS, inverter overload protector, fusible plugs
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • inlet water temperature: 30°C • equivalent refrigerant piping: 7.5m • level difference: 0m
• Nominal heating capacities are based on: indoor temperature: 20°CDB • inlet water temperature: 20°C • equivalent refrigerant piping: 7.5m • level difference: 0m
• This unit should not be installed outdoors, but indoors eg. in a machine room, etc.
• Indoor operating ambient temperature: 0 ~ 40°C. Heat rejection from the outdoor unit: 0,71kW/10HP
• *Dimensions of 20HP and 30HP units depend on the method of stacking
• **Data were not available at the time of publication
5.2+5.2+5.2
19.1 (flare)
34.9 (brazing)
-
5.2
9.52 (flare)
19.1 (brazing)
R-410A
5.2+5.2
Expansion valve (electronic type)
Synthetic (ether) oil
Hermetically sealed scroll compressor
Soft start
15.9 (flare)
22.2 (brazing)
22.2 (brazing) 28.6 (brazing)
HPS, inverter overload protector, fusible plugs
5.2+5.2+5.2
19.1 (flare)
28.6 (brazing)
34.9 (brazing)
p . 4 0
3. ACCESSORIES
VRVIII COOLING ONLY
Fixing box
REFNET header
REFNET joint
Central drain pan kit
Digital pressure gauge kit
Increase height difference between indoor & outdoor to 90m (see note 2)
1 All options are kits
2 The option should be installed inside the outdoor unit
VRVIII HEAT PUMP
Cool/heat selector
Fixing box
REFNET header
REFNET joint
Outdoor unit multi connection kit for 2 outdoor units
Outdoor unit multi connection kit for 3 outdoor units
Central drain pan kit
Digital pressure gange kit
Increase height difference between indoor & outdoor to 90m (see note 5)
1 All options are kits
2 Central drain pan kit shall be combined based on the outdoor unit combination table
3 Only 1 option per installation is needed
4 1 option per module is required
5 The option should be installed inside the outdoor unit
RXQ5P RXQ8-10P RXQ12P RXQ14-18PA
KJB111A
KHRQ22M29H KHRQ22M29H KHRQ22M29H KHRQ22M29H
- - KHRQ22M64H KHRQ22M64H
KHRQ22M20T KHRQ22M20T KHRQ22M20T KHRQ22M20T
- KHRQ22M29T KHRQ22M29T KHRQ22M29T
- - KHRQ22M64T KHRQ22M64T
KWC26B160 KWC26B280 KWC26B280 KWC26B450
BHGP26A1 BHGP26A1 BHGP26A1 BHGP26A1
- EKLD90P12 EKLD90P12 EKLD90P18
RXYQ5P
KHRQ22M29H
-
-
KHRQ22M20T
-
-
-
-
-
KWC26B160
BHGP26A1
-
RXYQ8-10P RXYQ12P RXYQ14-18PA RXYQ20-54P
KHRQ22M29H
-
-
KHRQ22M20T
KHRQ22M29T
-
-
-
KWC26B280
BHGP26A1
EKLD90P12
KKRC19-26A6
KJB111A
KHRQ22M29H KHRQ22M29H
KHRQ22M64H
-
KHRQ22M20T
KHRQ22M29T
KHRQ22M64H
-
KHRQ22M20T
KHRQ22M29T
KHRQ22M64T
-
-
-
KHRQ22M64T
-
-
KWC26B280
BHGP26A1
KWC26B450
BHGP26A1
EKLD90P12 EKLD90P18
KHRQ22M29H
KHRQ22M64H
KHRQ22M75H
KHRQ22M20T
KHRQ22M29T
KHRQ22M64T
KHRQ22M75T
BHFQ22P1007
BHFQ22P1517 see note 2 see note 3
p . 4 1
O u t d o o r U n i t s
VRVIII HEAT RECOVERY
REFNET header
REFNET joint
Outdoor unit multi piping connection kit
Central drain pan kit
REYQ8P REYQ10-16P REYQ18P REYQ20-24P REYQ26-28P REYQ30-32P REYQ34-40P REYQ42-44P REYQ46-48P
KHRP25M33H KHRP25M33H KHRP25M33H KHRP25M33H KHRP25M33H KHRP25M33H KHRP25M33H KHRP25M33H KHRP25M33H
-
-
KHRP25M72H KHRP25M72H KHRP25M72H KHRP25M72H KHRP25M72H KHRP25M72H KHRP25M72H KHRP25M72H
- KHRP25M73H KHRP25M73H KHRP25M73H KHRP25M73H KHRP25M73H KHRP25M73H KHRP25M73H
KHRP25A22T KHRP25A22T KHRP25A22T KHRP25A22T KHRP25A22T KHRP25A22T KHRP25A22T KHRP25A22T KHRP25A22T
KHRP25A33T KHRP25A33T KHRP25A33T KHRP25A33T KHRP25A33T KHRP25A33T KHRP25A33T KHRP25A33T KHRP25A33T
- KHRP25A72T KHRP25A72T KHRP25A72T KHRP25A72T KHRP25A72T KHRP25A72T KHRP25A72T KHRP25A72T
- KHRP25M72TP KHRP25M72TP KHRP25M72TP KHRP25M72TP KHRP25M72TP KHRP25M72TP KHRP25M72TP KHRP25M72TP
-
-
-
KWC25C450
-
-
-
- KHRP25A73T KHRP25A73T KHRP25A73T KHRP25A73T KHRP25A73T KHRP25A73T
- KHRP25M73TP KHRP25M73TP KHRP25M73TP KHRP25M73TP KHRP25M73TP KHRP25M73TP
- BHFP26A90 BHFP26A90 BHFP26A90 BHFP26A90 BHFP26A136 BHFP26A136 BHFP26A136
KWC25C450 - - KWC26C450 KWC26C450 x 2 KWC26C450 KWC26C450 x 2 KWC26C450 x 3
- KWC26C280 x 2 KWC26C280 x 2 KWC26C280 - KWC26C280 x 2 KWC26C280 -
VRV-WII HEAT PUMP
Cool/heat selector
Fixing box
REFNET header
REFNET joint
Outdoor unit multi piping connection kit
Strainer kit
External control adapter for outdoor unit
RWEYQ10M RWEYQ20M RWEYQ30M
KRC19-26A
KJB111A
KHRQ22M29H
-
-
KHRQ22M20T
KHRQ22M29H
KHRQ22M64H
KHRQ22M75H
KHRQ22M20T
KHRQ22M29H
KHRQ22M64H
KHRQ22M75H
KHRQ22M20T
KHRQ22M29T
-
-
-
KHRQ22M29T
KHRQ22M64T
KHRQ22M75T
BHFP22MA56
DTA104A62
KHRQ22M29T
KHRQ22M64T
KHRQ22M75T
BHFP22MA84
VRV-WII HEAT RECOVERY
Fixing box
REFNET header
REFNET joint
Outdoor unit multi piping connection kit
Strainer kit
External control adapter for outdoor unit
RWEYQ10M RWEYQ20M RWEYQ30M
KJB111A
KHRQ23M29H
-
KHRQ23M29H
KHRQ23M64H
KHRQ23M29H
KHRQ23M64H
-
KHRQ23M20T
KHRQ23M29T
-
KHRQ23M75H
KHRQ23M20T
KHRQ23M29T
KHRQ23M64T
KHRQ23M75H
KHRQ23M20T
KHRQ23M29T
KHRQ23M64T
-
-
KHRQ23M75T
BHFP26MA56
DTA104A62
KHRQ23M75T
BHFP26MA84
BS BOX
Total capacity of connectable indoor units
Maximum number of connectable indoor units
Casing
Dimensions HxWxD
Weight
Piping connections indoor unit outdoor unit liquid/gas liquid/suction gas/discharge gas
Safety devices
Cool/heat selector
Fixing box mm kg mm mm
BSVQ100PV1 x ≤ 100
5
14
9.5/15.9
9.5/15.9/12.7
BSVQ160PV1
100 < x ≤ 160
8 galvanised steel plate
207x388x326
14
9.5/15.9
9.5/15.9/12.7
KRC19-26A
KJB111A
BSVQ250PV1
160 < x ≤ 250
5
15
9.5/22.2
9.5/22.2/19.1
p . 4 2
Indoor Units
1. F
EATURES
FXFQ-P
20-25-32-40-50-63-
80-100-125
C
OMFORT
9 Modern style decoration panel in white (RAL9010)
9 360° air discharge ensures uniform air flow and temperature distribution
9
Air discharge from the corners avoids dead zones that may be subject to temperature differences
9 Comfortable horizontal air discharge ensures draughtfree operation and prevents ceiling soiling
9 23 different air flow patterns possible
9
Fresh air intake: up to 20%
F LEXIBLE INSTALLATION AND EASY
MAINTENANCE
9 Reduced installation height: 214mm for class 20-63
9
Easy visible drain check thanks to clear drain socket
9 Drain-up pump with 850 mm lift fitted as standard
E XAMPLES OF A IRFLOW P ATTERNS
850 mm
360° Round Flow 4-Way Flow 3-Way Flow 2-Way Flow
FXZQ-M8
20-25-32-40-50
C OMFORT
9 Modern style decoration panel in white (RAL9010)
9 Extremely quiet in operation
9 Excellent low draught characteristics. Since the flaps can move to a 0° position, virtually no draught can be experienced
Ceiling void is 295 mm
0°
60°
9
Any one of 5 different air flow patterns can be freely selected between 0° and 60° and will then be maintained during the operational cycle of the air conditioner
F
LEXIBLE
I
NSTALLATION AND
E
ASY
M
AINTENANCE
9 Thanks to the compact casing, it matches standard architectural modules of 600 x 600mm, therefore ceiling tile cutting is no longer necessary
9
Air can be discharged in any of 4 directions.
