Damocles MINI Specifications

Damocles MINI Specifications
Damocles MINI - Specifications
HW group
Damocles MINI – Specifications
Connectors and LEDs
Power – green (RJ-45 connector)........ External power connected
LINK
– yellow (RJ-45 connector)...... Ethernet interface activity
Power
LINK
Parameters

Ethernet: RJ45 – 10BASE-T/10 Mbps

Communication:

4 Digital Inputs: Dry contact inputs (voltage-free)
o
WEB, SNMP, XML, SMTP
4x digital pulses counter: Yes, 4x 32 bits

2 Relay Outputs: Low voltage relay outputs NO/NC

Configuration DIP switches
o
DIP1: Restores factory defaults when 3x toggled within 5 seconds after power up
o
DIP2: Prevents configuration changes - lock

Power supply: +9-15V / 250 mA

Dimensions: 35 x 102 x 77 [mm]

LED indicators: Power, LINK, STATUS, ALARM
www.HW-group.com
1/4
Damocles MINI - Specifications
ETHERNET
Interface
Supported protocols
SNMP compatibility
RJ45 (10BASE-T) – 10 Mbps or 10/100 Mbps network compatible
IP: ARP, TCP/IP (HTTP, NTP, SMTP), UDP/IP (SNMP)
Ver.1.00 compatible, partial ver.2.0 implementation
DRY CONTACT INPUTS
Port
Type
Sensitivity
Max. distance
Counter
I1, I2, I3, I4
Digital Input (supports NO/NC Dry contact)
1 (On) = 0-500 Ω (Right pin on the terminal block can be connected to 12V GND)
Up to 50m
4x 32 bits, Counter is clear after reset or power failure
OUTPUTS
Port / type
Max. load
State
OUT1, OUT2 / Relay contacts (NC-COM-NO)
Max 2A, up to 24W (2A/12V or 0.5A/48V)
Power up state (no state restart memory)
POWER input
Port
Type
Connector
POWER 9-15V DC
Main device power input (typically 250 mA)
Jack (barrel, inner 2.5 mm outer 6.3 mm)
LED Status indicators
POWER (RJ45)
LINK & Activity (RJ45)
Green - power OK
Yellow - Ethernet connectivity
HW group
DIP SWITCH
DIP1: Setup
DIP2: Security
Physical parameters
Temperature range
Dimensions / Weight
EMC
www.HW-group.com
Load defaults: Set ON, power-up device, toggle 3 times during first 5 seconds to load
defaults
ON = Security mode - remote configuration disabled
OFF = Non-secure mode - remote configuration enabled
Operating: 0 to +65 °C (+14 to +150 °F) / Storage: -25 to +85 °C (-13 to +185 °F)
35 x 102 x 77 [mm] / 150 g
FCC Part 15, Class B, CE - EN 55022, EN 55024, EN 61000
2/4
Damocles MINI - Specifications
HW group
Dry contact Inputs
Digital input terminals may be connected to voltage-free contacts or the GND pin. The inputs are
electrically connected to the 12V power supply. Never connect the inputs to the 48V supply voltage!

Unconnected inputs read as “0 (Off)”

Active inputs read as “1 (On)”



Supported sensors: Any contact without external voltage (dry contact)
Polling period: 800 ms
Range of sensor IDs: Inputs use IDs from 1 to 4
In
COM
In
I1
I1
COM
Power
12V
+U
+
+
GND
-
-
12V
GND
Relay outputs
NO
COM
NO NC
POWER OUT
12V
+
-

NO and NC labels apply to Off (0) state, or device turned off

When the output is On (1), a “Normally Open” (NO) relay contact is closed

Indication: Contact state (closed / open) is indicated by a LED

Isolation: The double-throw contact is electrically isolated from the rest of the device

ID range: Outputs use ID addresses from 151 to 180
www.HW-group.com
3/4
Damocles MINI - Specifications
HW group
M2M interface
This product can be used with third-party SW applications.
For a description of the interfaces (XML format, detailed description of SNMP, mapping of
Modbus/TCP variables), see the detailed “Poseidon family” manual.

XML (over HTTP)

SNMP, SNMP traps

Modbus/TCP

SMTP (E-mail)
TIP
• For a detailed description of the M2M interfaces and interfacing details, see
the detailed Poseidon family manual.
SDK (Software Development Kit)
Programmers can take advantage of the HWg SDK (Software Development Kit) with an ActiveX
interface and ready-made examples.

VB - Visual
examples)

Borland C++ (1xx examples)

Microsoft Visual C++ (2xx examples)

C# / .NET (5xx examples)

Borland Delphi (4xx examples)

JAVA

PHP / ASP

other examples that do not directly
use SDK functions (all 9xx examples)
www.HW-group.com
Basic
(6.0)
- (3xx
4/4
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement