- Industrial & lab equipment
- Electrical equipment & supplies
- Power conditioning
- Power adapters & inverters
- User manual
advertisement
HIGH POWER FACTOR CONVERTER
HC2
Compatible with the Harmonic
Suppression Guidelines
Effectively suppresses inverter's power supply harmonics.
Renewed
FR-HC
Features
1
1
Greatly suppressed power supply harmonics
The HC2 converters, being the self-excitation three-phase bridge circuit under "the Harmonic Suppression Guidelines for
Specific Consumers", take the conversion coefficient of the equivalent capacity (K5 = 0).
Harmonic Conversion Coefficient of the Equivalent Capacity
(Excerpt from the Guidelines Appendix)
Classification Circuit type
6-pulse converter
Conversion coefficient Application examples
K11 = 1 Railway substation
1
3
5
Three-phase bridge 12-pulse converter
24-pulse converter
Three-phase bridge
(smoothing capacitor)
Without a reactor
With a reactor (on AC side)
With a reactor (on DC side)
With reactors (on AC/DC sides)
Self-excitation three-phase bridge
K12 = 5.5
K13 = 0.25
K31 = 3.4
K32 = 1.8
K33 = 1.8
K34 = 1.4
K5 = 0
Electro-chemistry
Other
General-purpose inverter
Lift
Refrigerating air conditioner
Other
PWM converter
The waveform with high peaks, which is typical of inverter's input current, is reshaped to be a sine wave with lower input current effective values.
The lowered effective value enables adoption of smaller power-supply-side devices, such as a power supply transformer, MCCB, and cables.
Such smaller equipment saves the cost of equipment.
Power supply voltage
Input current
Power supply voltage
Input current
[Without FR-HC2] [With FR-HC2]
2
Power regeneration function for energy saving
The power regeneration function, which comes as a standard feature, eliminates the need for brake units. The power regeneration function gives a great breaking capability.
(Regeneration is available continuously with 100% torque, and for 60s with the maximum of 150% torque.)
The regenerative power from the motor is returned to the power source, and such a system significantly saves energy.
500
300
200
100
50
30
7.5K
15K 30K 55K
10
10 20 30 40 50 60 70 80
Short-time permissible regenerative power (kW)
[55K or lower]
3
Connectable to multiple inverters
Inverter
The common converter method enables the connection to up to
10 inverters.
*1
The power returned during regenerative driving can be supplied to another inverter, saving the overall energy.
FR-HC2
Max.10 units connectable
Inverter
*1 : Be sure to use a converter with the capacity higher than the total capacities of the inverters.
(Refer to page 8.)
Inverter
4
Compact design for space saving
The high power factor converters (excluding 15K) and input reactors (75K or higher) have become much smaller than their conventional models (FR-HC, MT-HC).
5
Long life parts and life diagnosis function
(1) Longer life parts
The service life of the cooling fans is now 10 years
*1
and that can be even longer with the ON/OFF control of the cooling fan.
Capacitors with a design life of 10 years *1*2 are adapted.
(Using a surrounding air temperature of 105˚C for 5000 hours). With these capacitors, the service life of the converter is further extended.
*1 : Surrounding air temperature: Annual average of 40ºC (free from corrosive gas, flammable gas, oil mist, dust and dirt).
The design life is a calculated value and is not a guaranteed product life.
*2 : Input current: 80% of the high power factor converter rating
Estimated service lifespan of the consumable parts
Part name
Cooling Fan
Estimated lifespan
10 years
Reference value by JEMA *3
2 to 3 years
Main circuit smoothing capacitor
Smoothing capacitors on the printed board
10 years
10 years
5 years
5 years
*3 : Excerpt from "The Periodic Inspection Recommendations on General-purpose
Inverters" by the Japan Electrical Manufactures Association (JEMA).
(2) The leading-edge life diagnosis function
The degree of deterioration of the main circuit capacitor, cooling fan, and inrush current limit circuit can be diagnosed on the monitor.
Using the self-diagnosis function, the part life warning can be output and the deterioration degree can be monitored. Thus, the self-diagnosis function prevents troubles from occurring.
*4 : A warning is output when any of the control circuit capacitor, inrush current limit circuit, and cooling fan reaches its output level.
6
Operation panel equipped with the setting dial
(FR-DU07-CNV)
7
Supporting more network protocols
Parameters can be copied using the operation panel
(FR-DU07-CNV).
The setting values of the parameters can be stored to the operation panel and the option parameter unit (FR-PU07).
Items such as input current, input voltage, input power (with the regenerative display), bus voltage, etc. can be monitored.
Operation can be easily performed with the setting dial.
HC2 supports RS-485 as a standard. With the option
FR-A7NC, HC2 also supports CC-Link.
•The power can be monitored during driving/regenerative driving, and this monitoring tells you the energy saving effect.
•Alarm functions and voltage monitors of each phase help you to spot the cause of the alarm.
FR-HC2 Inverter Inverter
Parameter change example
Programmable controller
Terminating resistor
FR-A7NC FR-A7NC
CC-Link dedicated cable
CC-Link network
FR-A7NC
Terminating resistor
Applications
[Ceiling crane]
G
Trolley line
Trolley line
IM
IM
Crane
IM G
W
Traveling wheel
Rail
Power supply
Standard accessories
High power factor converter
(FR-HC2)
Inverter
Inverter
Inverter
B
Traveling motor
B
Traveling motor
Hosting motor
B
•The power regeneration function is installed. A brake
unit is not required.
•The mechanical brake is powered from the power
supply side of the standard accessories.
[Water treatment plant (pump)]
Power supply
Standard accessories
High power factor converter
(FR-HC2)
Inverter
Inverter
•Power supply harmonics of inverters can be
suppressed.
•The power regeneration function is installed.
A brake unit is not required.
Motor
Motor
Protective Functions
Dimension Drawings
Extensive lineup
Model
F R - H C 2 - 7.5K
High power factor converter basic model name
Capacity (kW)
Three-phase 200V class
Three-phase 400V class
7.5
15
30
Symbol
No sign
H
55
Voltage
200V class
400V class
75
Symbol
7.5K to 560K
Applicable capacity
Represents the capacity kW.
110
−
160
−
220
−
280
−
400
−
560
−
: Available model −: Not available
Compatible with UL, cUL, EC Directives (CE marking) as standard.
Compliant with the RoHS Directive. Friendly to people and to the environment.
To obtain higher environmental resistance, the FR-HC2 has coated printed circuit boards and copper plated conductors.
Magnetic contactors also have anti-corrosive coatings on.
The coated printed circuit board model (FR-HC-K-60
)of the conventional series is replaceable with the standard model of this series.
[Note]
•These coating treatments do not guarantee an operation environment beyond the range indicated in the product specification.
•Coating is applied to the printed circuit board areas excluding its LEDs, connectors, terminal blocks and their peripherals, where coating cannot be applied.
•As for the anti-corrosive treatment of the magnetic contactor, plating is applied to the copper areas where no surface treatment is applied.
Standard accessories
Refer to page 6
High power factor converter
*1
(FR-HC2)
Reactor 1
(FR-HCL21)
Reactor 2
(FR-HCL22)
Outside box
(FR-HCB2)
*2
*1 : Use in combination with standard accessories. Cables for connecting standard accessories are not provided.
*2 : Peripheral devices are separately provided for 280K or higher (not provided as the outside box).
2
3
Connection example
Three-phase AC power supply
Use within the permissible power supply specifications of the converter.
Moulded case circuit breaker (MCCB), earth leakage current breaker (ELB), or fuse
The breaker must be selected carefully since an inrush current flows in the converter at power ON.
Magnetic contactor (MC)
Install the magnetic contactor to ensure safety.
Do not use this magnetic contactor to start and stop the high power factor converter and the inverter. Doing so will shorten the life of the inverter and the converter.
Reactor 1 (FR-HCL21)
Confirm that the capacity of the reactor is selected according to the capacity of the converter.
R4S4 T4
P N
Outside box (FR-HCB2)
∗
Check that the capacity of the outside box matches with the capacity of the high power factor converter.
∗
Outside box is not available for 280K or higher.
Connect filter capacitors, inrush current limit
resistors, and magnetic contactors.
Reactor 2 (FR-HCL22)
Confirm that the capacity of the reactor is selected according to the capacity of the converter.
High power factor converter
(FR-HC2)
Install and wire correctly.
Do not install the moulded case circuit breaker (MCCB) between terminals P and P, or N and N of the converter and the inverter.
Fuse
Installation of a fuse is recommended for safety.
Select a fuse according to the connected motor capacity.
Inverter
Confirm that this is a FR-HC2 supporting inverter.
Connect an inverter that corresponds with the each capacity of the converter.
Match the control logic (sink logic / source logic) of the converter and the inverter.
Devices connected to the output
Do not install a power factor correction capacitor, surge suppressor or radio noise filter on the output side of the inverter. When installing a moulded case circuit breaker on the output side of the inverter, contact each manufacturer for selection of the moulded case circuit breaker.
Earth (Ground)
To prevent an electric shock, always earth (ground) the motor and inverter.
Earth
(Ground)
Motor
Connect the motor corresponds to the each capacity.
