advertisement
USER’S MANUAL
Rev. 01/2012
00002
CD3000
E
-3PH
Thyristor Unit
With PROFIBUS-DP from 25A to 600A
CD Automation S.r.l.
Via Picasso 34/36 - 20025 – Legnano (MI) – ITALY
Tel +39 0331 577479 – Fax +39 0331 579479
E-Mail: [email protected]
- WEB: www.cdautomation.com
SUMMARY
2.1 Advantages compared with analog thyristor unit
5.1 Identification of the unit
6.1 Environmental installation conditions
6.2 Dimensions and Fixing holes
7.3 Command Terminals Size S09
7.4 Diagram of control connection Size S09
7.5 Command Terminals Size S11/S13/S14
7.6 Diagram of control connection Size S11/S13/S14
11.5 Action of the Limit Current
12.1 Access to the Electronic boards
12.2 Supply the Electronic Board
14.6 Profibus data table exchange
CD Automation srl CD3000E-3PH from 25A to 500A
1 Important warnings for safety
User’s Manual
This chapter contains important information for the safety. The not observance of these instructions may result in serious personal injury or death and can cause serious damages to the Thyristor unit and to the components system included.
The installation should be performed by qualified persons.
The Thyristor unit are integral part of industrial equipments. When it is supply, the
Thyristor unit is subject to dangerous tensions.
Don't remove the protection Cover.
Don't use these unit in aerospace applications and/ or nuclear.
The nominal current corresponds to use at temperature not superior to 45°C.
The Thyristor unit must be mounted in vertical position and without obstruction above and below to allow a good flow ventilation.
The hot air of one thyristor unit must not invest the unit positioned above.
For side by side placed leave a space of 15mm between the unit.
A suitable device must ensure that the unit can be electrically isolated from the supply, this allows the qualified people to work in safety.
Protection (Protection, Protezione)
The unit have IP20 protection rating as defined by the specific international. Is necessary consider the place of installation.
Earth (Terre, Messa a terra)
For safety, the Thyristor unit with isolated heat-sink must be connected to earth.
Earth impedance should be correspondent to local earth regulation. Periodically the earth efficiency should be inspected.
Electronic supply (Alimentation électronique, Alimentazione elettronica)
The electronic circuit of the Thyristor unit must be supplied by dedicated voltage for all electronic circuits and not in parallel with coil contactors, solenoids and other.
It's recommended to use a shielded transformer.
Electric Shock Hazard (Risque de choque électrique, Rischi di scosse elettriche)
When the Thyristor unit is energized, after the power supply is shut off, wait least a minute for allow the discharge of the internal capacitors where there is a dangerous tension. Before working, make sure that:
Only authorized personnel must perform maintenance, inspection, and replacement operations.
The authorized personnel must read this manual before to have access to the unit.
Unqualified People don't perform jobs on the same unit or in the immediate vicinities.
4
CD Automation srl CD3000E-3PH from 25A to 500A User’s Manual
Important warnings (Attention, Avvertenze importanti)
During the operations with units under tension, local regulations regarding electrical installation should be rigidly observed:
Respect the internal safety rules.
Don't bend components to maintain insulation distances.
Protect the units from high temperature humidity and vibrations.
Don't touch components to prevent electrostatic discharges on them.
Verify that the size is in line with real needs.
To measure voltage current etc. on unit, remove rings and other jewels from fingers and hands.
Authorized personnel that work on thyristor unit under power supply voltage must be on insulated board
This listing does not represent a complete enumeration of all necessary safety cautions.
Electromagnetic compatibility
(Compatibilità électromagnétique, Compatibilità elettromagnetica)
Our thyristor units have an excellent immunity to electromagnetic interferences if all suggestions contained in this manual are respected. In respect to a good Engineering practice, all inductive loads like solenoids contactor coils should have a filter in parallel.
Emissions (Emission, Emissioni)
All solid-state power controllers emit a certain amount of radio-frequency energy because of the fast switching of the power devices.
The CD Automation’s Thyristor unit are in accord with the EMC norms, CE mark.
In most installations, near by electronic systems will experience no difficulty with interference. If very sensitive electronic measuring equipment or low-frequency radio receivers are to be used near the unit, some special precautions may be required. These may include the installation of a line supply filter and the use of screened (shielded) output cable to the load.
Note
Warning: This icon is present in all the operational procedures where the Improper operation may result in serious personal injury or death
Caution: This icon is present in all the operational procedures where the Improper operation can cause damage for the Thyristor unit.
CD Automation reserves the right to modify the own products and this manual without any advise.
C
LISTED
US
5
CD Automation srl
2 Introduction
CD3000E-3PH from 25A to 500A User’s Manual
A thyristor unit is semiconductor device which acts as a switch formed by two thyristors in ant parallel.
To switch on the alternating current the input signal will be on and the thyristor will switch off at first
Zero Crossing voltage with no input signal.
The benefits of thyristor units compared with elettromechanical contactors are numerouses: no moving parts, no maintenance and capacity to switch very fast. Thyristors are the only solution to control transformers and special loads that change resistance with temperature and with age.
2.1 Advantages compared with analog thyristor unit
CD3000E is an universal Thyristor unit, designed to control resistive or inductive loads including three phase transformers. The electronic circuit is completely digital and is based on a powerful microprocessor with high performance that allow the use in different ways:
Single cycle
Burst Firing with soft start and current limit
Delayed triggering
Phase Angle with soft start and current limit
On same unit can be used different feed back that define the control mode:
Voltage
Current
Power VxI
External 0÷10Vdc
On same unit can be used different input:
4÷20mA
0÷10Vdc
Potentiometer 10KΩ
SSR
Communication RS485 is a standard feature of CD3000E this allows the use of many information like: tension, current, power, load state and all the parameters for diagnostic and configuration. Ulterior advantages of the digital system vs the analogical is the flexibility and the possibility of implement special characteristics without change the hardware. Several strategies can be implemented and selected through the configuration parameters.
With CD-KP, you can have access to the configuration parameters without expose at the dangerous voltage inside the cabinet and without stop the plant.
6
CD Automation srl
2.2 CD-KP
CD3000E-3PH from 25A to 500A User’s Manual
The CD-KP is designed to be connected with all CD Automation's Thyristor units via RS485 communication. On front unit is possible to read the principal operational parameters of the unit like: power, tension, current, reference, alarms, etc.
One of these variables can be selected and retransmitted via an isolated output (4÷20mA or 0÷10V)
All the menus (except the operator menu) can be protected by password to avoid accidental change of configuration parameters by unauthorised personnel.
On front unit is also available a plug-in connector RS485 for connect a PC with the Thyristor units without open the cabinet and without stop the production process.
Technical Specification:
Use in Local/Remote
Set Point Ramp UP - Down
Scroll selection of:
- Set point
- Power output
- Current
- Voltage
Display indication for:
- Heater Break alarm
- SCR short circuit
Password for configuration parameters
Plug-in connector on front to use software configurator
Retransmission (4-20mA or 0-10Vdc) of one of these parameters: Power PV, Current, Voltage.
Dimension 48x96x92mm (LxAxP)
Comply with EMC, CE marked
2.3 CD-EASY
CD-EASY is a Memory of support used for maintenance people that is not confident in personal computer.
With the CD-EASY is possible memorize the configuration of one Thyristor Unit and paste it into another in few seconds.
CD-EASY could be loaded with the personal configuration of the unit and stored together with the system drawings in a convenient place, enabling unit reconfiguration within seconds if require.
7
CD Automation srl CD3000E-3PH from 25A to 500A
2.4 Software Configurator
User’s Manual
The software configuration is free and is possible download it from our site: www.cdautomation.com
If the Order Code is in line with requirement, then
CD3000E has been already configured in Factory and it's ready to use.
You need the software only to modify the ordered configuration. Anyway we suggest to check the unit on the machine with the "Test unit" section.
For install the software, launch the program and follow the instructions on the screen.
To connect the unit at the PC, it's necessary use the programming cable connected between the PG
connector (see par. 12.7) and the serial port
RS232 of the PC.
The programming cable is not included.
8
With the CD-RS serial converter is possible configure the Thyristor unit also through the
For this solution, the programming cable is not necessary.
Run the software configurator and set the serial port of the PC like the parameters P114 and
P115 of the Thyristor unit.
CD Automation srl
3 Quick Start
CD3000E-3PH from 25A to 500A User’s Manual
Caution: this procedure must be performed only by qualified persons.
If the Order Code of the Thyristor unit is in line with what you really need, then CD3000E has been already configured in Factory and you just need to do the following steps:
1. Verify the CD3000E Sizing. Making sure that:
The load current is equal or less than the MAX current of CD3000E.
The load voltage is equal or less than the MAX voltage of CD3000E.
2. Verify the Order Code
3. Verify the Installation
4. Verify the Diagram of control connection:
All auxiliary connections must be done in line with wirings on this manual.
Verify that there isn’t a short circuit on the load.
5. Supply the Electronic boards
(see Order Code)
6. If not specified in the Order Code:
Set the Load Voltage in the parameter P116 .
Set the Load Current in the parameter P119 .
7. Make the Current Limit Procedure
8. With Burst Firing (BF) or Heater Break Alarm (HB) make the Calibration procedure
The CD3000E Thyristor unit is ready to start.
