DA3 D/A CONVERTER BEFORE USE .... MODEL
DA3
INSTRUCTION MANUAL
D/A CONVERTER
MODEL
(16-bit resolution)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System's Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket) ..................... (1)
■ MODEL NO.
Check that model No. described on specification label is
exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you
use this product, including installation, connection and basic
maintenance procedures.
POINTS OF CAUTION
■ CONFORMITY WITH EC DIRECTIVES
• This equipment is suitable for use in a Pollution Degree 2
environment and in Installation Category II, with the maximum operating voltage of 300V.
Basic insulation is maintained between the signal input and
output. Prior to installation, check that the insulation class
of this unit satisfies the system requirements.
• Altitude up to 2000 meters
• The equipment must be mounted inside a panel.
• Insert a noise filter for the power source connected to the
unit. Densei-Lambda Noise Filter Model MZS-1206-33 or
equivalent is recommended.
• The actual installation environments such as panel configurations, connected devices, connected wires, may affect
the protection level of this unit when it is integrated in a
panel system. The user may have to review the CE requirements in regard to the whole system and employ additional
protective measures to ensure the CE conformity.
■ POWER INPUT RATINGS
• Operational range & power consumption: Check the power
rating for the unit on the specification label.
Rating 100 – 240V AC: 85 – 264V, 47 – 66 Hz, approx. 10VA
Rating 12 – 24V DC: 10.8 – 26.4V, approx. 4W
Rating 110V DC: 85 – 150V, approx. 4W
• Power fuse: A power fuse of the rating as shown below is
incorporated for safety. However, DO NOT replace it by the
user.
AC rating and 110V DC: T 0.5A 250V
DC rating except 110V DC: T 1A 250V
■ UNPLUGGING THE UNIT
• Before you remove the unit from its base socket or mount it,
turn off the power supply and signal input for safety.
DA3
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air,
install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C (23
to 131°F) with relative humidity within 30 to 90% RH in order
to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output) close
to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind the unit's cables together with cables where
high noise levels are present. Do not install them in the same
duct.
■ AND ....
• The unit is designed to function as soon as power is
supplied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data sheet.
COMPONENT IDENTIFICATION
Connection
Diagram Label
Base Socket
Specification
Label
Body
INSTALLATION
Detach the yellow clamps located at the top and bottom of the
unit for separating the body from the base socket.
■ DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bottom. Position the upper hook
at the rear side of base socket
on the DIN rail and push in the
lower. When removing the
socket, push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■ WALL MOUNTING
Refer to the drawings in the
Shape and size of the base socket
“TERMINAL CONNECTION” are slightly different with various
section.
socket types.
P. 1 / 5
EM-1395 Rev.5
DA3
FRONT PANEL CONFIGURATION & PROGRAMMING
■ PROGRAMMING PROCEDURE
DATA Display
1) Press ITEM UP or DOWN key until ITEM display indicates “01”.
ITEM Display
2) Press DATA UP or DOWN key and choose “2” on DATA display.
1 : Data indication only.
PL1 (POL) LED
2 : All parameters are modifiable.
PL2 (LOAD) LED
3) Press ITEM UP or DOWN key until ITEM display shows the ITEM No.
ITEM
you need to change.
UP-DOWN Keys
4) Press DATA UP or DOWN key and choose a DATA No. or value you need
DATA
on DATA display.
UP-DOWN Keys
5) Repeat above 3 and 4. (Entered data is stored when you move to a new
ITEM.)
6) Press ITEM UP or DOWN key until ITEM display indicates “01”.
7) Press DATA UP or DOWN key and choose “1” on the display.
8) Press ITEM UP or DOWN key until ITEM display indicates “P”.
DATA display shows process input. You can now check data setting by choosing ITEM No.
Note : DO NOT press UP and DOWN keys simultaneously.
ITEM
P
MDF.
CODE
N/A
01
DATA
-9999 – 9999
(-FFFF – FFFF)
1, 2
02
N/A
0 – 99
03/L
2
-15.0 – 115.0
04
05
06
2
2
2
-99.99 – 99.99
-99.99 – 99.99
0, 1, 2, 3, 4
07
2
0, 1, 2, 3, 4
08
09
08
09
08
09
08
09
08
09
10
2
2
2
2
2
2
2
2
2
2
2
-9999 – 9999
-9999 – 9999
-7FFF – 7FFF
-7FFF – 7FFF
0000 – FFFF
0000 – FFFF
8000 – 7FFF
8000 – 7FFF
0000 – FFFF
0000 – FFFF
0, 1
11
2
0, 1, 2
12
2
0, 1
13
2
0, 1
14
2
0, 1, 2
15
2
0, 1
16
2
0.0 – 60.0
DATA
26-pin Connector
ITEM
(Pin Assignments)
ITEM
1
2
25
26
DATA
CONTENTS
Input display in engineering unit, BCD (as set in ITEM 08/09)
( ) for binary, offset binary, two's complement, reflected binary
Modification code
1 : Data indication only.
