Tech Guide Y 25 30 60
036-21091-004-B-0205
®
TOMORROW’S UNIT TODAY
GENERAL
Introducing the YORK Millennium 25, 30, & 40 ton rooftop
line - units designed to provide peak performance and value
both today and for years to come. Millennium units are manufactured at an ISO 9001 registered facility, and each rooftop
is completely computer-run tested prior to shipment.
TECHNICAL GUIDE
MILLENNIUM®
SINGLE PACKAGE ROOFTOP UNITS
25, 30, & 40 TON
The Millennium is designed to be flexible enough to meet
your needs today and in the future. The true value of YORK’s
Millennium is that it can be designed to fit any need, from
cooling only, constant volume applications to variable air volume systems with variable frequency drive.
FEATURING:
25 TON (10 EER)
30 & 40 TON (9.5 EER)
30 TON UNIT SHOWN
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Cooling Only Units
Cooling/Gas Heating Units (Natural Gas or Propane)
Cooling/Electric Heating Units
Cooling/Hot Water Heating Units
Cooling/Steam Heating Units
Industry Leading Efficiency
Double Wall Construction
Stainless Steel Drain Pan
Multiple Scroll Compressors
Multiple Refrigeration Circuits
Upgradable Motor Efficiency
Enhanced Filtration
Vibration Isolated Supply Fan/Motor
Technicoated Condenser Coils
High Capacity Evaporator Coils
Single Power Point Connection
Easy Access Hinged Doors
Variable Air Volume
Constant Air Volume
Factory Installed Economizers/Disconnect/Convenience
Outlet/Control Options
Low Profile
MILLENNIUM SIMPLICITY® ELITE™ FEATURES:
•
•
•
•
•
•
•
•
•
•
•
Single Button Programming and LED Display
Designed to operate on both constant and variable air
volume units
365-Day real time clock with automatic Daylight Savings
time adjustment
Occupancy Schedule allowing two schedules per day
20 Holiday schedules with programmable schedules that
can start at any time, day or night
Patented Comfort Ventilation operation for economical
and comfortable economizer operation
Demand Ventilation option to assure proper IAQ conditions based on available space or return air CO2 levels
Temperature/Humidity programming algorithm allows
programmable limits to help control humidity in the space
Smoke Purge automatically ventilates the space when
smoke is detected
Monitors dirty filters and proves airflow before starting
heating or cooling
Intelligent recovery to bring the space temperature up to
occupied setting quicker and more economically
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21091-004-B-0205
TABLE OF CONTENTS
GENERAL 1
FEATURING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
MILLENNIUM SIMPLICITY® ELITE™ FEATURES . . . . . 1
OVERVIEW. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
FEATURES AND BENEFITS . . . . . . . . . . . . . . . . . . . . . . . . 5
INSTALLATION FEATURES. . . . . . . . . . . . . . . . . . . . . . . 6
CONSTRUCTION FEATURES . . . . . . . . . . . . . . . . . . . . . 7
LIST OF FEATURES AND BENEFITS . . . . . . . . . . . . . . . 8
STANDARD FEATURES . . . . . . . . . . . . . . . . . . . . . . . . 8
FACTORY INSTALLED OPTIONS . . . . . . . . . . . . . . . . 8
FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . . . . 8
SELECTION PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . 11
SELECT UNIT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
SELECT FAN SPEED AND HORSEPOWER
REQUIREMENTS OF SUPPLY AIR FAN . . . . . . . . . . . . 11
SIZE OVERCURRENT PROTECTION DEVICE AND
DETERMINE CIRCUIT AMPACITY . . . . . . . . . . . . . . . . 12
HOT WATER HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
PHYSICAL DATA HOT WATER COIL - 1 ROW . . . . . . . 12
PIPING CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . 13
PHYSICAL DATA HOT WATER COIL - 2 ROW . . . . . . . 18
STEAM HEATING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
PHYSICAL DATA STEAM COIL - 1 ROW . . . . . . . . . . . 23
PIPING CONNECTIONS. . . . . . . . . . . . . . . . . . . . . . . . . 23
SUPPLY AIR DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . . 26
CFM, STATIC PRESSURE, AND POWER - ALTITUDE
AND TEMPERATURE CORRECTIONS . . . . . . . . . . . . . 48
GUIDE SPECIFICATIONS - YORK
MILLENNIUM 25, 30, & 40 TON UNITS. . . . . . . . . . . . . . . 88
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
CONSTRUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
BASE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
CASING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
SUPPLY AIR SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . 88
SUPPLY AIR FAN . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
OPTIONAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
BEARINGS AND DRIVES . . . . . . . . . . . . . . . . . . . . . . . . 88
AIR FILTERING SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . 89
OPTIONAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
AIR INLET SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
ECONOMIZER (OPTIONAL) . . . . . . . . . . . . . . . . . . . . 89
2
RELIEF SYSTEM (OPTIONAL). . . . . . . . . . . . . . . . . . 89
BAROMETRIC RELIEF (OPTIONAL) . . . . . . . . . . . . . 89
EXHAUST AIR FANS (OPTIONAL). . . . . . . . . . . . . . . 89
ENERGY RECOVERY VENTILATION
(FIELD INSTALLED OPTION) . . . . . . . . . . . . . . . . . . . . 89
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
HEATING SYSTEM . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
GAS-FIRED HEATING SECTION (OPTIONAL) . . . . . 89
ELECTRIC HEATING SECTION . . . . . . . . . . . . . . . . . 90
HOT WATER HEATING COIL. . . . . . . . . . . . . . . . . . . 90
STEAM HEATING COIL . . . . . . . . . . . . . . . . . . . . . . . 90
REFRIGERATION SYSTEM. . . . . . . . . . . . . . . . . . . . . . 90
EVAPORATOR COILS . . . . . . . . . . . . . . . . . . . . . . . . 90
COMPRESSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
CONDENSER COILS . . . . . . . . . . . . . . . . . . . . . . . . . 91
CONDENSER FANS AND MOTORS . . . . . . . . . . . . . 91
REFRIGERANT PIPING . . . . . . . . . . . . . . . . . . . . . . . 91
HOT GAS BYPASS (OPTIONAL ON CV;
STANDARD ON VAV) . . . . . . . . . . . . . . . . . . . . . . . . . 91
CONTROLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . 91
COMPRESSOR CONTROL . . . . . . . . . . . . . . . . . . . . 91
FAN CONTROL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
EQUIPMENT CONTROL FEATURES. . . . . . . . . . . . . 92
COMFORT CONTROL FEATURES . . . . . . . . . . . . . . . . 92
OPTIONAL MODLINC TRANSLATOR . . . . . . . . . . . . . . 93
OVERVIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
AVAILABLE ACCESSORIES . . . . . . . . . . . . . . . . . . . . . 94
FULL PERIMETER AND PARTIAL
PERIMETER ROOF CURBS. . . . . . . . . . . . . . . . . . . . 94
BURGLAR BARS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
FIELD INSTALLED BAROMETRIC RELIEF . . . . . . . . 94
PROGRAMMABLE THERMOSTAT, WITH OR
WITHOUT REMOTE SENSOR (REQUIRED FOR
CONSTANT VOLUME UNITS) . . . . . . . . . . . . . . . . . . 94
REMOTE WALL MOUNTED TEMPERATURE
SENSORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
DIRTY FILTER SWITCH . . . . . . . . . . . . . . . . . . . . . . . 94
NATURAL GAS AND PROPANE
CONVERSION KITS . . . . . . . . . . . . . . . . . . . . . . . . . . 94
HIGH ALTITUDE CONVERSION KITS . . . . . . . . . . . . 94
ENERGY RECOVERY VENTILATORS . . . . . . . . . . . 94
Unitary Products Group
036-21091-004-B-0205
LIST OF FIGURES
Fig.#
Pg.#
Fig.#
Pg.#
1
HOT WATER PIPING CROSS-SECTION . . . . . . . . . 13
19 STEAM COIL - 25 & 30 TON, 1 ROW . . . . . . . . . . . . 24
2
HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 10 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
20 STEAM COIL - 40 TON, 1 ROW. . . . . . . . . . . . . . . . . 24
3
HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 20 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
4
HOT WATER COIL - 25 & 30 TON, 1 ROW,
AT 30 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
5
HOT WATER COIL - 25 & 30 TON, 1 ROW
AT 40 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
6
HOT WATER COIL - 40 TON, 1 ROW, AT 10 GPM . . 16
7
HOT WATER COIL - 40 TON, 1 ROW, AT 20 GPM . . 16
26 POWER EXHAUST - TWO FORWARD CURVED
FANS - 30 & 40 TONS . . . . . . . . . . . . . . . . . . . . . . . . 60
8
HOT WATER COIL - 40 TON, 1 ROW, AT 30 GPM . . 17
27 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 77
9
HOT WATER COIL - 40 TON, 1 ROW, AT 40 GPM . . 17
28 COMPONENT LOCATION . . . . . . . . . . . . . . . . . . . . 79
10 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 20 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
29 END RETURN, BOTTOM SUPPLY . . . . . . . . . . . . . . 80
11 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 40 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
31 BOTTOM RETURN, FRONT & REAR SUPPLY . . . . 82
21 ALTITUDE/TEMPERATURE CONVERSION
FACTOR . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
22 FAN PERFORMANCE - 25 TON . . . . . . . . . . . . . . . . 51
23 FAN PERFORMANCE - 30 TON . . . . . . . . . . . . . . . . 53
24 FAN PERFORMANCE - 40 TON . . . . . . . . . . . . . . . . 55
25 POWER EXHAUST - ONE FORWARD CURVE
FAN - 25 TONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
30 BOTTOM SUPPLY AND RETURN . . . . . . . . . . . . . . 81
12 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 60 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
32 END RETURN, FRONT & REAR SUPPLY . . . . . . . . 83
13 HOT WATER COIL - 25 & 30 TON, 2 ROW,
AT 80 GPM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
34 MILLENNIUM MAJOR COMPONENT LAYOUT . . . . 84
14 HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM . . 21
15 HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM . . 21
33 MILLENNIUM OVERHEAD VIEW . . . . . . . . . . . . . . . 84
35 CLEARANCES - HOOD/ECONOMIZER & MOTOR
DRIVE - SIDE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
16 HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM . . 22
36 CLEARANCES - HOOD/ECONOMIZER & MOTOR
DRIVE - FRONT & END . . . . . . . . . . . . . . . . . . . . . . 85
17 HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM . . 22
37 PARTIAL ROOF CURB MODEL 1RC0455P . . . . . . . 86
18 STEAM PIPING CROSS SECTION . . . . . . . . . . . . . . 23
38 FULL ROOF CURB MODEL 1RC0455F . . . . . . . . . . 87
Unitary Products Group
3
036-21091-004-B-0205
LIST OF TABLES
Tbl.#
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
4
Pg.#
GENERAL PHYSICAL DATA . . . . . . . . . . . . . . . . . . . 10
REFRIGERANT CHARGE . . . . . . . . . . . . . . . . . . . . . 11
GAS HEATING CAPACITIES . . . . . . . . . . . . . . . . . . . 12
ELECTRIC HEATING CAPACITIES . . . . . . . . . . . . . . 12
STATIC RESISTANCE HOT WATER COIL
(25 & 30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
HOT WATER COIL (1 ROW, 25 & 30 TON) . . . . . . . . 13
WATER PRESSURE DROP (1 ROW, 25 &
30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
STATIC RESISTANCE HOT WATER COIL
(1 ROW, 40 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
HOT WATER COIL (1 ROW 40 TON) . . . . . . . . . . . . 13
WATER PRESSURE DROP (2 ROW,
25 & 30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
STATIC RESISTANCE HOT WATER COIL
(25 & 30 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
HOT WATER COIL (2 ROW, 25 & 30 TON) . . . . . . . . 18
HOT WATER COIL (2 ROWS, 40 TON) . . . . . . . . . . . 18
STATIC RESISTANCE HOT WATER COIL
(40 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
WATER PRESSURE DROP (2 ROW, 40 TON) . . . . . 18
STEAM COIL (1 ROW, 25 & 30 TON) . . . . . . . . . . . . 23
STATIC RESISTANCE STEAM COIL
(1 ROW, 25 & 30 TON) . . . . . . . . . . . . . . . . . . . . . . . . 23
STEAM COIL (1 ROW, 40 TON) . . . . . . . . . . . . . . . . 23
STATIC RESISTANCE STEAM COIL
(1 ROW, 40 TON) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
EXHAUST FAN DRIVE DATA . . . . . . . . . . . . . . . . . . 25
SUPPLY FAN MOTOR AND DRIVE DATA . . . . . . . . 25
25 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . . 27
30 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . . 27
40 TON DRIVE ADJUSTMENT . . . . . . . . . . . . . . . . . 27
DRIVE ADJUSTMENT FOR POWER EXHAUST
- 25 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
DRIVE ADJUSTMENT FOR POWER EXHAUST
- 30 & 40 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
COOLING PERFORMANCE - 25 TON STANDARD
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
COOLING PERFORMANCE - 30 TON STANDARD
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
COOLING PERFORMANCE - 30 TON HIGH
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Tbl.#
Pg.#
30 COOLING PERFORMANCE - 40 TON STANDARD
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
31 COOLING PERFORMANCE - 40 TON HIGH
CAPACITY COIL . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
32 ALTITUDE CORRECTION FACTORS . . . . . . . . . . . . 48
33 FAN PERFORMANCE - 25 TON, . . . . . . . . . . . . . . 50
34 FAN PERFORMANCE - 30 TON , . . . . . . . . . . . . . . 52
35 FAN PERFORMANCE - 40 TON, . . . . . . . . . . . . . . . 54
36 COMPONENT STATIC RESISTANCE, . . . . . . . . . . 56
37 POWER EXHAUST - ONE FORWARD CURVED
FAN 25 TON . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
38 POWER EXHAUST - TWO FORWARD CURVED
FANS - 30 & 40 TON . . . . . . . . . . . . . . . . . . . . . . . . . 59
39 ELECTRICAL DATA 25 TON BASIC UNIT . . . . . . . . 61
40 ELECTRICAL DATA 30 TON BASIC UNIT . . . . . . . . 61
41 ELECTRICAL DATA 40 TON BASIC UNIT . . . . . . . . 61
42 ELECTRICAL DATA 25 TON BASIC UNIT W/
ELECTRIC HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62
43 ELECTRICAL DATA 30 TON BASIC UNIT W/
ELECTRIC HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
44 ELECTRICAL DATA 40 TON BASIC UNIT W/
ELECTRIC HEAT . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
45 ELECTRICAL DATA 25 TON BASIC UNIT W/
POWER EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . 65
46 ELECTRICAL DATA 30 TON BASIC UNIT W/
POWER EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . 66
47 ELECTRICAL DATA 40 TON BASIC UNIT W/
POWER EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . 67
48 ELECTRICAL DATA 25 TON BASIC UNIT W/
POWER EXHAUST & ELEC HEAT . . . . . . . . . . . . . . 68
49 ELECTRICAL DATA 30 TON BASIC UNIT W/
POWER EXHAUST & ELEC HEAT . . . . . . . . . . . . . . 71
50 ELECTRICAL DATA 40 TON BASIC UNIT W/
POWER EXHAUST & ELEC HEAT . . . . . . . . . . . . . . 74
51 UNIT WEIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
52 SUPPLY FAN MOTOR VFD WEIGHTS . . . . . . . . . . . 77
53 EXHAUST FAN MOTOR VFD WEIGHTS. . . . . . . . . . 77
54 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . 77
55 UNIT CORNERWEIGHT . . . . . . . . . . . . . . . . . . . . . . 78
56 INDOOR SOUND POWER RATING . . . . . . . . . . . . . 78
57 ATTENUATION FACTORS . . . . . . . . . . . . . . . . . . . . 78
58 OUTDOOR SOUND POWER RATING . . . . . . . . . . . 79
Unitary Products Group
036-21091-004-B-0205
YORK Millennium®
OVERVIEW
Introducing the YORK Millennium 25, 30, & 40 ton rooftop
line - units designed to provide peak performance and value
both today and for years to come. When we asked our customers what they wanted in a new rooftop line, we were careful to listen to both the needs of today and tomorrow. So,
you'll find that Millennium units not only help you solve
today's problems, but can handle tomorrow's difficulties as
well:
Industry Leading Efficiency - The Millennium's 9.5 EER (10
EER 25 ton) rating makes it the most frugal energy consumer
in its class. When it comes to lower operating costs, Millennium simply outperforms the competition.
Double Wall Construction - Millennium units come double
walled as standard. The galvanized sheet metal liner provides the best protection against microbial growth, helping
both the unit and the indoor air stay fresh and clean. And, the
rigid sheet metal inner liner keeps the insulation completely
out of the air stream, eliminating concerns about fiberglass
particles.
Drain Pan Whisks Away Condensate - Condensate is frequently the source of microbial contamination. Competitive
drain pans often are insufficiently sloped to properly drain all
of the condensate, causing drain pan corrosion and bacterial
growth to begin almost immediately. The YORK design is
stainless steel, for long life. And, it is sloped at the 1/4” per
foot recommended by the new ASHRAE ventilation draft
standard, with an extra large drain connection capable of
removing up to three gallons of condensate per minute. Best
of all, the drain pan is easily removed from the unit so that it
can be cleaned at regular intervals.
Unitary Products Group
Efficient, Durable Scroll Compressors - The Millennium
design uses industrial grade hermetic scroll compressors for
peak efficiency and low noise operation. The compressor
design is so durable that it can actually hold more liquid
charge without slugging than is present in each refrigerant
circuit at shipment, dramatically reducing the chances of ever
slugging a compressor with liquid charge.
Multiple Refrigeration Circuits for Greater Turndown - The
YORK Millennium unit has intertwined 10 ton circuits (12.5
ton circuits on the 25 ton) - giving the best unloading capability in the industry. With more and more designs requiring
higher outside air quantities, the lower capacity capability is
an outstanding way to neutralize outside air without over-conditioning the space on off-peak days. And, Millennium's high
quality balance-port thermal expansion valves are more
effective at metering refrigerant flow in part-load conditions,
making Millennium a peak-performer across a wide capacity
range.
FEATURES AND BENEFITS
When it comes to flexibility, Millennium really shines. Our customers were clear about one thing - not all installations are
the same. Some have very simple needs, others are more
involved. The YORK Millennium serves both markets - and all
of those in between - extremely well. YORK engineers crafted
a design which is both uniquely flexible and competitive, giving you the best of both worlds. In addition to a competitive
base product, Millennium offers unparalleled flexibility.
Optional features include:
Variable Air Volume - YORK gives you the ability to vary air
volume by inlet guide vanes or variable frequency drive - the
choice is yours. All Millennium VAV units come standard with
hot gas bypass to give extended operation range.
5
036-21091-004-B-0205
Optional Head Pressure Control - For those applications
where mechanical cooling is required below 40°F, optional
low ambient operation allows compressor operation down to
0°F.
Heating Done Your Way - Millennium offers the choice of natural gas or propane, electric resistance heat, hot water heat,
steam, or no heat at all. Very simply, the choice is yours.
INSTALLATION FEATURES
Easily Upgrade Motor Efficiency to Meet Tighter Codes Optional high efficiency motors help you make simple
upgrades to meet more demanding building and energy
codes.
Enhanced Filtration Options - Millennium gives designers the
flexibility to meet various IAQ requirements with a full range
of rigid and throwaway filters at different efficiency levels.
Vibration Isolation - The Millennium's 1” isolator springs are
typically sufficient for most applications, but when sound and
vibration transmission are a major concern, YORK offers 2”
isolation springs for even greater protection from supply air
fan noise and vibration.
Optional TechniCoated Coated Condenser Coils - Many
industrial and seacoast applications require enhanced protection from corrosive environments. The special dipped phenolic coating process provides a high level of protection for
the exposed condenser coil.
High Capacity Evaporator Coils - For those applications
which require slightly more capacity than offered by the standard Millennium product, YORK offers the option of higher
capacity evaporator coils, boosting cooling output without
increasing unit size.
Variety of Exhaust Air Options - YORK Millennium offers a
wide variety of exhaust air options, including barometric
relief, non-modulating power exhaust, and modulating power
exhaust. And, because Millennium units use forward-curved
blowers for power exhaust fans, they can exhaust up to 100%
of the nominal supply air at much greater static pressure
loads than competitive units. Not available on end return.
With YORK Millennium, high performance doesn't mean high
complexity. YORK listened carefully to make sure that Millennium was as simple as possible, and service convenience
comes standard with each unit. From a single curb size to the
easy service access, you'll find that Millennium was designed
to be easy from start to finish.
Full Range of Air Flows and Static Pressures - The Millennium design gives a complete offering of supply air flows and
static pressure combinations to meet most every application
requirement.
Single Power Point Connection - Millennium units have a single gas and electric connection, minimizing time at the job
site. For further installation flexibility, power and gas connections may be brought up from the curb or through the side of
the unit.
Simple Controls - Millennium's controls system is easy to
understand and apply, and it doesn't lock you into proprietary
devices. A choice for YORK Millennium today does not limit
your choices tomorrow.
Rain Hoods Rotate Into Place - No bulky, field--installed rain
hoods here. Millennium rain hoods ship rotated inside the
unit. Once on the job, installer merely rotates the hood
upward and puts in a few screws - an easy one-person job.
Excellent Access for Service - Service access on Millennium
is a snap. Hinged and latched doors give access on both
sides of the unit to all major components. All doors have positive action slide latches for even greater ease of access. All
service fittings are conveniently located to minimize time and
effort.
Optional Factory Installed Economizers - Millennium units
offer an optional factory installed economizer with low leak
dampers. Comparative enthalpy, single enthalpy and dry bulb
control are available.
Optional Factory Installed Disconnect - A conveniently
located actuator handle in the front of the unit can disconnect
line power to the entire unit, eliminating the need for a field
provided disconnect. The handle may also be locked in either
position through the use of a standard padlock. Millennium's
single point power connection makes this option particularly
appealing. If desired, the disconnect may be ordered with a
115 volt, GFCI protected convenience outlet, including a factory wired transformer to power the outlet from the single
point power connection; the convenience outlet remains
operational when the disconnect is open.
6
Unitary Products Group
036-21091-004-B-0205
A N G L E D C O N D E N S E R
C O IL S
P IT C H E D R O O F
S O L ID , C L A S S II F A N
C O N S T R U C T IO N
IN T E R T W IN E D
D O U B L E W A L L C O N S T R U C T IO N
C O IL
H IN G E D , L A T C H E D
A C C E S S D O O R S
L O W
CONSTRUCTION FEATURES
YORK's Millennium rooftop line is built for the long haul, with
high end features and construction offered at a competitive
price. Millennium units are manufactured at an ISO 9001 registered facility, and each rooftop is completely computer-run
tested prior to shipment. Some of the valuable construction
features of the Millennium which are not found on competitive
units include:
Double Wall Construction - Each unit has both an exterior
and an interior wall, which make for a more rigid design with
panels and doors that are solid, not flimsy. The unit features a
fully framed construction for even greater stability.
Powder Paint - Industry leading 1000 salt spray hour paint
keeps the unit in great condition for years to come.
L E A K D A M P E R S
Extended flue connection - Each gas unit ships with a field
mounted external flue. The flue lifts all products of furnace
combustion far above the unit - eliminating the possibility of
corrosion in the furnace heat exchanger from recirculating
flue gases.
Protective Covering - Special polyurethane sleeves which
cover the distributor tubing keep distributor tubes from contacting each other and wearing out.
Built-in Hail Guard - Condenser coils angled at 30 degrees
from the vertical are inherently protected from damage due to
shipment, hail, etc.
Induced Draft Furnace - This design provides a positive
exhaust of all combustion products.
Low Profile - Millennium units stand only 64” above their
curb, minimizing potential aesthetic conflicts.
Unitary Products Group
7
036-21091-004-B-0205
LIST OF FEATURES AND BENEFITS
Standard Features
Field Installed Accessories
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
9.5 EER (10 EER on 25 ton)
Double wall construction
Hinged and latched access doors
Industrial duty scroll compressors
Sturdy framed construction
Sloped stainless steel drain pan
Separate 10 ton circuits (30 and 40 ton units) or 12.5 ton
(25 ton unit)
Intertwined evaporator coil
Angled condenser coils for superior protection
Single power point connection
Through-the-curb or through-the-base utility connections
Retractable outside air hoods
Powder paint tested to 750 salt spray hours
Mechanical cooling from 40° F to 120° F
1-1/2” insulation
Sloped unit roof with drip lip
High and low refrigerant pressure protection
Polyurethane sleeves to protect small diameter tubing
Steel framing around blowers with 1” deflection springs
for low vibration
Fully factory packaged and run-tested
10 year gas heat exchanger warranty
One year compressor warranty
One year warranty on all parts
•
•
•
•
•
•
•
•
Factory Installed Options
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
8
Economizer with low leak dampers
Natural gas heat with reliable induced draft design
Electric heat in three sizes
Variable air volume with either inlet guide vanes wired for
VFD variable frequency drive, or factory installed VFD.
2” blower isolator springs
A variety of blower horsepower offerings
High efficiency motors
High efficiency filtration
Barometric relief
Power exhaust of 100% of nominal air flow
Technicoat corrosive resistant coating on condenser
coils
0°F low ambient operation of mechanical cooling
Hot gas bypass (standard on all VAV units)
High capacity evaporator coils
Single unit disconnect
Convenience outlet and transformer factory wired
Hot water heating coil with one or two rows
One row steam heating coil
Simplicity ® Elite™ controls
ModLINC translator
•
•
7-Day Programmable Wall Thermostat-Can be used with
or without remote sensors. Can be used on CV and VAV
units when wall thermostat is required for scheduling and
temperature control.
Energy Recovery Ventilators- 8,000 and 13,000 CFM
models available.
Great for applications involving 30% or more of required
outdoor air where energy use and comfort must be optimized.
Wall Sensors- Remote space sensors used with CV or
VAV unit for unit control via the Simplicity® Elite™ control. Standard sensor, sensor with override and sensor
with override and + 5 degree adjustment.
Simplicity® Transporter- Device allows internet control
and monitoring of HVAC units equipped with Simplicity®
Elite™ controls.
Phase Monitor Kit- Includes control and wiring to monitor
and protect the unit from phase reversal, phase loss and
low voltage.
Burglar Bars- Prevent any type of building entry through
the RTU unit with bars that block the return and supply
openings on downflow applications.
Full and partial perimeter roofcurbs- Designed for application on all 25-40 ton Millennium rooftop units. 14"
height.
Barometric Relief Kit- Provides barometric relief hood
and dampers for duct mounting on units requiring end
return.
Natural Gas to Propane Conversion Kits- Contains orifices and gas valves parts to convert from Natural Gas to
Propane.
High Altitude Kit- Natural and propane gas kit designed
for natural gas heating applications between 2,000 and
6,000 feet above sea level.
Unitary Products Group
Unitary Products Group
;52:
:52:
52:
&=(512+($7
(.:
.:
.:
160%+
0%+
0%+721/<
4
5
6
7
0
1
2
3
,
-
.
/
(
)
*
+
$
%
&
'
´'()/(&725
´'()/(&725
)&
$)
&9
9$9,*9
9$99)'&86720(5
9$99)')$&725<
,167$//('
%<3$669)'
$67$1'$5'
%
&
'´+,())
$
%
&
'
(
)
*
+
,
-
.
/
0
1
2
3
4
+3
+3
+3
+3+,())
+3+,())
+3+,())
+3721/<
+3+,,))721/<
02'8/$7,1*
12102'8/$7,1*
$:9)'
+367'
+367'
+367'
+367'
+3+,())
+3+,())
+3+,())
+3+,())
+367'721/<
+3+,())721/<
$%$520(75,&
%
&
'
(
)
*
+
,
-
.
/
0
1121(
2
3
4
5
6$
7$
8$
9$
:$
;$
=$
FIP(59
FIP(59
+($7&$3$&,7<.127$9$,/$%/(9
7+(67$1'$5'()),&,(1&<027250((76&$1$',$10,1,080
()),&,(1&<5(*8/$7,216$60$1'$7(',17+(&$1$',$1(1(5*<
()),&,(1&<5(*8/$7,216+,*+(525³8/75$+,*+´()),&,(1&<
027256$5(127$9$,/$%/()259
9)'&86720(5:,5(')259)'21/<9)':,//%(&86720(5
6833/,('$1'),(/',167$//('
0867+$9(+27*$6%<3$66:9$9
*$6+($7127$9$,/$%/(,1)52176833/<&21),*85$7,21
+27:$7(567($0$1'(/(&75,&+($721/<$9$,/$%/(,1%277206833/<&21),*85$7,21
32:(5(;+$867$1'%$520(75,&5(/,()127$9$,/$%/(,1(1'5(7851&21),*85$7,21
$))$16$9$,/$%/(21&22/,1*21/<81,76
7+,6237,210867%((/(&7(',)$33/<,1*$),(/',167$//('(59727+(522)723
127(6
11$785$/*$6
61$785$/*$666+($7(;&+$1*(5
((/(&75,&+($7
&&22/,1*21/<
:+27:$7(5&2,/
;67($0&2,/
)52176833/<&22/,1*21/<
(/(&75,&+($7%277206833/<
*$6+($7%27720255($56833/<
$%277205(7851
%%277206833/<
&(1'5(7851
'5($56833/<
()52176833/<
)
721
721
721
9
5
6
7
8
9
:
;
<
=
<(6
12
(%!$02%33#4,
67$1'$5'
+,&$37
67'&2,/:7&
+,&$3&2,/:7&
67$1'$5'
+27*$6%<3$66
67$1'$5'
7(&+1,&2$7
$'8$/(17+
%6,1*/((17+
&'5<%8/%
'0$18$/
(121(
'6<17+(6<6&21752/
(6<17+(6<6&21752/
',6&9287/(7
)6<17+(6<6',6&
*237,/2*,&(6*21/<
+6,03/,&,7<&21752/:,7+287
',6&211(&7129287/(7
,6,03/,&,7<&21752/:,7+
',6&211(&7$1'9287/(7
-6,03/,&,7<&21752/:,7+
',6&211(&7129287/(7
.6,03/,&,7<&21752/:02'/,1&
/6,03/,&,7<&21752/:02'/,1&
',6&9287/(7
06,03/,&,7<&21752/:02'/,1&
',6&129287/(7
(
036-21091-004-B-0205
NOMENCLATURE
9
036-21091-004-B-0205
TABLE 1: GENERAL PHYSICAL DATA
UNIT SIZE
UNIT EER / IPLV
(STANDARD CAPACITY EVAPORATOR)
NUMBER/SIZE
TYPE
UNIT CAPACITY STEPS
NUMBER / TYPE
DIAMETER X WIDTH (INCHES)
HP RANGE
CFM RANGE (FULL LOAD)
ESP RANGE
NUMBER/SIZE/TYPE
HP RANGE (SINGLE MOTOR)
CFM
SIZE (SQ. FT.)
ROWS/FPI
SIZE (SQ. FT.)
ROWS/FPI
SIZE (SQ. FT.)
ROWS/FPI
QUANTITY / DIAMETER (INCHES)
NOMINAL CFM
MOTOR HP
KW RANGE
40 KW CAPACITY STEPS
80 AND 108 KW CAPACITY STEPS (CV/VAV)
UNIT SIZE
233 MBH CAPACITY STEPS (CV/VAV)
466 MBH CAPACITY STEPS (CV/VAV)
699 MBH CAPACITY STEPS (CV/VAV)
SIZE (INCHES)
CAPACITY
SIZE (INCHES)
TYPE
NUMBER / SIZE
FACE AREA (SQ. FT.)
NUMBER / SIZE
FACE AREA (SQ. FT.)
NUMBER / SIZE
FACE AREA (SQ. FT.)
