User Guide UPS 20 - 40 kVA, 380/400/415V, 50/60 Hz
(3-phase input/3-phase output)
614-06749-03 Revision 03
1.
2.
1.4 User precaution….....………………….....………………….....……………… 02
3.
4.
5.
5.4 Connecting the external battery……………………………………………… 27
6.
7.
8.
9.
10.
Recycling the used UPS or battery……………………………………………… 49
11.
12.
1 Safety instructions
This user manual contains important safety instructions and operating instructions. Please read the user manual carefully before operating or working on the UPS and save it for reference in the future.
1.1 Safety caution
The UPS operates with external AC mains, battery cabinet(s) or bypass power. It contains components that carry hazardous voltages and high currents, The properly installed enclosure is earthed and IP20 rated against electrical shock and foreign objects. The user is not permitted to open it. Failure to observe this could result in electric shock risk.
Only qualified personnel is allowed to install and service the UPS.
Warning!
Operations inside the UPS must be performed by a service engineer from the manufacturer or from an agent authorised by the manufacturer.
Use the optional Maintenance Bypass Switch (MBS) for service inside the UPS when installed to the system. Remember to open battery cabinet(s) breaker. Always ensure by measuring with a multimeter that no dangerous voltages are present. For detailed MBS operation instructions please see 4.5.
1.2 Audience caution
The intended audiences of this manual are people who plan the installation, install, commission, and use or service the UPS. The manual provides guidelines to check delivery, installing and commissioning of the UPS. The reader is expected to know the fundamentals of electricity, wiring, electrical components and electrical schematic symbols. This manual is written for a global reader.
1
Caution!
Read the manual before operating or working on the UPS.
1.3 CE marking
The product has the CE marking in compliance with the following European directives:
LVD Directive (Safety) 2006/95/EEC
EMC Directive 2004/108/EEC
Note!
This product for commercial and industrial application in the second environment Installation restrictions or additional Measures may be needed to prevent disturbances.
1.4 User precaution
The only user operations permitted are:
Start up and shut down the UPS, excluding the commissioning start-up.Use of the LCD control panel and Emergency Power Off (EPO) switch.Use of optional connectivity modules and their software.The user must follow the precautions and only perform the described operations.Any deviations from the instructions could be dangerous to the user or cause accidental load loss.
Warning!
The user is not permitted to open any screws excluding connectivity plates and the
Emergency Power Off (EPO) switch. Failure to recognise the electrical hazards could prove fatal.
2
1.5 Environment
The UPS must be installed according to the recommendations in this manual.Under no circumstances the UPS should be installed in an airtight room, in the presence of flammable gases, or in an environment exceeding the specification.Excessive amount of dust in the operating environment of UPS may cause damage or lead to malfunction. The UPS should be always protected from the outside weather and sunshine. The recommended operating temperature is from +15 to +20 Celsius degrees.The recommended operating humidity:20% to 90%.
1.6 Inquiries
Address any inquiries about the UPS and battery cabinet(s) to the local office or agent authorized by the manufacturer. Please quote the type code and the serial number of the equipment.
3
4
2 Introduction
The product described in this manual is an Uninterruptible Power Supply (UPS). It is a true online, continuous duty, double conversion, solid state, three-phase system, providing conditioned and uninterruptible AC power to protect the end-user's load.
2.1 System description
Eaton E Series DX products are high-efficiency and high-performance, double conversion, pure-online and three phase input and three phase output UPS, with unit capacity ranging between 20KVA-40KVA. Categorized by capacity, the products can be further divided into
20KVA, 30KVA and 40KVA. This series not only provides perfect solution for power source protection and successfully solves problems such as blackout, boost, brownouts, sags, decaying, oscillation, high voltage impulse, voltage fluctuations, surges, harmonic distortion, disturbances, frequency fluctuation etc, but also enhances adaptability to complicated working environments so that the application fields is well extended to computer equipments, communication equipments and other controlling equipments with good adaptability to complicated industrial environments as well. Therefore, this series products can be applied in a diversified multi-industries field such as telecommunications, financing, transportation, government, manufacturing and energy sectors.