2 : All parameters are modifiable.
Status indication (“0” is normally indicated.)
0: Normal 1: Memory error 10: Out of input range -15 – 115%
Input indicated in % (of the range set in ITEM 17/18)
Loop test output with ITEM 01 DATA 2 (‘L’ is indicated as ITEM No.)
Zero adjustment (%) (fine adj. of the value set in ITEM 17)
Span adjustment (%) (fine adj. of the value set in ITEM 18)
Display code
0 : BCD with polarity (decimal)
1 : Binary with polarity
2 : Offset binary
3 : Two’s complement
4 : Reflected binary
Available number of bits
0: 16 bits
1: 14 bits
2: 12 bits
3: 10 bits
4: 8 bits
BCD
Display range scaling 0% *1
Display range scaling 100% *1
Binary
Display range scaling 0% *1
Display range scaling 100% *1
Offset binary
Display range scaling 0% *1
Display range scaling 100% *1
Two’s complement
Display range scaling 0% *1
Display range scaling 100% *1
Reflected binary
Display range scaling 0% *1
Display range scaling 100% *1
2
Data input logic*
0 : Positive
1 : Negative
ITEM 11 and 13 are independent from ITEM 10.
LOAD input
0 : LOAD at Low or shortcircuit*3
1 : LOAD at High or opencircuit*4
2 : Unavailable (not used)
POL input
0 : Unavailable (not used)
1 : Available (used)
POL input
0 : Negative at High or opencircuit*4
1 : Negative at Low or shortcircuit*3
Parity check
0: Disable
1: Enable Parity per each digit
2: Enable Parity for all digits
Odd or even parity
0 : Odd
1 : Even
Delay buffer (seconds, 0 – 90%)
When the Response Time model suffix code is specified to 1, the set value is
only effective at 5.0 or higher value.
P. 2 / 5
DEFAULT
––
1
0
––
0.00
0.00
0
0
-9999
9999
-7FFF
7FFF
0000
FFFF
8000
7FFF
0000
FFFF
1
0
1
1
0
0
0.0
EM-1395 Rev.5
DA3
ITEM
17
18
17
18
17
18
19
20
MDF.
CODE
2
2
2
2
2
2
2
2
DATA
-1.00 – 1.00
-1.00 – 1.00
-10.0 – 10.0
-10.0 – 10.0
0.0 – 20.0
0.0 – 20.0
0 – 99
0, 1 – 60
21
2
0 – 9999
22
3
0, 1
23
N/A
–
*1: ITEM 08 < ITEM 09.
*2: Open collector input logic
CONTENTS
0% output voltage (V) *5
100% output voltage (V) *5
Output code V2
0% output voltage (V) *5
100% output voltage (V) *5
Output code Z1
0% output current (mA) *5
100% output current (mA) *5
Power ON-delay time (seconds)
Power-saving mode
0 : Continuous display
1 – 60 : Time before display turned off (minutes)
Parity check error count
The count value is reset to 0 with double-clicking the DATA DOWN key.
Reset all settings *6
ROM version
DEFAULT
-1.00
1.00
-10.0
10.0
4.0
20.0
5
10
Output code V1
LOGIC ITEM 10
INPUT
DATA
TTL level, open collector sink type
(TTL level)
24V DC, open collector source type
0 : Positive logic
0
1
Short
Open
(LOW)
(HIGH)
Open
Short
0
0
–
1 : Negative logic
0
1
Open
Short
(HIGH)
(LOW)
Short
Open
*3: “Opencircuit” with 24V DC input
*4: “Shortcircuit” with 24V DC input
*5: Of the range set in ITEM 08/09. ITEM 17 < ITEM 18.
*6: Press DATA UP key and choose DATA 1. Double-click DATA DOWN key. The display shows DATA 0 after the initialization is
complete.
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram label on top of the unit.
■ DIMENSIONS mm (inch)
CLAMP
(top & bottom)
20
(.79)
7.8 (.31)
50 (1.97)
16
(.63)
55 (2.17) min.
6
5
4
3
7
8
1
2
80 (3.15)
80 (3.15)
35.4 (1.39)
DIN RAIL
35mm wide
2–4.5 (.18) dia.
