ATAD/ATAB - Adjustable Pitch Airfoil Fans
Air Moving Solutions.
axipal® adjustable pitch airfoil fans
ATAD | ATAB
CATALOG AX210
December 2012
AdjustablePitch
Models
ATAD | ATAB
Model ATAD
Arrangement 4 - Direct Drive
The ATAD Adjustable Pitch Airfoil Tubeaxial Fan is
designed for clean air applications that permit the
location of the motor in the airstream. Standard fan/
motor configuration is suitable for maximum air temperature of 104°F. Special motors are available for
higher temperature applications. Please consult the
factory for assistance.
Sizes
Available in ten sizes:
14" (035) to 49" (125) wheel diameters
Model ATAD
(Direct Drive)
Performance
Airflow to 75,600 CFM
Static pressure to 4.5" w.g.
Model ATAB
Arrangement 9 - Belt Driven
The ATAB Adjustable Pitch Airfoil Axial Fan is designed for where it is advantageous to have the motor
out of the airstream due to the presence of corrosive
or hazardous fumes, or dirt-laden, hot, or moist air.
Standard fan configuration is suitable for a maximum
temperature of 275°F.
Sizes
Available in nine sizes:
16" (040) to 49" (125) wheel diameters
Performance
Airflow to 65,100 CFM
Static pressure to 2.5" w.g.
Model ATAB
(Belt Driven)
Twin City Fan & Blower certifies that the
model ATAD and ATAB fans shown herein
are licensed to bear the AMCA Seal. The
ratings shown are based on tests and procedures performed in accordance with AMCA
Publication 211 and AMCA Publication 311
and comply with the requirements of the
AMCA Certified Ratings Program.
2
Twin City Fan Catalog AX210
ConstructionFeatures
Design Innovation
AXIPAL® fan blades have an ever-increasing airfoil
chord length from the blade root to the blade tip.
The additional chord length is placed at the leading
edge rather than the trailing edge of the blade so that
when set at an angle, the widest part of the airfoil is
at maximum rotational speed in close proximity to the
fan casing. This very wide blade tip area allows the
AXIPAL® to maximize energy transfer to the airstream
and minimize noise generation.
The blade pitch can be individually manually adjusted
while the fan is stopped. This feature allows the
user to balance the present system while affording
the flexibility of further possible pitch adjustment in
the future.
Propeller Construction
The blades are made of permanent mold A319
aluminum alloy castings for high strength and
precision. Retaining bolts hold the root of the blade
casting in position in a spherical pocket between two
stamped carbon steel hub plates. The hub center
boss is made of cast iron and is straight bored and
keyed for direct attachment to motor or fan shafts
or, in fans of 24" diameter and larger, is fitted with
a taper-lock bushing.
in the illustration above. This arrangement permits
adjustment to be made with a minimum of effort,
particularly when the motor is of large size.
Belt Driven Design
Housing
AXIPAL® housings are made of continuously welded,
heavy-gauge carbon steel with integrally rolled inlet
and outlet flanges. Integral flanges are provided with
bolt holes for bolting to fan accessories or ductwork.
Housings can be supported by bolting the integral
flanges directly to ductwork or can be provided with
bolted support legs or welded clips for mounting in
a horizontal or vertical position. After fabrication the
housing is chemically pretreated, phosphatized, and
painted with two coats of air dried acrylic enamel.
Extended grease fittings and grease leads are
standardly furnished to permit relubrication of the
motor bearings at the exterior of the fan housing.
Motor leads are extended through liquid-tight conduit
to the exterior of the fan housing to facilitate wiring.
Well suited for applications where it is advantageous
to have the motor out of the airstream due to
the presence of corrosive or hazardous fumes, or
dirt-laden, hot, or moist air, Arrangement 9 fans
include the following features as standard equipment:
• Belts and driven sheave enclosed in a metal tube
protected from the airstream.
• Single jackscrew belt tension adjustment (see detail
above).
• Standard NEMA foot-mounted motors, of open
drip-proof, totally enclosed or explosion-proof
design are used on belt driven fans. Motors
are squirrel cage induction, single speed, single
winding, variable torque type for continuous duty
operation.
Standard NEMA foot-mounted motors, of open
drip-proof, totally enclosed or explosion-proof design
are used on direct drive fans. Motors are squirrel
cage induction, single speed, single winding, variable
torque type for continuous duty operation.
Adjusting Belt Tension
All belt driven units are constructed with the motor
base plate welded to the outside of the fan casing
which provides strength and rigidity. Except for very
small motors, the adjustment of the belt tension is
accomplished by means of a jackscrew as shown
©2012 Twin City Fan Companies, Ltd. All rights reserved throughout the
world. Catalog illustrations cover the general appearance of Twin City Fan
& Blower products at the time of publication and we reserve the right
to make changes in design and construction at any time without notice.
www.tcf.com
3
AdjustablePitch
Models
ATAD | ATAB
Model ATAD
Arrangement 4 - Direct Drive
The ATAD Adjustable Pitch Airfoil Tubeaxial Fan is
designed for clean air applications that permit the
location of the motor in the airstream. Standard fan/
motor configuration is suitable for maximum air temperature of 104°F. Special motors are available for
higher temperature applications. Please consult the
factory for assistance.
Sizes
Available in ten sizes:
14" (035) to 49" (125) wheel diameters
Model ATAD
(Direct Drive)
Performance
Airflow to 75,600 CFM
Static pressure to 4.5" w.g.
Model ATAB
Arrangement 9 - Belt Driven
The ATAB Adjustable Pitch Airfoil Axial Fan is designed for where it is advantageous to have the motor
out of the airstream due to the presence of corrosive
or hazardous fumes, or dirt-laden, hot, or moist air.
Standard fan configuration is suitable for a maximum
temperature of 275°F.
Sizes
Available in nine sizes:
16" (040) to 49" (125) wheel diameters
Performance
Airflow to 65,100 CFM
Static pressure to 2.5" w.g.
Model ATAB
(Belt Driven)
Twin City Fan & Blower certifies that the
type ATAD and ATAB fans shown herein are
licensed to bear the AMCA Seal. The ratings shown are based on tests and procedures performed in accordance with AMCA
Publication 211 and AMCA Publication 311
and comply with the requirements of the
AMCA Certified Ratings Program.
2
Twin City Fan Catalog AX210
ConstructionFeatures
Design Innovation
AXIPAL® fan blades have an ever-increasing airfoil
chord length from the blade root to the blade tip.
The additional chord length is placed at the leading
edge rather than the trailing edge of the blade so that
when set at an angle, the widest part of the airfoil is
at maximum rotational speed in close proximity to the
fan casing. This very wide blade tip area allows the
AXIPAL® to maximize energy transfer to the airstream
and minimize noise generation.
The blade pitch can be individually manually adjusted
while the fan is stopped. This feature allows the
user to balance the present system while affording
the flexibility of further possible pitch adjustment in
the future.
Propeller Construction
The blades are made of permanent mold A319
aluminum alloy castings for high strength and
precision. Retaining bolts hold the root of the blade
casting in position in a spherical pocket between two
stamped carbon steel hub plates. The hub center
boss is made of cast iron and is straight bored and
keyed for direct attachment to motor or fan shafts
or, in fans of 24" diameter and larger, is fitted with
a taper-lock bushing.
in the illustration above. This arrangement permits
adjustment to be made with a minimum of effort,
particularly when the motor is of large size.
Belt Driven Design
Housing
AXIPAL® housings are made of continuously welded,
heavy-gauge carbon steel with integrally rolled inlet
and outlet flanges. Integral flanges are provided with
bolt holes for bolting to fan accessories or ductwork.
Housings can be supported by bolting the integral
flanges directly to ductwork or can be provided with
bolted support legs or welded clips for mounting in
a horizontal or vertical position. After fabrication the
housing is chemically pretreated, phosphatized, and
painted with two coats of air dried acrylic enamel.
Extended grease fittings and grease leads are
standardly furnished to permit relubrication of the
motor bearings at the exterior of the fan housing.
Motor leads are extended through liquid-tight conduit
to the exterior of the fan housing to facilitate wiring.
Well suited for applications where it is advantageous
to have the motor out of the airstream due to
the presence of corrosive or hazardous fumes, or
dirt-laden, hot, or moist air, Arrangement 9 fans
include the following features as standard equipment:
• Belts and driven sheave enclosed in a metal tube
protected from the airstream.
• Single jackscrew belt tension adjustment (see detail
above).
• Standard NEMA foot-mounted motors, of open
drip-proof, totally enclosed or explosion-proof
design are used on belt driven fans. Motors
are squirrel cage induction, single speed, single
winding, variable torque type for continuous duty
operation.
Standard NEMA foot-mounted motors, of open
drip-proof, totally enclosed or explosion-proof design
are used on direct drive fans. Motors are squirrel
cage induction, single speed, single winding, variable
torque type for continuous duty operation.
Adjusting Belt Tension
All belt driven units are constructed with the motor
base plate welded to the outside of the fan casing
which provides strength and rigidity. Except for very
small motors, the adjustment of the belt tension is
accomplished by means of a jackscrew as shown
©2012 Twin City Fan Companies, Ltd. All rights reserved throughout the
world. Catalog illustrations cover the general appearance of Twin City Fan
& Blower products at the time of publication and we reserve the right
to make changes in design and construction at any time without notice.
www.tcf.com
3
Accessories
MountingArrangements
Curb Base
A square-to-round transition piece to convert an axial
fan to a roof ventilator when mounted between a roof
curb and the fan inlet flange. A stack cap or other
device is necessary for weather protection in installations of this type.
