TT 73

TT 73
TT 73
MICROPROCESSOR-BASED
DIGITAL ELECTRONIC TIMER
INDEX
1
1.1
1.2
2
2.1
2.2
2.3
3
3.1
3.2
3.3
3.4
4
4.1
4.2
4.3
4.4
4.5
5
5.1
5.2
6
6.1
6.2
7
7.1
7.2
7.3
7.4
7.5
INSTRUMENT DESCRIPTION
GENERAL DESCRIPTION
FRONT PANEL DESCRIPTION
PROGRAMMING
SET POINT PROGRAMMING
PARAMETERS PROGRAMMING
PARAMETERS LOCK
INSTALLATION AND USE ADVICES
USE ALLOWED
MECHANICAL MOUNTING
ELECTRICAL CONNECTIONS
ELECTRICAL CONNECTION DRAWING
OPERATING MODE
COMMANDS OPERATING MODE
DISPLAY OPERATING MODE
OUT 1 OPERATING MODE
OUT 2 OPERATING MODE
CNT EN INPUT OPERATING MODE
PROGRAMMABLE PARAMETERS
PARAMETERS TABLE
PARAMETERS DESCRIPTION
TROUBLES, MAINTENANCE, WARRANTY
CLEANING
WARRANTY AND REPAIRS
TECHNICAL DATA
ELECTRICAL DATA
MECHANICAL DATA
MECHANICAL DIMENSIONS, PANEL CUT OUT AND
FIXING DEVICE
FUNCTIONAL DATA
INSTRUMENT CODE
1 - INSTRUMENT DESCRIPTION
OPERATING INSTRUCTIONS
Vr. 01 (ENG) - cod.: ISTR 06083
TECNOLOGIC S.p.A.
VIA INDIPENDENZA 56
27029 VIGEVANO (PV) ITALY
TEL.: +39 0381 69871
FAX: +39 0381 698730
internet : http:\\www.tecnologic.it
e-mail: [email protected]
1.1 – GENERAL DESCRIPTION
TT 73 is a programmable microprocessor based timer with 1or 2
outputs.
The instrument offers the possibility to program: up to 3 set points
time, 5 operating modes for the output OUT1, 4 operating modes for
the output OUT2, 4 time scales (from 9999 hrs. maximum to 0.1
sec. minimum), 4 functioning modes of counting enable and 2
counting modes (UP or DOWN).
The instrument can have an inside back up battery (optional) which
permits the counting also without power supply.
The counting state is visualised on 4 digits display while the outputs
state is signalised by a led.
The instrument can have 2 outputs (relay or to drive solid state
relays) and 2 digital inputs for count enable (CNT EN) and reset
(RES) which can be for free voltage contacts or voltage signals (the
same voltage supply value).
The programming of the instrument is possible by means of the 3
keys placed on the front while the counting is possible using the
frontal key START/STOP or using the back inputs CNT EN and
RES.
PREVIOUS STATEMENT:
In this manual are contained all the necessary information for a
correct installation and the instructions for the use and the 1.2 - FRONT PANEL DESCRIPTION
maintenance of the product; we recommend, therefore, to read
carefully the following instructions.
The maximum care has been used in the realisation of this
document, anyway TECNOLOGIC S.p.A. does not assume any
responsibility deriving from the use of itself.
The same consideration has to be done for each person or
Company involved in the creation of this manual.
The herewith issue is an exclusive property of TECNOLOGIC
S.p.A. which forbids any reproduction and divulgation, although
partial, if not expressly authorised.
TECNOLOGIC S.p.A. reserves the right to execute aesthetically and
functional modifications, at any moment and without any notice.
1 - Key P : Used for the set point setting and to program the
functioning parameters
TECNOLOGIC spa - TT 73 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06083 - PAG. 1
2 - Key DOWN : Used to decrease the values or to select
parameters
3 - Key UP : Used to increase the values or to select parameters
4 - Key U (Start/Stop) : Used to Start, Stop or reset the count
5 - Led OUT 1 : It indicates when the output OUT1 is on or off.
6 - Led OUT 2 : It indicates when the output OUT2 is on or off.
7 - Led separator : It indicates the separation between hours and
minutes, minutes and seconds or seconds and cents.
8 - Led SET/CNT : Signalize the set point or the parameters
programming mode (flashing fast), the count on (flashing each
second), the count stopped (on) or reset mode (off).