Standard specification rating
200V
Model name FR-HC2-K
Applicable inverter capacity (kW)
Rated input voltage (V)
Rated input current (A)
Permissible power supply voltage fluctuation
Permissible power supply frequency fluctuation
Input power factor
Power supply capacity (kVA)
Protective structure of the converter
Cooling system
7.5
15 30 55 75
7.5
15 30 55
10.7
33
19.8
38 71 92
Three-phase 200V to 220V 50Hz/200V to 230V 60Hz
61 115 215
150% 60s
170V to 242V 50Hz
278
170V to 230V
170V to 253V 60Hz 50Hz/60Hz
5%
14
0.99 or more (when load ratio is 100%)
25
47 88
7 12
Open type (IP00)
Forced air cooling
24 39
75
110
53
400V
Applicable inverter capacity (kW)
Rated input current (A)
Permissible power supply voltage fluctuation
Permissible power supply frequency fluctuation
Input power factor
Power supply capacity (kVA)
Protective structure of the converter
Cooling system
7.5
15 30 55 75 110 160 220
0.99 or more (when load ratio is 100%)
90 113 165 235 322
43
5%
Open type (IP00)
Forced air cooling
37 56 120 120
280
7.5
11.0
17
15
20.2
31
30
37
57
323V to 506V 50/60Hz
55 75 110 160 220
73 92 135 192 264
Three-phase 380V to 460V 50Hz/60Hz
110 139 203
150% 60s
290 397
280
336
506
323V to 460V 50/60Hz
14 26
Enclosed type
(IP20)
9 9
47
26
410
160
400
400
476
716
580
560
560
660
993
804
250 250
Model name of the 400V class ends with H.
The permissible voltage imbalance ratio is 3% or less. (Imbalance ratio = (highest voltage between lines - average voltage between three lines) / average voltage between three lines
100).
DC output capacity when the input voltage is 200VAC (400V for the 400V class).
Change the MC power supply stepdown transformer tap according to the input voltage. (Refer to the Instruction Manual)
The % value of the overload current rating indicates the ratio of the overload current to the converter's rated input current. For repeated duty, allow time for the converter and the inverter to return to or below the temperatures under 100% load.
The protective structure is IP40 for FR-DU07-CNV (except the PU connector) and IP00 for the outside box (220K or lower) and the reactor regardless of their capacities.
When the hook of the converter front cover is cut off for installation of the plug-in option, the protective structure changes to the open type (IP00).
Mass of FR-HC2 alone.
4
5
Common specifications
Control method
PWM control
Power supply frequency range
50Hz to 60Hz
Current limit level
Current limit value selectable (0 to 220% variable)
Input signal (Five terminal)
Output signal
Open collector output
(Five terminals)
Relay output (One terminal)
Operating status
The following signals can be assigned to Pr. 3 to Pr. 7 (input terminal function selection): converter stop, monitor switching, converter reset, external thermal relay, and inrush resistance overheat detection.
The following signals can be assigned to Pr. 11 to Pr. 16 (output terminal function selection): inverter run enable signal, converter reset, converter running, overload alarm, power supply phase detection, output voltage match, instantaneous power failure detection, regenerative drive recognition, electronic thermal relay pre-alarm, fan alarm, heatsink overheat pre-alarm, during retry, input current detection, zero current detection,life alarm, maintenance timer, instantaneous power failure detection hold, alarm, and fault output.
For meter
Pulse train output
(Max. 2.4kHz: one terminal)
Analog output
(Max. 10VDC: one terminal)
The following signals can be assigned to Pr. 54 FM terminal function selection (pulse train output) and
Pr. 50 AM terminal function selection (analog output): power supply frequency, input current, input voltage, converter output voltage, electronic thermal relay load factor, input power, reference voltage output.
Operation panel
(FR-DU07-CNV)
Operating status
Power supply frequency, input current, input voltage, fault or alarm indication, converter output voltage, electronic thermal relay load factor, cumulative energization time, cumulative power, input
power, input power (with regenerative display), I/O terminal status
, power/regenerative drive indication, option fitting states
Fault definition is displayed when a fault occurs. Past eight fault records and the data right before the fault (input voltage/current/bus voltage/cumulative energization) are stored.
Parameter unit
(FR-PU07)
Fault record
Interactive guidance
Function (help) for operation guide
Protective/warning function
Surrounding air temperature
Ambient humidity
Storage temperature
Atmosphere
Altitude/ vibration
Protective function
Warning functions
Overcurrent, overvoltage, converter protection thermal, fin overheat, instantaneous power failure, undervoltage, input phase loss, HC2 dedicated board disconnection, input power supply fault, external thermal relay operation
, parameter error, PU disconnection
, converter
CPU fault, operation panel power supply short circuit, 24VDC power output short circuit, input cur-
, inrush current limit circuit fault, internal circuit fault, option fault
, communication option fault
Fan alarm, overload signal detection, electronic thermal relay pre-alarm, PU stop, maintenance timer alarm
, parameter write error, copy operation error, operation panel lock, parameter copy alarm, no-phase detection
-10
C to +50C (non-freezing)
90%RH or less (non-condensing)
-20
C to +65C
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
Maximum 1,000m above sea level, 5.9m/s
2
or less
at 10 to 55Hz (directions of X, Y, Z axes)
Can be displayed only on the operation panel (FR-DU07-CNV).
Can be displayed only on the option parameter unit (FR-PU07).
Temperature applicable for a short time, e.g. in transit.
This protective function is not available in the initial status.
This protective function is enabled when FR-A7NC is mounted.
2.9m/s
2
or less for the 160K or higher.
Checking peripheral devices
Peripheral devices
Always install the included peripheral devices. Check the model name of the each peripheral device.
For the 400V class peripheral devices, H is indicated in front of the model name.
FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K
Peripheral Device
Model Name
FR-HC2-(H)K
FR-HCL21-(H)K
FR-HCL22-(H)K
FR-HCB2-(H)K
Description
High power factor converter
Filter reactor 1
Filter reactor 2
Outside box
Quantity
1
1
1
1
Terminal screws are enclosed for FR-HCB2-7.5K, 15K, FR-HCB2-H7.5K to H30K. (M5 6)
FR-HC2-H280K to H560K
Peripheral Device
Model Name
FR-HC2-HK
FR-HCL21-HK
FR-HCL22-HK
FR-HCC2-HK
Model Name of Consisting Parts
FR-HC2-HK
FR-HCL21-HK
FR-HCL22-HK
FR-HCC2-HK
MDA-1
FR-HCR2-HK
FR-HCM2-HK
0.96OHM BKO-CA1996H21
0.96OHM BKO-CA1996H31
1PH 630VA BKO-CA2001H06
S-N400FXYS AC200V 2A2B
S-N600FXYS AC210V 2A2B
SR-N4FX AC210V 4A
TS-807BXC-5P
C152C481H21
C152C423H21
MYQ4Z AC200/220
PYF14T
PYC-A1
M12
50 ZENNEJI
M12
MIGAKI 12
BANE 12
SW-PW-P-NA M5
12
Description
High power factor converter
Filter reactor 1
Filter reactor 2
Filter capacitor
Filter capacitor alarm detector
Inrush current limit resistor (without thermostat)
Inrush current limit resistor (with thermostat)
MC power supply stepdown transformer
(400V-200V)
Inrush current limit MC
Inrush current limit MC
Buffer relay
Terminal block
Terminal block shorting conductor
MC shorting conductor
Mini relay for filter capacitor alarm detector
Mini relay terminal block
Mini relay clip
MC shorting conductor bolt (M12
50)
MC shorting conductor nut (M12)
MC shorting conductor washer (flat washer)
MC shorting conductor washer (spring washer)
Inrush current limit resistor screw (M5
12)
1
—
—
—
—
—
—
6
—
—
—
—
1
1
6
8
1
Quantity
280K 400K 560K
1
1
1
1
—
1
2
1
1
2
1
3
1
1
3
15
3
1
2
24
24
48
24
54
—
6
1
1
3
—
2
—
15
3
1
2
24
24
48
24
54
—
6
1
1
3
—
2
—
6
7
Compatible inverter for the high power factor converter
Refer to the table below for the compatible inverter capacities when connecting one inverter to a converter. (Other combinations are not applicable.)
: Compatible
—
: The converter can be used as a common converter or a regenerative converter, but its harmonic suppression effect reduces.
: Not compatible (Not applicable)
Inverter capacity
FR-HC2-7.5K
FR-HC2-15K
FR-HC2-30K
FR-HC2-55K
FR-HC2-75K
FR-HC2-H7.5K
FR-HC2-H15K
FR-HC2-H30K
FR-HC2-H55K
FR-HC2-H75K
2.2K
or lower
—
—
—
—
—
—
—
—
—
—
3.7K
5.5K
7.5K
11K
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
15K 18.5K
22K
—
—
—
—
—
—
—
—
—
—
—
—
30K
—
—
37K
45K
55K
75K
Inverter capacity
FR-HC2-H110K
45K or lower
—
55K
75K
90K 110K 132K 160K 185K 200K 220K 250K
FR-HC2-H160K
FR-HC2-H220K
—
—
—
—
—
—
—
FR-HC2-H280K
— — — — — —
FR-HC2-H400K
FR-HC2-H560K
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
—
Inverter capacity
FR-HC2-H280K
FR-HC2-H400K
FR-HC2-H560K
280K 315K 355K 375K 400K 450K 500K 530K 560K
Wiring of several inverters to one converter
Up to ten inverters can be connected to one converter. Be sure to use a converter with the capacity higher than the total capacities of inverters. Additionally, the total capacity of the inverters needs to be higher than half the converter capacity.
If the total inverter capacity is less than half the converter capacity, the converter can be used as a common converter or a regenerative converter. However, it's harmonic suppression effect reduces.
(1) Junction terminals or cross wiring are used to connect several inverters, so carefully select the wire gauge. Start adding the inverter capacities from the furthest inverter.