Shaft Seal
An elastomeric viton rotary seal rides against a heavy
Teflon, bolted-in-place, wear plate which surrounds
the shaft of belt driven fans to provide protection of
the shaft and bearings when handling dirty, wet or
corrosive air. Note: The seal does not make the installation gas-tight and is not appropriate in ambient
temperatures above 250°F.
Curb Base
Motor Cover
A vented cover bolted to the exterior of a belt driven fan to provide drip-proof protection of the motor
and drive tube when units are installed outdoors in
horizontal or vertical configuration. Note: The standard
belt guard is not provided when a motor cover is
specified.
Shaft Seal
Motor Cover
Following are the mounting arrangements for AXIPAL®
fans. Please specify the mounting arrangement
required at time of order.
Example 2: For a direct drive fan with
mounting arrangement horizontal floor
mounted, specify “support legs.”
Example 1: For a belt driven fan with mounting
arrangement horizontal floor mounted and motor on
top, specify “top.”
Example 3: For a belt driven fan with mounting
arrangement floor down discharge, specify “SA2”.
Belt Driven Fans
Horizontal Floor Mounted
(view from outlet)
Standard (Std)
Inlet Bell
Opposite Standard, (Opp Std)
Requires F-2 Motor
Vertical Floor & Ceiling Mounted
AIRFLOW
AIRFLOW
AIRFLOW
Stack Cap
A backdraft damper assembly bolted to the fan discharge flange in vertical upblast rooftop installations.
Ideally this device should be selected to handle discharge velocities ranging from 1800 to 3000 FPM and
will add approximately 1∕8" pressure drop to system.
Top
AIRFLOW
Floor Up
Discharge (SA1)
Floor Down
Discharge (SA2)
Ceiling Down
Discharge (SA3)
Ceiling Up
Discharge (SA4)
Horizontal Ceiling Mounted
(view from outlet)
A spun steel aerodynamic inlet bell minimizes inlet
losses on installations where ductwork does not precede the fan.
Stack Cap
Inlet Bell
Right Hand (A9)
Left Hand (A10)
Requires F-2 Motor
Bottom
(A11)
Top
(A12)
Direct Drive Fans
Horizontal Floor
Ceiling Horizontal
Discharge
Vertical Floor & Ceiling Mounted
AIRFLOW
AIRFLOW
AIRFLOW
AIRFLOW
Support Legs
4
Twin City Fan Catalog AX210
A13
Floor
Down
Discharge
(A5)
Floor
Up
Discharge
(A6)
www.tcf.com
Ceiling
Up
Discharge
(A7)
Ceiling
Down
Discharge
(A8)
5
Accessories
MountingArrangements
Curb Base
A square-to-round transition piece to convert an axial
fan to a roof ventilator when mounted between a roof
curb and the fan inlet flange. A stack cap or other
device is necessary for weather protection in installations of this type.
Shaft Seal
An elastomeric viton rotary seal rides against a heavy
Teflon, bolted-in-place, wear plate which surrounds
the shaft of belt driven fans to provide protection of
the shaft and bearings when handling dirty, wet or
corrosive air. Note: The seal does not make the installation gas-tight and is not appropriate in ambient
temperatures above 250°F.
Curb Base
Motor Cover
A vented cover bolted to the exterior of a belt driven fan to provide drip-proof protection of the motor
and drive tube when units are installed outdoors in
horizontal or vertical configuration. Note: The standard
belt guard is not provided when a motor cover is
specified.
Shaft Seal
Motor Cover
Following are the mounting arrangements for AXIPAL®
fans. Please specify the mounting arrangement
required at time of order.
Example 2: For a direct drive fan with
mounting arrangement horizontal floor
mounted, specify “support legs.”
Example 1: For a belt driven fan with mounting
arrangement horizontal floor mounted and motor on
top, specify “top.”
Example 3: For a belt driven fan with mounting
arrangement floor down discharge, specify “SA2”.
Belt Driven Fans
Horizontal Floor Mounted
(view from outlet)
Standard (Std)
Inlet Bell
Opposite Standard, (Opp Std)
Requires F-2 Motor
Vertical Floor & Ceiling Mounted
AIRFLOW
AIRFLOW
AIRFLOW
Stack Cap
A backdraft damper assembly bolted to the fan discharge flange in vertical upblast rooftop installations.
Ideally this device should be selected to handle discharge velocities ranging from 1800 to 3000 FPM and
will add approximately 1∕8" pressure drop to system.
Top
AIRFLOW
Floor Up
Discharge (SA1)
Floor Down
Discharge (SA2)
Ceiling Down
Discharge (SA3)
Ceiling Up
Discharge (SA4)
Horizontal Ceiling Mounted
(view from outlet)
A spun steel aerodynamic inlet bell minimizes inlet
losses on installations where ductwork does not precede the fan.
Stack Cap
Inlet Bell
Right Hand (A9)
Left Hand (A10)
Requires F-2 Motor
Bottom
(A11)
Top
(A12)
Direct Drive Fans
Horizontal Floor
Ceiling Horizontal
Discharge
Vertical Floor & Ceiling Mounted
AIRFLOW
AIRFLOW
AIRFLOW
AIRFLOW
Support Legs
4
Twin City Fan Catalog AX210
A13
Floor
Down
Discharge
(A5)
Floor
Up
Discharge
(A6)
www.tcf.com
Ceiling
Up
Discharge
(A7)
Ceiling
Down
Discharge
(A8)
5
ATAD, Arrangement 4 - Direct Drive
Present methods of testing fans provide
accurate, dependable performance data;
however, information available for designing
systems is necessarily based on averages.
Therefore, a certain amount of “rounding off”
of design figures is a reasonable approach
and will produce a practical air handling system
design. Most engineers prefer the static pressure
or friction loss method of calculation.
• If the fan is at the beginning of the duct, then an
inlet bell should be used and no entrance loss is
calculated.
The fan is usually located somewhere within the
system; therefore, it is only necessary to figure the
entrance loss and the duct friction loss, then select
the fan directly from the tables. This method assumes
that the duct size from the outlet of the fan to where
the air is released to atmosphere is essentially the
same as the diameter of the fan.
Some systems are designed using total pressure (TP).
Using the following formulas, the total pressure can
be calculated.
• If the fan is at the end of the duct, then the
entrance loss and duct friction are calculated and
this is the fan static pressure.
• If an outlet cone is used and there is a static
regain, the regain can be added to the static
pressure.
(AREACFMx 4005)
CFM
x Density in lbs.per ft
VP = (
AREA x 1096.7)
2
2
NOTE: This formula is used only
for density at standard air, 0.075
lbs./ft3, 70°F and sea level.
3 NOTE: This formula is used when
density is other than standard.
TP = VP + SP
OV =
CFM
(AREA
)
Where:
VP =
SP =
TP =
OV =
AREA
Velocity pressure, IWG
Static pressure, IWG
Total pressure, IWG
Fan outlet velocity, FPM
= Fan outlet area, Ft2
Temperature and Altitude Correction
The performance tables in this catalog are based on
standard air density: 70°F at sea level (0.075 lbs./
cu.ft. density). The fan performance tables provide
the fan RPM and brake horsepower requirements for
the given CFM and static pressure, at standard air
density.
6
0
1000
2000
29.92
1.293
1.152
1.039
1.000
0.946
0.869
0.803
0.747
0.697
0.654
0.616
0.582
0.552
0.525
0.500
28.86
1.247
1.111
1.003
0.964
0.912
0.838
0.774
0.720
0.672
0.631
0.594
0.561
0.532
0.506
0.482
27.82
1.201
1.071
0.967
0.930
0.880
0.808
0.747
0.694
0.648
0.608
0.573
0.542
0.513
0.488
0.465
Size 035A ATAD – 1750 RPM
When the fan performance is not at standard
conditions, the performance must be converted
to standard conditions before entering the fan
performance tables. The fan performance is converted
to standard conditions by using the “Temperature and
Altitude Density Ratio” from the table shown below.
ALTITUDE IN FEET ABOVE SEA LEVEL
3000
4000
5000
6000
7000
8000
BAROMETRIC PRESSURE IN INCHES OF MERCURY
26.82
25.84
24.90
23.98
23.09
22.22
1.159
1.116
1.076
1.036
0.997
0.960
1.032
0.995
0.959
0.923
0.889
0.856
0.932
0.897
0.864
0.833
0.801
0.772
0.896
0.864
0.832
0.801
0.772
0.743
0.848
0.818
0.787
0.758
0.730
0.703
0.770
0.751
0.723
0.696
0.671
0.646
0.720
0.694
0.668
0.643
0.620
0.596
0.669
0.645
0.622
0.598
0.576
0.555
0.624
0.604
0.580
0.558
0.538
0.518
0.586
0.565
0.544
0.524
0.505
0.486
0.552
0.532
0.513
0.493
0.476
0.458
0.522
0.503
0.484
0.466
0.449
0.433
0.495
0.477
0.459
0.442
0.426
0.410
0.470
0.454
0.437
0.421
0.405
0.390
0.448
0.432
0.416
0.400
0.386
0.372
Twin City Fan Catalog AX210
1/8"
CFM
035A307
035A312
035A317
035A322
035A327
035A332
035A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
1/12 783
1/12 1021
1/8
1287
1/8
1505
1/6
1749
1/4
1912
1/4
2049
035A607
035A612
035A617
035A622
035A627
035A632
035A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
1/12 795
1/8
1137
1/6
1397
1/4
1661
1/4
1939
1/2
2174
1/2
2423
035 A 3 17 ATAD 1750 1/8
Wheel Dia. (cm)
Wheel Design
No. Blades
Blade Angle (Degrees)
Fan Type
Fan RPM
Motor HP
Outlet Area = 1.04 ft2
CU. FT. PER MIN. & HP @ STATIC PRESSURE
SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG56
0.06 492 0.06
0.08 785 0.08
0.10 1056 0.11
0.13 1256 0.13
0.17 1487 0.18
0.22 1615 0.21 1190 0.20
0.27 1728 0.26
6-BLADE
Fan Efficiency Grade = FEG56
0.09 618 0.09 410 0.08
0.12 1000 0.13 670 0.12
0.15 1262 0.16 1085 0.17
0.19 1524 0.20 1353 0.22
0.25 1788 0.26 1604 0.27
0.30 1998 0.32 1783 0.32
0.39 2218 0.39 1960 0.39
Size 035A ATAD – 3500 RPM
Temperature and Altitude Density Ratios
AIR
TEMP
°F
–50
0
50
70
100
150
200
250
300
350
400
450
500
550
600
To identify a specific fan for ordering or engineering
specifications, it is necessary to show the complete
information listed in the tables below under “catalog
number.” All performance data is available in curve
form upon request.