2 - PROGRAMMING
2.1 – SET POINTS PROGRAMMING
The instrument permits to program up to 3 time sets: “t1”, “t2”,
“t3”.
To program this times do proceed as follows :
Pushing key P and keeping it pushed for 1 sec. approx., the display
will visualize “t1” and led SET/CNT will blink rapidly.
Releasing the key, on the display will be visualized the programmed
Set Point “t1”.
To modify it, work on keys UP, to increase the value or on key
DOWN, to decrease it.
If the programmed functioning mode require the set “t2” (F1 = 3, 4
or 5), for programming this pressing key P again and the display will
show “t2”.
Releasing the key, on the display will be visualized the programmed
Set Point “t2” and will be possible to modify it by the key UP or
DOWN.
If the programmed functioning mode require the set “t3” (F2 = 3 o
4), for programming this pressing key P again and the display will
show “t3”.
Releasing the key, on the display will be visualized the programmed
Set Point “t3” and will be possible to modify it by the key UP or
DOWN.
The outgoing from the set points programming it’s automatically
obtainable not working on any key for 5 sec. approx. or pressing
only one time the key U, thus the counting value willl again be
displayed.
The programming of the set times is always possible, both with
counting on or off.
The display will go back to the normal functioning, the parameters
will not be accessible anymore and it will only be possible to modify
the Set Point.
To have again access at the parameters, repeat the same
procedure pushing key P and selecting "uL" ; finally go out from the
parameters lock modality.
3 - INSTALLATION AND USE ADVICES
3.1 – USE ALLOWED
The instrument has been projected as measure and
control device, built according to EN61010-1 for the
altitudes operation until 2000 ms.
The use of the instrument for applications not
expressly allowed by the above mentioned rule has
to foreseen proper protection devices.
The instrument CAN’T be used in environments with dangerous
atmosphere (flammable or explosive) without a proper protection.
It has to be reminded that the user has to take care that the
electromagnetic rules are being respected also after the instrument
installing, eventually using proper filters.
Whenever a failure or a bad functioning of the instrument may
cause dangerous situations or damage to people, things or animals
it has to be reminded that the plant has to be equipped with
additional electromechanical devices in order to grant the safety.
3.2 – MECHANICAL MOUNTING
The instrument, in DIN case 72 x 72 mm, is designed for flush-in
panel mounting.
Make a hole 66,5 x 66,5 mm and insert the instrument, fixing it with
the provided special brackets.
We recommend to mount the gasket to obtain the front protection
degree as declared. Do avoid to place the instrument in ambient
with very high humidity or dirt that may create condensation or
introduction into the instrument of conductive substances.
Ensure the adequate ventilation to the instrument and avoid the
installation within boxes where are placed devices which may
overheat or have as a consequence the instrument’s functioning at
higher temperature than allowed and declared.
Connect the instrument as far as possible from source of
electromagnetic disturbances so as motors, power relays, relays,
electrovalves,etc.
3.3 – ELECTRICAL CONNECTIONS
Carry out the electrical wiring connecting only one wire for each
terminal , according to the following diagram, checking that the
power supply is the same as indicated on the instrument and the
loads current is not higher than the maximum current admitted.
The instrument, being a built in equipment with permanent
connection into a cabinet, is not equipped neither with switches nor
with internal devices protecting from overcurrent : the installation
shall employ a two-phase circuit-breaker, placed as near as
possible to the instrument, located in a position easily reachable by
the user and marked as instrument disconnecting device.
It's recommended, furthermore, to properly protect all the electric
circuits connected to the instrument, with devices (ex. fuses)
proportionate to the circulating currents.
It's strongly recommended to use cables with proper insulation,
according to the working voltages and temperatures.
Furthermore, the input cable of the probe has to be kept separate
from line voltage wiring. If the input cable of the probe is screened, it
has to be connected on the ground with only one side.
When you choose the "b" parameter with option 2 (timer goes on
operating in case of power failure) is necessary to check that the
2.3 – PARAMETERS LOCK
inside battery is present and enable.
It’s possible to lock the access at the programming parameters with With the purpose to prolong its duration it recommends him to
the following procedure :
disconnect the battery when it is not necessary to the operation.