(2) When connecting several inverters, connect starting with the inverter with the highest capacity.
(3) Installation of a fuse, which corresponds with each motor capacity, is recommended for each inverter when connecting several inverters to one converter. Select a fuse according to the motor capacity.
When using a motor, of which capacity is smaller than the inverter capacity by two ranks or more, select the converter
capacity according to the inverter capacity. (Refer to page 24)
(4) Keep the total wiring length within 50m.
Main circuit wiring example
The following diagram shows a connection example when connecting six inverters in total (FR-A720-30K, 15K, 5.5K, 2.2K,
1.5K, and 0.75K) to FR-HC2-55K.
FR-HC2
-55K
P
N
3)
1)
Junction terminal 1
Fuse
P
2)
N
INV1
A720
30K
Junction terminal 2
4)
INV2
P
N
A720
15K
30kW
Motor
1st inverter
1) Wire gauge between FR-HC2 and the junction terminal 1 is 100mm
2 according to the FR-HC2 capacity.
2) Wire gauge between the junction terminal 1 and the inverter is 60mm 2 because the inverter capacity is 30K.
15kW
5)
Junction terminal 3
6)
P
N
INV3
A720
5.5K
2nd inverter 3) Wire gauge between the junction terminal 1 and junction terminal 2 can be calculated as follows: 15+5.5+2.2+1.5+0.75=24.95K, and 24.95K rounds up to 30K, so the wire gauge is 60mm
2
.
4) The Wire gauge between the junction terminal 2 and the inverter is 22mm
2 because the inverter capacity is 15K.
5.5kW
Motor
7)
Junction terminal 4
8)
P
N
INV4
A720
2.2K
3rd inverter 5) Wire gauge between the junction terminal 2 and junction terminal 3 can be calculated as follows: 5.5+2.2+1.5+0.75=9.95K, and 9.95K rounds up to
11K, so the wire gauge is 14mm
2
.
6) Wire gauge between the junction terminal 3 and the inverter is 14mm
2 because the inverter capacity is 5.5K.
2.2kW
Motor
9)
11)
Junction terminal 5
10)
P
N
INV5
A720
1.5K
Junction terminal 6
12)
INV6
P
N
A720
0.75K
4th inverter 7) Wire gauge between the junction terminal 3 and junction terminal 4 can be calculated as follows: 2.2+1.5+0.75=4.45K, and 4.45 K rounds up to 5.5K, so the wire gauge is 5.5mm
2
.
8) Wire gauge between the junction terminal 4 and the inverter is 2mm
2 because the inverter capacity is 2.2K.
1.5kW
Motor
5th inverter 9) Wire gauge between the junction terminal 4 and junction terminal 5 can be calculated as follows: 1.5+0.75=2.25K, and 2.25K rounds down to
2.2K, so the wire gauge is 2mm
2
.
10) Wire gauge between the junction terminal 5 and the inverter is 2mm 2 because the inverter capacity is 1.5K.
0.75kW
Motor
6th inverter 11) Wire gauge between the junction terminal 5 and junction terminal 6 is
2mm 2 because the inverter capacity is 0.75K.
12) Wire gauge between the junction terminal 6 and the inverter is 2mm
2 because the inverter capacity is 0.75K.
8
Outline dimension drawings
Converter (FR-HC2)
FR-HC2-75K or lower
FR-HC2-H110K or lower
(Dimension drawing example: FR-HC2-7.5K)
2-
φd hole
P.CPY PWR
REGEN DRIVE
PSCLR
3-
φd hole
FR-HC2-H160 to H560K
(Dimension drawing example: FR-HC2-H560K)
FAN
W1
W
D
200V class
Model
FR-HC2-7.5K
FR-HC2-15K
FR-HC2-30K
FR-HC2-55K
FR-HC2-75K
W W1 H H1 D d
220 195 260 245 170 6
250 230 400 380 190 10
325 270 550 530 195 10
370 300 620 595 250 10
465 400 620 595 300 12
W1
400V class
Model
FR-HC2-H7.5K, H15K
FR-HC2-H30K
FR-HC2-H55K
FR-HC2-H75K
FR-HC2-H110K
FR-HC2-H160K, H220K
FR-HC2-H280K
FR-HC2-H400K, H560K
W
W1
W W1 H
220 195 300
H1 D d
285 190 6
325 270 550
370 300 670
325 270 620
465 400 620
530 195 10
645 250 10
595 250 10
595 300 12
498 200 1010 985 380 12
680 300 1010 984 380 12
790 315 1330 1300 440 12
(Unit: mm)
Reactor 1 (FR-HCL21) (Dimension drawing example : FR-HCL21-7.5K)
9
4-d hole
W1
MAX W
200V class
Model
FR-HCL21-15K
FR-HCL21-30K
FR-HCL21-55K
FR-HCL21-75K
W
W1 H D
FR-HCL21-7.5K
132 50
0.5
150 100
162 75
0.5
172 126 107
195 75
0.5
210 150
210 75
0.5
180 200.5
97
240 150
1
D1
86
87
215 215.5 109
+0
-2.5
+0
-2.5
+0
-2.5
+0
-2.5
+0
-2.5
d
400V class
Model
M6 FR-HCL21-H7.5K
M6 FR-HCL21-H15K
M6 FR-HCL21-H30K
M6 FR-HCL21-H55K
M8 FR-HCL21-H75K
FR-HCL21-H110K
FR-HCL21-H160K
FR-HCL21-H220K
The sizes indicated by W and D are not the sizes of the legs. These indicate the sizes of whole reactors.
FR-HCL21-H280K
FR-HCL21-H400K
FR-HCL21-H560K
D1
MAX D
W
132
162
182
W1 H D
50
0.5
140 105
D1
90
75
0.5
170 128 105
75
0.5
195 145.5
90
+0
-1
+0
-1
+0
-1
d
M6
M6
M6
282.5 255
1.5
245 165 112
1.5
M6
210 75
1
240 150
1
280 150
1
330 170
1
330 170
1
402 250
1
452 300
1
175 210.5 105
230 220 99
295 274.5 150
335 289.5 150
335 321 203
+0
-5
+0
-5
+0
-2.5
+0
-5
+0
-5
M6
M8
M8
M10
M10
460 550 305
10
M10
545 645 355
10
M12
(Unit: mm)
Reactor 2 (FR-HCL22) (Dimension drawing example : FR-HCL22-7.5K)
MAX D
W1
MAX W
400V class
4-d hole
200V class
Model W
W1 H D
D1 d
FR-HCL22-7.5K
237.5 210
1.5
230 140 110
1.5
M6
FR-HCL22-15K
FR-HCL22-30K
FR-HCL22-55K
257.5 230
1.5
260 165 120
1.5
M6
342.5 310
1.5
305 180 130
1.5
M8
432.5 270
1.5
380 280 240
1.5
M8
FR-HCL22-75K 474 430
2
460 280 128
2
Model
FR-HCL22-H7.5K
FR-HCL22-H15K
FR-HCL22-H30K
FR-HCL22-H55K
M12 FR-HCL22-H75K
The sizes indicated by W and D are not the sizes of the legs. These indicate the sizes of whole reactors.
FR-HCL22-H110K
FR-HCL22-H160K
FR-HCL22-H220K
FR-HCL22-H280K
FR-HCL22-H400K
FR-HCL22-H560K
D1
W
W1 H D
D1 d
237.5 210
1.5
220 140 110
1.5
M6
257.5 230
1.5
260 165 120
1.5
M6
342.5 310
1.5
300 180 130
1.5
M8
392.5 360
1.5
365 200 130
1.5
M8
430 265
1.5
395 280 200
1.5
M10
500 350
1.5
440 370 260
1.5
M10
560 400
1.5
520 430 290
1.5
M12
620 400
1.5
620 480 320
1.5
M12
690 500
2
700 560 350
2
M12
632 400
2
632 400
2
675 705 435
10
M12
720 745 475
10
M12
(Unit: mm)
Outside box (FR-HCB2)
FR-HCB2-55K or lower
FR-HCB2-H75K or lower
(Dimension drawing example : FR-HCB2-7.5K)
FR-HCB2-75K
FR-HCB2-H110K, H160K, H220K
(Dimension drawing example : FR-HCB2-75K)
2-A hole 3-A hole
D
W1
W
Type A hole dimensions
7
W1 W1
W
13
200V class
Model
FR-HCB2-7.5K, 15K
FR-HCB2-30K, 55K
FR-HCB2-75K
W W1 H H1 D
190 130 320 305 165
270 200 450 435 203
400 175 450 428 250
400V class
Model
FR-HCB2-H7.5K to H30K
FR-HCB2-H55K
FR-HCB2-H75K
FR-HCB2-H110K
FR-HCB2-H160K, H220K
Peripheral devices are separately provided for the FR-HC2-H280K or higher (not provided as the outside box).