9 Possibility to shut 1 or 2 flaps for easy installation in corners
9 Since the switch box is located within the unit, it is easy to access from below for maintenance without removing ceiling tiles
9 Drain-up pump with 500mm lift fitted as standard
500mm
p . 4 3
C
OMFORT
9 Quiet in operation
9 Leaves maximum floor and wall space for furniture, decorations and fittings
9 Automatic air flow director ensures uniform air flow and temperature distribution
9
Anti-ceiling soiling technology
F ILTER
9 Standard long life filter
F
LEXIBLE
I
NSTALLATION AND
E
ASY
M
AINTENANCE
9 Easy installation in false ceilings of only 355mm minimum ceiling height is 355mm
9 Drain-up pump with 600mm lift fitted as standard
600mm
9 Maintenance can be performed by simply removing the front panel
9 Easy to clean flat suction grille
9 Detachable swing flaps
FXCQ-M8
20-25-32-40-50-63-
80-125
C OMFORT
9
Equipped with special draught prevention and anti-ceiling soiling technology
9 Automatic air flow director ensures uniform air flow and temperature distribution
1
Standard
2
Draught prevention
Note: Standard setting when shipped.
3
Anti-ceiling soiling technology
9 Air flow by either downward air discharge, frontal discharge or a combination of both
Downward discharge Frontal discharge Combination
FXKQ-MA
20-32-40-63
Closed by the decoration panel
F
LEXIBLE
I
NSTALLATION
9 Compact dimensions, can easily be mounted in a narrow ceiling void (only 220mm ceiling space required, 195 with panel spacer, available as accessory)
9 Drain-up pump with 500mm lift fitted as standard
Min. 195 mm
20 mm
Panel spacer
500 mm
p . 4 4
FXDQ-M8
20-25
C
OMFORT
9 Designed for hotel bedrooms
9 Blends unobtrusively with any interior décor: only the suction and discharge grilles are visible
9
E xtremely quiet in operation
F ILTER
9 Air suction filter fitted as standard
F
LEXIBLE
I
NSTALLATION
9 Compact dimensions (230mm high & 652mm deep), can easily be mounted in a ceiling void
9
The air suction direction can be altered from rear to bottom suction
9 For easy mounting, the drain pan can be located to the left or the right of the unit
FXDQ-P/NA
20-25-32-40-50-63
C
OMFORT
9 Quiet in operation
9 Blends unobtrusively with any interior décor
9
Leaves maximum floor and wall space for furniture, decorations and fittings
F LEXIBLE I NSTALLATION
9 Slim design, can easily be mounted in a ceiling void of only 240mm
200mm Air filter
Suction Chamber
[Duct connection]
9 Can be installed in both new and existing buildings
9 Medium external static pressure facilitates unit use with flexible ducts of varying lengths
9
Drain-up pump with 750mm lift fitted as standard
Ceiling
i n d o o r u n i t s p . 4 5
C
OMFORT
9 High flexibility for a wide variety of applications
9 Quiet in operation
9 Blends unobtrusively with any interior décor
F ILTER
9 Long life filter fitted as standard
9
High efficiency filters (65% and 95%) available as accessory
F LEXIBLE I NSTALLATION AND E ASY M AINTENANCE
9
High external static pressure facilitates unit use with flexible ducts of varying lengths
9 When using suction panel, unit requires only
350mm of ceiling space
Min.
350mm
9
Drain-up pump with 625mm lift fitted as standard
9 The air suction direction can be altered from rear to bottom suction
9
The switch box can be reached from the side or from the bottom side of the unit for easy servicing
625mm
FXSQ-M8
20-25-32-40-50-63-
80-100-125
C OMFORT
9
Leaves maximum floor and wall space for furniture, decorations and fittings
F LEXIBLE I NSTALLATION
9
More than 150 Pa external static pressure allows extensive ductwork runs and flexible application: ideal for use in large areas
9 Drain-up pump with 750mm lift available as accessory for class 40-125
FXMQ-MA
40-50-63-80-100-125
200-250
390mm
Min.
450mm
750mm
120mm
9 External static pressure can be easily adjusted using a change-over switch inside the electrical box to meet the resistance in the duct system
9
Built-in drain pump (accessory): housing the drain pump inside the unit (class 200 & 250) has reduced the required installation space
470mm
without drain pump
Min.
530mm
470mm
with drain pump
0 - 250mm
222mm
p . 4 6
FXAQ-MA
20-25-32-40-50-63
C
OMFORT
9 Compact and stylish design blends unobtrusively in any interior décor
9 Automatic air flow director ensures efficient air distribution via louvers that close automatically when the unit is switched off
9
5 different discharge angles can be programmed via the remote control
9 Discharge angle automatically returns to its previous position on restart (initial setting 10 degrees for cooling and 70 degrees for heating)
10°
25°
40°
55°70°
F
ILTER
9 Mildew proof polystyrene filter and drain pan
F
LEXIBLE
I
NSTALLATION AND
E
ASY
M
AINTANCE
9 Both horizontal flaps and front panel can easily be removed and washed
9 All maintenance operations can be carried out from the front of the unit
9 Drain-up pump with 1,000mm lift available as accessory
9 Drain pipe can be fitted either to the left or right side of the unit
Height of drain-up
10° Cooling
70° Heating
1,000mm
Indoor unit
Drain-up kit
Drain-up kit
FXHQ-MA
32-63-100
C
OMFORT
9 Quiet in operation
9 Leaves maximum floor and wall space for furniture, decorations and fittings
9 Enhanced horizontal and vertical air circulation in all directions thanks to an air flow pattern of 100°
F
ILTER
9 Long life filter fitted as standard
F
LEXIBLE
I
NSTALLATION AND
E
ASY
M
AINTENANCE
9 Can be installed in both new and existing buildings
9 The ideal solution for installation without false ceilings
9 Drain-up pump with 600mm lift available as accessory
9 Maintenance can be performed easily from below the unit
9 Bristle free flap makes cleaning easier
100°
Drain-up kit
(built inside main unit)