9
CD Automation srl
4 CD3000E Sizing
CD3000E-3PH from 25A to 500A
4.1.1 Star wiring with resistive load
I
P
1, 73
V
V = Nominal voltage phase to phase
I = Nominal current of the load
P = Nominal power of the load
4.1.2 Star wiring with inductive load
I
1
,
73
V
P
cos
V = Nominal voltage phase to phase
I = Nominal current of the load
P = Nominal power of the load
4.1.3 Delta wiring with resistive load
I
P
1, 73
V
V = Nominal voltage phase to phase
I = Nominal current of the load
P = Nominal power of the load
4.1.4 Delta wiring with inductive load
I
1
,
73
V
P
cos
V = Nominal voltage phase to phase
I = Nominal current of the load
P = Nominal power of the load
4.1.5 Open Delta wiring with resistive load
I
P
3
V
V = Nominal voltage phase to phase
I = Nominal current of the load
P = Nominal power of the load
User’s Manual
10
CD Automation srl CD3000E-3PH from 25A to 500A
5 Identification and Order Code
5.1 Identification of the unit
User’s Manual
Caution: Before to install, make sure that the Thyristor unit have not damages. If the product has a fault, please contact the dealer from which you purchased the product.
The identification's label give all the information regarding the factory settings of the Thyristor unit, this label is on the unit, like represented in figure.
Verify that the product is the same thing as ordered (see par. 5.2).
11
CD Automation srl
5.2 Order Code
CD3000E-3PH from 25A to 500A
Model
CD3000E-3PH
1 2 3 4 5 6 7 8 9 10
1 Max Current of CD3000E
25A
35A
45A
75A
100A
125A
150A
225A
The Max Current must be equal or more than Load Current
2 Load Current
Specify this value to configure the unit in CD Automation
300A
350A
3 Load Voltage
Specify this value to configure the unit in CD Automation
4 Max Voltage of CD3000E
480V
5 Load Connection
3S
4S
Star
Star + neutral
600V
The Max Voltage must be equal or more than Load Voltage
3D
6D
Delta
Open Delta
400A
450A
6 Voltage supply for the Electronic boards
110V From 100 to 130Vac 230V From 210 to 265Vac
7 Load Type
RES
TRA
Resistive
Transformer
IRSW
IRW
Infrared short wave form
Infrared medium and long
CR Cold resistance
If the load is transformer that supply a normal resistive load write TRA+RES
8 Firing Type
SC
PA
Single Cycle
Phase Angle
S+PA Soft Start + Phase Angle
V
I
10 Input
DT Delay Triggering
Burst Firing
S+BF___ Soft Start + Burst Firing
Specify the number of firing cycles at 50% of the input signal (from 1 to 255)
9 Feed-Back
Voltage
Current
W
EX
Power
External (0÷10Vdc)
0÷10V 0÷10Vdc
4÷20mA 4÷20mA
POT
Comm
Potentiometer 10KΩ
RS485
Specify if you use the second analogical input, example: 0÷10V + 4÷20mA
11 External Current Profiler or External Feed-Back
0÷10V 0÷10Vdc POT Potentiometer 10KΩ
Comm RS485
If you don't use the External Current Profiler or External Feed-Back, write: NONE
12 Retransmission
010 0÷10Vdc 020 0÷20mA 420 4÷20mA
13 Option
CD-KP External Keypad
FUMS Fuse Microswitch
NO-HB Without Heater Break alarm
UL UL Certification
11
12
User’s Manual
12
500A
600A
13
CD Automation srl
6 Installation
CD3000E-3PH from 25A to 500A User’s Manual
Caution: Don't install near the hot elements or near the units that could give electromagnetic interferences.
The CD3000E Thyristor unit must be always mounted in vertical position to improve air cooling on heatsink. Maintain the minimum distances in vertical and in horizontal as represented.
When more unit has mounted inside the cabinet maintain the air circulation like represented in figure.
Sometimes is necessary installing a fan to have better air circulation.
6.1 Environmental installation conditions
Ambient temperature
0-45°C at nominal current. Over 45°C use the
Storage temperature
Installation place
Altitude
Humidity
-25°C to 70°C
Don’t install at direct sun light, where there are conductive dust, corrosive gas, vibration or water and also in salty environmental.
Up to 1000 meter over sea level. For higher altitude reduce the nominal current of 2% for each
100m over 1000m
From 5 to 95% without condense and ice
13
CD Automation srl CD3000E-3PH from 25A to 500A
6.2 Dimensions and Fixing holes
User’s Manual
96mm
5mm
7mm
Size S09
(25A÷75A)
Weight 5kg
116 mm
18
7m m
104mm
97mm
7mm
12mm
Size S11
(100A÷150A)
Weight 10,5kg
137 mm
27
0m m
97mm
222mm
7mm
12mm
Size S13
(225A)
Weight 18kg
262 mm
27
0m m
222mm
222mm
7mm
12mm
Size S14
(300A÷600A)
Weight 22,5kg
262 mm
27
0m m
222mm
14
CD Automation srl
6.3 Removing the cover
CD3000E-3PH from 25A to 500A
Remove the screw, if present
Size S09
Open the unit
Screw
Open
Remove the screw, if present
Screw
Size S11
Remove the plastic cover
User’s Manual
Open the unit
Open
Screw
Remove the screw
Screw
Screw
Size S13/S14
Remove the plastic cover Open the unit
Open
Screw
Screw
15
CD Automation srl
7 Wiring instructions
CD3000E-3PH from 25A to 500A User’s Manual
Caution: this procedure must be performed only by qualified persons.
The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply, for this reason in accord to the fundamental practices rules is opportune take some precautions:
The electronic circuit of the Thyristor unit must be supplied from a dedicated voltage and not with inductive or capacitive loads. We recommend the use of a screened transformer.
The coil contactor, the relays and other inductive loads must be equipped with opportune RC filter.
Use shielded bipolar cables for all the input and output signals.
The signal cables must not be near and parallel to the power cables.
Local regulations regarding electrical installation should be rigidly observed.
For safety connect the heat-sink to the earth with his terminal.
7.1 Wiring details
Use copper cables and wires rated for use at 75°C only.
7.1.1 Power cable torque (suggested)
Current
Connector
Type
Torque
Lb-in (N-m)
Wire
Range
AWG / kcmil
Wire
Terminal
25A÷225A
Terminal Block
M8
265 (30.0)
8
4/0
Copper wire
Compact (Solid) Stranded
300A
Bus Bar with M8 screw
505 (57.0)
2x1/0
350
UL Listed (ZMVV)
Copper Tube Crimp. Lug
505 (57.0)
2x3/0
600
UL Listed (ZMVV)
Copper Tube Crimp. Lug
350A÷400A
Bus Bar with M10 screw
450A
Bus Bar with M10 screw
500÷600A
Bus Bar with M10 screw
505 (57.0)
505 (57.0)
Bus Bar 30x6mm
Bus Bar 60x4mm
16
CD Automation srl CD3000E-3PH from 25A to 500A
7.1.2 Power cable dimensions (suggested)
Power Supply Cable Load Cable (Output)
Current
25A (S09)
35A (S09)
45A (S09)
75A (S09)
100A (S11)
125A (S11)
150A (S11)
25
35
50
70
mm²
10
10
10
AWG
8
8
8
4
3
1
1/0
25
35
50
70
mm²
10
10
10
225A (S13)
300A (S14)
350A (S14)
400A (S14)
120
2 x 70
2 x 95
2 x 95
4/0
2 x 1/0
2 x 3/0
2 x 3/0
120
2 x 70
2 x 95
2 x 95
4/0
2 x 1/0
2 x 3/0
2 x 3/0
450A (S14)
500A (S14)
Bus Bar 30 x 6 mm
Bus Bar 60 x 4 mm
Bus Bar 30 x 6 mm
Bus Bar 60 x 4 mm
600A (S14) Bus Bar 60 x 4 mm Bus Bar 60 x 4 mm
7.1.3 Cable dimensions of the Command Terminals
Maximum connection capacity for all size: 1.5 mm2 (14 AWG)
AWG
8
8
8
4
3
1
1/0
User’s Manual
70
70
70
25
50
50
50
10
16
16
16
mm²
4
6
6
Earth
1/0
1/0
1/0
1
1
4
1
6
6
8
6
AWG
12
10
10
17
CD Automation srl
7.2 Power Terminals
CD3000E-3PH from 25A to 500A User’s Manual
Terminal
Warning: Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources.
Description
L1
L2
Line Input Phase 1
Line Input Phase 2
L3
T1
T2
T3
Line Input Phase 3
Load Output Phase 1
Load Output Phase 2
Load Output Phase 3
Size S14
L1 L2 L3
Size S11
L1 L2 L3
L1
Size S13
L2 L3
Size S09
L1 L2 L3
T1 T2 T3
18
CD Automation srl CD3000E-3PH from 25A to 500A
7.3 Command Terminals Size S09
User’s Manual
Warning: Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources.