Eaton E Series DX products are also capable of ECO mode. ECO mode means UPS load is powered by bypass AC supply while in case of abnormal AC supply the load will be supplied by accumulator battery after conversion through inverter. As the energy conversion efficiency reaches as high as 98% and transfer time less than 10ms under ECO mode when there is normal AC supply, the energy saving effect of UPS is remarkable.
Remark: ECO mode is applicable only to single unit.
2.2 Basic system configuration
2.3 Panel figure
5
① AC: This light and inverter light will turn "green" when UPS is powered by Rectifier Input;
② Inverter: This light will turn "green" when UPS load is through the inverter;
③ Battery: This light will turn "yellow" when UPS is powered by batteries;
④ Bypass: This light will turn "green" when UPS load is powered by Bypass Input;
⑤ Fault: If the UPS worked under fault condition,this light would turn on and stay “red” with continuous warning tone being given off in case of UPS abnormal function;or flash “red” with intermittent warning tone being given off.
⑥ LCD: Display UPS commands.
⑦ :Confirm/Enter; press this button to select a menu or confirm an operation.
⑧ :PageDown; press this button to switch to next screen display under the same menu.
⑨ :PageUp; press this button to return to next screen display under the same menu.
⑩ Esc: Escape; press this button to return to previous menu or cancel a certain operation.
Remark: Refer to Chapter 12 for detailed information of LED in accordance with
UPS condition.
2.4 Exterior view
Exterior figure of Eaton E Series DX 20KVA UPS
LCD panel
PARALLEL
Intelligent slot
Extended slot
Button
LED indicator light
SERVICE
AS400
EPO
RS485
RS232
Fan
Front view Rear view
6
CHGR FAN
Maintenance Bypass Switch
Neutral Switch
Bypass Input Switch
Rectifier Input Switch
Front view(door open)
Exterior figure of Eaton E Series DX 30KVA,40KVA UPS
LCD panel
Button
LED indicator light
PARALLEL
Intelligent slot
Extended slot
SERVICE
AS400
EPO
RS485
RS232
Fan
Front view Rear view
7
CHGR FAN
Front view(door open)
Maintenance Bypass Switch
Neutral Switch
Bypass Input Switch
Rectifier Input Switch
8
3 Technical data
3.1 Standards
UPS 20kVA 30kVA 40kVA
Safety IEC62040-1-1:2004,EN62040-1-1:2003 and EN60950-1:2001
EMC IEC62040-2:2005 and EN62040-2:2006
Product IEC62040-3:1999 and EN62040-3:2001
3.2 Environment
UPS 20kVA 30kVA 40kVA
Ambient 0 to +40℃(UPS), 15 to +25℃(battery cabinet(s))
Relative humidity 20% to 90%, no condensation allowed
Altitude derating coefficient See user operations section for more detail information
Vibration IEC68-2-6; max.0.3mm(2 to 9Hz), max.1m/s2(9 to 200Hz) sinusoidal
3.3 Dimensional drawings
UPS 20kVA 30kVA 40kVA
Width 420mm 470mm 470mm
Depth 643mm 710mm 710mm
Height 956mm 1150mm 1150mm
N.W(Kg) 82 110 114
G.W(Kg) 122 160 164
9
3.4 Characteristics
20kVA 30kVA 40kVA
Efficiency-nominal load Up to 92% Up to 92% Up to 92%
Noise (ISO 7779) <65dB at 75% load <65dB at 75% load <65dB at 75% load
3.5 AC input
20kVA 30kVA 40kVA
Rectifier input 3 phases + N
Bypass input 3 phases + N
Voltage (L-N) 165V-275 Volts without using battery
Frequency 40-70 Hz
Power factor 0.99
Input distortion < 5% THD(I)
Rated input voltage 380V/400 V/415V 380V/400 V/415V 380V/400 V/415V
Rated input current 29A/28A/27A 43A/41A/40A 57A/54A/52A
3.6 DC circuit
Battery number 32
Battery nominal voltage
Positive battery +192V DC
Negative battery -192V DC
Cut off voltage 160 ± 2V DC
Battery charging current (A) ± 4.5A
10
3.7 AC output
20kVA 30kVA 40kVA
Active power 16KW 24KW 32KW
Number of phases 3-phases + N
Frequency 50/60HZ
Voltage (L-N) 220/230/240 VAC
110%<Load<=125%
10 minutes minimum, then transfer to bypass and alarm