p . 4 7 i n d o o r u n i t s
C
OMFORT
9 Group control with other VRV indoor units possible
9 Cool heat selection
9 Prevention of cold draught at hot start, defrost and oil return in heating
9
Air can be discharged in any of 4 directions
9 Air can be discharged at 5 different angles between 0 and 60 degrees
9 Automatic air flow director ensures efficient air and temperature distribution.
9 Air flow distribution for ceiling heights up to 3.5m without loss of capacity.
F ILTER
9 Air filter, drain pan and heat exchanger fin are mildew proof and
F LEXIBLE I NSTALLATION
9
Ideal for installation in new and existing buildings
9 5m maximum distance between FXUQ unit and junction box
9 Possibility to shut 1 or 2 flaps for easy installation in corners
FXUQ-MA
71-100-125
9 Drain-up pump with 500mm lift fitted as standard
p . 4 8
FXLQ-MA
20-25-32-40-50-63
C
OMFORT
9 Ideal for installation beneath a window
9 Compact dimensions (only 222mm deep and 600mm high)
9 All models are available with remote control
F ILTER
9 Long life filter fitted as standard
F
LEXIBLE
I
NSTALLATION
& E
ASY
M
AINTENANCE
9 Running the pipes from connections at the back, enables the unit to be wall mounted
Wall mounted Floor standing
9 On site connection during installation is easier
9 The fibreless discharge grille prevents condensation and staining
FXNQ-MA
20-25-32-40-50-63
C
OMFORT
9 Ideal for perimeter air conditioning
9 Ideal for installation below a window
9
All models are available with remote control
F ILTER
9
Long life filter fitted as standard
F LEXIBLE I NSTALLATION
9
On site connection during installation is easier
9 The connecting port faces downward, eliminating the need to attach
Connecting port
Refrigerant piping
2. S
PECIFICATIONS
FXFQ-P
p . 4 9
R o u n d f l o w c e i l i n g m o u n t e d c a s s e t t e
FXFQ-P
Capacity
Power input
Dimensions
Weight
Casing
Air Flow Rate cooling heating
Sound power (nominal) cooling
Sound pressure cooling
Refrigerant heating name cooling heating cooling heating
(H x W x D) unit
Power Supply
Piping Connections
Air Filter
Drain-up Height
L/G/D
Decoration Panel model colour
(H x W x D) weight high/low high/low high/low high/low diameter kW kW kW kW mm kg m3/min m3/min dBA dBA dBA mm mm mm kg
20
2.2
2.5
6.35/12.7/32
25
2.8
3.2
0.053
0.045
12.5/9.0
12.5/9.0
49
31/28
31/28
20.0
32
3.6
4.0
204x840x840
4.5
5.0
0.063
0.055
6.4/12.7/32
40
13.5/9.0
13.5/9.0
50
32/28
32/28
50
5.6
6.3
0.083
0.067
Galvanised steel
15.5/10.0
15.0/9.5
51
50x950x950
5.5
Notes: • The sound pressure values are mentioned for a unit installed with rear suction
• The sound power level is an absolute value indicating the power wich a sound source generates.
• Nominal cooling capacities are based on : indoor temperature : 270CDB, 190CWB, outdoor temperature : 350CDB, equivalent refrigerant piping : 5m, level difference : 0m.
• Nominal heating capacities are based on : indoor temperature : 20°CDB, outdoor temperature : 7°CDB, 6°CWB, equivalent refrigerant piping : 5m, level difference : 0m.
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
21.0
33/28
33/28
R-410A
1~ / 220-240V / 50Hz
Resin net with mold resistance
750
BYCQ140CW1
RAL9010
16.5/11.0
17.5/12.0
52
34/29
36/30
63
7.1
8.0
0.095
0.114
A C C E S S O R I E S
FXFQ-P
Wired remote control
Infrared remote control
Decoration panel
Replacement long life filter (non-woven type) cooling only heat pump
Fresh air intake kit (20 % fresh air intake) (chamber type)
Air discharge outlet sealing member
20 25 32 40
BRC1D52
BRC7F533F
BRC7F532F
BYCQ140CW1
KAFP551K160
KDDQ5C140
KDBHQ55C140
50 63
23.5/14.5
23.5/14.5
55
38/32
38/32
80 100
9.0
10.0
0.120
0.108
246x840x840
24.0
11.2
12.5
0.173
0.176
26.5/17.0
28.0/17.5
58
41/33
42/34
9.5/15.9/32
80
125
14.0
16.0
0.258
0.246
288x840x840
26.0
33.0/20.0
33.0/20.0
61
44/34
44/34
125
p . 5 0
FXZQ-M8
4 - w a y b l o w c e i l i n g m o u n t e d c a s s e t t e ( 6 0 0 m m x 6 0 0 m m )
FXZQ-M8 20 25 32 40 50
Cooling capacity
Heating capacity
Nominal input cooling
heating
Dimensions (HxWxD)
Weight
Casing
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Piping connections
Air filter
Drain-up height liquid/gas
Power supply
Decoration panel dimensions (HxWxD)
weight
colour kW kW
W
W mm kg m
3 dB(A) dB(A) mm mm
V1 mm kg
/min
2.2 2.8 3.6 4.5 5.6
2.5
73
64
9.0/7.0
30/25
47
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent piping length: 7.5m (horizontal)
• Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent piping length: 7.5m (horizontal)
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat
3.2
73
64
9.0/7.0
30/25
47
4.0
76
68
286x575x575
18 galvanised steel plate
9.5/7.5
32/26
49
R-410A
ø6.4/ø12.7
resin net with mold resistant
500
1~, 50Hz, 220-240V
55x700x700
2.7 white (RAL 9010)
5.0
89
80
11.0/8.0
36/28
53
6.3
115
107
14.0/10.0
41/33
58
A C C E S S O R I E S
FXZQ-M8
Wired remote control
Infrared remote control
Decoration panel
Sealing member of air discharge outlet
Panel spacer
Replacement long life filter
Fresh air intake kit cooling only heat pump direct installation type
20 25 32
BRC1D52
BRC7E531
BRC7E530
BYFQ60B
KDBH44B60
KDBQ44B60
KAFQ441B60
KDDQ44X60
40 50
FXCQ-M8
p . 5 1
2 - w a y b l o w c e i l i n g m o u n t e d c a s s e t t e
FXCQ-M8 20 25 32 40 50 63 80 125
Cooling capacity
Heating capacity
Nominal input
Dimensions (HxWxD) cooling
heating
Weight
Casing
Air flow rate (H/L) kW kW
W
W mm kg m
3
/min
2.2 2.8 3.6 4.5
2.5
77 92 92 130
44
3.2
59
4.0
59
305x780x600
5.6 7.1 9.0
5.0 6.3
97 97
8.0
126
14.0
10.0 16.0
130 161 209 256
176 223
26 31 32 35 47
7/5 9/6.5 9/6.5
galvanised steel plate
12/9 12/9 16.5/13
48
26/21 33/25
Sound pressure level (H/L)
Sound power level
Refrigerant type
Piping connections
Air filter
Drain-up height
Power supply
Decoration panel liquid/gas dimensions (HxWxD)
weight
colour dB(A) dB(A) mm mm
V3 mm kg
33/28 35/29 35/29 35.5/30.5 35.5/30.5
45 50 50 50
R-410A
38/33 40/35 45/39
50 52 54 60
53x1,030x680
ø6.4/ø12.7
8
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 8m • level difference: 0m
• Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 8m • level difference: 0m
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat
resin net with mold resistant
600
1~, 50Hz, 230V
8.5 9.5
ø9.5/ø15.9
12
A C C E S S O R I E S
FXCQ-M8
Wired remote control
Infrared remote control cooling only
Decoration panel
High efficiency filter 65% *1
High efficiency filter 90% *1
Filter chamber for bottom suction
Replacement long life filter
Note: *1. Filter chamber is required when installing a high efficiency filter
20 25 32 40 50 63 80 125