The model ATAD fans shown herein have been tested
in accordance with ASHRAE 51-85 and AMCA 210-85
Test Code and are guaranteed by the manufacturer
to deliver rated performance.
CATALOG NUMBER
PROP
TYPE
RPM HP
Fan Selection Formulas
VP =
Catalog Numbering System
9000
10000
15000
21.39
0.924
0.824
0.743
0.714
0.676
0.620
0.573
0.533
0.498
0.467
0.440
0.416
0.394
0.375
0.352
20.58
0.889
0.792
0.715
0.688
0.651
0.598
0.552
0.514
0.480
0.450
0.424
0.401
0.380
0.361
0.344
16.89
0.729
0.650
0.586
0.564
0.534
0.490
0.453
0.421
0.393
0.369
0.347
0.328
0.311
0.296
0.282
CATALOG NUMBER
PROP
TYPE
RPM HP
035A307
035A312
035A317
035A322
035A327
035A332
035A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
3500
3500
3500
3500
3500
3500
3500
1/2
3/4
1
1
11⁄2
2
2
035A607
035A612
035A617
035A622
035A627
ATAD
ATAD
ATAD
ATAD
ATAD
3500
3500
3500
3500
3500
3/4
1
11⁄2
2
2
PerformanceData
FanSelection
Outlet Area = 1.04 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG56
1761 0.47 1566 0.48 1348 0.48
985
0.45
2228 0.58 2042 0.60 1831 0.63 1570 0.63
2751 0.77 2574 0.81 2355 0.84 2111 0.85 1773 0.85
3194 0.99 3010 1.02 2771 1.06 2511 1.08 2175 1.07
3688 1.36 3498 1.40 3263 1.42 2973 1.43 2617 1.40
4046 1.71 3824 1.73 3547 1.73 3229 1.72 2864 1.68 2379 1.60
4359 2.14 4097 2.13 3787 2.11 3456 2.07 3053 2.00
6-BLADE
Fan Efficiency Grade = FEG56
1729 0.73 1590 0.73 1425 0.73 1236 0.71 1047 0.70
819
0.66
2390 0.90 2274 0.95 2147 0.99 2000 1.02 1806 1.04 1340 0.96
2914 1.13 2794 1.19 2665 1.25 2523 1.31 2363 1.35 2171 1.38
3450 1.43 3322 1.50 3187 1.56 3048 1.63 2894 1.68 2705 1.72
4013 1.90 3878 1.97 3733 2.04 3575 2.10 3400 2.15 3208 2.18
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
www.tcf.com
7
ATAD, Arrangement 4 - Direct Drive
Present methods of testing fans provide
accurate, dependable performance data;
however, information available for designing
systems is necessarily based on averages.
Therefore, a certain amount of “rounding off”
of design figures is a reasonable approach
and will produce a practical air handling system
design. Most engineers prefer the static pressure
or friction loss method of calculation.
• If the fan is at the beginning of the duct, then an
inlet bell should be used and no entrance loss is
calculated.
The fan is usually located somewhere within the
system; therefore, it is only necessary to figure the
entrance loss and the duct friction loss, then select
the fan directly from the tables. This method assumes
that the duct size from the outlet of the fan to where
the air is released to atmosphere is essentially the
same as the diameter of the fan.
Some systems are designed using total pressure (TP).
Using the following formulas, the total pressure can
be calculated.
• If the fan is at the end of the duct, then the
entrance loss and duct friction are calculated and
this is the fan static pressure.
• If an outlet cone is used and there is a static
regain, the regain can be added to the static
pressure.
(AREACFMx 4005)
CFM
x Density in lbs.per ft
VP = (
AREA x 1096.7)
2
2
NOTE: This formula is used only
for density at standard air, 0.075
lbs./ft3, 70°F and sea level.
3 NOTE: This formula is used when
density is other than standard.
TP = VP + SP
OV =
CFM
(AREA
)
Where:
VP =
SP =
TP =
OV =
AREA
Velocity pressure, IWG
Static pressure, IWG
Total pressure, IWG
Fan outlet velocity, FPM
= Fan outlet area, Ft2
Temperature and Altitude Correction
The performance tables in this catalog are based on
standard air density: 70°F at sea level (0.075 lbs./
cu.ft. density). The fan performance tables provide
the fan RPM and brake horsepower requirements for
the given CFM and static pressure, at standard air
density.
6
0
1000
2000
29.92
1.293
1.152
1.039
1.000
0.946
0.869
0.803
0.747
0.697
0.654
0.616
0.582
0.552
0.525
0.500
28.86
1.247
1.111
1.003
0.964
0.912
0.838
0.774
0.720
0.672
0.631
0.594
0.561
0.532
0.506
0.482
27.82
1.201
1.071
0.967
0.930
0.880
0.808
0.747
0.694
0.648
0.608
0.573
0.542
0.513
0.488
0.465
Size 035A ATAD – 1750 RPM
When the fan performance is not at standard
conditions, the performance must be converted
to standard conditions before entering the fan
performance tables. The fan performance is converted
to standard conditions by using the “Temperature and
Altitude Density Ratio” from the table shown below.
ALTITUDE IN FEET ABOVE SEA LEVEL
3000
4000
5000
6000
7000
8000
BAROMETRIC PRESSURE IN INCHES OF MERCURY
26.82
25.84
24.90
23.98
23.09
22.22
1.159
1.116
1.076
1.036
0.997
0.960
1.032
0.995
0.959
0.923
0.889
0.856
0.932
0.897
0.864
0.833
0.801
0.772
0.896
0.864
0.832
0.801
0.772
0.743
0.848
0.818
0.787
0.758
0.730
0.703
0.770
0.751
0.723
0.696
0.671
0.646
0.720
0.694
0.668
0.643
0.620
0.596
0.669
0.645
0.622
0.598
0.576
0.555
0.624
0.604
0.580
0.558
0.538
0.518
0.586
0.565
0.544
0.524
0.505
0.486
0.552
0.532
0.513
0.493
0.476
0.458
0.522
0.503
0.484
0.466
0.449
0.433
0.495
0.477
0.459
0.442
0.426
0.410
0.470
0.454
0.437
0.421
0.405
0.390
0.448
0.432
0.416
0.400
0.386
0.372
Twin City Fan Catalog AX210
1/8"
CFM
035A307
035A312
035A317
035A322
035A327
035A332
035A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
1/12 783
1/12 1021
1/8
1287
1/8
1505
1/6
1749
1/4
1912
1/4
2049
035A607
035A612
035A617
035A622
035A627
035A632
035A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
1/12 795
1/8
1137
1/6
1397
1/4
1661
1/4
1939
1/2
2174
1/2
2423
035 A 3 17 ATAD 1750 1/8
Wheel Dia. (cm)
Wheel Design
No. Blades
Blade Angle (Degrees)
Fan Type
Fan RPM
Motor HP
Outlet Area = 1.04 ft2
CU. FT. PER MIN. & HP @ STATIC PRESSURE
SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG56
0.06 492 0.06
0.08 785 0.08
0.10 1056 0.11
0.13 1256 0.13
0.17 1487 0.18
0.22 1615 0.21 1190 0.20
0.27 1728 0.26
6-BLADE
Fan Efficiency Grade = FEG56
0.09 618 0.09 410 0.08
0.12 1000 0.13 670 0.12
0.15 1262 0.16 1085 0.17
0.19 1524 0.20 1353 0.22
0.25 1788 0.26 1604 0.27
0.30 1998 0.32 1783 0.32
0.39 2218 0.39 1960 0.39
Size 035A ATAD – 3500 RPM
Temperature and Altitude Density Ratios
AIR
TEMP
°F
–50
0
50
70
100
150
200
250
300
350
400
450
500
550
600
To identify a specific fan for ordering or engineering
specifications, it is necessary to show the complete
information listed in the tables below under “catalog
number.” All performance data is available in curve
form upon request.
The model ATAD fans shown herein have been tested
in accordance with ASHRAE 51-85 and AMCA 210-85
Test Code and are guaranteed by the manufacturer
to deliver rated performance.