Overload
capability
(Mains
available)
125%<Load<=150%
1 minutes minimum, then transfer to bypass and alarm
Load>150%
0.5 seconds minimum, then transfer to bypass and alarm
Overload
capability
(battery
available)
110%<Load<=125%
125%<Load<=150%
10 minutes minimum, then transfer to bypass and alarm
1 minutes minimum, then transfer to bypass and alarm
Load>150%
0.5 seconds minimum, then transfer to bypass and alarm
11
4 Mechanical installation
The UPS and accessories are delivered on a specifically designed pallet that is easy to move with a forklift or a pallet jack. Keep the UPS always in upright position and do not drop the equipment. Do not stack the pallets.
4.1 Delivery check
The UPS is delivered with the following items:
1. W inpower disc
2.RS-232 serial cable
3.Delivery documents
4.User Guide
5.Key
4.2 Unpacking and visual inspection
Check that there are no signs of shipping damages. The equipment should be transported in the upright position.
Note!
A claim for shipping damage must be filed immediately and the carrier must be informed within 7 days of receipt of the equipment. The packing materials should be stored for further investigation.
Unpack the equipment by removing the packing and shipping materials. Make a visual inspection.
Remove the equipment from the pallet and make sure that the floor surface is solid and suitable for the wheeling and heavy weight.
Remove cover plate → Remove side plate → Remove stuffing and fix
12
Check the information on the type designation label of the equipment to verify that the unit is of the correct type. The type designation label includes ratings, a CE marking, a type code, a part number and a serial number. The serial number is important when making inquiries. It allows individual recognition of the equipment.
13
4.3 Planning before installation
The equipment must be installed in upright position. The equipment requires space to front and back to enable cooling airflow. Service and maintenance require more than 40cm clearance on right hand side. All cooling air enters at front and exits at unit rear. The required minimum clearance from unit rear to an obstruction is 50cm. Because the service and user access is in the front there should be reserved enough space (min 60cm).
Preparation for installation.
1. Avoid extremes of ambient temperature; excessive dust, moisture or vibration; flammable gases; and corrosive or explosive atmospheres.
2.Altitude for normal UPS function should not exceed 1000m.
3.The battery cabinet should work within a temperature range from15℃ to 25℃.
4.The maximum ambient temperature for normal UPS performance should not exceed 40℃.
14
4.4 Cabinet installation
The required distance for UPS units should allow for service access. The same applies to the battery cabinet(s) that should be installed next to the UPS cabinet(s).
Caution!
UPS cabinet(s) can fall over if the installation brake pads are not used. Both rear and front pads must be used to secure the UPS cabinet to the floor.
Use a 19mm wrench in clockwise direction to screw the brake pad down to the ground, keeping the machine from moving.
4.5 Maintenance Bypass Switch(MBS)
Warning!
All operations inside the unit must be performed only by a service engineer from the manufacturer or from an agent, authorised by the manufacturer.
The operation of the MBS is allowed for a service engineer from the manufacturer or from an agent, authorised by the manufacturer. The full UPS wiring diagram with a MBS switch is presented in the installation part of the manual.
15
The switching sequence for circuit breaker from normal position to maintenance position:
The normal positions of the MBS switches.