BYBC32G
KAFJ532G36
KAFJ533G36
KDDFJ53G36
KAFJ531G36
BRC1D52
BRC7C67
BRC7C62
BYBC50G BYBC63G BYBC125G
p . 5 2
FXKQ-MA
C e i l i n g m o u n t e d c o r n e r c a s s e t t e
FXKQ-MA
Cooling capacity
Heating capacity
Nominal input cooling
heating
Dimensions (HxWxD)
Weight
Casing
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Piping connections
Air filter
Drain-up height
Power supply
Decoration panel liquid/gas dimensions (HxWxD)
weight
colour kW kW
W
W mm kg m
3
/min dB(A) dB(A) mm mm
VE mm kg
25 32 40 63
2.8 3.6 4.5 7.1
3.2
66
4.0 5.0
66 76
8.0
105
46 46 56
215x1,110x710
31 galvanised steel plate
85
215x1,310x710
34
11/9
38/33
*
11/9 13/10
38/33 40/34
* *
R-410A
ø6.4/ø12.7 resin net with mold resistant
500
1~, 50Hz, 220-240V
18/15
42/37
*
ø9.5/ø15.9
70x1,240x800
8.5 white
70x1,440x800
9.5
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m (horizontal)
• Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 7.5m (horizontal)
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat
• *Data were not available at time of publication
A C C E S S O R I E S
FXKQ-MA
Wired remote control
Infrared remote control
Decoration panel
Panel spacer
Replacement long life filter
Air discharge grille
Air discharge blind panel
Flexible duct (with shutter) cooling only heat pump
25 32 40
BRC1D52
BRC4C63
BRC4C61
BYK45F
KPBJ52F56
KAFJ521F56
K-HV7AW
KDBJ52F56W
KFDJ52F56
63
BYK71F
KPBJ52F80
KAFJ521F80
K-HV9AW
KDBJ52F80W
KFDJ52F80
FXDQ-M8
p . 5 3
S m a l l c o n c e a l e d c e i l i n g u n i t
FXDQ-M8
Cooling capacity
Heating capacity
Nominal input cooling
heating
W
W kW kW
2.2 2.8
Dimensions (HxWxD)
Weight
Casing
Air flow rate (H/L) mm kg
Sound pressure level (H/L)
Sound power level m
3
/min dB(A) dB(A)
Refrigerant type
Piping connections liquid/gas mm
Air filter
Power supply V3
Notes : • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 8m • level difference : 0m
• Nominal heating capacities are based on: indoor air temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 8m • level difference : 0m
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
50
50
230x502x652
17 galvanised steel plate
37/32
50
R-410A
ø6.4/ø12.7
resin net with mold resistant
1~, 50Hz, 230V
A C C E S S O R I E S
FXDQ-M8
Wired remote control
Infrared remote control cooling heating
20
BRC1D52, BRC2C51, BRC3A61
BRC4C64
BRC4C62
25
p . 5 4
FXDQ-P/NA
S l i m c o n c e a l e d c e i l i n g u n i t
FXDQ-P/NA FXDQ20P FXDQ25P FXDQ32P FXDQ40NA FXDQ50NA FXDQ63NA
Cooling capacity
Heating capacity kW kW
2.2 2.8 3.6 4.5 5.6 7.1
2.5 3.2 4.0 5.0 6.3 8.0
Nominal input cooling heating
W
W
86
67
86
67
Dimensions (HxWxD)
Weight mm kg 23
Casing
Air flow rate (H/L)
Sound pressure level (H/L)
Sound power level m
3
/min dB(A) dB(A)
8.0/6.4
33/29
*
Refrigerant type
Drain-up height
Piping connections
Air filter liquid/gas mm mm
Power supply VE
Notes: • Nominal cooling capacities are based on: • Indoor temperature: 27°CDB, 19°CWB • Outdoor temperature: 35°CDB • Equivalent piping length: 7.5m (horizontal)
• Nominal heating capacities are based on: • Indoor temperature: 20°CDB • Outdoor temperature: 7°CDB, 6°CWB • Equivalent piping length: 7.5m (horizontal)
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat
• The sound pressure values are mentioned for a unit installed with rear suction
• * Data were not available at time of publication
200x700x620
23
8.0/6.4
33/29
*
89 160
70 70
23 27
8.0/6.4 10.5/8.5
33/29 34/30
* *
R-410A
ø6.4/ø12.7 plate removable, washable, mildew proof
1~, 50Hz, 220-240V
200x900x620
750
165
152
28
12.5/10.0
35/31
*
181
168
200x1,100x620
31
16.5/13.0
36/32
*
ø9.5/ø15.9
A C C E S S O R I E S
FXDQ-P/NA
Wired remote control
Infrared remote control cooling only heat pump
FXDQ20P FXDQ25P FXDQ32P FXDQ40NA FXDQ50NA FXDQ63NA
BRC1D52
BRC4C64
BRC4C62
p . 5 5
FXSQ-M8
C o n c e a l e d c e i l i n g u n i t
FXSQ-M8
Cooling capacity
Heating capacity
Nominal input cooling
Dimensions (HxWxD)
Weight
Casing
Air flow rate (H/L)
Sound pressure level (H/L)
Sound power level
Refrigerant type
Piping connections
Air filter
Drain-up height
Power supply
Decoration panel liquid/gas dimensions (HxWxD)
colour kW kW
W mm kg m
3 mm
V3 mm
/min dB(A) dB(A) mm
20 25 32 40 50 63 80 100 125
2.2 2.8 3.6 4.5 14.0
2.5
110
3.2
110
4.0
114
90 90 94
300x550x800
5.0 6.3
127 143
107 123
8.0
189
169
10.0
234
214
12.5 16.0
242 321
222 301
30
9/6.5
32/28
50
30
9/6.5
32/28
50
30
9.5/7
33/28
51
ø6.4/ø12.7
55x650x500
3
30 31 resin net with mold resistant
625
1~, 50Hz, 230V
3.5
41
56 58 56
R-410A
4.5
51
55
51 52
11.5/9 15/11 21/15.5 27/20 28/20.5 38/28
33/29 35/31 35/30 37/31 38/33 40/35
56 65
ø9.5/ø15.9
6.5
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 8m • level difference: Om
• Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 8m • level difference: Om
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat
• The sound pressure values are mentioned for a unit installed with rear suction
A C C E S S O R I E S
FXSQ-M8
Wired remote control
Infrared remote control cooling only
Decoration panel
Service access panel
High efficiency filter 65% *1
High efficiency filter 90% *1
Filter chamber for bottom suction
Filter chamber rear suction
Air suction canvas
Screening door/blind board
Air discharge adapter for round duct
Notes: • *1. If installing a high efficiency filter in the unit, an assembly chamber for either bottom or rear suction is required.
20 25 32
BYBS32D
KTBJ25K36W
KAFJ252L36
KAFJ253L36
KAJ25L36D
KAJ25L36B
KSA-25K36
KBBJ25K36
KDAJ25K36
40 50 63 80 100 125
BRC1D52, BRC2C51, BRC3A61
BRC4C64
BRC4C62
BYBS45D BYB571D BYBS125D
p . 5 6
FXMQ-MA
L a r g e c o n c e a l e d c e i l i n g u n i t
FXMQ-MA 40 50 63 80 100 125 200 250
Cooling capacity
Heating capacity
Nominal input cooling heating kW kW
W
W mm kg m
3
/min dB(A)
4.5
5.0
211
211
5.6
6.3
211
211
7.1
8.0
211
211
390x720x690
9.0
10.0
284
284
11.2
12.5
411
411
14.0
16.0
619
619
390x1,110x690
22.4
25.0
1,294
1,294
470x1,380x1,100
28.0
31.5
1,465
1,465
Dimensions (HxWxD)
Weight
Casing
Air flow rate (H/L)
Sound power level
Sound pressure level (H/L)(220V) dB(A)
44
39/35
*
44
14/11.5 14/11.5
39/35
*
Refrigerant type
Piping connections liquid/gas mm ø6.4/ø12.7
Air filter
Power supply VE
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m (horizontal)
• Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 7.5m (horizontal)
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat
• The air filter is not a standard accessory, but please mount it in the duct system at the suction side. Select its colorimetric method (gravity method) 50% or more.