CATALOG NUMBER
PROP
TYPE
RPM HP
Fan Selection Formulas
VP =
Catalog Numbering System
9000
10000
15000
21.39
0.924
0.824
0.743
0.714
0.676
0.620
0.573
0.533
0.498
0.467
0.440
0.416
0.394
0.375
0.352
20.58
0.889
0.792
0.715
0.688
0.651
0.598
0.552
0.514
0.480
0.450
0.424
0.401
0.380
0.361
0.344
16.89
0.729
0.650
0.586
0.564
0.534
0.490
0.453
0.421
0.393
0.369
0.347
0.328
0.311
0.296
0.282
CATALOG NUMBER
PROP
TYPE
RPM HP
035A307
035A312
035A317
035A322
035A327
035A332
035A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
3500
3500
3500
3500
3500
3500
3500
1/2
3/4
1
1
11⁄2
2
2
035A607
035A612
035A617
035A622
035A627
ATAD
ATAD
ATAD
ATAD
ATAD
3500
3500
3500
3500
3500
3/4
1
11⁄2
2
2
PerformanceData
FanSelection
Outlet Area = 1.04 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG56
1761 0.47 1566 0.48 1348 0.48
985
0.45
2228 0.58 2042 0.60 1831 0.63 1570 0.63
2751 0.77 2574 0.81 2355 0.84 2111 0.85 1773 0.85
3194 0.99 3010 1.02 2771 1.06 2511 1.08 2175 1.07
3688 1.36 3498 1.40 3263 1.42 2973 1.43 2617 1.40
4046 1.71 3824 1.73 3547 1.73 3229 1.72 2864 1.68 2379 1.60
4359 2.14 4097 2.13 3787 2.11 3456 2.07 3053 2.00
6-BLADE
Fan Efficiency Grade = FEG56
1729 0.73 1590 0.73 1425 0.73 1236 0.71 1047 0.70
819
0.66
2390 0.90 2274 0.95 2147 0.99 2000 1.02 1806 1.04 1340 0.96
2914 1.13 2794 1.19 2665 1.25 2523 1.31 2363 1.35 2171 1.38
3450 1.43 3322 1.50 3187 1.56 3048 1.63 2894 1.68 2705 1.72
4013 1.90 3878 1.97 3733 2.04 3575 2.10 3400 2.15 3208 2.18
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
www.tcf.com
7
Size 040A ATAD – 1160 RPM
ATAD, Arrangement 4 - Direct Drive
Size 050A ATAD – 1160 RPM
Outlet Area = 1.35 ft2
CATALOG NUMBER
PROP
TYPE
RPM HP
CU.FT. PER MIN. & HP @ SP
1/8" SP
1/4" SP
3/8" SP
CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG56
3-BLADE
1/12 551 0.03
1/12 895 0.04
1/12 1133 0.06
1/12 1346 0.08
1/12 1506 0.09
1/8
1647 0.11
1/4
1742 0.13
Fan Efficiency Grade = FEG56
6-BLADE
1/12 702 0.05
1/12 1031 0.07 503 0.06
1/8
1322 0.09
1/8
1593 0.12 1236 0.12
1/6
1831 0.15 1473 0.15
1/4
2041 0.19
1/4
2253 0.23 1791 0.22
CATALOG NUMBER
PROP
TYPE
RPM HP
040A307
040A312
040A317
040A322
040A327
040A332
040A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
050A307
050A312
050A317
050A322
050A327
050A332
050A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
1/8
1/6
1/4
1/4
1/2
1/2
1/2
040A607
040A612
040A617
040A622
040A627
040A632
040A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
050A607
050A612
050A617
050A622
050A627
050A632
050A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
1/6
1/4
1/2
1/2
1/2
3/4
3/4
Size 040A ATAD – 1750 RPM
CATALOG NUMBER
PROP
TYPE
RPM HP
040A307
040A312
040A317
040A322
040A327
040A332
040A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
1/8
1/4
1/4
1/4
1/2
1/2
1/2
040A607
040A612
040A617
040A622
040A627
040A632
040A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
1/6
1/4
1/2
1/2
1/2
3/4
3/4
Outlet Area = 1.35 ft2
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG56
1215 0.11 936 0.11
1648 0.14 1426 0.15 1077 0.14
2018 0.19 1786 0.20 1462 0.20
2347 0.25 2110 0.26 1780 0.26
2628 0.31 2361 0.32 2011 0.32
2907 0.40 2590 0.40 2191 0.38
3103 0.47 2740 0.46 2324 0.44
6-BLADE
Fan Efficiency Grade = FEG56
1268
0.17 1109 0.17 918 0.17 652 0.16
1734 0.22 1599 0.23 1413 0.23 1104 0.23
2163 0.28 2034 0.30 1874 0.31 1609 0.31
2589 0.37 2446 0.39 2277 0.41 2059 0.42
2973 0.48 2811 0.50 2623 0.51 2393 0.52
3326 0.62 3135 0.64 2920 0.65 2661 0.64
3668 0.78 3465 0.79 3192 0.78 2908 0.76
Outlet Area = 2.11 ft2
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG63
3-BLADE
1860 0.12 1300 0.11
2354 0.15 1848 0.15
2797 0.19 2274 0.20
3274 0.25 2715 0.25
3729 0.33 3136 0.32
4064 0.39 3432 0.38
4313 0.47 3645 0.45
Fan Efficiency Grade = FEG60
6-BLADE
1943 0.18 1586 0.18 1030 0.17
2510 0.23 2172 0.24 1321 0.22
3117 0.29 2816 0.31 2328 0.32
3721 0.38 3410 0.40 2992 0.42
4269 0.48 3941 0.51 3458 0.52
4796 0.62 4417 0.64 3851 0.64
5209 0.76 4744 0.77 4118 0.74
Size 050A ATAD – 1750 RPM
CATALOG NUMBER
PROP
TYPE
RPM HP
050A307 050A312 050A317 050A322 050A327 050A332 050A337 ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
1/2
1/2
3/4
1
11⁄2
11⁄2
11⁄2
050A607 050A612 050A617 050A622 050A627 050A632 ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
3/4
3/4
1
11⁄2
2
2
PerformanceData
PerformanceData
ATAD, Arrangement 4 - Direct Drive
Outlet Area = 2.11 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
3146 0.39 2885 0.40 2584 0.41 2220 0.40 1664 0.36
3874 0.48 3624 0.50 3346 0.52 3011 0.53 2574 0.52 1650
0.44
4557 0.62 4296 0.65 4009 0.66 3664 0.68 3221 0.68
5289 0.84 5019 0.86 4718 0.87 4357 0.87 3856 0.86 3236
0.82
5976 1.10 5707 1.11 5397 1.12 5019 1.12 4432 1.07 3876
1.03
6513 1.35 6219 1.35 5881 1.35 5470 1.34 4885 1.29 4333
1.23
6937 1.62 6605 1.60 6227 1.59 5780 1.56 5238 1.53 4474
1.42
Fan Efficiency Grade = FEG60
6-BLADE
3161 0.60 2985 0.62 2773 0.62 2534 0.62 2267 0.62 1942 0.60
3989 0.74 3833 0.77 3652 0.79 3422 0.81 3146 0.82 2771 0.81
4904 0.96 4748 0.99 4576 1.03 4376 1.06 4135 1.09 3847 1.11
5829 1.24 5662 1.28 5479 1.32 5274 1.36 5032 1.39 4755 1.42
6663 1.61 6491 1.65 6301 1.69 6086 1.72 5818 1.76 5496 1.78 4716
1.75
7491 2.09 7293 2.12 7075 2.15 6826 2.18 6516 2.20
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Size 040A ATAD – 3500 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
040A307
040A312
040A317
040A322
ATAD
ATAD
ATAD
ATAD
3500
3500
3500
3500
1
11⁄2
11⁄2
2
040A607
040A612
040A617
ATAD
ATAD
ATAD
3500
3500
3500
11⁄2
2
2
Outlet Area = 1.35 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG56
2645 0.84 2430 0.86 2166 0.87 1872 0.85 1449 0.79
3481 1.07 3296 1.10 3090 1.14 2851 1.16 2560 1.17 2154 1.13
4220 1.44 4035 1.49 3824 1.53 3572 1.56 3284 1.59 2924 1.58
4889 1.97 4694 2.02 4476 2.06 4219 2.10 3921 2.12 3560 2.11
6-BLADE
Fan Efficiency Grade = FEG56
2676 1.33 2537 1.35 2384 1.36 2217 1.36 2035 1.36 1837 1.35 1303 1.27
3585 1.68 3468 1.73 3341 1.78 3198 1.83 3033 1.86 2827 1.87 2207 1.80
4440 2.14
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
8
Twin City Fan Catalog AX210
www.tcf.com
9
Size 040A ATAD – 1160 RPM
ATAD, Arrangement 4 - Direct Drive
Size 050A ATAD – 1160 RPM
Outlet Area = 1.35 ft2
CATALOG NUMBER
PROP
TYPE
RPM HP
CU.FT. PER MIN. & HP @ SP
1/8" SP
1/4" SP
3/8" SP
CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG56
3-BLADE
1/12 551 0.03
1/12 895 0.04
1/12 1133 0.06
1/12 1346 0.08
1/12 1506 0.09
1/8
1647 0.11
1/4
1742 0.13
Fan Efficiency Grade = FEG56
6-BLADE
1/12 702 0.05
1/12 1031 0.07 503 0.06
1/8
1322 0.09
1/8
1593 0.12 1236 0.12
1/6
1831 0.15 1473 0.15
1/4
2041 0.19
1/4
2253 0.23 1791 0.22
CATALOG NUMBER
PROP
TYPE
RPM HP
040A307
040A312
040A317
040A322
040A327
040A332
040A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
050A307
050A312
050A317