16
The maintenance positions of the MBS switches
Transfer UPS from normal mode to maintenance bypass mode:
1.The normal start position should be following:
2.Use LCD to turn the UPS from normal mode to bypass mode:
Switch-off action (press ESC to exit above picture)
17
1)Switch-off picture 2)If it is in single machine mode, the
following will appear
Remember to verify the transfer before proceeding the next step.
3.Remove the locking plate of maintenance switch.
4.Turn OFF the Rectifier Input switch.
5.Turn the Maintenance switch to “MAINTENANCE” side.
6.Turn OFF the Bypass Input switch and N switch.
18
7.UPS is now in the maintenance bypass mode,see below:
Transfer UPS from maintenance bypass mode to normal mode:
1.The normal start position should be following:
2.Turn ON the Bypass Input switch and N switch
W hen the LED of bypass turns green,the UPS enters into bypass mode.
3.Turn the Maintenance switch to “UPS” side.
19
Then the UPS turn to bypass mode.
4.Turn ON the Rectifier Input switch.
5.Use LCD to turn the UPS from bypass mode to normal mode:
Switch-off action (press ESC to exit above picture)
1)Switch-on picture 2)Press ENTER
20
6.UPS is now in the normal mode,see below:
7.Remount the locking plate of maintenance switch to the position to prevent the use of it.
21
5 Electrical installation
5.1 Electrical Preparations
Note!
It must be ensured that no line input source can accidentally be connected to the UPS during installation.
Warning!
Installation may only be carried out by qualified technicians and in conformity with the applicable safety standards.
Warning!
The UPS unit is not applicable to the IT power distribution system.
5.2 Installation and wire connection diagram
The UPS unit has the following power connections:
Three-phase (L1, L2, L3), Neutral (N) and Protective Earth (PE) connection for the rectifier input.
Three-phase (L1, L2, L3), Neutral (N) and Protective Earth (PE) connection for the bypass input ( N is INTERNALLY common for rectifier and bypass inputs).
Three-phase (L1, L2, L3), Neutral (N) and Protective Earth (PE) connection for the load output.
Positive pole (+),Negative pole (-), Common midpoint/Neutral pole and Protective Earthing
(PE) connection for the external batteries.
22
1.If UPS rectifier input and bypass input are supplied from two mains:
Connect the mains 1 supply cables to the UPS rectifier input terminals L1, L2, L3, N and PE.
Connect the mains 2 supply cables to the UPS bypass input terminals L1, L2, L3, N and PE.
23
2.If UPS rectifier input and bypass input are supplied from one mains only:
Connect the mains supply cables to the UPS rectifier input terminals L1, L2, L3, N and PE .
The following three jumpers must be fixed between the rectifier and bypass input terminals:
L1-L1, L2- L 2, L3- L3.
Terminal block diagram
Warning!
High touch current earth connection essential before connecting supply.
24
In order to gain access to the external electrical connections it is necessary to remove the front terminal protective panel of the UPS. Before the cables are connected they shall be passed through the cable glands to hold them in position and tightened.
Connect the Protective Earthing (PE) cable first.
Connect other cables as shown in the connection terminal representations on the preceding and following pages.
Ensure that the UPS is isolated before removing front terminal protective panel.
5.3 Suggested cable and protective devices
Caution!
All cables should always use copper cable type.
The conductor cross sections apply for maximum currents:
(1) For PVC-insulated copper cables (at 70℃)
(2) When routed in conduits for electrical installations
(3) W hen air temperature surrounding the conduits does not exceed 30℃
(4) For cable lengths up to 30 m
Notice!
Should there be any variation in the conditions it will be necessary to verify whether the cable dimensions satisfy the requirements of IEC-287 and DIN VDE 0298. In cases where the cables are so long that they cause a drop in voltage of >3%, a larger dimension shall be selected.
25
Routing of communication cables or data lines should be kept separate from the UPS input, output, and external battery cables.
