Original instructions
SIRe Competent Fan Heater
Electric
With quick guide
SIReFCX
SE .... 2
GB .... 19
DE .... 36
FR .... 53
ES .... 70
IT
NL .... 104
NO .... 121
PL .... 138
RU .... 155
.... 87
For wiring diagram, please see last pages
GB
SIRe Competent Fan Heater Electric
Quick guide/start up
Enter ID/ Operation without control unit
Check that all constituent parts are present
(see section Constituent parts).
The control system can control one or more
units in parallel (max 9). Each unit must get a
unique ID number (1-9) which is set in the ID
selector of the SIReB1/B2/B1EC. E.g. Unit 1:
ID=1, unit 2: ID:2
If the external control for some reason has
not been installed the unit can still be run
temporarily. The ID selector is then set to
mode 0 see the image below.
The function is half speed and half heating
output
When the ID number must be changed the
unit must be disconnected from power.
Advice about location
PC board Base SIReB1X and PC board HUB
SIReC1X are installed close to the unit.
Control unit SIReUA1 has an integrated
room temperature sensor and is installed so
that it is easily accessible to the user. Wiring
between the PC Board Base SIReB1X and
heating fan must be laid for 230V.
RJ12 (6p/6c) modular cables, which are
available in different lengths, are used to connect the PC board and the control unit. Longer cables are available as options. Maximum
cable lengths see section Options.
To prevent unauthorised people from accessing the Control unit it can instead be placed
in another area and an external room sensor,
SIReRTX (option), can be installed in the
premises to sense the correct temperature.
Note! Internal sensor SIReIT02 shall be
mounted in the fan exhaust in the fan heater
unit in intended holder.
3
4
5
6
3
4
5
6
7
2
7
1
8
1
8
0
9
0
9
2
Each unit should
have a unique ID on
its SIReB1/B2/B1EC
card.
To run the unit
temporarily without
external control select
mode 0.
Connect the system
In control board base SIReB1X the unit is
connected further with RJ12 (6p/6c) modular
cable if several units are to be connected in
parallel.
If an external room temperature sensor SIReRTX is used it is connected using modular
cable RJ11 (4p/4c) on HUB SIReC1X.
Control board Base SIReB1X in/at the unit
and control unit SIReUA1 are connected by
PC board HUB SIReC1X with RJ12 (6p/6c)
modular cables, after the other units are powered up.
Power supply for electric heat must be connected separately (check manual for the fan
heater unit).
Wiring diagrams
The wiring diagrams are in a separate section
at the end of this manual.
19
GB
SIRe Competent Fan Heater Electric
Start up
System supplied with power. At the first start
up, the start-up wizard is run and the basic
settings are made. Fan and heating steps
are tested through the test program. Then a
status window is displayed.
At the first start up alarm and error codes
can occur, these will usually be reset without
actions.
Start-up wizard
1
Start-up wizard
5
Set language
English
Start-up wizard
Function test
Start test
Skip test
Screen function test
2
Start-up wizard
Start-up wizard
Set temp. unit
Fan step 1-5
Heating step off-3
°C
°F
3
Start-up wizard
6
Set date
2011-05-28
Function test
Test completed
Restart test
YYYY-MM-DD
4
Start-up wizard
Set time
14:07
24h format
Checking system...