Terminal
1
2
3
4
5
10
11
12
13
6
7
8
9
14
15
16
17
18
19
20
Description
Voltage Supply for Electronic Boards (See par. 12.2)
Voltage Supply for Electronic Boards (See par. 12.2)
Not used
Isolated output +12Vdc MAX 20mA
GND for Digital Input
Output +10Vdc MAX 5mA
GND for Analogue Input
(+)Analogue Input 1: Primary (See par. 12.3)
(+)Analogue Input 2: Ext. Current (See par. 12.3)
Analogue Output 1: Power (See par. 12.4)
RS485 B
RS485 A
Output relay: Run (Max 500mA, 125Vac)
Common of the contact relay: Run
NPN Output 1: Critical Alarm (12Vdc max 20mA)
NPN Output 2: Configurable (12Vdc max 20mA)
Digital Input: Reset Alarm
Digital Input: Start/Stop
Digital Input: Calibration
Digital Input: Configurable
19
CD Automation srl CD3000E-3PH from 25A to 500A
7.4 Diagram of control connection Size S09
L1
Caution: this procedure must be performed only by qualified persons.
L2 L3
* 1
K1
* 2
CD-KP
(option)
Pot.10K
0-10Vdc
-
4-20mA
-
+
+
-
+
User’s Manual
+
mA
+
V
L1 L2 L3
M
1 2 A B
RS485
T1 T2 T3
8
Input 1
9
Input 2
4
12Vdc
+ -
5 17 18 19 20 15 16
6 7
+
10Vdc
-
10
Run
*
13
4
14
* 3
K1
* 4
TO LOAD
NOTE:
The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator.
*² Use an appropriate external transformer based on the voltage supply of the electronic board
(see the identification label)
*³ The coil contactor, the relays and other inductive loads must be equipped with opportune RC
filter.
Before give the Start command supply the auxiliary voltage.
Load Type
T1 T2 T3 T1 T2 T3 L1 L3 L2 T1 T2 T3 T1 T2 T3 N
Delta Open Delta
20
Star Star + Neutral
CD Automation srl CD3000E-3PH from 25A to 500A
7.5 Command Terminals Size S11/S13/S14
User’s Manual
Warning: Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources.
Terminal
1
2
3
4
Internal use
Internal use
RS485 A
RS485 B
Description
Terminal
1
2
3
4
5
6
7
12
13
14
15
8
9
10
11
16
17
18
19
20
Description
Voltage Supply for Electronic Boards (See par. 12.2)
Voltage Supply for Electronic Boards (See par. 12.2)
Not used
Isolated output +12Vdc MAX 20mA
GND for Digital Input
Output +10Vdc MAX 5mA
GND for Analogue Input
(+)Analogue Input 1: Primary (See par. 12.3)
(+)Analogue Input 2: Ext. Current (See par. 12.3)
Analogue Output 1: Power (See par. 12.4)
Output relay: Conf (Max 500mA, 125Vac)
Common of the contact relay: Conf
Output relay: Run (Max 500mA, 125Vac)
Common of the contact relay: Run
NPN Output 1: Critical Alarm (12Vdc max 20mA)
NPN Output 2: Configurable (12Vdc max 20mA)
Digital Input: Reset Alarm
Digital Input: Start/Stop
Digital Input: Calibration
Digital Input: Configurable
21
CD Automation srl CD3000E-3PH from 25A to 500A
7.6 Diagram of control connection Size S11/S13/S14
L1
Caution: this procedure must be performed only by qualified persons.
L2 L3
* 1
K1
* 2
CD-KP
(option)
Pot.10K
0-10Vdc
-
4-20mA
-
+
+
-
+
User’s Manual
+
mA
+
V
L1 L2 L3
M
1 2 A B
RS485
T1 T2 T3
8
Input 1
9
Input 2
4
12Vdc
+ -
5 17 18 19 20 15 16
6 7
+
10Vdc
-
10
Conf
*
11
4
12
Run
*
13
4
14
* 3
K1
* 4
TO LOAD
NOTE:
The user installation must be protecting by electromagnetic circuit breaker or by fuse isolator.
*² Use an appropriate external transformer based on the voltage supply of the electronic board
(see the identification label)
*³ The coil contactor, the relays and other inductive loads must be equipped with opportune RC
filter.
Before give the Start command supply the auxiliary voltage.
Load Type
T1 T2 T3 T1 T2 T3 L1 L3 L2 T1 T2 T3 T1 T2 T3 N
Delta Open Delta
22
Star Star + Neutral
CD Automation srl CD3000E-3PH from 25A to 500A
8 Power output features
Current
(A)
25A
35A
45A
Voltage range
(V)
Repetitive peak reverse voltage
(480V) (600V)
330÷600
330÷600
330÷600
1600
1600
1600
1600
1600
1600
Latching current
(mAeff)
450
450
450
Max peak one cycle
(10msec.)
(A)
500
1000
1000
Leakage current
(mAeff)
15
15
15
User’s Manual
I
2
T value max
tp=10msec
Frequency range
(Hz)
Power loss
I=Inom (W)
Isolation
Voltage
Vac
1030
4750
4810
47÷70
47÷70
47÷70
90
126
162
2500
2500
2500
75A
100A
125A
150A
225A
300A
350A
400A
450A
500A
330÷600
330÷600
330÷600
330÷600
330÷600
330÷600
330÷600
330÷600
330÷600
330÷600
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
600A 330÷600 1600 1600
8.1 Derating curve
1600
1600
1600
1600
1600
1600
1600
1600
1600
1600
300
300
200
200
450
450
450
450
1000
1000
1000
1000
1540
2000
2000
4800
5250
7800
8000
17800
17800
17800
15
15
15
15
15
15
15
15
15
15
15
4810
11300
19100
19100
108000
128000
300000
306000
1027000
1027000
1027000
47÷70
47÷70
47÷70
47÷70
47÷70
47÷70
47÷70
47÷70
47÷70
47÷70
47÷70
810
1080
1260
1440
270
360
450
540
1620
1800
2160
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
2500
K
1
0.8
0.6
0.4
0.2
0
45 55 65 75 85
°C
8.2 Cooling fans
The CD3000E thyristor unit is equipped with a cooling fans. The supply votage is the same of the
electronic board (see par. 12.2). The fan’s power consumption is below listed:
Size
25A ÷ 150A
225A
350A, 450A
300A, 400A, 500A,600A
Number of fans
One Fan - 17W
Two Fans - 30W
Two Fans - 30W
Four Fan - 60W
C
LISTED
US
Number of fans
One Fan - 17W
Two Fans - 30W
Four Fan - 60W
Four Fan - 60W
23
CD Automation srl CD3000E-3PH from 25A to 500A
9 Led status and Alarms
9.1 LED Status Table
On the Electronic board there are LED that indicates the state of the Electronic cards:
LED
For All size
STATUS DESCRIPTION
User’s Manual
The power supply is not connected or fault on the electronic board
AUX Fault on the electronic board
All ON
SC
HB
Electronic board is OK
No alarm
In Alarm
Critical Alarm
SCR OK
SCR short circuit
Laod OK
Load Fault
Current limit active
= OFF
= ON
= Lampeggiante
24
CD Automation srl
9.2 Critical Alarms
CD3000E-3PH from 25A to 500A User’s Manual
When a critical alarm is active, it stops the CD3000E thyristor unit and activates the relative digital output (terminal 15).
The parameter P001 allows to visualize the state of these alarms (see par. 13.1).
9.2.1 Phase loss
This critical alarm is active when one of the three phases R-S-T is loss. The phase loss could be also activated by an interrupted fuse.
For restart the thyristor unit, check the presence of the line voltage on the power terminals L1, L2, L3 and check the state of the internal fuses, When the problem is solved before to restart is necessary use
the digital input: "Reset Alarm" (see par. 12.5).
9.2.2 External Alarm
This critical alarm is active when the Digital input 4 is configured like “External Alarm" and is activated.
For restart the thyristor unit, you must disarm the external alarm. When the problem is solved before to
restart is necessary use the digital input: "Reset Alarm" (see par. 12.5).
9.2.3 Heat-sink Over temperature
This critical alarm is active when the thermal switch mounted on the heat-sink is activated.
For restart the thyristor unit, you must wait that the heat-sink returns at the safety temperature. When the problem is solved before to restart is necessary use the digital input: "Reset Alarm"
If this alarm becomes active, check if the indications described in the “par. 6” of this manual are
respected.
Caution: this procedure must be performed only by qualified persons.
25
CD Automation srl
9.3 Not Critical Alarm
CD3000E-3PH from 25A to 500A User’s Manual
The Not Critical Alarm, doesn’t stop the CD3000E thyristor unit, but is possible to associate an digital
output at these alarms (see par. 12.6).
The parameter P002 allows to visualize the state of these alarms (see par. 13.1).
9.3.1 SCR Short Circuit
This alarm is active when CD3000E read the output current in absence of the input signal. This is possible if there are a short circuit on the thyristor or if there are a wrong wiring of the load.
When the problem is solved is necessary use the digital input: "Reset Alarm" (see par. 12.5).
9.3.2 Unbalanced Load
This alarm is active when one of the three load current (read on the terminals T1, T2, T3) differs from the others more than 30%.
The unbalanced alarm could be active also if there are a wrong wiring of the load.
When the problem is solved is necessary use the digital input: "Reset Alarm" (see par. 12.5).
9.3.3 Heater Break alarm (HB)
This alarm is active when the load current decrease under the threshold set on the parameter P066
The Heater Break alarm could be active also if there are a wrong wiring of the load.
When the problem is solved is necessary use the digital input: "Reset Alarm" (see par. 12.5).
The Heater Break alarm to work properly must have an input signal more then 25% of the nominal current value.
Caution: In the first start, and each time that the load is replaced, it’s necessary make the
Calibration procedure.