NUMBER / SIZE
FACE AREA (SQ. FT.)
10
25 TON
30 TON
40 TON
10.0 / 10.92
9.5 / 10.97
9.5 / 9.73
3 x 10 Ton
Scroll
33%, 67%, 100%
4 x 10 Ton
Scroll
25%, 50%, 75%, 100%
1 / FC
22 x 20
10 - 25
6,000 - 15,000
0.2" - 4.0”
1 / FC
25 x 22
10 - 25
8,000 - 18,000
0.2" - 4.0"
2/FC
7.5 - 15
4,000 - 18,000
2/FC
7.5 - 15
4,000 - 18,000
26.0
3 / 16
30.4
4 / 13
26.0
4 / 16
30.4
4 / 16
48.8
2 /16
65.0
2 /16
3 / 24
6,800
1.0
4 / 24
6,800
1.0
40 - 108
1
2/1
40 - 108
1
2/1
30 TON
1/1
2/1
-
40 TON
1/1
2/1
3/1
22.5" X 65”
30 Ton
22.5" X 65”
40 Ton
COMPRESSOR DATA
2 x 13 Ton
Scroll
50%, 100%
INDOOR FAN AND DRIVE
1 / FC
22 x20
7.5 - 20
6,000 - 12,500
0.2” - 4.0”
EXHAUST FAN
1/FC
5 - 10
3,000 - 9,000
STANDARD EVAPORATOR COIL
26.0
3 / 13
HIGH CAPACITY EVAPORATOR COIL
26.0
2/16
CONDENSER COIL
52.0
2/16
CONDENSER FANS
4 / 24
4,600
3/4
ELECTRIC HEAT
40 - 108
1
2/1
NATURAL GAS HEAT
25 TON
1/1
2/1
HOT WATER COIL
22.5” x 65”
25 Ton
STEAM COIL
21" X 65"
Steam Coil
FILTERS 2" HI. EFF. TA
4 / 16 x 25 & 6 / 20 x 25
4 / 16 x 25 & 6 / 20 x 25
30.4
30.4
FILTERS 2" PLEATED, 65%
4 / 16 x 25 & 6 / 20 x 25
4 / 16 x 25 & 6 / 20 x 25
30.4
30.4
FILTERS 65% RIGID W/ 2” TA PREFILTERS
4 / 16 x 25 & 6 / 20 x 25
4 /16 x 25 & 6 / 20 x 25
30.4
30.4
FILTERS 95% RIGID W/ 2” TA PREFILTERS
4 ea. 16 x 25 / 6 ea. 20 x 25
4 ea. 16 x 25 / 6 ea. 20 x 25
30.4
30.4
4 / 16 x 25 & 6 / 20 x 25
30.4
4 / 16 x 25 & 6 / 20 x 25
30.4
4 / 16 x 25 & 6 / 20 x 25
30.4
4 ea. 16 x 25 / 6 ea. 20 x 25
30.4
Unitary Products Group
036-21091-004-B-0205
TABLE 2: REFRIGERANT CHARGE
UNIT (TONS)
MODEL
TYPE
FACTORY/ FIELD
CHARGED
25
25
30
wo/HGBP
w/HGBP
wo/HGBP
R22
R22
R22
Factory
Factory
Factory
30
wo/HGBP1
R22
30
w/HGBP1
w/HGBP
wo/HGBP
w/HGBP
R22
R22
R22
R22
30
40
40
1.
CHARGE
SYS #1
27 lb. / 0 oz.
27 lb. / 8 oz.
13 lb. / 4 oz.
SYS #2
26lb / 0oz
26 lb. / 0oz
13 lb. / 8 oz.
SYS #3
13 lb. / 8 oz.
Factory
14 lb. / 6 oz.
14 lb. / 10 oz.
14 lb. / 10 oz.
-
Factory
14 lb. / 0 oz.
13 lb. / 8 oz.
13 lb. / 8 oz.
-
Factory
Factory
Factory
15 lb. / 2 oz.
15 lb. / 5 oz.
15 lb. / 13 oz.
14 lb. / 10 oz.
15 lb. / 4 oz.
15 lb. / 4 oz.
14 lb. / 10 oz.
15 lb. / 5 oz.
15 lb. / 5 oz.
15 lb. / 15 oz.
15 lb. / 15 oz.
With high capacity evaporator coil.
SELECTION PROCEDURE
The 40 ton unit will meet the cooling requirements. From
the nomenclature, the unit will be a Y14. Choose the
appropriate configuration for the next digit. Assuming
bottom return and supply, the fourth digit would be an
“A,” making the model Y14A.
GIVEN:
Required Cooling Capacity
460,000 Btuh
Required Sensible Cooling
390,000 Btuh
Required Heating (Gas)
320,000 Btuh
3.
Entering Air on Evaporator
83° F DB/ 67° F WB
Outside Design Temperature
Supply Fan CFM
a.
Trace down Output column.
b.
Find output which exceeds 320,000 Btuh requirement. The N4 option gives 373 MBH output.
c.
Ensure that it is offered in the Y14 unit. Read option
model as N4.
13,000 CFM
1.25 IWG
Electrical Supply Voltage
460-3-60
Economizer Required
2” Throw Away Filters
Constant Volume
SELECT UNIT:
2.
Find Gas Heating Capacity Table.
95° F
External Static Pressure
1.
SYS #4
-
Determine nominal tons:
From the basic nomenclature, the model now becomes
Y14AN4. Add voltage code of “4” for 460-3-60. Nomenclature becomes Y14AN44.
SELECT FAN SPEED AND HORSEPOWER
REQUIREMENTS OF SUPPLY AIR FAN
1.
Find Supply Air Performance Tables for the 40 ton unit.
a.
Check footnotes and make necessary additions or
deductions to static resistance of ductwork:
Ductwork static resistance 1.25 IWG
460,000 / 12,000 = 38.33 Tons
Economizer static resistance addition (interpolate) =.25
IWG + Gas Heat (High) = 0.5 IWG
Thus, a nominal 40 ton unit is selected.
Total Static Resistance
Reference Cooling Capacity Table for a 40 ton unit with
standard evaporator coil.
b.
a.
Enter table at 13,000 CFM and 67°F WB air on
evaporator
c.
Trace to 83° F Entering Dry Bulb column.
d.
Read 493 MBH total capacity and 403 MBH sensible capacity.
BHP = 10.2
c.
Unitary Products Group
Enter Fan Performance Table at 13,000 CFM and
2.0 IWG static pressure:
RPM = 690
Locate the table for a standard evaporator coil with
95° F air on the condenser.
b.
2.0 IWG
Correct BHP for drive losses (using 1.05 correction
factor). 10.2 BHP x 1.05 = 10.7 BHP. Enter the Fan
Motor Drive Tables. Selecting a 15 hp motor allows
(service factor of 1.5) for a maximum operating BHP
greater than the 10.7 BHP requirement.
11
036-21091-004-B-0205
SIZE OVERCURRENT PROTECTION DEVICE AND
DETERMINE CIRCUIT AMPACITY
1.
Find electrical tables for the basic 40 ton unit.
a.
Enter table for 460-3-60 voltage.
b.
Find 15 hp in the Supply Air Fan column.
c.
Trace to Minimum Circuit Ampacity column - read
109.
d.
Trace to M.O.P.D. column - read 125.
e.
Size wire and overprotection device accordingly.
f.
Check all footnotes.
TABLE 3: GAS HEATING CAPACITIES
GAS HEAT
OPTION
AVAILABLE ON
MODELS
1ST STAGE
TOTAL
N2
N4
Y22/Y23/Y24
Y22/Y23/Y24
233
233
233
466
OUTPUT
CAPACITY
(MBH)2
186
373
N74
Y24 ONLY
466
699
560
INPUT CAPACITY (MBH)1
GAS RATE, CU. FT./HR.3
1ST STAGE
TOTAL
TEMP. RISE °F
AT FULL RATE
217
217
217
434
5 - 35
15 - 45
434
650
20 - 50
1.
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.
2.
Blower motor heat not included.
3.
based on a heat content of 1075 Btu/Ft.3
4.
Minimum heating CFM for N7 700 MBH heat is 11,700 CFM.
TABLE 4: ELECTRIC HEATING CAPACITIES
ELECTRIC
HEAT OPTION
AVAILABLE ON
MODELS
RATED
VOLTAGE
NOMINAL KW
NOMINAL
MBH1
STAGE 1
STAGE 2
KW
MBH
KW
MBH
E4
Y22,Y23, Y24
2403/4804/
575
E8
Y22, Y23,
Y24
2402/4803/
575
80
273
40
137
40
136
E1
Y22, Y23,Y24
(460 & 575
volt only)
4803/575
108
369
72
246
36
123
40
137
40
137
0
0
1.
Supply air fan motor heat not included.
2.
Heating capacity is only staged on CV models. VAV models use only one stage at full capacity.
3.
For 208 volts, multiply kW and MBH values by .751. For 203 volts, multiply kW and MBH values by .918
4.
For 460 volts, multiply kW and MBH values by .918.
HOT WATER HEATING1
The YORK Millennium Rooftop units (30 - 40 Ton sizes) can
be furnished with a YORK hot water coil as the source of
heat (Bottom Supply Only). A one or two row coil will be factory installed in the heating section downstream of the supply
air fan and just above the supply air opening in the bottom of
the unit.
The hot water control valve will not be provided. The installer
will need to field supply a water valve. The installer must also
connect the hot water piping, and valve wiring at the job site
for the hot water heat section to be operational.
1. Hot water, steam or electric heat is not available for
front or rear supply.
12
MBH AND KW PER STAGE2
For all hot water coils the entering water temperature should
not exceed 200°F.
PHYSICAL DATA HOT WATER COIL - 1 ROW
Coil Casing . . . . . . . . . . . . . . . . . . . . Galvanized Steel
Coil Construction . . . . . . . . . . . . . . . Al Fin / Cu. Tube
Rows Deep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . ..006”
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..016”
Tubes / Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Fins Per Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . .22.50”
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65”
Face Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.16ft.2
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71lbs.
Operating Weight . . . . . . . . . . . . . . . . . . . . . . . . 83lbs.
Unitary Products Group
036-21091-004-B-0205
TABLE 5: WATER PRESSURE DROP (1 ROW, 25 &
30 TON)
GPM
WATER PRESSURE DROP
10
0.9
20
3.0
30
6.0
40
10.0
TABLE 6: STATIC RESISTANCE HOT WATER COIL
(25 & 30 TON)
CFM
AIR PRESSURE DROP 1 ROW
AIR PRESSURE DROP 2 ROW
6000
0.07
0.14
8000
0.11
0.23
10000
0.16
0.33
PIPING CONNECTIONS
The hot water piping must enter the unit through the floor of
the heat section compartment. The access doors to the compartment are gasketed so the compartment can be sealed.
However, as added protection for water leakage into the
space, the piping access holes should be sealed with a heat
resistant mastic (see the following illustration for approximate
location of the compartment and piping connections.
15000
0.32
0.65
(1 OR 2 ROW)
26"
INLET (2")
OUTLET (2")
OUTSIDE OF
BASE RAIL
15.8"
11.88"
8.38"
2.25"
2.55"
88.75"
HEAT SECTION
COMPARTMENT
FIGURE 1 DO NOT use tin based solder. Brazing with tin
based solder could cause equipment damage or
possible injury to OCCUPANTS of the structure
that is being conditioned.
TABLE 7: HOT WATER COIL (1 ROW, 25 & 30 TON)1
GPM
10
20
30
40
1.
CFM
6000
8000
10000
12000
15000
6000
8000
10000
12000
15000
6000
8000
10000
12000
15000
6000
8000
10000
12000
15000
CAPACITY (MBH) AT ENTERING WATER
TEMPERATURE
140 °F
160 °F
180 °F
200 °F
91.4
115.3
139.3
163.6
102
128.8
155.8
182.9
110.4
139.5
168.8
198.4
117.3
148.4
179.6
211.2
125.9
159.2
192.9
226.9
103
129.4
156
182.7
116.8
147
177.2
207.7
128.2
161.3
194.7
228.2
137.8
173.6
209.5
245.6
150
189
228.2
267.8
107.6
135
162.5
190.1
122.8
154.3
185.8
217.5
135.5
170.3
205.1
240.2
146.4
184
221.8
259.7
160.3
201.6
243
284.8
110.1
138
166
194.1
126.1
158.2
190.5
222.8
139.6
175.2
210.9
246.8
151.2
189.8
228.5
267.5
166.1
208.6
251.3
294.1
CL
HOT WATER PIPING CROSS-SECTION
TABLE 8: STATIC RESISTANCE HOT WATER COIL
(1 ROW, 40 TON)
CFM
AIR PRESSURE DROP 1 ROW
AIR PRESSURE DROP 2 ROW
8000
0.11
0.23
11000
0.19
0.39
14000
0.29
0.58
20000
0.52
1.06
TABLE 9: HOT WATER COIL (1 ROW 40 TON)1
GPM
10
20
30
Based on 60°F entering air temperature, 2.00” maximum pressure drop across the hot water coil.
40
1.
Unitary Products Group
CONDENSING
SECTION
HOT WATER
COIL
NOTE: Water pressure drop numbers are based on 60°F
entering air temperature, 2.00” maximum air pressure drop across the hot water coil(s). ARI certified
ratings at covering other conditions are available
upon request. Hot water coils are approved for use
with glycol (rates available upon request).
CFM
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
CAPACITY (MBH) AT ENTERING WATER
TEMPERATURE
140 °F
160 °F
180 °F
200 °F
102
128.8
155.8
182.9
114
144.1
174.4
205.1
123.2
155.9
188.8
222.1
130.6
165.4
200.4
235.8
136.8
173.3
210.1
247.3
116.8
147
177.2
207.7
133.2
167.7
202.3
237.2
146.2
184.2
222.4
260.8
157
197.9
239
280.5
166.2
209.6
253.2
297.3
122.8
154.3
185.8
217.5
141.2
177.4
213.8
250.3
155.9
196.1
236.4
276.9
168.3
211.8
255.4
299.3
179.1
225.3
271.8
318.6
126.1
158.2
190.5
222.8
145.6
182.7
220
257.5
161.4
202.6
244.1
285.8
174.7
219.5
264.5
309.7
186.3
234.2
282.3
330.6
Based on 60°F entering air temperature, 2.00” maximum pressure drop across the hot water coil.
13
036-21091-004-B-0205
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
1 9 0 .0
CAPACITY (MBH)
1 8 0 .0
1 7 0 .0
140
160
180
200
1 6 0 .0
1 5 0 .0
°F
°F
°F
°F
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
9 0 .0
8 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 2 -
HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 10 GPM
2 7 0 .0
2 6 0 .0
2 5 0 .0
2 4 0 .0
2 3 0 .0
2 2 0 .0
CAPACITY (MBH)
2 1 0 .0
2 0 0 .0
1 9 0 .0
140
160
180
200
1 8 0 .0
1 7 0 .0
°F
°F
°F
°F
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
9 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 3 -
14
HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 20 GPM
Unitary Products Group
036-21091-004-B-0205
2 9 0 .0
2 8 0 .0
2 7 0 .0
2 6 0 .0
2 5 0 .0
2 4 0 .0
2 3 0 .0
CAPACITY (MBH)
2 2 0 .0
2 1 0 .0
140
160
180
200
2 0 0 .0
1 9 0 .0
1 8 0 .0
°F
°F
°F
°F
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 4 -
HOT WATER COIL - 25 & 30 TON, 1 ROW, AT 30 GPM
3 0 0 .0
2 9 0 .0
2 8 0 .0
2 7 0 .0
2 6 0 .0
2 5 0 .0
2 4 0 .0
CAPACITY (MBH)
2 3 0 .0
2 2 0 .0
140
160
180
200
2 1 0 .0
2 0 0 .0
1 9 0 .0
°F
°F
°F
°F
1 8 0 .0
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 5 -
HOT WATER COIL - 25 & 30 TON, 1 ROW AT 40 GPM
Unitary Products Group
15
036-21091-004-B-0205
2 5 0 .0
2 4 0 .0
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
CAPACITY (MBH)
1 9 0 .0
1 8 0 .0
1 7 0 .0
1 6 0 .0
140
160
180
200
°F
°F
°F
°F
140
160
180
200
°F
°F
°F
°F
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
9 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 6 -
HOT WATER COIL - 40 TON, 1 ROW, AT 10 GPM
3 0 0 .0
2 9 0 .0
2 8 0 .0
2 7 0 .0
2 6 0 .0
2 5 0 .0
2 4 0 .0
CAPACITY (MBH)
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
1 9 0 .0
1 8 0 .0
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
1 0 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 7 -
16
HOT WATER COIL - 40 TON, 1 ROW, AT 20 GPM
Unitary Products Group
036-21091-004-B-0205
3 2 0 .0
3 1 0 .0
3 0 0 .0
2 9 0 .0
2 8 0 .0
2 7 0 .0
2 6 0 .0
2 5 0 .0
CAPACITY (MBH)
2 4 0 .0
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
140
160
180
200
°F
°F
°F
°F
140
160
180
200
°F
°F
°F
°F
1 9 0 .0
1 8 0 .0
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
1 1 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 8 -
HOT WATER COIL - 40 TON, 1 ROW, AT 30 GPM
3 4 0 .0
3 3 0 .0
3 2 0 .0
3 1 0 .0
3 0 0 .0
2 9 0 .0
2 8 0 .0
2 7 0 .0
CAPACITY (MBH)
2 6 0 .0
2 5 0 .0
2 4 0 .0
2 3 0 .0
2 2 0 .0
2 1 0 .0
2 0 0 .0
1 9 0 .0
1 8 0 .0
1 7 0 .0
1 6 0 .0
1 5 0 .0
1 4 0 .0
1 3 0 .0
1 2 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 9 -
HOT WATER COIL - 40 TON, 1 ROW, AT 40 GPM
Unitary Products Group
17
036-21091-004-B-0205
PHYSICAL DATA HOT WATER COIL - 2 ROW
TABLE 12: HOT WATER COIL (2 ROW, 25 & 30
TON)1
Coil Casing . . . . . . . . . . . . . . . . . . . . Galvanized Steel
GPM
Coil Construction. . . . . . . . . . . . . . . . Al Fin / Cu. Tube
CFM
6000
8000
10000
12000
15000
6000
8000
10000
12000
15000
Rows Deep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
60
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . .006”
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .016”
Tubes / Circuit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
80
Fins Per Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22.50”
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65”
1.
2
Based on 60°F entering air temperature, 2.00” maximum pressure drop across the hot water coil
Face Area . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.16 ft.
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .90 lbs
TABLE 13: HOT WATER COIL (2 ROWS, 40 TON)1
Operating Weight . . . . . . . . . . . . . . . . . . . . . . . 110 lbs
GPM
TABLE 10: WATER PRESSURE DROP (2 ROW, 25 &
30 TON)
GPM
WATER
20
40
60
80
PRESSURE
DROP
0.9
3.0
6.0
10.0
TABLE 11: STATIC RESISTANCE HOT WATER COIL
(25 & 30 TON)
CFM
AIR PRESSURE DROP
1 ROW
AIR PRESSURE DROP
2 ROW
6000
8000
10000
15000
0.07
0.11
0.16
0.32
0.14
0.23
0.33
0.65
TABLE 12: HOT WATER COIL (2 ROW, 25 & 30
TON)1
20
40
CFM
6000
8000
10000
12000
15000
6000
8000
10000
12000
15000
20
40
60
NOTE: Water pressure drop numbers are based on 60°F
entering air temperature, 2.00” maximum air pressure drop across the hot water coil(s). ARI certified
ratings at covering other conditions are available
upon request. Hot water coils are approved for use
with glycol (rates available upon request.)
GPM
CAPACITY (MBH) AT ENTERING WATER TEMPERATURE
140 °F
160 °F
180 °F
200 °F
206.1
258.7
311.4
364.2
243.6
305.9
368.4
431.1
275.3
345.9
416.8
488.0
302.9
380.7
458.9
537.6
338.4
425.7
513.4
601.7
210.5
263.9
317.4
371.1
249.8
313.3
377.1
441.1
283.3
355.6
428.2
501.0
312.7
392.7
473.0
553.6
351.0
440.9
531.3
622.1
CAPACITY (MBH) AT ENTERING WATER TEMPERATURE
140 °F
160 °F
180 °F
200 °F
177.5
223.8
270.4
317.3
203.8
257.2
311.1
365.5
224.8
284.1
343.9
404.2
242.2
306.4
371.1
436.4
263.6
333.8
404.6
476.1
198.1
248.9
300.0
351.3
232.2
292.0
352.2
412.7
260.7
328.1
395.9
464.1
285.0
359.0
433.4
508.3
316.0
398.4
481.3
564.8
80
1.
CFM
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
8000
11000
14000
17000
20000
CAPACITY (MBH) AT ENTERING WATER
TEMPERATURE
140 °F
160 °F
180 °F
200 °F
203.8
257.2
311.1
365.5
233.9
295.7
358.1
421.0
257.0
325.3
394.2
463.8
275.5
349.0
423.3
498.3
290.9
368.7
447.4
526.9
232.2
292.0
352.2
412.7
273.3
344.1
415.3
487.0
306.3
386.0
466.3
547.1
333.9
421.1
508.9
597.3
357.5
451.1
545.4
640.5
243.6
305.9
368.4
431.1
289.5
363.9
438.5
513.6
327.2
411.5
496.3
581.5
359.2
452.0
545.3
639.2
386.9
487.1
587.9
689.4
249.8
313.3
377.1
441.1
298.5
374.7
451.2
528.1
338.9
425.7
512.8
600.5
373.4
469.3
565.6
662.5
403.6
507.5
611.8
716.8
Based on 60°F entering air temperature, 2.00” maximum air pressure drop across the hot water coil.
ARI certified ratings at other conditions available upon
request.
Hot water coils are approved for use with glycol (ratings
available upon request.)
TABLE 14: STATIC RESISTANCE HOT WATER
COIL (40 TON)
CFM
AIR PRESSURE DROP 1 ROW
AIR PRESSURE DROP 2 ROW
11000
0.19
0.39
14000
0.29
0.58
20000
0.52
1.06
TABLE 15: WATER PRESSURE DROP (2 ROW, 40
TON)
GPM
WATER PRESSURE DROP
18
8000
0.11
0.23
20
0.9
40
3.0
60
6.0
80
10.0
Unitary Products Group
036-21091-004-B-0205
4 8 0 .0
4 6 0 .0
4 4 0 .0
4 2 0 .0
4 0 0 .0
3 8 0 .0
CAPACITY (MBH)
3 6 0 .0
3 4 0 .0
3 2 0 .0
3 0 0 .0
140
160
180
200
°F
°F
°F
°F
140
160
180
200
°F
°F
°F
°F
2 8 0 .0
2 6 0 .0
2 4 0 .0
2 2 0 .0
2 0 0 .0
1 8 0 .0
1 6 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 10 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 20 GPM
5 8 0 .0
5 6 0 .0
5 4 0 .0
5 2 0 .0
5 0 0 .0
4 8 0 .0
4 6 0 .0
CAPACITY (MBH)
4 4 0 .0
4 2 0 .0
4 0 0 .0
3 8 0 .0
3 6 0 .0
3 4 0 .0
3 2 0 .0
3 0 0 .0
2 8 0 .0
2 6 0 .0
2 4 0 .0
2 2 0 .0
2 0 0 .0
1 8 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 11 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 40 GPM
Unitary Products Group
19
036-21091-004-B-0205
6 1 0 .0
5 9 0 .0
5 7 0 .0
5 5 0 .0
5 3 0 .0
5 1 0 .0
4 9 0 .0
CAPACITY (MBH)
4 7 0 .0
4 5 0 .0
4 3 0 .0
4 1 0 .0
3 9 0 .0
3 7 0 .0
140
160
180
200
°F
°F
°F
°F
140
160
180
200
°F
°F
°F
°F
3 5 0 .0
3 3 0 .0
3 1 0 .0
2 9 0 .0
2 7 0 .0
2 5 0 .0
2 3 0 .0
2 1 0 .0
1 9 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 12 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 60 GPM
6 4 0 .0
6 2 0 .0
6 0 0 .0
5 8 0 .0
5 6 0 .0
5 4 0 .0
5 2 0 .0
5 0 0 .0
CAPACITY (MBH)
4 8 0 .0
4 6 0 .0
4 4 0 .0
4 2 0 .0
4 0 0 .0
3 8 0 .0
3 6 0 .0
3 4 0 .0
3 2 0 .0
3 0 0 .0
2 8 0 .0
2 6 0 .0
2 4 0 .0
2 2 0 .0
2 0 0 .0
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 13 - HOT WATER COIL - 25 & 30 TON, 2 ROW, AT 80 GPM
20
Unitary Products Group
036-21091-004-B-0205
5 3 0 .0
5 1 0 .0
4 9 0 .0
4 7 0 .0
4 5 0 .0
4 3 0 .0
CAPACITY (MBH)
4 1 0 .0
3 9 0 .0
3 7 0 .0
3 5 0 .0
140
160
180
200
°F
°F
°F
°F
140
160
180
200
°F
°F
°F
°F
3 3 0 .0
3 1 0 .0
2 9 0 .0
2 7 0 .0
2 5 0 .0
2 3 0 .0
2 1 0 .0
1 9 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 14 - HOT WATER COIL - 40 TON, 2 ROW, AT 20 GPM
6 5 0 .0
6 3 0 .0
6 1 0 .0
5 9 0 .0
5 7 0 .0
5 5 0 .0
5 3 0 .0
5 1 0 .0
CAPACITY (MBH)
4 9 0 .0
4 7 0 .0
4 5 0 .0
4 3 0 .0
4 1 0 .0
3 9 0 .0
3 7 0 .0
3 5 0 .0
3 3 0 .0
3 1 0 .0
2 9 0 .0
2 7 0 .0
2 5 0 .0
2 3 0 .0
2 1 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 15 - HOT WATER COIL - 40 TON, 2 ROW, AT 40 GPM
Unitary Products Group
21
036-21091-004-B-0205
7 0 0 .0
6 8 0 .0
6 6 0 .0
6 4 0 .0
6 2 0 .0
6 0 0 .0
5 8 0 .0
5 6 0 .0
5 4 0 .0
CAPACITY (MBH)
5 2 0 .0
5 0 0 .0
4 8 0 .0
4 6 0 .0
4 4 0 .0
140
160
180
200
°F
°F
°F
°F
140
160
180
200
°F
°F
°F
°F
4 2 0 .0
4 0 0 .0
3 8 0 .0
3 6 0 .0
3 4 0 .0
3 2 0 .0
3 0 0 .0
2 8 0 .0
2 6 0 .0
2 4 0 .0
2 2 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 16 - HOT WATER COIL - 40 TON, 2 ROW, AT 60 GPM
7 3 0 .0
7 1 0 .0
6 9 0 .0
6 7 0 .0
6 5 0 .0
6 3 0 .0
6 1 0 .0
5 9 0 .0
5 7 0 .0
CAPACITY (MBH)
5 5 0 .0
5 3 0 .0
5 1 0 .0
4 9 0 .0
4 7 0 .0
4 5 0 .0
4 3 0 .0
4 1 0 .0
3 9 0 .0
3 7 0 .0
3 5 0 .0
3 3 0 .0
3 1 0 .0
2 9 0 .0
2 7 0 .0
2 5 0 .0
2 3 0 .0
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 17 - HOT WATER COIL - 40 TON, 2 ROW, AT 80 GPM
22
Unitary Products Group
036-21091-004-B-0205
STEAM HEATING
TABLE 18: STEAM COIL (1 ROW, 40 TON)1
The YORK Millennium units (25, 30, and 40 ton sizes) can be
manufactured with a steam heat coil (Bottom Supply only).
YORK's one row steam coil is installed in the heating section
just downstream of the supply air fan and just above the supply air opening in the bottom of the unit.
The steam control valve will not be provided. The installer
will need to field supply a steam control valve. Connect the
steam piping and valve power wiring at the job site for the
steam heat section to be operational.
There are no provisions in the coil or control sequence to prevent freezing of condensate. The control valve, piping and
field installed wiring connections are particularly vulnerable
because they are installed in the vestibule outside of the conditioned air stream.
All piping, control valves, and wiring that is field installed must
conform to all local and national codes
Condensate can freeze on the control valve and piping if they
are not properly insulated.
PHYSICAL DATA STEAM COIL - 1 ROW
Coil Casing . . . . . . . . . . . . . . . . . . . . Galvanized Steel
Coil Construction . . . . . . . . . . . . . . . Al Fin / Cu. Tube
Rows Deep . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
Fin Thickness . . . . . . . . . . . . . . . . . . . . . . . . . . . ..010”
Tube Wall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ..035”
Tubes / Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2
Fins Per Inch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6
Tubes High . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21”
Tube Length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65”
Face Area . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9.48 ft.2
Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92 lbs.
CAPACITY (MBH) AT STEAM PRESSURE (PSI)
2
6
10
15
221.1
236.9
250.4
265.0
252.9
271.0
286.4
303.1
278.2
298.0
315.0
333.4
299.4
320.7
339.0
358.8
317.6
340.2
359.6
380.6
CFM
8000
11000
14000
17000
20000
1.
Based on 60°F entering air temperature, 2.00” maximum air pressure drop across the coil.
TABLE 19: STATIC RESISTANCE STEAM COIL
(1 ROW, 40 TON)
CFM
AIR PRESSURE DROP
17000
0.67
20000
0.88
T O P V IE W
C O N D E N S IN G
S E C T IO N
S T E A M
C O IL
2 6 "
O U T L E T (1 1 /2 ")
1 5 .8 "
TABLE 16: STEAM COIL (1 ROW, 25 & 30 TON)1
1.
14000
0.48
The steam piping must enter the unit through the floor of the
heat section compartment. The access doors to the compartment are gasketed to the compartment can be sealed. However, as added protection for condensate leakage into the
space, the piping access holes should be sealed with a heat
resistant mastic. The following figure illustrates the approximate location of the compartment and piping connections.
*Hot water, steam coil or electric heat not available for front or
rear supply.
6000
8000
10000
12000
15000
11000
0.31
PIPING CONNECTIONS
IN L E T (2 ")
8 "
CFM
8000
0.18
CAPACITY (MBH) AT STEAM PRESSURE (PSI)
2
6
10
15
194.1
207.9
219.8
232.6
221.1
236.9
250.4
265.0
243.2
260.5
275.4
291.4
261.9
280.6
296.6
313.9
285.6
306.0
323.5
342.4
Based on 60°F entering air temperature, 2.00” maximum air pressure drop across the coil.
2 .5 5 "
9 "
H E A T S E C T IO N
C O M P A R T M E N T
O U T S ID E O F
B A S E R A IL
8 .3 8 "
8 8 .7 5 "
CL
FIGURE 18 - STEAM PIPING CROSS SECTION
DO NOT use tin based solder. Brazing with tin
based solder could cause equipment damage or
possible injury to OCCUPANTS of the structure that
is being conditioned.
TABLE 17: STATIC RESISTANCE STEAM COIL
(1 ROW, 25 & 30 TON)
CFM
AIR PRESSURE DROP
Unitary Products Group
6000
0.11
8000
0.18
10000
0.26
12000
0.36
15000
0.54
23
036-21091-004-B-0205
350
340
330
320
310
300
CAPACITY (MBH)
290
280
2 psi
6 psi
10 psi
15 psi
270
260
250
240
230
220
210
200
190
180
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
F L O W R A T E (C F M )
FIGURE 19 - STEAM COIL - 25 & 30 TON, 1 ROW
390
380
370
360
350
340
CAPACITY (MBH)
330
320
310
2 psi
6 psi
10 psi
15 psi
300
290
280
270
260
250
240
230
220
210
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
F L O W R A T E (C F M )
FIGURE 20 - STEAM COIL - 40 TON, 1 ROW
24
Unitary Products Group
036-21091-004-B-0205
TABLE 20: EXHAUST FAN DRIVE DATA
MODEL
25 TON
30 TON
40 TON
BLOWER
RPM
RANGE
HP
FRAME
SIZE
732
827
955
852
976
1069
852
976
1069
5
7.5
10
7.5
10
15
7.5
10
15
213T
215T
215T
213T
215T
254T
184T
215T
254T
MOTOR
MOTOR EFF
(STD.