20
Start-up wizard
7
Start-up wizard
Start-up finished
Proceed
Restart wizard
SIRe Competent Fan Heater Electric
GB
Contents
Quick guide/start up
Advice about location Connect the system Wiring diagrams Enter ID/Operation without control unit
Start up
19
19
19
19
20
Constituent parts
SIReFCX 22
Option23
Operating modes
Operating modes
24
Control unit SIReUA1
Overview25
Statuswindow25
Main menu
Current settings
26
Temperature settings
26
Fan control
26
Summer/Winter26
System on/off
26
Installer menu
26
Installer menu
Installer status screen
Week program
Fan settings
Heating settings
Filter guard settings (not for electric)
External control (BMS)
General settings
Service menu
27
27
28
28
29
30
31
31
Alarm and error codes
Displaying alarm and error codes
Reset alarm
Power failure
Overheat protection
32
32
32
32
Wiring diagrams, see last pages
21
GB
SIRe Competent Fan Heater Electric
Constituent parts
SIReFCX
SIReUA1,
control unit
Competent and
Advanced
Wall unit
cover
SIReB1X, External
PC board Basic
SIReC1X,
PC board HUB Competent
SIReIT02, internal
temperature
sensor 2 m
SIReCC,
modular cable
Dimensions constituent parts
Type
Description
SIReUA1
SIReB1X
SIReIT02
SIReC1X
SIReCC603
SIReCC605
Control unit Competent and Advanced
External PC Board Base
Internal temperature sensor
PC Board HUB Competent
Modular cable RJ12 (6/6)
Modular cable RJ12 (6/6)
22
HxWxD
[mm]
120x70x35
L
[m]
1
202x139x50
3
5
GB
SIRe Competent Fan Heater Electric
Option
SIReRTX, external room SIReUR, kit
temperature sensor
for recessed
installation
SIReCJ4, joint
piece
SIReCJ6, joint
piece
SIReCC,
modular cable
Typ
RSK-nr
E-nr
Beskrivning
HxBxD
SIReRTX
SIReUR*
SIReCJ4
SIReCJ6
SIReCC603
SIReCC605
SIReCC610
SIReCC615
SIReCC403
SIReCC405
SIReCC410
SIReCC415
673 09 22
673 09 21
87 510 12
87 510 11
70x33x23
114x70x50
673 09 23
673 09 24
673 09 25
673 09 26
673 09 27
673 09 28
673 09 29
673 09 30
87 510 13
87 510 14
87 510 15
87 510 16
87 510 17
87 510 18
87 510 19
87 510 20
Extern rumstemperaturgivare
Kit för infällt montage
Skarvstycke för två st. RJ11 (4/4)
Skarvstycke för två st. RJ12 (6/6)
Modularkabel RJ12 (6/6)
Modularkabel RJ12 (6/6)
Modularkabel RJ12 (6/6)
Modularkabel RJ12 (6/6)
Modularkabel RJ11 (4/4)
Modularkabel RJ11 (4/4)
Modularkabel RJ11 (4/4)
Modularkabel RJ11 (4/4)
L
[m]
10
3
5
10
15
3
5
10
15
*) See separate manual.
Max. cable lenghts
• Modular cabel RJ12 (6p/6c) between SIReUA1 and SIReB1(X): max 50 m.
• Modular cable RJ12 (6p/6c) between SIReC1X and SIReB1(X): max 10 m
• Modular cabel RJ12 (6p/6c) between two SIReB1(X): max 50 m.
• Modular cabel RJ11 (4p/4c) to room sensor SIReRTX: max 20 m.
Total cable length permitted in the system is a maximum of 300 m.
23
GB
SIRe Competent Fan Heater Electric
Operating modes
Operating modes
Control is based on the three operating
modes:
•Thermostat / Manual fan
•Thermostat / Automatic fan
•Manual
Thermostat / Manual fan
The thermostat just controls the heating and
the fan runs continually. The fan speed is set
manually. The fan symbol is marked in the
status window, select desired speed with the
rotary dial and confirm. (High speed limit is
step 4 for SE06-15 and step 2 for SE20/30).
When the setpoint value is fallen below by
0.5 K the first heating step is engaged , if the
temperature falls further the next heating step
is engaged, etc. (SE06-15, 20 has 2 heating
steps, SE30 has 3 heating steps).
The difference between the set point value
and the room temperature that controls the
engagement of the Heating step is set under
Heating step diff., see Installer menu > Settings heating > Heating step diff.
Thermostat / Automatic fan
The thermostat controls both the heating and
the fan. The fan speed is set manually in the
status window. [Installer menu > Settings fan
> Fan mode.]