050A322
050A327
050A332
050A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
1/8
1/6
1/4
1/4
1/2
1/2
1/2
040A607
040A612
040A617
040A622
040A627
040A632
040A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
050A607
050A612
050A617
050A622
050A627
050A632
050A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
1/6
1/4
1/2
1/2
1/2
3/4
3/4
Size 040A ATAD – 1750 RPM
CATALOG NUMBER
PROP
TYPE
RPM HP
040A307
040A312
040A317
040A322
040A327
040A332
040A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
1/8
1/4
1/4
1/4
1/2
1/2
1/2
040A607
040A612
040A617
040A622
040A627
040A632
040A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
1/6
1/4
1/2
1/2
1/2
3/4
3/4
Outlet Area = 1.35 ft2
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG56
1215 0.11 936 0.11
1648 0.14 1426 0.15 1077 0.14
2018 0.19 1786 0.20 1462 0.20
2347 0.25 2110 0.26 1780 0.26
2628 0.31 2361 0.32 2011 0.32
2907 0.40 2590 0.40 2191 0.38
3103 0.47 2740 0.46 2324 0.44
6-BLADE
Fan Efficiency Grade = FEG56
1268
0.17 1109 0.17 918 0.17 652 0.16
1734 0.22 1599 0.23 1413 0.23 1104 0.23
2163 0.28 2034 0.30 1874 0.31 1609 0.31
2589 0.37 2446 0.39 2277 0.41 2059 0.42
2973 0.48 2811 0.50 2623 0.51 2393 0.52
3326 0.62 3135 0.64 2920 0.65 2661 0.64
3668 0.78 3465 0.79 3192 0.78 2908 0.76
Outlet Area = 2.11 ft2
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG63
3-BLADE
1860 0.12 1300 0.11
2354 0.15 1848 0.15
2797 0.19 2274 0.20
3274 0.25 2715 0.25
3729 0.33 3136 0.32
4064 0.39 3432 0.38
4313 0.47 3645 0.45
Fan Efficiency Grade = FEG60
6-BLADE
1943 0.18 1586 0.18 1030 0.17
2510 0.23 2172 0.24 1321 0.22
3117 0.29 2816 0.31 2328 0.32
3721 0.38 3410 0.40 2992 0.42
4269 0.48 3941 0.51 3458 0.52
4796 0.62 4417 0.64 3851 0.64
5209 0.76 4744 0.77 4118 0.74
Size 050A ATAD – 1750 RPM
CATALOG NUMBER
PROP
TYPE
RPM HP
050A307 050A312 050A317 050A322 050A327 050A332 050A337 ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
1/2
1/2
3/4
1
11⁄2
11⁄2
11⁄2
050A607 050A612 050A617 050A622 050A627 050A632 ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
3/4
3/4
1
11⁄2
2
2
PerformanceData
PerformanceData
ATAD, Arrangement 4 - Direct Drive
Outlet Area = 2.11 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
3146 0.39 2885 0.40 2584 0.41 2220 0.40 1664 0.36
3874 0.48 3624 0.50 3346 0.52 3011 0.53 2574 0.52 1650
0.44
4557 0.62 4296 0.65 4009 0.66 3664 0.68 3221 0.68
5289 0.84 5019 0.86 4718 0.87 4357 0.87 3856 0.86 3236
0.82
5976 1.10 5707 1.11 5397 1.12 5019 1.12 4432 1.07 3876
1.03
6513 1.35 6219 1.35 5881 1.35 5470 1.34 4885 1.29 4333
1.23
6937 1.62 6605 1.60 6227 1.59 5780 1.56 5238 1.53 4474
1.42
Fan Efficiency Grade = FEG60
6-BLADE
3161 0.60 2985 0.62 2773 0.62 2534 0.62 2267 0.62 1942 0.60
3989 0.74 3833 0.77 3652 0.79 3422 0.81 3146 0.82 2771 0.81
4904 0.96 4748 0.99 4576 1.03 4376 1.06 4135 1.09 3847 1.11
5829 1.24 5662 1.28 5479 1.32 5274 1.36 5032 1.39 4755 1.42
6663 1.61 6491 1.65 6301 1.69 6086 1.72 5818 1.76 5496 1.78 4716
1.75
7491 2.09 7293 2.12 7075 2.15 6826 2.18 6516 2.20
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Size 040A ATAD – 3500 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
040A307
040A312
040A317
040A322
ATAD
ATAD
ATAD
ATAD
3500
3500
3500
3500
1
11⁄2
11⁄2
2
040A607
040A612
040A617
ATAD
ATAD
ATAD
3500
3500
3500
11⁄2
2
2
Outlet Area = 1.35 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG56
2645 0.84 2430 0.86 2166 0.87 1872 0.85 1449 0.79
3481 1.07 3296 1.10 3090 1.14 2851 1.16 2560 1.17 2154 1.13
4220 1.44 4035 1.49 3824 1.53 3572 1.56 3284 1.59 2924 1.58
4889 1.97 4694 2.02 4476 2.06 4219 2.10 3921 2.12 3560 2.11
6-BLADE
Fan Efficiency Grade = FEG56
2676 1.33 2537 1.35 2384 1.36 2217 1.36 2035 1.36 1837 1.35 1303 1.27
3585 1.68 3468 1.73 3341 1.78 3198 1.83 3033 1.86 2827 1.87 2207 1.80
4440 2.14
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
8
Twin City Fan Catalog AX210
www.tcf.com
9
Size 063A ATAD – 870 RPM
CATALOG NUMBER
PROP
TYPE
RPM HP
063A307
063A312
063A317
063A322
063A327
063A332
063A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
1/6
1/4
1/4
1/2
1/2
1/2
3/4
063A607
063A612
063A617
063A622
063A627
063A632
063A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
1/4
1/2
1/2
1/2
3/4
1
1
CATALOG NUMBER
PROP
TYPE
RPM HP
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
2709 0.16 1581 0.14
3456 0.20 2508 0.20
4118 0.26 3153 0.26
4830 0.34 3781 0.34
5511 0.44 4346 0.42
6005 0.53 4793 0.50
6367 0.62 5144 0.60
6-BLADE
Fan Efficiency Grade = FEG60
2857 0.24 2225 0.24
3716 0.30 3097 0.32
4629 0.40 4085 0.43
5531 0.51 4976 0.55 4177 0.56
6352 0.65 5754 0.69 4870 0.69
7135 0.84 6443 0.86 5376 0.84
7745 1.03 6872 1.02
1/8"
CFM
063A307
063A312
063A317
063A322
063A327
063A332
063A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
1/2
1/2
3/4
3/4
1
11⁄2
11⁄2
063A607
063A612
063A617
063A622
063A627
063A632
063A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
3/4 4092
3/4 5201
1 6413
11⁄2 7633
11⁄2 8736
2 9819
3
10678
4026
4996
5895
6860
7772
8470
9011
Outlet Area = 3.36 ft2
Outlet Area = 3.36 ft2
CATALOG NUMBER
PROP
TYPE
RPM HP
063A307
063A312
063A317
063A322
063A327
063A332
063A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
063A607
063A612
063A617
063A622
063A627
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
11⁄2 6162 1.24 5466 1.28 4618 1.27 3268 1.15
2 7622 1.55 6968 1.63 6182 1.68 5106 1.65
2 8982 2.00 8301 2.08 7495 2.14 6401 2.14
3
10441 2.67 9733 2.74 8890 2.77 7668 2.74
5
11817 3.50 11103 3.55 10221 3.56 8813 3.40 7348 3.20
5
12878 4.27 12098 4.28 11136 4.26 9716 4.07 8247 3.84
5 13707 5.13 12830 5.06 11768 4.98 10423 4.86
6-BLADE
Fan Efficiency Grade = FEG60
2 6234 1.92 5759 1.97 5175 1.98 4511 1.96 3638 1.90
3 7900 2.37 7485 2.48 6954 2.57 6266 2.61 5210 2.52
5 9728 3.07 9321 3.21 8846 3.35 8248 3.47 7490 3.51
5
11572 3.97 11137 4.14 10642 4.29 10041 4.43 9338 4.53
8491 4.55
5 13239 5.13 12789 5.30 12271 5.45
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
10
Twin City Fan Catalog AX210
Outlet Area = 4.26 ft2
CATALOG NUMBER
PROP
TYPE
RPM HP
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
0.36 3481 0.37 2766 0.36
0.46 4487 0.48 3836 0.49 2703 0.44
0.59 5367 0.61 4693 0.63 3624 0.60
0.78 6310 0.80 5595 0.81 4542 0.77
1.02 7213 1.04 6464 1.03 5334 0.96
1.25 7859 1.25 7053 1.23 5929 1.15
1.49 8325 1.47 7463 1.44 6289 1.36
6-BLADE
Fan Efficiency Grade = FEG60
0.56 3715 0.57 3258 0.57 2699 0.56 1889 0.52
0.70 4875 0.73 4432 0.75 3829 0.75 2357 0.67
0.90 6097 0.95 5711 0.99 5208 1.02 4049 0.96
1.16 7296 1.22 6899 1.27 6403 1.31 5835 1.33
1.50 8388 1.56 7969 1.60 7401 1.64 6753 1.65
1.95 9419 1.99 8934 2.02 8278 2.04 7496 2.01
2.41 10217 2.44 9621 2.44 8791 2.41 8029 2.33
Size 063A ATAD – 1750 RPM
Size 071A ATAD – 870 RPM
Outlet Area = 3.36 ft2
Size 063A ATAD – 1160 RPM
ATAD, Arrangement 4 - Direct Drive
PerformanceData