MOTOR)
87.5
88.5
89.5
84
86.5
85.7
84
86.5
85.7
MOTOR PULLEY
MOTOR
EFF (HI
EFF OPT)
89.5
91.7
91
86.5
89.5
89.5
86.5
89.5
89.5
BLOWER PULLEY
BELTS
PITCH DIA
(INCHES)
BORE
(INCHES)
PITCH DIA
(INCHES)
BORE
(INCHES)
DESIGNATION
QTY
4.9
5.5
6.3
5.5
6.3
6.9
5.5
6.3
6.5
1-3/8
1-3/8
1-5/8
1-3/8
1-3/8
1-3/8
1-3/8
1-3/8
1-3/8
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
11.3
2-3/16
2-3/16
2-3/16
1-11/16
1-11/16
1-11/16
1-11/16
1-11/16
1-11/16
BX63
BX63
BX63
B65
B65
B65
B65
B65
B65
2
2
2
2
2
2
2
2
2
TABLE 21: SUPPLY FAN MOTOR AND DRIVE DATA1
MOTOR
MODEL
25 Ton
30 Ton
40 Ton
1.
BLOWER
RPM
RANGE
HP
567
692
793
894
617
743
844
919
567
642
717
768
7.5
10
15
20
10
15
20
25
10
15
20
25
FRAM
SIZE
MOTOR
EFFICIENCY
(STD. MOTOR)
213t
215T
254T
256T
215T
254T
256T
284T
215T
254T
256T
284T
88.5
89.5
91
91
89.5
91
91
91.7
89.5
91
91
91.7
E
MOTOR PULLEY
BLOWER PULLEY
BELTS
MOTOR
EFFICIENCY
(ULTRA HI
EFF OPT)
PITCH DIA
(INCHES)
BORE
(INCHES)
PITCH DIA
(INCHES)
BORE
(INCHES)
DESIGNA
91.7
91
91.7
93
91
91.7
93
93.6
91
91.7
93
93.6
4.5
5.5
6.3
7.1
4.9
5.9
6.7
7.1
4.5
5.1
5.7
6.1
1-3/8
1-3/8
1-5/8
1-5/8
1-3/8
1-5/8
1-5/8
1-7/8
1-3/8
1-5/8
1-5/8
1-7/8
13.9
13.9
13.9
13.9
13.9
13.9
13.7
13.7
13.9
13.7
13.7
13.7
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-3/16
2-7/16
2-7/16
2-7/16
2-7/16
BX56
BX56
BX56
BX56
BX56
BX56
5VX610
5VX610
BX67
5VX710
5VX710
5VX710
TION
QTY
2
2
2
2
2
2
2
2
2
2
2
2
kW = (BHP X 0.746) / Motor Eff.
MBH = kW X 3.414
MBH = (BHP X 2.546) / Motor Eff.
Unitary Products Group
25
036-21091-004-B-0205
SUPPLY AIR DRIVE ADJUSTMENT
At unit start-up, the measured CFM may be higher or lower
than the specified CFM shown in Figures 22, 23, and 24. To
achieve the specified CFM, the speed of the drive may have
to be decreased or increased by changing the pitch diameter
(PD) of the motor sheave as outlined below:
Even small changes in blower speed can result in
substantial changes in static pressure and bhp.
Bhp or amp draw of the blower motor will increase
(see table) by the cube ratio of the blower speed.
Static pressure will increase by the square ratio of
the blower speed. Tables 22, 23 and 24 are for
reference only. All blower speed changes must be
made by qualified personnel with strict adherence
to the fan laws.
Example:
Failure to properly adjust the total system air quantity can result in extensive blower damage.
Before making any blower speed changes review
the installation for any installation errors, leaks or
undesirable systems effects that can result in loss
of air flow.
A 30-ton unit was selected to deliver 12,000 CFM with a 20
HP motor and a 966 RPM drive, but the unit is only delivering
11,000 CFM per Figures 22, 23, and 24.
Use the equation to determine the required PD for the new
motor sheave (12,000 CFM / 11,000 CFM) x 6.9” = 7.53”
Use the 30-ton table to select a Browning 2B5V74 which will
increase the speed of the unit's drive and its supply air CFM
108.7%.
New drive speed = 1.087 x 966 = 1,050 RPM
New supply air
= 1.087 x 11,000 = 11,957 CFM
Re-use the existing belts and blower sheave.
New motor BHP = (speed increase)3 x estimated motor
BHP at original start-up with 11,000 CFM and 966 RPM =
(1.087)3 x 13.5 BHP = 1.284 x 13.5 BHP = 17.3 BHP
New motor amps = (speed increase)3 x measured motor
amps at original start-up with 11,000 CFM and 966 RPM.
26
Unitary Products Group
036-21091-004-B-0205
TABLE 22: 25 TON DRIVE ADJUSTMENT
7.5 HP MOTOR & 567 RPM DRIVE
10 HP MOTOR & 692 RPM DRIVE
15 HP MOTOR & 793 RPM DRIVE
20 HP MOTOR & 894 RPM DRIVE
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
%RPM
& CFM
REQ’D
PD
BROWNING
2B5V_ _
-
-
-
82
4.5
42
84
5.3
50
86
6.1
58
-
-
-
86
4.7
44
87
5.5
52
89
6.3
60
100
(Std.)4.5
42
89
4.9
46
90
5.7
54
91
6.5
62
104
4.7
44
93
5.1
48
94
5.9
56
94
6.7
64
109
4.9
46
96
5.3
50
97
6.1
58
97
6.9
66
113
5.1
48
100
(Std.)5.5
52
100
(Std)6.3
60
100
(Std.)7.1
68
118
5.3
50
104
5.7
54
103
6.5
62
103
7.3
70
122
5.5
52
107
5.9
56
106
6.7
64
108
7.7
74
126
5.7
54
111
6.1
58
110
6.9
66
117
8.3
80
-
-
-
115
6.3
60
113
7.1
68
125
8.9
86
-
-
-
118
6.5
62
116
7.3
70
-
-
-
-
-
-
122
6.7
64
122
7.7
74
-
-
-
TABLE 23: 30 TON DRIVE ADJUSTMENT
10 HP MOTOR & 617 RPM DRIVE
BROWNING
%RPM
REQ’D
2B5V_ _
PD
& CFM
91.8
4.5
42
95.9
4.7
44
(Std.)
46
100.0
4.9
104.1
5.1
48
108.2
5.3
50
15 HP MOTOR & 743 RPM DRIVE
%RPM
REQ’D
BROWNING
& CFM
2B5V_ _
PD
86.4
5.1
48
89.8
5.3
50
20 HP MOTOR & 856 RPM DRIVE
%RPM
REQ’D
BROWNING
& CFM
2B5V_ _
PD
82.1
5.5
54
85.1
5.7
56
“25 HP MOTOR & 933 RPM DRIVE”
%RPM
REQ’D
BROWNING
& CFM
2B5V_ _
PD
86.3
6.1
60
89.0
6.3
62
93.2
5.5
52
88.1
5.9
58
91.8
6.5
64
96.6
5.7
(Std.)
5.9
54
91.0
6.1
60
94.5
6.7
66
56
94.0
6.3
62
97.3
6.9
68
(Std.)
7.1
70
100.0
112.2
5.5
52
103.4
6.1
58
97.0
116.3
5.7
54
106.8
6.3
60
100.0
120.4
124.5
-
5.9
6.1
-
56
58
-
110.2
113.6
116.9
120.3
123.7
6.5
6.7
6.9
7.1
7.3
62
64
66
68
70
103.0
106.0
109.0
114.9
123.9
6.5
64
100.0
(Std.)
6.7
6.9
7.1
7.5
8.1
8.7
66
105.5
7.5
74
68
70
74
80
86
113.7
121.9
-
8.1
8.7
-
80
86
-
TABLE 24: 40 TON DRIVE ADJUSTMENT
10 HP MOTOR & 667 RPM DRIVE
%RPM
REQ’D
BROWNING
2B5V_ _
& CFM
PD
100.0
4.5
42
104.4
4.7
44
(Std.)
108.9
46
4.9
15 HP MOTOR & 768 RPM DRIVE
% RPM
REQ’D
BROWNING
& CFM
2B5V_ _
PD
88.2
4.5
44
92.1
4.7
46
96.0
4.9
20 HP MOTOR & 830 RPM DRIVE
%RPM
REQ’D
BROWNING
& CFM
PD
2B5V_ _
82.5
4.7
46
86.0
4.9
48
25 HP MOTOR & 881 RPM DRIVE
%RPM
REQ’D
BROWNING
2B5V_ _
& CFM
PD
83.7
5.1
50
86.9
5.3
52
48
89.5
5.1
50
90.2
5.5
54
50
93.0
5.3
52
93.4
5.7
56
5.9
(Std.)
6.1
6.3
6.5
6.7
6.9
7.1
7.5
58
117.8
5.3
50
103.9
(Std.)
5.1
5.3
52
96.5
5.5
54
96.7
122.2
5.5
52
107.8
5.5
54
100.0
5.7
56
100.0
126.7
-
5.7
-
54
-
111.7
115.6
119.5
123.4
127.4
-
5.7
5.9
6.1
6.3
6.5
-
56
58
60
62
64
66
103.5
107.0
110.5
114.0
117.5
121.1
5.9
6.1
6.3
6.5
6.7
6.9
58
60
62
64
66
68
103.3
106.6
109.8
113.1
116.4
119.7
113.3
5.1
Unitary Products Group
48
100.0
60
62
64
66
68
70
74
27
036-21091-004-B-0205
TABLE 25: DRIVE ADJUSTMENT FOR POWER EXHAUST - 25 TON
5 HP MOTOR & 732 RPM DRIVE
%RPM
REQ’D
BROWNING
& CFM
PD
2B5V_ _
100
4.9
46
104
5.1
48
109
5.3
50
113
5.5
52
117
5.7
54
122
5.9
56
7.5 HP MOTOR & 827 RPM DRIVE
%RPM
REQ’D
BROWNING
2B5V_ _
& CFM
PD
92
5.1
48
96
5.3
50
100
5.5
52
104
5.7
54
108
5.9
56
112
6.1
58
10 HP MOTOR & 955 RPM DRIVE
BROWNING
%RPM
REQ’D PD
2B5V_ _
& CFM
93
5.9
56
97
6.1
58
100
6.3
60
103
6.5
62
107
6.7
64
110
6.9
66
TABLE 26: DRIVE ADJUSTMENT FOR POWER EXHAUST - 30 & 40 TON
7.5 HP MOTOR & 852 RPM DRIVE
% RPM
REQ’D
BROWNING
& CFM
PD (IN)
2B5V_ _
96.4
5.3
52
100.0
(Std.) 5.5
54
103.6
5.7
56
107.3
5.9
58
110.9
6.1
60
114.5
6.3
62
28
10 HP MOTOR & 976 RPM DRIVE
% RPM
REQ’D
BROWNING
& CFM
PD (IN)
2B5V_ _
93.7
5.9
58
96.8
6.1
60
100.0
(Std.) 6.3
62
103.2
6.5
64
106.3
6.7
66
109.5
6.9
68
15 HP MOTOR & 1069 RPM DRIVE
% RPM
REQ’D
BROWNING
& CFM
PD (IN)
2B5V_ _
94.2
6.5
64
97.1
6.7
66
100.0
(Std.) 6.9
68
102.9
7.1
70
108.7
7.5
74
117.4
8.1
80
Unitary Products Group
036-21091-004-B-0205
TABLE 27: COOLING PERFORMANCE - 25 TON STANDARD CAPACITY COIL
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
Unitary Products Group
25.8
25.5
25.0
24.6
24.4
26.0
25.7
25.2
24.8
24.6
26.1
25.8
25.3
25.0
24.9
26.2
25.9
25.5
25.2
25.1
26.3
26.1
25.6
25.3
25.2
26.4
26.1
25.7
25.5
25.4
26.5
26.2
25.8
25.6
25.5
26.5
26.2
25.9
25.7
25.6
90
TOT SEN
350 208
335 229
310 263
299 299
299 299
360 223
345 247
323 288
317 317
317 317
368 237
353 264
332 310
333 333
332 332
375 251
360 281
341 333
345 345
345 345
380 264
367 300
356 356
356 356
356 356
384 277
372 315
366 366
366 366
366 366
388 290
377 331
374 374
374 374
374 374
391 303
381 345
382 382
381 381
381 381
86
TOT SEN
348 181
333 203
309 238
288 272
288 288
358 193
343 217
319 257
300 297
305 305
366 203
351 230
329 277
320 320
319 319
372 213
358 243
336 295
332 332
332 332
377 223
363 256
342 312
342 342
342 342
382 232
367 268
347 328
351 351
351 351
385 241
371 280
353 346
359 359
359 359
388 250
374 291
366 366
366 366
366 366
85 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
346 160 344 139 341 118
----332 183 330 162 328 141 325 120
308 217 307 198 306 179 304 159
286 253 284 232 283 213 282 194
279 279 272 272 263 247 261 227
356 170 354 145 350 120
----342 195 340 172 338 148 334 123
318 235 317 211 315 191 313 167
297 275 294 251 293 229 291 207
296 296 287 287 274 268 272 246
364 179 361 151 357 123
----350 205 348 181 345 154 341 126
326 251 325 224 323 200 320 175
306 295 304 270 300 244 299 219
310 310 300 300 291 291 280 263
370 186 367 157 363 126
----356 215 353 188 351 160 347 128
332 265 331 236 329 209 326 182
321 321 311 287 307 258 305 230
321 321 311 311 301 301 287 280
375 193 372 163 367 128
----361 225 358 195 356 165 351 131
337 279 336 247 334 218 331 188
331 331 317 304 314 273 310 241
331 331 321 321 311 311 301 301
379 199 376 167 371 130
----365 234 362 201 359 169 355 133
344 296 341 258 338 226 335 193
340 340 329 329 318 286 314 251
340 340 329 329 318 318 308 308
383 205 379 171 373 133
----369 243 366 208 363 173 358 135
348 309 344 269 341 234 338 199
348 348 336 336 322 298 317 261
347 347 336 336 325 325 314 314
385 211 382 175 377 135
----372 252 369 214 365 176 360 137
352 321 347 279 344 242 341 204
354 354 343 343 326 310 320 271
354 354 342 342 331 331 320 320
71
TOT SEN
--------302 138
280 175
260 207
--------311 143
290 185
269 223
--------318 148
297 194
276 237
--------323 153
303 202
284 252
--------328 158
308 210
289 264
--------332 162
312 218
294 276
--------335 165
315 225
299 289
--------337 167
318 232
303 299
68
TOT SEN
--------299 116
279 154
258 188
--------308 118
288 163
268 200
--------315 120
295 169
275 212
--------319 121
301 175
281 222
--------324 123
306 180
285 232
--------327 124
309 185
289 242
--------330 125
312 190
293 251
--------330 126
315 194
297 262
29
036-21091-004-B-0205
TABLE 27: COOLING PERFORMANCE - 25 TON STANDARD CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
30
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
28.4
28.1
27.6
27.2
27.0
28.6
28.3
27.8
27.4
27.2
28.7
28.5
27.9
27.6
27.5
28.9
28.6
28.1
27.8
27.7
28.9
28.7
28.2
28.0
27.9
29.1
28.8
28.3
28.1
28.0
29.2
28.8
28.4
28.2
28.1
29.2
28.9
28.5
28.3
28.3
90
TOT SEN
337 202
322 223
300 259
291 291
290 290
347 217
332 241
311
282
308 308
308 308
354 232
340 259
320 304
322 322
322 322
360 245
346 276
334 334
334 334
334 334
365 259
353 294
345 345
345 345
344 344
369 271
358 309
354 354
353 353
353 353
372 284
362 324
361 361
361 361
361 361
375 296
365 339
368 368
368 368
368 368
86
TOT SEN
335 176
321 197
298 232
278 266
279 279
345 188
330
211
307 251
296 296
296 296
352 198
338 225
316 271
309 309
309 309
357 208
344 237
323 289
321 321
321 321
362 217
348 250
329 306
331 331
330 330
366 226
352 262
335 324
339 339
339 339
369 235
356 274
347 347
346 346
346 346
372 244
358 285
353 353
353 353
353 353
95 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
333 155 331 134 328
113
----320 178 318 157 315 136 313
115
297 212 296 192 294 174 293 154
276 247 274 227 273 208 272 189
271 271 263 263 254 242 252 222
342 165 340 140 336
116
----329 189 327 167 324 143 321
118
306 229 305 205 303 184 302 163
286 269 284 247 282 223 281 201
287 287 278 278 265 263 262 241
350 174 347 146 343
118
----336 200 334 175 331 149 328 121
313 244 312 218 310 194 308 169
295 290 292 264 289 238 288 213
300 300 291 291 281 281 270 257
355 181 352 152 348 121
----342 210 339 183 337 155 333 123
319 259 318 230 316 203 314 176
311
311
299 281 296 254 293 224
311
311
301 301 291 291 277 273
359 187 356 158 352 123
----346 219 344 189 341 160 337 126
326 276 323 241 320 212 318 181
320 320 305 298 301 267 298 235
320 320 310 310 300 300 290 290
363 194 360 162 355 126
----350 228 348 195 344 163 340 128
331 289 327 252 324 220 321 188
328 328 318 318 306 280 301 245
328 328 318 318 307 307 297 297
367 200 363 166 358 128
----354 237 351 201 347 167 343 130
335 302 330 263 327 228 325 192
335 335 324 324 310 292 305 255
335 335 324 324 314 314 303 303
369 206 366 169 360 130
----356 246 354 207 350 171 345 133
338 315 333 274 330 236 327 198
341 341 330 330 314 305 309 267
341 341 330 330 319 319 308 308
71
TOT SEN
--------290 133
271 171
251 203
--------299 138
279 179
259 218
--------306 143
286 188
266 232
--------311
148
291 196
273 246
--------315 152
296 204
278 258
--------318 156
299 212
282 270
--------321 159
302 219
287 282
--------324 161
305 226
298 298
68
TOT SEN
--------288
112
269 149
250 184
--------296
113
277 157
258 196
--------302
115
284 163
265 207
--------307
116
289 169
270 217
--------310
118
293 174
274 227
--------314
119
296 179
278 236
--------316 120
299 184
283 247
--------318 121
302 188
286 256
Unitary Products Group
036-21091-004-B-0205
TABLE 27: COOLING PERFORMANCE - 25 TON STANDARD CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
Unitary Products Group
31.5
31.2
30.6
30.2
30.0
31.7
31.4
30.8
30.4
30.2
31.9
31.6
31.0
30.6
30.4
32.0
31.7
31.2
30.8
30.7
32.1
31.8
31.3
31.0
30.9
32.2
31.8
31.4
31.1
31.0
32.2
31.9
31.5
31.3
31.2
32.2
31.9
31.6
31.4
31.3
90
TOT SEN
323 197
309 217
288 253
281 281
281 281
332 212
318 235
299 276
297 297
297 297
339 226
325 253
307 299
311
311
311
311
344 239
332 271
323 323
322 322
322 322
349 253
338 287
332 332
332 332
332 332
352 266
342 302
341 341
340 340
340 340
355 278
346 317
348 348
348 348
348 348
361 294
351 335
354 354
354 354
354 354
86
TOT SEN
321 171
308 192
286 226
268 261
270 270
330 182
317 206
294 245
286 286
286 286
337 192
323 219
303 264
298 298
298 298
342 202
329 232
310 283
309 309
309 309
346
211
333 244
315 299
319 319
318 318
350 221
337 256
321 316
326 326
326 326
353 229
340 267
333 333
333 333
333 333
355 238
344 282
339 339
339 339
339 339
105 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
319 150 317 129 314 108
----307 173 305 152 302 131 300
110
285 207 284 188 282 170 281 149
266 242 263 222 262 203 261 183
263 263 255 255 245 236 243 218
328 160 325 135 322
111
----315 184 313 162
311
138 307
113
294 223 293 201 291 180 289 157
275 263 273 241 271 218 270 196
277 277 269 269 261 261 252 235
334 168 331 141 327
113
----322 194 320 169 317 144 313
116
300 238 299 213 297 189 295 164
289 289 281 258 277 232 276 208
289 289 280 280 271 271 259 251
340 175 336 147 332
116
----327 204 325 176 322 150 318
118
307 255 305 223 302 197 300 170
299 299 287 275 284 248 281 218
299 299 290 290 281 281 272 272
344 181 340 152 336
118
----331 213 329 183 326 154 321 120
312 269 309 235 306 205 304 175
308 308 298 298 289 261 285 229
308 308 298 298 288 288 279 279
347 187 343 156 339 121
----335 222 332 189 327 157 324 123
316 282 312 246 310 214 307 181
316 316 305 305 293 273 288 239
316 316 305 305 295 295 285 285
350 194 346 160 340 122
----337 231 335 195 330 161 327 125
320 295 315 256 313 222 310 186
322 322 312 312 297 288 293 251
322 322 312 312 301 301 291 291
353 200 349 163 343 125
----340 240 336 200 333 164 328 127
324
311
320 269 315 229 312 191
328 328 317 317 301 297 296 260
328 328 317 317 307 307 296 296
71
TOT SEN
--------278 128
260 164
241 197
--------286 133
268 173
249 212
--------292 138
274 183
257 227
--------297 143
279 191
262 240
--------301 147
283 197
267 252
--------304 150
286 205
271 264
--------305 152
289 212
281 281
--------307 154
291 219
286 286
68
TOT SEN
--------276 106
258 144
240 178
--------283 108
266 152
248 190
--------289
110
272 158
254 200
--------293
111
277 163
259
211
--------296
112
280 168
263 221
--------298
113
284 172
266 230
--------301
115
286 177
270 240
--------303
116
289 181
273 249
31
036-21091-004-B-0205
TABLE 28: COOLING PERFORMANCE - 30 TON STANDARD CAPACITY COIL
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
32
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
31.0
30.6
30.0
29.4
28.9
31.2
30.9
30.2
29.7
29.4
31.4
31.1
30.4
29.9
29.7
31.6
31.2
30.6
30.1
30.0
31.7
31.4
30.7
30.2
30.2
31.8
31.5
30.8
30.3
30.4
31.9
31.5
30.9
30.6
30.6
32.0
31.6
31.0
30.7
30.7
32.1
31.7
31.1
30.9
30.9
32.1
31.7
31.2
31.0
31.0
TOT
388
371
342
318
318
400
382
355
339
338
409
392
366
356
355
417
399
373
370
370
422
405
382
383
382
427
411
394
394
393
431
416
404
403
403
434
420
412
411
411
437
424
419
419
418
441
427
426
425
425
90
SEN
222
244
280
316
318
239
265
307
339
338
256
285
334
356
355
273
306
359
370
370
290
326
380
383
382
307
346
394
394
393
322
363
404
403
403
336
378
412
411
411
350
394
419
419
418
364
411
426
425
425
TOT
387
370
341
316
306
399
382
353
329
326
408
391
362
342
342
415
398
371
356
356
421
404
378
368
367
425
408
383
378
378
429
412
388
387
387
432
416
393
395
395
435
419
403
402
402
438
422
409
408
408
86
SEN
195
217
254
289
306
208
234
276
318
326
220
250
298
342
342
233
266
320
356
356
245
281
339
368
367
258
297
358
378
378
270
311
377
387
387
281
324
392
395
395
291
337
403
402
402
301
350
409
408
408
85 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
386 174 384 154 382 133
----369 197 368 177 366 157 364 136
341 234 340 214 339 194 338 174
314 269 313 249 313 229 312 209
298 298 290 283 289 263 287 243
397 184 396 160 393 136
----381 210 379 187 378 163 375 139
353 253 352 230 351 206 350 183
327 294 325 271 324 248 324 224
316 316 307 307 301 288 299 264
406 193 404 166 401 138
----390 223 388 196 386 169 383 141
362 271 361 245 360 218 358 191
337 319 335 292 333 265 332 239
332 332 322 322 312 312 308 285
413 202 411 172 408 140
----397 236 395 205 393 175 390 143
369 290 368 260 367 230 365 199
345 341 343 312 340 283 339 253
345 345 335 335 324 324 316 304
419 211 416 177 413 143
----402 248 401 214 398 180 395 146
375 308 374 275 372 241 371 207
357 357 350 331 347 300 345 267
357 357 346 346 335 335 323 321
423 221 421 183 417 145
----407 260 405 223 403 186 399 148
381 324 379 289 377 253 375 216
367 367 355 348 352 315 350 280
366 366 355 355 344 344 333 333
427 230 425 189 420 147
----411 273 409 232 407 192 403 150
385 339 383 302 381 263 379 223
375 375 364 364 357 329 354 291
375 375 363 363 352 352 340 340
430 239 428 195 423 150
----414 283 412 241 410 197 406 153
390 354 386 314 384 272 382 231
383 383 371 371 361 342 357 302
383 383 371 371 359 359 347 347
433 246 431 200 426 152
----417 293 415 249 412 203 408 155
393 368 390 326 387 281 385 237
390 390 377 377 364 355 361 314
389 389 377 377 365 365 353 353
436 254 433 206 428 154
----420 302 418 256 415 209 410 157
396 383 393 337 390 290 388 243
396 396 383 383 368 366 364 324
395 395 383 383 370 370 358 358
TOT
----337
312
287
----348
323
298
----356
331
306
----363
338
314
----368
344
320
----373
348
325
----376
352
330
----380
356
333
----382
359
341
----385
361
346
71
SEN
----153
189
223
----159
201
241
----164
212
258
----169
223
275
----173
234
290
----178
244
304
----183
253
317
----187
261
329
----192
269
341
----196
277
346
TOT
----335
311
286
----346
322
297
----354
330
305
----360
337
312
----365
342
318
----369
347
322
----372
350
326
----375
353
330
----378
356
333
----380
359
336
68
SEN
----133
169
203
----135
177
218
----136
185
232
----138
193
245
----139
200
258
----140
207
269
----141
214
280
----142
220
291
----143
226
300
----145
231
310
Unitary Products Group
036-21091-004-B-0205
TABLE 28: COOLING PERFORMANCE - 30 TON STANDARD CAPACITY COIL ((CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
Unitary Products Group
34.5
34
33.3
32.7
32.2
34.7
34.3
33.6
33
32.6
34.9
34.5
33.8
33.2
32.9
35.1
34.6
34
33.4
33.2
35.2
34.8
34.1
33.5
33.6
35.3
34.9
34.2
33.7
33.8
35.4
35
34.3
34
34
35.5
35
34.4
34.2
34.2
35.6
35.1
34.5
34.3
34.3
35.6
35.2
34.6
34.5
34.5
TOT
373
356
329
308
308
384
367
341
327
327
392
376
351
344
343
399
382
359
357
357
404
389
369
369
369
408
394
380
379
379
412
399
389
388
388
415
402
397
396
396
419
406
404
403
403
422
409
410
409
409
90
SEN
216
238
274
308
308
233
259
301
327
327
250
279
328
344
343
267
300
352
357
357
284
320
369
369
369
301
340
380
379
379
316
356
389
388
388
330
372
397
396
396
345
389
404
403
403
357
402
410
409
409
95°F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
86
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN TOT SEN
372 189 371 169 369 148 367 128
----355 211 354 191 353 171 352 151 350 130
328 248 327 228 327 208 326 188 325 168
303 283 302 263 301 243 300 223 300 203
296 296 288 288 279 277 278 257 276 237
383 202 381 178 379 154 377 130
----366 228 365 204 364 181 362 157 360 133
339 270 338 247 338 223 337 200 335 176
316 312 314 288 312 264 311 241 310 218
314 314 305 305 296 296 288 282 287 258
391 214 389 187 387 160 384 132
----375 244 373 217 372 190 370 163 367 135
348 292 347 265 346 239 345 212 343 185
330 330 322 312 321 286 319 259 318 232
330 330 320 320 310 310 301 301 295 279
397 227 396 196 393 166 390 135
----381 260 380 230 378 199 376 168 373 137
356 314 353 283 352 254 351 223 349 193
343 343 333 333 329 306 325 276 325 247
343 343 333 333 322 322 312 312 302 297
403 239 401 206 398 171 395 137
----387 276 385 242 383 208 381 174 378 140
362 334 359 302 358 268 356 235 355 201
355 355 344 344 334 325 332 293 330 260
354 354 343 343 333 333 322 322 312 312
407 252 405 215 402 177 398 139
----391 291 389 254 388 217 385 180 381 142
367 352 365 318 362 283 361 246 359 209
364 364 353 353 342 342 337 308 334 273
364 364 353 353 342 342 331 331 319 319
411 264 409 224 406 183 402 141
----394 305 393 267 391 226 389 186 385 144
372 367 369 333 366 295 364 257 362 217
373 373 361 361 350 350 342 321 338 284
372 372 361 361 349 349 338 338 327 327
414 275 412 233 409 189 404 144
----397 318 396 277 394 235 391 191 387 146
381 381 373 347 369 306 367 266 365 225
380 380 368 368 357 357 345 334 342 296
380 380 368 368 356 356 344 344 333 333
416 285 414 241 411 194 407 146
----401 332 399 287 397 243 394 197 390 149
387 387 375 361 373 319 370 274 368 231
387 387 375 375 363 363 349 345 345 306
386 386 374 374 362 362 350 350 338 338
419 295 417 248 413 200 409 148
----404 343 401 296 399 250 396 203 392 151
393 393 379 372 375 330 373 284 370 237
393 393 380 380 368 368 356 356 348 316
392 392 380 380 367 367 355 355 343 343
71
TOT
----323
299
275
----333
309
285
----341
317
293
----347
324
300
----352
329
306
----356
333
311
----359
337
315
----362
340
322
----365
342
327
----367
345
331
SEN
----147
183
217
----153
195
235
----158
206
252
----162
216
269
----167
227
283
----172
237
296
----176
246
308
----181
254
322
----185
262
327
----190
270
331
68
TOT
----321
298
275
----331
308
285
----338
316
292
----344
322
298
----349
327
303
----352
331
308
----355
334
312
----358
337
315
----359
340
318
----362
342
321
SEN
----126
163
197
----128
171
211
----130
179
225
----131
186
238
----132
193
251
----134
200
262
----135
207
273
----136
213
283
----137
218
292
----138
223
302
33
036-21091-004-B-0205
TABLE 28: COOLING PERFORMANCE - 30 TON STANDARD CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
34
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
38.5
38
37.2
36.5
36
38.8
38.2
37.4
36.8
36.4
39
38.5
37.7
37
36.9
39.2
38.7
37.8
37.2
37.1
39.3
38.9
37.9
37.4
37.3
39.4
39
38.1
37.7
37.6
39.5
39.1
38.2
37.8
37.8
39.6
39.2
38.3
38
38
39.7
39.2
38.4
38.1
38.1
39.7
39.3
38.4
38.3
38.3
TOT
357
341
315
297
297
367
351
327
316
315
374
359
335
331
330
380
365
344
343
343
385
371
356
355
354
389
376
365
365
364
393
381
373
373
373
397
383
381
380
380
400
387
387
387
386
403
394
392
392
391
90
SEN
210
232
268
297
297
227
253
295
316
315
244
273
321
331
330
261
293
344
343
343
278
314
356
355
354
295
333
365
365
364
309
350
373
373
373
324
366
381
380
380
338
379
387
387
386
350
394
392
392
391
TOT
356
340
314
291
286
366
350
324
303
303
373
357
333
318
317
379
364
340
330
329
384
369
345
340
340
388
373
351
349
349
391
376
358
357
357
394
379
365
365
364
397
382
371
371
370
399
385
377
376
376
86
SEN
183
205
241
277
286
196
222
263
303
303
208
238
286
318
317
221
254
307
330
329
233
269
326
340
340
246
285
345
349
349
257
299
358
357
357
267
311
365
365
364
279
323
371
371
370
288
335
377
376
376
105 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
355 163 353 142 351 122
----339 185 338 165 337 145 335 124
313 222 313 202 312 182 311 161
289 257 288 236 287 217 287 197
277 277 269 269 266 251 264 231
364 172 363 148 360 124
----349 198 348 175 346 151 344 127
323 240 322 217 322 194 320 170
300 282 298 258 297 235 296 212
294 294 285 285 276 275 274 252
372 181 370 154 367 126
----356 211 355 184 353 157 350 129
331 259 330 232 329 205 328 178
309 306 307 279 305 252 304 226
308 308 298 298 289 289 282 272
377 191 375 160 372 129
----362 223 361 193 359 162 356 131
337 277 336 247 335 217 333 187
320 320 314 299 311 270 310 240
319 319 309 309 300 300 290 290
382 200 380 166 376 131
----367 236 365 202 363 168 360 134
343 295 341 262 340 228 338 195
330 330 319 316 317 286 314 254
329 329 319 319 309 309 299 299
386 209 384 171 380 133
----371 248 369 211 367 174 363 136
348 311 345 276 344 240 342 203
339 339 328 328 321 300 318 265
338 338 327 327 317 317 306 306
389 218 387 177 383 136
----374 259 372 220 370 179 366 138
352 326 348 287 347 249 345 211
346 346 335 335 326 314 322 277
346 346 334 334 323 323 312 312
392 226 389 183 384 138
----377 269 375 227 373 185 369 140
355 340 352 300 350 259 348 218
353 353 341 341 329 326 326 288
352 352 341 341 329 329 318 318
394 233 392 188 386 140
----379 279 378 234 375 191 370 142
359 351 355 312 352 268 350 224
359 359 347 347 336 336 329 299
358 358 346 346 335 335 323 323
396 240 393 193 388 142
----382 288 380 241 377 195 372 145
365 365 358 323 354 277 352 230
364 364 352 352 340 340 331 309
364 364 351 351 340 340 328 328
TOT
----309
286
263
----319
295
272
----326
303
280
----331
308
287
----336
313
292
----339
317
296
----342
320
302
----345
323
307
----347
325
312
----349
327
316
71
SEN
----141
177
211
----146
188
228
----151
199
245
----156
210
262
----161
220
276
----165
230
288
----170
239
302
----174
247
307
----179
255
312
----183
262
316
TOT
----307
285
263
----316
294
272
----323
301
279
----328
307
284
----332
311
289
----335
315
293
----338
318
297
----340
321
300
----342
323
303
----344
325
305
68
SEN
----120
157
191
----122
165
205
----123
172
218
----125
179
232
----126
187
244
----127
194
255
----128
200
265
----129
206
275
----130
211
284
----132
216
293
Unitary Products Group
036-21091-004-B-0205
TABLE 28: COOLING PERFORMANCE - 30 TON STANDARD CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
Unitary Products Group
43
42.5
41.7
40.7
40.3
43.3
42.8
41.8
41
40.8
43.5
42.8
42
41.3
41.2
43.7
43
42.2
41.5