W W1 H H1 D
190 130 320 305 165
270 200 450 435 203
300 250 350 328 250
350 125 450 428 380
400 175 450 428 440
(Unit: mm)
10
Filter capacitor (FR-HCC2)
FR-HCC2-H280K
300
90 5 90 5
Enlarged drawing of the installation foot
(Recommended bolt size: M12)
370 3
394 3
R7.5
FR-HCC2-H400K
400 3
365 3
52.5
102.5
300
90 5 90 5
2-15 20 oval-shaped hole
Enlarged drawing of the installation foot (Recommended bolt size: M12)
R7.5
370 3
394 3
M12 bolt
2-15 20 oval-shaped hole
365 3
400 3
370 3
394 3
FR-HCC2-H560K
500 3
140 5
400
140 5
Earth (ground) terminal
(M8 bolt)
(25)
80 2
(Unit: mm)
Mass: 17kg
370 3
Earth (ground)
terminal (M8 bolt)
394 3 80 2
Installation foot
Filter capacitor alarm detector (MDA-1)
(FR-HCC2-H400K, H560K)
150 3
Enlarged drawing of the installation foot
(Recommended bolt size: M12)
R7.5
M12 bolt
470 2
494 3 arm
Reference value as some margins are taken for the arm
Case
(Unit: mm)
Mass: 15kg
Plunger
2-15 20 oval-shaped hole Earth (ground)
terminal
(M8 bolt)
4
1
3
2
Micro switch
Screw(M4)
Connector
Switch terminal and contact symbol of the detector
NC
NO
NC
NO
NO4
NC1
NO3
NC2
Circuit diagram
4-M4 5.6
Screw with toothed washer
40 2
15 1
53 2
65MAX
(Unit: mm)
Mass: 0.3kg
470 2
494 3
FR-HCM2
Contactor (S-N600FXYS AC210V 2A2B)
(FR-HCM2-H280K)
M16 screw
(with washer and spring washer)
13.5
20
263
250
80 2
(Unit: mm)
Mass: 21kg
156
Contactor (S-N400FXYS AC200V 2A2B)
(FR-HCM2-H400K, H560K)
(4-M8 hole)
145
(60)
M4 screw (self-up)
4-M8 hole
136
11
M4 screw
(self-up)
Installation hole for 4-M10 screw
80
70
40
12 hole 10 235
10.5
290
MC power supply stepdown transformer
(BKO-CA2001H06) (FR-HCM2-H280K to H560K)
(Unit: mm)
Mass: 24kg
Terminal block for tap switching
M4 screw
Enlarged drawing of installation hole
7 18 or more
Input side terminal block
M4 screw
R/L1
Output side terminal block
M4 screw
S/L2
V3 V3 V2 V2 V1 V1
R5/L15 S5/L25
Output side
5 2
100 1
E
Varnish removed area
8 1
Input side
M12 screw
(with washer and spring washer)
55
30
163
M4 screw
(self-up)
Terminal block
(TS-807BXC-5P) (FR-HCM2-H280K)
128
116
1
3 17.5
2.5
20
X
100 1
153 2
4- 8 open hole for M6 bolt
(30)
81 2
115 2
Within 180 (Unit: mm)
Mass: 10kg
X
37
12
26
3.2
195
(Unit: mm)
Mass: 9.5kg
Sectional view of X - X
(Unit: mm)
Mass: 0.3kg
Terminal block shorting conductor (C152C481H21)
(FR-HCM2-H280K)
(8)
5-oval 7-8
8 80 0.4
60 0.4
40 0.4
20 0.3
(4) 16 (4)
(2.3) 2.8
A
10-C2
MC shorting conductor (C152C423H21)
(FR-HCM2-H400K, H560K)
4.5
2 M4 hole
35 (Installation size)
A2 A1
(self-up)
A
96
Sectional view of A - A
7.9
30
28 40
2-C2
(Unit: mm)
Mass: 0.1kg
Buffer relay for driving MCs (SR-N4FX AC210V 4A)
(FR-HCM2-H280K to H560K)
59
13 23 33 43
IEC
35mm width rail
14 24 34 44
10
43
8
5
Mini relay terminal block (PYF14T)
(FR-HCM2-H400K, H560K)
2-
φ4.2 5 hole
MAX 33
7 0.2
30
23.5
11.5
11
78
10
3.5
(When rail width is 7.5mm)
(Unit: mm)
Mass: 0.3kg
4- 14 hole (M12)
57.5
65
180
(57.5)
9-M5 screw for installation of inrush resistor
8
(Unit: mm)
Mass: 1.6kg
Mini relay for filter capacitor alarm detector
(MYQ4Z AC200/220) (FR-HCM2-H400K, H560K)
2.6
21.5 or less
14-
φ1.2 2.2 oval hole
6.4
28 or less
35.5 or less 21.5 or less
28 or less
(Unit: mm)
Mass: 35kg
14-M3.5 8
10
17.4
Inrush current limit resistor (FR-HCR2)
With thermostat (BKO-CA1996H31)
(FR-HCR2-H280K to H560K)
(Unit: mm)
Mass: 53kg
Without thermostat (BKO-CA1996H21)
(FR-HCR2-H280K to H560K)
2-(17)
Board thickness2.5
215 2
200 1.2
175 2
2-500 10
325 15
2-6 1
2-6 1
60 1.5
(30)
(Unit: mm)
Mass: 0.8kg
Board thickness2.5
2-(17)
215 2
200 1.2
175 2
2-500 10
2-6 1
60 1.5
(30)
(Unit: mm)
Mass: 0.8kg
12
13
Protruding the heatsink
When installing a converter inside an enclosure, the heat generated in the enclosure can be greatly reduced by protruding the heatsink of the converter.
This installation method is recommended when downsizing the enclosure and such.
When using a heatsink protrusion attachment (FR-A7CN)
For the FR-HC2-7.5K to 75K and FR-HC2-H7.5K to H110K, a heatsink can be protruded outside the enclosure using a heatsink protrusion attachment (FR-A7CN). (For the 160K or higher, the attachment is not necessary when the heatsink is to be protruded.)
Refer to the table below for the applicable heatsink protrusion attachments.
(For the details of FR-A7CN, refer to the Instruction Manual of the option FR-A7CN.)
(1) Heatsink protrusion attachments
Model Name
FR-A7CN02
FR-A7CN03
FR-A7CN04
FR-A7CN05
FR-A7CN09
Applicable converter
FR-HC2-7.5K
FR-HC2-H7.5K, H15K
FR-HC2-15K
FR-HC2-30K
FR-HC2-H30K
FR-HC2-75K
FR-HC2-H110K
For a combination other than above, please contact your sales representative.
(2) Drawing after attachment installation (when used with the FR-A7CN)
S screw
W
Attachment
D2
Panel
Model W H H1 H2
FR-A7CN02
245 408.5
260 116.5
FR-A7CN03
245 448.5
300 116.5
554 400 122
FR-A7CN04
280
FR-A7CN05
338
FR-A7CN09
510
645
725
480
535
130
150
D
Panel
D1
Attachment
(3) Panel cut dimension drawing (when used with the FR-A7CN)
FR-A7CN02 FR-A7CN03
175 175
FR-A7CN04
H3
32
32
32
35
40
D D1
86
89
88.5
89.4
106.4
110.6
123.5
71.5
116.5
183.5
D2
12.3
20
45.3
105
S
M5
M5
M8
M8
45 M10
(Unit:mm)
200
FR-A7CN05
6-M5 screw
195
212
298
279
6-M5 screw
195
212
FR-A7CN09
470
440
244
6-M8 screw
230
260
4-M8 screw
270
330
4-M10 screw
400
477
(Unit:mm)
Heatsink protrusion for 160K or higher
(1) Enclosure cut
Cut the enclosure according to the capacity of the converter.
FR-HC2-H160K, H220K FR-HC2-H280K
6-M10 screw
200
484
200
300
662
300
6-M10 screw
FR-HC2-H400K, H560K
771
315 315
6-M10 screw
Hole
Hole
Hole
(2) Moving and removing the back installation frames
FR-HC2-H160K to H280K
One installation frame is attached to each of the upper and lower parts of the converter. Change the position of the rear side installation frame on the upper and lower sides of the converter to the front side as shown on the right. When changing the installation frames, make sure that the installation orientation is correct.
Shift
Upper installation frame
FR-HC2-H400K, H560K
The converter has installation frames: two on the top and the two on the bottom. As shown on the right, remove the back installation frames on the top and bottom of the converter.
Removal
Upper installation frame (rear side)
Shift
Lower installation frame
(3) Installing the converter to the enclosure
Removal
Lower installation frame (rear side)
Protrude the heatsink of the converter from the installation enclosure, and secure the converter using the top and bottom installation frames.
Inside the enclosure
Enclosure
Exhausted air
∗
The enclosure enclosing FR-HC2-H160K and higher has a finger guard on its back. The thickness of the enclosure should be less than 10mm (
), and do not place anything around the finger guard to avoid contact with the finger guard.
Enclosure
Converter
Installation frame
10
∗
140
Finger guard
Cooling wind
D1
Dimension of the outside of the enclosure
Converter model
FR-HC2-H160K, H220K
FR-HC2-H280K to H560K
D1
185
184
NOTE
• Protruding area contains a cooling fan, so it cannot be used in the environment where water drops, oil mist, dust and other substances exist.
• Foreign substances such as screws and dust must be prevented to enter in the converter or the cooling fan section.
14
Terminal connection diagram (when using with the FR-A700 series)
15
Before making connections, check the cable size and connection method to each device in the Instruction Manual.
