12-2008:C

12-2008:C
Product data sheet
Sheet No.: 1.604.07 - Rev: C, Page 1 of 3
Date:
December, 2008
FieldQ
Integrated Base Control Module
QC14 Intrinsic Safe
Pilot valve specifications
The pilot valve inside the Control Module sends the actuator
to its open or closed position.
Typical functional ratings Pilot Valves
Voltage
Turn on
V
Turn off
V
Current
Peak
mA
Hold
mA
Resistance
Barrier+Cable
Ohm
Safety parameters Pilot Valves
Voltage
Ui
Maximum
Li
Power
Pi
Capacity maximum
Ci
Inductivity
Li
21.6 ... 28
5
10
1.9
1200
V
mA
W
nF
mH
30
200
0.9
0
0
Wiring diagram:
- Pilot valves
FieldQ Control Module
Unclassified or Non Hazardous or ClassiHazardous Location fied Location
Description:
The Intrinsic Safe FieldQ conventionally wired control modules offer an integrated concept for valve automation. Its
compact and robust construction incorporates basic control
and feedback functionality.
Construction:
The Control Module is mounted at the side of the Pneumatic
Module in front of the basic actuator housing. Inside, wiring
terminals are available for connecting control signal to the
pilot valve and feedback signals to the switches. Three cable
entries are available.
Features:
- Basic actuator functions for fail safe (spring return) or
double acting applications.
- Robust IP65/NEMA4X enclosure, protecting the IPT
system, the pilot valve’s coil, the feedback switches and
terminals, suitable for indoor and outdoor use.
- All the control and feedback connections can be wired to
the Control Module.
- IPT-technology.
- Easy to set feedback signals.
- Control module can be easily plugged in the pneumatic
module.
- ATEX and CSA Intrinsically Safe approvals.
General specifications:
Material housing
: Aluminium alloy
Electrical connections : Internal 9 pole terminal strip.
Cable entries
: 3x M20x1.5 or 3x 1/2”NPT
Operating media
: Air or inert gasses, filtered at 5μm
Switch point
: Factory set at 15° before each end of
travel (open and closed position).
- Adjustable range
: Between -3° to 15° and +75° to +93°
of the end position.
Enclosure
: IP65 / NEMA 4X
Finish
: Polyester non-TGIC based powder
coating.
Temperature
: -20°C ... +50°C (-4°F ... +122°F)
Dimensions
: See 1.603.01 metric
See 1.603.04 imperial/UNC
See 1.603.02 DIN 3337
1
2
COM NO
3
4
5
NC COM NO
6
NC
Switch specifications:
- See section “Feedback
switches”
Cable range : 0.2 - 2.5mm2 or 30-12AWG
TM
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
7
8
9
-
+
NC
IS Approved
Barrier
Product data sheet
Sheet No.: 1.604.07 - Rev: C, Page 2 of 3
Date:
December, 2008
FieldQ
Feedback switches QC14 Intrinsically Safe Control Module
The feedback switches inside the module senses the open or closed position and are prewired to the terminal strip. The following feedback switches are available:
Mechanical switches
Option code
Type
Contacts
Mechanical life
Temperature
M or G
Mechanical V4
NO and NC (G = Goldplated)
107 operations (depends on electrical load).
-20°C to +50°C (-4°F to +122°F)
Hermetically sealed switches
Option code
D
Type
Hermetically sealed V3
Contacts
Gold plated, NO and NC
Mechanical life
107 operations (depends on electrical load).
Temperature
-20°C to +50°C (-4°F to +122°F)
Hazardous area executions:
The Conventional Modules QC14 in combination with the mechanical gold plated and hermetically sealed switches, have
an ATEX and CSA Intrinsically Safe approval as listed below:
Wiring diagram:
- Mechanical switches
- Hermetically sealed switches
0344
II 1 G Ex ia IIC T4...T6,
II 1 D Ex tD A20 T80°C
Optional for D type switch:
II 1 G Ex ib d IIC T4...T6
: Certificate : TÜV 07 ATEX 553928X
Unclassified or Non Hazardous or
Hazardous Location Classified Location
ATEX
:
1
2
3
COM NO
IS barrier3
NC
4
5
6
COM NO
IS barrier3
NC
7
NC
8
9
-
+
IS barrier3
Pilot valve1
Open
Close
Switch Connections
Cable range : 0.2 - 2.5mm2 or 30-12AWG
1 See secton “Pilot valve specifications”
2 For Intrinsically Safe (Cl. I Div1 or Zone 1 or 21) hazardous area applications, see Installation Guide : DOC.IG.QC14.1