41.6
43.7
43.2
42.3
41.9
41.9
43.8
43.5
42.5
42.2
42
43.9
43.6
42.6
42.2
42.2
44.2
43.7
42.9
42.4
42.4
44.2
43.8
43
42.6
42.6
44.3
43.8
43.1
42.7
42.7
TOT
341
325
301
286
286
350
334
312
303
303
356
341
320
318
317
362
348
330
329
329
367
353
341
340
339
370
357
349
349
348
374
362
357
357
356
378
365
364
363
363
380
371
370
369
369
383
376
375
375
374
90
SEN
204
226
262
286
286
221
246
289
303
303
238
267
315
318
317
255
288
330
329
329
272
308
341
340
339
289
324
349
349
348
305
342
357
357
356
318
358
364
363
363
331
371
370
369
369
344
376
375
375
374
TOT
339
324
299
277
275
348
333
309
291
291
355
340
317
305
305
360
345
323
317
316
365
350
329
326
326
368
353
335
334
334
372
357
343
342
341
374
361
349
348
348
377
364
354
354
353
379
366
359
359
359
86
SEN
177
199
235
270
275
190
215
257
291
291
202
231
279
305
305
215
247
300
317
316
228
263
320
326
326
240
278
335
334
334
253
292
343
342
341
263
305
349
348
348
272
317
354
354
353
282
329
359
359
359
115 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
338 157 337 136 334 116
----323 179 322 159 321 138 319 118
299 215 298 195 297 175 296 155
276 250 274 230 274 210 273 190
266 266 258 258 253 244 252 224
347 166 345 142 343 118
----332 192 331 168 329 144 327 120
308 234 307 211 306 187 305 164
286 275 284 252 282 228 282 205
282 282 273 273 265 265 261 245
354 175 352 148 349 120
----339 205 338 178 336 150 333 123
314 252 314 226 313 199 311 172
296 296 292 273 290 246 289 219
295 295 286 286 276 276 268 264
359 185 357 154 353 123
----344 217 343 187 341 156 338 125
321 271 319 240 318 210 316 180
307 307 298 292 296 262 294 233
306 306 296 296 287 287 277 277
363 194 361 160 357 125
----349 230 347 196 345 162 341 127
326 289 324 255 322 222 321 188
316 316 306 306 301 277 298 245
315 315 305 305 295 295 285 285
367 203 364 165 360 127
----353 242 351 205 348 168 345 130
331 304 327 269 326 233 324 196
324 324 314 314 304 291 302 257
323 323 313 313 303 303 292 292
370 212 367 171 363 130
----355 252 354 214 351 173 347 132
334 318 331 281 329 241 327 204
331 331 320 320 309 304 305 268
330 330 319 319 309 309 298 298
372 220 369 177 365 132
----358 264 356 221 353 179 349 134
338 332 334 291 331 250 330 210
337 337 326 326 315 315 308 278
336 336 325 325 314 314 304 304
374 227 371 182 367 134
----360 274 358 228 355 184 351 136
343 343 337 302 334 261 331 215
342 342 331 331 320 320 311 288
342 342 330 330 319 319 308 308
376 233 373 187 368 137
----363 283 360 234 357 188 353 139
348 348 339 313 335 268 333 221
347 347 335 335 324 324 313 300
347 347 335 335 323 323 312 312
TOT
----295
272
250
----303
281
259
----309
287
266
----314
293
272
----318
297
276
----321
300
282
----324
303
288
----326
306
293
----328
308
297
----330
310
301
71
SEN
----135
170
204
----140
182
221
----145
192
239
----149
203
254
----154
213
267
----159
223
282
----163
231
288
----168
239
293
----172
247
297
----176
255
301
TOT
----293
271
250
----301
280
258
----306
286
265
----311
291
270
----315
295
274
----317
298
278
----320
301
281
----321
304
284
----322
306
287
----324
308
289
68
SEN
----114
150
184
----115
158
198
----117
165
212
----118
173
225
----119
180
235
----120
186
247
----122
191
256
----122
197
267
----123
203
276
----124
208
283
35
036-21091-004-B-0205
TABLE 29: COOLING PERFORMANCE - 30 TON HIGH CAPACITY COIL
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
36
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
31.4
31.0
30.4
29.8
29.2
31.7
31.3
30.6
30.0
29.5
31.9
31.5
30.9
30.3
29.8
32.1
31.7
31.0
30.4
30.1
32.2
31.8
31.1
30.6
30.4
32.3
32.0
31.2
30.7
30.6
32.4
32.0
31.3
30.9
30.8
32.5
32.1
31.4
31.0
31.0
32.5
32.2
31.5
31.2
31.2
32.6
32.3
31.6
31.3
31.3
TOT
404
385
355
328
324
417
398
369
346
346
426
408
380
364
364
434
416
389
380
380
440
423
397
394
393
445
429
406
405
405
450
434
416
416
415
454
438
425
425
424
458
442
433
433
432
461
446
441
440
440
90
SEN
228
250
286
321
324
245
271
313
346
346
262
291
340
364
364
279
312
367
380
380
296
332
393
394
393
313
353
406
405
405
330
373
416
416
415
347
394
425
425
424
364
413
433
433
432
381
430
441
440
440
TOT
403
385
354
327
312
416
397
367
340
333
425
407
378
351
350
433
415
387
366
365
439
421
393
378
378
444
426
399
390
389
448
431
405
399
399
451
434
411
408
408
454
438
416
416
415
457
441
423
422
422
86
SEN
201
224
260
295
312
214
240
282
323
333
227
256
304
351
350
239
272
327
366
365
251
288
348
378
378
264
304
370
390
389
276
319
392
399
399
289
335
409
408
408
301
351
416
416
415
313
367
423
422
422
85°F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
402 181 401 161 400 140
----384 204 383 184 382 163 381 143
354 240 354 220 353 200 353 180
326 275 325 255 325 235 325 216
303 303 299 288 299 269 298 249
415 190 413 167 411
143
----397 217 396 193 395 170 393 146
367 259 367 236 366 213 365 189
340 300 338 277 337 254 337 231
323 323 314 314 311
293
311
271
424 200 422 172 420 145
----406 229 405 203 404 175 402 148
377 278 376 251 375 225 374 198
349 325 348 299 347 272 347 246
340 340 330 330 323 318 321 292
431 209 429 178 427 147
----414 242 413 212 411
181 408 150
385 296 384 266 383 236 382 206
359 350 357 320 355 290 354 260
354 354 344 344 333 333 328 312
437 218 435 184 432 149
----420 254 418 221 416 187 413 152
392 315 390 281 389 248 388 214
367 367 363 341 362 307 360 274
367 367 356 356 345 345 336 332
442 227 440 189 436 151
----425 267 423 230 421 192 418 155
397 333 395 296 394 259 392 222
378 378 370 362 368 325 366 288
377 377 366 366 354 354 343 343
446 236 443 195 439 153
----429 279 427 239 425 198 421 157
402 351 400 311
398 270 396 230
387 387 376 376 372 342 370 302
387 387 375 375 363 363 351 351
449 245 447 200 442 156
----432 291 431 248 428 204 424 159
406 369 404 326 401 282 400 238
396 396 383 383 377 357 374 315
395 395 383 383 371 371 358 358
452 254 451 206 445 158
----435 304 433 257 431 209 426 161
410 386 407 340 404 293 403 246
403 403 390 390 381 372 378 329
402 402 390 390 377 377 365 365
455 263 453 212 446 160
----438 316 436 266 433 215 428 163
414 400 410 354 407 304 405 254
409 409 397 397 385 385 381 340
409 409 396 396 383 383 371 371
TOT
----352
324
298
----364
337
310
----373
346
319
----380
353
327
----386
359
334
----390
364
339
----394
368
344
----397
372
349
----399
375
353
----402
377
358
71
SEN
----160
196
229
----166
208
247
----171
219
265
----176
230
282
----180
240
299
----185
251
315
----189
261
329
----194
272
343
----198
282
353
----203
292
358
TOT
----350
324
298
----362
336
309
----371
345
318
----377
352
326
----382
358
332
----386
363
337
----390
366
341
----393
370
345
----395
373
349
----393
375
351
68
SEN
----140
176
210
----142
184
224
----143
192
238
----145
200
252
----146
207
265
----147
214
278
----148
221
291
----149
228
304
----150
235
315
----150
241
326
Unitary Products Group
036-21091-004-B-0205
TABLE 29: COOLING PERFORMANCE - 30 TON HIGH CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
Unitary Products Group
34.9
34.5
33.8
33
32.4
35.2
34.8
34.1
33.4
32.8
35.4
35
34.3
33.6
33.1
35.5
35.2
34.5
33.8
33.5
35.7
35.3
34.6
34
33.8
35.8
35.5
34.7
34.1
34.1
36
35.5
34.8
34.3
34.3
36
35.6
34.9
34.5
34.5
36.1
35.7
34.9
34.7
34.6
36.2
35.8
35
34.8
34.8
TOT
388
369
341
313
313
399
381
354
334
334
408
390
363
352
351
415
399
373
367
366
421
405
379
379
379
426
411
391
391
390
431
414
401
400
400
434
419
409
409
408
438
423
417
416
416
440
427
424
423
423
90
SEN
221
244
280
313
313
239
264
307
334
334
256
285
333
352
351
273
306
360
367
366
290
326
379
379
379
307
347
391
391
390
324
367
401
400
400
341
387
409
409
408
358
406
417
416
416
375
422
424
423
423
TOT
387
369
340
314
302
398
381
352
326
321
407
390
362
338
338
414
397
370
352
352
420
402
376
365
364
424
407
382
375
375
428
412
388
384
384
431
415
393
392
392
434
418
400
400
399
436
421
406
406
405
86
SEN
195
217
253
288
302
208
234
276
317
321
220
250
298
338
338
233
265
320
352
352
245
281
341
365
364
258
297
363
375
375
270
313
384
384
384
282
329
393
392
392
295
345
400
400
399
307
361
406
406
405
95°F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
386 175 385 154 383 134
----369 197 368 177 367 157 365 136
340 233 340 214 339 194 338 174
313 268 312 248 312 229 312 209
293 293 288 282 287 262 286 243
397 184 396 160 394 136
----380 210 379 187 378 163 376 139
351 252 351 229 351 206 350 183
325 294 324 270 323 247 323 224
312 312 303 303 299 287 298 264
406 193 404 166 402 138
----389 223 388 196 386 169 384 141
360 271 360 245 359 218 358 191
335 319 334 292 332 265 332 239
328 328 318 318 308 308 307 285
413 202
411
172 408 141
----396 235 395 205 393 175 390 144
368 290 367 260 366 230 365 199
341 341 341 313 340 283 338 253
341 341 331 331 320 320 315 305
418
211
416 177 412 143
----401 248 400 214 398 180 395 146
374 308 372 274 372 241 370 207
354 354 348 334 346 300 344 267
353 353 342 342 331 331 321 321
422 220 420 183 416 145
----406 260 404 223 402 186 399 148
380 326 378 289 376 252 375 215
364 364 355 353 351 318 349 281
363 363 352 352 341 341 329 329
426 229 423 189 419 147
----410 273 408 232 406 191 402 150
384 344 382 304 380 264 378 223
372 372 361 361 356 334 353 294
372 372 360 360 349 349 337 337
429 238 426 194 422 149
----413 285
411
241 409 197 404 152
388 363 386 319 383 275 381 231
380 380 368 368 360 348 357 308
380 380 368 368 356 356 344 344
432 248 429 200 424 151
----416 297 414 250
411
203 406 154
392 378 389 333 386 286 384 239
387 387 375 375 364 362 360 320
387 387 374 374 362 362 350 350
434 257 431 206 426 154
----418 310 416 259 413 208 407 156
396 391 392 347 388 297 386 247
393 393 380 380 368 368 363 332
393 393 380 380 368 368 355 355
TOT
----338
311
286
----348
322
297
----357
331
306
----363
338
313
----368
343
319
----372
347
324
----376
351
329
----378
354
332
----380
357
338
----383
360
343
71
SEN
----154
189
223
----159
201
241
----164
212
258
----169
223
275
----173
233
291
----178
244
307
----183
254
322
----187
264
332
----191
274
338
----196
284
343
TOT
----336
310
285
----347
321
296
----354
330
305
----360
336
311
----365
342
317
----368
346
322
----371
350
326
----372
353
329
----374
355
332
----377
357
335
68
SEN
----133
169
203
----135
178
218
----137
185
231
----138
193
245
----139
200
258
----140
207
271
----141
214
284
----141
221
295
----142
227
306
----144
234
316
37
036-21091-004-B-0205
TABLE 29: COOLING PERFORMANCE - 30 TON HIGH CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
38
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
38.9
38.4
37.5
36.7
36.1
39.2
38.7
37.9
37.1
36.7
39.5
39
38.2
37.3
37.1
39.6
39.2
38.2
37.5
37.3
39.8
39.3
38.5
37.9
37.6
39.9
39.4
38.7
37.9
37.9
40
39.5
38.8
38.2
38.1
40.3
39.9
38.9
38.4
38.4
39.9
40
39
38.6
38.6
40.2
40.1
39.1
38.8
38.8
TOT
371
353
326
302
302
381
364
338
322
322
390
373
347
338
338
396
380
353
352
352
401
386
365
365
364
406
391
376
375
375
411
395
385
384
384
414
400
393
392
392
417
404
400
399
399
419
407
406
406
405
90
SEN
215
237
273
302
302
232
258
300
322
322
249
279
327
338
338
267
299
352
352
352
283
320
365
365
364
301
340
376
375
375
318
360
385
384
384
335
381
393
392
392
352
398
400
399
399
369
407
406
406
405
TOT
370
353
325
299
291
381
364
337
310
309
389
372
346
325
325
395
378
353
338
338
400
383
359
350
349
404
388
365
360
360
408
392
369
369
368
411
396
377
376
376
413
399
383
383
382
415
401
389
389
388
86
SEN
188
211
247
281
291
201
227
269
309
309
214
243
291
325
325
226
259
313
338
338
239
275
335
350
349
251
291
357
360
360
264
307
369
369
368
276
322
377
376
376
289
338
383
383
382
301
354
389
389
388
105°F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
369 168 368 148 366 127
----353 191 352 171 351 150 349 130
325 227 325 207 324 187 324 167
299 262 299 242 298 222 298 202
282 282 274 274 274 256 274 236
380 178 378 154 376 130
----363 204 362 180 361 156 359 132
336 246 335 223 335 199 334 176
310 286 310 264 309 240 308 217
300 300 291 291 286 280 284 257
387 187 386 160 383 132
----371 216 370 189 368 162 366 135
344 264 343 238 343
211
342 184
320 312 319 285 317 258 316 232
315 315 306 306 296 296 292 277
393 196 391 165 388 134
----377 229 376 199 374 168 371 137
351 283 350 253 349 223 348 192
328 328 325 306 324 276 322 246
328 328 317 317 308 308 300 298
398 205 396 171 393 136
----382 241 381 208 379 174 375 139
357 301 355 267 354 234 352 200
339 339 332 327 329 293 328 260
339 339 328 328 317 317 307 307
402 214 400 177 396 138
----386 254 385 217 383 179 377 141
362 319 360 282 358 245 356 208
348 348 337 337 334 310 332 274
348 348 337 337 326 326 315 315
405 223 403 182 398 141
----390 266 388 226 386 185 382 143
366 337 364 297 361 257 360 216
357 357 346 346 339 326 336 287
356 356 345 345 333 333 322 322
408 232 405 188 401 143
----393 278 391 235 388 190 384 145
370 354 367 312 364 268 363 224
364 364 352 352 343 341 340 301
364 364 352 352 340 340 328 328
411
241 406 193 402 145
----396 291 393 244 390 196 385 147
374 369 370 326 367 279 364 232
371 371 359 359 347 347 342 313
370 370 358 358 346 346 334 334
413 250 410 199 402 147
----398 303 395 252 393 202 388 150
377 377 373 339 370 291 366 239
376 376 364 364 352 352 345 324
376 376 364 364 351 351 339 339
TOT
----323
297
273
----332
308
283
----340
315
291
----346
322
298
----350
327
303
----354
331
308
----357
334
311
----359
337
317
----361
339
322
----362
342
327
71
SEN
----147
182
216
----152
194
234
----157
205
251
----162
216
268
----166
226
284
----171
237
299
----175
247
311
----180
257
317
----184
267
322
----188
278
327
TOT
----321
297
273
----330
307
283
----337
314
290
----342
320
296
----347
325
302
----347
329
306
----352
332
310
----353
335
313
----355
337
316
----358
339
319
68
SEN
----126
162
196
----128
171
211
----129
178
224
----131
185
237
----132
193
251
----132
200
264
----134
206
276
----134
213
287
----135
220
299
----137
227
309
Unitary Products Group
036-21091-004-B-0205
TABLE 29: COOLING PERFORMANCE - 30 TON HIGH CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
Unitary Products Group
43.5
42.9
41.9
41.2
40.3
43.8
43.3
42.4
41.5
41
44
43.5
42.6
41.8
41.4
44.1
43.7
42.8
42
41.8
44.4
43.9
43
42.4
42.2
44.5
44
43.1
42.5
42.3
44.6
44.1
43.3
42.5
42.5
44.5
44.2
43.4
42.8
42.7
44.8
44.3
43.5
43.1
43.1
45.1
44.3
43.4
43.3
43.3
TOT
353
337
311
291
291
363
347
321
309
309
370
355
331
325
325
377
361
338
338
337
381
367
350
349
349
386
371
359
359
358
389
376
368
367
367
393
380
375
375
374
395
383
382
382
381
398
388
388
387
387
90
SEN
209
231
266
291
291
226
251
293
309
309
243
272
320
325
325
260
293
338
338
337
277
313
350
349
349
294
333
359
359
358
311
354
368
367
367
328
374
375
375
374
345
383
382
382
381
362
388
388
387
387
TOT
353
336
310
286
280
362
346
321
297
297
370
354
329
312
312
375
359
335
324
324
380
364
341
335
334
383
369
345
344
344
386
372
353
352
352
389
375
360
359
359
392
378
366
366
365
394
381
371
371
371
86
SEN
182
204
240
274
280
195
220
262
297
297
207
236
284
312
312
220
252
306
324
324
232
268
328
335
334
245
284
345
344
344
257
300
353
352
352
270
316
360
359
359
282
332
366
366
365
295
347
371
371
371
115°F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (°F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
352 162 350 141 348 121
----336 184 335 164 334 144 332 123
310 220 309 200 309 180 308 160
285 255 284 235 284 215 284 195
271 271 263 263 261 248 260 229
361 171 360 147 357 123
----345 197 344 173 343 150 341 126
319 239 319 216 318 192 317 169
295 280 294 257 293 233 293 210
288 288 279 279 270 270 270 250
368 180 366 153 363 125
----353 210 352 183 350 155 347 128
327 258 326 231 325 204 324 177
303 303 302 277 301 251 300 224
302 302 293 293 283 283 278 270
374 189 371 159 368 128
----359 222 357 192 355 161 352 130
334 276 332 246 331 216 330 185
314 314 309 299 308 269 306 238
314 314 304 304 294 294 284 284
378 199 376 164 372 130
----363 235 362 201 359 167 356 132
339 294 337 260 336 227 334 193
324 324 314 314 312 286 311 252
324 324 314 314 303 303 293 293
382 208 379 170 374 132
----367 247 365 210 363 172 359 134
343 312 341 275 339 238 338 201
333 333 322 322 317 303 315 266
333 333 322 322 311
311 301 301
385 217 382 176 376 134
----370 259 368 219 366 178 360 136
347 331 345 290 342 250 341 209
341 341 329 329 322 318 319 280
340 340 329 329 318 318 307 307
387 226 384 181 380 136
----373 272 371 228 368 184 363 139
352 347 348 305 345 261 343 217
347 347 336 336 325 325 321 293
347 347 335 335 324 324 313 313
389 235 386 187 381 139
----375 284 373 237 370 189 366 141
354 354 351 319 348 272 345 225
354 354 342 342 330 330 324 305
353 353 341 341 330 330 318 318
390 244 387 193 390 143
----378 297 375 246 372 195 355 139
359 359 354 332 350 283 347 233
359 359 347 347 335 335 327 315
358 358 346 346 334 334 323 323
TOT
----307
283
260
----316
292
269
----323
299
277
----328
305
282
----332
309
288
----335
313
293
----338
316
296
----340
319
302
----342
321
307
----344
324
311
71
SEN
----140
175
209
----145
187
227
----150
198
244
----155
208
260
----159
219
277
----164
229
291
----168
239
296
----173
250
302
----177
260
307
----182
270
311
TOT
----305
282
259
----314
291
268
----320
298
275
----324
304
281
----326
308
286
----330
311
290
----332
314
293
----336
317
296
----314
319
299
----333
320
302
68
SEN
----119
155
189
----121
163
203
----122
171
217
----123
178
230
----124
185
243
----125
192
256
----126
199
267
----128
206
280
----120
213
290
----128
219
298
39
036-21091-004-B-0205
TABLE 30: COOLING PERFORMANCE - 40 TON STANDARD CAPACITY COIL
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
40
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
31.4
31.0
30.4
29.8
29.2
31.7
31.3
30.6
30.0
29.5
31.9
31.5
30.9
30.3
29.8
32.1
31.7
31.0
30.4
30.1
32.2
31.8
31.1
30.6
30.4
32.3
32.0
31.2
30.7
30.6
32.4
32.0
31.3
30.9
30.8
32.5
32.1
31.4
31.0
31.0
32.5
32.2
31.5
31.2
31.2
32.6
32.3
31.6
31.3
31.3
TOT
404
385
355
328
324
417
398
369
346
346
426
408
380
364
364
434
416
389
380
380
440
423
397
394
393
445
429
406
405
405
450
434
416
416
415
454
438
425
425
424
458
442
433
433
432
461
446
441
440
440
90
SEN
228
250
286
321
324
245
271
313
346
346
262
291
340
364
364
279
312
367
380
380
296
332
393
394
393
313
353
406
405
405
330
373
416
416
415
347
394
425
425
424
364
413
433
433
432
381
430
441
440
440
TOT
403
385
354
327
312
416
397
367
340
333
425
407
378
351
350
433
415
387
366
365
439
421
393
378
378
444
426
399
390
389
448
431
405
399
399
451
434
411
408
408
454
438
416
416
415
457
441
423
422
422
86
SEN
201
224
260
295
312
214
240
282
323
333
227
256
304
351
350
239
272
327
366
365
251
288
348
378
378
264
304
370
390
389
276
319
392
399
399
289
335
409
408
408
301
351
416
416
415
313
367
423
422
422
85 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
402 181 401 161 400 140
----384 204 383 184 382 163 381 143
354 240 354 220 353 200 353 180
326 275 325 255 325 235 325 216
303 303 299 288 299 269 298 249
415 190 413 167 411 143
----397 217 396 193 395 170 393 146
367 259 367 236 366 213 365 189
340 300 338 277 337 254 337 231
323 323 314 314 311 293 311 271
424 200 422 172 420 145
----406 229 405 203 404 175 402 148
377 278 376 251 375 225 374 198
349 325 348 299 347 272 347 246
340 340 330 330 323 318 321 292
431 209 429 178 427 147
----414 242 413 212 411 181 408 150
385 296 384 266 383 236 382 206
359 350 357 320 355 290 354 260
354 354 344 344 333 333 328 312
437 218 435 184 432 149
----420 254 418 221 416 187 413 152
392 315 390 281 389 248 388 214
367 367 363 341 362 307 360 274
367 367 356 356 345 345 336 332
442 227 440 189 436 151
----425 267 423 230 421 192 418 155
397 333 395 296 394 259 392 222
378 378 370 362 368 325 366 288
377 377 366 366 354 354 343 343
446 236 443 195 439 153
----429 279 427 239 425 198 421 157
402 351 400 311 398 270 396 230
387 387 376 376 372 342 370 302
387 387 375 375 363 363 351 351
449 245 447 200 442 156
----432 291 431 248 428 204 424 159
406 369 404 326 401 282 400 238
396 396 383 383 377 357 374 315
395 395 383 383 371 371 358 358
452 254 451 206 445 158
----435 304 433 257 431 209 426 161
410 386 407 340 404 293 403 246
403 403 390 390 381 372 378 329
402 402 390 390 377 377 365 365
455 263 453 212 446 160
----438 316 436 266 433 215 428 163
414 400 410 354 407 304 405 254
409 409 397 397 385 385 381 340
409 409 396 396 383 383 371 371
TOT
----352
324
298
----364
337
310
----373
346
319
----380
353
327
----386
359
334
----390
364
339
----394
368
344
----397
372
349
----399
375
353
----402
377
358
71
SEN
----160
196
229
----166
208
247
----171
219
265
----176
230
282
----180
240
299
----185
251
315
----189
261
329
----194
272
343
----198
282
353
----203
292
358
TOT
----350
324
298
----362
336
309
----371
345
318
----377
352
326
----382
358
332
----386
363
337
----390
366
341
----393
370
345
----395
373
349
----393
375
351
68
SEN
----140
176
210
----142
184
224
----143
192
238
----145
200
252
----146
207
265
----147
214
278
----148
221
291
----149
228
304
----150
235
315
----150
241
326
Unitary Products Group
036-21091-004-B-0205
TABLE 30: COOLING PERFORMANCE - 40 TON STANDARD CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
Unitary Products Group
48.8
48.1
47.1
46
45.2
49.1
48.5
47.5
46.3
45.7
49.3
48.7
47.7
46.6
46.2
49.5
48.9
47.7
46.8
46.4
49.6
49.1
47.9
47
46.7
49.7
49.3
48.1
47.2
47.1
49.9
49.4
48.2
47.5
47.4
50
49.5
48.3
47.7
47.6
50.1
49.6
48.4
47.9
47.9
50.2
49.7
48.5
48.1
48.1
50.4
49.8
48.7
48.3
48.2
50.5
49.9
48.8
48.4
48.4
50.5
49.9
48.8
48.6
48.6
TOT
513
489
451
418
418
524
501
464
439
438
534
511
475
457
456
542
519
483
472
472
549
526
492
487
486
555
532
500
499
499
560
538
511
510
510
564
543
521
521
520
568
547
530
530
529
572
551
539
538
537
575
555
546
546
545
578
559
553
553
552
581
563
560
559
559
90
SEN
294
323
371
418
418
311
344
398
439
438
328
364
425
457
456
345
385
451
472
472
362
405
476
487
486
379
426
498
499
499
396
446
511
510
510
413
465
521
521
520
430
482
530
530
529
445
499
539
538
537
458
515
546
546
545
472
529
553
553
552
485
546
560
559
559
TOT
511
488
450
416
402
523
500
463
428
422
533
510
473
439
438
540
518
482
454
454
547
524
489
468
467
553
530
496
480
479
558
535
500
490
490
562
539
506
500
499
566
543
511
509
508
569
547
517
517
516
572
550
525
524
523
575
554
531
531
530
577
556
537
537
536
86
SEN
258
288
336
383
402
271
304
358
411
422
283
320
381
439
438
296
336
403
454
454
308
352
425
468
467
321
368
446
480
479
333
384
463
490
490
346
400
481
500
499
358
415
499
509
508
371
429
517
517
516
382
440
525
524
523
392
455
531
531
530
402
466
537
537
536
95 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
510 231 509 204 506 176
----487 261 486 234 485 207 483 180
450 310 449 283 448 257 447 230
414 356 414 330 413 304 412 277
391 391 381 375 381 349 379 322
522 240 520 210 517 179
----499 274 498 244 496 213 493 183
461 329 461 299 460 269 459 239
427 382 425 352 425 322 424 292
410 410 398 398 391 372 391 343
531 250 529 216 526 181
----509 287 507 253 505 219 502 185
472 347 470 314 469 281 468 247
437 407 436 373 434 340 433 307
426 426 413 413 402 397 400 364
539 259 536 221 533 183
----516 299 515 262 513 225 509 187
480 366 479 329 477 293 475 256
446 431 444 394 442 358 441 321
440 440 427 427 414 414 407 383
545 268 543 227 539 186
----523 312 521 272 519 231 515 190
487 384 485 344 484 304 482 264
454 451 452 415 449 375 448 335
453 453 439 439 425 425 415 403
551 277 548 233 544 188
----529 325 527 281 524 237 520 192
493 403 491 359 489 316 487 272
465 465 457 434 455 393 453 349
465 465 451 451 436 436 422 418
555 286 552 238 548 190
----534 337 531 290 529 242 524 194
499 421 496 374 494 327 492 280
476 476 463 449 461 409 458 363
475 475 460 460 445 445 431 431
559 295 556 244 552 192
----538 349 536 299 533 248 528 196
503 437 500 389 499 338 496 288
485 485 469 465 466 423 462 376
484 484 469 469 454 454 439 439
563 304 560 250 555 195
----542 362 539 308 536 254 532 199
508 452 504 402 502 350 500 296
493 493 478 478 469 435 467 388
493 493 477 477 462 462 447 447
566 313 563 255 558 197
----545 374 542 317 539 259 535 201
511
467 508 415 506 360 503 304
501 501 485 485 473 448 470 399
500 500 484 484 469 469 453 453
569 322 566 261 560 199
----548 385 545 326 542 265 537 203
514 479
511
426 509 369 506 310
508 508 492 492 477 461 474 410
507 507 491 491 475 475 459 459
572 331 568 267 562 201
----551 395 548 333 544 270 539 205
518 494 514 437
511
379 509 318
514 514 498 498 481 474 477 421
513 513 497 497 481 481 465 465
574 337 570 273 564 204
----553 404 550 340 547 276 541 207
522 507 517 449 514 387
511
322
520 520 503 503 487 487 479 431
519 519 503 503 486 486 470 470
TOT
----446
412
378
----457
423
389
----466
432
399
----473
440
407
----479
446
414
----485
452
419
----489
457
425
----493
461
429
----497
464
433
----499
468
437
----502
471
444
----505
473
449
----507
476
454
71
SEN
----203
251
296
----208
262
313
----213
274
331
----218
284
348
----223
295
365
----228
306
381
----232
316
395
----237
327
407
----242
337
420
----246
345
431
----251
353
444
----255
362
449
----260
370
454
TOT
----444
411
378
----455
422
389
----463
430
398
----470
438
405
----476
444
412
----481
450
417
----484
454
422
----488
458
426
----491
462
430
----492
465
434
----496
468
437
----498
470
440
----501
473
442
68
SEN
----175
224
269
----177
232
284
----179
240
298
----181
248
311
----182
255
324
----183
262
338
----184
269
350
----185
276
362
----186
283
372
----187
290
383
----188
297
393
----189
302
403
----191
307
411
41
036-21091-004-B-0205
TABLE 30: COOLING PERFORMANCE - 40 TON STANDARD CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
42
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
54.3
53.7
52.4
51.3
50.4
54.7
54
52.7
51.6
50.9
55
54.3
53
51.9
51.5
55.2
54.5
53.2
52.1
51.9
55.4
54.7
53.6
52.4
52.1
55.5
54.9
53.8
52.8
52.4
55.7
55
53.9
52.8
52.7
55.8
55.1
54
53.2
52.9
55.9
55.2
53.9
53.4
53.2
56
55.3
54.3
53.4
53.4
56.1
55.4
54.4
53.6
53.6
56.1
55.5
54.5
53.8
53.8
56.2
55.6
54.5
54.2
54.1
TOT
491
468
433
403
403
502
480
444
423
423
510
488
454
440
439
518
495
463
454
454
524
502
471
468
467
529
508
481
480
479
533
513
491
490
489
537
518
501
500
500
542
522
509
509
508
545
526
517
517
516
548
530
524
524
523
551
533
531
530
530
554
537
537
536
536
90
SEN
285
315
363
403
403
303
336
390
423
423
320
356
416
440
439
337
376
443
454
454
354
397
467
468
467
371
417
481
480
479
388
438
491
490
489
404
455
501
500
500
421
473
509
509
508
435
488
517
517