Manual
The fan speed and heating is set manually in
the status window. The heating can be set to
2 or 3 steps. Heating is blocked in summer
mode, see: Main Menu > Summer/Winter
24
GB
SIRe Competent Fan Heater Electric
Control unit SIReUA1
Overview
Statuswindow (Auto mode)
IN
19.0
°C
Statuswindow
Statuswindow (Manual mode)
IN
Back arrow
19.0°C
Forward arrow
Fan speed step
Rotary dial
Heating step
Menu
Week program
Day
Alarm Red led
Week program
Night
Run signal
Green led
AV
Explanations
Week program
Out of operation
Statuswindow
Statuswindow
The display shows the prevailing room
temperature, fan and heating step, door
status and day/night mode or Off when the
week program is used.
This also displays whether the control is
set to auto mode or manual mode.
For thermostat/manual control of the fan and
heating the relevant symbol is marked in the
status window with the forward arrow. Steps
can then be set, confirm with the forward
arrow. For description, see section Operating
modes. Press forward arrow to enter the main
menu.
Forward arrow
Confirm selection and proceed.
Rotary dial
Scroll between alternatives
Back arrow
Go back.
After three minutes the control unit goes
back to displaying the status window.
25
GB
SIRe Competent Fan Heater Electric
Main menu
Summer/Winter
Current settings
When summer mode is selected under Main
Menu > Summer/Winter, heating is blocked.
Displays set room temp, high speed limit and
week program status.
Main menu
Current settings
Current settings
Temperature settings
Fan control
Room temp. day
Room temp. night
High speed limit
Summer/Winter
Week program
20°C
18°C
Step 5
Winter
No program
Temperature settings
Set the desired room temperatures to apply
for day respectively night mode (room
temperature night is used for week program/
night reduction).
Main menu
Current settings
Temperature settings
Fan control
Main menu>Temperature
settings
Room temp. day
Room temp. night
Factory setting
Room temp. day: 20°C (5 – 35°C)
Room temp. night: 18°C (0 – 20°C)
Main menu
Main menu>Summer/Winter
Fan control
Summer/Winter
System on/off
Summer/Winter
Winter
•
Factory setting
Summer/Winter:
off)
Winter (Summer - heat
System on/off
Switch the whole unit off manually. In Off
the display goes out; as soon as a button is
pushed the display lights and shows System
on/off. To activate the unit again select On.
The unit’s safety functions are still active
when the system is switched off, which means
that the fan can continue to run for a moment
after mode Off has been selected.
Main menu
Main menu>System on/off
Summer/Winter
System on/off
Installer menu
System on/off
ON
•
Fan control
Installer menu
No function. This setting should be done
manually in the status menu.
The installer menu is at the bottom of the
main menu, this is password protected. See
Installer menu in this manual.
Main menu
Temperature settings
Fan control
Summer/Winter
26
Main menu
Main menu>Installer menu
Summer/Winter
System on/off
Enter password
Installer menu
0 0 0 0
(See manual)
GB
SIRe Competent Fan Heater Electric
Installer menu
To enter the Installer menu, code 1932 is
entered. Select the digits using the rotary dial
and confirm using the forward arrow.
To check which days a certain program is
active, select a week day by pressing the
forward arrow, the program is marked and
those days that the program is used will be
underlined, switch between the programs for
a particular day using the rotary wheel.
Check program
Main menu
Mon Tue Wed Thu Fri
Main menu>Installer menu
Summer/Winter
System on/off
Enter password
0 0 0 0
(See manual)
Installer menu
Installer status screen
Check the settings. The installer status screen
consists of three pages with settings, scroll
using the rotary dial.
>Installer menu
>Installer status screen
Installer status screen
Week program
Fan settings
Functionality mode
Program
Sat Sun
08:00 Day (1)
18:00 Night (2)
Comp.
FH42°C
To add program step, select New program
step. Confirm your selection with the forward
arrow. Select Day, Night or Off (if the unit
should not be in operation), set the time
for switch on and then for which days the
program applies, then go to End to finish.
>Installer menu>Week
program
Week program on/off
New program step
Check program
New program step 7/16
Mode
Day
00:00
Tue 10:45
FF
002 FF
FF
Mon Tue Wed Thu Fri
Tue 10:45
Sat Sun
Tue 10:45
Mon Tue Wed Thu Fri
End
Week program
A new program step does not replace a set
time for Day for example, but you can instead
select to change a program step.
To change a program step, select Change
program.