• *Data were not available at time of publication
44
14/11.5
39/35
*
45 galvanised steel plate
19.5/16
42/38
* cf. note 4
63
29/23
43/39
*
R-410A
ø9.5/ø15.9
1~, 50Hz, 220-240V
65
36/29
45/42
*
137
58/50
48/45
*
137
72/62
48/45
*
ø9.5/ø22.2
A C C E S S O R I E S
FXMQ-MA
Wired remote control
Infrared remote control cooling only
Drain pump kit
High efficiency filter 65%
High efficiency filter 90%
Filter chamber
Replacement long life filter
40 50 63 80 100 125
BRC1D52, BRC2C51, BRC3A61
BRC4C64
BRC4C62
KDU-30L125
KAFP372A80 KAFP372A160
KAFP373A80 KAFP373A160
KDDFP37A80 KDDFP37A160
KAFP371A80 KAFP371A160
200 250
KDU-30L250
KAFJ372L280
KAFJ373L280
KDJ3705L280
KAFJ371L280
FXAQ-MA
p . 5 7
W a l l m o u n t e d u n i t
FXAQ-MA
Cooling capacity
Heating capacity
Nominal input cooling
Dimensions (HxWxD) heating
Weight
Colour
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Piping connections
Air filter
Power supply liquid/gas kW kW
W
W mm kg m
3 dB(A) dB(A) mm
/min
20
2.2
2.5
16
24
7.5/4.5
35/29
*
VE
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 5m (horizontal)
• Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 5m (horizontal)
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat
• *Data were not available at time of publication
25 32 40
2.8 3.6 4.5
3.2 4.0 5.0
22 27 20
27 32 20
11 white
8/5 9/5.5 12/9
36/29 37/29 39/34
* * *
R-410A
ø6.4/ø12.7 resin net washable
1~, 50Hz, 220-240V
50 63
5.6 7.1
6.3 8.0
27 50
32 60
14
15/12 19/14
42/36 46/39
* *
ø9.5/ø15.9
A C C E S S O R I E S
FXAQ-MA
Wired remote control
Infrared remote control
Drain pump kit cooling only heat pump
20 25 32 40
BRC1D52
BRC7E619
BRC7E618
K-KDU572DVE
50 63
p . 5 8
FXHQ-MA
C e i l i n g s u s p e n d e d u n i t
FXHQ-MA 32 63 100
Cooling capacity
Heating capacity kW kW
3.6 7.1 11.2
4.0 8.0 12.5
Nominal input cooling
heating
Dimensions (HxWxD)
Weight liquid/gas
W
W mm kg
111
111
195x960x680
24
Colour
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level m
3
/min dB(A) dB(A)
12/10
36/31
*
Refrigerant type
Piping connections mm ø6.4/ø12.7
Air filter
Power supply VE
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m (horizontal)
• Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 7.5m (horizontal)
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat
• *Data were not available at time of publication
115
115
195x1,160x680
28
17.5/14
39/34
*
R-410A
ø9.5/ø15.9
resin net with mold resistant
1~, 50Hz, 220-240V
135
135
195x1,400x680
33
25/19.5
45/37
*
A C C E S S O R I E S
FXHQ-MA
Wired remote control
Infrared remote control cooling only
Drain pump kit
Replacement long life filter
L-type piping kit resin net for upward direction
32
KDU50M60
KAFJ501DA56
KHFP5M35
63
BRC1D52
BRC7E66
BRC7E63
KDU50M125
KAFJ501DA80
KHFP5M63
100
KDU50M125
KAFJ501DA112
KHFP5M63
p . 5 9
FXUQ-MA
4 - w a y b l o w c e i l i n g s u s p e n d e d u n i t
FXUQ-MA 71 100 125
Cooling capacity
Heating capacity kW kW
8.0
9.0
11.2
12.5
14.0
14.0
Nominal input
Dimensions (HxWxD)
Weight
Colour
Air flow rate (H/L)
Sound pressure level (H/L) (220V)
Sound power level (H)
Refrigerant type
Piping connections
Air filter
Power supply cooling heating liquid/gas
W
W mm kg dB(A) dB(A) mm
V1
180
160
165x895x895
25
289
269
230x895x895x
31
289
269
230x895x895
31
white
19/14
40/35
56
29/21
43/38
59
32/23
44/39
60
R-410A
ø9.5/ø15.9 ø9.5/ø15.9 ø9.5/ø15.9
resin net with mold resistant
1~, 50Hz, 230V
Combination with junction box BEVQ71MA
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB, 24° CWB
• Nominal heating capacities are based on: indoor temperature: 20°CDB, 15° CWB • outdoor temperature: 7°CDB, 6°CWB
• Capacities are net including a deduction for cooling (an addition for heating) for indoor fan motor heat
BEVQ100MA BEVQ125MA
A C C E S S O R I E S
FXUQ-MA
Wired remote control
Infrared remote control
Sealing member of air discharge outlet
Air discharge decoration panel cooling only heat pump
Vertical flap kit
Replacement long life filter
L-type connection piping kit
71
KDBHJ49F80
KDBTJ49F80
KDGJ49F80
KHFP49M63
100 125
BRC1D52
BRC7C529
BRC7C528
KDBHJ49F140
KDBTJ49F140
KDGJ49F140
KAFJ495F140
KHFP49M140
J U N C T I O N B O X F O R C O N N E C T I O N T O V R V
BEVQ-MA
Dimensions
Weight
Casing
Power supply
HxWxD mm kg
VE
71
3.0
100 125
100x350x225
3.0 3.5
1~, 50Hz, 220-240V
BEVQ-MA
FXLQ-MA
p . 6 0
F l o o r s t a n d i n g u n i t
FXLQ-MA 20 25 32 40
Cooling capacity
Heating capacity
Nominal input cooling
Dimensions (HxWxD) heating
Weight
Colour
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Piping connections
Air filter
Power supply liquid/gas kW kW
W
W mm kg m
3
/min dB(A) dB(A) mm
2.2 2.8 3.6 4.5
2.5 3.2 4.0 5.0
49 49 90 90
49 49 90 90
600x1,000x222 600x1,140x222
25 30 white
7/6 7/6 8/6 11/8.5
35/32 35/32 35/32 38/33
* * * *
R-410A
ø6.4/ø12.7 resin net with mold resistant
1~, 50Hz, 220-240V VE
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m (horizontal)
• Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 7.5m (horizontal)
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat
• *Data were not available at time of publication
50 63
5.6 7.1
6.3 8.0
110 110
110 110
600x1,420x222
36
14/11 16/12
39/34 40/35
* *
ø9.5/ø15.9
A C C E S S O R I E S
FXLQ-MA
Wired remote control
Infrared remote control
Long life replacement filter cooling only heat pump
20 25 32 40
KAFJ361K28
BRC1D52, BRC2C51, BRC3A61
BRC4C64
BRC4C62
KAFJ361K45
50 63
KAFJ361K71
p . 6 1
FXNQ-MA
C o n c e a l e d f l o o r s t a n d i n g u n i t
FXNQ-MA 20 25 32 40
Cooling capacity
Heating capacity
Nominal input cooling
Dimensions (HxWxD) heating
Weight
Casing
Air flow rate (H/L)
Sound pressure level (H/L)(220V)
Sound power level
Refrigerant type
Piping connections
Air filter
Power supply liquid/gas kW kW
W
W mm kg m
3
/min dB(A) dB(A) mm
2.2 2.8 3.6 4.5
2.5 3.2 4.0 5.0
49 49 90 90
49 49 90 90
610x930x220 610x1,070x220
19 23 galvanised steel plate
7/6 7/6 8/6 11/8.5
35/32 35/32 35/32 38/33
* * * *
R-410A
ø6.4/ø12.7 resin net with mold resistant
220-240V VE
Notes: • Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB • outdoor temperature: 35°CDB • equivalent refrigerant piping: 7.5m (horizontal)
• Nominal heating capacities are based on: indoor temperature: 20°CDB • outdoor temperature: 7°CDB, 6°CWB • equivalent refrigerant piping: 7.5m (horizontal)
• Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat
• *Data were not available at time of publication
50 63
5.6 7.1
6.3 8.0
110 110
110 110
610x1,350x220
27
14/11 16/12
39/34 40/35
* *
ø9.5/ø15.9
A C C E S S O R I E S
FXNQ-MA
Wired remote control
Infrared remote control
Replacement long life filter cooling only heat pump
20 25 32 40
KAFJ361K28
BRC1D52, BRC2C51, BRC3A61
BRC4C64
BRC4C62
KAFJ361K45
50 63
KAFJ361K71
Ventilation
1
HRV-Heat Reclaim Ventilation
1
VAM-FA7
The Daikin heat recovery ventilation system modulates the temperature and humidity of incoming fresh air to match indoor conditions. A balance is thus achieved between indoor and outdoor ambients, enabling the cooling or heating load placed on the air conditioning system to be reduced significantly.
Total heat exchanged foul air
Clean outdoor air
HRV units can be controlled individually or integral with the air conditioning system (Daikin VRV or Sky Air series).
• 9 models to choose from
• Compact, energy saving ventilation
• Specially developed heat exchange element with HEP (High Efficiency Paper)
• Easy integration into the VRV system
• Connectable to current Daikin control systems : p . 6 2
Foul indoor air
Total heat exchanged clean air
VAM-FA
VENTILATION
Air flow rate
Sound pressure level (max.) (1)
External static pressure (max.)
Temperature exchange efficiency
Enthalpy exchange efficiency heating cooling
Weight
Duct diameter
Power supply
(1) Sound pressure level is measured in heat exchange mode.