PerformanceData
ATAD, Arrangement 4 - Direct Drive
071A307
071A312
071A317
071A322
071A327
071A332
071A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
071A607
071A612
071A617
071A622
071A627
071A632
071A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
1/4
4102 0.28 3150 0.28
1/2
5154 0.36 4277 0.38
1/2
6110 0.46 5205 0.48
3/4
7139 0.61 6190 0.62 4579 0.58
3/4
8117 0.79 7132 0.79 5496 0.73
1
8845 0.96 7773 0.95 6147 0.87
9395 1.14 8214 1.11
11⁄2
6-BLADE
Fan Efficiency Grade = FEG60
1/2 4245 0.44 3601 0.44 2752 0.43
3/4 5452 0.54 4864 0.58 3928 0.57
3/4 6754 0.71 6222 0.75 5464 0.78
1 8054 0.91 7499 0.96 6757 1.01
11⁄2 9234 1.17 8654 1.22 7809 1.26 6686 1.24
11⁄2 10375 1.51 9706 1.55 8729 1.56 7385 1.50
2
11274 1.86 10479 1.87 9277 1.84
Size 071A ATAD – 1160 RPM
CATALOG NUMBER
PROP
TYPE
RPM HP
1/8"
CFM
071A307
071A312
071A317
071A322
071A327
071A332
071A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
3/4 5908
1 7291
11⁄2 8584
11⁄2 9970
2
11275
3
12287
3
13083
071A607
071A612
071A617
071A622
071A627
071A632
071A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
1 5955
11⁄2 7531
2 9266
3
11018
3
12601
5
14164
5
15409
Outlet Area = 4.26 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
11⁄4" SP
BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
0.65 5333 0.68 4656 0.68 3758 0.65
0.82 6746 0.85 6118 0.88 5319 0.89 4054 0.82
1.05 8015 1.09 7371 1.13 6538 1.14 5382 1.10
1.41 9381 1.44 8705 1.46 7805 1.46 6612 1.41
1.85 10684 1.88 9982 1.89 9017 1.85 7726 1.75
2.26 11642 2.27 10872 2.26 9862 2.21 8572 2.10
2.72 12356 2.69 11501 2.65 10467 2.60 9120 2.49
6-BLADE
Fan Efficiency Grade = FEG60
1.02 5567 1.04 5087 1.05 4557 1.04 3920 1.03 2994 0.97
1.25 7189 1.30 6772 1.34 6233 1.38 5594 1.37 3885 1.26
1.62 8927 1.69 8542 1.75 8077 1.81 7505 1.85 6720 1.84
2.09 10655 2.17 10250 2.25 9777 2.32 9212 2.37 8595 2.41
2.71 12225 2.79 11803 2.86 11298 2.93 10649 2.98 9933 3.00
3.52 13734 3.58 13248 3.64 12663 3.68 11912 3.70 11064 3.68
4.37 14918 4.41 14349 4.44 13605 4.44 12651 4.38 11828 4.29
Size 071A ATAD – 1750 RPM
Outlet Area = 4.26 ft2
CATALOG NUMBER
PROP
TYPE
RPM
HP
071A307
071A312
071A317
071A322
071A327
071A332
071A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
071A607
071A612
071A617
071A622
071A627
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
3 9009 2.23 8269 2.30 7417 2.34 6391 2.30 4847 2.12
3
11094 2.79 10385 2.91 9597 3.00 8651 3.05 7426 3.00 4979 2.59
5
13048 3.60 12308 3.72 11494 3.83 10521 3.91 9272 3.90
5
15142 4.82 14378 4.93 13525 5.01 12507 5.04 11097 4.99 9366 4.74
71⁄2 17110 6.32 16346 6.42 15470 6.48 14403 6.45 12758 6.20 11171 5.95
71⁄2 18646 7.76 17813 7.78 16855 7.78 15696 7.72 14054 7.44 12475 7.13
10 19861 9.36 18920 9.25 17848 9.15 16586 9.03 15060 8.85 13022 8.29
Fan Efficiency Grade = FEG60
6-BLADE
5 9049 3.48 8551 3.55 7951 3.58 7275 3.59 6522 3.57 5609 3.49
5
11420 4.27 10978 4.42 10465 4.56 9818 4.68 9038 4.74 7996 4.67
71⁄2 14037 5.53 13597 5.73 13108 5.93 12544 6.12 11865 6.29 11054 6.38
71⁄2 16686 7.15 16212 7.39 15694 7.62 15113 7.84 14429 8.04 13648 8.19 11352 8.13
10 19074 9.27 18586 9.50 18048 9.73 17438 9.94 16684 10.14 15773 10.28 13597 10.12
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
www.tcf.com
11
Size 063A ATAD – 870 RPM
CATALOG NUMBER
PROP
TYPE
RPM HP
063A307
063A312
063A317
063A322
063A327
063A332
063A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
1/6
1/4
1/4
1/2
1/2
1/2
3/4
063A607
063A612
063A617
063A622
063A627
063A632
063A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
1/4
1/2
1/2
1/2
3/4
1
1
CATALOG NUMBER
PROP
TYPE
RPM HP
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
2709 0.16 1581 0.14
3456 0.20 2508 0.20
4118 0.26 3153 0.26
4830 0.34 3781 0.34
5511 0.44 4346 0.42
6005 0.53 4793 0.50
6367 0.62 5144 0.60
6-BLADE
Fan Efficiency Grade = FEG60
2857 0.24 2225 0.24
3716 0.30 3097 0.32
4629 0.40 4085 0.43
5531 0.51 4976 0.55 4177 0.56
6352 0.65 5754 0.69 4870 0.69
7135 0.84 6443 0.86 5376 0.84
7745 1.03 6872 1.02
1/8"
CFM
063A307
063A312
063A317
063A322
063A327
063A332
063A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
1/2
1/2
3/4
3/4
1
11⁄2
11⁄2
063A607
063A612
063A617
063A622
063A627
063A632
063A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
3/4 4092
3/4 5201
1 6413
11⁄2 7633
11⁄2 8736
2 9819
3
10678
4026
4996
5895
6860
7772
8470
9011
Outlet Area = 3.36 ft2
Outlet Area = 3.36 ft2
CATALOG NUMBER
PROP
TYPE
RPM HP
063A307
063A312
063A317
063A322
063A327
063A332
063A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
063A607
063A612
063A617
063A622
063A627
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
11⁄2 6162 1.24 5466 1.28 4618 1.27 3268 1.15
2 7622 1.55 6968 1.63 6182 1.68 5106 1.65
2 8982 2.00 8301 2.08 7495 2.14 6401 2.14
3
10441 2.67 9733 2.74 8890 2.77 7668 2.74
5
11817 3.50 11103 3.55 10221 3.56 8813 3.40 7348 3.20
5
12878 4.27 12098 4.28 11136 4.26 9716 4.07 8247 3.84
5 13707 5.13 12830 5.06 11768 4.98 10423 4.86
6-BLADE
Fan Efficiency Grade = FEG60
2 6234 1.92 5759 1.97 5175 1.98 4511 1.96 3638 1.90
3 7900 2.37 7485 2.48 6954 2.57 6266 2.61 5210 2.52
5 9728 3.07 9321 3.21 8846 3.35 8248 3.47 7490 3.51
5
11572 3.97 11137 4.14 10642 4.29 10041 4.43 9338 4.53
8491 4.55
5 13239 5.13 12789 5.30 12271 5.45
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
10
Twin City Fan Catalog AX210
Outlet Area = 4.26 ft2
CATALOG NUMBER
PROP
TYPE
RPM HP
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
0.36 3481 0.37 2766 0.36
0.46 4487 0.48 3836 0.49 2703 0.44
0.59 5367 0.61 4693 0.63 3624 0.60
0.78 6310 0.80 5595 0.81 4542 0.77
1.02 7213 1.04 6464 1.03 5334 0.96
1.25 7859 1.25 7053 1.23 5929 1.15
1.49 8325 1.47 7463 1.44 6289 1.36
6-BLADE
Fan Efficiency Grade = FEG60
0.56 3715 0.57 3258 0.57 2699 0.56 1889 0.52
0.70 4875 0.73 4432 0.75 3829 0.75 2357 0.67
0.90 6097 0.95 5711 0.99 5208 1.02 4049 0.96
1.16 7296 1.22 6899 1.27 6403 1.31 5835 1.33
1.50 8388 1.56 7969 1.60 7401 1.64 6753 1.65
1.95 9419 1.99 8934 2.02 8278 2.04 7496 2.01
2.41 10217 2.44 9621 2.44 8791 2.41 8029 2.33
Size 063A ATAD – 1750 RPM
Size 071A ATAD – 870 RPM
Outlet Area = 3.36 ft2
Size 063A ATAD – 1160 RPM
ATAD, Arrangement 4 - Direct Drive
PerformanceData
PerformanceData
ATAD, Arrangement 4 - Direct Drive
071A307
071A312
071A317
071A322
071A327
071A332
071A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
071A607
071A612
071A617
071A622
071A627
071A632
071A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
1/4
4102 0.28 3150 0.28
1/2
5154 0.36 4277 0.38
1/2
6110 0.46 5205 0.48
3/4
7139 0.61 6190 0.62 4579 0.58
3/4
8117 0.79 7132 0.79 5496 0.73
1
8845 0.96 7773 0.95 6147 0.87
9395 1.14 8214 1.11
11⁄2
6-BLADE
Fan Efficiency Grade = FEG60
1/2 4245 0.44 3601 0.44 2752 0.43
3/4 5452 0.54 4864 0.58 3928 0.57
3/4 6754 0.71 6222 0.75 5464 0.78
1 8054 0.91 7499 0.96 6757 1.01
