MXT
INSTRUCTION MANUAL
THERMOCOUPLE TRANSMITTER
(front configurable)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below.
If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket + CJC sensor) .... (1)
MODEL
MXT
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air, install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
■ MODEL NO.
Confirm that the model number described on the product is exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
■ WIRING
• Do not install cables (power supply, input and output) close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• This equipment is suitable for Pollution Degree 2 and Installation Category II. Basic insulation (signal input to output: 300V) is maintained. Prior to installation, check that the insulation class of this unit satisfies the system requirements.
• Altitude up to 2000 meters
• The equipment must be mounted inside a panel.
• Insert a noise filter for the power source connected to the unit. TDK-Lambda Noise Filter Model MZS-1206-33 or equivalent is recommended.
• The actual installation environments such as panel configurations, connected devices and connected wires may affect the protection level of this unit when it is integrated in a panel system. The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure CE conformity.
COMPONENT IDENTIFICATION
Connection Diagram Base Socket
Specifications
Body CJC
Sensor
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and confirm its operational range as indicated below:
Rating 100 – 240V AC: 85 – 264V, 47 – 66 Hz, approx. 6VA
Rating 24V DC: 24V ±10%, approx. 3.5W
Rating 110V DC: 85 – 150V, approx. 3.5W
INSTALLATION
Detach the yellow clamps located at the top and bottom of the unit to separate the body from the base socket.
■ UNPLUGGING THE UNIT
• Before you remove the unit from its base socket or mount it, turn off the power supply and input signal for safety.
■ DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bottom. Position the upper hook at the rear side of base socket on the DIN rail and push in the lower. When removing the socket, push down the
DIN rail adaptor utilizing a minus screwdriver and pull.
Clamp
(top & bottom)
DIN Rail
35mm wide
■ WALL MOUNTING
Refer to “EXTERNAL DI-
MENSIONS.”
Spring Loaded
DIN Rail Adaptor
Shape and size of the base socket are slightly different with various socket types.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1712 Rev.3
P. 1 / 4
MXT
FRONT VIEW & PROGRAMMING
■ PROGRAMMING PROCEDURE
1) Press ITEM UP or DOWN key until ITEM display indicates “01”.
2) Press DATA UP or DOWN key and choose “2” on DATA display.
1 : Data indication only.
2 : All parameters are modifiable.
3) Press ITEM UP or DOWN key until ITEM display shows the
ITEM No. you need to change.
4) Press DATA UP or DOWN key and choose a DATA No. or value you need on DATA display.
5) Repeat above 3 and 4. (Entered data is stored 1 sec. after the operation has been complete.)
6) Press ITEM UP or DOWN key until ITEM display indicates “01”.
7) Press DATA UP or DOWN key and choose “1” on the display.
8) Press ITEM UP or DOWN key until ITEM display indicates “P”.
DATA display shows process input. You can now check data setting by choosing ITEM No.
Note : DO NOT press UP and DOWN keys simultaneously.
Polarity LED
Status LED
DATA
PL1
PL2
ITEM
PL3
PL4
ITEM
DATA
DATA Display
ITEM No. Display
DATA UP-DOWN Keys
ITEM No. UP-DOWN Keys
09
10
11
12
ITEM
P
01
N/A
DATA
-9999 – 9999
1, 2, 3
CONTENTS
Input display in engineering unit *
Modification code
1
DEFAULT
---
1 : Data indication only.
2 : All parameters are modifiable.
3 : Only ITEM 19 is modifiable.
1
02
03
N/A
2
0 – 99
0 – 12
Status indication (“0” is normally indicated.)
Thermocouple type
0: (PR), 1: K (CA), 2: E (CRC), 3: J (IC), 4: T (CC), 5: B (RH)
6: R, 7: S, 8: C (WRe 5-26), 9: N, 10: U, 11: L, 12: P (Platinel II)
---
1: K (CA)
04 N/A
05 N/A
06/L
07
08
2
2
2
2
2
2
2
0, 1, 2 Output range code 0 : V1 (-1 – +1V)
1 : V2 (-10 – +10V)
2 : Z1 (0 – 20mA)
-15.0 – 115.0 Input indicated in % (of the range set in ITEM 13/14)
0, 1, 2 Temperature unit 0: °C 1: °F 2: K
0, 1, 2, 3, 4 Moving average (sampling cycle: 10 msec.)
0: No 1: 4 samples 2: 8 samples 3: 16 samples 4: 32 samples
0, 1 – 60
0, 1
Power-saving mode
Burnout protection
0 : Continuous display
1 – 60 : Time before display turned off (minutes)
0 : Downscale
1 : Upscale
V1 : 0
V2 : 1
Z1 : 2
---
-15.0 – 115.0 Output indicated in % with ITEM 01 DATA 1 (of the range set in ITEM 15/16) ---
Loop test output with ITEM 01 DATA 2 (‘L’ is indicated as ITEM No.)
(Use DATA UP/DOWN key to set the output signal.)