9.4 Calibration Procedure
The Calibration procedure is an automatic procedure that save in memory the three different values of load current (for each phase)
This procedure is necessary if you use the Burst Firing (BF) or if you use the Heater Break Alarm.
To make the Calibration procedure follow these steps:
Give the power supply and start the thyristor unit (see par. 12.5).
Activate the digital input: "Cal" (terminal 19).
The CD3000E thyristor unit give the maximum output voltage.
After a few seconds the values of voltage and current are stored in memory.
The CD3000E thyristor unit returns to the initial situation.
Stop the thyristor unit.
The Calibration procedure is done.
26
CD Automation srl
10 Control Panel
CD3000E-3PH from 25A to 500A User’s Manual
The Control Panel is placed on the front of the thyristor unit, on his display you can visualize the alarms,
the input and output signals and all the configuration parameters (see par. 0).
SELECTION Key ENTER Key
DOWN Key UP Key
The function keys is the following:
The SELECTION key is used for enter and exit from the menu.
The UP key and DOWN key is used to scroll the parameters in the menu and to change data.
The ENTER key is used to edit the parameters and to save the modified values.
The Control Panel have three menu, and to enter in one of them you must set correctly the parameter
P000 :
Operator Menu (P000 = 0)
This menù contains a reading parameters that give information on the state of the unit, it include also the base parameters for quick start, like the value of current and voltage load and the Set-point data.
Hardware Menu (P000 = 5)
This menu contains all the configuration parameters for analogic and digital I/O, and the parameters to set the serial port like the address and the baudrate.
Setup Menu (P000 = 10)
This menù contains all the setting parameters to configure the thyristor unit, like the firing type, the current limit, [ecc].
27
CD Automation srl CD3000E-3PH from 25A to 500A
10.1 Scroll the parameters
Operator Menu
Hardware Menu
Setup Menu
28
User’s Manual
CD Automation srl
11 Firing type
CD3000E-3PH from 25A to 500A User’s Manual
Choose an correct firing type allows to optimize the thyristor unit for the installed load.
The firing type has already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the firing type you can use the software configurator or the Control Panel
Caution: this procedure must be performed only by qualified persons.
11.1 Single Cycle (SC)
Single Cycle it's the faster zero crossing switching method in relationship of the power demand from a temperature regulator or from an external signal.
With input signal at 25% the output is one cycle ON and three cycles OFF
With input signal at 50% the output is one cycle ON and one cycle OFF
With input signal at 75% the output is three cycles ON and one cycle OFF
With input signal at 76% the output is the same of 75% but for each ON cycle the microprocessor divides 76/75, and when the sum of rests is one, the unit does one more cycle ON. For this firing is necessary to have analog input.
The Single Cycle is used to control the loads with low inertia or for infrared lamps to short wave.
ON OFF
VOLTAGE SUPPLY (V)
LOAD VOLTAGE (V)
25%
50%
75%
100%
29
CD Automation srl CD3000E-3PH from 25A to 500A
11.1.1 Suggested recipe for Single Cycle
User’s Manual
The firing type has already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the firing type you can use the software configurator or the Control Panel
Caution: this procedure must be performed only by qualified persons.
Parameter Name
P003 (H03)
P004 (H04)
P019 (H13)
P024 (H18)
P025 (H19)
P116 (H74)
P119 (H77)
Value
0
100
0
0
V Load
I Load
OPERATOR MENU
Description
Setpoint selection Analog/Digital
Digital Setpoint value
Maximum Output
Setpoint Ramp Up
Setpoint Ramp Down
Operative load voltage
Load nominal current
Parameter Name
P023 (H17)
P066 (H42)
P070 (H46)
P083 (H53)
P084 (H54)
P085 (H55)
P090 (H5A)
P091 (H5B)
P098 (H62)
0÷
Value
0
20
1
1
0
0
1
0÷3
SETUP MENU
Description
Firing Type
HB sensitivity
Feed back selection
Burst Firing Cycles (Not used in Phase Angle)
Ramp Cycles of Burst (Not used in Phase Angle)
Delay triggering
Limit current Analog/Digital
Digital Limit current value
Define the load type connection:
0=star
1=star+N
2=delta
3=open delta
= modification is not necessary
= modification is necessary
If the current limit is not used set this value to 100,0%
%
UM Mode
R/W
R/W
%
Sec
Sec
V
A
%
°
R/W
R/W
R/W
R/W
R/W
UM Mode
R/W
%
R/W
R/W
Cycles R/W
Cycles R/W
R/W
R/W
R/W
R/W
30
CD Automation srl
11.2 Burst Firing (BF)
CD3000E-3PH from 25A to 500A User’s Manual
The Burst Firing is similar to the Single Cycle, but consecutive cycles ON are selectable between 2 and
255, with input signal equal at 50%.
Burst Firing is a method zero crossing that it reduces the electromagnetic interferences because the thyristor switches at zero voltage crossing.
The example show the Burst Firing with Burst cycles: P083 =4
ON OFF
VOLTAGE SUPPLY (V)
LOAD VOLTAGE (V)
25%
50%
75%
100%
11.2.1 Soft Start with Burst Firing (S+BF)
This is an additional function to the Burst Firing. The unit start in phase angle mode with a ramp starting from zero up to the full tension in the cycles number set in the parameter P084 .
When the ramp is over, the thyristor unit will stay in conduction at full voltage up to the end of cycles of burst. The S+BF firing is used to control small inductive loads to avoid inrush surge current and to reduce the electromagnetic interferences.
The example show the firing with Burst cycles: P083 =4 and ramp cycles: P084 =3
ON OFF
VOLTAGE SUPPLY (V)
LOAD VOLTAGE (V)
25%
50%
75%
100%
31
CD Automation srl CD3000E-3PH from 25A to 500A
11.2.2 Suggested recipe for Burst Firing
User’s Manual
The firing type has already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the firing type you can use the software configurator or the Control Panel
Caution: this procedure must be performed only by qualified persons.
Parameter Name
P003 (H03)
P004 (H04)
P019 (H13)
P024 (H18)
P025 (H19)
P116 (H74)
P119 (H77)
Value
0
100
0
0
V Load
I Load
OPERATOR MENU
Description
Setpoint selection Analog/Digital
Digital Setpoint value
Maximum Output
Setpoint Ramp Up
Setpoint Ramp Down
Operative load voltage
Load nominal current
Parameter Name
P023 (H17)
Value
0
SETUP MENU
Firing Type
Description
P066 (H42)
P070 (H46)
20
1
HB sensitivity
Feed back selection
P083 (H53) 8 Burst Firing Cycles (Not used in Phase Angle)
P084 (H54) <P083 ² Ramp Cycles of Burst (Not used in Phase Angle)
P085 (H55)
P090 (H5A)
P091 (H5B)
P098 (H62)
0÷
0
1
0÷3
Delay triggering
Limit current Analog/Digital
Digital Limit current value
Define the load type connection:
0=star
1=star+N
2=delta
3=open delta
= modification is not necessary
= modification is necessary
If the current limit is not used set this value to 100,0%.
² If don't use the ramp soft start (S+BF) set this value to 0.
%
UM Mode
R/W
R/W
%
Sec
Sec
V
A
R/W
R/W
R/W
R/W
R/W
%
UM Mode
R/W
R/W
R/W
Cycles R/W
Cycles R/W
°
%
R/W
R/W
R/W
R/W
32
CD Automation srl
11.3 Phase Angle (PA)
CD3000E-3PH from 25A to 500A User’s Manual
The Phase Angle firing allow the control of the power on the load, for this firing the thyristor can be in conduction only for a part of the voltage cycle.
This part of the voltage cycle is adjustable in function of the input signal from 0 at 100%.
The PA firing is normally used for control the inductive loads, and is also possible control a primary of transformer coupled with the cold resistances like: Superkanthal, Molybdenum, Platinum, Tungsten or
Quartz Lamp. The only disadvantage with phase angle is the possible generation of interferences that however can be reduced with opportune filters.
ON OFF
VOLTAGE SUPPLY (V)
LOAD VOLTAGE (V)
25%
50%
75%
100%
11.3.1 Soft Start with Phase Angle (S+PA)
This is an additional function to the Phase Angle. The firing angle of the thyristor increase or decrease up to the final setpoint value.
The Soft start ramp is an important feature to reduce the inrush current with transformers during the during the cycle of magnetization or with cold resistance that are near to the short circuit when they are supplied.
Setpoint Ramp Up : P024
Setpoint Ramp Down: P025
ON OFF
VOLTAGE SUPPLY (V)
Setpoint Value (%)
100%
0%
Load voltage RMS (V)
Ramp Up
OUTPUT VOLTAGE (V)
Ramp Down
33
CD Automation srl CD3000E-3PH from 25A to 500A
11.3.2 Suggested recipe for Phase Angle
User’s Manual
The firing type has already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the firing type you can use the software configurator or the Control Panel
Caution: this procedure must be performed only by qualified persons.