516
449
504
524
524
523
462
521
531
530
530
476
533
537
536
536
TOT
489
467
431
397
388
500
478
442
409
407
509
487
452
423
423
516
494
460
437
436
522
500
466
449
449
527
505
472
461
460
532
510
478
471
470
535
514
483
480
479
539
518
489
488
487
542
521
496
496
495
545
524
503
502
502
547
527
509
509
508
550
530
515
514
514
86
SEN
250
279
328
373
388
262
296
350
403
407
275
312
372
423
423
288
328
394
437
436
300
344
416
449
449
313
359
437
461
460
325
375
455
471
470
338
391
472
480
479
350
406
489
488
487
363
418
496
496
495
374
431
503
502
502
384
444
509
509
508
394
456
515
514
514
105 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
488 223 487 196 484 168
----466 253 465 226 464 199 461 171
431 301 430 275 429 248 428 221
397 348 396 321 395 295 395 268
377 377 365 365 364 340 363 313
499 232 497 202 494 171
----477 266 476 235 474 205 471 174
442 320 441 290 440 260 438 230
409 373 407 343 406 313 405 283
395 395 382 382 374 364 373 334
507 241 505 207 502 173
----486 278 484 245 482
211
479 176
450 339 449 305 448 272 447 238
417 397 416 364 414 331 413 298
410 410 398 398 385 385 382 355
514 251 512 213 508 175
----493 291 491 254 489 217 486 179
458 357 457 320 455 284 454 247
426 422 424 385 422 349 421 312
424 424
411
411
398 398 389 375
520 260 517 219 513 177
----499 303 497 263 495 222 491 181
465 375 462 335 461 295 460 255
436 436 430 405 429 366 427 326
435 435 422 422 409 409 396 393
525 269 522 224 518 180
----504 316 502 272 500 228 495 183
470 394 468 350 467 307 465 263
447 447 436 421 434 383 432 340
446 446 432 432 418 418 405 405
529 278 526 230 522 182
----509 328 507 281 504 234 499 185
475 410 472 365 471 318 469 271
456 456 442 440 439 399 436 354
456 456 441 441 427 427 413 413
533 287 530 236 525 184
----512 341 510 290 507 239 503 188
479 425 476 378 475 329 472 279
465 465 451 451 443 413 440 364
464 464 449 449 435 435 420 420
537 296 533 242 526 186
----516 353 514 299 510 245 506 190
483 441 481 392 478 341 476 287
473 473 458 458 447 426 444 375
472 472 457 457 442 442 427 427
539 305 536 247 529 188
----519 364 517 308 513 251 507 192
487 455 484 403 481 348 479 294
480 480 464 464 451 437 448 388
479 479 464 464 448 448 433 433
542 314 538 253 532 191
----521 374 519 317 516 256 509 194
491 468 487 414 484 358 481 301
486 486 470 470 455 450 451 399
486 486 470 470 454 454 439 439
544 322 541 259 535 193
----524 384 522 324 518 262
511
196
494 484 489 426 486 367 483 307
493 493 476 476 461 461 453 410
492 492 476 476 460 460 444 444
547 331 543 264 537 195
----526 394 524 331 520 268 514 199
498 494 492 437 488 375 486 313
498 498 482 482 466 466 455 419
497 497 481 481 465 465 449 449
TOT
----426
394
362
----437
404
372
----445
412
381
----451
419
388
----457
425
394
----462
430
400
----466
434
404
----469
438
409
----472
442
413
----475
445
419
----477
447
424
----480
450
429
----482
452
433
71
SEN
----194
242
287
----199
253
304
----204
264
322
----209
275
339
----214
286
355
----219
296
371
----223
307
384
----228
316
397
----232
326
408
----237
335
419
----241
343
424
----246
351
429
----250
359
433
TOT
----424
393
361
----434
403
371
----442
411
379
----448
418
386
----453
423
392
----457
428
397
----461
432
402
----464
436
406
----467
439
409
----469
442
413
----471
444
416
----473
447
418
----475
449
420
68
SEN
----167
215
260
----168
223
275
----170
231
288
----171
238
302
----173
246
315
----174
253
328
----175
260
341
----176
267
351
----177
274
362
----178
279
372
----179
284
382
----180
289
390
----181
294
398
Unitary Products Group
036-21091-004-B-0205
TABLE 30: COOLING PERFORMANCE - 40 TON STANDARD CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
Unitary Products Group
60.7
60
58.5
57.5
56.5
61.1
60.3
59.1
57.7
57.1
61.4
60.3
59.4
57.9
57.6
61.6
60.6
59.3
58.4
58.1
61.5
61.1
59.5
58.4
58.5
61.7
61.2
60
58.6
58.8
61.9
61.4
59.9
59.2
59.1
62
61.5
60.3
59.4
59.1
62.1
61.6
60.4
59.7
59.4
62.2
61.7
60.3
59.6
59.6
62.6
61.8
60.7
59.9
59.8
62.6
61.9
60.8
60.1
60
62.7
62
60.6
60.2
60.2
TOT
468
447
413
388
388
478
457
424
407
406
486
465
432
423
422
492
472
441
437
436
498
479
450
449
448
503
483
461
460
459
507
488
471
470
469
511
492
479
478
478
515
497
487
486
486
518
501
494
494
493
521
504
501
500
500
523
508
507
507
506
526
514
513
512
512
90
SEN
277
306
354
388
388
294
327
381
407
406
311
347
407
423
422
328
368
434
437
436
345
389
450
449
448
362
409
461
460
459
379
429
471
470
469
396
446
479
478
478
412
464
487
486
486
426
479
494
494
493
439
496
501
500
500
453
508
507
507
506
466
514
513
512
512
TOT
467
446
411
379
373
476
456
421
391
391
484
464
430
406
406
491
470
437
419
419
497
475
443
431
431
501
481
449
441
441
505
485
455
450
450
509
489
460
459
458
512
492
467
466
466
515
495
475
473
473
517
498
481
480
479
519
501
486
485
485
522
503
491
491
490
86
SEN
241
271
319
365
373
254
287
341
391
391
267
303
363
406
406
279
319
385
419
419
292
335
406
431
431
304
351
427
441
441
317
367
445
450
450
329
383
460
459
458
342
397
467
466
466
354
410
475
473
473
365
422
481
480
479
375
434
486
485
485
385
447
491
491
490
115 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
465 214 464 187 461 159
----445 244 443 217 442 190 439 163
410 292 410 266 409 239 408 212
379 339 377 312 377 286 376 259
362 362 351 351 346 330 346 304
475 224 473 193 470 162
----455 257 453 227 451 196 448 165
421 311 419 281 418 251 417 221
388 363 387 334 386 304 385 274
379 379 367 367 357 355 355 325
483 233 480 199 477 164
----462 270 461 236 459 202 455 168
429 330 427 296 426 263 425 229
398 388 396 355 394 321 393 288
393 393 381 381 369 369 363 345
489 242 487 205 483 167
----469 282 467 245 465 208 461 170
436 348 434 311 433 275 431 238
407 407 402 376 401 339 400 303
406 406 393 393 381 381 370 365
494 251 492 210 487 169
----475 295 472 254 470 214 466 172
442 366 440 326 438 286 436 246
418 418 409 395 407 357 405 316
417 417 404 404 391 391 378 378
499 260 496 216 491 171
----479 307 477 263 474 219 470 174
447 385 444 341 443 297 441 254
427 427 416 414 412 372 410 330
427 427 414 414 400 400 387 387
503 269 500 222 495 173
----483 320 481 272 478 225 473 177
452 402 449 356 447 309 445 262
436 436 423 423 416 386 414 344
436 436 422 422 408 408 395 395
506 279 503 227 498 176
----487 332 484 282 481 231 476 179
455 416 452 369 451 320 448 270
444 444 431 431 421 400 418 356
444 444 429 429 416 416 402 402
509 288 506 233 499 177
----490 345 487 291 484 236 479 181
459 432 456 381 453 330 451 278
452 452 437 437 424 414 421 367
451 451 436 436 422 422 408 408
512 297 509 239 503 180
----492 355 490 300 487 242 481 183
463 444 459 394 456 339 454 285
458 458 443 443 429 429 424 378
458 458 443 443 428 428 414 414
514 306
511 245 505 182
----495 367 492 307 489 248 483 186
466 460 462 404 458 348 456 291
464 464 449 449 434 434 427 389
464 464 448 448 433 433 419 419
516 313 513 250 506 185
----497 375 495 314 491 253 485 188
471 471 464 416 460 357 458 297
470 470 454 454 439 439 429 398
469 469 454 454 438 438 423 423
518 320 514 256 508 187
----499 385 496 321 493 259 486 190
475 475 467 429 462 366 460 303
475 475 459 459 444 444 432 407
474 474 458 458 443 443 427 427
TOT
----406
375
345
----415
384
354
----423
392
362
----429
398
369
----434
403
374
----438
408
379
----442
412
384
----445
416
388
----447
419
394
----450
421
399
----452
423
404
----454
425
408
----456
427
412
71
SEN
----185
233
278
----190
244
295
----195
255
312
----200
266
329
----205
276
344
----209
287
358
----214
297
372
----219
308
384
----223
316
394
----228
323
399
----232
331
404
----237
339
408
----241
347
412
TOT
----404
374
344
----412
383
353
----419
390
361
----425
397
367
----429
402
372
----433
406
377
----437
410
381
----439
413
385
----441
416
388
----442
419
391
----444
421
393
----442
423
396
----447
425
398
68
SEN
----158
206
251
----159
214
265
----161
222
279
----162
229
292
----163
236
305
----165
243
318
----166
250
330
----167
257
341
----167
264
351
----168
271
361
----169
276
371
----169
281
378
----171
286
386
43
036-21091-004-B-0205
TABLE 31: COOLING PERFORMANCE - 40 TON HIGH CAPACITY COIL
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
44
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
44.0
43.4
42.4
41.6
40.8
44.3
43.7
42.8
41.9
41.2
44.6
44.0
43.0
42.2
41.6
44.8
44.2
43.3
42.4
42.0
45.0
44.4
43.4
42.6
42.3
45.1
44.6
43.6
42.7
42.6
45.3
44.7
43.7
42.9
42.9
45.4
44.8
43.8
43.0
43.1
45.5
44.9
43.9
43.2
43.3
45.6
45.0
44.1
43.5
43.5
45.7
45.1
44.2
43.7
43.7
45.8
45.1
44.3
43.9
43.8
45.8
45.2
44.4
44.0
44.0
TOT
543
518
477
440
437
557
531
492
460
460
567
543
504
480
480
577
552
514
498
497
584
560
522
513
513
591
568
531
527
527
596
574
540
540
539
602
579
552
551
551
605
585
562
562
561
610
589
572
571
570
615
592
580
580
579
618
597
588
588
587
622
601
596
595
594
90
SEN
305
335
383
430
437
323
356
410
460
460
340
377
438
480
480
357
397
464
498
497
374
418
490
513
513
391
438
517
527
527
408
459
540
540
539
425
479
552
551
551
442
500
562
562
561
459
520
572
571
570
476
538
580
580
579
493
555
588
588
587
510
572
596
595
594
TOT
542
517
476
440
421
555
531
490
454
443
566
542
501
465
462
575
551
511
478
478
583
558
520
494
493
589
565
527
507
507
595
570
534
519
519
599
575
539
530
529
603
579
545
540
539
607
584
550
549
548
610
588
557
557
556
613
591
565
564
564
616
594
572
571
571
86
SEN
270
300
348
395
421
283
316
371
424
443
295
333
393
452
462
308
349
415
478
478
321
365
437
494
493
333
380
459
507
507
345
396
481
519
519
358
412
502
530
529
370
428
521
540
539
383
444
541
549
548
395
459
557
557
556
408
475
565
564
564
420
488
572
571
571
85 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
541 243 539 216 537 188
----516 273 515 246 514 219 512 192
476 322 476 295 475 269 474 242
438 368 437 342 437 316 437 289
409 409 401 386 402 360 401 334
554 252 552 222 549 191
----530 286 528 256 527 226 524 195
489 341 489 311 488 281 487 251
452 394 450 364 450 334 450 305
430 430 418 416 416 386 414 355
565 262 562 228 559 193
----541 299 539 266 537 232 534 197
500 360 500 327 499 294 498 260
464 419 462 386 461 353 460 320
448 448 435 435 426 409 425 377
573 271 571 233 567 196
----550 312 548 275 546 238 542 200
509 378 509 342 508 305 506 269
472 443 472 407 470 371 469 334
464 464 451 451 437 434 435 398
581 280 578 239 574 198
----557 325 555 284 553 243 549 202
518 397 517 357 515 317 514 277
482 468 480 428 478 388 477 348
479 479 465 465 450 450 441 417
587 289 584 245 580 200
----564 337 562 293 559 249 555 204
525 415 523 372 522 329 520 285
492 492 487 449 485 406 483 362
492 492 477 477 462 462 449 437
592 298 589 251 585 202
----569 349 567 302 564 255 560 207
531 434 529 387 527 340 525 293
504 504 493 470 492 423 489 376
503 503 488 488 473 473 456 455
597 307 594 256 589 204
----574 362 572 311 569 260 564 209
537 452 534 402 532 351 530 301
514 514 500 488 497 441 493 390
514 514 498 498 482 482 467 467
601 316 598 262 592 207
----578 374 576 320 573 266 568 211
542 470 538 416 536 363 534 309
524 524 506 505 502 457 499 404
523 523 507 507 491 491 475 475
605 325 601 267 595 209
----582 387 580 329 576 272 571 213
546 487 543 431 540 374 538 317
532 532 516 516 505 472 503 418
532 532 515 515 499 499 482 482
608 334 604 273 598 211
----585 399 583 338 579 277 574 215
549 503 546 446 543 385 541 325
540 540 523 523 510 485 506 430
539 539 523 523 506 506 489 489
611 343 607 279 600 213
----588 411 586 347 582 283 576 217
553 517 550 458 547 397 544 333
547 547 530 530 514 499 510 441
546 546 529 529 512 512 496 496
614 353 609 284 603 215
----591 424 588 356 584 288 578 220
557 532 553 470 549 408 547 341
554 554 536 536 517 513 513 452
553 553 536 536 518 518 501 501
TOT
----473
436
401
----485
449
413
----496
459
423
----504
468
433
----511
475
440
----517
482
447
----522
487
453
----527
492
458
----531
496
462
----534
500
467
----537
503
471
----540
506
479
----542
509
484
71
SEN
----215
263
308
----221
275
326
----226
286
343
----231
298
361
----236
308
378
----241
319
395
----246
330
411
----250
340
427
----255
350
441
----259
361
454
----264
371
466
----268
381
479
----273
389
484
TOT
----471
435
400
----483
447
412
----493
458
423
----501
466
431
----507
474
439
----513
480
445
----518
485
450
----522
490
455
----525
494
460
----528
497
464
----531
500
468
----533
503
471
----535
506
474
68
SEN
----188
236
281
----190
245
296
----192
253
310
----193
261
324
----195
268
338
----196
275
351
----197
283
364
----198
290
377
----199
297
390
----200
304
403
----201
311
413
----203
317
423
----204
324
433
Unitary Products Group
036-21091-004-B-0205
TABLE 31: COOLING PERFORMANCE - 40 TON HIGH CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
Unitary Products Group
49
48.4
47.2
46.2
45.4
49.4
48.7
47.5
46.5
45.9
49.7
48.8
47.8
46.8
46.4
49.7
49.1
48
47.1
46.6
49.9
49.2
48.2
47.3
46.9
50.1
49.4
48.4
47.4
47.4
50.2
49.5
48.5
47.6
47.7
50.3
49.7
48.6
47.8
47.9
50.4
49.8
48.8
48.2
48.2
50.5
49.9
48.9
48.4
48.4
50.8
50
49
48.6
48.6
50.8
50
49.1
48.8
48.8
50.9
50.1
49.2
48.9
48.9
TOT
522
497
458
423
423
534
510
473
445
444
544
521
483
464
463
553
529
491
480
480
560
537
501
495
495
566
544
510
509
508
571
549
521
521
520
575
555
532
531
531
580
560
542
541
540
585
563
551
550
549
588
567
559
558
557
591
571
566
565
565
594
575
573
572
572
90
SEN
297
327
374
421
423
314
348
402
445
444
332
368
429
464
463
349
389
455
480
480
366
409
482
495
495
383
430
508
509
508
400
450
521
521
520
416
471
532
531
531
434
491
542
541
540
451
511
551
550
549
468
527
559
558
557
485
543
566
565
565
499
564
573
572
572
TOT
520
497
458
422
408
533
509
470
434
428
543
519
481
447
445
551
528
491
462
462
558
535
499
476
476
564
540
506
489
488
569
546
510
500
500
573
550
516
510
510
577
555
521
520
519
580
559
529
528
527
584
563
536
536
535
586
566
543
543
542
589
569
550
549
548
86
SEN
261
291
339
386
408
274
308
362
414
428
287
324
384
444
445
300
340
407
462
462
312
356
428
476
476
325
372
450
489
488
337
387
471
500
500
349
403
491
510
510
362
419
511
520
519
374
435
529
528
527
387
451
536
536
535
399
467
543
543
542
412
481
550
549
548
95 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
519 235 518 207 515 180
----496 265 495 238 493 211 491 184
457 313 457 287 456 260 455 233
421 359 420 333 420 307 419 280
396 396 386 378 386 351 385 325
531 244 529 213 527 183
----508 278 507 248 505 217 503 186
470 332 469 303 468 273 467 242
434 385 433 355 432 325 431 296
416 416 403 403 397 375 397 347
541 253 539 219 536 185
----518 291 517 257 515 223 512 189
480 351 479 318 478 285 477 251
445 410 443 377 442 344 441 310
432 432 420 420 408 401 407 368
549 263 547 225 543 187
----527 303 525 266 522 229 519 191
489 370 488 333 486 296 485 259
453 434 453 398 450 361 449 325
447 447 434 434 421 421 416 388
556 272 553 231 550 189
----533 316 532 275 529 235 525 193
496 388 495 348 493 308 491 268
463 460 460 419 458 379 456 339
462 462 447 447 434 434 423 408
561 281 559 236 555 192
----539 328 537 285 534 240 531 196
503 407 501 363 499 320 497 276
474 474 466 440 464 397 462 353
474 474 459 459 444 444 430 428
566 290 564 242 559 194
----544 341 542 294 539 246 535 198
509 425 506 378 504 331 502 284
485 485 473 460 470 414 467 367
484 484 469 469 455 455 440 440
571 299 568 248 563 196
----549 353 547 303 543 252 539 200
514 443 510 392 509 342 506 292
495 495 479 478 475 431 472 381
494 494 479 479 464 464 448 448
575 308 571 253 566 198
----553 366 550 312 547 257 542 202
518 461 515 407 513 354 510 300
504 504 488 488 479 447 476 395
503 503 487 487 472 472 456 456
578 317 574 259 569 200
----556 378 554 321 550 263 545 205
521 478 519 422 516 365 513 308
512 512 496 496 483 458 480 408
511
511 495 495 479 479 463 463
581 326 577 265 571 203
----559 390 557 330 553 269 547 206
525 492 522 436 519 376 516 316
519 519 503 503 487 472 484 421
518 518 502 502 486 486 469 469
584 335 580 270 574 205
----562 403 559 339 556 274 549 209
529 505 525 448 522 387 519 324
526 526 509 509 491 486 487 432
525 525 508 508 492 492 475 475
586 344 582 276 576 207
----564 415 562 348 558 280 551 211
533 524 528 461 524 399 521 331
532 532 515 515 498 498 489 439
531 531 514 514 497 497 481 481
TOT
----454
418
384
----465
430
396
----475
440
405
----482
448
414
----489
455
421
----494
460
428
----499
466
433
----503
470
437
----506
474
442
----510
477
446
----512
480
453
----515
483
459
----517
485
464
71
SEN
----206
254
299
----212
266
317
----217
277
334
----222
288
352
----227
299
368
----232
310
385
----236
320
402
----241
331
416
----245
341
430
----250
351
442
----254
361
453
----259
371
459
----263
380
464
TOT
----452
417
384
----463
429
395
----472
438
405
----479
446
412
----485
453
419
----490
458
425
----494
463
430
----498
467
435
----501
471
439
----504
474
443
----507
477
446
----510
480
448
----510
482
451
68
SEN
----179
227
272
----181
236
287
----183
244
301
----184
251
315
----185
259
328
----187
266
341
----188
273
354
----189
280
368
----190
287
380
----191
294
392
----192
301
403
----194
308
409
----194
315
423
45
036-21091-004-B-0205
TABLE 31: COOLING PERFORMANCE - 40 TON HIGH CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
46
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
54.7
54
52.6
51.5
50.5
55
54.1
53
51.9
51.3
55.3
54.6
53.2
52.2
51.7
55.5
54.9
53.5
52.4
52.2
55.7
55.1
53.7
52.7
52.4
55.9
55.2
53.9
53
52.7
56.1
55.4
54
53.1
53
56.2
55.5
54.2
53.5
53.3
56.3
55.6
54.3
53.7
53.5
56.4
55.7
54.4
53.8
53.7
56.5
55.8
54.7
54
53.9
56.2
55.9
54.8
54.1
54.1
56.6
56
55.2
54.6
54.5
TOT
499
476
439
408
409
510
487
452
429
429
520
496
462
446
446
527
506
470
462
462
533
513
479
476
476
539
519
490
489
488
544
523
501
500
499
549
529
511
510
510
554
533
520
520
519
557
537
528
528
527
560
541
536
535
535
563
545
543
542
542
566
550
549
549
548
90
SEN
288
318
366
408
409
306
339
393
429
429
323
359
420
446
446
340
380
446
462
462
357
401
473
476
476
374
421
490
489
488
391
441
501
500
499
408
462
511
510
510
425
482
520
520
519
443
500
528
528
527
459
517
536
535
535
475
535
543
542
542
490
550
549
549
548
TOT
498
475
438
405
393
509
487
450
415
412
518
495
460
429
429
526
503
468
445
444
532
509
476
457
457
537
515
480
469
469
542
520
487
480
479
546
524
492
489
489
550
528
499
498
497
553
532
507
506
506
556
536
514
513
513
558
539
521
520
519
561
542
527
526
525
86
SEN
253
283
330
377
393
266
299
353
405
412
278
315
375
429
429
291
331
397
445
444
303
347
419
457
457
316
363
440
469
469
328
379
463
480
479
341
395
483
489
489
353
410
499
498
497
366
426
507
506
506
378
443
514
513
513
391
458
521
520
519
403
471
527
526
525
105 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
497 226 495 199 493 171
----474 256 473 229 472 202 470 175
438 304 437 278 436 251 435 224
403 351 402 324 401 298 401 271
382 382 370 369 369 343 368 316
508 235 506 205 503 174
----486 269 484 239 483 208 480 177
449 323 448 293 447 264 446 233
415 376 413 346 413 316 412 286
400 400 388 388 380 367 380 338
517 245 515 211
511 176
----495 282 493 248 491 214 488 180
459 342 457 309 456 275 455 242
424 400 423 368 422 334 421 301
416 416 404 404 391 391 389 358
524 254 522 216 518 179
----502 294 501 257 498 220 495 182
466 360 465 324 464 287 462 250
433 425 432 389 430 352 428 315
430 430 418 418 405 405 396 378
530 263 528 222 524 181
----508 307 507 267 504 226 501 184
474 379 472 339 470 299 468 258
444 444 437 409 437 370 435 329
443 443 429 429 416 416 404 399
535 272 533 228 528 183
----514 319 512 276 509 231 505 187
480 397 477 354 476 310 474 267
455 455 444 429 443 387 440 343
454 454 440 440 426 426 413 413
540 281 537 234 532 185
----518 332 516 285 514 237 509 189
485 416 482 368 480 322 478 274
465 465 451 449 448 405 445 357
464 464 450 450 435 435 421 421
544 290 541 239 534 187
----522 344 520 294 517 243 513 191
490 434 486 383 484 333 482 282
474 474 460 460 452 421 450 371
474 474 459 459 444 444 429 429
547 299 544 245 537 189
----526 357 524 303 521 248 514 193
492 450 491 398 488 344 485 290
482 482 468 468 456 434 454 385
482 482 466 466 451 451 436 436
550 308 547 251 540 192
----529 369 527 312 523 254 517 195
497 465 494 413 490 355 488 298
490 490 474 474 461 450 457 398
489 489 474 474 458 458 443 443
553 318 549 256 543 194
----532 381 530 321 526 260 519 197
501 480 497 424 493 367 491 306
497 497 481 481 465 465 460 409
496 496 480 480 464 464 448 448
556 327 551 262 545 196
----534 394 532 330 528 265 522 200
505 496 500 437 496 376 493 314
503 503 487 487 471 471 463 420
503 503 486 486 470 470 454 454
558 336 554 268 547 199
----537 405 534 339 530 271 524 202
510 510 501 448 498 386 495 321
509 509 493 493 476 476 465 429
509 509 492 492 476 476 459 459
TOT
----434
400
367
----444
411
378
----453
420
387
----460
427
395
----466
433
402
----471
438
407
----475
443
412
----479
447
417
----482
451
421
----485
454
428
----487
456
433
----489
459
438
----491
461
443
71
SEN
----197
245
290
----203
257
308
----208
268
325
----213
279
342
----218
290
359
----222
300
375
----227
311
391
----232
321
405
----236
331
417
----241
341
428
----245
352
433
----249
361
438
----254
369
443
TOT
----432
399
367
----442
410
377
----450
418
386
----456
425
393
----462
431
399
----466
437
405
----470
441
410
----473
445
414
----476
448
418
----478
451
421
----481
454
424
----482
456
426
----484
458
429
68
SEN
----170
218
263
----172
226
278
----174
234
292
----175
242
305
----176
249
319
----177
256
332
----179
263
345
----180
270
358
----181
277
370
----182
284
381
----183
291
390
----184
298
399
----185
305
408
Unitary Products Group
036-21091-004-B-0205
TABLE 31: COOLING PERFORMANCE - 40 TON HIGH CAPACITY COIL (CONTINUED)
AIR ON EVAPORATOR COIL
POWER INPUT KW
CFM
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
19000
20000
WB°F
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
75
72
67
62
57
Unitary Products Group
61.1
60.3
59
57.7
56.7
61.5
60.7
59.4
57.9
57.3
61.8
60.7
59.4
58.2
57.9
62
61
59.7
58.9
58.3
61.9
61.5
59.9
59
58.8
62.1
61.6
60.1
59.2
59.1
62.3
61.8
60.5
59.5
59.5
62.7
61.9
60.4
59.8
59.5
62.8
62.1
60.8
60.1
59.8
62.9
62.2
60.7
60
60
63
62.3
61.1
60.2
60.2
63.1
62.3
61.1
60.5
60.4
63.1
62.4
61
60.6
60.6
TOT
476
454
419
393
393
487
464
431
412
412
494
473
439
429
429
501
481
448
444
443
507
488
458
457
456
513
493
469
468
468
517
498
480
479
478
522
502
489
488
488
525
506
497
497
496
529
510
505
504
504
532
515
512
511
511
534
520
518
518
517
537
526
524
524
523
90
SEN
280
309
357
393
393
297
330
384
412
412
314
350
410
429
429
331
371
437
444
443
348
392
458
457
456
366
412
469
468
468
383
433
480
479
478
400
453
489
488
488
417
474
497
497
496
434
490
505
504
504
451
510
512
511
511
465
520
518
518
517
480
526
524
524
523
TOT
475
453
417
384
378
485
464
428
396
396
493
472
438
412
412
500
478
446
427
426
506
484
451
438
438
511
490
457
449
449
515
494
464
459
459
519
499
469
468
468
522
502
477
476
476
525
505
485
483
483
527
508
491
490
489
530
511
497
496
496
532
513
502
502
501
86
SEN
244
274
321
367
378
257
290
344
396
396
270
306
366
412
412
282
322
388
427
426
295
338
409
438
438
307
354
431
449
449
320
370
453
459
459
332
386
469
468
468
345
402
477
476
476
357
418
485
483
483
370
432
491
490
489
382
446
497
496
496
395
460
502
502
501
115 °F AIR ON CONDENSER COIL
CAPACITY (MBH) AT ENTERING DRY BULB (F)
83
80
77
74
TOT SEN TOT SEN TOT SEN TOT SEN
473 217 472 190 469 163
----452 247 451 220 450 193 447 166
417 295 416 269 416 242 415 215
385 342 383 315 382 288 382 262
367 367 356 356 350 333 351 307
484 227 482 196 479 165
----463 260 461 230 459 199 457 168
427 314 426 284 426 254 424 224
395 367 394 337 392 307 392 277
384 384 373 373 363 358 361 328
492 236 489 202 486 167
----471 273 469 239 467 205 464 171
436 333 435 300 434 266 432 233
404 391 403 358 401 325 400 292
400 400 387 387 375 375 368 348
498 245 496 208 492 170
----477 285 476 248 474
211
470 173
444 351 442 315 441 278 439 241
413 413 409 379 408 342 406 306
413 413 400 400 387 387 377 369
504 254 501 213 497 172
----483 298 481 258 479 217 475 175
450 370 448 329 447 289 445 249
425 425 416 400 414 360 412 320
425 425
411
411
398 398 385 385
509 263 506 219 501 174
----488 310 486 267 484 222 479 178
456 388 453 344 451 301 449 257
436 436 423 420 420 377 417 334
435 435 421 421 408 408 394 394
513 273 510 225 505 176
----493 323 490 276 487 228 483 180
461 406 457 359 455 312 453 265
445 445 431 431 424 394 422 348
444 444 431 431 416 416 402 402
516 282 513 231 507 179
----496 335 494 285 491 234 486 182
464 424 462 374 459 324 457 273
453 453 439 439 429 408 426 361
453 453 438 438 424 424 410 410
519 291 516 236 510 181
----499 348 497 294 494 239 488 184
468 442 465 389 462 335 460 281
461 461 446 446 433 425 429 373
460 460 445 445 430 430 416 416
522 300 518 242 512 183
----502 360 500 303 496 245 490 186
472 455 469 404 465 346 462 289
468 468 453 453 438 438 433 385
467 467 452 452 437 437 422 422
524 309 521 248 514 185
----504 372 502 312 499 251 492 189
476 472 471 414 467 357 465 297
474 474 458 458 444 444 436 398
474 474 458 458 442 442 427 427
527 318 523 253 515 187
----507 385 504 321 500 256 493 190
481 481 473 428 470 367 467 305
480 480 464 464 449 449 438 408
479 479 464 464 448 448 432 432
529 327 525 259 517 190
----509 396 506 330 502 262 495 193
486 486 477 441 472 376 469
311
485 485 469 469 453 453 441 420
485 485 469 469 453 453 437 437
TOT
----413
381
350
----423
391
360
----430
399
368
----437
406
375
----442
411
381
----446
416
386
----450
420
391
----453
424
395
----456
427
402
----459
429
407
----461
431
412
----463
434
417
----465
436
421
71
SEN
----188
236
281
----194
247
298
----199
258
316
----203
269
332
----208
280
349
----213
290
365
----217
301
380
----222
311
395
----227
321
402
----231
330
407
----235
339
412
----240
348
417
----244
356
421
TOT
----411
380
349
----420
390
359
----427
397
367
----433
404
373
----438
409
379
----442
414
384
----445
418
388
----447
421
392
----448
424
396
----450
427
398
----452
429
401
----455
431
404
----458
433
407
68
SEN
----161
209
254
----163
217
268
----164
225
282
----166
232
296
----167
239
309
----168
247
322
----169
254
335
----169
260
348
----170
267
359
----171
274
368
----172
281
380
----174
288
389
----175
294
399
47
036-21091-004-B-0205
CFM, STATIC PRESSURE, AND POWER - ALTITUDE AND TEMPERATURE CORRECTIONS
order to use the indoor blower tables for high altitude applications, certain corrections are necessary.