FR-HC2-7.5K to 75K, FR-HC2-H7.5K to H220K
Power supply
MCCB MC
Outside box (FR-HCB2)
(1)
Reactor1
(FR-HCL21)
R2/
L12
R/
L1
S/
L2
T/
L3
R2/
L12
S2/
L22
T2/
L32
S2/
L22
T2/
L32
Limit resistor
Filter capactors
MC power supply stepdown transformer
Reactor2
(FR-HCL22)
Converter
(FR-HC2)
Auxiliary contact
(NO contact)
MC1
R3/
L13
S3/
L23
T3/
L33
Limit MC1
88S
R3/
L13
R4/
L14
S3/
L23
S4/
L24
T3/
L33
T4/
L34
(2)
ROH1
Inrush current limit resistor overheat protection
ROH2
Contact input common
88R
MC connection terminal
MC connection terminal
R4/L14
S4/L24
T4/L34
ROH
SD
Fuses
P/+
N/-
RDY
RSO
C
B
A
Relay output
(fault output)
Inverter run enable signal
Converter reset
88R
88S
CVO
During converter run
Y1
Y2
Multi-purpose output 1
Multi-purpose output 2
Reset RES
SE
Overheat detection thermostat for the limit resistor (NC contact)
Converter stop
Monitor switching
SOF
X1
Inverter
R/L1
S/L2
T/L3
U
V
W
R1/L11
S1/L21
P/+
N/-
X10
RES
SD
Open collector output common
Y3
Multi - purpose output 3
SE2
Open collector output common
Motor
Earth
(Ground)
Monitor switching X2
FM
+ -
Contact input common
24VDC power supply
(External transistor common)
SD
PC
PU connector
SD
Indicator
AM
R/L1
S/L2
T/L3
R1/L11
S1/L21
5
(+)
Analog signal output
(0 to 10VDC)
(-)
FR-HC2-H280K
Power
Supply
MCCB MC
(1)
Reactor 1
(FR-HCL21)
R/
L1
S/
L2
T/
L3
R2/
L12
S2/
L22
T2/
L32
Limit resistors
Filter capacitors
(FR-HCC2)
Auxiliary contact for limit MCs (NO contact)
MC
Reactor 2
(FR-HCL22)
R3/
L13
R4/
L14
S3/
L23
S4/
L24
T3/
L33
T4/
L34
Limit resistor
(2)
(with a thermostat) (NC contact)
MC
Limit
MC
Converter
(FR-HC2)
R4/L14
S4/L24
T4/L34
ROH
Inrush current limit resistor overheat protection
Contact input common
SD
P/+
N/-
RDY
RSO
MC power supply stepdown transformer
Buffer relay for driving MC
C
B
A
Fuses
Relay output
(Fault output)
Inverter
R/L1
S/L2
T/L3
R1/L11
S1/L21
U
V
W
P/+
N/-
MC
Bu1
MC connection terminal
MC connection terminal
Converter reset
Converter stop
Monitor switching
Monitor switching
Contact input common
24VDC power supply
(External transistor common)
88R
88S
RES
SOF
X1
X2
SD
PC
R/L1
S/L2
T/L3
R1/L11
S1/L21
PU connector
CVO
Y1
Y2
SE
Inverter run enable signal
Converter reset
During converter run
Multi-purpose output 1
Multi-purpose output 2
Open collector output common
Y3
X10
RES
SD
Multi - purpose output 3
SE2
FM
+
-
SD
AM
5
Indicator
(+)
Analog signal output
(0 to 10VDC)
(-)
Motor
Earth
(Ground)
Do not connect anything to the inverter power input terminals R/L1, S/L2 and T/L3. Incorrect connection will damage the inverter. Connecting opposite polarity of terminals P and N will damage the converter and the inverter.
Use input terminal function selection to assign the terminal used for X10 signal. (Refer to the Inverter Instruction Manual.)
The power phases of the terminals R4/L14, S4/L24, and T4/L34 and the terminals R/L1, S/L2, and T/L3 must be matched.
Do not insert MCCB between terminals P and N (P and P, N and N).
Always connect the terminal R/L1, S/L2, T/L3 of the converter to the power supply. If the inverter is operated without connecting the terminals to the power supply, the converter will be damaged.
Do not insert MCCB or MC between (1) (terminal R/L1, S/L2, and T/L3 input of the Reactor 1) and (2) (terminal R4/L14, S4/L24, and T4/L34 input of the converter) of the above diagram. It will not operate properly.
Securely perform grounding (earthing) by using the grounding (earthing) terminal.
Installation of a fuse is recommended. (Refer to page 24)
The MC power supply stepdown transformer is only equipped in the 400V class models.
FR-HC2-H400K, H560K
Power
Supply
MCCB
MC
MC
MC
(1)
Reactor 1
(FR-HCL21)
R/
L1
R2/
L12
S/
L2
S2/
L22
T/
L3
T2/
L32
MC power supply stepdown transformer
Limit resistor
Filter capacitors
(FR-HCC2)
Filter capacitor alarm detector
(NC contact)
MC
Bu2
Buffer relay for filter capacitor alarm detectors
Limit MC
MC1
MC2
MC3
MC1
MC2
MC3
MC
Bu1
Reactor 2
(FR-HCL22)
R3/
R4/
L13
L14
S3/
L23
S4/
L24
(2)
T3/ T4/
L33
L34
Limit resistor (with thermostat)
(NC contact) 3
Mini relay for filter capacitor alarm detector
MC1 MC2 MC3
Auxiliary contact for limit MCs (NO contact) 3
MC
Small
Reset
Converter stop
Monitor switching
Monitor switching
Contact input common
24VDC power supply
(External transistor common)
Buffer relay for driving MCs
Converter
(FR-HC2)
Inverter
R4/L14
S4/L24
T4/L34
Fuses
R/L1
S/L2
T/L3
R1/L11
S1/L21
88S
R/L1
S/L2
T/L3
R1/L11
S1/L21
P/+
N/-
AM
5
P/+
N/-
Inrush current limit resistor overheat protection
RDY
ROH
RSO
CVO
SD
Contact input common
Y1
Y2
RES
SOF
SE
C
B
A
Relay output
(fault output)
Inverter run enable signal
Converter reset
During converter run
Multi-purpose output 1
Multi-purpose output 2
X1
X2
SD
PC
88R
PU connector
X10
RES
SD
Open collector output common
Y3
Multi-purpose output 3
SE2 Open collector output common
+ -
FM
SD
Indicator
(+)
Analog signal output
(0 to 10VDC)
(-)
U
V
W
Motor
Earth
(Ground)
Do not connect anything to the inverter power input terminals R/L1, S/L2, and T/L3. Incorrect connection will damage the inverter. Connecting opposite polarity of terminals P and N will damage the converter and the inverter.
Use input terminal function selection to assign the terminal used for X10 signal. (Refer to the Inverter Instruction Manual.)
The power phases of the terminals R4/L14, S4/L24, and T4/L34 and the terminals R/L1, S/L2, and T/L3 must be matched.
Do not insert MCCB between terminals P/+ and N/- (P and P, N and N).
Always connect the terminal R, S, and T of the converter to the power supply. If the inverter is operated without connecting the terminals to the power supply, the converter will be damaged.
Do not insert MCCB or MC between (1) (terminal R/L1, S/L2, T/L3 input of the converter) and (2) (terminal R4/L14, S4/L24, T4/L34 input of the converter) of the above diagram. It will not operate properly (except for the inrush current limit MC).
Securely perform grounding (earthing) by using the grounding (earthing) terminal.
Installation of a fuse is recommended. (Refer to page 24)
The number of filter capacitors and filter capacitor alarm detectors differs by the capacity. Connect two sets of filter capacitors and filter capacitor alarm detectors for H400K, and connect three sets for H560K.
NOTE
• When connecting the converter to the inverter, match the control logic (sink logic (initial setting)/source logic). The converter does not operate properly if the control logic is different.
(Refer to Instruction Manual for the switching of the control logic. Refer to Inverter Instruction Manual for the switching of the control logic of the inverter.)
• Keep the wiring length between terminals as short as possible.
• When sudden large distortion or depression of power supply occurs, reactor may generate abnormal acoustic noise.
This acoustic noise is caused by the power supply fault and not by the damage of the converter.
• Do not connect the DC reactor to the inverter when using a high power factor converter.
• When using a sine wave filter with FR-HC2 (75K or higher), select MT-BSL-HC as a reactor for the sine wave filter.
16
17
Terminal specifications
Type
Terminal
Symbol
R/L1, S/L2,
T/L3
R4/L14,
S4/L24,
T4/L34
R1/L11,
S1/L21
P/+, N/-
RES
SOF
ROH
X1
X2
SD
PC
RDY
CVO
Y1
Y2
RSO
SE
FM
AM
5
A, B, C
88R, 88S
Terminal Name Description
Power input
Power input
These terminals are used to detect power phase and power voltage, and to input control power. Connect them to the commercial power supply. If the inverter is operated without connecting them to the commercial power supply, the converter will be damaged.
Connect them to the reactor 2.
The voltage phases of the terminals R4/L14, S4/L24 and T4/L34 and the terminals R/L1, S/L2 and T/L3 must be matched. If these terminals are not connected correctly, the converter does not operate properly.
Power supply for control circuit
These terminals are connected to the phase detection terminals R/L1 and S/L2 in the initial status. To retain the fault display and fault output, remove the jumpers (cables) and apply external power to these terminals.
Inverter connection Connect them to the inverter terminals P/+ and N/-.
Earth (Ground) For earthing (grounding) the converter chassis. It must be earthed (grounded).
Reset
Converter stop
Inrush current limit resistor overheat protection
Monitor switching
Used to reset fault output provided when a fault occurs.
Turn ON the RES signal for more than 0.1s, then turn it OFF.
Turning ON the SOF signal stops the converter.
RDY signal turns OFF, limit MC turns ON
200V class
7.5K to 75K
400V class
7.5K to 220K
Connect this terminal to terminal ROH1 of the outside box (FR-
HCB2). The ROH signal is input to stop the converter operation when the limit resistor may overheat.