Parameter Name
P003 (H03)
P004 (H04)
P019 (H13)
Value
0
100
OPERATOR MENU
Description
Setpoint selection Analog/Digital
Digital Setpoint value
Maximum Output
P024 (H18) 0÷1000² Setpoint Ramp Up
P025 (H19) 0÷1000² Setpoint Ramp Down
P116 (H74)
P119 (H77)
V Load
I Load
Operative load voltage
Load nominal current
Parameter Name
P023 (H17)
P066 (H42)
P070 (H46)
P083 (H53)
P084 (H54)
P085 (H55)
P090 (H5A)
P091 (H5B)
P098 (H62)
0÷
Value
1
20
1
0
1
0÷3
SETUP MENU
Description
Firing Type
HB sensitivity
Feed back selection
Burst Firing Cycles (Not used in Phase Angle)
Ramp Cycles of Burst (Not used in Phase Angle)
Delay triggering
Limit current Analog/Digital
Digital Limit current value
Define the load type connection:
0=star
1=star+N
2=delta
3=open delta
= modification is not necessary
= modification is necessary
If the current limit is not used set this value to 100,0%.
² If don't use the ramp soft start (S+PA) set this value to 0.
%
UM Mode
R/W
R/W
%
Sec
Sec
V
A
%
°
R/W
R/W
R/W
R/W
R/W
UM Mode
R/W
%
R/W
R/W
Cycles R/W
Cycles R/W
R/W
R/W
R/W
R/W
34
CD Automation srl CD3000E-3PH from 25A to 500A
11.4 Delay Triggering (DT)
User’s Manual
The Delay Triggering firing is used the control a primary of transformer coupled with the normal resistances on the secondary (N.B. don't connect cold resistances on the secondary like: Superkanthal,
Molybdenum, Platinum, Tungsten, Quartz Lamp).
For an inductive load (ex transformer), switching the thyristors at zero crossing can generates transient over currents that can blow the fuses, to avoid this problem you must use the Delay Triggering. This firing delay the first half cycle of Burst for an angle from 0 to 100° relative to the zero, besides all the first burst start with soft start ramp to reduce the inrush current during the cycle of magnetization.
Without Delay Triggering With Delay Triggering
Transient over-current
Delay angle
(0° to 100°)
Voltage
Current
Voltage
Current
0 0
Zero
Crossing
Voltage
Zero
Crossing
Voltage
For understand the Delay Triggering firing, we have represented the waves generate by vectors that rotates in counterclockwise:
Without Delay Triggering With Delay Triggering
V
2 y y
I
2
V
2
I
2
V
1 i
3 i
1 i
2
I
1
V x
1 i
3 i
2
Delay Angle
I
1 x
I
3
I
3
V
3
V
3
Without delay at zero crossing when V1 is to zero (projected on the X axis) the unit switch On.
In this case the instantaneous value of the currents are i1, i2 and i3 and this condition, for the curve of magnetization, could generate transient over currents that can blow the fuses.
With Delay Triggering the firing of the thyristor are triggered with a delay until the instantaneous value of the curret i1=0, i2 positive and i3 negative like represented.
In this case the risk of transient over currents is reduced and the fuses don't blow.
The angle alpha is the delay to have i1=0 and this angle depends on the power factor.
The delay angle suggest for most applications is 80°
35
CD Automation srl CD3000E-3PH from 25A to 500A
11.4.1 Suggested recipe for Delay Triggering
User’s Manual
The firing type has already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the firing type you can use the software configurator or the Control Panel
Caution: this procedure must be performed only by qualified persons.
Parameter Name
P003 (H03)
P004 (H04)
P019 (H13)
Value
0
100
OPERATOR MENU
Description
Setpoint selection Analog/Digital
Digital Setpoint value
Maximum Output
P024 (H18) 0÷1000² Setpoint Ramp Up
P025 (H19) 0÷1000² Setpoint Ramp Down
P116 (H74)
P119 (H77)
V Load
I Load
Operative load voltage
Load nominal current
Parameter Name
P023 (H17)
P066 (H42)
P070 (H46)
P083 (H53)
P084 (H54)
P085 (H55)
P090 (H5A)
P091 (H5B)
P098 (H62)
Value
2
20
1
0÷100³
1
0÷
8
0
0÷3
SETUP MENU
Description
Firing Type
HB sensitivity
Feed back selection
Burst Firing Cycles (Not used in Phase Angle)
Ramp Cycles of Burst (Not used in Phase Angle)
Delay triggering
Limit current Analog/Digital
Digital Limit current value
Define the load type connection:
0=star
1=star+N
2=delta
3=open delta
= modification is not necessary
= modification is necessary
If the current limit is not used set this value to 100,0%.
² If don't use the setpoint ramp set this value to 0.
³ The delay angle suggest for most applications is 80°
%
UM Mode
R/W
R/W
%
Sec
Sec
V
A
%
°
R/W
R/W
R/W
R/W
R/W
UM Mode
R/W
%
R/W
R/W
Cycles R/W
Cycles R/W
R/W
R/W
R/W
R/W
36
CD Automation srl CD3000E-3PH from 25A to 500A
11.5 Action of the Limit Current
User’s Manual
The Current Limit is available for each firing type.
It control the firing angle of the thyristor to maintain the three RMS current under the set value.
When the current exceeds this value, the voltage is decreased up to reach the current limit set.
I Load <= I Limit Set I Load > I Limit Set
11.5.1 Current Limit Procedure
The current limit could be set through the analogic input 2: External Current Profiler, or in digital mode through the parameter P091 .
To select Analog/Digital mode use the parameter P090
0 = Analog, Current Limit from analog input (terminals 9-7)
1 = Digital, Current Limit from parameter P091
To make Current Limit Procedure follow these steps:
Caution: this procedure must be performed only by qualified persons.
Give the power supply and set the current limit to zero:
- In analog mode, set the analog input 2 at the min value (ex. 0V for 0÷10Vdc or 4 for 4÷20mA)
- In digital mode, set the parameter P091 =0
Start the thyristor unit (see par. 12.5).
Set the primary input or the setpoint value at 100% (see par. 12.3).
Increase the current limit until to reach the desired value.
Stop the thyristor unit.
The Current Limit Procedure is done.
37
CD Automation srl
11.6 Feed-back type
CD3000E-3PH from 25A to 500A User’s Manual
The Feed-back type has already configured in line with customer requirements that are defined in the
Order Code. The Order Code is written on the identification label.
However, if you wish to change the Feed-back type you can use the software configurator or the Control
Caution: this procedure must be performed only by qualified persons.
The Feed-back type is defined by the parameter P070 (see par. 13.3).
the select Feed-Back with the Voltage Feed-Back (V) simply activating the input.
The feed-back defines the Control Mode. It’s possible to have:
V=Voltage feed-back.
The input signal is proportional to the output voltage. This means that input signal becomes a voltage demand. This control mode compensates the voltage fluctuation of the incoming line supply.
I=Current feed-back.
The input signal is proportional to the current output. This means that input signal becomes a current demand. This control mode maintain the current also if the load impedance changes.
W=Power feed-back.
The input signal is proportional to the power output. This means that input signal becomes a power demand. The power remains constant also if voltage and load impedance change. This control mode is used with silicon carbide elements that change its resistive value with temperature and with age.
In addition it compensates the voltage fluctuation of the incoming line supply.
EX=External feed-back 0÷10Vdc (see par. 12.3).
The input signal is proportional to an external signal. This means that input signal becomes a demand to maintain this signal always constant. This control mode is used for example with galvanic systems, where it's necessary to control the current value through the electrodes.
38
CD Automation srl CD3000E-3PH from 25A to 500A
12 Connection description
12.1 Access to the Electronic boards
To have access to the electronic boards the user must removing the unit’s cover
User’s Manual
Warning: Before operate, be sure that power and control cables are isolated from voltage sources
Size S09 Size S11/S13/S14
12.2 Supply the Electronic Board
The CD3000E thyristor unit, to work, requires a voltage supply for the electronic boards. This voltage is used also to supply the internal fans.
The voltage supply for the electronic boards is configured in line with customer requirements that are defined in the Order Code. The Order Code is written on the identification label.
Warning: Before connecting or disconnecting the unit check that power and control cables
are isolated from voltage sources.
Terminal
1
2
Description
Voltage Supply for Electronic Boards
Voltage Supply for Electronic Boards
39
CD Automation srl
12.3 Analog Inputs
CD3000E-3PH from 25A to 500A User’s Manual
The CD3000E thyristor unit has 2 configurable analog inputs (0÷10V, 4÷20mA, ecc):
The primary input for the analog setpoint, the secondary input for the Current Profiler or Ext. Feed-Back.
12.3.1 Primary Input (Terminals 8 and 7)
The primary input is already configured in line with customer requirements that are defined in the Order
Code. The Order Code is written on the identification label.
However, if you wish to change the primary input (ex. from 0÷10V to 4÷20mA) proceed as follows:
Size S09 Size S11/S13/S14
JP6
Type Input features
0 10V (default) Impedance 40K
POT
4 20mA
Impedance
Impedance
10K
500
min
Jumper
Open
Open
Close
Primary Input calibration procedure
When you change the hardware setting is necessary make the Input calibration procedure.
To make the Input calibration procedure follow these steps:
Give the power supply.
With Control Panel go in the Hardware menu (P000 = 5)
Set the input signal to the min value (ex. 0V for 0÷10V or 4mA for 4÷20mA)
Set the parameter P057 = 1
Press ENTER key
Set the input signal to the max value (ex.10V for 0÷10V or 20mA for 4÷20mA)
Set the parameter P058 = 1
Press ENTER key
The Input calibration procedure is done.