The information below should be used to assist in application
of product when being applied at altitudes at or exceeding
1000 feet above sea level.
A centrifugal fan is a "constant volume" device. This means
that, if the rpm remains constant, the CFM delivered is the
same regardless of the density of the air. However, since the
air at high altitude is less dense, less static pressure will be
generated and less power will be required than a similar
application at sea level. Air density correction factors are
shown in Table 32 and Figure 21.
The air flow rates listed in the standard blower performance
tables are based on standard air at sea level. As the altitude
or temperature increases, the density of air decreases. In
TABLE 32: ALTITUDE CORRECTION FACTORS
AIR TEMP
40
50
60
70
80
90
100
0
1.060
1.039
1.019
1.000
0.982
0.964
0.946
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
ALTITUDE (FEET)
4000
5000
0.916
0.882
0.898
0.864
0.880
0.848
0.864
0.832
0.848
0.817
0.833
0.802
0.817
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
The examples below will assist in determining the airflow performance of the product at altitude.
blower tables to select the blower speed and the BHP
requirement.
Example 1: What are the corrected CFM, static pressure,
and BHP at an elevation of 5,000 ft. if the blower performance
data is 6,000 CFM, 1.5 IWC and 4.0 BHP?
Solution: As in the example above, no temperature information is given so 70°F is assumed.
Solution: At an elevation of 5,000 ft the indoor blower will still
deliver 6,000 CFM if the rpm is unchanged. However, Table
32 must be used to determine the static pressure and BHP.
Since no temperature data is given, we will assume an air
temperature of 70°F. Table 32 shows the correction factor to
be 0.832.
The 1.5" static pressure given is at an elevation of 5,000 ft.
The first step is to convert this static pressure to equivalent
sea level conditions.
Sea level static pressure = 1.5 / .832 = 1.80"
Enter the blower table at 6000 sCFM and static pressure of
1.8". The rpm listed will be the same rpm needed at 5,000 ft.
Corrected static pressure = 1.5 x 0.832 = 1.248 IWC
Corrected BHP = 4.0 x 0.832 = 3.328
Example 2: A system, located at 5,000 feet of elevation, is to
deliver 6,000 CFM at a static pressure of 1.5". Use the unit
48
Suppose that the corresponding BHP listed in the table is 3.2.
This value must be corrected for elevation.
BHP at 5,000 ft = 3.2 x .832 = 2.66
Unitary Products Group
036-21091-004-B-0205
FIGURE 21 - ALTITUDE/TEMPERATURE CONVERSION FACTOR
Unitary Products Group
49
036-21091-004-B-0205
TABLE 33: FAN PERFORMANCE - 25 TON1, 2
0.2
AIRFLOW CFM
BHP3
0.62
0.93
1.34
1.88
2.56
3.40
4.38
5.55
6.90
RPM
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
306
337
370
408
444
481
520
557
596
549
555
562
573
591
611
634
662
690
720
728
736
740
744
751
760
774
792
811
833
757
767
772
775
781
789
801
817
834
855
RPM
864
878
885
889
892
897
903
913
926
942
3.4
BHP3
4.90
5.69
6.47
7.25
8.13
9.09
10.15
11.50
12.96
14.55
RPM
890
904
911
914
918
921
927
936
948
963
404
415
433
456
484
514
545
579
612
647
BHP3
0.82
1.08
1.43
1.88
2.49
3.21
4.11
5.12
6.37
7.76
RPM
456
465
478
497
520
547
576
608
638
671
1.0
BHP3
1.08
1.36
1.72
2.20
2.80
3.58
4.47
5.54
6.78
8.22
RPM
RPM
628
634
638
645
657
673
692
715
739
766
BHP3
2.23
2.66
3.11
3.68
4.35
5.12
6.13
7.25
8.59
10.09
RPM
BHP3
2.55
3.00
3.52
4.09
4.76
5.59
6.58
7.70
9.07
10.65
RPM
663
670
674
679
689
703
719
741
763
789
RPM
787
798
803
805
810
817
826
841
857
877
BHP3
3.87
4.50
5.14
5.84
6.63
7.48
8.54
9.75
11.21
12.87
RPM
BHP3
4.21
4.88
5.58
6.31
7.11
8.01
9.07
10.30
11.79
13.43
RPM
814
825
830
833
837
843
852
865
880
899
BHP3
6.01
6.92
7.82
8.75
9.71
10.78
11.97
13.30
14.70
16.45
RPM
2.0
RPM
913
927
935
939
942
946
951
959
970
984
BHP3
5.64
6.51
7.36
8.24
9.18
10.18
11.36
12.70
14.12
15.79
RPM
935
950
959
964
967
970
975
983
992
1005
BHP3
2.86
3.38
3.92
4.50
5.19
6.06
7.03
8.21
9.55
11.20
698
705
709
713
720
732
747
766
787
811
3.0
BHP3
4.55
5.28
6.03
6.78
7.60
8.55
9.60
10.90
12.38
13.99
839
851
858
861
865
870
878
890
903
921
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.6
3.8
BHP3
5.26
6.10
6.91
7.74
8.66
9.63
10.76
12.10
13.54
15.12
BHP3
1.35
1.66
2.04
2.54
3.15
3.96
4.83
5.97
7.19
8.69
506
512
521
535
555
579
606
635
664
696
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
2.6
2.8
BHP3
3.53
4.13
4.73
5.37
6.15
7.00
8.01
9.24
10.63
12.32
RPM
3.2
AIRFLOW CFM
50
2.4
BHP3
3.19
3.75
4.32
4.92
5.67
6.53
7.48
8.72
10.05
11.76
RPM
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
591
597
602
610
624
642
663
689
714
743
RPM
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.6
1.8
BHP3
1.93
2.31
2.74
3.27
3.95
4.72
5.68
6.82
8.10
9.61
RPM
2.2
AIRFLOW CFM
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
342
362
387
415
446
480
514
550
585
622
1.4
BHP3
1.63
1.97
2.39
2.88
3.55
4.34
5.23
6.39
7.62
9.15
RPM
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.6
0.8
BHP3
0.59
0.83
1.17
1.60
2.17
2.86
3.76
4.74
5.96
7.32
RPM
1.2
AIRFLOW CFM
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
0.4
4.0
957
973
983
988
992
995
999
1005
1013
1025
BHP3
6.39
7.33
8.29
9.25
10.26
11.37
12.57
13.90
15.33
17.11
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density
and 0’ elevation.
2.
Refer to Tables 6, 11, 17 and 36 for component additions and deductions to fan performance tables.
3.
BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.
Unitary Products Group
036-21091-004-B-0205
FIGURE 22 - FAN PERFORMANCE - 25 TON
Unitary Products Group
51
036-21091-004-B-0205
TABLE 34: FAN PERFORMANCE - 30 TON 1, 2
0.2
AIRFLOW (CFM)
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
RPM
BHP3
RPM
321
357
398
436
477
519
560
603
645
688
0.9
1.3
1.8
2.5
3.2
4.2
5.4
6.8
8.4
10.2
373
404
437
473
511
549
589
629
669
711
1.2
AIRFLOW (CFM)
554
568
587
610
636
665
697
729
764
800
734
741
750
763
779
799
821
847
874
904
RPM
52
765
772
781
792
807
824
845
869
896
924
877
885
892
900
910
923
939
958
980
1004
3.4
BHP3
6.4
7.3
8.4
9.5
10.9
12.4
14.0
15.8
17.9
20.2
RPM
904
911
917
925
934
946
961
980
1001
1023
422
447
477
509
543
579
617
654
694
733
BHP3
1.5
1.9
2.5
3.2
4.1
5.1
6.4
7.8
9.5
11.5
RPM
632
642
655
673
695
720
747
777
809
842
BHP3
3.2
3.8
4.5
5.4
6.5
7.6
9.1
10.7
12.6
14.6
RPM
796
803
810
820
833
849
869
892
917
944
BHP3
5.1
6.0
6.9
7.9
9.1
10.5
12.1
13.9
15.8
18.1
469
490
515
543
575
609
643
680
718
755.6
RPM
928
935
942
949
958
970
984
1001
1021
1043
BHP3
7.3
8.3
9.4
10.6
12.1
13.6
15.3
17.2
19.4
21.8
1.0
BHP3
1.8
2.2
2.9
3.6
4.5
5.6
6.9
8.4
10.0
12.1
RPM
BHP3
3.5
4.2
5.0
5.9
7.0
8.2
9.6
11.3
13.2
15.2
RPM
668
676
689
704
723
746
772
801
831
863
BHP3
5.5
6.4
7.4
8.5
9.7
11.1
12.7
14.5
16.5
18.8
RPM
BHP3
7.7
8.8
9.9
11.2
12.7
14.2
16.0
17.9
20.1
22.5
RPM
2.0
824
830
837
847
859
874
893
914
938
964
3.0
951
959
966
974
982
993
1006
1022
1040
1062
BHP3
6.0
6.9
7.9
9.0
10.3
11.7
13.4
15.1
17.2
19.5
850
858
865
873
885
899
916
936
959
984
3.8
RPM
BHP3
3.9
4.6
5.4
6.4
7.5
8.8
10.2
11.9
13.8
15.9
703
710
720
734
751
773
797
824
853
884
2.8
RPM
BHP3
2.1
2.6
3.3
4.0
5.0
6.1
7.4
8.9
10.7
12.7
513
529
551
577
606
637
670
705
741
778
1.8
RPM
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.6
BHP3
6.8
7.8
8.9
10.1
11.5
13.0
14.6
16.5
18.7
21.0
0.8
RPM
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
2.6
BHP3
4.7
5.5
6.4
7.4
8.6
9.9
11.5
13.2
15.1
17.4
RPM
3.2
AIRFLOW (CFM)
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
2.4
BHP3
4.3
5.0
5.9
6.9
8.0
9.3
10.8
12.6
14.5
16.6
RPM
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
596
607
622
642
666
693
722
753
787
821
RPM
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.6
BHP3
2.8
3.4
4.1
4.9
6.0
7.1
8.5
10.0
11.9
13.9
RPM
2.2
AIRFLOW (CFM)
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.6
BHP3
1.1
1.6
2.1
2.8
3.7
4.7
5.9
7.3
8.9
10.8
1.4
BHP3
2.4
3.0
3.7
4.5
5.5
6.6
7.9
9.5
11.3
13.3
RPM
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
0.4
4.0
975
984
991
998
1006
1015
1028
1043
1060
1081
BHP3
8.2
9.2
10.4
11.8
13.3
14.8
16.7
18.6
20.8
23.3
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density
and 0’ elevation.
2.
Refer to Tables 6, 11, 17 and 36 for component additions and deductions to fan performance tables.
3.
BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.
Unitary Products Group
036-21091-004-B-0205
FIGURE 23 - FAN PERFORMANCE - 30 TON
Unitary Products Group
53
036-21091-004-B-0205
TABLE 35: FAN PERFORMANCE - 40 TON1,2
0.2
AIRFLOW (CFM)
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
54
1.4
BHP3
3.3
4.0
4.7
5.5
6.5
7.6
8.9
10.3
11.9
13.6
15.6
RPM
506
518
532
549
568
588
609
631
654
678
703
RPM
537
549
563
579
596
614
634
655
677
701
724
2.2
2.4
BHP3
5.7
6.5
7.4
8.4
9.6
10.9
12.4
13.9
15.7
17.6
19.7
RPM
654
664
675
687
700
714
729
746
764
784
805
RPM
681
691
701
712
723
737
752
768
786
805
824
3.2
AIRFLOW (CFM)
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
RPM
348
371
396
421
446
473
502
529
557
587
616
1.2
AIRFLOW (CFM)
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
BHP3
1.3
1.8
2.3
2.9
3.7
4.6
5.7
6.9
8.3
9.9
11.7
RPM
304
329
356
385
414
442
472
503
532
562
593
AIRFLOW (CFM)
8000
9000
10000
11000
12000
13000
14000
15000
16000
17000
18000
0.4
RPM
774
784
794
804
814
825
837
851
866
882
900
3.4
BHP3
8.3
9.3
10.3
11.6
12.9
14.4
16.0
17.8
19.7
21.9
24.2
RPM
797
806
815
824
835
846
858
871
886
901
-
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.6
RPM
RPM
BHP3
BHP3
1.7
393
2.1
431
2.2
411
2.6
448
2.7
432
3.2
467
3.4
454
3.9
488
4.3
479
4.8
510
5.2
504
5.8
532
6.3
529
6.9
556
7.6
555
8.2
581
9.0
583
9.7
607
10.6
611
11.4
633
12.5
638
13.2
660
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.6
RPM
RPM
BHP3
BHP3
3.8
569
4.2
601
4.4
581
4.9
610
5.2
594
5.8
621
6.1
608
6.7
634
7.1
623
7.7
649
8.2
640
8.9
665
9.5
658
10.2
683
11.0
679
11.7
702
12.6
700
13.4
722
14.4
722
15.2
742
16.4
744
17.2
764
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
2.6
RPM
RPM
BHP3
BHP3
6.2
706
6.7
729
7.0
715
7.6
738
8.0
725
8.6
748
9.0
735
9.7
758
10.2
747
10.9
770
11.6
760
12.3
782
13.1
774
13.8
796
14.7
790
15.4
811
16.5
807
17.3
826
18.5
824
19.3
843
20.6
843
21.5
862
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
3.6
RPM
RPM
BHP3
BHP3
8.8
9.8
11.0
12.2
13.6
15.1
16.8
18.6
20.5
22.7
-
817
826
836
845
855
866
878
891
905
919
-
9.4
10.4
11.6
12.9
14.3
15.8
17.5
19.4
21.4
23.6
-
0.8
1.0
BHP3
2.5
3.0
3.7
4.5
5.4
6.4
7.6
8.9
10.4
12.1
14.0
RPM
469
484
502
519
539
560
583
607
631
656
682
BHP3
4.7
5.5
6.3
7.2
8.3
9.5
10.9
12.5
14.1
16.0
18.1
RPM
627
637
648
661
675
690
707
724
743
763
785
BHP3
7.2
8.1
9.1
10.3
11.6
13.0
14.5
16.2
18.1
20.1
22.4
RPM
752
761
771
781
793
805
817
831
846
863
881
BHP3
9.9
11.0
12.3
13.6
15.0
16.6
18.3
20.2
22.2
24.5
-
RPM
1.8
2.0
2.8
BHP3
5.2
6.0
6.8
7.8
9.0
10.2
11.6
13.2
14.9
16.8
18.9
3.0
3.8
837
846
856
865
876
886
898
910
923
937
-
BHP3
2.9
3.5
4.2
5.0
5.9
7.0
8.2
9.6
11.2
12.9
14.7
BHP3
7.7
8.7
9.7
10.9
12.3
13.7
15.2
17.0
18.9
21.0
23.3
4.0
857
866
876
886
896
906
917
928
941
-
BHP3
10.5
11.6
12.9
14.2
15.7
17.3
19.1
21.0
23.1
-
1.
Fan performance is based on wet evaporator coils, clean 2” throwaway filters and system/cabinet effects at standard air density and 0°
elevation.
2.
Refer to Tables 8, 14, 19 and 36 for component additions and deductions to fan performance tables.
3.
BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.
Unitary Products Group
036-21091-004-B-0205
FIGURE 24 - FAN PERFORMANCE - 40 TON
Unitary Products Group
55
036-21091-004-B-0205
TABLE 36: COMPONENT STATIC RESISTANCE1, 2
CFM
COMPONENT COIL
LOSSES
6,000
8,000
10,000
12,000
14,000
16,000
STD. 25 TON, DRY
-0.06
-0.08
-0.10
-0.13
-
-
-
STD. 25 TON, WET
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
18,000
STD. 30 TON, DRY
-0.045
-0.075
-0.112
-0.157
-0.207
-0.264
-0.326
STD. 30 TON, WET
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
-0.155
HI CAP 30 TON, DRY
-0.019
-0.035
-0.052
-0.073
-0.098
-0.124
HI CAP 30 TON, WET
0.042
0.069
0.103
0.142
0.186
0.236
0.290
STD. 40 TON, DRY
-0.030
-0.051
-0.076
-0.106
-0.140
-0.177
-0.219
STD. 40 TON, WET
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
HI CAP 40 TON, DRY
-0.020
-0.033
-0.050
-0.069
-0.092
-0.116
-0.144
HI CAP 40 TON, WET
0.023
0.038
0.057
0.079
0.105
0.133
0.164
2” TA OR HI EFF.
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
Baseline
RIGID 6”, 65%
0.048
0.080
0.119
0.165
0.217
0.274
0.338
RIGID 6”, 95%
0.189
0.308
0.448
0.609
0.790
0.988
1.205
FILTER LOSSES
IGV LOSSES
25 & 30 TON
0.048
0.085
0.132
0.190
0.259
0.338
0.428
40 TON
0.027
0.049
0.076
0.110
0.149
0.195
0.246
233 MBH HEAT
0.106
0.141
0.177
0.212
0.247
0.283
0.318
466 MBH HEAT
0.212
0.283
0.353
0.424
0.495
0.566
0.636
699 MBH HEAT
0.318
0.423
0.531
0.636
0.741
0.849
0.954
ELECTRIC HEAT
0.050
0.100
0.150
0.310
0.430
0.530
0.680
ECONOMIZER
0.063
0.104
0.153
0.210
0.276
0.349
0.429
POWER EXHAUST
0.046
0.081
0.127
0.182
0.248
0.324
0.410
GAS HEAT
56
1.
Baseline losses based on system/cabinet effects, wet standard coil and 2” throwaway filters at 70°F, 0° elevation with standard air.
2.
See Tables 6, 8, 11, 14 and 17 for hot water and steam water coil static resistance.
Unitary Products Group
036-21091-004-B-0205
TABLE 37: POWER EXHAUST - ONE FORWARD CURVED FAN 25 TON1
0.2
AIRFLOW CFM
2000
3000
4000
5000
6000
7000
8000
9000
10000
RPM
BHP2
RPM
----442
524
612
703
791
877
967
----0.63
1.15
1.84
2.86
3.63
5.53
8.02
--450
496
566
646
731
821
911
1004
RPM
2000
3000
4000
5000
6000
7000
8000
9000
10000
754
736
743
768
806
857
921
995
1077
BHP2
--0.41
0.74
1.29
2.08
3.16
4.09
5.88
8.34
RPM
524
531
562
609
679
759
844
932
1022
BHP2
0.32
0.51
0.87
1.43
2.25
3.37
4.54
6.22
8.66
RPM
609
605
626
663
717
787
868
953
1041
BHP2
0.42
0.64
1.00
1.58
2.43
3.57
4.99
6.57
8.98
1.0
BHP2
0.66
0.92
1.32
1.90
2.78
3.98
5.47
7.27
9.62
RPM
819
797
799
818
850
895
953
1020
1096
BHP2
0.78
1.08
1.47
2.08
2.95
4.19
5.71
7.59
9.94
RPM
878
854
850
865
895
933
985
1048
1119
BHP2
0.90
1.24
1.66
2.28
3.17
4.39
5.95
7.86
10.25
RPM
933
909
900
911
937
972
1018
1075
1143
BHP2
0.54
0.77
1.16
1.74
2.60
3.78
5.23
6.92
9.30
RPM
685
672
687
717
762
820
892
974
1059
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.4
1.6
1.8
1.2
AIRFLOW CFM
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
0.6
0.8
0.4
2.0
BHP2
1.03
1.41
1.84
2.48
3.40
4.60
6.19
8.13
10.55
RPM
986
961
948
955
978
1010
1052
1103
1167
1.
Fan performance is based on system/cabinet effects and back draft damper effects at standard air density and 0° elevation.
2.
BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.
Unitary Products Group
BHP2
1.16
1.58
2.04
2.68
3.62
4.80
6.43
8.39
10.86
57
036-21091-004-B-0205
Power Exhaust 25 Ton
8.0
7.5
7.0
6.5
1600
6.0
Total Static Pressure (IWG)
5.5
1500
10 BHP
5.0
7.5 BHP
1400
4.5
5 BHP
1300
4.0
1200
3.5
1100
3.0
1000
2.5
900
2.0
800
700
1.5
600
1.0
500
0.5
400
300
0.0
0.0
2.0
4.0
6.0
8.0
10.0
12.0
14.0
16.0
18.0
CFM (x1000)
FIGURE 25 - POWER EXHAUST - ONE FORWARD CURVE FAN - 25 TONS
58
Unitary Products Group
036-21091-004-B-0205
TABLE 38: POWER EXHAUST - TWO FORWARD CURVED FANS - 30 & 40 TON1
0.2
AIRFLOW CFM
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
16000
RPM
BHP2 3
RPM
363
402
445
494
544
597
651
705
761
817
874
932
989
0.3
0.5
0.8
1.2
1.7
2.3
3.1
4.1
5.2
6.6
8.1
9.9
12.0
468
494
527
565
609
654
703
753
805
858
912
967
1022
1.2
AIRFLOW CFM
RPM
4000
5000
6000
7000
8000
9000
10000
11000
12000
13000
14000
15000
0.4
783
788
798
814
837
866
900
936
976
1018
1061
1107
BHP2 3
0.5
0.7
1.0
1.5
2.0
2.7
3.5
4.5
5.6
7.0
8.6
10.4
12.6
1.4
BHP2 3
1.4
1.7
2.1
2.7
3.3
4.1
5.0
6.1
7.4
8.9
10.6
12.6
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
.06
RPM
844
848
855
869
889
915
945
979
1016
1055
1098
1141
RPM
560
576
602
633
670
711
754
801
849
899
950
1002
1055
BHP2 3
0.7
1.0
1.3
1.7
2.3
3.0
3.8
4.9
6.0
7.4
9.1
11.0
13.1
RPM
903
906
911
922
938
961
989
1020
1055
1093
1133
1175
BHP2 3
1.8
2.3
2.8
3.3
4.0
4.9
5.9
7.0
8.3
9.9
11.7
13.7
RPM
956
959
963
972
987
1007
1032
1061
1094
1129
1167
1208
1.0
BHP2 3
0.9
1.2
1.6
2.0
2.6
3.3
4.2
5.3
6.5
7.9
9.5
11.5
13.6
641
652
670
697
729
765
805
847
893
939
988
1037
1088
AVAILABLE EXTERNAL STATIC PRESSURE (IWG)
1.6
BHP2 3
1.6
2.0
2.5
3.0
3.7
4.5
5.4
6.6
7.9
9.4
11.1
13.1
0.8
RPM
BHP2 3
1.1
1.4
1.9
2.4
3.0
3.7
4.6
5.7
6.9
8.4
10.0
12.0
RPM
716
722
735
757
784
817
853
893
934
979
1025
1072
1.8
2
BHP2 3
2.1
2.5
3.1
3.7
4.4
5.3
6.3
7.5
8.8
10.4
12.3
14.2
RPM
1008
1011
1014
1021
1033
1050
1073
1101
1131
1165
1202
1240
1.
Fan performance is based on system/cabinet effects and back draft damper effects at standard air density and 0° elevation.
2.
BHP includes the sum of both exhaust fan blowers
3.
BHP does not include drive losses. Multiply BHP by 1.05 to account for drive losses.
Unitary Products Group
BHP2 3
2.3
2.8
3.4
4.0
4.8
5.7
6.8
7.9
9.3
11.0
12.8
14.8
59
036-21091-004-B-0205
FIGURE 26 - POWER EXHAUST - TWO FORWARD CURVED FANS - 30 & 40 TONS
60
Unitary Products Group
036-21091-004-B-0205
TABLE 39: ELECTRICAL DATA 25 TON BASIC UNIT
VOLTAGE
QTY.
COMPRESSORS
RLA
LRA
COND. FAN MOTOR
QTY
FLA
208-3-60
2
45.7
350
4
7.6 ea.
230-3-60
2
45.7
350
4
6.9 ea.
460-3-60
2
24.3
158
4
3.5 ea.
575-3-60
2
19.3
125
4
3.0 ea.
SUPPLY AIR MOTOR
HP
FLA
7.5
24.2
10
30.8
15
46.2
20
59.4
7.5
22.0
10
28.0
15
42.0
20
54.0
7.5
11.0
10
14.0
15
21.0
20
27.0
7.5
9.0
10
11.0
15
17.0
20
22.0
MCA
157
164
180
196
152
158
172
187
80
83
90
96
64
66
72
78
BASIC UNIT
MAX OVERCURRENT PROTECTION DEVICE
200
200
225
250
175
200
200
225
100
100
110
110
80
80
90
100
TABLE 40: ELECTRICAL DATA 30 TON BASIC UNIT
VOLTAGE
COMPRESSORS
QTY.
RLA
LRA
COND. FAN MOTOR
QTY.
FLA
TOTAL
208-3-60
3
38.5
228
3
4.0 ea.
12.0
230-3-60
3
38.5
255
3
3.6 ea.
10.8
460-3-60
3
18.8
127
3
2.2 ea.
6.6
575-3-60
3
15.7
100
3
1.4 ea.
4.2
SUPPLY AIR MOTOR
HP
FLA
10
30.8
15
46.2
20
59.4
25
74.8
10
28
15
42
20
54
25
68
10
14
15
21
20
27
25
34
10
11
15
17
20
22
25
27
MCA
168
185
202
221
164
179
194
211
81
88
96
104
66
73
79
85
BASIC UNIT
MAX. Overcurrent Protection Device
200
225
250
250
200
200
225
250
90
100
110
125
80
80
100
110
SUPPLY AIR MOTOR
HP
FLA
10
30.8
15
46.2
20
59.4
25
74.8
10
28
15
42
20
54
25
68
10
14
15
21
20
27
25
34
10
11
15
17
20
22
25
27
MCA
210
228
244
264
206
221
236
253
101
109
116
125
83
90
96
102
BASIC UNIT
MAX. Overcurrent Protection Device
225
250
300
300
225
250
250
300
110
125
125
150
90
100
110
125
TABLE 41: ELECTRICAL DATA 40 TON BASIC UNIT
VOLTAGE
COMPRESSORS
QTY.
RLA
LRA
COND. FAN MOTOR
QTY.
FLA
TOTAL
208-3-60
4
38.5
228
4
4.0 ea.
12.0
230-3-60
4
38.5
255
4
3.6 ea.
14.4
460-3-60
4
18.8
127
4
2.2 ea.
8.8
575-3-60
4
15.7
100
4
1.4 ea.