400V class
280K to 560K
An auxiliary contact (NO contact) of a limit resistor MC, a limit resistor (with thermostat) (NC contact), and a filter capacitor alarm detector (NC contact, 400K and 560K) are connected to stop the converter operation when overheating of the limit resistor becomes a concern and when a filter capacitor is faulty.
FM and AM output or PU monitor display can be switched by a combination of ON/
OFF of X1 signal and X2 signal.
Contact input common
(sink) (initial setting)
Common terminal for contact input terminal (sink logic) and terminal FM.
External transistor common (source)
24VDC power supply common
External transistor common
(sink) (initial setting)
When connecting the transistor output (open collector output), such as a programmable controller in source logic, connect the external power supply common for transistor output to this terminal to prevent a malfunction caused by undesirable currents.
Common output terminal for 24VDC 0.1A power supply (terminal PC).
Isolated from terminals 5, SE and SE2.
When connecting the transistor output (open collector output), such as a programmable controller in sink logic, connect the external power supply common for transistor output to this terminal to prevent a malfunction caused by undesirable currents.
External transistor common
(sink) (initial setting)
24VDC power supply
Inverter run enable signal
Turns ON at alarm occurrence and reset (RES) signal input.
Connect this terminal to the terminal MRS or a terminal where the X10 signal is assigned to in the inverter.
Turning ON RDY signal stops the inverter.
RYD signal OFF: Inverter can run
RYD signal ON: Inverter cannot run
During converter run
Multi-purpose output 1
Multi-purpose output 2
Converter reset
Open collector output common
Common terminal for contact input terminal (source logic)
Can be used as 24VDC 0.1A power supply.
Signal is output during harmonic suppression.
Output item: OL signal (overload alarm) (initial setting)
Turns ON at an occurrence of overcurrent (150% overload or more).
Output item: PHS signal (power phase detection) (initial setting)
Turns ON when power phase detection is locked.
Turns ON at a converter reset (RES-ON).
Connect this terminal to the inverter terminal of which RES signal is assigned to.
Reset the connected inverter by turning ON the RSO.
Common terminal for the terminals RDY, CVO, OL, Y1, Y2
Connect it to the inverter terminal SD (sink logic).
For meter
Analog signal output
Input resistance : 4.7k
Voltage at opening: 21 to
27VDC
Contacts at short-circuited: 4 to 6mADC
100mA is ON.)
Power supply voltage range 19.2 to 28.8VDC
Permissible load current
Permissible load 24VDC
(27VDC maximum) 0.1A
(A voltage drop is 2.8V maximum when the signal
Select one monitor item from multiple monitor items such as input current and bus voltage. Not output during a converter reset.
The output signal is proportional to the magnitude of the corresponding monitoring item.
Monitor item can be switched by ON/OFF of terminals X1 and X2.
Permissible load current
2mA
At rated input current of the converter: 1440 pulses/s
Output signal 0 to 10VDC
Permissible load current
1mA
Load impedance 10k
Analog signal output common
Common terminal for analog signal output
Fault contact
1 changeover contact output indicates that the converter's protective function is activated and the output is stopped.
Fault: No conduction across B and C (Conduction across A and C),
Normal: Conduction across B and C (No conduction across A and C)
Contact capacity AC230V
0.3A
(Power factor=0.4)
30VDC output 0.3A
MC connection terminal
Controls the MC for the limit resistor.
Type
Terminal
Symbol
Terminal Name
Y3
Multi-purpose output 3
Description
Output item: Y5 signal (output voltage match) (initial setting)
Turns ON when the detected bus voltage equals to the commanded bus voltage.
P ermissible load: 24VDC
0.1A
SE2
Open collector output common
Common terminal for terminal Y3
— PU connector
With the PU connector, communication can be made through RS-485. (for connection on a 1:1 basis only)
Conforming standard : EIA-485 (RS-485)
Transmission format : Multidrop
Communication speed : 4800 to 38400bps
Overall length : 500m
NOTE
If the inverter is operated without connecting the terminals R/L1, S/L2, T/L3 of the converter to the power supply, the converter will be damaged.
indicates that terminal functions can be selected using Pr. 3 to Pr. 7 (input terminal function selection) and Pr. 11 to Pr.
16 (output terminal function selection).
18
Parameter list
19
REMARKS
indicates simple mode parameters.
The parameters shaded in
Parameter write selection.
allow their settings to be changed during operation even if "1" (write disabled) is set to Pr. 77
Parameter
44
45
46
47
48
49
13
14
15
16
22
23
24
29
30
31
32
25
26
27
28
33
34
35
36
10
11
12
8
9
6
7
0
1
2
3
4
5
50
51
52
53
54
55
56
57
Name Range
Simple mode selection
Maximum power supply frequency
Minimum power supply frequency
ROH terminal function selection
SOF terminal function selection
X1 terminal function selection
X2 terminal function selection
RES terminal function selection
SOF input selection
OH input selection
RDY signal logic selection
RSO terminal function selection
CVO terminal function selection
0, 9999
60Hz (Read only)
50Hz (Read only)
0 to 5, 9999
0, 1, 2
0, 1
0, 100
Y1 terminal function selection
Y2 terminal function selection
Y3 terminal function selection
ABC terminal function selection
Current limit level
Current limit level (regenerative)
OL signal output timer
0 to 16, 98, 99, 100 to 116,
198, 199, 9999
0 to 220%
0 to 220%, 9999
0 to 25s, 9999
Input current detection level
Input current detection signal delay time
0 to 220%
0 to 10s
Input current detection signal retention time 0 to 10s, 9999
Input current detection operation selection 0, 1
Zero current detection level
Zero current detection time
Life alarm status display
Inrush current limit circuit life display
0 to 220%
0 to 1s
0 to 15 (Read only)
0 to 100% (Read only)
Control circuit capacitor life display
Maintenance timer
Maintenance timer alarm output set time
Cooling fan operation selection
0 to 100% (Read only)
0 (1 to 9998)
0 to 9998, 9999
0, 1
Instantaneous power failure detection signal clear
AM output filter
Watt-hour meter clear
0, 9999
0 to 5s
0, 10, 9999
Energization time carrying-over times Read only
Cumulative power monitor digit shifted times 0 to 4, 9999
Power supply frequency monitoring reference
45Hz to 65Hz
AM terminal function selection
1 to 3, 5, 6, 7, 21,
1111 to 4444
Input power monitoring reference
DU/PU main display data selection
Input voltage monitoring reference
FM terminal function selection
Bus voltage monitoring reference
Current monitoring reference
Restart selection
0 to 100kW/0 to 3600kW
*
0, 5 to 10, 25,
1111 to 4444
0 to 500V
1 to 3, 5, 6, 7, 21,
1111 to 4444
0 to 1000V
0 to 500A/0 to 3600A
0, 9999
Increments Initial value
1
0.01s
1
1
1
0.01Hz
1
1
1
1
0.1%
0.1%
0.1s
0.1%
0.1s
0.1s
1
0.1%
0.01s
1
1%
1%
1
1
1
1
1
1
1
1
1
1
1
1
1
—
—
1
9999
0.01s
9999
0
9999
60Hz
3
4
5
99
150%
9999
0s
150%
0s
0.1s
0
5%
0.5s
0
100%
100%
0
9999
1
100
1
2
0
0
2
3
0
60Hz
50Hz
5
0
1
Customer setting
1
0.01kW/
0.1kW
1
0.1V
1234
Rated power
1234
220V/440V
1 1234
0.1V
340V/680V
0.01A/0.1A
Rated current
1 9999
Parameter Name Range
58
59
61
65
67
68
69
Free parameter 1
Free parameter 2
Key lock operation selection
Retry selection
Number of retries at fault occurrence
Retry waiting time
Retry count display erase
Reset selection/disconnected PU detection/
0 to 9999
0 to 9999
0, 10
0, 1, 2, 3, 4
0 to 10, 101 to 110
0.1 to 360s
0
75
77
80
81
82
83
117
118
119
PU stop selection
Parameter write selection
Voltage control proportional gain
Voltage control integral gain
Current control proportional gain
Current control integral gain
PU communication station number
PU communication speed
0 to 3, 14 to 17
1, 2
0 to 1000%
0 to 1000%
0 to 200%
0 to 200%
0 to 31
48, 96, 192, 384
0, 1, 10, 11
120
121
123
124
145
168
169
269
342
500
PU communication stop bit length
PU communication parity check
Number of PU communication retries
PU communication waiting time setting
PU communication CR/LF selection
PU display language selection
0, 1, 2
0 to 10, 9999
0 to 150ms, 9999
0, 1, 2
0 to 7
Parameter for manufacturer setting. Do not set.
501
Communication EEPROM write selection 0, 1
Communication error execution waiting time 0 to 999.8s
Communication error occurrence count display
0
502
Stop mode selection at communication error 0, 3
542
Communication station number (CC-Link)
543
Baud rate (CC-Link)
544
CC-Link extended setting
C0(900)
FM terminal calibration
C1(901)
989
990
991
Pr.CL
ALLC
Er.CL
PCPY
AM terminal calibration
Parameter copy alarm release
PU buzzer control
PU contrast adjustment
Parameter clear
All parameter clear
Fault history clear
Parameter copy
1 to 64
0 to 4
0, 1, 12
—
—
10, 100
0, 1
0 to 63
0, 1
0, 1
0, 1
0, 1, 2, 3
Increments
1
1
1
1
1
0.1s
1
1
1%
1
1
1
1
1%
1%
1%
1
1
1ms
1
1
1
0.1s
1
1
1
1
1
1
1
1
1
1
1
1
—
—
Initial value
Differ according to capacities. (55K or lower/75K or higher)
Differs according to the voltage class. (200V class/400V class)
Parameters which can be set when the plug-in option (FR-A7NC) is mounted.