Use cable cross section and protective device specification
Model 20kVA 30kVA 40kVA
Rectifier Input L1, L2, L3, N,
Bypass Input L1, L2, L3, N,
min. conductor cross section[mm ] 6 10 16
max. possible cross section[mm ] 35 35 35
Rectifier Input L1, L2, L3, N breaker (A) 60A 230VAC 80A 230VAC 100A 230VAC
Bypass Input L1, L2, L3, breaker (A) 60A 230VAC 80A 230VAC 100A 230VAC
Rectifier Input fuse (A) 60A 250VAC 80A 250VAC 100A 250VAC
Bypass Input fuse (A) 60A 250VAC 80A 250VAC 100A 250VAC
Output L1, L2, L3, N,
min. conductor cross section[mm ] 6 10 16
max. possible cross section[mm ] 35 35 35
External Battery Cabinet Positive
pole(+),Neutral pole,Negative pole (-),
min. conductor cross section[mm ] 10 16 25
max. possible cross section[mm ] 35 35 35
External Battery Cabinet Fuse (A) in
Positive pole(+),Neutral pole,
Negative pole (-),
External Battery Cabinet breaker (A) in Positive pole(+),Neutral pole,Negative pole (-),
80A 250VDC 120A 250VDC 150A 250VDC
80A 250VDC 120A 250VDC 150A 250VDC
Backfeed protection device
40A 250V AC Clearance distances:>=1.4mm
Break time<=15s
Protective Earthing conductor [mm ] Max 35
Torque for fixing above terminals 2.8-3 Nm
26
Notice!
The following label must be displayed on all switching devices installed in the same electrical system as the UPS, even when these are located at a distance from the area in which it is located (according to European standard EN 62040-1-1).
Warning!
ENSURE THAT THE UNINTERRUPTIBLE POWER SYSTEM IS ISOLATED BEFORE
WORKING ON THIS CIRCUIT.
5.4 Connecting the external battery
Before connecting the external battery, please read the notice and warning label on the UPS.
Warning!
In the event of malfunction, the battery cabinet chassis or battery cabinet frames may become live!
Warning!
Special care should be taken when working with the battery cabinet associated with the Eaton E Series DX 20 - 40 kVA. W hen the battery cabinet is connected the overall voltage exceeds 400V. It is very important to ensure that the batteries are installed separately, in a dedicated battery cabinet.
27
Notice!
The most common battery type used in UPS installations is the valve regulated battery.
Valve regulated cells are not sealed. The amount of gas given off is less than for flooded cells, but when planning the battery installation, allowance must be made for adequate ventilation and heat dissipation. Valve-regulated cells are not completely maintenace- free. They must be kept clean and their connections checked periodically to ensure they are tight, and that there is no evidence of corrosion. It is inevitable that the batteries will lose charge during transportation and storage; before attempting to carry out an autonomy test, ensure that the batteries are fully charged as this may take several hours. Cell performance typically improves after a few discharge/recharge cycles.
Notice!
The requirements of the EC directives are satisfied when battery cabinet are used with original accessories. If alternative batteries are used, you must ensure that the applicable EC directives are met and declare conformity.
The battery cabinet is preferably installed to the left of the UPS.
Connect the battery cabinet as follows:
Check the battery fuses are not inserted and/or any external battery switch is open.
Connect PE first.
Connect the battery cabinet(s) with cables sized according to cable cross setion and protective device specification to terminals + (positive pole) ,- (negative pole) and Neutral pole.
Refer to instruction provided with the battery cabinet or by vendor.
Warning!
ENSURE CORRECT POLARITY!
28
5.5 Connections between battery cabinet and UPS
Make sure the Protective Earthing (PE) connected first.
External Battery Cabinet Connections
5.6 Handling the batteries
Warning!
Batteries are a potential source of danger due to their electrical charge and chemical composition. Therefore observe the battery handling instructions of the manufacturer.
These usually can be found in the material which accompanies the shipment.
29
Recharging batteries
Warning!
W hen recharging, observe the indications on the packaging.
Exchanging batteries
Warning!
