DL105 Error Code
Description
E003
SOFTWARE
TIME-OUT
If the program scan time exceeds the time allotted to the watchdog timer, this
error will occur. SP51 will be on and the error code will be stored in V7755. To
correct this problem use AUX 55 to extend the time allotted to the watchdog
timer.
E004
INVALID
INSTRUCTION
The CPU attempted to execute an instruction code, but the RAM contents
had a parity error. Performing a program download to the CPU in an
electrically noisy environment can corrupt a program’s contents. Clear the
CPU program memory, and download the program again.
E099
PROGRAM
MEMORY
EXCEEDED
If the compiled program length exceeds the amount of available CPU RAM
this error will occur. SP52 will be on and the error code will be stored in
V7755. Reduce the size of the application program.
E151
BAD COMMAND
A parity error has occurred in the application program. SP44 will be on and
the error code will be stored in V7755 .This problem may possibly be due to
electrical noise. Clear the memory and download the program again. Correct
any grounding problems. If the error returns replace the Micro PLC.
E155
RAM FAILURE
A checksum error has occurred in the system RAM. SP44 will be on and the
error code will be stored in V7755. This problem may possibly be due to a low
battery, electrical noise or a CPU RAM failure. Clear the memory and
download the program again. Correct any grounding problems. If the error
returns replace the CPU.
E210
POWER FAULT
A short duration power drop-out occurred on the main power line supplying
power to the base.
DL105 PLC User Manual, 3rd Edition
DL105 Error Codes
Description
A data error was encountered during communications with the CPU. Clear
the error and retry the request. If the error continues check the cabling
between the two devices, replace the handheld programmer, then if
necessary replace the CPU. The error code will be stored in V7756.
E313
HP COMM
ERROR 3
An address error was encountered during communications with the CPU.
Clear the error and retry the request. If the error continues check the cabling
between the two devices, replace the handheld programmer, then if
necessary replace the CPU. The error code will be stored in V7756.
E316
HP COMM
ERROR 6
A mode error was encountered during communications with the CPU. Clear
the error and retry the request. If the error continues replace the handheld
programmer, then if necessary replace the CPU. The error code will be stored
in V7756.
E320
HP COMM
TIME-OUT
The CPU did not respond to the handheld programmer communication
request. Check to insure cabling is correct and not defective. Power cycle the
system if the error continues replace the CPU first and then the handheld
programmer if necessary.
E321
COMM ERROR
A data error was encountered during communication with the CPU. Check to
insure cabling is correct and not defective. Power cycle the system and if the
error continues replace the CPU first and then the handheld programmer if
necessary.
E4**
NO PROGRAM
A syntax error exists in the application program. The most common is a
missing END statement. Run AUX21 to determine which one of the E4**
series of errors is being flagged. SP52 will be on and the error code will be
stored in V7755.
E401
MISSING END
STATEMENT
All application programs must terminate with an END statement. Enter the
END statement in appropriate location in your program. SP52 will be on and
the error code will be stored in V7755.
E402
MISSING LBL
A MOVMC or LDLBL instruction was used without the appropriate label.
Refer to the Chapter 5 for details on these instructions. SP52 will be on and
the error code will be stored in V7755.
E406
MISSING IRT
An interrupt routine in the program does not end with the IRT instruction.
SP52 will be on and the error code will be stored in V7755.
E421
DUPLICATE STAGE
REFERENCE
Two or more SG or ISG labels exist in the application program with the same
number. A unique number must be allowed for each Stage and Initial Stage.
SP52 will be on and the error code will be stored in V7755.
E422
DUPLICATE LBL
REFERENCE
Two or more LBL instructions exist in the application program with the same
number. A unique number must be allowed for each and label. SP52 will be
on and the error code will be stored in V7755.
E431
INVALID ISG/SG
ADDRESS
An ISG or SG instruction must not be placed after the end statement (such as
inside a subroutine). SP52 will be on and the error code will be stored in
V7755.
DL105 PLC User Manual, 3rd Edition
Appendix B
DL105 Error Codes
E312
HP COMM
ERROR 2
Appendix A
DL405 Error Codes
DL105 Error Code
B--3
B--4
DL105 Error Codes
Appendix B
DL105 Error Codes
DL105 Error Code
Description
E436
INVALID INT
ADDRESS
An INT must be programmed after the end statement, not in the main body of
the program. SP52 will be on and the error code will be stored in V7755.
E438
INVALID IRT
ADDRESS
An IRT must be programmed after the end statement, not in the main body of
the program. SP52 will be on and the error code will be stored in V7755.
E440
INVALID DATA
ADDRESS
Either the DLBL instruction has been programmed in the main program area
(not after the END statement), or the DLBL instruction is on a rung containing
input contact(s).
E441
ACON/NCON
An ACON or NCON must be programmed after the end statement, not in the
main body of the program. SP52 will be on and the error code will be stored
in V7755.