Switch off the instrument, push key P and keep it pushed while the Finally, it is advisable to check that the parameters are those
instrument is switched on again.
desired before connecting the outputs to the actuators in order to
After approx. 5 sec. on the display will appear "uL" (unlock) which avoid plant anomalies which may cause injuries to people, things or
indicates that the parameters are accessible.
animals.
Keeping pushed key P and pushing key DOWN it will appear "Lo"
(lock) which indicates that the parameters are not accessible.
Tecnologic S.p.A. and its legal representatives are not
Release key P to exit from this modality.
responsible for any eventual damages to people, things or
2.2 – PARAMETERS PROGRAMMING
To have access at the functioning parameters, it’s necessary to
push key P and keep it pushed for 5 sec. approx.
After 4 sec. will appear the label of the first parameter ("F1").
Now it possible to release key P and it will appear the value
programmed for parameter "F1".
To modify this value work on keys UP or DOWN.
Once the desired value has been programmed, pushing again key P
the display will show the label of the successive parameter.
Releasing then key P, it will appear the value programmed for that
parameter which can be modified working on keys UP and DOWN.
Pushing and releasing key P it’s possible to visualize all the
parameters labels (when key is pushed) and the relative
programming (when key is released) one after the other.
The outgoing from the parameters programming it’s obtainable not
working on any key for 20 sec. approx. or pressing only one time the
key U, thus the counting value willl again be displayed.
P.A.: During the counting is not possible to enter in the parameters
programming mode.
TECNOLOGIC spa - TT 73 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06083 - PAG. 2
animals deriving from the instrument violation, not proper or
wrong use or in any case not in accordance with the instrument
features.
3.4 - ELECTRICAL CONNECTION DRAWING
F1 = 2 - FEEDTHROUGH :
On receiving the START signal, the instrument enables the output
OUT1.
The output is disabled when the set time value “t1” has been
reached.
The output will be enabled again after the transmission of a RESET
signal and a subsequent START signal.
F1 = 3 - ASYMMETRICAL OSCILLATOR START ON:
This operating mode allows the user to enter two SET times “t1” and
“t2”, and therefore also involves the "S2" parameter .
On receiving the START signal, the output OUT1 is immediately
enabled and remains enabled for the time period t1.
4 - OPERATING MODE
Then the output is disabled and remains disabled for the time period
t2.
4.1 – FUNCTIONING OF THE COUNTING COMMANDS
The counting can be enabled and disabled through the frontal key This procedure goes on until a RESET signal is transmitted.
U, or through the remote inputs CNT EN and RES.
The operating mode of the key U is defined by the parameter "t",
the operating mode of the input CNT EN is defined by the parameter
"E" while the input RES always works as reset, i.e. it stops and
resets the counting when it is activated and moreover it has priority
on the other commands (when it is activated it doesn't allow the
starting of the counting).
When the instrument is predisposed for the continuation of the
counting also without power supply, during the counting under F1 = 4 - ASYMMETRICAL OSCILLATOR START OFF:
conditions of lack of supply the only active command is the RESET This operating mode allows the user to enter two SET times “t1” and
one, which can be given only from the frontal key U.
“t2”, and therefore also involves the "S2" parameter .
When the instrument is supplied through the battery it is not On receiving the START signal, the output remains disabled until
therefore possible to make the counting start again once stopped.
the set time period “t1” has expired.
4.2 – FUNCTIONING OF THE DISPLAY
The led SET/CNT is used to indicate the access into the
programming (flashing fast), the counting in action (flashing each
second), the counting interrupted before the term (lighted fixed) or
the counting finished and the state of reset (off).
After the reset, the display visualizes 0000 if the counting mode is
programmed as UP (par. "C" = 1) or it visualizes the programmed
set value if the counting mode is programmed as DOWN (par. "C" =
2).
During the counting, the display visualizes the value of time that
spends in UP or in DOWN mode.
If the back-up mode has been programmed to continue the counting
in action without power supply, the display remains lighted but with
an inferior brightness (with the purpose to limit as much as possible
the absorption from the battery).
Then the output is enabled.
The output is disabled again when the set time period “t2” has
expired. This procedure goes on until a RESET signal is transmitted.
F1 = 5 - ONE CYCLE ASYMMETRICAL OSCILLATOR START OFF:
The operation results similar to the "F1"=4 with the only difference
that only one cycle of OFF/ON is performed.