The setting is reflected after converter reset or at the next power-ON.
"L.ERR" LED on FR-A7NC flickers when a setting is changed. If the converter is reset, the setting is reflected and LED turns off.
The parameter number in parentheses is the one for use with the parameter unit (FR-PU07).
0
0s
0
0
1
9999
9999
0
0
0
1s
0
14
2
100%
100%
100%
100%
0
192
1
2
1
9999
1
0
0
0
—
—
10/100
1
58
0
0
0
0
Customer setting
20
Protective functions
21
When a fault occurs in the converter, the protective function activates to trip the converter, and the PU display automatically changes to one of the following fault or alarm indications.
Operation Panel Indication
E — — —
Faults history
Name
Error
message
HOLD
Er1 rE1 to 4
Operation panel lock
Parameter write error
Copy operation fault
Warning
Alarm
Fault
E.THT
E.FIN
E.IPF
E.UVT
E.ILF
E.OHT
E. 2
E. 3
Err.
OL
PS
TH
MT
CP
SL
FN
E.OC2
E.OV2
E.OP3
E.PE
E.PE2
E.PUE
E.RET
E. 6
E. 7
CPU
Error
Overload signal detection
PU stop
Electronic thermal relay pre-alarm
Parameter copy
Power supply not detected
Fan fault
Overcurrent trip
Overvoltage trip
Converter overload trip (electronic thermal relay function)
Fin overheat
Instantaneous power failure
Undervoltage
Input phase loss
External thermal relay operation
HC2 dedicated board disconnection
Option fault
Communication option fault
Parameter storage device fault (control circuit board)
Parameter storage device fault (main circuit board)
Retry count excess
CPU fault
E. 8
E. 9
Input power supply fault 1
Input power supply fault 2
E.CTE
E.P24
E.CDO
E.IOH
Operation panel power supply short circuit, RS-485 terminal power supply short circuit
24VDC power output short circuit
Input current detection value exceeded
Inrush current limit circuit fault
E. 13
Internal circuit fault
Resetting the converter initializes the cumulative value of the internal thermal relay.
The error message shows an operational error. The converter does not trip.
Warnings are messages given before faults occur. The converter does not trip.
Alarms warn the operator of failures with output signals. The converter does not trip.
When faults occur, the protective functions are activated to trip the converter and output the fault signals.
Assign the OH signal to one of Pr.3 to Pr.7 (Input terminal function selection) to enable the external thermal relay operation.
This protective function is not available in the initial status.
Option and peripheral devices
Option List
Name Type Applications, Specifications, etc.
Applicable converter
CC-Link communication FR-A7NC
Converter operation, monitoring, and parameter setting can be commanded from a programmable controller.
Shared among all models
Parameter unit
(8 languages)
Parameter unit with battery pack
Parameter unit connection cable
Operation panel connection connector
Heatsink protrusion attachment
Radio noise filter
Line noise filter
FR-PU07
FR-PU07BB
FR-CB20
FR-ADP
FR-A7CN
02 to 05, 09
FR-BIF(H)
FR-BSF01/
FR-BLF
Interactive parameter unit with LCD display
Parameter unit enables parameter setting without supplying power to the converter.
Cable for connection of operation panel or parameter unit
indicates a cable length. (1m, 3m, 5m)
Connector to connect the operation panel (FR-DU07-CNV) and connection cable
Attachment for protruding the converter heatsink at the back of the
enclosure. Refer to page 13 for the enclosure cut dimensions.
For radio noise reduction (connect to the input side)
For line noise reduction
Shared among all models
Shared among all models
Shared among all models
Shared among all models
According to capacities
Shared among all models
Shared among all models
Peripheral devices/cable size list
cable size
200V class
Model
7.5K
15K
30K
55K
75K
FR-HC2-
R4/L14, S4/L24,
T4/L34
P/+, N/-
5.5
8
22
60
100
100
14
38
100
100
FR-HCB2-
R2/L12, S2/L22, T2/L32
R3/L13, S3/L23, T3/L33
8
22
60
125
100
FR-HCL21-
R/L1, S/L2, T/L3
R2/L12, S2/L22, T2/L32
8
22
60
125
100
FR-HCL22-
R3/L13, S3/L23, T3/L33
R4/L14, S4/L24, T4/L34
8
22
60
125
100
H7.5K
H15K
H30K
H55K
H75K
H110K
H160K
H220K
H280K
H400K
H560K
400V class
Model
FR-HC2-
R4/L14, S4/L24,
T4/L34
P/+, N/-
2 3.5
5.5
22
60
38
60
100
150
200
2
200
2
250
5.5
14
38
38
60
125
2
100
2
125
2
200
3
250
FR-HCB2/FR-HCC2-
R2/L12, S2/L22, T2/L32
R3/L13, S3/L23, T3/L33
38
60
100
150
3.5
5.5
22
60
60
60
38
FR-HCL21-
R/L1, S/L2, T/L3
R2/L12, S2/L22, T2/L32
3.5
5.5
22
60
38
60
100
150
200
2
200
2
250
FR-HCL22-
R3/L13, S3/L23, T3/L33
R4/L14, S4/L24, T4/L34
3.5
5.5
22
60
38
60
100
150
200
2
200
2
250
For the 55K or lower, the cable size is that of the cable (HIV cable (600V class 2 vinyl-insulated cable) etc.) with continuous maximum permissible temperature of 75
C. It assumes that the surrounding air temperature is 50C or less and the wiring distance is 20m or less.
For the 75K or higher, the recommended cable size is that of the cable (LMFC (heat resistant flexible cross-linked polyethylene insulated cable) etc.) with continuous maximum permissible temperature of 90
C. It assumes that the surrounding air temperature is 50C or less and wiring is performed in an enclosure.
22
23
Circuit breakers and magnetic contactors
Check the model of the converter and select peripheral devices according to the capacity. Refer to the table below to prepare appropriate peripheral devices.
200V class
Converter Model
FR-HC2-7.5K
FR-HC2-15K
FR-HC2-30K
FR-HC2-55K
FR-HC2-75K
Moulded Case Circuit Breaker (MCCB)
or Earth Leakage Circuit Breaker (ELB)
(NF, NV type)
50A
75A
150A
300A
350A
Magnetic
Contactor (MC)
S-N25
S-N50
S-N80
S-N180
S-N300
400V class
Converter Model
FR-HC2-H7.5K
FR-HC2-H15K
FR-HC2-H30K
FR-HC2-H55K
FR-HC2-H75K
FR-HC2-H110K
FR-HC2-H160K
FR-HC2-H220K
FR-HC2-H280K
FR-HC2-H400K
FR-HC2-H560K
Moulded Case Circuit Breaker (MCCB)
or Earth Leakage Circuit Breaker (ELB)
(NF, NV type)
30A
50A
75A
150A
175A
250A
400A
500A
700A
900A
1500A
Magnetic
Contactor (MC)
S-N18
S-N20
S-N35
S-N80
S-N95
S-N180
S-N300
S-N400
S-N600
S-N800
S-N400
(three in parallel)
Select an NFB according to the power supply capacity.
Install one NFB per converter.
For the use in the United States or Canada, provide the appropriate UL and cUL listed fuse that is
MCCB
MCCB
Converter
Converter
Inverter
Inverter
IM
IM suitable for branch circuit protection. (Refer to the instruction manual)
Magnetic contactor is selected based on the AC-1 class.The electrical durability of magnetic contactor is 100,000 times.When the magnetic contactor is used for emergency stop during motor driving, the electrical durability is 25 times.
When using the MC for emergency stop during motor driving or using on the motor side during commercial-power supply operation, select the MC with class
AC-3 rated current for the motor rated current.
NOTE
When the MCCB on the converter input side trips, check for the wiring fault (short circuit), damage to internal parts of the converter, etc. Identify the cause of the trip, then remove the cause and power ON the breaker.
Configure a system where the magnetic contactor at the converter input side shuts off the power supply at a failure of the converter or the connected inverter. (The converter does not shut off the power supply by itself.) Failure to do so may overheat and burn the resistors in the converter and the connected inverter.
Fuse
Installation of a fuse is recommended between a high power factor converter and an inverter.
Select a fuse according to the capacity of the connected motor. When using a motor, of which the capacity is smaller than the inverter capacity by two ranks or more, select the fuse with the capacity that is one rank lower than the inverter capacity.
Select a fuse from the table below, and install it to both of the P side and the N side between the high power factor converter and the inverter.