Before replacing batteries, make sure that those to be installed are fully charged.
Connecting external battery cabinet
Warning!
If a battery cabinet has been disconnected and is to be reconnected, the battery isolator may only be reconnected after you have made certain that voltage with the correct polarity is present on both sides of isolating device.
30
6 Software and connectivity
The Series provide Intelligent Slot, Expanded Slot, PARALLEL, AS400, EPO, RS485 and
RS232 as well as SERVICE Supervising Communication Interface exclusively available to
Eaton technical personnel.
1
3 4
5
7
Intelligent slot
PARALLEL PARALLEL AS400 EPO RS485 SERVICE
RS232
Expanded slot
2
6 8
1. Intelligent slot: suitable for WebPower card of remote supervising management,enabling you to realize remote supervising management on UPS through Internet.
2. Expanded slot: Reserved for special applications
3. PARALLEL: communication interface for parallel machine mode.
4. Standard AS400 interface: provides AS400 and users can directly use UPS supervising function offered by AS400 system to realize power source management (See Appendix for
AS400 port Pin).
5. EPO: Emergency Power Off, providing the possibility of emergency shut down.Normally
closed.
6. Standard RS485 Interface: It can be used to monitor parallel units for completely control of
UPS (See Appendix for RS485 port Pin ).
7. SERVICE Interface: available only to Eaton technicians
8. Standard RS232 Interface: applicable to W inPower supervising software of graphic management (See Figure for RS232 port Pin)
31
RS232 port
RS485 port
32
AS400 port
Note!
The UPS have to be manually reset if remote shutdown occurs.
33
7 User operations
Warning!
High touch current earth connection essential before connecting supply.
The only user operations permitted are:
Start up and shut down the UPS, excluding the commissioning start-up.
Use of the LCD control panel and Emergency Power Off (EPO) switch.
Use of optional connectivity modules and their software.
Warning!
The user must follow the precaution, warnings and only perform the described operation.
Any deviations from the user manual could be dangerous to the user or cause accidental load loss.
Should the UPS be intended for application above 1000m, progressive decrease of rated output should be applied as listed in the following chart:
7.1 Single machine operation
1. Make sure L1, L2 and L3 phase sequences are correctly connected and then supply power to UPS.
2. Turn on the switch on battery box (make sure that the “+”,“N” and “-” of terminal bay are in accordance with those on the battery box).
3. Switch on “Input Switch” (Rectifier Input Switch,Bypass Input Switch) on UPS and fans start to rotate for UPS self-inspection. Main menu can be accessed within about 4sec and then operations should be carried.
34
Remark: the following drawing takes Eaton E Series DX 20KVA as an example and statistics are only for reference.
1)Power on 2)Automatic access within about 4s
3)Press ESC to access or automatically within 1min with no button being pressed
4)Press ▼ to obtain the below information
35
5)Press ▼ again to obtain the below 6)Press ▼ again to obtain the below information information
7)Press ▼ again to obtain the below 8)Press ▼ again to obtain the below information information
36
Note!
If malfunction occurs, “x” will appear at the lower right corner of the display,while a warning occurs, “ ” will appear at the same position (as illustrated in the below picture with battery mode as an example).
4. Start-up action (press ESC to exit the above picture)
1)Switch-on picture 2)Press ENTER
37
3)Select “Yes, Confirm” to switch on 4)Normal Switch-on the machine
5)Battery power supply (switch off line input switch)
38
5. Switch-off action (press ESC to exit above picture)
1)Switch-off picture 2)If it is in single machine mode, the
following will appear
3)If it is in parallel machine mode, the 4)Press ENTER following will appear
39
5)Select “Yes, Confirm” to switch off 6)Normal Switch-off the machine
Note!
If you intend to switch off only one set of UPS among the parallel machine system, select “single machine switch-off”; if switch-off is intended for the entire parallel machine system, select “parallel machine switch-off”.