To the start signal the output OUT1 remains disabled for the time
“t1".
4.3 - OUT1 OPERATING MODE
When the time “t1” is expire the output will be on for the time “t2”.
The instrument can be programmed by the parameter "F1" to The cycle will be enabled again after the transmission of a RESET
signal and a subsequent START signal.
operate in any of the following 5 modes:
F1 = 1 - DELAYED :
On receiving the START signal, the instrument starts counting time.
When the set time value “t1” has been reached, the instrument
enables the output OUT1.
The output is disabled by the RESET signal.
TECNOLOGIC spa - TT 73 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06083 - PAG. 3
4.4 - OUT2 OPERATING MODE
The instrument can be programmed by the parameter "F2" to
operate in any of the following 4 modes:
F2 = 1 - Output OUT2 operating like OUT1
The output OUT2 exactly operates like the output OUT1 so that to
be able to have two output contacts.
F2 = 2 - Output OUT2 operating as instant contact
The output OUT2 is activated during the counting phase and
remains activated to the reset command.
F2 = 4 - Same function of OUT1 (time t1) with time t3 relative to t1
(in advance) : The choice of this mode of operation enable the set
"t3" that it has the same range time "S1" and cannot be higher of
"t1."
Received the start signal the instrument begins the counting and
exactly operating on the output OUT 2 in the same way with which it
operates the function F1 on the output OUT1.
If F1 = 1, 4 or 5 the output OUT 2 operate with the function of delay
with the time [”t1” - "t3"] while if F1 = 2 or 3 the output OUT 2
F2 = 3 - Same function of OUT1 (time t1) with time t3 absolute:
The choice of this mode of operation enable the set "t3" that it has operate with the feedthrough function always with the time [”t1” "t3"].
the same range time "S1" and cannot be higher of "t1."
Received the start signal the instrument begins the counting and In the programming mode of the time "t3" the display shows "t3 d"
exactly operating on the output OUT 2 in the same way with which it to indicate that the time t3 is dependent.
operates the function F1 on the output OUT1.
If F1 = 1, 4 or 5 the output OUT 2 operate with the function of delay
with the time "t3" while if F1 = 2 or 3 the output OUT 2 operate with
the feedthrough function always with the time "t3."
In the programming mode of the time "t3" the display shows "t3 i" to
indicate that the time t3 is independent.
If “F2” = 0 the output OUT 2 is always disabled.
TECNOLOGIC spa - TT 73 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06083 - PAG. 4
4.5 - CNT EN INPUT OPERATING MODE
The start signal can be given by the frontal key U programmed as
START/STOP function (“t”=1 or 2), which normally has bistable
functioning, or by the CNT EN input count enable.
As regards the CNT EN input, which enables time counting, the
instrument can be programmed to operate in any of the following 4
modes:
E = 1 - BISTABLE START/STOP:
After resetting the timer using the RESET input, close the CNT EN
contact to start the timer. Now release the contact.
When the contact is closed again, the timer stops on the current
counting value.
The timer starts again following another impulse to the CNT EN
input port.
This procedure goes on until a RESET signal is transmitted or the
set time period has expired.
E = 4 - MONOSTABLE RESET-START/STOP:
By closing the CNT EN input and keeping it closed, the timer is
resetted and starts the counting, at the opening of the CNT EN input
the counting is stopped.
This operating mode is recommended when the user wants to
control the timer using voltage signals. In fact, with an appropriate
interface (eg. an external relay) the timer is reset and starts counting
when voltage is supplied, and stops when voltage is cut off (just like
a conventional timer).
In this functioning mode the U frontal key works only as reset.
5 - PROGRAMMABLE PARAMETERS
5.1 - PARAMETERS TABLE
E = 2 - BISTABLE RESET-START/STOP:
This operating mode is very similar to that of the front START/STOP
key and dipends also from "t" parameter which has 2 possible
functioning modes:
E = 2 , t = 1 - RESET-START/STOP:
The first impulse on CNT EN input reset and start the timer, at the
second impulse, if it is given before the end of the time, the timer
stops (if the output was actived now will be disabled), otherwise, if it
is given after the end of the time, the second pulse actives a new
counting cycle.
E = 2, t = 2 - RESET/START/STOP:
At the first pulse on CNT EN input the timer is resetted, at the
second the counting starts, at the third pulse the counting is
stopping, and so on.
