WIRING DIAGRAM 3 Phase 60 Hz. R6GP Series 6-10T 208-230/460 Volt

WIRING DIAGRAM 3 Phase 60 Hz. R6GP Series 6-10T 208-230/460 Volt
WIRING DIAGRAM
R6GP Series 6-10T
3 Phase 60 Hz.
208-230/460 Volt
NOTES:
1. Disconnect all power before servicing.
2. For supply connections use copper conductors only.
3. If any of the original wire as supplied with the furnace must be replaced,
it must be replaced with wiring material having a temperature rating of
at least 105C and 600V.
4. For supply wire ampacities and overcurrent protection, see unit
rating label.
5. On “C” Series Models only. For 208V operation remove wire from
230V tap and place on 208V tap.
6. This wire replaced by auto transformer when used.
1. Couper le courant avant de faire letretien.
2. Employez uniquement des conducteurs en cuivre.
24V Hot
LVT-R
Outdoor Fan Motor
Inducer Motor
WH BK
BLOWER
TIME
DELAY
R
See Alternate
OD fan wiring
Diagram B
Outdoor Fan Motor
OFC
IC-IND
K4-IC
IC-L1
Max
Temp.
Limit
R
Indoor Fan Motor
IBC
Auto Transformer
460V Units Only
See Note 6
T1
L3
T2
Upper
Scndry
Limit
1
24V Sec.
Primary
CCH2
T3
4 Amp
Circuit
Breaker
Aux. Switch
(N.C.)
K2
Aux.
CC1 Switch
(N.C.)
CCH1
T1
CC1
GND
L1
L2
L3
For supply connections use
copper conductors only.
LVT-Y1(Stage 1 Cool)
E-2
E-4
P2-4 W2
E-5
P2-3 W1
E-8
Y1
Factory
Jumper
Y2
Factory
Jumper
E-9
IBC
High
Limit
Input
Rollout Switch
Input
R
P1-8
P1-9
High
Pressure
Switchs
INDUCER MTR
CENTRIFUGAL
SWITCH
P1-6
OFC
HV
TRANSFORMER
P2-2
Low
Pressure
Switchs
FS
P2-1
2 Stage Equipment Only
- Indicates plug connection.
Letter Indicates which plug.
Number indicates pin location.
24V Common
Steady On
2 flashes
3 flashes
Unit
Terminal 4 flashes
Block
5 flashes
6 flashes
7 flashes
IBC
Aux. Switch
(N.O.)
S2
P1-3
COM
Status Light
(Red)
T2
CC1
Aux. Switch
(N.O.)
S1
P1-4
Compressor 1
T3
CC2
Aux. Switch
(N.O.)
P1-2 C GAS VALVE
3
See Note 5
CC2
LVT-G
C
E-1
P1-7
1
Flame
Rollout
Switch
Transformer
T2
LVT-W1(Heat)
LVT-Y2(Stage 2 Cool)
K1
L2
CC2
T1
L
NO
G
24 VAC
3
T3
Compressor 2
NC
R
UTEC
IGNITION
CONTROL
C
S
COM
C
S
LVT-W2(Heat)
Ignition Control Failure Code
Operation Normal
Pressure/centrifugal switch open with inducer on
Pressure/centrifugal switch closed with inducer off
Evap.
Freezestats
GND
FLAME
SENSOR
SPARK
IGNITOR
CC1
Lockout from too many failed ignition tries
Lockout from too many flame losses
High temperature switch open
Rollout switch open
8 flashes Flame present with gas off`
Field Supplied
9 flashes Exceeded max limit trips in one call for heat (5)
Disconnect
(3Phase Power Only) 10 flashes Gas Valve Fault
- Indicates screw connection.
CC2
LVT-C (24V COM.)
CCH - Crankcase Heaters, Stage 1&2 Compressor
CC1&2 - Contactor, Stage 1&2 Compressor
E - Economizer
LVT - Low Voltage Terminal
OFC - Contactor, Outdoor Fan
IBC - Contactor, Indoor Blower Motor
IC - Integrated Control
711153B
(Replaces 711153A)
06/11