3 IS Approved barrier
4 Wiring diagram is shown in the actuators mid-stroke position.
: Intrinsically safe, Class I, II, III, Division 1,
Groups ABCDEFG T4...T6, Type 4X
: Ex ia IIC, T6, IP65
: DIP A20 TA 80°C
: Certificate : 1638508
Temperature range:
T4..T6 @ Ta = -20°C(-4°F) to +50°C (122°F)
QC14 Intrinsically Safe Entity Parameters Feedback switches
Circuit Terminal
Ui
Ii
Pi
Ci
Li
M-type, 1 - 2 - 3,
30Vdc 300mA
1.2W
0
0
D type
4-5-6
1 - 2 - 3,
30Vdc 100mA
1.2W
0
0
G-type
4-5-6
ATEX classified hazardous areas:
Base FieldQ actuators do not comply to all Zone 0 requirement. Please contact our sales for these Zone 0 appplications.
The combination of basic actuator and the above control
module QC14 is allowed to be used up to Zone 1 or 21.
TM
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.07 - Rev: C, Page 3 of 3
Date:
December, 2008
FieldQ
Feedback switches QC14 Intrinsically Safe Control Module
The feedback switches inside the module senses the open or closed position and are prewired to the terminal strip. The following feedback switches are available:
2-Wire NAMUR proximity switches
Option code
N
Type
2-wire inductive, normally closed
Voltage
8 VDC nominal
Ouput
Unswitched , > 3mA
Switched , < 1mA
Temperature
-20°C to T* (-4°F to +T*)
Compliant to
DIN EN 60947-5-6 (NAMUR)
QC14 Intrinsically Safe Entity Parameters Feedback switches
Circuit
Terminal
Ui
Ii
Pi
Ci
Li
Type 1
1 – 2, 4 - 5 16Vdc 25mA 34mW 100nF 100μH
Type 2
1 – 2, 4 - 5 16Vdc 25mA 64mW 100nF 100μH
Type 3
1 – 2, 4 - 5 16Vdc 52mA 169mW 100nF 100μH
Type 4
1 – 2, 4 - 5 16Vdc 76mA 242mW 100nF 100μH
* a cable length of 10 m is considered.
Hazardous area executions:
The Conventional Modules QC14 in combination with the NAMUR proximity switches, have an ATEX and CSA Intrinsically
Safe approval as listed below:
Wiring diagram:
2-Wire NAMUR proximity switches
Unclassified or
Non Hazardous Location
Hazardous or
Classified Location
ATEX
L+
1
L-
2
L+
3
4
:
:
0344
II 1 G Ex iaT*
II 1 G Ex tD A20 T80°C IP65
: Certificate : TÜV 07 ATEX 553928X
L-
5
6
7
8
9
: Intrinsically safe, Class I, II, III, Division 1,
Groups ABCDEFG T*, Type 4X
: Ex ia IIC, T*, IP65
: DIP A20 TA 80°C
: Certificate : 1638508
Temperature range:
T4...T6 @ Ta = -20°C(-4°F) to +50°C (122°F)
IS
barrier3
(+)
L
(-)
N
IS
barrier3
(+)
L
(-)
N
Open
Close
Switch Connections1
IS
barrier3
(-)
N
(+)
L
Pilot valve1
Cable range : 0.2 - 2.5mm2 or 30-12AWG
1 See secton “Pilot valve specifications”
2 For Intrinsically Safe (Cl. I Div1 or Zone 1 or 21) hazardous area applications, see Installation Guide : DOC.IG.QC14.1
3 IS Approved barrier
4 Wiring diagram is shown in the actuators mid-stroke position.
T* ambient at T class:
Connection
T6
Type 1
50°C / 122°F
Type 2
46°C / 114°F
Type 3
25°C / 77°F
Type 4
10°C / 50°F
T5
50°C / 122°F
50°C / 122°F
37°C / 98°F
22°C / 71°F
T4 – T1
50°C / 122°F
50°C / 122°F
50°C / 122°F
50°C / 122°F
ATEX classified hazardous areas:
Base FieldQ actuators do not comply to all Zone 0 requirement. Please contact our sales for these Zone 0 appplications.
The combination of basic actuator and the above control
module QC14 is allowed to be used up to Zone 1 or 21.
TM
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be
obtained from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 813 630 2255 (fax +1 630 9449) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 626 24 515 (fax +65 626 80 028)
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement