Extech EX622 clamp meter User guide
Below you will find brief information for clamp meter EX622. This device is a 400 amp true rms ac clamp meter with an ir thermometer. It has a double molded case for heavy duty use and measures ac current, ac/dc voltage, resistance, capacitance, frequency, diode test, duty cycle, and continuity. Some of its special features include dual input thermocouple temperature, non-contact ir temperature, and a non-contact voltage detector.
Advertisement
Advertisement
User's Guide
400Amp True RMS AC Clamp Meter with IR Thermometer
Model EX622
Introduction
Congratulations on your purchase of this Extech EX622 True RMS Clamp Meter. This meter measures AC Current , AC/DC Voltage, Resistance, Capacitance, Frequency, Diode Test,
Duty Cycle and Continuity. Special features include Dual Input Thermocouple Temperature,
Non-Contact IR Temperature and Non-Contact Voltage detector. The double molded case is designed for heavy duty use. This meter is shipped fully tested and calibrated and, with proper use, will provide years of reliable service.
Safety
International Safety Symbols
This symbol, adjacent to another symbol or terminal, indicates the user must refer to the manual for further information.
This symbol, adjacent to a terminal, indicates that, under normal use, hazardous voltages may be present
Double insulation
WARNING
This WARNING symbol indicates a potentially hazardous situation, which if not avoided, could result in death or serious injury.
CAUTION
This CAUTION symbol indicates a potentially hazardous situation, which if not avoided, may result damage to the product.
PER IEC1010 OVERVOLTAGE INSTALLATION CATEGORY
OVERVOLTAGE CATEGORY I
Equipment of OVERVOLTAGE CATEGORY I is equipment for connection to circuits in which measures are taken to limit the transient overvoltages to an appropriate low level.
Note – Examples include protected electronic circuits.
OVERVOLTAGE CATEGORY II
Equipment of OVERVOLTAGE CATEGORY II is energy-consuming equipment to be supplied from the fixed installation.
Note – Examples include household, office, and laboratory appliances.
OVERVOLTAGE CATEGORY III
Equipment of OVERVOLTAGE CATEGORY III is equipment in fixed installations.
Note – Examples include switches in the fixed installation and some equipment for industrial use with permanent connection to the fixed installation.
OVERVOLTAGE CATEGORY IV
Equipment of OVERVOLTAGE CATEGORY IV is for use at the origin of the installation.
Note – Examples include electricity meters and primary over-current protection equipment
2 EX622-EU V2.3 04/10
SAFETY NOTES
• Do not exceed the maximum allowable input range of any function.
• Do not apply voltage to meter when resistance function is selected.
• Set the function switch OFF when the meter is not in use.
• Remove the battery if meter is to be stored for longer than 60 days.
WARNINGS
• Set function switch to the appropriate position before measuring.
• When measuring volts do not switch to current/resistance modes.
• Do not measure current on a circuit whose voltage exceeds 600V.
• When changing ranges always disconnect the test leads from the circuit under test.
CAUTIONS
• Improper use of this meter can cause damage, shock, injury or death. Read and understand this user manual before operating the meter.
• Always remove the test leads before replacing the battery or fuses.
• Inspect the condition of the test leads and the meter itself for any damage before operating the meter. Repair or replace any damage before use.
• Use great care when making measurements if the voltages are greater than 25VAC rms or 35VDC. These voltages are considered a shock hazard.
• Always discharge capacitors and remove power from the device under test before performing Diode, Resistance or Continuity tests.
• Voltage checks on electrical outlets can be difficult and misleading because of the uncertainty of connection to the recessed electrical contacts. Other means should be used to ensure that the terminals are not "live".
• If the equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
• This device is not a toy and must not reach children’s hands. It contains hazardous objects as well as small parts that the children could swallow. In case a child swallows any of them, please contact a physician immediately
• Do not leave batteries and packing material lying around unattended; they can be dangerous for children if they use them as toys
• In case the device is going to be unused for an extended period of time, remove the batteries to prevent them from training
• Expired or damaged batteries can cause cauterization on contact with the skin.
Always, therefore, use suitable hand gloves in such cases
• See that the batteries are not short-circuited. Do not throw batteries into the fire.