MTG HOLE
15 (.59) deep
8–M3.5
SCREW
103 (4.06)
123 (4.84)
40 (1.57)
[3.3 (.13)]
50 (1.97)
•When mounting, no extra space is needed between units.
P. 3 / 5
EM-1395 Rev.5
DA3
■ CONNECTION DIAGRAM
CONNECTOR
INPUT
1 +
OUTPUT
2 –
7 U(+)
POWER
8 V(–)
■ Input Connection Examples
• Standard type
TTL level
PLC
Open collector, sink type
DA3
PLC
DA3
• Option /A
24V DC
PLC
DA3
24V
CONNECTOR
CONNECTOR
CONNECTOR
5V
INPUT CONNECTOR (26-pin)
■ BCD INPUT
■ BINARY, TWO'S COMPLEMENT INPUTS
PIN NO.
ASSIGNMENT
PIN NO.
ASSIGNMENT
17
COM (–)
1
1 × 100
2
2 × 100
18
COM (–)
3
4 × 100
19
No connection
20
POL
4
8 × 100
5
1 × 101
21
LOAD *1
6
2 × 101
22
LOAD *1
7
4 × 101
23
P0 * 2
8
8 × 101
24
P1
2
9
1 × 10
25
P2
2
10
2 × 10
26
P3
11
4 × 102
12
8 × 102
13
1 × 103
14
2 × 103
15
4 × 103
16
8 × 103
*1. Pin No. 21 and 22 are internally connected.
*2. P0 corresponds to n × 100, P1 to n × 101, P2 to n × 102, P3 to n
× 103. Only P0 corresponds when the parity for all digits are
valid.
Note: With the number of bits set to 14 (or 12, 10, 8) with
ITEM 07, Pin No. 1 – 14 (or 1 – 12, 1 – 10, 1 – 8) are valid.
PIN NO.
ASSIGNMENT
PIN NO.
ASSIGNMENT
17
COM (–)
1
B0
2
B1
18
COM (–)
3
B2
19
No connection
20
POL
4
B3
5
B4
21
LOAD *1
6
B5
22
LOAD *1
7
B6
23
P0 *2
8
B7
24
P1
8
9
B
25
P2
9
10
B
26
P3
11
B10
12
B11
13
B12
14
B13
15
B14
16
B15
*1. Pin No. 21 and 22 are internally connected.
*2. P 0 corresponds to B0 through B3, P1 to B4 through B7, P2 to
B8 through B11, P3 to B12 through B15. Only P0 corresponds
when the parity for all digits are valid.
Note: With the number of bits set to 14 (or 12, 10, 8) with
ITEM 07, Pin No. 1 – 14 (or 1 – 12, 1 – 10, 1 – 8) are valid.
TIMING CHART
• Example: TTL Level Input (factory setting)
10 ms min.
LOAD INPUT
1 ms min.
DATA INPUT
The unit reads data upon detecting a change of LOAD input status.
DO NOT change LOAD input setting when the data input logic is changed.
P. 4 / 5
EM-1395 Rev.5
DA3
INPUT-OUTPUT RELATION EXAMPLE
■ BCD, BINARY (WITH POLARITY)
POL
DIGITAL INPUT
DATA
POLARITY
MSB
OR
OR
LSB
–
–FS
POL
available
■ OFFSET BINARY
+ ANALOG OUTPUT
not available
DATA
MSB
OR
LSB
–
OR
–FS
■ TWO'S COMPLEMENT
0
+FS
+ ANALOG OUTPUT
DIGITAL INPUT
DATA
UNUSED
POL
+FS
DIGITAL INPUT
POLARITY
UNUSED
POL
0
MSB
LSB
OR
–
OR
–FS
0
+FS
+ ANALOG OUTPUT
CHECKING
LIGHTNING PROTECTION
1) Terminal wiring: Check that all cables are correctly
connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal 7
– 8 with a multimeter.
3) Input: Dry contact or open collector. Check the input
device meets the following requirements.
TTL level
Sensing: 5V DC @1mA
Threshold voltage of the input circuit: 1V DC
24V DC
Sensing: 24V DC @3.5mA
Threshold voltage of the input circuit: 3V DC
LOAD signal: ON time 1 millisec. min.
4) Output: Check that the load resistance meets the described specifications.
In order to protect the unit from lightning surges entering
through power supply cables, use of appropriate lightning
surge protectors are recommended. Please contact M-System.
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such
product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System's sole liability, and purchaser's exclusive remedies,
under this warranty are, at M-System's option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To
submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
P. 5 / 5
EM-1395 Rev.5