kg mm
VE
%
%
Pa
% m
3
/h dBA
VAM150FA VAM250FA VAM350FA VAM500FA VAM650FA VAM800FA VAM1000FA VAM1500FA VAM2000FA
150 250 350 500 650 800 1,000 1,500 2,000
27/28.5 28/29 32/34 33/34.5 34.5/35.5 36/37 36/37 39.5/41.5 40/42.5
69
74
58
64
269
760
64
72
58
64
269
760
98
75
61
65
285
812
98
74
58
62
285
812
93
74
58
63
348
988
137
74
60
65
348
988
157
75
61
66
348
988
137
75
61
66
710
1,498
137
75
61
66
710
1,498
509
24
Ø 100
509
24
Ø 150
800
33
Ø 150
800
33
Ø 200
852
48
Ø 200
1~, 50Hz, 220-240V
852
48
Ø 250
1,140
61
Ø 250
852
132
Ø 350
1,140
158
Ø 350
p . 6 3
2
VKM-GA / VKM-GAM
• Heat purge (economiser): heat accumulated indoors is discharged at night
• Integration of humidification and air conditioning into
HRV unit
• Increased static pressure thanks to improved fan performance
• Individual control via HRV remote control
• Connectable to current Daikin control systems:
VKM-GAM
VENTILATION, DX COIL & HUMIDIFIER
Fresh air conditioning load
Air flow rate
Sound pressure level - 220V
Sound pressure level - 240V
Static pressure
Temperature exchange efficiency
Enthalpy exchange efficiency - cooling
Enthalpy exchange efficiency - heating
Humidifier type
Humidification capacity cooling ultra high - high - low ultra high - high - low ultra high - high - low ultra high - high - low ultra high - high - low ultra high - high - low ultra high - high - low kW
%
% m
3
/h dBA dBA
Pa
% kg/h
VKM50GAM VKM80GAM VKM100GAM
4.71 7.46 9.12
8.79 10.69
500 - 500 - 440
37 - 35.5 - 32
38 - 36 - 34
160 - 120 - 100
750 - 750 - 640
38.5 - 36 - 33
40 - 37.5 - 35.5
140 - 90 - 70
950 - 950 - 820
39 - 37 - 34
40 - 38 - 35.5
110 - 70 - 60
76 - 76 - 77.5
64 - 64 - 67
67 - 67- 69
78 - 78 - 79
66 - 66 - 68
71 - 71 - 73 natural evaporating humdifier
74 - 74 - 76.5
62 - 62 - 66
65 - 65 -69
2.70 4.00 5.40
387 387 387
1,764 1,764 1,764
1,214 1,214
102 120 125
1~, 220-240V, 50Hz Power supply V1
VKM-GA
VENTILATION & DX COIL
Fresh air conditioning load cooling
Air flow rate
Sound pressure level - 220V
Sound pressure level - 240V
Static pressure
Temperature exchange efficiency
Enthalpy exchange efficiency - cooling
Enthalpy exchange efficiency - heating ultra high - high - low ultra high - high - low ultra high - high - low ultra high - high - low ultra high - high - low ultra high - high - low ultra high - high - low
Power supply kW m 3 /h dBA dBA
Pa
%
%
%
V1
VKM50GA VKM80GA VKM100GA
4.71 7.46 9.12
8.79 10.69
500 - 500 - 440
38 - 36 - 33.5
39 - 37 - 35.5
180 - 150 - 110
750 - 750 - 640
40 - 37.5 - 34.5
41.5 - 39 - 37
170 - 120 - 80
950 - 950 - 820
40 - 38 - 35
41 - 39 - 36.5
150 - 100 - 70
76 - 76 - 77.5
64 - 64 - 67
78 - 78 - 79
66 - 66 - 68
74 - 74 - 76.5
62 - 62 - 66
67 - 67- 69 71 - 71 - 73 65 - 65 -69
387 387 387
1,764 1,764 1,764
1,214 1,214
96 109
1~, 220-240V, 50Hz
114
2
FXMQ-MFV1 - Outdoor Air Processing Unit
Combined fresh air treatment and air conditioning via a single system.
Both fresh air treatment and air conditioning can be achieved successfully in a single system via heat pump technology without the usual design problems associated with balancing air supply and discharge. Air conditioning fan coil units and an outdoor air treatment unit can be connected to the same refrigerant line, resulting in enhanced design flexibility and a significant reduction in total system costs.
• 100% fresh air intake possible
• Leaves maximum floor and wall space for furniture, decorations and fittings
• Operation range: -5°C to 43°C
• 225 Pa external static pressure allows extensive ductwork runs and flexible application: ideal for use in large areas
• Drain pump kit available as accessory p . 6 4
FXMQ-MFV1
INDOOR UNITS
Capacity
Power Input
Dimensions
Weight
Air Flow Rate
Refrigerant
Power Supply
Piping Connections cooling heating cooling heating
HxWxD cooling heating liquid (od)/gas/drain medium medium kw kw kw kw mm kg m3/min m3/min mm
14.0
8.9
0.359
0.359
470x744x1,100
86
18.0
18.0
9.5 / 15.9 / PS1B
22.4
13.9
0.548
0.548
28.0
28.0
-
220-240V/50Hz
9.5 / 19.1 / PS1B
470x1380x1,100
123
p . 6 5
3
VRV+EXV-kit - VRV Air Handling Applications
A new range of R-410A inverter condensing units for multi application with air handling units.
• Inverter controlled units
• Large capacity range (from 5 to 18HP)
• Cooling only
• R-410A
• Control z: control of air temperature (suction temperature, room temperature) via Daikin control (no DDC controller needed)
• Large range of expansion valve kits available
• BRC1D52 is used to set the set point temperature
(connected to the EKEXMCB).
gas pipe liquid pipe
F1, F2 communication
COOLING ONLY
RXQ-P(A)
Capacity range
Capacity
Power input (Nominal)
Dimensions
Weight cooling cooling
HxWxD
Sound Level
Air Flow Rate (nominal at 230V)
Operation Range
Refrigerant
Power Supply sound power sound pressure cooling cooling
Max n° of indoor units to be connected
Piping connections liquid (OD)/gas cooling cooling min~max
HP kw kw mm kg dBA dBA m /min
°CDB mm
COMBINATION TABLE
OUTDOOR UNIT
3ph
RXQ5P
RXQ8P
RXQ10P
RXQ12P
RXQ14PA
RXQ16PA
RXQ18PA
5
5
14.0
3.52
1,680x635x765
157
72
54
95
8
9.5 / 15.9
185
57
171
22.4
5.56
8
8
13
9.5 / 19.1
78
10
10
28.0
7.42
1,680x930x765
238
58
185
16
9.5 / 22.2
12
12
33.5
9.62
196
-5.0~43.0
R-410A
3N~/400V/50Hz
19
12.7 / 22.2
14
14
40.0
12.4
315
16
16
45.0
14.2
1,680x1,240x765
80
60
233
23
12.7 / 28.6
26
323
83
63
239
18
18
49.0
16.2
29
15.9 / 28.6
CONTROL
BOX
CONTROL Z CLASS 50
EKEXMCB
X
X
X
X
X
X
X
EKEXV50
X
X
X
X
X
X
X
CLASS 63
EKEXV63
X
X
X
X
X
X
X
EXPANSION VALVE KIT
CLASS 80
EKEXV80
X
X
X
X
X
X
X
CLASS 100 CLASS 125 CLASS 140 CLASS 200 CLASS 250
EKEXV100 EKEXV125 EKEXV140 EKEXV200 EKEXV250
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
User Friendly Control Systems
p . 6 6
1. I
NDIVIDUAL
C
ONTROL
S
YSTEMS
BRC4*
BRC7*
Infrared remote control
Operation buttons: ON/OFF, timer mode start/stop, timer mode on/off, programme time, temperature setting, air flow direction (FXHQ, FXFQ, FXCQ and FXAQ models only), operating mode, fan speed control, filter sign reset, inspection / test indication
Display: Operating mode, battery change, set temperature, air flow direction
(FXHQ, FXFQ, FXCQ and FXAQ models only), programmed time, inspection/test operation, fan speed
BRC2C51
BRC3A61
Simplified remote control
Simple, compact and easy to operate unit, suitable for use in hotel bedrooms
Operation buttons: ON/OFF, operating mode selection, fan speed control, temperature setting
Display: Cool/heat changeover control, Heat Recovery Ventilation (HRV) in operation, set temperature, operating mode, centralised control indication, fan speed, defrost/hot start, malfunction adjustment, operating mode selection, fan speed control, filter sign reset, inspection test/operation
Simplified built-in remote control for hotel applications
Compact, user friendly unit, ideal for use in hotel bedrooms
Operation buttons: ON/OFF, fan speed control, temperature setting
Display : Heat Recovery Ventilation (HRV) in operation, set temperature, operating mode, centralised control indication, fan speed, defrost/hot start, malfunction
BRC1D52
p . 6 7
Wired remote control
9 Limit operation (min/max): room temperature is controlled within adjustable upper and lower limits. Limit operation can be activated manually or by schedule timer