11⁄2 9234 1.17 8654 1.22 7809 1.26 6686 1.24
11⁄2 10375 1.51 9706 1.55 8729 1.56 7385 1.50
2
11274 1.86 10479 1.87 9277 1.84
Size 071A ATAD – 1160 RPM
CATALOG NUMBER
PROP
TYPE
RPM HP
1/8"
CFM
071A307
071A312
071A317
071A322
071A327
071A332
071A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
3/4 5908
1 7291
11⁄2 8584
11⁄2 9970
2
11275
3
12287
3
13083
071A607
071A612
071A617
071A622
071A627
071A632
071A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
1 5955
11⁄2 7531
2 9266
3
11018
3
12601
5
14164
5
15409
Outlet Area = 4.26 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
11⁄4" SP
BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
0.65 5333 0.68 4656 0.68 3758 0.65
0.82 6746 0.85 6118 0.88 5319 0.89 4054 0.82
1.05 8015 1.09 7371 1.13 6538 1.14 5382 1.10
1.41 9381 1.44 8705 1.46 7805 1.46 6612 1.41
1.85 10684 1.88 9982 1.89 9017 1.85 7726 1.75
2.26 11642 2.27 10872 2.26 9862 2.21 8572 2.10
2.72 12356 2.69 11501 2.65 10467 2.60 9120 2.49
6-BLADE
Fan Efficiency Grade = FEG60
1.02 5567 1.04 5087 1.05 4557 1.04 3920 1.03 2994 0.97
1.25 7189 1.30 6772 1.34 6233 1.38 5594 1.37 3885 1.26
1.62 8927 1.69 8542 1.75 8077 1.81 7505 1.85 6720 1.84
2.09 10655 2.17 10250 2.25 9777 2.32 9212 2.37 8595 2.41
2.71 12225 2.79 11803 2.86 11298 2.93 10649 2.98 9933 3.00
3.52 13734 3.58 13248 3.64 12663 3.68 11912 3.70 11064 3.68
4.37 14918 4.41 14349 4.44 13605 4.44 12651 4.38 11828 4.29
Size 071A ATAD – 1750 RPM
Outlet Area = 4.26 ft2
CATALOG NUMBER
PROP
TYPE
RPM
HP
071A307
071A312
071A317
071A322
071A327
071A332
071A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
071A607
071A612
071A617
071A622
071A627
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG63
3 9009 2.23 8269 2.30 7417 2.34 6391 2.30 4847 2.12
3
11094 2.79 10385 2.91 9597 3.00 8651 3.05 7426 3.00 4979 2.59
5
13048 3.60 12308 3.72 11494 3.83 10521 3.91 9272 3.90
5
15142 4.82 14378 4.93 13525 5.01 12507 5.04 11097 4.99 9366 4.74
71⁄2 17110 6.32 16346 6.42 15470 6.48 14403 6.45 12758 6.20 11171 5.95
71⁄2 18646 7.76 17813 7.78 16855 7.78 15696 7.72 14054 7.44 12475 7.13
10 19861 9.36 18920 9.25 17848 9.15 16586 9.03 15060 8.85 13022 8.29
Fan Efficiency Grade = FEG60
6-BLADE
5 9049 3.48 8551 3.55 7951 3.58 7275 3.59 6522 3.57 5609 3.49
5
11420 4.27 10978 4.42 10465 4.56 9818 4.68 9038 4.74 7996 4.67
71⁄2 14037 5.53 13597 5.73 13108 5.93 12544 6.12 11865 6.29 11054 6.38
71⁄2 16686 7.15 16212 7.39 15694 7.62 15113 7.84 14429 8.04 13648 8.19 11352 8.13
10 19074 9.27 18586 9.50 18048 9.73 17438 9.94 16684 10.14 15773 10.28 13597 10.12
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
www.tcf.com
11
Size 080A ATAD – 870 RPM
ATAD, Arrangement 4 - Direct Drive
Size 090A ATAD – 870 RPM
Outlet Area = 5.41 ft2
CATALOG NUMBER
PROP
TYPE
RPM HP
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG71
3-BLADE
1/2 6343 0.47 5428 0.50 3131 0.42
3/4 7890 0.61 7053 0.64 5738 0.64
1 9413 0.78 8596 0.83 7360 0.84
11⁄2 10823 1.06 9931 1.10 8715 1.12 6507 1.05
11⁄2 12141 1.33 11124 1.35 9766 1.34 7577 1.27
11⁄2 13329 1.65 12201 1.64 10682 1.60 8469 1.54
2
14367 2.01 13164 1.97 11302 1.88
6-BLADE
Fan Efficiency Grade = FEG63
3/4 6333 0.77 5617 0.79 4543 0.76 3450 0.75
1 8339 0.97 7809 1.04 6957 1.06 4428 0.93
11⁄2 10034 1.19 9527 1.27 8876 1.35 7810 1.39
2
11868 1.58 11345 1.67 10693 1.75 9754 1.81
2
13554 2.00 12951 2.09 12199 2.17 11166 2.23
3
15232 2.54 14552 2.62 13642 2.68 12400 2.71 11110 2.67
3
16915 3.26 16192 3.32 15053 3.34 13465 3.27
CATALOG NUMBER
PROP
TYPE
RPM HP
080A307
080A312
080A317
080A322
080A327
080A332
080A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
090A307
090A312
090A317
090A322
090A327
090A332
090A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
080A607
080A612
080A617
080A622
080A627
080A632
080A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
090A607
090A612
090A617
090A622
090A627
090A632
090A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
Size 080A ATAD – 1160 RPM
CATALOG NUMBER
TYPE
RPM
PROP
080A307
080A312
080A317
080A322
080A327
080A332
080A337
080A607
080A612
080A617
080A622
080A627
080A632
080A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
1160
1160
1160
1160
1160
1160
1160
HP
1/8"
CFM
11⁄2 8940
11⁄2 10944
2
13011
3
14908
3
16718
5
18360
5
19699
2 8792
3
11377
3
13641
5
16097
5
18387
71⁄2 20660
71⁄2 22915
Outlet Area = 5.41 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER
SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4"
BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM
3-BLADE
1.09 8317 1.13 7656 1.17 6864 1.18 5643 1.13
1.39 10393 1.46 9783 1.51 9061 1.53 8048 1.53 6665
1.79 12416 1.87 11806 1.93 11164 1.98 10248 2.01 8878
2.44 14289 2.52 13625 2.58 12915 2.62 12019 2.65 10686
3.10 16030 3.16 15279 3.19 14450 3.19 13438 3.19 12069
3.91 17597 3.91 16765 3.90 15842 3.88 14711 3.83 13224
4.76 18989 4.75 18146 4.71 16984 4.62 15583 4.50 13884
6-BLADE
1.79 8339 1.84 7820 1.87 7189 1.86 6352 1.81 5471
2.24 11040 2.33 10656 2.42 10189 2.48 9553 2.51 8288
2.74 13301 2.84 12928 2.95 12509 3.05 12021 3.17 11414
3.64 15743 3.77 15358 3.89 14931 4.00 14442 4.11 13848
4.66 17978 4.78 17534 4.89 17043 4.99 16479 5.10 15793
5.94 20205 6.04 19706 6.15 19145 6.24 18467 6.33 17563
7.67 22445 7.76 21917 7.83 21303 7.89 20487 7.92 19051
Size 080A ATAD – 1750 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
080A307
080A312
080A317
080A322
080A327
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
5
5
71⁄2
10
10
080A607
080A612
080A617
ATAD
ATAD
ATAD
1750
1750
1750
71⁄2
10
10
AT STATIC PRESSURE
SP
1" SP
11⁄4" SP
BHP CFM BHP CFM BHP
PROP
1.49
1.96
2.65
3.15
3.74
4.38
090A307
090A312
090A317
090A322
090A327
090A332
090A337
Fan Efficiency Grade = FEG63
1.80 3944 1.75
2.47 4950 2.20
3.27
4.21 12056 4.30
5.20 14091 5.32
6.39 15825 6.42
7.86 17223 7.66
CATALOG NUMBER
TYPE
RPM
HP
Fan Efficiency Grade = FEG71
Outlet Area = 5.41 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
13598 3.72 12777 3.84 11929 3.97 10967 4.05 9764 4.03 6712 3.51
16605 4.73 15888 4.97 15105 5.14 14232 5.22 13130 5.26 11656 5.23
19734 6.12 18952 6.36 18143 6.57 17329 6.74 16388 6.86 14930 6.88
22600 8.35 21789 8.58 20925 8.78 20019 8.93 19010 9.03 17646 9.11 13393 8.62
25341 10.61 24442 10.80 23474 10.93 22427 10.97 21248 10.96 19763 10.93 15448 10.34
6-BLADE
Fan Efficiency Grade = FEG63
13342 6.11 12754 6.28 12097 6.39 11338 6.41 10370 6.32 9221 6.21 7031 6.14
17221 7.64 16784 7.93 16297 8.19 15735 8.42 15034 8.58 14076 8.64 9063 7.60
20638 9.36 20195 9.68 19715 10.00 19188 10.31 18597 10.63 17907 10.97
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
1 9254 0.84 8293 0.88 7086 0.89
11⁄2 11423 1.08 10546 1.14 9444 1.16 7726 1.15
11⁄2 13602 1.38 12693 1.46 11716 1.51 10026 1.51
2
15614 1.87 14645 1.94 13571 1.99 11947 2.01 9441 1.90
3
17514 2.36 16426 2.41 15175 2.42 13434 2.40 10895 2.28