40
JP8
CD Automation srl CD3000E-3PH from 25A to 500A
12.3.2 External Current Profiler (Terminals 9 and 7)
User’s Manual
The secondary input is for the External Current Profiler or for the External Feed-Back. The secondary input is already configured in line with customer requirements that are defined in the Order Code. The
Order Code is written on the identification label.
However, if you wish to change the secondary input proceed as follows:
Caution: this procedure must be performed only by qualified persons
Size S09 Size S11/S13/S14
JP3
C
B
A
Type (0÷10Vdc)
Current Profiler
External Feed-Back
P070 P090
0÷2 0
3 1
Jumper
A-B
B-C
External Current Profiler or External Feed-Back Input calibration procedure
When you change the hardware setting is necessary make the Input calibration procedure.
To make the Input calibration procedure follow these steps:
Give the power supply.
With Control Panel go in the Hardware menu (P000 = 5)
Set the input signal to the min value (ex. 0V for 0÷10V)
Set the parameter P061 = 1
Press ENTER key
Set the input signal to the max value (ex.10V for 0÷10V 5V for 0÷5V)
Set the parameter P062 = 1
Press ENTER key
The Input calibration procedure is done.
41
JP20
C
B
A
CD Automation srl
12.4 Analog Outputs
CD3000E-3PH from 25A to 500A
The CD3000E thyristor unit have 1 analog output (0÷10V, 4÷20mA, ecc).
The output is for retransmitting the average power on the three phases.
User’s Manual
12.4.1 Output 1: Average Power (Terminals 10 and 6 or 10 and 7)
The average power output is already configured in line with customer requirements that are defined in the Order Code. The Order Code is written on the identification label.
However, if you wish to change the average power output (ex. from 0÷10V to 4÷20mA) proceed as follows:
Caution: this procedure must be performed only by qualified persons
Size S09 Size S11/S13/S14
JP2
C B A
Type
4 20mA
Output features
0 10V (default) 20mA Max
0 20mA 500 Max
500 Max
P097
0
0
1
Jumper
A-B
B-C
B-C
Setting the Output Value
The parameter P104 allows to set the full scale value to have the maximum output, for example if you use an indicator with full scale 50Kw set the parameter P104 = 50.
42
JP21
C B A
CD Automation srl
12.5 Digital Input
CD3000E-3PH from 25A to 500A User’s Manual
The CD3000E thyristor unit has 4 digital inputs opto-isolated to 12Vdc.
You can activate the inputs with the internal supply (see par. 7.4) or with an external source for
example the PLC.
12.5.1 Reset alarm (Terminal 17)
The Reset Alarm is used for restore the unit after an alarm occurs.
Before using this input you must resolve the fault or the alarm status come back.
12.5.2 Start/Stop (Terminal 18)
This is the start command of the CD3000E thyristor unit and active the relative digital output (terminal
13 and 14) connected to the main contactor, if no alarm occurs, the CD3000E thyristor unit give an output proportional at the input signal.
If you Remove the Start command the CD3000E thyristor unit will be stopped and the output will return at zero following the ramp. When the ramp is over the Run contact will be reopened and the main contactor goes down.
12.5.3 Calibration (Terminal 19)
The Calibration input activates the Calibration procedure that is necessary if you use the Burst Firing
(BF) or the Heater break alarm (see par. 9.4).
12.5.4 Configurable Input (Terminal 20)
This digital input is configured by the parameter P103 and could perform different functions:
Additional Reset Alarm:
This function is the same of the Reset Alarm command.
Setpoint zero:
This function forces the output at zero maintaining the Run contact closed.
Feed-Back Selection:
With this function, when you active the input, the feed-back setted in the parameter P070 change in Voltage Feed-Back (V).
Analog/Digital Setpoint:
With this function, when you active the input, the setpoint reference change from Analog input to
Digital value, setted in the parameter P004 (see par. 13.1).
External Alarm:
With this function the thyristor unit, to work, must not have this digital input active.
When the unit is in Run and you active the External Alarm, the unit will be stopped and the output goes at zero without follow the ramp. The Run contact at the terminals 13 and 14 will be immediately reopened and the main contactor goes down. The External Alarm activates also the
Critical Alarm digital output.
43
CD Automation srl
12.6 Digital Output
CD3000E-3PH from 25A to 500A User’s Manual
The CD3000E thyristor unit has 2 digital output (1 for size S09) with relay contact (Max 500mA,
125Vac) and 2 digital output with logic NPN 12Vdc (20ma Max).
12.6.1 Configurable Relay (Terminals 11 and 12 not available for size S09)
This digital output can be configured in order to activate itself after that one of these alarms occors:
SCR in short circuit
Unbalanced Load
Heater Break Alarm (HB)
Low Voltage
The parameter for configurate the output is the P113 (see par. 13.2).
The standard contact used for this output is normally open (NO), but is possible change the contact type:
Size S11/S13/S14
Type
NC
NO (standard)
Jumper
A-B
B-C
JP23
C B A
12.6.2 Run Relay (Terminals 13 and 14)
This digital output is used to control the main contactor, when the thyristor unit is in run the output is active and the contact is closed.
12.6.3 Critical Alarm (Terminal 15)
This digital output is active when a critical alarm occurs (see par. 9.2).
12.6.4 Configurable Relay Digital Output (Terminal 16)
This digital output can be configured in order to activate itself after that one of these alarms occors:
SCR in short circuit
Unbalanced Load
Heater Break Alarm (HB)
Current Limit active
The parameter for configurate the output is the P112 (see par. 13.2).
44
CD Automation srl
12.7 PG Connector
CD3000E-3PH from 25A to 500A User’s Manual
The PG Connector is used to configure the thyristor unit with the configuration software and with the programming cable.
The programming cable is not included.
Connettore PG
45
CD Automation srl CD3000E-3PH from 25A to 500A
13 Configuration Parameters
User’s Manual
The Configuration Parameters are accessible from the Control Panel (place in front of unit), from the software configurator or through the serial communication port RS485.
With the RS485 Serial Port the parameters are not divided by menu, but only by numerical order.
13.1 Operator Menu
P000 (H00)
Function:
Value:
Password
This parameter gives access at the available menus.
0 = Operator Menu
5 = Setup Menu
10 = Hardware Menu
With the RS485 Serial Port this parameter are not used. Note:
P001 (H01)
Function:
Valore:
Note:
R/W
Code of Critical alarm R
This parameter read only gives information on the following alarms that they stop the CD3000E.
00 = No Alarm
01 = Phase Loss
20 = External Alarm
40 = Heat-sink over temperature
If more alarms occur, the value will be equal at the sum of the two alarms. example: External Alarm + Phase Loss= 20 + 01 = 21
P002 (H02)
Function:
Value:
Note:
Code of Not Critical alarm R
This parameter read only gives information on the following alarms that don't stop the CD3000E.
00 = No Alarm
01 = Thyristor Failure
02 = Heater Break Alarm
04 = Unbalanced Load
If more alarms occur, the value will be equal at the sum of the two alarms. example: Thyristor Failure + Heater Break Alarm = 01 + 02 = 03
P003 (H03)
Function:
Value:
Default:
Note:
P004 (H04)
Function:
Min/Max:
Default:
Note:
P008 (H08)
Function:
Setpoint selection Analog / Digital R/W
This parameter determines the use of the analog setpoint (terminal 7-8) or of the digital setpoint setted in the parameter P004 .
0 = Analog setpoint
1 = Digital setpoint
0
The parameter is not memorized in EEPROM.
Setpoint Digital Value
This parameter contains the digital setpoint value, active with
P003 = 1
0 ÷ 100%
0
The parameter is not memorized in EEPROM.
% R/W
Min/Max:
Example:
Valore Setpoint Analogico % R
This parameter read only contains the analog setpoint value present at the terminals 7-8 of the command terminals.
0 ÷ 100%
With input 4÷20mA:
Input 4mA P008 = 0
Input 12mA P008 = 50
Input 20mA P008 = 100
46
CD Automation srl
P011 (H0B)
Function:
P019 (H13)
Function:
Min/Max:
Default:
P024 (H18)
Function:
Min/Max:
Default:
P025 (H19)
Function:
Min/Max:
Default:
P031 (H1F)
Function:
P032 (H20)
Function:
P033 (H21)
Function:
P034 (H22)
Function:
P035 (H23)
Function:
P116 (H74)
Function:
Min/Max:
Default:
Note:
P119 (H77)
Function:
Min/Max:
Default:
Example:
Note:
CD3000E-3PH from 25A to 500A User’s Manual
Voltage supply V
This parameter read only contains the voltage value of the power supply.
R
Maximum output
This parameter set in % the maximum output voltage.
0 ÷ 100%
100
% R/W
Setpoint Ramp Up
This parameter set the Setpoint Ramp Up.
0 ÷ 1000 seconds
2
Setpoint Ramp Down
This parameter set the Setpoint Ramp Down.
0 ÷ 1000 seconds
2
Sec
Sec
R/W
R/W
Average voltage output on the three phases V R
This parameter read only show the Average voltage output on the three phases.
Average power output on the three phases Kw R
This parameter read only show the Average power output on the three phases.
RMS Current on the phase R A R
This parameter read only shows the RMS current present on the power terminal
L1.
RMS Current on the phase S A R
This parameter read only shows the RMS current present on the power terminal
L2.
RMS Current on the phase T A R
This parameter read only shows the RMS current present on the power terminal
L3.