Make settings for week program.
>Installer menu
Installer status screen
Week program
Fan settings
>Installer menu>Week
program
A basic program is pre-entered in SIRe.
Mon-Fri Day from 08:00, Night from 18:00
Sat Day from 10:00, Night from 16:00
Sun Day from 11:00:00, Night from 14:00
Check program
Change program
Remove program
Change program
Mon Tue Wed Thu Fri
1. 08:00
2. 18:00
3. 10:00
4. 16:00
Day
Night
Day
Night
00:00
Sat Sun
Tue 10:45
Mon Tue Wed Thu Fri
Tue 10:45
Sat Sun
Tue 10:45
Mon Tue Wed Thu Fri
End
To check which program is set for a particular
day, select Check program and then switch
between the days using the rotary dial.
>Installer menu>Week
program
New program step
Check program
Change program
Check program
Mon Tue Wed Thu Fri
08:00 Day (1)
18:00 Night (2)
Sat Sun
Tue 10:45
Sat Sun
Sat Sun
Tue 10:45
The program steps that should not apply
are removed in Remove program. One or all
program steps can be removed in the menu.
To return to the factory set basic program,
select Reset all.
>Installer menu>Week
program
Check program
Change program
Remove program
Remove program
Remove single
Remove all
Reset all
27
GB
SIRe Competent Fan Heater Electric
Week program is activated by selecting On,
under Week program on/off. In On-mode,
a sun, moon or Off in the Status window
appears to indicate day, night respectively
Off-function.
>Installer menu>Week program
>Installer menu>Week program
Week program on/off
New program step
Check program
Week program on/off
Fan settings
Make settings for fan mode (see also
Operating modes section).
>Installer menu
Week program
Fan settings
Heating settings
>Installer menu>Fan settings
>Installer menu>Fan settings
Fan mode
Fan mode
Auto
>Installer menu>Fan settings
Fan mode
Thermostat
Manual fan
>Installer menu>Fan settings
Fan mode
Thermostat
Auto fan
>Installer menu>Fan settings
Fan mode
•
Manual
Factory setting
Fan mode: Thermostat / Manual fan
(Thermostat / Automatic fan, Manual)
28
Make settings for heating.
>Installer menu
Fan settings
Heating settings
Filter guard settings
OFF
•
•
Heating settings
Heating step diff.
The temperature difference between
connection of the electrical heating step.
Factory setting of 1.0 and a set point value of
20°C gives the following function: low output
step cuts in at +19.5°C (cuts out at +20.0°C).
If the temperature continues to fall below
+18.5°C another output step cuts in (cuts
out at +19.0°C). For 3 output steps the last
step is engaged at +17.5°C and switches off at
+19.0°C.
>Installer menu>Heating
settings
Heating step diff.
Sensor calibration
Control range limit
>Installer menu>Heating settings
Heating step diff.
•
1.0 K
Factory setting
Heating step diff.: 1.0 K (0 K – 10 K)
GB
SIRe Competent Fan Heater Electric
Heating step limit
Possibility of limiting the heating.
>Installer menu>Heating
settings
Heating step diff.
Heating step limit
Sensor calibration
>Installer menu>Heating
settings
>Installer menu
•
Heating settings
Filter guard settings
External control
2
Sensor calibration
If the sensor displays the wrong values these
can be calibrated. Some display errors may
occur, but this is primarily due to the location
(cold/hot surfaces etc). The value + or – adds
to or subtracts from the measured value
(for example +2K gives an increase of the
displayed value of 2 degrees).
>Installer menu>Heating
settings>Sensor calibration
Heating step diff.
Sensor calibration
Control range limit
Room temp. sensor
Outdoor temp. sensor
Room temp. sensor
0.0 K
Factory setting
Room temperature sensor: 0.0 K (-10 K – 10
K)
Control range limit
The maximum room temperature that a user
can select is limited to between 5 – 35°C.
Heating step diff.
Sensor calibration
Filter timer setting
Under Filter timer setting, set the desired run
time to between 50 and 9950 hours.