• Do not directly view or direct the laser pointer at an eye. Low power visible lasers do not normally present a hazard, but may present some potential for hazard if viewed directly for extended periods of time
A AC, 400A DC/AC
V DC, V AC 600V DC/AC
Resistance, Capacitance, Frequency, Diode Test 250V DC/AC
Type K Temperature 30V DC, 24V AC
3 EX622-EU V2.3 04/10
Description
Meter Description
3. IR thermometer and Laser Button
5. MODE / ZERO button
6. Backlit LCD Display
7. Type K input jacks
9. IR thermometer sensor and Laser pointer (rear)
14. Thermocouple display button
16. Non-Contact Voltage Detector
17. NCV LED indicator
Display icons Description
APO Auto Power Off
AUTO Autoranging
P Peak
DC Direct Current
ZERO mV or V
DCA or CAP zero
Milli-volts or Volts (Voltage) o
F and o
C Fahrenheit and Celsius units (Temperature)
T
1
, T
2
, T
1
-T
2
Therocouple 1, Thermocouple 2, Thermocouple difference n, m,
μ, M, k Unit of measure prefixes: nano, milli, micro, mega, and kilo
•
)
) test
Diode test
Laser pointer
4 EX622-EU V2.3 04/10
Operation
NOTES: Read and understand all Warning and Caution statements in this operation manual prior to using this meter. Set the function select switch to the OFF position when the meter is not in use.
Input Shutter
The Input Shutter inhibits simultaneous connection to the thermocouple jacks and the
DMM input jacks. This is a safety feature which prevents a potentially hazardous condition from existing during high voltage measurements. Slide the shutter up for test lead measurements or slide it down for thermocouple temperature measurements.
Non-Contact Voltage Detector
WARNING: Risk of Electrocution. Before use, always test the Voltage Detector on a known live circuit to verify proper operation.
1. Rotate the Function switch to any measurement position.
2. Place the detector probe tip on the conductor to be tested.
3. If AC voltage is present, the NCV detector light will turn on with a steady red light.
NOTE: The conductors in electrical cord sets are often twisted. For best results, move the probe tip along a length of the cord to assure placing the tip in close proximity to the live conductor.
NOTE: The detector is designed with high sensitivity. Static electricity or other sources of energy may randomly trip the sensor. This is normal operation.
5 EX622-EU V2.3 04/10
AC Current Measurements
WARNING: Disconnect the test leads before making clamp measurements.
1. Rotate the Function switch to the
400A
AC
position
2. Press the trigger to open jaw. Fully enclose only one conductor.
3. Read the current value in the display.
4. If the value is less than 40A, rotate the function switch to the 40A
AC
position to improve resolution.
AC/DC Voltage Measurements
CAUTION: Do not measure voltages if a motor on the circuit is being switched ON or
OFF. Large voltage surges may occur that can damage the meter.
1. Slide the input shutter to the up position.
2. Rotate the function switch to the V position.
4. Insert the black test lead banana plug into the negative COM jack.
Insert the red test lead banana plug into the positive V jack.
5. Touch the black test probe tip to the negative side of the circuit.
Touch the red test probe tip to the positive side of the circuit.
6. Read the voltage value in the display.
Frequency
When ACA is selected, the measured frequency can be viewed in the lower display.
6 EX622-EU V2.3 04/10
Resistance Measurements
Note: Remove power from the device under test before making resistance measurements
1. Slide the input shutter to the up position.
2. Set the function switch to the
Ω position.
3. Insert the black test lead banana plug into the negative COM jack.
Insert the red test lead banana plug into the positive V jack.
4. Touch the black test probe tip to one side of the device.
Touch the red test probe tip to the other side of the device.
5. Read the resistance value in the display.
Continuity Test
1. Connect as described for resistance measurements. the •
)
)
).
3. Touch the test probe tips across the circuit or component under test.
4. If the resistance is < 50
Ω, a tone will sound.
Diode Test
1. Connect as described for resistance measurements the .
3. Touch the test probe tips to the diode or semiconductor junction under test. Note the meter reading.
4. Reverse the test lead polarity by reversing the red and black leads. Note this reading.
5. The diode or junction can be evaluated as follows:
If one reading displays a value (typically 0.400V to 01.800V) and the other reading displays OL, the diode is good.
If both readings display OL the device is open.
If both readings are very small or ‘0’, the device is shorted.