9
Real time clock: indicates real time and day
9 Schedule timer: week.
Five day actions can be set as follows:
- Set point: unit is switched ON and normal operation is maintained
- OFF: unit is switched OFF more details)
9 Home leave (frost protection): during occupants’ absence, the indoor temperature can be maintained at a certain level. This function can also switch the unit ON/OFF
9 Different levels of disabled buttons can be selected as follows: up/down, fan speed, cooling/heating mode, enable/disable schedule timer, air flow direction adjustment button up/down, fan speed
9
User friendly HRV function, thanks to the introduction of a button for ventilation mode and fan speed
9 Constantly monitoring of the system for malfunctions in a total of 80 components
9
Immediate display of fault location and condition
9 Reduction of maintenance time and costs
Operation buttons: ON/OFF, timer mode start/stop, timer on/off, programmed time, temperature setting, air flow direction adjustment, operating mode selection, fan speed control, filter sign reset, inspection test/operation
Display: Operating mode, Heat Recovery Ventilation (HRV) in operation, cool/heat changeover control, centralised control indication, group control indication, set temperature, air flow direction, programmed time, inspection/ test operation, fan speed, clean air filter, defrost/hot start, malfunction
p . 6 8 c o n t r o l s y s t e m s
2. C
ENTRALISED
C
ONTROL
S
YSTEMS
DCS302C51
Centralised remote control
Providing individual control of 64 groups (zones) of indoor units
9 A maximum of 64 groups (128 indoor units, max. 10 outdoor units) can be controlled
9
A maximum of 128 groups (128 indoor units, max. 10 outdoor units) can be controlled via 2 centralised remote controls in separate locations
9 Zone control
9 Group control (up and down buttons are added for group selection)
9 Control of HRV air flow direction and air flow rate
9
Expanded timer function
9
Malfunction code display
9
Maximum wiring length of 1,000m (total: 2,000m)
DCS301B51
Unified ON/OFF control
Providing simultaneous and individual control of 16 groups of indoor units
9 A maximum of 16 groups (128 indoor units) can be controlled
9 2 remote controls in separate locations can be used
9
Operating status indication (normal operation, alarm)
9
Centralised control indication
9 Maximum wiring length of 1,000m (total: 2,000m)
DST301B51
Schedule timer
Enabling 64 groups to be programmed
9
A maximum of 128 indoor units can be controlled
9 8 types of weekly schedule
9 A maximum of 48 hours back-up power supply
9
Maximum wiring length of 1,000m (total: 2,000m)
p . 6 9
3. N
ETWORK
S
OLUTIONS
DS-NET adapter
P1 - P2
The ideal solution for control and management up to 2,000 indoor units
PC for monitoring
Modem
Public phone line
Malfunction
Modem
Max. of 10 DS-NET adapters
P1 - P2
F1 - F2
F1 - F2
A
PPLICATION AREA
9
A small commercial area of less than 40 indoor units.
9
Critical applications for centralized monitoring.
S
YSTEM LAYOUT
9
Allows monitoring and control of up to up to 50 stores or sites and 2,000 indoor units with just one modem and phone line.
9 Automates daily air conditioning operation in order to free users from the hassle of air conditioning operation/management.
9 The daily schedule setting allows automatic operation afterward.
9
Automates alarm (report messages) for any malfunctions/errors. Immediate report of any indoor unit breakdown to the servicing company.
9 Automatic report of breakdown/ malfunction information.
9
Minimizes the inconvenience of not having air conditioning via rapid messages
F
UNCTIONS
9 Schedule setup (Daily schedule)
- Start/stop
9
A/C malfunction report
- Send message to monitoring system
9 Manual operation mode, fan speed
9
Status monitoring
- Start/Stop, set temperature, operation time, error code
p . 7 0 n e t w o r k s o l u t i o n s
Allows detailed and easy monitoring and operation of VRV systems (max. 2 x 64 control groups) third party controller
(domotics, BMS, etc.)
AIRNET
Public line
Onboard modem
Open Interface
Ethernet
PCMCIA flash memory
• CSV output of
PPD (option) result
Onboard
Ethernet port
Pi-port
Links to the wattmeter when using the PPD
(option) function
Malfunction
DIII-NET
Remote monitoring/control via internet, e-mail
PPD data is available on the internet
Forced OFF contact input
Fire alarm
HRV
Indoor units
RS-232C
DIO unit
DI unit
DIII-NET Allows monitoring/control of up to 64 units (groups)
Controls drain pump, lighting etc.
Monitoring of room enter/exit sign
DIII-NET PLUS adapter
Indoor unit HRV
p . 7 1
L
ANGUAGES
English, French, German, Italian, Spanish
S
YSTEM LAYOUT
9
Up to 2 x 64 indoor units can be controlled
9
Onboard Ethernet port (web browser & e-mail)
9 Digital i/o contacts (option)
9 Touch panel (full colour LCD via icon display)
M
ANAGEMENT
9 Web application & internet compatibility
- Monitoring & control according to user one building one building via internet
9
Power Proportional Distribution (option)
9
PPD data is available on the internet
9 Easy management of electricity consumption
9 Enhanced history function
C
ONTROL
9 Individual control (set point, start / stop, fan speed) (max. 2 x 64 indoor units/groups)
9
Schedule control (8 schedules, 17 patterns)
9
Flexible grouping in zones
9 Yearly schedule
9 Fire emergency stop control
9
Interlocking control
9
Increased HRV monitoring and control function
9 Automatic cooling/heating changeover
9 Quick selection and full control
9
Simple navigation
9
Heating optimization
9 Temperature limit
(general, administration & service)
M
ONITORING
9 Visualisation via Graphical User Interface
(GUI)
9
Icon colour display change function
9 Indoor units operation mode
9 Error messages via e-mail & mobile phone
(option)
9
Indication filter replacement
9 Multi PC
C
OST PERFORMANCE
9
Labour saving
9 Easy installation
9 Compact design: limited installation space
9
Overall energy saving
O
PEN INTERFACE
9 Communication to any third party controller
(domotics, BMS, etc.) is possible via open interface.
C
ONNECTABLE TO
9
VRV
9
HRV
9 Sky Air (via interface adapter)
9 Split (via interface adapter)
p . 7 2 n e t w o r k s o l u t i o n s
~ Intranet/Internet
Web Access
The ideal solution for control and management of maximum 1,024
VRV indoor units
Web Access
S
YSTEM LAYOUT
9
Up to 1,024 indoor units can be controlled (by 4 iPUs)
9 Ethernet TCPIP / 10 base /
T communication
9
Integrated digital contacts on the Intelligent Processing Unit
(iPU)
• 19 general input ports
• 2 digital outputs
9 Stand alone operation of the iPU for minimum 48 hours
9 Compatible with UPS shutdown software
Sub PC
~
DAM602B51/52
Malfunction report by E-Mail
(Via Internet)
Ai unit
Air Conditioning
Network Service System
(Optional Maintenance Service)
DIII-NET
DIII-NET
DIII-NET
Dio unit
Power supply facility
· Elevator
· Pump
· Lighting,...
Fire alarm Electricity
Measurement
Local monitoring
& control
VRV System
Daikin Central
Air Conditioning System
HRV
M
ANAGEMENT
9
Web access function (option)
9
Power Proportional
9 Operational history management (start/stop, malfunction, operation hours)
9 Generation of reports
(graphics & tables) (daily, weekly, monthly)
9
Peak load shedding
9 Advanced tenant management
9
Sliding temperature
9
Eco mode (option)
C
ONTROL
9
Individual control
(setpoint, start/stop, fan speed)
(max. 1,024 indoor units)
9 Group control (100 groups)
9
Schedule control
(128 programs)
9 Fire emergency stop control
(32 programs)
9
Interlocking control
9
Setpoint limitation
9 Automatic cooling heating changeover
9
Power failure/release control
9
Temperature limit
(automatic start)
9 Timer extension
M
ONITORING
9
Visualisation via a Graphical
User Interface (GUI) featuring free layout
9 Operation mode of indoor & outdoor units
9
Fault indication
9 Indication filter replacement
9 Setpoint indication
9
Operation time monitoring
9
Multi PC
9 On-line help
p . 7 3
LON
®
BMS
) adapter
LonTalk
DMS504B51
HRV
BUILDING
CONTROL
NETWORK adapter
LonPoint
LonTalk
LonPoint
Security
Fire alarm
System
Local Control
DIII- NET
VRV
Outdoor unit
L
ON
W
ORKS ®
Networks Compatible Gateway
9 Interface for connection to L ON W ORKS ® networks
9
Communication via L
ON ®
protocol
(twisted pair wire)
9 64 units connectable per DMS-IF
9
Unlimited site size
9
Quick and easy installation
Remote Control
DAIKIN A/C INFRASTRUCTURE
BMS DMS502A51
DIII- NET
Local Control
VRV
Outdoor unit
Integrated control system connecting
VRV system with BMS system
9
PPD data is available on BMSsystem
9 Interface for BMS system
9
Communication via BACnet protocol (connection via Ethernet)
9 256 units connectable per BACnet gateway
9
Unlimited site size
9
Easy and fast installation BUILDING
CONTROL
NETWORK
HRV
DAIKIN A/C INFRASTRUCTURE
Fire alarm
Pump
Security
Lighting
Remote Control
Power supply facility
Elevator
c o n t r o l s y s t e m s p . 7 4
4.