>Installer menu>Filter guard
settings
Filter timer on/off
Filter timer setting
Last filter change
>Installer menu>Filter guard
settings
Filter timer setting
•
1500 h
Factory setting
Filter timer setting: 1500 h (50 - 9950 h)
Filter timer on/off
Filter alarm is activated by selecting On,
under Filter timer on/off.
>Installer menu>Heating
settings>Sensor calibration
•
>Installer menu>Heating
settings
Filter alarm alarms when the set fixed run
time has been exceeded.
Heating step limit
Factory setting
Heating step limit: 2 (SE06-15, 20) 3 (SE30)
>Installer menu>Heating
settings
Filter guard settings (not for electric)
>Installer menu>Heating
settings
Control range limit
•
35°C
>Installer menu>Filter guard
settings
Filter timer on/off
Filter timer setting
Last filter change
Factory setting
Filter timer on/off: Off (On)
Last filter change
To check the number of run time hours since
the last filter replacement, select Last filter
change. The time is reset when the filter
alarm is reset. If the time is to be reset before
the alarm has gone, switch the filter timer on
and off.
Control range limit
Factory setting
Control range limit temperature: 35°C (5 –
35°C)
>Installer menu>Filter guard
settings
Filter timer on/off
Filter timer setting
>Installer menu>Filter guard
settings
Last filter change
0h
Last filter change
29
GB
SIRe Competent Fan Heater Electric
External control (BMS)
BMS functions can be activated under
External control.
Activate External on/off (5-30V AC/DC from
BMS) or 0-10V fan control by selecting On
under the respective one. See diagram on
next page and Connecting external control.
>Installer menu>External
control
External on/off
0-10V fan control
>Installer menu
Filter guard settings
External control
General settings
>Installer menu>External
control
External on/off
0-10V fan control
Current stage
Current
stage
7,1
5
6,0
4
4,9
3
3,9
2
2,8
1
7,6
6,5
5,5
4,3
3,2
0
1
2
3
4
5
6
7
8
9
10
11
[V]
Fan
Heat
0
1
2
3
0
1
2
2
0
1
2
2
4
3
2
5
4
2
Diagram: The fan- and heatingstep at incoming 0-10V DC voltage level, SE06-15.
Current stage
3,9
2
2,8
1
Current
stage
5,5
4,3
3,2
0
1
2
3
4
5
6
7
8
9
10
11
[V]
0
1
2
Fan
Heat
0
1
2
0
1
2
Diagram: The fan- and heatingstep at incoming 0-10V DC voltage level, SE20.
Current stage
4,9
3
3,9
2
2,8
1
Current
stage
6,5
5,5
4,3
3,2
0
1
2
3
4
5
6
7
8
9
10
11
[V]
0
1
2
3
Fan
Heat
0
1
2
2
0
1
2
3
Diagram: The fan- and heatingstep at incoming 0-10V DC voltage level, SE30.
30
SIRe Competent Fan Heater Electric
GB
General settings
Service menu
Possibility of making general settings that are
also in the Start-up wizard and execute user
reset.
The service menu is password protected and
is used for support in contact with Frico or
authorised installer.
>Installer menu
External control
General settings
Support menu
Change the date, time, language and
temperature unit.
>Installer menu>General
settings
Set date
Set time
Set language
Function test
To test the fan and heating steps, run the
function test.
>Installer menu>General
settings
Function test
Start test
Skip test
>Installer menu>General
settings
Fan step 1-5
Heating step off-1
>Installer menu>General
settings
Function test
Test completed
Restart test
User reset
User reset (Room temp. day resp. night, high
speed limit, speed closed door, door, Summer
/ Winter) to factory setting.
>Installer menu>General
settings
Function test
User reset
>Installer menu>User reset
Execute user reset?
No
Yes
31
GB
SIRe Competent Fan Heater Electric
Alarm and error codes
SIRe has different alarms and error codes for
safe and problem free operation.
If alarms or error codes have been indicated
these must be reset in order to return to
normal operation, for example activating the
heating again. Fan mode is active even when,
for example, the over heating alarm has been
indicated.
Displaying alarm and error codes
In event of alarm or error the alarm/error
code is shown in the status window. In event
of alarm/error code the unit it applies to is
displayed.
