datasheet for M2VS by M
M2VS
INSTRUCTION MANUAL
SIGNAL TRANSMITTER
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket + input resistor) ..... (1)
Input resistor is provided only with current input type.
■ MODEL NO.
Confirm that the model number described on the product is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■ WARNING
If equipment is not used in a manner not specified by MSystem, the protection provided by the equipment may be
impaired.
■ NONINCENDIVE APPROVAL OPTION
•This equipment is suitable for use in Class I, Div. 2,
GroupsA,B,CandDorNon-HazardousLocationsonly.
•WARNING!Before You Remove the Unit from Its Base
Socket or Mount It, Turn Off the Power Supply and Input
Signal for Safety.
•WARNING!–ExplosionHazard–
Substitution of Components May Impair Suitability for
ClassI,Div.2.
•WARNING!–ExplosionHazard–
Do Not Disconnect Equipment Unless Power Has Been
SwitchedOfforTheAreaisKnownToBeNon-Hazardous.
•Theequipmentwasevaluatedforuseintheambienttemperature and relative humidity as mentioned in ‘ENVIRONMENT’section.
•Theinputandoutputwiringmustbeinaccordancewith
ClassI,Div.2wiringmethodsandinaccordancewiththe
authority having jurisdiction for use in these hazardous
locations.
■ CONFORMITY WITH EC DIRECTIVES OR UL
•ThisequipmentissuitableforPollutionDegree2andInstallationCategoryII.Reinforcedinsulation(signalinput
oroutputtopowerinput:300V)andbasicinsulation(signalinputtooutput:300V)aremaintained.Priortoinstallation, check that the insulation class of this unit satisfies
the system requirements.
• The equipment must be mounted inside a suitable ire
enclosure.
•Altitudeupto2000meters
•The equipment must be installed such that appropriate
clearance and creepage distances are maintained to conformtoCE/ULrequirements.FailuretoobservetheserequirementsmayinvalidatetheCE/ULconformance.
M2VS
MODEL
■ POWER INPUT RATING & OPERATIONAL RANGE
•Locatethepowerinputratingmarkedontheproductand
confirm its operational range as indicated below:
100–240Vand85–264VACrating:85–264V
(90–264VforUL),47–66Hz,approx.3–5VA
24VDCrating:24V±10%,approx.3W
11–27VDCrating:11–27V,approx.3W
110VDCrating:85–150V(110V±10%forUL),approx.3W
■ GENERAL PRECAUTIONS
•Beforeyouremovetheunitfromitsbasesocketormount
it, turn off the power supply and input signal for safety.
■ ENVIRONMENT
•Indooruse
•Whenheavydustormetalparticlesarepresentintheair,
install the unit inside proper housing with sufficient ventilation.
•Donotinstalltheunitwhereitissubjectedtocontinuous
vibration.Donotsubjecttheunittophysicalimpact.
•Environmental temperature must be within -5 to +55°C
(23to131°F)withrelativehumiditywithin30to90%RH
in order to ensure adequate life span and operation.
•Besurethattheventilationslitsarenotcoveredwithcables, etc.
■ WIRING
•Do not install cables (power supply, input and output)
close to noise sources (relay drive cable, high frequency
line, etc.).
•Do not bind these cables together with those in which
noisesarepresent.Donotinstalltheminthesameduct.
■ AND ....
•Theunitisdesignedtofunctionassoonaspowerissupplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
•With voltage output, do not leave the output terminals
shortcircuited for a long time. The unit is designed to endure it without breakdown, however, it may shorten appropriate life duration.
COMPONENT IDENTIFICATION
Body
Base Socket
Input Resistor
Model
Fixing Screw
ZERO
SPAN
Zero Adj.
Span Adj.
Connection
Diagram
Specifications
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-5018 Rev.10
P. 1 / 2
M2VS
INSTALLATION
CHECKING
Loosentheixingscrewatthefrontoftheunitinorderto
separate the body from the base socket.
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Powerinputvoltage:Checkvoltageacrosstheterminal
13–14withamultimeter.
3) Input:Checkthattheinputsignaliswithin0–100%of
the full-scale.
4) Output: Check that the load resistance meets the described specifications.
■ DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Position the
upper hook at the rear side
of base socket on the DIN
rail and push in the lower.
Whenremovingthesocket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
DIN Rail
35mm wide
ADJUSTMENT PROCEDURE
Spring Loaded
DIN Rail Adaptor
■ WALL MOUNTING
Referto“EXTERNALDIMENSIONS.”
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
Whenaninputresistorisprovidedwiththemodule,attach
it together with input wiring to the input screw terminals.
+
INPUT
R
–
*
1
9 +
4
12 –
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any calibration.
Formatchingthesignaltoareceivinginstrumentorincase
of regular calibration, adjust the output as explained in the
following.
■ HOW TO CALIBRATE THE OUTPUT SIGNAL
Useasignalsourceandmeasuringinstrumentsofsuficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO:Apply0%inputandadjustoutputto0%.
2) SPAN:Apply100%inputandadjustoutputto100%.
3) CheckZEROadjustmentagainwith0%input.
4) When ZERO value is changed, repeat the above procedure1)–3).
OUTPUT
MAINTENANCE
13 U(+)
POWER
14 V(–)
*Input shunt resistor attached for current input.
Regularcalibrationprocedureisexplainedbelow:
■ CALIBRATION
Warmuptheunitforatleast10minutes.Apply0%,25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accuracydescribedinthedatasheet.Whentheoutputisoutof
tolerance, recalibrate the unit according to the “ADJUSTMENTPROCEDURE”explainedearlier.
EXTERNAL DIMENSIONS unit: mm (inch)
■ TERMINAL ASSIGNMENTS
INPUT RESISTOR
(model: REM2)
DIN RAIL
35mm wide
8–M3
SCREW
21.5 (.85) 10 (.39)
84 (3.31)
4 1
12
[4 (.16)]
4 1
8
5
12
9
9
14 13
15 (.59)
114 (4.49)
72 (2.83)
5
59 (2.32)
8
23 (.91)
4 (.16)
70.5 (2.78)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
19 (.75)
6 (.23)
• When mounting, no extra space is needed between units.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
14 13
Input shunt resistor attached
for current input.
EM-5018 Rev.10
P. 2 / 2