7 EX622-EU V2.3 04/10
Capacitance Measurements
WARNING: To avoid electric shock, discharge the capacitor before measuring.
1. Slide the input shutter to the up position.
2. Rotate the function switch to the
capacitance position.
3. Insert the black test lead banana plug into the negative COM jack.
Insert the red test lead banana plug into the positive jack.
4. Touch the black test probe tip to one side of the device.
Touch the red test probe tip to the other side of the device.
5. Read the capacitance value in the display.
Note: For very large values of capacitance measurement time can be several seconds before the final reading stabilizes.
Note: The Zero feature removes stray test lead capacitance to improve the accuracy of low value capacitance measurements. To perform a zero, Press and hold the MODE ZERO button for two beeps. The display will zero. The offset value is now stored and is removed from all measurements.
.
Frequency and Duty Ratio Measurements
1. Slide the input shutter to the up position.
2. Rotate the function switch to the Hz % Position.
3. Insert the black test lead banana plug into the negative COM jack.
Insert the red test lead banana plug into the positive Hz jack.
4. Touch the black test probe tip to one side of the device.
Touch the red test probe tip to the other side of the device.
5. Read the Frequency value on the upper large display.
Read the Duty Ratio on the lower small display. display.
8 EX622-EU V2.3 04/10
μA DC/AC Current Measurements
1. Slide the input shutter to the up position.
2. Rotate the function switch to the
μA position.
4. Insert the black test lead banana plug into the negative COM jack.
Insert the red test lead banana plug into the positive
μA jack.
5. Turn power to the circuit under test off and make a break in the circuit.
6. Insert the meter in series with the circuit;
Touch the black test probe tip to the negative side of the break.
Touch the red test probe tip to the positive side of the break.
7. Turn circuit power on.
8. Read the current value in the display.
Type K Temperature Measurements
1. Slide the input shutter to the down position.
2. Rotate the function switch to the TYPE K
temperature position.
3. Press the MODE button to select °F or °C.
4. Insert the Temperature Probe(s) into the T1 and/or T2 type k sockets.
5. Place the temperature probe tip(s) where needed.
6. Read the temperature on the display.
Upper display a. T1 b. T2 c. T1-T2
Lower display
T2
T1
T1
T2
Note: In case of an open input or a temperature overrange, the meter will display “- - - -” .
9 EX622-EU V2.3 04/10
Non-Contact InfraRed Temperature Measurements
1. Rotate the function switch to the IR position.
2. Press the MODE button to select °F or °C.
3. Aim the infrared sensor (rear of the meter) at the surface to be measured. the button to turn on the IR thermometer and laser pointer. The laser pointer identifies the surface spot to be measured.
5. The area of the surface to be measured must be larger than the spot size as determined by the distance to spot size specification.
6. Read the temperature in the large upper display.
When the IRT button is released the displayed temperature will be held for approx. 10 seconds.
7. Read the MAX temperature in the lower display.
Press the MAX/MIN button to toggle the lower display between the maximum and minimum measured values.
WARNING: Do not directly view or direct the laser pointer at
an eye. Low power visible lasers do not normally present a hazard, but may present some potential for hazard if viewed directly for extended periods of time.
IR Spot to Distance Diagram
The 8:1 spot to distance ratio determines the size of the measured surface area with respect to the distance the meter is held away from the surface.
IR Measurement Notes
1. The object under test should be larger than the spot (target) size calculated by the field of view diagram.
2. If the surface of the object under test is covered with frost, oil, grime, etc., clean before taking measurements.
3. If an object's surface is highly reflective, apply masking tape or flat black paint to the surface before measuring.
4. The meter may not make accurate measurements through transparent surfaces such as glass.
5. Steam, dust, smoke, etc. can obscure measurements.
6. To find a hot spot, aim the meter outside the area of interest then scan across (in an up and down motion) until the hot spot is located.
10 EX622-EU V2.3 04/10
Data Hold
To freeze the LCD reading, press the HOLD button. While data hold is active, the HOLD icon appears on the LCD. Press the HOLD button again to return to normal operation.
MAX/MIN
"MAX" will appear. The meter will begins recording and displaying the maximum value measured. value measured during the recording session. present reading, but will continue to update and store the max and min readings.