See Table - Alarms and Table – Error codes.
Reset alarm
Note! Before resetting, check that the fault is
rectified and there is nothing to prevent the
unit from being recommissioned!
When the fault is rectified, the alarm is
reset by pressing the forward arrow and selecting Reset alarm and then confirm. If several
units give an alarm at the same time, the fact
that there are several alarms is indicated, but
only one is shown in the display. By resetting
that alarm the next alarm can be read.
At the first start up alarm and error codes
can occur, these can usually be reset without
action.
Power failure
Note that in case of power failure the time
settings need to be checked, if the time is not
set correctly week program will be affected.
32
Overheat protection
SE06-15:
The over heating protection is intended to
restrict the exhaust temperature to 70 °C.
At 70 °C an output step is tripped off. If the
temperature continues to rise all output
is interrupted at 75 °C. If the temperature
continues to rise despite this, for example
because of a faulty contactor, the fan will
start to spin at 70 °C to keep the temperature
down. At the same time there is an over
heating alarm, see Table - Alarm. At internal
temperatures of +80 °C the fan runs at
maximum speed.
If the unit cools the output is engaged again.
The alarm remains in the control unit’s display. If the unit overheats twice within an
hour, the alarm must be reset before the heating can be engaged again, the fan operates
until the alarm is reset.
SE20-30:
The over heating protection is intended to
restrict the exhaust temperature to 85 °C.
At 85 °C an output step is tripped off. If the
temperature continues to rise all output
is interrupted at 90 °C. If the temperature
continues to rise despite this, for example
because of a faulty contactor, the fan will
start to spin at 85 °C to keep the temperature
down. At the same time there is an over
heating alarm, see Table - Alarm. At internal
temperatures of 95 °C the fan runs at
maximum speed.
If the unit cools the output is engaged again.
The alarm remains in the control unit’s display. If the unit overheats twice within an
hour, the alarm must be reset before the heating can be engaged again, the fan operates
until the alarm is reset.
Note! In event of repeated alarms and over
heating alarms, carry out a thorough check
and if the fault cause cannot be found contact
authorised service personnel or Frico.
SIRe Competent Fan Heater Electric
A1
Motor alarm
Thermal switch has deployed. One or
several motors have overheated. (Only
units with withdrawn thermal switches.)
A2
Over heating
alarm
The temperature in the unit has
exceeded the alarm limit for
overheating.
A4
Filter alarm
A5
Ext. alarm
Check that nothing is obstructing the
Fixed run time before the filter
alarm has been reached.
External alarm input on
SIReC1X has been activated.
GB
Check that nothing is obstructing the
unit’s air intake and exhaust. When
the overheated motor has cooled the
thermal switch shuts again and the
alarm can be reset. At repeated alarms,
check the motors, replace damaged
motors.
unit’s air intake and exhaust, the
function of the internal temperature
sensor.
Replace or clean the filter, adjust any
alarm time based on how dirty the
filter was and reset the alarm.
Check the external alarm.
33
GB
SIRe Competent Fan Heater Electric
Error code
Cause
E1
Communication
SIReB1X has no contact
with SIReC1X.
Check connection between
the boards. Replace any
modular cables.
E2
ID Error
Two or more SIReB1 X have
the same ID number.
Interrupt the current and select
different ID numbers for all
SIReB1X in the system.
E3
ID Error
One or several SIReB1X does
not have a program.
Contact Frico for support.
E4
Room sensor
error
Fault on or missing external room
sensor SIReRTX connected to
SIReB1X.
Always disconnect the
power when connecting or
disconnecting sensors. Check
connection of the sensor.
E8
Internal sensor
faults
Fault on or missing
internal sensor in the unit.
Check connection of the
sensor. If there is no sensor,
contact Frico for support.
E10
ID Error
E12 Room sensor error
E14
Outdoor sensor fault
E20 Communication
E21
Room sensor error
E23 Soft ware error
34
Action
Two or more SIReB1X in
the system have different
programs.
Contact Frico for support.
Error in or missing external
room sensor SIReRTX
connected to SIReC1X.
Always disconnect the
power when connecting or
disconnecting sensors. Check
connection of the sensor.