5.6
Unitary Products Group
61
036-21091-004-B-0205
TABLE 42: ELECTRICAL DATA 25 TON BASIC UNIT W/ ELECTRIC HEAT
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
40
SUPPLY AIR MOTOR
APPLIED KW
30
208-3-60
80
40
60.1
40
230-3-60
80
40
460-3-60
80
108
40
575-3-60
80
108
62
80
40
80
108
40
80
108
BASIC UNIT W/ ELECTRIC HEAT
HP
FLA
MCA
MAX OVERCURRENT PROTECTION DEVICE
7.5
24.2
157
200
10
30.8
164
200
15
46.2
180
225
20
59.4
196
250
7.5
22.0
197
225
10
28.0
205
225
15
42.0
225
250
20
54.0
241
300
7.5
11.0
152
175
10
14.0
158
200
15
21.0
172
200
20
27.0
187
225
7.5
9.0
212
250
10
11.0
219
250
15
17.0
237
250
20
22.0
252
300
7.5
24.2
80
100
10
30.8
83
100
15
46.2
90
110
20
59.4
96
110
7.5
22.0
106
125
10
28.0
110
125
15
42.0
118
125
20
54.0
126
150
7.5
22.0
138
150
10
28.0
142
175
15
42.0
151
175
20
54.0
158
175
7.5
11.0
64
80
10
14.0
66
80
15
21.0
72
90
20
27.0
78
100
7.5
9.0
92
110
10
11.0
94
110
15
17.0
102
110
20
22.0
108
125
7.5
9.0
120
150
10
11.0
122
150
15
17.0
130
150
20
22.0
136
150
Unitary Products Group
036-21091-004-B-0205
TABLE 43: ELECTRICAL DATA 30 TON BASIC UNIT W/ ELECTRIC HEAT
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
APPLIED KW
40
30
80
60.1
40
40
80
80
40
40
80
80
108
108
40
40
80
80
108
108
208-3-60
230-3-60
460-3-60
575-3-60
Unitary Products Group
SUPPLY AIR MOTOR
HP
FLA
10
30.8
15
46.2
20
59.4
25
74.8
10
30.8
15
46.2
20
59.4
25
74.8
10
28
15
42
20
54
25
68
10
28
15
42
20
54
25
68
10
14
15
21
20
27
25
34
10
14
15
21
20
27
25
34
10
14
15
21
20
27
25
34
10
11
15
17
20
22
25
27
10
11
15
17
20
22
25
27
10
11
15
17
20
22
25
27
MCA
210
228
244
264
210
228
244
264
206
221
236
253
227
245
260
277
101
109
116
125
114
122
130
139
147
156
164
172
83
90
96
102
94
102
108
114
122
130
136
142
BASIC UNIT WITH ELECTRIC HEAT
MAX OVERCURRENT PROTECTION DEVICE
225
250
300
300
225
250
300
300
225
250
250
300
250
250
300
300
110
125
125
150
125
125
150
150
175
175
175
200
90
100
110
125
110
110
125
125
150
150
150
150
63
036-21091-004-B-0205
TABLE 44: ELECTRICAL DATA 40 TON BASIC UNIT W/ ELECTRIC HEAT
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
APPLIED KW
40
30
80
60.1
40
40
80
80
40
40
80
80
108
108
40
40
80
80
108
108
208-3-60
230-3-60
460-3-60
575-3-60
64
SUPPLY AIR MOTOR
HP
FLA
10
30.8
15
46.2
20
59.4
25
74.8
10
30.8
15
46.2
20
59.4
25
74.8
10
28.0
15
42.0
20
54.0
25
68.0
10
28.0
15
42.0
20
54.0
25
68.0
10
14.0
15
21.0
20
27.0
25
34.0
10
14.0
15
21.0
20
27.0
25
34.0
10
14.0
15
21.0
20
27.0
25
34.0
10
11.0
15
17.0
20
22.0
25
27.0
10
11.0
15
17.0
20
22.0
25
27.0
10
11.0
15
17.0
20
22.0
25
27.0
MCA
210
228
244
264
210
228
244
264
206
221
236
253
227
245
260
277
101
109
116
125
114
122
130
139
147
156
164
172
83
90
96
102
94
102
108
114
122
130
136
142
BASIC UNIT WITH ELECTRIC HEAT
MAX. OVERCURRENT PROTECTION DEVICE
225
250
300
300
225
250
300
300
225
250
250
300
250
250
300
300
110
125
125
150
125
125
150
150
175
175
175
200
90
100
110
125
110
110
125
125
150
150
150
150
Unitary Products Group
036-21091-004-B-0205
TABLE 45: ELECTRICAL DATA 25 TON BASIC UNIT W/ POWER EXHAUST
VOLTAGE
SUPPLY AIR MOTOR
HP
7.5
10
208-3-60
15
20
7.5
10
230-3-60
15
20
7.5
10
460-3-60
15
20
7.5
10
575-3-60
15
20
Unitary Products Group
EXHAUST OR ERV FAN MOTOR(S)
HP
FLA
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
15.2
7.5
22.0
10 (5 x 2)
28.0
5
15.2
7.5
22.0
10 (5 x 2)
28.0
5
15.2
7.5
22.0
10 (5 x 2)
28.0
5
15.2
7.5
22.0
10 (5 x 2)
28.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
MCA
174
182
188
181
188
195
196
204
210
213
220
227
168
174
180
174
180
186
188
194
200
202
209
215
87
91
94
90
94
97
97
101
104
104
107
110
71
74
76
73
76
78
79
82
84
84
87
89
BASIC UNIT W/ EXHAUST FAN
MAX OVERCURRENT PROTECTION DEVICE
200
225
225
225
225
225
225
225
250
250
250
250
200
200
225
200
225
225
225
225
225
250
250
250
110
110
110
110
110
110
110
110
125
125
125
125
80
90
90
90
90
90
90
100
100
100
100
110
65
036-21091-004-B-0205
TABLE 46: ELECTRICAL DATA 30 TON BASIC UNIT W/ POWER EXHAUST
VOLTAGE
SUPPLY AIR MOTOR
HP
10
15
208-3-60
20
25
10
15
230-3-60
20
25
10
15
460-3-60
20
25
10
15
575-3-60
20
25
66
EXHAUST OR ERV FAN MOTOR(S)
HP
FLA
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
22.0
10 (5 x 2)
28.0
15 (7.5 x 2)
42.0
7.5
22.0
10 (5 x 2)
28.0
15 (7.5 x 2)
42.0
7.5
22.0
10 (5 x 2)
28.0
15 (7.5 x 2)
42.0
7.5
22.0
10 (5 x 2)
28.0
15 (7.5 x 2)
42.0
7.5
11.0
10 (5 x 2)
14.0
15 (7.5 x 2)
21.0
7.5
11.0
10 (5 x 2)
14.0
15 (7.5 x 2)
21.0
7.5
11.0
10 (5 x 2)
14.0
15 (7.5 x 2)
21.0
7.5
11.0
10 (5 x 2)
14.0
15 (7.5 x 2)
21.0
7.5
9.0
10 (5 x 2)
11.0
15 (7.5 x 2)
17.0
7.5
9.0
10 (5 x 2)
11.0
15 (7.5 x 2)
17.0
7.5
9.0
10 (5 x 2)
11.0
15 (7.5 x 2)
17.0
7.5
9.0
10 (5 x 2)
11.0
15 (7.5 x 2)
17.0
MCA
192
199
216
209
216
231
226
233
248
245
252
267
186
192
207
201
207
221
216
222
236
233
239
253
92
95
102
99
102
109
107
110
117
115
118
125
75
77
84
82
84
90
88
90
96
94
96
102
BASIC UNIT WITH EXHAUST FAN
MAX. OVERCURRENT PROTECTION DEVICE
225
225
250
250
250
250
250
250
300
300
300
300
200
225
225
225
225
250
250
250
250
300
300
300
110
110
110
110
110
125
125
125
125
125
150
150
90
90
100
90
100
100
100
110
110
110
110
125
Unitary Products Group
036-21091-004-B-0205
TABLE 47: ELECTRICAL DATA 40 TON BASIC UNIT W/ POWER EXHAUST
VOLTAGE
SUPPLY AIR MOTOR
HP
10
15
208-3-60
20
25
10
15
230-3-60
20
25
10
15
460-3-60
20
25
10
15
575-3-60
20
25
Unitary Products Group
EXHAUST OR ERV FAN MOTOR(S)
HP
FLA
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
9
10 (5 x 2)
11
15 (7.5 x 2)
17
7.5
9
10 (5 x 2)
11
15 (7.5 x 2)
17
7.5
9
10 (5 x 2)
11
15 (7.5 x 2)
17
7.5
9
10 (5 x 2)
11
15 (7.5 x 2)
17
MCA
235
241
259
252
259
274
268
275
290
288
294
310
228
234
249
243
249
263
258
264
278
275
281
295
112
115
123
120
123
130
127
130
137
136
139
146
92
94
101
99
101
107
105
107
113
111
113
119
BASIC UNIT WITH EXHAUST FAN
MAX. OVERCURRENT PROTECTION DEVICE
250
250
300
300
300
300
300
300
300
350
350
350
250
250
250
250
250
300
300
300
300
300
300
350
125
125
125
125
125
150
150
150
150
150
150
175
100
110
110
110
110
110
125
125
125
125
125
125
67
036-21091-004-B-0205
TABLE 48: ELECTRICAL DATA 25 TON BASIC UNIT W/ POWER EXHAUST & ELEC HEAT
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
APPLIED KW
SUPPLY AIR MOTOR
HP
7.5
10
40
30
15
20
208-3-60
7.5
10
80
60.1
15
20
7.5
10
40
40
15
20
230-3-60
7.5
10
80
80
15
20
68
EXHAUST OR ERV FAN MOTOR(S)
HP
FLA
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
16.7
7.5
24.2
10 (5 x 2)
30.8
5
15.2
7.5
22.0
10 (5 x 2)
28.0
5
15.2
7.5
22.0
10 (5 x 2)
28.0
5
15.2
7.5
22.0
10 (5 x 2)
28.0
5
15.2
7.5
22.0
10 (5 x 2)
28.0
5
15.2
7.5
22.0
10 (5 x 2)
28.0
5
15.2
7.5
22.0
10 (5 x 2)
28.0
5
15.2
7.5
22.0
10 (5 x 2)
28.0
5
15.2
7.5
22.0
10 (5 x 2)
28.0
MCA
174
182
188
181
188
195
196
204
210
213
220
227
218
227
236
226
236
244
245
255
263
262
271
280
168
174
180
174
180
186
188
195
203
202
210
218
231
239
247
238
247
254
256
264
272
271
279
287
BASIC UNIT W/ EXHAUST FAN
MAX OVERCURRENT PROTECTION DEVICE
200
225
225
225
225
225
225
225
250
250
250
250
225
250
250
250
250
250
250
300
300
300
300
300
200
200
225
200
225
225
225
225
225
250
250
250
250
250
250
250
250
300
300
300
300
300
300
300
Unitary Products Group
036-21091-004-B-0205
TABLE 48: ELECTRICAL DATA 25 TON BASIC UNIT W/ POWER EXHAUST & ELEC HEAT (CONTINUED)
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
APPLIED KW
SUPPLY AIR MOTOR
HP
7.5
10
40
30
15
20
7.5
10
460-3-60
80
80
15
20
7.5
10
108
108
15
20
Unitary Products Group
EXHAUST OR ERV FAN MOTOR(S)
HP
FLA
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
5
7.6
7.5
11.0
10 (5 x 2)
14.0
MCA
87
91
94
90
94
97
97
101
104
104
107
110
115
120
123
119
123
127
128
132
136
135
140
143
148
152
156
151
156
159
160
164
168
168
172
176
BASIC UNIT W/ EXHAUST FAN
MAX OVERCURRENT PROTECTION DEVICE
110
110
110
110
110
110
110
110
125
125
125
125
125
125
125
125
125
150
150
150
150
150
150
150
175
175
175
175
175
175
175
175
175
175
175
200
69
036-21091-004-B-0205
TABLE 48: ELECTRICAL DATA 25 TON BASIC UNIT W/ POWER EXHAUST & ELEC HEAT (CONTINUED)
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
APPLIED KW
SUPPLY AIR MOTOR
HP
7.5
10
40
40
15
20
7.5
10
575-3-60
80
80
15
20
7.5
10
108
108
15
20
70
EXHAUST OR ERV FAN MOTOR(S)
HP
FLA
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
5
6.1
7.5
9.0
10 (5 x 2)
11.0
MCA
71
74
76
73
76
78
79
83
85
85
89
91
99
103
105
102
105
108
109
113
115
115
119
122
127
131
133
130
133
136
137
141
143
144
147
150
BASIC UNIT W/ EXHAUST FAN
MAX OVERCURRENT PROTECTION DEVICE
80
90
90
90
90
90
90
100
100
100
100
110
110
110
110
110
110
110
110
125
125
125
125
125
150
150
150
150
150
150
150
150
150
150
150
175
Unitary Products Group
036-21091-004-B-0205
TABLE 49: ELECTRICAL DATA 30 TON BASIC UNIT W/ POWER EXHAUST & ELEC HEAT
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
APPLIED KW
SUPPLY AIR Motor
HP
10
15
40
30
20
25
208-3-60
10
15
80
60.1
20
25
10
15
40
40
20
25
230-3-60
10
15
80
80
20
25
Unitary Products Group
EXHAUST OR ERV FAN MOTOR(S)
HP
FLA
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
24.2
10 (5 x 2)
30.8
15 (7.5 x 2)
46.2
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
7.5
22
10 (5 x 2)
28
15 (7.5 x 2)
42
BASIC UNIT WITH EXHAUST FAN AND ELECTRIC HEAT
MCA
MAX. OVERCURRENT PROTECTION DEVICE
192
225
199
225
216
250
209
250
216
250
231
250
226
250
233
250
248
300
245
300
252
300
267
300
236
250
244
250
263
300
255
300
263
300
282
300
271
300
280
300
299
300
291
350
299
350
318
350
186
200
192
225
208
225
201
225
208
225
225
250
216
250
223
250
240
250
233
300
240
300
258
300
255
300
262
300
280
300
272
300
280
300
297
300
287
300
295
300
312
350
305
350
312
350
330
350
71
036-21091-004-B-0205
TABLE 49: ELECTRICAL DATA 30 TON BASIC UNIT W/ POWER EXHAUST & ELEC HEAT (CONTINUED)
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
APPLIED KW
SUPPLY AIR Motor
HP
10
15
40
40
20
25
10
15
460-3-60
80
80
20
25
10
15
108
108
20
25
72
EXHAUST OR ERV FAN MOTOR(S)
HP
FLA
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
7.5
11
10 (5 x 2)
14
15 (7.5 x 2)
21
BASIC UNIT WITH EXHAUST FAN AND ELECTRIC HEAT
MCA
MAX. OVERCURRENT PROTECTION DEVICE
92
110
95
110
104
110
100
110
104
110
113
125
108
125
111
125
120
125
116
125
120
150
129
150
127
150
131
150
140
150
136
150
140
150
149
150
144
150
147
150
156
175
152
175
156
175
165
175
161
175
165
175
174
175
170
175
174
175
182
200
177
200
181
200
190
200
186
200
190
200
199
225
Unitary Products Group
036-21091-004-B-0205
TABLE 49: ELECTRICAL DATA 30 TON BASIC UNIT W/ POWER EXHAUST & ELEC HEAT (CONTINUED)
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
APPLIED KW
SUPPLY AIR Motor
HP
10
15
40
40
20
25
10
15
575-3-60
80
80
20
25
10
15
108
108
20
25
Unitary Products Group
EXHAUST OR ERV FAN MOTOR(S)
HP
FLA
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
BASIC UNIT WITH EXHAUST FAN AND ELECTRIC HEAT
MCA
MAX. OVERCURRENT PROTECTION DEVICE
75
78
85
83
85
93
89
91
99
95
98
105
105
108
115
113
115
123
119
122
129
125
128
135
133
136
143
141
143
151
147
150
157
153
156
163
90
90
100
90
100
100
100
110
110
110
110
125
110
110
125
125
125
125
125
125
150
150
150
150
150
150
150
150
150
175
150
150
175
175
175
175
73
036-21091-004-B-0205
TABLE 50: ELECTRICAL DATA 40 TON BASIC UNIT W/ POWER EXHAUST & ELEC HEAT
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
APPLIED KW
SUPPLY AIR MOTOR
HP
10
15
40
30
20
25
208-3-60
10
15
80
60.1
20
25
10
15
40
40
20
25
230-3-60
10
15
80
80
20
25
74
EXHAUST OR ERV FAN MOTOR(S) BASIC UNIT WITH EXHAUST FAN AND ELECTRIC HEAT
HP
FLA
MCA MAX. OVERCURRENT PROTECTION DEVICE
7.5
24.2
235
250
10 (5 x 2)
30.8
241
250
15 (7.5 x 2)
46.2
259
300
7.5
24.2
252
300
10 (5 x 2)
30.8
259
300
15 (7.5 x 2)
46.2
274
300
7.5
24.2
268
300
10 (5 x 2)
30.8
275
300
15 (7.5 x 2)
46.2
290
300
7.5
24.2
288
350
10 (5 x 2)
30.8
294
350
15 (7.5 x 2)
46.2
310
350
7.5
24.2
236
250
10 (5 x 2)
30.8
244
250
15 (7.5 x 2)
46.2
263
300
7.5
24.2
255
300
10 (5 x 2)
30.8
263
300
15 (7.5 x 2)
46.2
282
300
7.5
24.2
271
300
10 (5 x 2)
30.8
280
300
15 (7.5 x 2)
46.2
299
350
7.5
24.0
291
350
10 (5 x 2)
30.8
299
350
15 (7.5 x 2)
46.2
318
350
7.5
22
228
250
10 (5 x 2)
28
234
250
15 (7.5 x 2)
42
249
250
7.5
22
243
250
10 (5 x 2)
28
249
250
15 (7.5 x 2)
42
263
300
7.5
22
258
300
10 (5 x 2)
28
267
300
15 (7.5 x 2)
42
278
300
7.5
22
275
300
10 (5 x 2)
28
281
300
15 (7.5 x 2)
42
295
350
7.5
22
255
300
10 (5 x 2)
28
262
300
15 (7.5 x 2)
42
280
300
7.5
22
272
300
10 (5 x 2)
28
280
300
15 (7.5 x 2)
42
297
300
7.5
22
287
300
10 (5 x 2)
28
295
300
15 (7.5 x 2)
42
312
350
7.5
22
305
350
10 (5 x 2)
28
312
350
15 (7.5 x 2)
42
330
350
Unitary Products Group
036-21091-004-B-0205
TABLE 50: ELECTRICAL DATA 40 TON BASIC UNIT W/ POWER EXHAUST & ELEC HEAT (CONTINUED)
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
APPLIED KW
SUPPLY AIR MOTOR
HP
10
15
40
40
20
25
10
15
460-3-60
80
80
20
25
10
15
108
108
20
25
Unitary Products Group
EXHAUST OR ERV FAN MOTOR(S) BASIC UNIT WITH EXHAUST FAN AND ELECTRIC HEAT
HP
FLA
MCA MAX. OVERCURRENT PROTECTION DEVICE
7.5
11
112
125
10 (5 x 2)
14
115
125
15 (7.5 x 2)
21
123
125
7.5
11
120
125
10 (5 x 2)
14
123
125
15 (7.5 x 2)
21
130
150
7.5
11
127
150
10 (5 x 2)
14
130
150
15 (7.5 x 2)
21
137
150
7.5
11
136
150
10 (5 x 2)
14
139
150
15 (7.5 x 2)
21
146
175
7.5
11
127
150
10 (5 x 2)
14
131
150
15 (7.5 x 2)
21
140
150
7.5
11
136
150
10 (5 x 2)
14
140
150
15 (7.5 x 2)
21
149
150
7.5
11
144
150
10 (5 x 2)
14
147
150
15 (7.5 x 2)
21
156
175
7.5
11
152
175
10 (5 x 2)
14
156
175
15 (7.5 x 2)
21
165
175
7.5
11
161
175
10 (5 x 2)
14
165
175
15 (7.5 x 2)
21
174
175
7.5
11
170
175
10 (5 x 2)
14
174
175
15 (7.5 x 2)
21
182
200
7.5
11
177
200
10 (5 x 2)
14
181
200
15 (7.5 x 2)
21
190
200
7.5
11
186
200
10 (5 x 2)
14
190
200
15 (7.5 x 2)
21
199
225
75
036-21091-004-B-0205
TABLE 50: ELECTRICAL DATA 40 TON BASIC UNIT W/ POWER EXHAUST & ELEC HEAT (CONTINUED)
VOLTAGE
ELECTRIC HEAT
NOMINAL KW
APPLIED KW
SUPPLY AIR MOTOR
HP
10
15
40
40
20
25
10
15
575-3-60
80
80
20
25
10
15
108
108
20
25
76
EXHAUST OR ERV FAN MOTOR(S) BASIC UNIT WITH EXHAUST FAN AND ELECTRIC HEAT
HP
FLA
MCA MAX. OVERCURRENT PROTECTION DEVICE
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
7.5
10 (5 x 2)
15 (7.5 x 2)
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
9
11
17
92
94
101
99
101
107
105
107
113
111
113
119
105
108
115
113
115
123
119
122
129
125
128
135
133
136
143
141
143
151
147
150
157
153
156
163
100
110
110
110
110
110
125
125
125
125
125
125
110
110
125
125
125
125
125
125
150
150
150
150
150
150
150
150
150
175
150
150
175
175
175
175
Unitary Products Group
036-21091-004-B-0205
TABLE 51: UNIT WEIGHTS
COMPONENT
TABLE 52: SUPPLY FAN MOTOR VFD WEIGHTS
25 TON
30 TON
Basic Unit
4350
4550
Gas Heat
233 MBH
180
180
466 MBH
320
320
700 MBH
Electric Heat
40KW
40
40
80KW
105
105
108KW
110
110
Hot Water Heat
1 Row Coil
70
70
2 Row Coil
85
85
Steam Heat
1 Row Coil
85
85
Blower
Forward Curve Fan (Std Fan)
0
0
FC IGV
155
155
Air Foil Fan
135
135
AF IGV
155
155
Motor - Supply Fan
7.5hp
110
10hp
145
145
15hp
200
200
20hp
240
240
25hp
300
Supply Fan Motor VFD
See Table 52
Refrigeration
Hi Cap. Evap. Coil
50
T-Coat Evap.
32
30
T-Coat cond.
32
30
Hot Gas Bypass
10
10
Low Ambient Head Pressure Control
208-230/380/460
5
5
575
25
25
Filters
6" Rigid
70
70
40 TON
4950
Std. Econ.
Econ. w/ERV
Disconnect
110V outlet
Optilogic
Partial Curb
Full Curb
1.
575V
W/O Bypass
60
25
30
10hp
60
25
30
15hp
75
50
60
40
105
110
20hp
75
50
60
25hp
115
50
60
70
85
7.5hp
155
90
120
10hp
155
90
120
85
15hp
185
140
155
20hp
185
140
155
25hp
255
140
155
0
175
155
180
W/Bypass
TABLE 53: EXHAUST FAN MOTOR VFD WEIGHTS
Exhaust Fan Motor
145
200
240
300
15
40
40
10
460V
575V
5hp
15
10
20
7.5hp
50
15
20
10hp
50
15
20
15hp
65
40
50
25hp
255
140
155
NOTE: If the Millennium is VAV with ERV, add the
weight of an exhaust VFD - it will be in the unit.
5
25
70
230V
W/O Bypass
CENTER OF
GRAVITY
C
BACK
CONDENSER
COIL END
B
D
65
275
65
275
80
110
145
200
80
110
145
200
See Table 53
80
110
145
200
235
50
235
50
15
55
20
15
55
20
415
615
415
615
If ERV and Supply Fan VAV are selected, add the
weight of an Exhaust VFD, Table 52.
Unitary Products Group
460V
7.5hp
45
140
Economizer
235
50
Control
15
55
20
Roof Curb
415
615
230V
180
320
450
Exhaust1
Exhaust Type
Barometric
Modulated
Exhaust Motor
5hp
7.5hp
10hp
15hp
Exhaust Motor VFD
Supply Fan Motor VFD
X
92 "
Y
A
FRONT
240"
FIGURE 27 - CENTER OF GRAVITY
TABLE 54: UNIT CENTER OF GRAVITY
MODEL
BASIC UNIT
BASIC UNIT /W
ECON.
BASIC UNIT /W
ECON. & GAS OR
ELECT. HEAT,
STEAM OR HOT
WATER HEAT
BASIC UNIT /W
ECON. & GAS OR
ELECT. HEAT, &
POWER EXHAUST
25 TON
X
Y
99”
46”
30 TON
X
Y
98”
45”
40 TON
X
Y
93”
46"
110”
46”
108”
45”
97”
46"
104”
45”
102”
44”
96”
45"
118”
45”
112”
44”
108”
45"
77
036-21091-004-B-0205
TABLE 55: UNIT CORNERWEIGHT
25 TON
30 TON
40 TON
UNIT
DESCRIPTION
A
B
C
D
A
B
C
D
A
B
C
D
BASIC UNIT
1033
1033
1215
1215
1079
1053
1269
1294
1131
1131
1417
1417
BASIC UNIT WITH
ECONOMIZER
1112
1112
1253
1253
1185
1157
1280
1308
1205
1205
1460
1460
BASIC UNIT WITH
ECONOMIZER AND
GAS OR ELECTRIC
HEAT
1162
1162
1293
1293
1209
1155
1346
1400
1255
1224
1500
1531
BASIC UNIT WITH
ECONOMIZER AND
GAS OR ELECTRIC
HEAT AND POWER
EXHAUST
1284
1284
1296
1296
1359
1298
1389
1449
1416
1384
1532
1563
NOTES: Basic Unit = cooling only, 10hp FC fan.
+ Econ = +235lb
+ Heat = single stage gas, 180 lb
+ Power Exhaust = modulating 7.5hp
TABLE 56: INDOOR SOUND POWER RATING
MODEL NUMBER
CFM
Y22
Y23
Y24
10,000
12750
17500
ESP
IWG
1.5
1.5
1.3
BLOWER
RPM
750
840
800
BHP
7.5
12.8
20
63
90
93
95
Sound Power Ratings for Supply Air Blowers in our Millenium
Units with High Gas Heat, Economizer, 2: T/A Filters and Wet
DX Sound power calculations complements of Lau’s revised
“Whirlwind” application selection software for air moving components.
SOUND POWER (DB 10-12 WATTS)
OCTAVE BAND CENTERLINE FREQUENCY (Hz)
125
250
500
1000
2000
4000
88
85
85
80
78
74
91
88
88
83
81
77
92
89
89
84
83
78
8000
68
71
72
dba
87
90
91
The sound ratings above occur at the blower wheel. To determine the sound rating at a unit’s supply and return air duct
connection, subtract the attenuation factors listed below.
TABLE 57: ATTENUATION FACTORS
LOCATION
SUPPLY AIR
RETURN AIR
78
63
11
13
125
OCTAVE BAND CENTERLINE FREQUENCY (HZ)
250
500
1000
2000
4000
8000
13
15
SOUND ATTENUATION (DB12 WATTS)
10
21
23
25
23
29
23
29
18
22
21
25
Unitary Products Group
036-21091-004-B-0205
TABLE 58: OUTDOOR SOUND POWER RATING
MODEL
65
125
250
Y22
Y23
Y24
88
87
88
91
90
91
89
88
89
Octave Band Centerline Frequency (Hertz)
500
1000
2000
Sound Power Level, db (10)-12 Watts
86
82
79
86
82
80
86
82
80
NOTE: These values have been accessed using a model of
sound propagation from a point source into the
hemispheric free field (AMCA 303-79). The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of sysem
design, and the fan manufacturer has no way of
4000
8000
db(A)
76
77
77
72
73
73
88
88
88
knowing the details of each system. This consitutes
an exception to any specification or guarantee
requiring a dBA value or sound data in any other
form than sound power level ratings.
EVAPORATOR COIL
AND DRAINPAN ACCESS
POWER & CONTROL WIRING
FILTER ACCESS
COMPRESSOR ACCESS
REAR
RIGHT
SIDE
HEAT SECTION
FRONT
LEFT SIDE
POWER EXHAUST ACCESS
HEAT SECTION
FILTER DRIERS
EVAPORATOR COIL
AND DRAINPAN ACCESS
FILTER ACCESS
REAR
SUPPLY BLOWER & MOTOR
FIGURE 28 - COMPONENT LOCATION
Unitary Products Group
79
036-21091-004-B-0205
NOTE:
FACTORY INSTALLED POWER
EXHAUST CANNOT BE ORDERED
WITH END RETURN.
RETURN AIR
SUPPLY AIR
SEE
DETAIL
B
7-7/8"
64"
SEE
DETAIL
C
75.6"
24.9"
76-3/8
92"
6.25"
80.93"
4.5"
SEE
DETAIL
A
100.10"
128.50"
8.15"
OPEN
26"
71.61"
3.625"
6.46"
15.89"
12"
MIN
CL
88.7"
240"
1-1/4" FPT
4-5/8"
3-5/8"
4-5/8"
BASE RAIL
1-1/2" FPT
DETAIL A
(DRAIN CONNECTION)
BASE RAIL
3-1/16" 6.46"
2-1/2"
DETAIL B
(ELECTRICAL CONNECTION)
FOR COOLING ONLY AND ALL HEATING APPLICATIONS
10-1/4"
12"
MIN
14"
MIN
3-1/16"
NOTE: Hole must be drilled
at job site.
DETAIL C
(GAS CONNECTION
THROUGH CURB)
FIELD SUPPLIED
FIGURE 29 - END RETURN, BOTTOM SUPPLY
80
Unitary Products Group
036-21091-004-B-0205
RETURN AIR
SUPPLY AIR
SEE
SEE DETAIL
DETAIL C
B
64"
100.10"
92"
128.50"
4.5"
80.93"
4.5"
SEE
DETAIL
A
OPEN
26"
71.61"
4.5"
12"
MIN
15.89"
6.46"
38.59"
83"
3.625"
88.7"
127.5"
CL
240"
CL
1-1/4" FPT
4-5/8"
1-5/8" FPT FLANGE D
FITTING
4-5/8"
3-5/8"
BASE RAIL
1-1/2" FPT
DETAIL A
(DRAIN CONNECTION)
10-1/4"
3-1/16"
BASE RAIL
6.46"
1-1/4" FPT
DETAIL B
(ELECTRICAL CONNECTION)
FOR COOLING ONLY AND ALL HEATING APPLICATIONS
12"
MIN
14"
MIN
3-1/16"
NOTE: Hole must be drilled
at job site.
DETAIL C
(GAS CONNECTION,
THROUGH CURB)
FIGURE 30 - BOTTOM SUPPLY AND RETURN
Unitary Products Group
81
036-21091-004-B-0205
FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS
REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS
FRONT
REAR
RETURN AIR
SUPPLY AIR
REAR
RIGHT SIDE
26"
55"
64"
75.6"
8.15"
SEE
DETAIL
B SEE
FRONT
DETAIL
C
92"
LEFT SIDE
REAR
80.93"
4.5"
LEFT SIDE
RIGHT
SIDE
OPEN
SEE
DETAIL
A
83"
100.10"
128.50"
38.59"
3.625"
12"
MIN
6.46"
FRONT
240"
4.5"
1-1/4" FPT
4-5/8"
3-5/8"
4-5/8"
BASE RAIL
1-1/2" FPT
DETAIL A
(DRAIN CONNECTION)
BASE RAIL
3-1/16" 6.46"
2-1/2"
DETAIL B
(ELECTRICAL CONNECTION)
10-1/4"
12"
MIN
14"
MIN
3-1/16"
NOTE: Hole must be drilled
DETAIL C at job site.
(GAS CONNECTION
THROUGH CURB)
FIELD SUPPLIED
FIGURE 31 - BOTTOM RETURN, FRONT & REAR SUPPLY
82
Unitary Products Group
036-21091-004-B-0205
FRONT SUPPLY: FOR COOLING ONLY APPLICATIONS
REAR SUPPLY: FOR COOLING ONLY OR GAS HEAT APPLICATIONS
26"
55"
RETURN AIR
SUPPLY AIR
26"
55"
7-7/8"
64"
75.6"
24.9"
76-3/8
92"
6.25"
8.15"
SEE
DETAIL
SEE
B DETAIL
C
80.93"
SEE
DETAIL
A
100.10"
128.50"
OPEN
3.625"
12"
MIN
6.46"
240"
1-1/4" FPT
4-5/8"
3-5/8"
4-5/8"
BASE RAIL
1-1/2" FPT
DETAIL A
(DRAIN CONNECTION)
3-1/16" 6.46"
BASE RAIL
2-1/2"
DETAIL B
(ELECTRICAL CONNECTION)
10-1/4"
12"
MIN
14"
MIN
3-1/16"
NOTE: Hole must be drilled
DETAIL C at job site.