4. To exit MAX/MIN mode press and hold the MAX/MIN button for 2 seconds.
Peak Hold
When ACA or ACV is selected, pressing the PEAK button enables the peak capture circuit.
The meter will now capture and display the maximum and minimum peaks of the waveform.
RANGE
In the Voltage, Resistance, Capacitance, Frequency or uA function the meter automatically selects the best range for the measurements being made. For measurement situations requiring that a range be manually selected, perform the following: point and units displayed until the preferred range is located.
3. To exit the Manual Ranging mode and return to Autoranging, press and hold the
RANGE key for 2 seconds.
LCD Backlight
The LCD is equipped with backlighting for easier viewing, especially in dimly lit areas.
Press and hold the HOLD/ button for 2 seconds to turn the backlight on. The backlight will automatically turn off after 30 seconds.
Automatic Power OFF with Disable
In order to conserve battery life, the meter will automatically turn off after approximately 30 minutes. To turn the meter on again, turn the function switch to the OFF position and then to the desired function position.
To disable APO:
1. From the OFF position, hold the MODE button and rotate the FUNCTION switch to a measurement function.
2. will appear in the display
3. Release the MODE button
4. APO is now disabled (APO icon is off) and will be reset when the Function switch is returned to the OFF position.
Low battery indication
When the icon appears in the display, the battery should be replaced. Refer to the battery replacement procedure in the maintenance section.
11 EX622-EU V2.3 04/10
Maintenance
WARNING: To avoid electrical shock, disconnect the meter from any circuit, remove the test leads from the input terminals, and turn OFF the meter before opening the case. Do not operate the meter with an open case.
Cleaning and Storage
Periodically wipe the case with a damp cloth and mild detergent; do not use abrasives or solvents. If the meter is not to be used for 60 days or more, remove the battery and store it separately.
Battery Replacement
1. Remove the Phillips head screw that secures the rear battery door
2. Open the battery compartment
3. Replace the 9V battery
4. Secure the battery compartment door
5.
You, as the end user, are legally bound (Battery ordinance) to return all used batteries and accumulators; disposal in the household garbage is prohibited!
You can hand over your used batteries / accumulators, gratuitously, at the collection points for our branches in your community or wherever batteries / accumulators are sold!
Disposal
Follow the valid legal stipulations in respect of the disposal of the device at the end of its lifecycle
Fuse Replacement
2. Remove the Phillips head screws (2) that secures the rear cover.
3. Replace the fuse with one of equal rating. (500mA, 660V fast blow [SIBA 70-180-40])
4. Replace the rear cover and battery
12 EX622-EU V2.3 04/10
Specifications
Function Range
AC Current
50/60 Hz
True RMS
AC/DC
μA
Current
400.0 AAC
Resolution
Accuracy
(% of reading + digits)
0.1A
±(1.5% + 5 digits)
40.00 AAC 0.01A
400.00
μA 0.01μA
4000.0
μA 0.1μA
DC: ±(1.0% + 2 digits)
AC: ±(1.5% + 2 digits)
AC Voltage
50/60 Hz
True RMS
400.0 mVAC
4.000 VAC
0.1mV
0.001V
±(1.0% + 20 digits)
40.00 VAC 0.01V
±(2.0% + 5 digits)
400.0 VAC
600 VAC
0.1V
1V
DC Voltage
400.00 mVDC 0.01mV
Resistance
Capacitance
Frequency
(clamp)
4.0000 VDC
40.000 VDC
400.00 VDC
0.0001V
0.001V
0.01V
600.0 VDC 0.1V