6. Help
1)Help picture 2)Press ENTER on help picture
40
7. Configuration (press ESC to exit the above picture)
You are able to access Setting picture by using user combination (default: 1234, subject to personal modification) so as to set the following programs.
1)Action display (bypass power supply) 2) Press ▼
3)Enter respective password 4)Select action item
8. The Series is capable of DC start-up without AC input, panel display being similar to switch-on picture with AC supply. DC switch-on and off are available by following instructions appearing in the pictures.
41
9. Procedures of DC switch-on:
Activate DC switch-on function set under UPS bypass mode
Make sure that “+”, “-” and “N” wires of batteries are properly connected to UPS
Switch on batteries
Lightly touch ENTER
Manually conduct switch-on order within about 1min after LCD self-inspection
Note!
UPS will be switched off automatically if there is no operation within 1min after LCD self
-inspection is completed!
7.2 Parallel machine operation
Redundancy introduction
N+X is currently the most reliable power supply structure, in which N indicates the minimum
UPS number required for the total load and X is the redundant UPS number, namely, the malfunctioning UPS number that the system can simultaneously bear. The larger X is, the higher reliability of system will be. For instance, if the total load of a customer registers
55kVA, we can use 20KVA for N+X design. W ith N taking up 3, X can be selected in accordance with reliability degree or cost requirement. Supposing customer selects X=2 and equalized UPS power supply is 11kVA for each unit, when one set of UPS breaks down with malfunction, the remaining four sets will provide power with almost 14kVA equalized current; if two sets of UPS fail, the remaining three sets of UPS are supposed to provide power supply with almost 18kVA equalized current. The maximum allowance of this system is for two sets of UPS going down at the same time, the chances of which are much smaller than those of one UPS malfunction. Therefore, the reliability degree can be largely enhanced, making it an optimal mode for application in locations where high degree of reliability is always a focus.
Eaton E Series DX 20 - 40 kVA is capable of direct parallel connection, which only requires the parallel connection wires (optional) for 2 to 8 sets of UPS in parallel connection in order to realize power redundancy (N+X).
42
Parallel machine wire connection drawing(one battery supply)
Parallel machine wire connection drawing(separate battery supply)
43
Single machine wire connection drawing
44
8 Maintenance
Warning!
The Maintenance must be performed by a service engineer form the manufacturer or form an agent authorised by the manufacturer.
Eaton E Series DX 20 - 40 kVA requires minimum maintenance.
1. If battery is switched off, loaded equipments will not be covered for power-off protection.
2. Under normal circumstance, if batteries should be found in poor performance, replacement should be done as soon as possible only by qualified personnel with proper training.
Users are not allowed to replace without authorization.
Remark:
A. Prior to battery replacement, switch off UPS and remove it from AC.
B. Take off metallic articles such as rings and watches.
C. Use screw drivers equipped with insulated handles and do not place tools or other metallic substances on the batteries.
D. Short circuit or reverse connection is forbidden for battery polarity connection.
3. It’s not recommended to replace batteries individually. Complete replacement should follow instructions given by battery suppliers.
4. Make sure UPS vent are properly ventilated and clean side frames and fan vents from dusts every half a year (switch off AC and battery cabinet prior to cleaning)
The troubleshooting procedure gives simple remedial if a malfunction occurs in the UPS.
The operator should start the trouble shooting if there is an active alarm indicated on the LCD screen. Service should be contacted if the active alarm is abnormal and displayed as a service code.
Should maintenance prove necessary, the following steps should be followed:
1. Check if UPS input wiring is done properly.
2. Check if all air switches are tripped out.
3. Check if voltage input is within specified range
Please refer to “Light Reference Table” of this User Manual first and then conduct proper treatment. If problems still exist, please record UPS model, serial number as well as purchase date, symptom on fault, light condition, LCD malfunction or warning information.
45
8.1 Regular service/intervals
The UPS requires very little maintenance if installed in an appropriate environment. In order to ensure maximum availability of the UPS, manufacturer recommends signing a proactive service agreement with a local authorised service provider.