[Fuse selection table]
Motor capacity
(kW)
55
75
90
110
132
160
185
18.5
22
30
37
45
0.1
0.2
0.4
0.75
1.5
2.2
3.7
5.5
7.5
11
15
220
250
280
315
355
400
Fuse rating (A)
700
800
—
—
—
—
—
250
315
400
500
630
25
50
63
100
125
160
200
5
10
16
20
—
—
—
—
—
—
200V class
6.9 URD 30 TTF 0050
6.9 URD 30 TTF 0063
6.9 URD 30 TTF 0100
6.9 URD 30 TTF 0125
6.9 URD 30 TTF 0160
6.9 URD 30 TTF 0200
6.9 URD 30 TTF 0250
6.9 URD 30 TTF 0315
6.9 URD 30 TTF 0400
6.9 URD 30 TTF 0500
6.9 URD 31 TTF 0630
6.9 URD 31 TTF 0700
6.9 URD 31 TTF 0800
—
—
—
—
—
—
—
—
—
—
—
Fuse rating (A)
350
450
500
550
630
800
900
125
160
200
250
315
—
—
12.5
16
16
20
30
50
50
80
125
1000
1250
1400
1600
1800
1800
400V class
—
—
6.900 CP GR 10.38 0012.5
6.900 CP GR 10.38 0016
6.900 CP GR 10.38 0016
6.900 CP GR 10.38 0020
6.900 CP GR 10.38 0030
6.9 URD 30 TTF 0050
6.9 URD 30 TTF 0050
6.9 URD 30 TTF 0080
6.9 URD 30 TTF 0125
6.9 URD 30 TTF 0125
6.9 URD 30 TTF 0160
6.9 URD 30 TTF 0200
6.9 URD 30 TTF 0250
6.9 URD 30 TTF 0315
6.9 URD 30 TTF 0350
6.9 URD 30 TTF 0450
6.9 URD 30 TTF 0500
6.9 URD 31 TTF 0550
6.9 URD 31 TTF 0630
6.9 URD 31 TTF 0800
6.9 URD 32 TTF 0900
6.9 URD 32 TTF 1000 or
6.9 URD 31 TTF 0630
6.9 URD 33 TTF 1250 or
6.9 URD 31 TTF 0700
6.9 URD 33 TTF 1400 or
6.9 URD 31 TTF 0800
6.9 URD 232 TTF 1600 or
6.9 URD 31 TTF 0800
6.9 URD 232 TTF 1800 or
6.9 URD 32 TTF 0900
6.9 URD 232 TTF 1800 or
6.9 URD 32 TTF 0900
6.9 URD 33 TTF 1250
6.9 URD 32 TTF 0900
6.9 URD 32 TTF 0900
450
500
—
—
—
—
2500
2700
560 — — 2700
Manufacturer: Mersen Japan K.K.
Contact: Sun-Wa Technos Corporation
For fuse holders (2-pole type), use US102 (no blowout indicator) or US102I (with blowout indicator).
When installing several fuses in parallel, leave 12mm or more between the fuses.
NOTE
Install a fuse across terminal P/+ of the inverter and the converter and across terminal N/- of the inverter and the
[Estimated lifespan of fuse]
Part Name
Replacement method
Fuse 10 years Replace with a new one
Estimated lifespan for when the yearly average surrounding air temperature is 50?C (without corrosive gas, flammable gas, oil mist, dust and dirt etc.)
NOTE
If the fuse melts down, wiring failure such as a short circuit may be the cause. Identify the problem and fix it before replacing the fuse.
24
25
Precaution on selection and operation
SAFETY INSTRUCTIONS
To use the product safely and correctly, make sure to read "the Instruction Manual" before using the product.
This product has not been designed or manufactured for use with any equipment or system operated under life-threatening conditions.
Please contact our sales office when you are considering using this product in special applications such as passenger mobile, medical, aerospace, nuclear, power or undersea relay equipment or system.
Although this product was manufactured under conditions of strict quality control, you are strongly advised to install safety devices to prevent serious accidents when it is used in facilities where breakdowns of the product or other failures are likely to cause a serious accident.
Do not use this product for a load other than dedicated inverters.
Installation Precautions Peripheral Device Selection
Precautions
Wiring distance
For the wiring distance between the high power factor converter (FR-HC2) and inverter, refer to the following table.
Across terminals P and P / terminals
N and N
Other control signal lines
50m or shorter
30m or shorter
The total wiring distance between the high power factor converter (FR-HC2) and standard accessories must be
30m or shorter. For 280K or higher, refer to the Instruction
Manual.)
Selection and installation of the moulded case circuit breaker
Install a moulded case circuit breaker (MCCB) on the power receiving side to protect the wiring at the converter's
input side. For the MCCB selection, refer to page 23. (Refer
to the materials related to the breaker.) For earth leakage circuit breakers, use the harmonic/surge compatible model provided by Mitsubishi.
Reactor installation at power supply side
The terminals R/L1, S/L2, and T/L3 of the high power factor converter are control terminals to detect power phases of the power supply. When wiring, the voltage phases of terminals R4/L14, S4/L24, and T4/L34 and the voltage phases of terminals R/L1, S/L2, and T/L3 must be matched. Failure to connect these terminals correctly will lead to an improper operation of the high power factor converter.
If the inverter is operated without connecting the terminals R/L1, S/L2, and T/L3 of the high power factor converter to the power supply, the high power factor converter will be damaged.
Operating Precautions
The Guideline treats the converter as a no-harmonicemitting device (K5 = 0), but the harmonic component is not completely 0.
Selection Precautions
Connectable inverter
Connect to the inverter that can accept DC inputs.
For the MELTRAC, FR-A500L, and FR-F500L series inverters, make sure the connecting inverter is compatible with the high power factor converter.
Connection with an incompatible inverter will damage the inverter and the converter.
Electromagnetic interference
Since the high power factor converter chops input voltage at high carrier frequency, it generates noises. If these noises cause peripheral devices to malfunction, countermeasures should be taken to suppress noises (EMI measures). The EMI measures differ depending on the noise transmission paths.
The FR-BIF radio noise filter is useful to suppress noises on AM radio broadcasting.
The FR-BSF01/FR-BLF line noise filters are useful for preventing malfunction of sensors, etc.
For the noise emitted from power cables, take a distance of 30cm (at least 10cm) from the power cables, and use shielded twisted pair cables for signal cables. Do not earth (ground) the shield. Connect the shield to one common terminal.
EMI measure example
FR-
BLF
Enclosure
Decrease carrier frequency
FR-
BLF
Install common mode filter
(FR-BLF, FR-BSF01) on the inverter output side
M Motor
Equipment power supply
Refer to the instruction manual for earthing (grounding) the high power factor converter and accessories.
Separate the inverter and power line by more than
30cm (at least 10cm) from sensor circuit.
Control power supply
FR-
BIF
Power supply for sensor
Use 4-core cable for motor power cable and use one cable as earth (ground) cable.
Use a shielded twisted pair cable
Sensor
Do not earth (ground) enclosure directly
Do not earth (ground) control cable
Do not earth (ground) shield but connect it to signal common cable.
Sine wave filter selection precautions
When using a sine wave filter with FR-HC2 (75K or higher), use MT-BSL-HC for the sine wave filter.
Warranty
1. Gratis warranty period and coverage
[Gratis warranty period]
Note that an installation period of less than one year after installation in your company or your customer's premises or a period of less than18 months (counted from the date of production) after shipment from our company, whichever is shorter, is selected.
[Coverage]
(1) Diagnosis of failure
As a general rule, diagnosis of failure is done on site by the customer.
However, Mitsubishi or Mitsubishi service network can perform this service for an agreed upon fee upon the customer's request.
There will be no charges if the cause of the breakdown is found to be the fault of Mitsubishi.
(2) Breakdown repairs
There will be a charge for breakdown repairs, exchange replacements and on site visits for the following four conditions, otherwise there will be a charge.
1) Breakdowns due to improper storage, handling, careless accident, software or hardware design by your company and your customers.
2) Breakdowns due to modifications of the product without the consent of the manufacturer.
3) Breakdowns resulting from using the product outside the specified specifications of the product.
4) Breakdowns that are outside the terms of warranty.
Since the above services are limited to Japan, diagnosis of failures, etc. are not performed abroad.
If you desire the after service abroad, please register with Mitsubishi. For details, consult us in advance.
2. Exclusion of opportunity loss from warranty liability
Regardless of the gratis warranty term, compensation to opportunity loss incurred to your company or your customers by failures of Mitsubishi products and compensation for damages to products other than Mitsubishi products and other services are not covered under warranty.
3. Repair period after production is discontinued
Mitsubishi shall accept product repairs for seven years after production of the product is discontinued.
4. Terms of delivery
In regard to the standard product, Mitsubishi shall deliver the standard product without application settings or adjustments to the customer and Mitsubishi is not liable for on site adjustment or test run of the product.
Related Factory Automation Products
Contactors and Motor Starters MS-N Series
Compact body with full satisfaction
* Lineup from 10A to 800A frames. Available in wide range of applications.
* Conforming to various international specifications as standard.
* Equipped with safe open function contact, applicable to circuits in “machine safety category 4”.
* CAN terminals achieved wiring rationalization and safety improvement.
26
L(NA)06070ENG-A(1212)MEE
Safety Warning
To ensure proper use of the products listed in this catalog, please be sure to read the instruction manual prior to use.
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement
Table of contents
- 1 FR-HC2 catalog
- 2 Features
- 3 Connection example
- 4 Standard specification rating
- 5 Common specifications
- 6 Checking peripheral devices
- 7 Compatible inverter for the high power factor converter
- 8 Wiring of several inverters to one converter
- 9 Outline dimension drawings
- 13 Protruding the heatsink
- 15 Terminal connection diagram (when using with the FR-A700 series)
- 17 Terminal specifications
- 19 Parameter list
- 21 Protective functions
- 22 Option and peripheral devices
- 22 Option List
- 22 Peripheral devices/cable size list
- 25 Precaution on selection and operation
- 25 Installation Precautions
- 25 Wiring distance
- 25 Reactor installation at power supply side
- 25 Operating Precautions
- 25 Selection Precautions
- 25 Connectable inverter
- 25 Sine wave filter selection precautions
- 25 Peripheral Device SelectionPrecautions
- 25 Selection and installation of themoulded case circuit breaker
- 25 Electromagnetic interference
- 26 Warranty
- 26 Related Factory Automation Products