E = 3 - MONOSTABLE START/STOP:
After being reset by means of the RESET input, the timer starts
when the CNT EN contact is closed and stops when the contact is
opened.
At this point, if the contact is closed again, the timer will re-start from
the current value, and so on until a RESET signal is transmitted or
the set time period has expired.
In this functioning mode the U frontal key works only as reset.
1
Par.
F1
2
F2
3
4
5
6
7
8
9
S1
S2
H1
H2
C
b
E
10
t
Description
OUT
1
operating
mode
OUT
2
0perating
mode
Time Range “t1”
Time Range “t2”
Maximum set time “t1”
Maximum set time “t2”
Counting mode
Back-up mode
CNT
EN
input
operating mode
U key operating mode
Range
1-2-3-4-5
Def.
1
0-1-2-3-4
0
1-2-3-4
1-2-3-4
00_ _ ... 99_ _
00_ _ ... 99_ _
1-2
1-2-3
1-2-3-4
1
1
99_ _
99_ _
1
1
1
0-1-2-3
1
Notes
5.2 – PARAMETERS DESCRIPTION
F 1 - OUT 1 OPERATING MODE: Permits the user to select the
operating mode of the output OUT 1 as regards counting.
The 5 mode are:
1 = Delayed
2 = Feedthrough
3 = Asymmetrical Oscillator Start Off
4 = Asymmetrical Oscillator Start On
5 = One cycle Asymmetrical Oscillator Start Off
F 2 - OUT 2 OPERATING MODE: Permits the user to select the
operating mode of the output OUT 2 as regards counting.
The 5 mode are:
0 = Ouput disable
1 = Operating like OUT1
2 = On during counting
3 = Same function of OUT1 with time t3 absolute
4 = Same function of OUT1 with time t3 dependent from time t1
S1 - TIME RANGE t1 (and t3) : This parameter allows the user to
select the full range of the time t1 (and t3 if activate) according to
the following options:
1 = hrs (9999)
2 = hrs - min. (99 hrs 59 min.)
3 = min. - sec. (99 min. 59 sec. )
4 = sec. - cents (99 sec. 99 cents).
S2 -TIME RANGE t2: This parameter only involves the operating
modes "F1"= 3 and 4, and is used to select the full range of the t2
time period. The options are the same as for the "S1" parameter.
H1 - HIGH SET POINT TIME t1 : This parameter allows the user to
program the 2 most significative figures of the Higher value
programmable as Set Point “t1”
H2 - HIGH SET POINT TIME t2: Similar to “H1” but referred to the
set “t2”.
TECNOLOGIC spa - TT 73 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06083 - PAG. 5
C - COUNTING MODE. Permits the user to choose the UP or
DOWN mode, ie. whether the display must show the time which has
passed or the remaining time. The options are:
1 = UP mode
2 = DOWN mode
b - BACK-UP MODE. This parameter determines the instrument
reaction in the case of power failure. The options are:
1 = Timer stops and memorized the counting current value
2 = Timer goes on counting (only with internal battery present and
enabled)
3 = Timer reset the counting
When option 1 has been chosed, the instrument goes off and the
counting current value is saved. When the power supply is restored,
the timer can will start working from the saved value.
When option 2 has been chosed, in the case of power failure the
display and the output will go off, but the timer will continue to count.
Note that the mode 2 is enabled only if the internal battery is present
and activated by the connection of relative terminal blocks (see
electrical connections).
Under these conditions of operation the display results turned on but
with an inferior brightness to the normal mode
We recommends to disable the battery when it is not necessary.
In case 3 finally, at the missing of power supply, the instrument
stops the counting and does not memorize the reached value, so
that at the returning of power supply the instrument will be in the
reset conditions.
E - CNT EN INPUT OPERATING MODE. Allows the user to select
the operating mode of the Count Enable (CNT EN) external input.
The options are:
1 = Bistable Start/Stop
2 = Bistable Reset-Start/Stop
3 = Monostable Start/Stop
4 = Monostable Reset-Start/Stop
t - U KEY OPERATING MODE: This parameter permits to decide
the operating mode of the frontal U key and the possibilities are:
0 = Key disable
1 = RESET-START/STOP
2 = RESET/START/STOP
3 = RESETonly
Battery for counting without supply: Optional, 3,6 V internal
rechargeable battery.