E451
BAD MLS/MLR
MLS instructions must be numbered in ascending order from top to bottom.
E452
X AS COIL
An X data type is being used as a coil output.
E453
MISSING T/C
A timer or counter contact is being used where the associated timer or
counter does not exist.
E454
BAD TMRA
One of the contacts is missing from a TMRA instruction.
E455
BAD CNT
One of the contacts is missing from a CNT or UDC instruction.
E456
BAD SR
One of the contacts is missing from the SR instruction.
E461
STACK OVERFLOW
More than nine levels of logic have been stored on the stack. Check the use
of OR STR and AND STR instructions.
E462
STACK
UNDERFLOW
An unmatched number of logic levels have been stored on the stack. Insure
the number of AND STR and OR STR instructions match the number of STR
instructions.
E463
LOGIC ERROR
A STR instruction was not used to begin a rung of ladder logic.
E464
MISSING CKT
A rung of ladder logic is not terminated properly.
E471
DUPLICATE COIL
REFERENCE
Two or more OUT instructions reference the same I/O point.
E472
DUPLICATE TMR
REFERENCE
Two or more TMR instructions reference the same number.
E473
DUPLICATE CNT
REFERENCE
Two or more CNT instructions reference the same number.
DL105 PLC User Manual, 3rd Edition
DL105 Error Codes
Description
An invalid keystroke or series of keystrokes was entered into the handheld
programmer.
E502
BAD ADDRESS
An invalid or out of range address was entered into the handheld
programmer.
E503
BAD COMMAND
An invalid command was entered in the handheld programmer.
E504
BAD REF/VAL
An invalid value or reference number was entered with an instruction.
E505
INVALID
INSTRUCTION
An invalid instruction was entered into the handheld programmer.
E506
INVALID
OPERATION
An invalid operation was attempted by the handheld programmer.
E520
BAD OP--RUN
An operation which is invalid in the RUN mode was attempted by the
handheld programmer.
E524
BAD OP--PGM
An operation which is invalid in the PROGRAM mode was attempted by the
handheld programmer.
E526
OFF LINE
The handheld programmer is in the OFFLINE mode. To change to the
ONLINE mode use the MODE the key.
E527
ON LINE
The handheld programmer is in the ON LINE mode. To change to the OFF
LINE mode use the MODE the key.
E528
CPU MODE
The operation attempted is not allowed during a Run Time Edit.
E540
CPU LOCKED
The CPU has been password locked. To unlock the CPU use AUX82 with the
password.
E541
WRONG
PASSWORD
The password used to unlock the CPU with AUX82 was incorrect.
E542
PASSWORD RESET
The CPU powered up with an invalid password and reset the password to
00000000. A password may be re-entered using AUX81.
DL105 PLC User Manual, 3rd Edition
Appendix B
DL105 Error Codes
E501
BAD ENTRY
Appendix A
DL405 Error Codes
DL105 Error Code
B--5
B--6
DL105 Error Codes
Appendix B
DL105 Error Codes
DL105 Error Code
Description
E601
MEMORY FULL
Attempted to enter an instruction which required more memory than is
available in the CPU.
E602
INSTRUCTION
MISSING
A search function was performed and the instruction was not found.
E604
REFERENCE
MISSING
A search function was performed and the reference was not found.
E620
OUT OF MEMORY
An attempt to transfer more data between the CPU and handheld
programmer than the receiving device can hold.
E621
EEPROM NOT
BLANK
An attempt to write to a non-blank EEPROM in the handheld programmer
was made. Erase the EEPROM and then retry the write.
E622
NO HPP EEPROM
A data transfer was attempted with no EEPROM (or possibly a faulty
EEPROM) installed in the handheld programmer.
E623
SYSTEM EEPROM
A function was requested with an EEPROM in the handheld programmer
which contains system information only.
E624
V-MEMORY ONLY
A function was requested with an EEPROM in the handheld programmer
which contains V-memory data only.
E625
PROGRAM ONLY
A function was requested with an EEPROM in the handheld programmer
which contains program data only.
E627
BAD WRITE
An attempt to write to a write-protected or faulty EEPROM in the handheld
programmer was made. Check the write protect jumper and replace the
EEPROM if necessary.
E628
EEPROM TYPE
ERROR
The wrong size EEPROM is being used in the handheld programmer. This
error occurs when the program size is larger than what the HPP can hold.
E640
COMPARE ERROR
A compare between the EEPROM handheld programmer and the CPU was
found to be in error.
E650
HPP SYSTEM
ERROR
A system error has occurred in the handheld programmer. Power cycle the
handheld programmer. If the error returns replace the handheld programmer.
E651
HPP ROM ERROR
A ROM error has occurred in the handheld programmer. Power cycle the
handheld programmer. If the error returns replace the handheld programmer.
E652
HPP RAM ERROR
A RAM error has occurred in the handheld programmer. Power cycle the
handheld programmer. If the error returns replace the handheld programmer.
DL105 PLC User Manual, 3rd Edition