400.00
Ω 0.01Ω
4.0000k
Ω 0.0001kΩ
40.000k
Ω 0.001kΩ
400.00k
Ω 0.01kΩ
4.0000M
Ω 0.0001MΩ
40.000M
Ω 0.001MΩ
±(0.1% + 2 digits)
±(1.0% + 2 digits)
±(0.8% + 20 digits)
±(0.8% + 4 digits)
400.00nF
4000.0nF
400.00µF
0.01nF
0.1nF
0.01µF
±(2.5% + 10 digits)
±(5.0% + 40 digits)
±(3.0% + 10 digits)
±(3.5% + 10 digits)
4000.0µF 0.1µF
±(5.0% + 10 digits)
40.000mF 0.001mF
400.00Hz
0.01Hz ±(1.0% + 3 digits)
Sensitivity: 5Arms minimum
13 EX622-EU V2.3 04/10
Function Range
Frequency
(test leads)
40.000Hz
Resolution
0.001Hz
Accuracy
(% of reading + digits)
±(0.3% + 3 digits)
400.00Hz 0.01Hz
4000.0Hz 0.1Hz
40.000kHz 0.001kHz
±(0.3% + 2 digits)
400.00kHz 0.01kHz
4000.0kHz 0.1kHz
40.000MHz 0.001MHz
Duty Cycle
Temperature
Type K
Temperature
IR
Sensitivity: 5 to 5kHz; 0.8Vrms min., 5kHz to 150kHz; 5Vrms min
0.5% to 99.0% 0.1% ±(1.2% + 2 digits)
Pulse width: 100
μs to 100ms, Frequency: 5Hz to 150kHz
-58 to -4°F
-50 to -19°C
-4 to 31°F
-20 to -1°C
32°F
0°C
33 to 211°F
1 to 100°C
0.1° <1000°
1° >1000°
± 7°C/13°F
±(1.0% + 1°C/2°F)
±1°C/2°F
±(1.0% + 1°C/2°F)
212 to 718°F
101 to 399°C
719 to 1832°F
400 to 1000°C
Specification does not include probe accuracy
±(1.5% + 2°C/3°F)
±(2.5% + 4°C/7°F)
-58 to -4°F
-50 to -20°C
-4 to 31°F
-20 to -1°C
32°F
0°C
33 to 518°F
1 to 270°C
0.1°
± 5°C/9°F
±2% of reading or ±2°C/4°F whichever is greater
±1°C/2°F
±2% of reading or ±2°C/3°F whichever is greater
14 EX622-EU V2.3 04/10
General Specifications
Clamp jaw opening
Display
Non-Contact Voltage
Continuity check
Diode test
Low Battery indication
1.25" (32mm) approx.
Dual 40,000/4,000 count backlit LCD
100 to 600VAC
Threshold 50
Ω; Test current < 0.5mA
Test current of 0.3mA typical;
Open circuit voltage
[ 2.8VDC typical
Battery symbol is displayed
Measurement rate
Peak detector
Thermocouple sensor
Fuse
2 readings per second, nominal
>1ms
Type K thermocouple required
500mA, ceramic fast blow
IR Spectral response
IR Emissivity
6 to 16µm
0.95 fixed
IR distance ratio
Laser pointer
8:1
Class 2 laser < 1mW power; Wavelength is 630 to 670nm
10M
Ω (VDC and VAC)
Input Impedance
AC bandwidth
AC response
50 to 400Hz (AAC and VAC)
True rms (AAC and VAC)
Crest Factor
3.0 in 40A and 400A ranges, 1.4 in 1000A range (50/60Hz and 5% to 100% of range)
Operating Temperature 5
°C to 40°C (41°F to 104°F)
Storage Temperature -20
°C to 60°C (-4°F to 140°F)
Operating Humidity
Max 80% up to 31
°C (87°F) decreasing linearly to 50% at
40
°C (104°F)
Storage Humidity
<80%
Operating Altitude
Battery
7000ft. (2000meters) maximum.
One (1) 9V Battery (NEDA 1604)
Auto power OFF
Dimensions & Weight
Safety
After approx. 30 minutes, with disable
9.5x3.8x1.75” (241x96x44.5mm); 13.6 oz. (386g)
For indoor use and in accordance with the requirements for double insulation to IEC1010-1 (2001): EN61010-1 (2001)
Overvoltage Category III 600V and Category II 1000V,
Pollution Degree 2.
Approvals
Patent notice
CE
U.S. Patent 7163336
Copyright © 2008 Extech Instruments Corporation (a FLIR company)
All rights reserved including the right of reproduction in whole or in part in any form.
15 EX622-EU V2.3 04/10

Public link updated
The public link to your chat has been updated.
Advertisement
Key features
- true rms ac clamp meter
- 400 amp capacity
- ir thermometer
- dual input thermocouple temperature
- non-contact ir temperature
- non-contact voltage detector
- double molded case for heavy duty use
- measures ac current, ac/dc voltage, resistance, capacitance, frequency, diode test, duty cycle, and continuity