ACCESSORIES
• I
NDIVIDUAL CONTROL SYSTEMS
DESCRIPTION
Wired remote control
Infrared remote control
Simplified remote control
Simplified remote control for hotel use cooling only heat pump
FXFQ FXZQ FXCQ FXKQ FXDQ FXDQ-N FXSQ FXMQ FXUQ FXHQ FXAQ FXLQ FXNQ
BRC1D52
BRC7F533 BRC7E531 BRC7C67 BRC4C63 BRC4C64 BRC4C64 BRC4C64 BRC4C64 BRC7C529 BRC7E66 BRC7E619 BRC4C64 BRC4C64
BRC7F532 BRC7E530 BRC7C62 BRC4C61 BRC4C62 BRC4C62 BRC4C62 BRC4C62 BRC7C528 BRC7E63 BRC7E618 BRC4C62 BRC4C62
BRC2C51 BRC2C51 BRC2C51 BRC2C51 BRC2C51 BRC2C51
BRC3A61 BRC3A61 BRC3A61 BRC3A61 BRC3A61 BRC3A61
• C
ENTRALISED CONTROL SYSTEMS
DESCRIPTION
Centralised remote control
Unified ON/OFF control
Schedule timer
FXFQ FXZQ FXCQ FXKQ FXDQ FXDQ-N FXSQ FXMQ FXUQ FXHQ FXAQ FXLQ FXNQ
DCS302C51
DCS301B51
DST301B51
• O
THERS
DESCRIPTION
Wiring adapter
Wiring adapter (hour meter)
Wiring adapter for electrical appendices (1)
Wiring adapter for electrical appendices (2)
Remote sensor
Installation box for adapter PCB
Electrical box with earth terminal (3 blocks)
Electrical box with earth terminal (2 blocks)
Noise filter (for electromagnetic interface only)
External control adapter
Interface adapter for Sky Air series
Connector for forced on/forced off
FXFQ FXZQ FXCQ FXKQ FXDQ FXDQ-N FXSQ FXMQ FXUQ FXHQ FXAQ FXLQ FXNQ
-
EKRP1C11*1
KRP1B61 KRP1B61 KRP1B56
EKRP1B2*2 -
-
EKRP1B2
KRP1B61 KRP4A53
-
KRP2A526*1 KRP2A526*1 KRP2A516*1 KRP2A61 KRP2A516 KRP2A53 KRP2A516 KRP2A61
KRP4AA53*1 KRP4A536*1 KRP4A516*1 KRP4A51 KRP4A516 KRP4A54 KRP4A516 KRP4A51
KRCS01-4
KRP1H98 KRP1BA101 KRP1B96*3/4
-
KJB212AA
-
-
-
-
KRP1B57*1
-
KRP1BA101
KRCS01-1
KJB311A
KJB212A
KEK26-1A
-
DTA104A52 DTA104A51*1 DTA104A61 DTA104A51 DTA104A53 DTA104A51 DTA104A61
-
-
-
EKRP1B2
-
-
-
-
-
-
-
-
-
-
-
-
KRP1B97
DTA102A52
EKRORO
KRP1B3
-
KRP2A62*
KRP4A52*
DTA104A62 DTA104A51 DTA104A61 DTA104A61
-
-
-
-
KRP2A51
KRP4A51
KRP1C93*3 KRP4A93*3/4
-
-
KRP1B61
-
KRP2A51
KRP4A51
-
-
-
KRP1B61
-
KRP2A51
KRP4A51
-
-
-
Notes: • *1: Installation box is required • *2: Fixing box is KRP1A90 • *3: Up to 2 adapters can be fixed per installation box • *4: Only 1 installation box can be installed per indoor unit
•
DESCRIPTION
DS-net adapter
Software
REFERENCE
DTA113B51
DPC001B1-B51
COMMENTS
4 units can be connected per adapter, 40 units when 10 adapters are connected
Monitoring panel software
•
DESCRIPTION
Intelligent Touch Controller
Software
Hardware
Installation box
Touch-Pen
Interface adapters
Digital input
Digital input/output
REFERENCE
DCS601C51
DCS002C51
DCS004A51
DCS601A52
KJB411A
1264009
KRP928A2S
DTA102A52
DTA112B51
DEC101B51
DEC102B51
COMMENTS
2x64 units can be connected
Power Proportional Distribution (PPD) software
E-mail / Web software
DIII NET-Plus adapter
For wall mounted installation
Spare part n° of Touch-Pen for Intelligent Touch Controller
For connection to Split units
For connection to R-22 / R-407C Sky Air units
For connection to R-410A Sky Air units
Input contacts: 16 points
Input contacts: 8 points; output contacts: 4 points
p . 7 5
•
DESCRIPTION
Intelligent Processing unit
Software
Interface adapters
DIII Ai
Digital input
Digital input/output
•
DESCRIPTION
L ON W ORKS ®
networks compatible Gateway
Interface adapters
REFERENCE
DAM602B51
DAM602B52
IM3.XX
KRP928A2S
DTA102A52
DTA112B51
DAM101A51
DEC101B51
DEC102B51
COMMENTS
256 indoor units per IPU
128 indoor units per IPU
Up to 1,024 indoor units
For connection to Split units
For connection to R-407C/R-22 Sky Air units
For connection to R-410A Sky Air units
Outdoor temperature sensor
Input contacts: 16 points
Input contacts: 8 points; output contacts: 4 points
REFERENCE
DMS504B51
KRP928A2S
DTA102A52
DTA112B51
COMMENTS
Up to 64 units can be connected per DMS-IF
For connection to Split units
For connection to R-407C/R-22 Sky Air units
For connection to R-410A Sky Air units
•
DESCRIPTION
BACnet Gateway
DIII board
Digital input/output
Interface adapters
REFERENCE
DMS502B51
DAM411B51
DAM412B51
KRP928A2S
DTA102A52
DTA112B51
COMMENTS
64 units per Gateway
Extension of 3 x DIII lines (3 x 64) indoor units
For forced shutdown
For connection to Split units
For connection to R-407C/R-22 Sky Air units
For connection to R-410A Sky Air units
• BMS: B
UILDING
M
ANAGEMENT SYSTEM
DESCRIPTION
Parallel interface - Basic unit
Temperature measurement units
Temperature setting units
Unification adapter for computerised control
Wiring adapter for electrical appendices (1)
Wiring adapter for electrical appendices (2)
External control adapter for outdoor unit
DIII-net expander adapter
Mounting kit
REFERENCE
DPF201A51
DPF201A52
DPF201A53
DCS302A52
KRP2A51
KRP2A52
KRP4A51-53
DTA104A51
DTA104A52
DTA109A51
KRP4A92
COMMENTS enables ON/OFF command, operation and display of malfunction can be used in combination with up to 4 units.
enables temperature measurement output for 4 groups; 0~5VDC.» enables temperature setting input for 16 groups; 0~5VDC.» used for combining of air conditioning control computer and central remote controller (ON/OFF, display) simultaneously controls air conditioning control computer and up to 64 groups of indoor units. to control the group of indoor units collectively, which are connected by the transmission wiring of remote controller.
cooling/heating mode change over, demand control and low noise control are available between the plural outdoor units.
a maximum of 10 outdoors or 128 indoors can be connected to 1 DTA109A51 a maximum of 8 DTA109A51 can be connected to DIII-net for easy installation of the DTA109A51
Notes
p . 7 6 n o t e s
Notes
p . 7 7 n o t e s
Notes
p . 7 8 n o t e s
Notes
p . 7 9 n o t e s
Head Offi ce
Daikin Airconditioning UK Limited
The Heights, Brooklands, Weybridge, Surrey KT13 0NY
Tel 0845 6419000 Fax 0845 6419109
www.daikin.co.uk
Daikin Europe N.V. is approved by LRQA for its Quality
Management System in accordance with the ISO9001 standard. ISO9001 pertains to quality assurance regarding design, development, manufacturing as well as to services related to the product.
ISO14001 assures an effective environmental management system in order to help protect human health and the environment from the potential impact of our activities, products and services and to assist in maintaining and improving the quality of the environment.
Daikin products are distributed by:
Daikin units comply with the European regulations that guarantee the safety of the product.
VRV products are not within the scope of the Eurovent certifi cation programme.
The present catalogue is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V..
Daikin Europe N.V. has compiled the content of this catalogue to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fi tness for particular purpose of its content and the products and services presented therein. Specifi cations are subject to change without prior notice.
Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this catalogue. All content is copyrighted by Daikin Europe N.V..