Operative Load Voltage V R/W
This parameter is used to set in volt the operative voltage of the load.
24 ÷ 1000V
400 (if not specified in the Order Code)
For voltage under the 330V or upper to 600V its necessary makes hardware modification. For this reason it's very important specify this value in the Order
Code.
Load nominal Current
This parameter is used to set the Load nominal Current.
0 ÷ 300.0 Ampere for size from 25 to 300A
0 ÷ 3000 Ampere for size upper to 300A
Max Current of CD3000E (if not specified in the Order Code)
Size of CD3000E (Max Current) : 100A
Load nominal Current: 50A
A R/W
P119 =50.0
This parameter is necessary to have the correct rescaling inside the unit. For this reason it's very important specify this value in the order code.
47
CD Automation srl
13.2 Hardware Menu
P057 (H39)
Function:
Value:
Note:
CD3000E-3PH from 25A to 500A User’s Manual
Calibration min value of analog input 1 R/W
This parameter saves in memory the min value of the primary analog input
0 = Default
1 = Save value
The input Calibration procedure is necessary only if you change the input type
(ex. from 0÷10V to 4÷20mA) and must be performed only by qualified persons.
P058 (H3A)
Function:
Value:
Note:
Calibration max value of analog input 1 R/W
This parameter saves in memory the max value of the primary analog input
0 = Default
1 = Save value
The input Calibration procedure is necessary only if you change the input type
(ex. from 0÷10V to 4÷20mA) and must be performed only by qualified persons.
P061 (H3D)
Function:
Value:
Default:
Note:
Calibration min value of analog input 2 R/W
This parameter saves in memory the min value of the External Current Profiler
analog input (see par. 12.3.2)
0 = Default
1 = Save value
0
The input Calibration procedure is necessary only if you change the input type
(ex. from 0÷10V to 0÷5V) and must be performed only by qualified persons.
P062 (H3E)
Function:
Value:
Default:
Note:
Calibration max value of analog input 2 R/W
This parameter saves in memory the max value of the External Current Profiler
analog input (see par. 12.3.2)
0 = Default
1 = Save value
0
The input Calibration procedure is necessary only if you change the input type
(ex. from 0÷10V to 0÷5V) and must be performed only by qualified persons.
P097 (H61)
Function:
Value:
Offset of the Analog Outputs
This parameter is used to set the offset for the Analog Outputs.
0 = 0 ÷ 10Vdc / 0 ÷ 20mA
1 = 4 ÷ 20mA
0 (if not specified in the Order Code)
R/W
Default:
P103 (H67)
Function:
Value:
Digital input configuration (terminal 20)
This parameter selects the function of digital input.
0 = Additional Reset Alarm
1 = Setpoint Zero
2 = Feed-back Selection
3 = Setpoint Analog/Digital
4 = External Alarm
1
R/W
Default:
P104 (H68)
Function:
Min/Max:
Default:
Full scale of Analog Output 1 (Power Avarage) Kw R/W
This parameter is used to adjust the full scale value of the analog output.
0 ÷ 300.0 Kw for size from 25 to 300A
0 ÷ 3000 Kw for size upper to 300A
1000
48
CD Automation srl
P112 (H70)
Function:
Value:
Default:
P113 (H71)
Function:
Value:
Default:
Note:
P114 (H72)
Function:
Value:
Default:
P115 (H73)
Function:
Min/Max:
Default:
CD3000E-3PH from 25A to 500A User’s Manual
Digital output configuration (terminal 16)
This parameter selects the function of the digital output.
0 = Thyristor Failure
1 = Heater Break Alarm (HB)
2 = Unbalanced Load
3 = Current limit active
1
Digital output configuration (terminal 11 and 12)
This parameter selects the function of the digital output.
0 = Thyristor Failure
1 = Heater Break Alarm (HB)
2 = Unbalanced Load
3 = Low voltage
0
Not available for size S09
R/W
R/W
Baud Rate
This parameter selects the Baud rate on the serial port.
0 = 4800
1 = 9600
2 = 19200
2
R/W
Address R/W
This parameter selects the Address on the serial port for the thyristor unit.
1 ÷ 127
1
49
CD Automation srl
13.3 Setup Menu
P023 (H17)
Function:
Value:
CD3000E-3PH from 25A to 500A
Firing Type
This parameter selects the Firing Type.
0= BURST firing mode
1= PHASE ANGLE mode
2= DELAY TRIGGERING mode
1 (if not specified in the Order Code) Default:
P066 (H42)
Function:
Min/Max:
Default:
Example:
User’s Manual
R/W
HB sensitivity % R/W
This parameter defines the threshold of current that activates the HB alarm
This value is in percentage respect the nominal load value
0,0 ÷ 100,0%
100,0
Nominal Current 100A P066 =20. This means that the Heather Break
Alarm became active when the current goes below 80A
P070 (H46)
Function:
Value:
Default:
Note:
P083 (H53)
Function:
Min/Max:
Default:
P084 (H54)
Function:
Feed back selection
This parameter selects the Feed-back type.
0 = Current feed-back (rms value)
1 = Voltage feed-back (rms value)
2 = Power feed-back VxI
3 = External feed-back
1 (if not specified in the Order Code)
Feed-back value is the average value on the three phase R, S, T
R/W
Burst Firing Cycles (Not used in PHASE ANGLE) Cycles R/W
It defines the number of voltage cycles in ON condition at 50% of power demand
1 ÷ 255 cycles
8 (if not specified in the Order Code)
Ramp Cycles of Burst (Not used in PHASE ANGLE)
In Burst Firing is possible to have a soft start ramp.
Cycles R/W
With this parameter you can define how much cycles are necessary to reach the complete wave form. You must set a value between 0 and the number of cycles setted in the parameter P083 . If you set 0 value the ramp is disabled
0 ÷ 100 cycles
4 (con accensione S+BF) 0 (per altre accensioni)
Min/Max:
Default:
P085 (H55)
Function:
Min/Max:
Default:
P090 (H5A)
Function:
Value:
Default:
Note:
P091 (H5B)
Function:
Min/Max:
Default:
Delay triggering (Not used in others firing)
This parameter set firing delay in °
0 ÷ 100°
80
°
Digital Limit current value %
This parameter contains the digital Current Limit value, active with
P091 = 1
0,0 ÷ 100,0%
100,0
R/W
Current Limit select Analog/Digital
This parameter determines the use of the analog or digital Current Limit
0 = Analog, Current Limit from analog input (terminals 9-7)
1 = Digital, Current Limit from parameter P091
1
This parameter is saved in EEPROM
R/W
R/W
50
CD Automation srl
P098 (H62)
Value:
Default:
CD3000E-3PH from 25A to 500A
Load Type
0=star
1=star+N
2=delta
3=open delta
0 (if not specified in the Order Code)
User’s Manual
R/W
51
CD Automation srl
14 PROFIBUS DP
CD3000E-3PH from 25A to 500A
14.1 Connections (S14)
The communication port RS485 is available on the Command Terminals.
User’s Manual
We planned on routing the cables on the left side of the cover
To connect the Profibus we suggest use a 90° PROFIBUS connector
52
CD Automation srl CD3000E-3PH from 25A to 500A
14.2 How to set PROFIBUS ID
Low High
To set the PROFIBUS ID address use rotary switch “ID Low” and “ID
14.3 PROFIBUS Termination
Is possible use a terminato for Profibus
To enable set to ON, di disble set to OFF
14.4 Leds Status
LED
1,2,3
4
State
Status
Scrolling
Fixed
1 Fash
No flash
Red
Green
Meaning
Communication Active
Communication Stopped
Write a value
No data are sent
Communicatio error present
Communication OK
omation
PROFIBUS-DP
LED
Bus
State
Status
Green
Red
Green
Meaning
Profibus ok
Profibus error
Profibus in state data exchange
Flash green
Gateway waits for profibus comminication data
Flash green/red
Gateway waits for profibus parametercomminication data
Red
General profibus error
53
User’s Manual
CD Automation srl
14.5 PLC Configuration
CD3000E-3PH from 25A to 500A
To work right the PLC configurator need a GSD file that are supplied with CD
Install on developer Software the GSD file and configure hardware like follow
You need to use only the universal module with
Input: length = 122
= Word – Format Unit
Output length = 16
Unit = Word – Format
User’s Manual
1.1.1 To start read data
To start the read data function set the bit 0 offset 0 to 1
To stop the read data function set the bit 0 offset 0 to 0
When the communication on RS485 side is active the led 1, 2 and 3 will scroll.
When the communication on RS485 side is not active the led 1, 2 and 3 will stop scroll.