-99.99 – 99.99 Zero adjustment (%) (fine adj. of the value set in ITEM 15)
0.000 – 9.999 Gain adjustment (fine adj. of the value set in ITEM 16)
0.00
1.000
0
0
10
1
13
14
15
16
15
16
15
16
17
18 3
19 N/A
2
2
2
2
2
2
2
2
2
-270.0 – 2410 Lower range temperature (ITEM 13 < ITEM 14) * 1 0.0
-270.0 – 2410 Upper range temperature (ITEM 13 < ITEM 14) * 1 100.0
-1.00 – 1.00 Output code V1 0% output voltage (V) * 2 -1.00
-1.00 – 1.00 100% output voltage (V) * 2 1.00
-10.0 – 10.0 Output code V2 0% output voltage (V) * 2 -10.0
-10.0 – 10.0 100% output voltage (V) * 2 10.0
0.0 – 20.0
0.0 – 20.0
0, 1
Output code Z1 0% output current (mA) *
100% output current (mA) *
Output characteristic
2
2
0: Positive 1: Negative (inverted output)
4.0
20.0
0
0, 1
---
Reset all settings * 4
ROM version
0
---
*1 : According to the temperature unit specified in ITEM 09. For under -1000 or over 1000 values, under decimal point position cannot be displayed and setting is unavailable.
*2 : ITEM 15 < ITEM 16.
*3 : Press DATA UP key and choose DATA 1. Double-click DATA DOWN key. The display shows DATA 0 after the initialization is complete.
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1712 Rev.3
P. 2 / 4
Programming can be done in the Program Mode. Return the unit back to Monitor Mode other than for programming. Turning the power supply off in the Program Mode may not save modified settings.
■ SELECTING THERMOCOUPLE TYPE
[E.G.] J thermocouple
1) Program Mode
Set ITEM 01 – DATA 2 to turn the unit into Program
Mode.
2) Thermocouple Type
Choose ITEM 03 – DATA 3.
3) Monitor Mode
Set ITEM 01 – DATA 1 to turn the unit into Monitor
Mode.
■ SELECTING TEMPERATURE RANGE
[E.G.] -200 to 750°C
1) Turn the unit into Program Mode.
2) 0% Temperature Range
Choose ITEM 13 – DATA -200.
3) 100% Temperature Range
Choose ITEM 14 – DATA 750.
4) Turn the unit into Monitor Mode.
Note: Enter the temperature values in the unit specified with ITEM 09.
■ SELECTING OUTPUT RANGE
[E.G.] -10.0 to 0.0V DC
1) Turn the unit into Program Mode.
2) 0% Output Voltage
Choose ITEM 15 – DATA -10.0.
3) 100% Output Voltage
Choose ITEM 16 – DATA 0.0.
4) Turn the unit into Monitor Mode.
5) Set to ITEM P.
■ BURNOUT
[E.G.] Downscale burnout
1) Turn the unit into Program Mode.
2) Burnout Protection
Choose ITEM 12 – DATA 0.
3) Turn the unit into Monitor Mode.
■ RESET ALL SETTINGS
Returning the unit into the factory-default settings.
1) Turn the unit into Reset Mode.
Set ITEM 01 – DATA 3 to turn the unit into Reset
Mode.
2) Call up the Reset menu.
Choose ITEM 18 – DATA 1. (Press DATA UP key.)
3) Resetting Enable
Double-click DATA DOWN key. DATA 0 is displayed after the initialization is complete.
4) Turn the unit into Monitor Mode.
If necessary, go to Moving Average and other adjustments.
Set the unit to Monitor Mode other than for programming.
MXT
■ STATUS LED, PL2
When the PL2 is turned on, identify the device status with
ITEM 02.
REF. STATUS
12 Burnout: Wire breakdown or invalid overrange input.
Check T/C wires, T/C type and temperature range.
13 Input range setting: 0% Setting > 100% Setting
See ITEM 13 / 14.
15 Output range setting: 0% Setting > 100% Setting
See ITEM 15 / 16.
99 Memory error: Initialize all the settings of the unit by operating ITEM 18 and program the unit again.
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on top of the unit.
comp. leadwire
T/C
+
+
– metal leg
CJC
SENSOR
3
–
4
5 model: CJM
CHECKING
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3) Input: Check that the input voltage is within 0 – 100% of full-scale.
If the thermocouple or its extension wires are broken, the output goes over 100% (below 0% with downscale) due to the burnout function. Check leadwires in such a case.
4) Output: Check that the load resistance meets the described specifications.
MAINTENANCE
1 +
2 –
7 U(+)
8 V(–)
OUTPUT
POWER
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output signal for the respective input signal remains within accuracy described in the data sheet. When the output is out of tolerance, recalibrate the unit as explained earlier (ITEM
07 and 08).
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1712 Rev.3
P. 3 / 4
EXTERNAL DIMENSIONS
unit: mm (inch)
50 (1.97)
20 (.79)
CLAMP
(top & bottom)
DIN RAIL
35mm wide
7.8 (.31)
6 5 4 3
103 (4.06)
123 (4.84)
2–4.5 (.18) dia.
MTG HOLE
15 (.59) deep
8–M3.5
SCREW
7 8 1 2
40 (1.57)
50 (1.97) [3.3 (.13)]
• When mounting, no extra space is needed between units.
■ TERMINAL ASSIGNMENTS
CJC SENSOR
(model: CJM)
6
5 4
3
MXT
7 8 1 2
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: [email protected]
EM-1712 Rev.3
P. 4 / 4