(GAS CONNECTION
THROUGH CURB)
FIELD SUPPLIED
FIGURE 32 - END RETURN, FRONT & REAR SUPPLY
Unitary Products Group
83
036-21091-004-B-0205
259.68
35.42
39.31
93.43
241.22
FIGURE 33 - MILLENNIUM OVERHEAD VIEW
FIGURE 34 - MILLENNIUM MAJOR COMPONENT LAYOUT
84
Unitary Products Group
036-21091-004-B-0205
FIGURE 35 - CLEARANCES - HOOD/ECONOMIZER & MOTOR DRIVE - SIDE
15.93
RAIN HOOD FOR
FIXED OUTSIDE AIR
OR ECONOMIZER
79.0
33.90
33.90
59.52
15.93
20.12
19.6
29.36
HOOD FOR
OPTIONAL
EXHAUST AIR
(NOT AVAILABLE WITH
END RETURN OR WITH
FIXED OUTSIDE AIR)
7.94
RAIN HOOD FOR
OPTIONAL POWER EXHAUST
OR BAROMETRIC RELIEF
(NOT AVAILABLE WITH
END RETURN OR WITH
FIXED OUTSIDE AIR)
FIGURE 36 - CLEARANCES - HOOD/ECONOMIZER & MOTOR DRIVE - FRONT & END
Unitary Products Group
85
036-21091-004-B-0205
2 3 5 .0 0
9 5 .0 9
3 8 .5 9
7 1 .6 1
R E T U R N
A IR
O P E N IN G
8 3 .0 0
2 6 .0 0
S U P P L Y
A IR
O P E N IN G
8 7 .0 0
1 1 .3 9
4 .0 0
2 .0 0
1 4 .0 0
In s u la tio
P ro te
(S h e e t
N o s e P
n E
c to
M e
ie c
r
d g e
ta l
e )
A
A
F IE L D
S U P P L IE D
D U C T
A
T y p ic a l In s u la tio n
B
A
S E E S E C T IO N "A -A "
B
- IF
- IF
U N IT
U N IT
IS
IS
N O T IN S T A L L E D
A L R E A D Y IN S T A L L E D
N O T E : P r o te c t in s u la tio n w ith a s h e e t m e ta l
n o s e p ie c e w h e n in s ta llin g a in te r n a lly in s u la te d
d u c t w o rk .
T Y P IC A L D U C T IN S T A L L A T IO N S
B A S E R A IL
(Y O R K U N IT )
C U R B G A S K E T
B A S E R A IL C R O S S -S E C T IO N
1 .2 5 "
1 .7 5 "
4 .6 3 "
2 " X 4 "
N A IL E R
2 .5 0 "
1 .5 0 "
(1 4 .0 0 )
1 4 G A . G A L V S T E E L
R O O F C U R B
2 .0 0 "
S E C T IO N "A -A "
FIGURE 37 - PARTIAL ROOF CURB MODEL 1RC0455P
86
Unitary Products Group
036-21091-004-B-0205
2 3 5 .0 0
2 6 .0 0
2 .0 0
8 3 .0 0
3 8 .5 9
7 3 .3 0
2 3 .7 6
7 1 .6 1
R E T U R N
A IR
O P E N IN G
2 3 .7 7
3 .0 0
2 3 .7 7
2 .0 0
S U P P L Y
A IR
O P E N IN G
8 7 .0 0
1 1 .3 9
2 .0 0
1 1 7 .5 0
1 1 .0 0
1 4 .0 0
A
A
B A S E R A IL
(Y O R K U N IT )
C U R B G A S K E T
B A S E R A IL C R O S S -S E C T IO N
1 .2 5 "
1 .7 5 "
2 " X 4 "
N A IL E R
4 .6 3 "
(1 4 .0 0 )
1 4 G A . G A L V S T E E L
R O O F C U R B
2 .5 0 "
1 .5 0 "
2 .0 0 "
S E C T IO N "A -A "
FIGURE 38 - FULL ROOF CURB MODEL 1RC0455F
Unitary Products Group
87
036-21091-004-B-0205
GUIDE SPECIFICATIONS - YORK
MILLENNIUM 25, 30, & 40 TON UNITS
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility. Introducing
the YORK Millennium 25, 30, & 40 ton rooftop line - units
designed to provide peak performance and value both today
and for years to come. Millennium units are manufactured at
an ISO 9001 registered facility, and each rooftop is completely computer-run tested prior to shipment. The Millennium
is designed to be flexible enough to meet your needs today
and in the future. The true value of York's Millennium is that it
can be designed to fit any need, from cooling only, constant
volume applications to variable air volume systems with variable frequency drive.
NFPA-90A regulations for smoke and flame spread ratings.
The cabinet corner post and the intermediate side supports
shall be 16 gauge steel. All access doors shall be 18 gauge
on the exterior surfaces, and 20 gauge on the interior. Floor
shall be 18 gauge, and 24 gauge. All serviceable sections
shall have hinged access doors with latches on both sides of
the unit. All access doors shall be constructed of 20 gauge
steel on the outside, with 24 gauge on the inside. Each door
shall seal against a rubber gasket to prevent air and water
leakage. The roof shall be double wall, with 18 gauge on the
external surface and 24 gauge on the interior. The roof shall
be formed with a 45 degree drip lip overhanging the sidewalls
to prevent precipitation drainage from streaming down the
side of the unit. Roof sections shall be connected together via
integral channels fastened with screws and sealed with rubber gasketing. Each fastened seam shall be further protected
by a sheet metal channel covering the full length of the gasket surface, making a completely water tight seal.
DESCRIPTION
SUPPLY AIR SYSTEM
Supply York Millennium packaged rooftop system in accordance with the capacities in the plans. Units shall be rated by
the manufacturer at a minimum (30/40 Ton units: 9.5 EER /
25 Ton units: 10 EER) according to ARI 360. Units shall be
shipped in a single package, fully charged with R-22 refrigerant. The manufacturing facility shall be registered under ISO
9001 Quality Standards for Manufacturing. Units shall carry
both ETL and CGA safety approval ratings. Tags and decals
to aid in the service or indicate caution areas shall be provided. Installation and maintenance manuals shall be supplied with each unit. Units shall be capable of providing
mechanical cooling down to 40°F (0°F with low ambient kit).
Unit shall be capable of starting and running at 120°F. Unit
electric and gas connections shall be either through the curb
or the side of the unit.
SUPPLY AIR FAN
CONSTRUCTION
OPTIONAL
GENERAL
Base
The base rail shall be constructed of 12 gauge galvanized
steel, extending the full perimeter of the unit. All components
shall be supported from the base, and the base shall include
integral lifting lugs. The unit base rail shall overhang the roof
curb for water runoff and shall have a fabricated recess with a
continuous flat surface to seat on the roof curb gasket, providing a positive, weather tight seal between the unit and the
curb.
Casing
The unit cabinet shall be double wall construction to provide
both maximum resistance to bacterial growth in the air stream
and superior structural integrity. All sheet metal shall be G90
mill galvanized sheet metal, formed and reinforced to provide
a rigid assembly. Sheet metal shall be cleaned in an alkaline
and zinc phosphate bath, and the exterior surfaces shall be
coated with a 1.5 mil powder paint, capable of withstanding
1000 salt spray hours in accordance with ASTM B-117. The
unit shall be insulated with 1-1/2," 1 pound fiberglass insulation between the two sheet metal skins. Insulation shall meet
88
Fans shall be centrifugal type, statically and dynamically balanced in the factory. Fan wheels shall be designed for continuous operation at the maximum rate of fan speed and motor
HP. The fan and motor assembly shall be mounted on a common base to allow consistent belt tension with no relative
motion between the fan and motor shafts. The entire assembly shall be isolated from the unit base with 1" (or 2" optional)
deflection springs. The fan discharge shall be connected to
the cabinet through a reinforced neoprene flexible connection
to eliminate vibration transmission from the fan to the unit
casing. Fans shall be double-width, double-inlet with forward
curved blades. Fan wheels shall be a minimum of Class II
construction.
On variable air volume units without variable frequency
drives, fans shall be provided with heavy gauge, corrosion
resistant blades, with zinc-plated steel inter-locking operating
mechanism. Both inlet vanes must operate from a single
shaft and be synchronized for precise control.
Units equipped with variable frequency drive on supply fan
must be controlled by a duct static transducer providing a 210 VDC signal to the drive. Supply fan variable frequency
drives shall have factory option of being equipped with a
manual drive bypass.
BEARINGS AND DRIVES
Bearings shall be self-aligning pillow-block re-greasable ball
bearings with an average life expectancy of 200,000 hours.
Grease fittings shall be accessible through access doors. Fan
motors shall be NEMA designed, Standard efficiency (option,
Hi-efficiency) ball bearing type with electrical characteristics
and horsepower as specified. Motors shall be 1750 RPM,
open drip proof type. The motor shall be located within the
unit on an adjustable, heavy steel base. All fan motor drives
Unitary Products Group
036-21091-004-B-0205
shall be selected for a minimum service factor of 1.2 and
have fixed pitched sheaves.
dampers will open relative to the building pressure. The
opening pressure shall be adjustable.
AIR FILTERING SYSTEM
Exhaust Air Fans (Optional)
All filter holding frames shall be of heavy duty construction
designed for industrial applications. All filters shall be either
side accessible or front loading with access doors provided
on both sides of the filter section. All filter media shall be
Class II listed under UL Standard 900. Filter efficiencies shall
be rated in accordance with ASHRAE Standard 52-76 2"
Throwaway Filters with fiberglass media multiple shall be
standard
OPTIONAL
Two inch pleated, throwaway filters with 30% efficiency. Rigid
filters shall be high performance, expanded area, disposable
type filters. Rigid filter sections shall be preceded by a 2
throwaway prefilter assembly. Filter efficiency shall be 95%
(Option: 65%) based on ASHRAE Standard 52-76.
AIR INLET SYSTEM
General - forward curved centrifugal fan(s) shall be installed
in the return air plenum for positive power exhaust. Fans shall
be on a common shaft, driven by a single motor. The fans,
motors and drives shall be of the same quality and design as
specified for the Supply Air Fan, except the fans shall be
Class I. Fans shall be capable of exhausting up to 100% of
the nominal CFM of the unit. Non-modulating Exhaust - Units
with non-modulating power exhaust shall have a barometric
relief damper to prevent outside air from entering in the off
cycle. The fans shall cycle on and off with building pressure.
Modulating Operation - The fans shall be capable of modulating the amount of air from 0% to 100% of nominal CFM. Modulation shall be through discharge dampers or variable
frequency motor speed modulation. Dampers or VFD shall be
controlled by static pressure in the conditioned space or
return air duct.
ENERGY RECOVERY VENTILATION (FIELD
INSTALLED OPTION)
General
Outside Air inlet openings shall be covered by a factory
installed rain hood permanently attached to the cabinet to
prevent windblown precipitation from entering the unit. The
rain hoods on the front and back of the unit shall be rotated
into the cabinet and secured for shipment so that upon installation they need only be rotated upwards and screwed into
place. The outside air hood shall contain a removable and
cleanable filter with an efficiency rating of 50% based on
ASHRAE 52- 76. All damper assemblies shall be of low leak
design. Damper blades shall be fabricated from a minimum of
16 gauge galvanized steel. Blade ends and edges shall be
covered with vinyl seals. Damper shafts shall be fabricated
from solid steel and mounted in the frame with bronze bearings. On all units not equipped with an economizer, an option
shall be available for a manually adjustable outside air
damper shall be capable of admitting 0-25% outside air.
General
The packaged rooftop unit shall have attached at the jobsite a
powered exhaust combined with an air intake through a rotating energy receovery wheel, which captures sensible and
latent heat from the exhaust air stream and returns it to the
incoming air stream. The energy recovery module will be contained in a separate enclosure designed to attach to the end
of the Millennium packaged rooftop unit equipped with Simplicity® Elite™ control.
The Energy Recovery Ventilation module will be capable of
exhausting up to 8,000 (13,000) CFM.
Control parameters for the ERV will be preset in the unit control.
HEATING SYSTEM
Economizer (Optional)
Gas-fired Heating Section (Optional)
An economizer shall have outdoor air and return air dampers
that are interlocked and positioned by fully modulating, solid
state damper actuators. The actuators shall be spring loaded
so that the outside air damper will close when power to the
unit is interrupted. The operation of the economizer shall be
fully integrated into the cooling control system. The economizer shall be available for control via a dry bulb sensor
(Optional: single or dual enthalpy sensors).
RELIEF SYSTEM (Optional)
All units with relief must have an economizer.
Barometric Relief (Optional)
Building air exhaust shall be accomplished through barometric relief dampers installed in the return air plenum. The
Unitary Products Group
One or more gas-fired heating modules shall be installed to
provide the heating requirements per the schedule shown on
the plans. The heat exchanger shall be of tubular design.
Tubes shall be 2 1/4 OD and constructed of minimum 20
gauge, G160 aluminized steel (1.6 mil aluminum silicone
alloy) for corrosion resistance (Optional: 409 Stainless Steel).
Flue baffles shall be made of 430 stainless steel. Each gasfired heat module shall have an induced draft combustion fan
with energy efficient intermittent pilot spark ignition and
redundant main gas valves with pressure regulator. Units with
standing spark ignition shall not be acceptable. An induced
draft fan shall be provided to maintain a positive flow of air
through each tube, to expel the flue gas and to maintain a
negative pressure within the heat exchanger relative to the
conditioned space. Induced draft fans shall be direct-drive.
One (1) high limit controller per heating module, with auto-
89
036-21091-004-B-0205
matic reset to prevent the heat exchanger from operating at
an excessive temperature will be installed. A centrifugal
switch on the induced draft fan motor shaft must be provided
to prevent ignition until sufficient air flow is established
through the heat exchanger. Secondary airflow safety shall
be provided by rollout switch protection. The rollout switch
shall discontinue furnace operation if the flue becomes
restricted. Units shall ship with an external flue to be shipped
in the unit and mounted on the job site. The flue shall discharge products of combustion above the unit, preventing
recycling of corrosive combustion gases back through the
heat exchanger. Gas heating sections shall be both ETL and
CGA approved to both US and Canadian safety standards.
Electric Heating Section
An electric slip-in heater shall be installed within the rooftop
unit to provide the heating requirements per the schedule
shown on the plans. The electric heater shall be wired in such
a manner as to provide two equal steps of capacity (80 and
108 kW) or a single step of capacity (40 kW). The furnace
shall be an industrial grade design using an open coil(s)
made of the highest grade resistance wire containing 80%
nickel and 20% chromium. The resistance coil(s) shall be
adequately supported in the air stream using ceramic bushings in the supporting framework. Terminals of the coil(s)
shall be stainless steel with high temperature ceramic bushings. The primary high temperature protection shall be an
automatic reset type thermal cut out. Secondary protection
shall be an automatic reset type thermal cut out. Secondary
protection shall be a replaceable thermal link. The operation
of the electric heater shall be an integral part of the roof top
control system. Power connection to the strip heater shall be
through the single power point connection for the entire unit.
Electric heat shall be ETL certified to both US and Canadian
safety standards.
Hot Water Heating Coil
The manufacturer shall furnish and factory install a hot water
coil in the rooftop units, as described in the following specifications. Water coil capacities and pressure drops shall be
certified in accordance with ARI Standard 410. The hot water
coil shall have eight fins per inch, 2 tubes per circuit, and and
2" inlet and outlet connection. Primary surface shall be 1/2"
OD copper tube, staggered in direction of airflow. Tubes shall
be mandrel expanded to form fin bond and provide burnished, work-hardened interior surface. Return bends shall
be die formed and silver-brazed to tubes. Headers shall be of
heavy seamless copper tubing, silver-brazed to tubes. Connections shall be of red brass, with male pipe threads, silver
brazed to headers. Connections also have 1/4" FPT drain
plug on each connection. Extended surface shall consist of
die-formed, continuous, aluminum fins with formed channels,
and surface treatment to minimize moisture carry-over. Fins
shall have fully drawn collars to accurately space fins, and to
form a protective sheath for the primary surface. A structural
galvanized steel casing shall protect the coil. Tube sheets on
each end shall have drawn collars to support tubes. An intermediate coil support shall be provided. The coil shall be circuited to provide free draining and venting, through one vent
and drain. Completed coil, including headers, connections
90
and return bends shall be tested with 325 pounds compressed air under water. Coils shall be designed for operation
at 250 psig design working pressure.
Steam Heating Coil
The manufacturer shall furnish and factory install a steam
heating coil in the rooftop units, as described in the following
specifications. Steam coil capacities and pressure drops shall
be certified in accordance with ARI standard 410. The steam
coil shall be constructed in the non-freeze style. The steam
coil shall have six fins per inch, and 2" inlet, and 1 1/2" outlet
connection. Tubes shall be 1" OD seamless copper tubing
with a minimum wall thickness of 0.035" and expanded into
the fin collars for maximum fin-tube bond. Inner distributing
tubes shall be 5/8" OD seamless copper tubing with a minimum wall thickness of 1/4". The copper to copper joints shall
be joined with high temperature, silver solder. Corrugated fins
with integral spacing collars shall cover the entire tube surface. Headers shall be constructed of seamless copper. The
header tube holes shall be extruded providing better tube to
header contact for a stronger braze connection. All header
connections shall be of red brass or steel, with male pipe
threads and silver braze to headers. Casing shall be 16
gauge galvanized steel. Chafing shall be prevented by
extruding and flaring the holes in the tube sheet and intermediate tube sheet. The core shall be pitched in the direction of
the condensate connection for proper drainage. The completed coil (including headers and connections) shall be
tested underwater with 325 lbs. compressed air to ensure a
leak free coil.
REFRIGERATION SYSTEM
Units shall have two (25 ton), three (30 ton) or four (40 ton)
independent refrigerant circuits for maximum load-matching
capability. Each refrigerant circuit shall be controlled with a
balance-port thermal expansion valve for maximum control at
low load conditions.
Evaporator Coils
Evaporator coils shall be direct expansion type with intertwined circuiting to assure complete coil face activity during
part load operation. Coil tubes shall be 3/8 OD copper, internally enhanced tubes. Fins shall be enhanced aluminum
mechanically expanded to bond with the copper tubes. Coil
casing shall be fabricated from heavy gauge galvanized
steel. All coils shall be pressure tested at a minimum of 450
PSIG. A stainless steel drain pan shall be provided under the
entire length and width of the evaporator coil, including all
return bends. The main drain pan shall be sloped a total of 1/
4 per foot towards the drainage point. Main drain pan shall be
easily cleanable in the field. The condensate drain opening
shall be flush with the bottom of the drain pan to allow complete drainage. Coils in excess of 48 high shall have an intermediate drain pan, also fabricated of stainless steel
extending the entire finned length of the coil to provide better
water drainage. Drainage from the intermediate drain pan
shall be to the primary drain pan. OPTIONAL: Evaporator
coils shall be protected by the Technicoat 10-1 four coat process. Coils shall be dipped in a phenolic coating, which pro-
Unitary Products Group
036-21091-004-B-0205
vides substantial resistance to corrosion of aluminum and
copper.
CONTROLS
GENERAL DESCRIPTION
Compressors
Units shall have two (25 ton), three (30 ton) or four (40 ton)
industrial duty hermetic scroll compressors, independently
piped and charged. Compressors shall have an enlarged liquid carrying capacity to withstand rugged operating conditions. Compressor frame shall be cast iron, with cast iron
fixed and orbiting scrolls. Each compressor shall feature a
solid state protection module, designed to protect the compressor from over temperature and overcurrent conditions.
Each compressor shall include the following safety and convenience devices: replaceable suction screen, discharge line
check valve, and oil sight glass. Compressors shall be vibration isolated from the unit, and installed in an easily accessible area of the unit.
Condenser Coils
Condenser coils shall have 3/8 seamless copper tubes,
arranged in staggered rows, mechanically expanded into aluminum fins. Coils shall be protected from hail damage with a
V configuration, with individual flat coils rotated 30 from the
vertical plane for each condensing circuit. Condensing coils
shall have an integral subcooler for more efficient, stable
operation. OPTIONAL: Condenser coils shall be protected by
the Technicoat 10-1 four coat process. Coils shall be dipped
in a phenolic coating, which provides substantial resistance
to corrosion of aluminum and copper.
Equipment with Simplicity® as standard shall be factory runtested through the control, after the test is complete; there will
be no wires to re-connect. All control wiring points shall be
tested and verified through communication.
The control shall be UL or CSA recognized. The control shall
be manufactured in a manufacturing facility that is certified to
ISO 9001.
COMPRESSOR CONTROL
The control shall have a five-minute Anti-Short Cycle Delay to
prevent excessive compressor cycling. The control shall
have a three-minute minimum run time to insure that oil gets
returned to the compressor each time it starts. The minimum
runtime shall be programmable up to 10 minutes.
The control shall monitor the High Pressure switch, the Low
Pressure switch, and the Compressor Overloads separately
for each refrigeration circuit. The control shall have a 30 second Low Pressure Switch bypass when it starts any compressor.
A hard compressor lockout shall occur if the control detects
the same switch trip three times in a two-hour window, which
starts when the first trip occurs. On the first and second trips,
the control will turn the compressor off and wait five-minutes
after the switch re-closes, before restarting the compressor.
Condenser Fans and Motors
Condenser fans shall be direct drive, propeller type, discharging vertically. Condenser fan motors shall be 3 phase, totally
enclosed air over (TEAO) type, with built in thermal overload
protection.
Refrigerant Piping
All interconnecting piping between refrigeration components
shall be copper tubing with brazed joints. Each refrigerant circuit shall be equipped with liquid line filter drier, and moisture
indicating sight glass. Each circuit shall also have both high
and low pressure switches installed on either side of the compressor and include shrader depressors for replacement of
the pressure switches without removing charge. All small
diameter distributor tubing to the evaporator coil shall be protected by polyurethane sleeves over the length of the tubing
to prevent the tubes from copper-to-copper contact during
shipment or operation.
Hot Gas Bypass (Optional on CV; standard on VAV)
Unit shall have hot gas bypass factory installed on the lead
compressor.
The control shall be capable of operating both compressors
and the economizer when there is a call for both stages of
cooling.
The control shall have a means of locking out mechanical
compression below a programmable low ambient trip point.
This must be done without adding extra components to the
unit.
The control shall have a means of locking out the mechanical
compression when the economizer is operating in free cooling mode without additional components
The control shall have a means of starting the compressor
before the indoor Fan comes on when operating with a Thermostat in the AUTO FAN mode.
FAN CONTROL
The control shall have fully adjustable Fan ON and Fan OFF
delays for both Heating and Cooling settable at the control or
via communication.
The control's default Fan OFF delay for Cooling shall be 30
seconds to take advantage of the remaining capacity in the
coil after the compressor has been turned off.
Unitary Products Group
91
036-21091-004-B-0205
The control shall lock on the Fan if the high temperature limit
trips three times in one hour of operation.
so when the Smoke Detector trips, the control will shut down
the unit immediately.
The control will have a software programmable Fan Mode
Switch for Auto operation or Continuous operation.
The control will have low voltage protection for the contactors
and will not energize a contactor if the voltage is below 19.2
VAC, to insure contactor pull-in. If the control has a compressor contactor energized when the voltage drops, it shall not
de-energize the contactor until the voltage drops below 16
VAC, which is the drop out voltage for most contactors.
When the Fan is in the Continuous mode, it will run continuously during the occupied schedule and in the Auto mode
when in an unoccupied schedule.
The control shall be capable of operating the fan without a G
or fan signal from the thermostat.
EQUIPMENT CONTROL FEATURES
The control shall be capable of communicating on the Standard Open protocol, Modbus® RTU.
The register data for the Modbus® must be publicly available
and open.
Monitoring Software shall be provided at no cost. The monitoring software shall have a flashing icon when any unit wired
to the computer has an alarm. Clicking the flashing icon shall
display the fault code and the details of the fault.
The networking setup shall be completed by connecting a
three-wire daisy chain cable to each unit, then powering all
the units up and pushing a button on each control. There
shall not be any dipswitches to configure the network
address.
The control shall use a communication driver that is capable
of having 64 nodes on the bus before a repeater is needed.
The control shall use non-volatile memory to store the last
five alarms. There shall be a single button to push to recall
these last five alarms. The alarms shall be stored first in last
out. The first flash code shall be the last alarm that occurred.
There shall be a button press sequence to clear the alarms in
non-volatile memory.
The control shall have a button to reset compressor lockouts
without powering the unit down.
The control shall have a button to clear compressor AntiShort Cycle Delays. When this button is pressed it will only
clear the Anti-Short Cycle Delays for one cycle only and not
permanently.
The control will be compatible with any BAS (Building Automation System). Any BAS shall be able to control the equipment when wired to the control's Thermostat Terminal Strip.
The control shall have loading of at least 25 milliamps on all
thermostat inputs for controllers and thermostats that use output TRIACs.
The control shall have a means of low ambient control without adding any additional components. The control shall
have a means of cycling the compressor on for 10 minutes
and off for 5 minutes to defrost the indoor coil when the out
side ambient is below a low ambient switch point without adding additional components.
The control shall have a means of storing compressor run
time. This data shall be available through communication.
The control shall have the ability to clear this data when a
compressor is replaced.
The control shall have the ability to store a name of at least
26 characters in length. The control will leave the factory with
the serial number of the equipment it is in, stored in non-volatile memory in the Name location.
The control shall have the ability to store the model number
of the equipment of at least 26 characters in length. The control will leave the factory with the model number of the equipment it is in, stored in non-volatile memory.
The control shall have the ability to store the serial number of
the equipment of at least 26 characters in length. The control
will leave the factory with the serial number of the equipment
it is in, stored in non-volatile memory.
The control shall not power the contactors through the thermostat wiring. Dropping voltage over the thermostat wiring
causes chattering contactors when the contactors are powered in this manner.
The control will operate and monitor up to 3 stages of heat
independently.
The control shall monitor the Gas Heat operation in the heating mode. It shall monitor the gas valve when there is a call
for heating. The control shall alarm when there is a call for
heat and no gas valve voltage after 5 minutes.
There will only be one control board for this series of units, for
both CV and VAV operation.
COMFORT CONTROL FEATURES
The control will be installed and tested at the factory where
the equipment is assembled.
The control shall have a Smoke Detector Shutdown input on
the board. The control shall be powered through this input,
92
Unitary Products Group
036-21091-004-B-0205
The control will use a Wall Senor that has a means of overriding the unoccupied mode for a programmable amount of
time.
The Unoccupied Override time will be programmed in minutes up to 4 hours.
The control will use a Wall Sensor that has a warmer/cooler
dial so the occupants can offset the programmed setpoint by
a programmed amount between 1 and 5 degrees.
The control will have a Supply Air Sensor as standard.
The control will have a Return Air Sensor as standard.
The control will have an Outside Air Sensor as standard.
The control will use the Return Air Sensor in place of the
Space Sensor if the Space Sensor fails for any reason, the
control will have a 365 day Real Time Clock.
The control will have programmable limits when offsetting the
Operating Setpoint to control Humidity.
The control must be able to lockout Cooling below a programmable Outside Air Temperature Setpoint.
The control will be able to lockout Heating above a programmable Outside Air Temperature Setpoint.
The control will have a Space Temperature Alarm.
The control will have a Supply Air Temperature Alarm for
Heating and Cooling. The Alarm temperature will be programmable
The Control will be able to do a Pre-Occupancy Purge at a
Programmable Time.
The control will have a hardware Smoke-Purge input.
The control will have the ability to read a dirty filter switch
The Real Time Clock will be able to do automatic Daylight
Savings Time adjustment.
The control will have an Occupancy Schedule that allows two
different Occupied schedules per day for each of the seven
days of the week individually.
The control will have 20 Holiday Schedules, each capable of
99 days.
The control's Holiday Schedules will have a start time associated with each schedule.
The control will have the capability of reading a Fan proving
switch.
The control will have an intelligent recovery function that will
bring the space to the Occupied Setpoint just before or at the
beginning of the first Occupied schedule each day. The control will learn and apply the minimum run time required to heat
or cool the space to setpoint for the first Occupied period of a
day.
The control will have Software controllable Mode Switches
(Heat, Cool, and Fan).
The control will control the Economizer directly.
The control will be capable of operating the Economizer using
Dry Bulb, Outside Enthalpy, or Differential Enthalpy.
The control will meter and track Unoccupied Override Time
for billing purposes.
OPTIONAL ModLINC TRANSLATOR
When the control is using Enthalpy to control the Economizer,
it will also have an Outside Air Temperature enable Setpoint.
The control will use two setpoints for Supply Air Temperature
for the Economizer operation. One will be for a small space
cooling demand and one for a large space cooling demand.
The control will have the ability to do Demand Ventilation
using one CO2 sensor.
The control will have a programmable maximum Outside Air
Damper Position for IAQ operation.
The control will have the ability to temper the ventilation air
during times when heating or cooling is not required.
The control will have the ability to offset the operating setpoint based on high Humidity in the Space.
Unitary Products Group
Overview
The ModLINC translator operates as a Modbus® Client providing an interface between a BACnet® control system and
devices that communicate using the Modbus® RTU protocol.
The ModLINC is preconfigured to provide an interface to
YORK UPG products equipped with an Intelli-Comfort or Simplicity-Elite controller and allows monitoring and control by an
ISN ConneXsys or third-party BACnet® Building Automation
System (BAS).
The ModLINC communicates using the Modbus® RTU protocol on one port and BACnet® MS/TP, which is the protocol
used by ISN ConneXsys devices, on the other port. By providing different communication protocols on the two ports,
data can be retrieved from and provided to two different systems.
93
036-21091-004-B-0205
The ModLINC mounts inside the control panel of the UPG
unit and utilizes 24 VAC power from the unit's control transformer. One port is connected to the UPG controller. The
other port must be connected to the ISN ConneXsys/BACnet® network.
The ModLINC translator is preconfigured to obtain operational data points from the controller and expose them on an
ISN ConneXsys/BACnet® network. The data can be transferred to any network device, including an ISN ConneXsys
OWS.
Field Installed Barometric Relief
This accessory is a set of barometric relief dampers and hood
used for the millennium barometric relief option that is fully
assembled for mounting to return ductwork. This accessory is
intended for use on horizontal return applications.
Programmable thermostat, with or without remote sensor (required for constant volume units)
Provides 2 Heat/4 Cool control and 7 day programming.
Remote Wall Mounted Temperature Sensors
"The ModLINC device is primary a control offered and configured by York's ESG (Engineering Systems Group). The
device is designed to tie into and function with the ISN ConneXsys system. The device can be used with other BACnet®
MS/TP systems, but a qualified controls contractor must be
involved. UPG cannot support the ModLINC device beyond
its hardware functionality and cannot guarantee functionality
with the ISN or other third party BAS device."
Please refer to the ModLINC Installation/Application manual
Part Number 126367-UIM-A-0305.
Attractive wall mounted temperature sensors are available to
precisely control multiple or individual zone temperature.
Sensors are available without adjustment, with override and
override with programmable setpoint adjustment.
Dirty Filter Switch
A Dirty Filter pressure switch kit is available for field installation. Switches will monitor pressure drop across the units air
filters and provide an alarm when filters become dirty.
Natural gas and propane conversion kits
AVAILABLE ACCESSORIES
The following accessories shall be available:
Full perimeter and partial perimeter roof curbs
14" high roof curb with wood nailer. Roof curb covers the
entire perimeter of the unit (full curb) or that portion of the
unit, which has airflow (partial curb).
Burglar Bars
This accessory mounts in the supply and return opening of
either the full or partial perimeter curb to prevent entry into
the building through the ductwork.
94
Contains the necessary orifices and gas valve parts to convert from natural gas to propane and from propane to natural
gas.
High altitude conversion kits
These kits are required for natural gas or propane applications between 2,000 and 6,000 feet.
Energy Recovery Ventilators
8,000 and 13,000 CFM models availalbe. Great applications
involving 30% or more of required outdoor air where energy
use and comfort must be optimized.
Unitary Products Group
036-21091-004-B-0205
Unitary Products Group
95
Subject to change without notice. Printed in U.S.A.
Copyright © by Unitary Products Group 2005. All rights reserved.
Unitary
Products
Group
5005
York
Drive
036-21091-004-B-0205
Supersedes: 036-21091-004-A-0804
Norman
OK
73069