Maintenance Interval
Batteries change 3-5 years or according to battery suppliers recommendations
Batteries test 18 months
Cooling fan change 5 years
8.2 Cooling fan
The cooling fan lifespan of the UPS unit is about 60 000 operating hours. The actual lifespan depends on the environment and ambient temperature.
Fan failure can be predicted by increasing noise from the fan bearings. The fan replacement is recommended once this symptom starts appearing.
Do not use other than manufacturer’s specified spare parts.
46
9 Parallel systems
Note!
Parallel is only connected to identical ports for UPS of same model / kVA rating.
1) Follow installation instructions for general installation requirements.
2)Ventilation spacing between machines should allow for service access.
3) Input wiring for each set of UPS should follow the requirements for that of single unit.Each
UPS input should be connected to the same input patch board.
4) Each UPS output wire should be connected to the output patch board, from which wires are distributed for load as illustrated in following figure.
Remark 1: common battery pack is applicable in parallel machine mode;
Remark 2: each battery pack should be of the same model from the same manufacturer;
Remark 3: requirement of output wiring length:
When the lead from the output terminal of each set of UPS to the output patch board is less than 20m, wire difference should be less than 20%;
When the lead from the output terminal of each set of UPS to the output patch board is longer than 20m, wire difference should be less than 10%.
47
48
Note!
Parrallel wires should be connected as a loop.
10 Recycling the used UPS or battery
Before scrapping UPS or its battery cabinet, the battery bank must be removed. Local requirements must be followed in battery recycling or discard. The removal of batteries is allowed only by authorised service personnel due to high energy and voltage.
Do not discard waste electrical or electronic equipment in the trash. For proper disposal, contact your local collecting/recycling/reuse or hazardous waste center and follow the local legislation.
These symbols indicate on a product:
You can find out which recycling firm is responsible for your neighbourhood by contacting your local authority.
Batteries must not be put in the domestic refuse either!
All consumers have a statutory duty to take all batteries to a collection point in their municipality/district or to a retail store so that they can be disposed of in an environmentally-friendly way,regardless of whether they contain toxic substances.
All batteries should be fully discharged before they are returned for disposal.
PROTECTION OF THE ENVIRONMENT/DISPOSAL OF THE EQUIPMENT.
Do not on any account put your old equipment out with the domestic refuse.
For the sake of the environment,please use your local authority’s collection point set to return and recycle old electric and electronic equipment.
49
11 Warranty
The product is warranted against defects in design, materials and workmanship for a period of twelve (12) months from its original date of purchase. The local office or distributor may grant a warranty period different to the above and refer to local terms of liability as defined in the supply contract.
The UPS manufacturer is not responsible for
1) Any costs resulting from a failure if the installation, commissioning, repair, alternation,or ambient conditions of the equipment do not fulfil the requirements specified in the documentation delivered with the unit and other relevant documentation.
2) Equipment subjected to misuse, negligence or accident
3) Equipment comprised of materials provided or designs stipulated by the purchaser.
Under no circumstances shall the manufacturer, its suppliers or subcontractors be liable for special, indirect, incidental or consequential damages, losses or penalties.
The technical data, information and specifications are valid at the time of printing. The UPS manufacturer reserves the right to modifications without prior notice.
50
12 Display reference Table
51
Should any display or warning message excluded in the above table be found,please contact distributor or call EATON Hot line for advice.
● Indicator light is on
★ Indicator light flashes
Warning include one or more than one of these:
1.EPO active 11.Charger failure
2.Line loss
3.Neutral loss
12.Battery over restrict
13.Battery over temperature
4.Line phase error
5.Bypass loss
6.Bypass phase error
7.Battery open
14.Fan over restrict
15.BUS capacitor over restrict
16.Fan failure
17.Fan disconnected
8.Low battery voltage
9.Over charger
10.Battery reverse
18.Low temperature Battery
19.communication disconnected
20.Auxiliary charger failure
52