Voltage inputs absorption: 1 mA Max.
Installation category: II
Protection class against electric shock: Class II for Front panel
Insulation: Reinforced insulation between the low voltage section
(supply and relay outputs) and the front panel; Reinforced insulation
between the low voltage section (supply and relay outputs) and the
extra low voltage section (inputs,
SSR outputs); Reinforced
insulation between the extra low voltage section (SSR outputs) and
voltage inputs.
7.2 – MECHANICAL DATA
Housing: Self-extinguishing plastic, UL 94 V0
Dimensions: 72 x 72 mm DIN, depth 96 mm
Weight: 270 g approx.
Mounting: Flush in panel in 66,5 x 66,5 mm hole
Connections: extractable 2,5 mm 2 screw terminal block
Degree of front panel protection : IP 54 mounted in panel with
gasket
Pollution situation: 2
Operating temperature: 0 ... 50 °C
Operating humidity: 30 ... 95 RH% without condensation
Storage temperature: -10 ... +60 °C
7.3 – MECHANICAL DIMENSIONS, PANEL CUT OUT AND
FIXING DEVICE [mm]
6 - PROBLEMS, MAINTENANCE AND WARRANTY
6.1 – CLEANING
It’s raccomanded to clean the instrument only with a cloth welted
with water or with a detergent neither abrasive nor containing
solvents.
6.2 – WARRANTY AND REPAIRS
The instrument is under warranty against construction vices or
defected material, noticed within 12 months from delivery date. The
warranty is limited to the repairs or to the substitution of the
instrument. The eventual opening of the housing, the violation of
the instrument or the wrong use and installation of the product
means the automatic decay of the warranty.
In case of defected instrument, noticed in warranty period or out of
warranty, do contact our sales department to obtain the shipment
authorisation.
The defected product must be shipped to TECNOLOGIC with the
detailed description of the failures found and without any fees or
charge for Tecnologic, safe different agreements.
7 - TECHNICAL DATA
7.1 – ELECTRICAL DATA
Power supply: 12 VDC/VAC, 24, 115, 230 VAC +/- 10%
Frequency AC: 50/60 Hz
Power consumption: 2 VA approx.
Input/s: 2 digital inputs for Count Enable (CNT EN) and Reset (RES)
for voltage-free contacts or voltage signals (the same voltage supply
value).
Output/s: Up to 2 outputs. Relay SPDT (8 A-AC1, 3 A-AC3 / 250
VAC); or in tension to drive SSR (12VDC/15 mA).
Electrical life for relay outputs: 100000 operat.
TECNOLOGIC spa - TT 73 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06083 - PAG. 6
7.4 – FUNCTIONAL DATA
Outputs operating mode: 5 modes for OUT 1: Delayed,
Feedthrough, asymmetric times oscillator with start on or start off
and One cycle Asymmetrical Oscillator Start Off .
4 modes for OUT 2: like OUT1, ON during count, like OUT1 with
time t3 absolute or relative in advance.
Measurement range: 4 times scales: 9999 hrs., 99 hrs. 59 min., 59
min. 59 sec., 99 sec. 99 cents.
Display resolution: according to the scale used: hrs., min., sec.,
cents
Overall accuracy: +/- 0,1 % fs
Counting autonomy in case of power failure: 10 hrs. approx. with full
charge battery
Inputs delay: 15 m sec. Max.
Display: 4 Digit Red h 14 mm
Compliance: ECC directive EMC 2004/108/CE (EN 61326), ECC
directive LV 2006/95/CE (EN 61010-1)
7.5 – INSTRUMENT CODE
TT 73 a b c d e ff
a : POWER SUPPLY
F = 12 VAC/VDC
Y = 24 VDC
A = 24 VAC
C = 115 VAC
D = 230 VAC
b : INPUTS
C = Free voltage contacts
V = Voltage signals (the same voltage supply value).
c : OUTPUT OUT1
R = Relay
O = 12 VDC for SSR
d : USCITA OUT2
R = Relay
O = 12 VDC for SSR
- = None
e : INTERNAL BATTERY
- = Battery not present
B = Battery present
ff = SPECIAL CODES
TECNOLOGIC spa - TT 73 - OPERATING INSTRUCTIONS - Vr. 01 - ISTR 06083 - PAG. 7