If a communication error (time out) is active the led State (near led 8) on RS485 side will light red otherwise will light green
1.1.2 To start write data
To be enabled to write data set the bit 2 offset 0 to 1
To be disabled to write data set the bit 2 offset 0 to 0
When a data are sent to a MODBUS device the led 4 will flash
54
OFFS
Byte
6
7
8
9
10
11
12
13
14
15
2
3
4
5
30
31
32
33
34
35
36
37
38
39
40
41
16
17
18
19
20
21
22
23
24
25
26
27
28
29
CD Automation srl CD3000E-3PH from 25A to 500A
14.6 Profibus data table exchange
14.6.1 Read Area (E)
OFFS
Byte
0
1
15
16
17
18
19
20
8
9
10
11
12
13
14
4
5 word
3
6
7
Word
Meaning
0
1.1.3 Tab status
Bit
0 Error communication wit board
(0=OK , 1=comm
Error)
1
2
3
4
5
6
7
1 Internal use
2 Internal use
Meaning
P001 AL1
P002 AL2
P003 L—r
0=Form Analogue input ; 1=from Bus
P004 L_SP
0 ÷ 4095 (Rescaled 0 ÷ 100.0%)
P005 Enab Supervisor
0=Disable
1=Enable
P006 Internal use
P007 Internal use
P008 r_SP
0 ÷ 4095 ((Rescaled 0 ÷ 100.0%)
P009 Internal use
P010 Internal use
P011 V_Ln
0 ÷ 4095 ((Rescaled 0 ÷ 1000V)
P012 Internal use
P013 Internal use
P014 Internal use
P015 Internal use
P016 Internal use
P017 Internal use
P018 Internal use
55
User’s Manual
67
68
69
70
71
72
73
74
75
76
77
57
58
59
60
61
62
63
64
65
66
52
53
54
55
56
34
35
36
37
38
29
30
31
32
33
26
27
28
48
49
50
51
78
79
80
81
82
83
CD Automation srl
42
43
44
45
46
47
21
22
23
84
85
86
87
88
89
90
91
24
25
39
40
41
42
43
44
45
CD3000E-3PH from 25A to 500A
P019 OutN
0 ÷ 4095 (Rescaled 0 ÷ 100.0%)
P020 Internal use
P021 Enable CL
0= Disabled
1= Enabled
P022 Internal use
P023 Fir
0= BURST firing
1= ANGOLO di FASE
2= DELAY TRIGGERING
P024 rP_u
0 ÷ 1000 Sec
P025 rP_d
0 ÷ 1000 Sec
P026 Internal use
P027 Internal use
P028 Internal use
P029 Internal use
P030 Internal use
P031 Vout
0 ÷ 4095 V
P032 Po
0 ÷ 4095 KW
P033 A__r
0 ÷ 4095 A
P034 A__s
0 ÷ 4095 A
P035 A__t
0 ÷ 4095 A
P045 Start/Stop Serial
0= Stop
1= Start
P046 Internal use
P047 RESET Serial
0->1 Reset Action
P048 DI Status
00 = No DI Input
01 = Reset Allarm Input
02 = Start / StopInput
04 = Enable Input (Always 1 con CD3000E)
10 = External alarm Input
20 = Na
40 = Configurable input
P049 DO Status
00 = No DO
01 = Run Output
02 = Critical Alarmo Output
04 = COnfigurable Output
P050 Flag cyle
0= Ok
1= Inverted
P051 Current Limit active
0= Disabled
1= Enabled
P052 Internal use
56
User’s Manual
104
105
106
107
108
109
110
111
112
113
114
115
CD Automation srl
92
93
94
95
96
97
98
99
100
101
102
103
46
47
48
49
50
51
116
117
118
119
132
133
134
135
136
137
138
139
120
121
122
123
124
125
126
127
128
129
130
131
66
67
68
69
60
61
62
63
64
65
52
53
54
55
56
57
58
59
CD3000E-3PH from 25A to 500A
P053 Frequency
0 ÷ 4095
P066 HB Sens
0 ÷ 4095 (Rescaled 0 ÷ 160.0%)
P067 HB dealy
0 ÷ 4095 (Rescaled 0 ÷ 10.00Sec)
P068 Internal use
P069 Internal use
P070 Feed back type
0 = Feed-back I
1 = Feed-back V
2 = Feed-back VxI
3 = Feed-back External
P071 Internal use
P072 Internal use
P083 bF_n Burst Number
1 ÷ 255
P084 bF_r Burst Ramp
P085 dt Delay triggeing
1 ÷ 100
P090 CL_i CL selection
0= From Analogueinput
1= From Bus
P091 CL Value
0 ÷ 4095 (Rescaled 0 ÷ 100.0%)
P098 LoAd Load Type
0= Star
1= Star+Neutral
2= Delta
3= Open Delta
P116 V_OP
100 ÷ 4095 (Rescaled 24 ÷ 1000V)
P117 Internal use
P118 Internal use
P119 A_Lo
0 ÷ 3000°
P120 Internal use
P121 tipo Unit type
302 = RE2
318 = RE3
P122 CT installed
0 ÷ 4095A
P123 Max Volt
100 ÷ 4095 (RRescaled 24 ÷ 1000V)
P124 Fw rev
P125 Comma
0= XXXX
1= XXX.X
57
User’s Manual
OFFS
Byte
6 H
7 L
8
9
10
11
12
13
14
15
16
2
3
4
5
CD Automation srl
14.6.2 Write Area (A)
OFFS
Byte
0
1
word
0
Word
3
L—r
4
L_SP
5
P005
6
P045
7
P047
8
CL
1
2
CD3000E-3PH from 25A to 500A
Meaning
1.1.4 Tab Comand
Bit ID
0 1= Start read ,
0= Stop read
1 Internal use
2 1=Write on data madific. enabled
0= Write on data madific. disabled
3 1=Enable retransmission measure
4
5
6
7
Bit
0
1
2
3
4
5
6
7
Internal use
Internal use
Meaning
Local/Remote selection
0=Form Analogue input ; 1=from Bus
Local Set-Poin
0 ÷ 4095 (Riscalato in 0 ÷ 100.0%)
Enable Start/Stop from Bus
0=Disable ; 1=Enable
Start/Stop from Bus
0=Stop ; 1 =Start
Reset From Bus
0 -> 1 Reset
Current Limit Value
0 ÷ 4095 (Riscalato 0 ÷ 100.0%)
User’s Manual
58
CD Automation srl
15 Internal Fuse
CD3000E-3PH from 25A to 500A User’s Manual
The CD3000E thyristor unit have internal fuse extrarapid at low I²t for the thyristor protection of against the short-circuits.
The fuse must have I²t lower than the thyristor one (I²t max)
25A (S09)
35A (S09)
45A (S09)
75A (S09)
100A (S11)
125A (S11)
150A (S11)
225A (S13)
300A (S14)
350A (S14)
400A (S14)
450A (S14)
500A (S14)
600A (S14)
Caution:
USE ONLY EXTRARAPID FUSE WITH APPROPRIATE I²
T
15.1 Fuse Code
Size
FU50FE
FU63FE
FU80FE
FU100FE
FU2x80FE
FU2x100FE
FU2x100FE
FUURB315
FU450FMM
FU550FMM
FU550FMM
FU700FMM
FU700FMM
FU700FMM
Fuse CODE
200 kARMS Symmetrical A.I.C.
Current
(A RMS)
50
I²T
(A²sec)
600
63
80
750
1500
100
160
200
2800
6000
11200
200
315
450
550
550
700
700
700
11200
82000
105000
215000
215000
420000
420000
420000
Vac
660
660
660
660
660
660
660
660
660
660
660
660
660
660
Qty
3
3
3
3
3
3
3
3
3
3
3
3
3
3
Caution:
The Fuses must have I²t 20% less than thyristor's I²t.
Caution:
High speed fuses are used only for the thyristor protection and can not be used to protect the installation.
Caution:
The warranty of thyristor is null if no proper fuses are used. See tab.
Warning:
The user installation must be protected by electromagnetic circuit breaker or by fuse isolator.
C
LISTED
US
59
CD Automation srl
16 Maintenance
CD3000E-3PH from 25A to 500A User’s Manual
16.1 Fans
The thyristor unit with forced ventilation uses fans that rotate permanently when the unit is supplied. In case of fan failure, the heat-sink can be reach high temperature. In this case to give protection to thyristor there is a thermal switch properly setted. The function of this switch is to open the input signal until the heat-sink temperature falls below the setted value. This means that also with input signal in ON condition the unit is switched OFF and the system can not work at full power. For this reason is important to control periodically the fans status checking that are rotating.
16.2 Maintenance
For maintain a correct cooling, the consumer must clean the heat-sink and the protective grate of the fans. The frequency of these operations depends on the atmospheric local pollution.
Check also that the screw of the power terminals and earth terminals are shut correctly
(see Diagram of control connection).
16.3 Repairing procedure
Phone to CD Automation.
Explain to Service Engineer the problem because sometimes it can be solved with a phone call.
If this is not possible, ship the unit to CD Automation or to your distributor.
Write a fault description and give the name of your personnel to which refers.
Use a rugged packaging to ship the unit.
16.4 Warranty condition
CD Automation gives a 12 months warranty to its products. The warranty is limited to repairing and parts substitution in our factory and does exclude products not properly used and fuses.
Warranty does not include products with serial numbers deleted. The faulty product should be shipped to
CD Automation at customer’s cost and our Service will evaluate if product is under warranty terms.
Substituted parts remain of CD Automation property.
ENG CD3000E-3PH_25-500A - 02.DOC
60
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 4 1 Important warnings for safety
- 6 2 Introduction
- 9 3 Quick Start
- 10 4 CD3000E Sizing
- 11 5 Identification and Order Code
- 13 6 Installation
- 16 7 Wiring instructions
- 23 8 Power output features
- 24 9 Led status and Alarms
- 27 10 Control Panel
- 29 11 Firing type
- 39 12 Connection description
- 46 13 Configuration Parameters
- 52 14 PROFIBUS DP
- 59 15 Internal Fuse
- 60 16 Maintenance