Fault on or missing outdoor
temperature sensor SIReOTX
connected to SIReC1X.
Always disconnect the power when
connecting or disconnecting sensors.
Check connection of the sensor.
Control unit SIReUA1 has no
contact with SIReC1X.
Check the connection. Replace
any modular cables.
Error in the internal room
sensor in the control unit
SIReUA1.
Check the connection between
SIReUA1 and SIReC1X. Replace any
modular cables. If the error is not
rectified SIReUA1 must be replaced.
Contact Frico for support.
GB
SIRe Competent Fan Heater Electric
Connecting external control - including BMS functions
SIReC1X
COM 1
External on/off 5-30V AC/DC
External signal activates the unit.
Set parameter: >> Installer menu >
External control > External On/Off=
On
19 20
Alarm outgoing (BMS) (potentialfree switch, max 3A, 230V)
Outgoing alarm indication.
Always active.
Closed = buzzer alarm
Open = no alarm
17 18
Door switch (obligatory) (External
potential-free switch)
SIReDC indicates door status.
Potential-free switch from door
automatic or BMS can also be used.
Closed = door open
Open = door closed
1516
+ -
1112
+ -
External speed control 0-10V DC
Controls the fan speed in steps (see
diagram section External control (BMS).
Set parameter: >> Installer menu >
External control > 0-10V Fan control =
On
9 10
External alarm IN (potential free
contact)
Input for external alarm. Closing gives
alarm.
7 8
External night reduction on/off
(potential-free switch)
Closes to activate the night reduction
function. Always active.
19 20
ALARM OUT (BMS)
ROOM
Door contact
15 161718
External ON/OFF
1112
+ -
Ext. speed ctrl. 0-10V DC IN
7 8 9 10
External alarm IN
COM 2
External night reduction
35
GB
SIRe Competent Fan Heater Electric
Connections between SIReB1X and Panther SE06, SE09,
SE12 and SE15.
L
L~ N
SIReB1X
SE06-15
SIRe Competent Fan Heater Electric
Connections between SIReB1X and Panther SE20
L
L~ N
SIReB1X
SE20
GB
GB
SIRe Competent Fan Heater Electric
Connections between SIReB1X and Panther SE30
L
L~ N
SIReB1X
SE30
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
EXTERNAL ON/OFF, 5-30V AC/DC
EXTERNAL RPM 0-10V DC IN
1112
+ -
ROOM
15 161718
19 20
SIReRTX
(optional)
SIReUA1
SIRe Competent Fan Heater Electric
7 8 9 10
EXTERNAL ALARM IN
(potential free contact)
~
230V~
N L L PE N L
ACTUATOR SUPPLY
COM 1
ROOM
X3
C1
X4
C2
Pot.
X5
Unit ID
SIReB1X
Wiring diagram - Competent
SIReC1X
COM 2
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
GB
C2
Pot.
X5
Unit ID
SIReB1X
C2
Pot.
X5
Unit ID
SIReB1X
SIReB1X
C1
X4
C1
X4
ROOM
X3
ROOM
X3
230V~
PE N L
230V~
15 161718
1112
+ -
ROOM
7 8 9 10
COM 2
EXTERNAL ALARM IN
(potential free contact)
EXTERNAL SETBACK TEMP.
ON/OFF (potential free contact)
PE N L
COM 1
SIReC1X
EXTERNAL RPM 0-10V DC IN
~
Pot.
Unit ID
EXTERNAL ON/OFF, 5-30V AC/DC
N L L
ACTUATOR SUPPLY
~
N L L
ACTUATOR SUPPLY
230V~
≠
Pot.
Unit ID
Wiring diagram - Competent- parallel connection
19 20
SIReRTX
SIReUA1
SIRe Competent Fan Heater Electric
ALARM OUT (BMS)
(potential free contact,
max 3A, 230V)
.
Tel: +46 31 336 86 00
[email protected]
www.frico.se
For latest updated information and information
about your local contact: www.frico.se
Art no: E4439, 2013-04-29 HH/SÅ/SÄ
Main office
Frico AB
Box 102
SE-433 22 Partille
Sweden