3
19231 2.96 18025 2.96 16632 2.93 14692 2.86 12224 2.77
5
20685 3.60 19508 3.58 17763 3.48 15519 3.35
6-BLADE
Fan Efficiency Grade = FEG63
11⁄2 9174 1.37 8438 1.41 7473 1.40 6169 1.37
4959 1.35
2
11976 1.72 11430 1.82 10722 1.89 9527 1.90 6390 1.67
3
14384 2.11 13846 2.22 13215 2.33 12416 2.45 11190 2.50
3
16994 2.80 16436 2.92 15794 3.05 14999 3.16 13920 3.25
5
19409 3.56 18765 3.68 18027 3.80 17108 3.91 15924 3.99 14474 4.03
5
21811 4.53 21090 4.64 20246 4.74 19087 4.82 17673 4.86 16429 4.84
71⁄2 24207 5.83 23452 5.92 22526 5.98 20895 5.98 19185 5.88 17858 5.74
Size 090A ATAD – 1160 RPM
11⁄2" SP
CFM BHP
Outlet Area = 6.85 ft2
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
2
3
5
5
71⁄2
71⁄2
10
090A607 090A612 090A617 090A622 090A627
090A632 090A637 ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
3
5
71⁄2
71⁄2
10
15
15
Outlet Area = 6.85 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
1/8" SP
1/4" SP
3/8" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
12874 1.94 12182 1.99 11473 2.06 10699 2.10 8564 2.07
15694 2.46 15094 2.57 14444 2.66 13737 2.72 11831 2.74
18647 3.18 17988 3.30 17304 3.40 16620 3.49 14954 3.60 11832 3.46
21347 4.35 20665 4.46 19944 4.56 19188 4.64 17438 4.74 14438 4.70
23934 5.53 23180 5.62 22374 5.69 21511 5.73 19485 5.72 16368 5.60
26286 7.01 25451 7.01 24558 7.01 23600 7.00 21343 6.91 18069 6.67
28168 8.55 27403 8.54 26544 8.50 25535 8.44 22643 8.14 18821 7.82
Fan Efficiency Grade = FEG63
6-BLADE
12611 3.18 12119 3.27 11579 3.33 10970 3.35 9323 3.27 7378 3.23 5690 3.15
16248 3.98 15884 4.11 15483 4.24 15032 4.36 13825 4.50 10452 4.19 7145 3.94
19466 4.87 19094 5.02 18696 5.17 18264 5.32 17256 5.63 15859 5.91
22958 6.49 22570 6.67 22157 6.84 21713 7.01 20694 7.33 19340 7.61 17289 7.73
26226 8.32 25777 8.48 25300 8.64 24788 8.80 23616 9.10 22060 9.38 20127 9.55
29465 10.61 28968 10.76 28435 10.91 27857 11.05 26493 11.31 24473 11.49 22570 11.52
32672 13.74 32159 13.86 31603 13.97 30988 14.06 29447 14.20 26477 14.05 24563 13.77
Size 090A ATAD – 1750 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
090A307
090A312
090A317
090A322
090A327 090A332 090A337 ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
71⁄2
10
15
15
20
25
30
090A607
090A612
090A617
090A622
090A627
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
15
15
20
25
30
PerformanceData
PerformanceData
ATAD, Arrangement 4 - Direct Drive
Outlet Area = 6.85 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG71
3-BLADE
19546 6.62 18635 6.80 17701 6.98 16728 7.16 15636 7.26 14356 7.26
23782 8.39 22997 8.75 22157 9.05 21256 9.25 20266 9.36 19089 9.43 15735 9.34
28250 10.88 27381 11.24 26485 11.56 25574 11.84 24659 12.07 23646 12.26 20352 12.27
32325 14.89 31430 15.23 30491 15.54 29504 15.80 28484 16.00 27380 16.16 24224 16.37 19343 15.56
36241 18.96 35252 19.24 34206 19.47 33094 19.63 31912 19.69 30619 19.67 27217 19.57 22215 18.62
39803 24.05 38708 24.08 37550 24.09 36317 24.06 35003 24.00 33562 23.89 29765 23.28 24978 22.59
42627 29.35 41632 29.32 40536 29.25 39302 29.11 37798 28.83 35874 28.35 31457 27.28
6-BLADE
Fan Efficiency Grade = FEG63
19110 10.88 18469 11.15 17775 11.37 17010 11.49 16149 11.51 15115 11.41 12533 11.12 10103 11.02 7887 10.63
24576 13.59 24100 14.01 23585 14.41 23019 14.77 22382 15.09 21625 15.34 19342 15.48 13080 13.63
29433 16.67 28945 17.13 28428 17.58 27877 18.03 27281 18.48 26630 18.93 25059 19.88 22706 20.36
34704 22.22 34195 22.75 33658 23.27 33088 23.78 32478 24.28 31817 24.76 30254 25.68 28144 26.39
39644 28.49 39056 28.99 38436 29.47 37778 29.95 37075 30.42 36317 30.88 34508 31.76 32176 32.47 29377 32.80
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
12
Twin City Fan Catalog AX210
www.tcf.com
13
Size 080A ATAD – 870 RPM
ATAD, Arrangement 4 - Direct Drive
Size 090A ATAD – 870 RPM
Outlet Area = 5.41 ft2
CATALOG NUMBER
PROP
TYPE
RPM HP
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG71
3-BLADE
1/2 6343 0.47 5428 0.50 3131 0.42
3/4 7890 0.61 7053 0.64 5738 0.64
1 9413 0.78 8596 0.83 7360 0.84
11⁄2 10823 1.06 9931 1.10 8715 1.12 6507 1.05
11⁄2 12141 1.33 11124 1.35 9766 1.34 7577 1.27
11⁄2 13329 1.65 12201 1.64 10682 1.60 8469 1.54
2
14367 2.01 13164 1.97 11302 1.88
6-BLADE
Fan Efficiency Grade = FEG63
3/4 6333 0.77 5617 0.79 4543 0.76 3450 0.75
1 8339 0.97 7809 1.04 6957 1.06 4428 0.93
11⁄2 10034 1.19 9527 1.27 8876 1.35 7810 1.39
2
11868 1.58 11345 1.67 10693 1.75 9754 1.81
2
13554 2.00 12951 2.09 12199 2.17 11166 2.23
3
15232 2.54 14552 2.62 13642 2.68 12400 2.71 11110 2.67
3
16915 3.26 16192 3.32 15053 3.34 13465 3.27
CATALOG NUMBER
PROP
TYPE
RPM HP
080A307
080A312
080A317
080A322
080A327
080A332
080A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
090A307
090A312
090A317
090A322
090A327
090A332
090A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
080A607
080A612
080A617
080A622
080A627
080A632
080A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
090A607
090A612
090A617
090A622
090A627
090A632
090A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
Size 080A ATAD – 1160 RPM
CATALOG NUMBER
TYPE
RPM
PROP
080A307
080A312
080A317
080A322
080A327
080A332
080A337
080A607
080A612
080A617
080A622
080A627
080A632
080A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
1160
1160
1160
1160
1160
1160
1160
HP
1/8"
CFM
11⁄2 8940
11⁄2 10944
2
13011
3
14908
3
16718
5
18360
5
19699
2 8792
3
11377
3
13641
5
16097
5
18387
71⁄2 20660
71⁄2 22915
Outlet Area = 5.41 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER
SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4"
BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM
3-BLADE
1.09 8317 1.13 7656 1.17 6864 1.18 5643 1.13
1.39 10393 1.46 9783 1.51 9061 1.53 8048 1.53 6665
1.79 12416 1.87 11806 1.93 11164 1.98 10248 2.01 8878
2.44 14289 2.52 13625 2.58 12915 2.62 12019 2.65 10686
3.10 16030 3.16 15279 3.19 14450 3.19 13438 3.19 12069
3.91 17597 3.91 16765 3.90 15842 3.88 14711 3.83 13224
4.76 18989 4.75 18146 4.71 16984 4.62 15583 4.50 13884
6-BLADE
1.79 8339 1.84 7820 1.87 7189 1.86 6352 1.81 5471
2.24 11040 2.33 10656 2.42 10189 2.48 9553 2.51 8288
2.74 13301 2.84 12928 2.95 12509 3.05 12021 3.17 11414
3.64 15743 3.77 15358 3.89 14931 4.00 14442 4.11 13848
4.66 17978 4.78 17534 4.89 17043 4.99 16479 5.10 15793
5.94 20205 6.04 19706 6.15 19145 6.24 18467 6.33 17563
7.67 22445 7.76 21917 7.83 21303 7.89 20487 7.92 19051
Size 080A ATAD – 1750 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
080A307
080A312
080A317
080A322
080A327
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
5
5
71⁄2
10
10
080A607
080A612
080A617
ATAD
ATAD
ATAD
1750
1750
1750
71⁄2
10
10
AT STATIC PRESSURE
SP
1" SP
11⁄4" SP
BHP CFM BHP CFM BHP
PROP
1.49
1.96
2.65
3.15
3.74
4.38
090A307
090A312
090A317
090A322
090A327
090A332
090A337
Fan Efficiency Grade = FEG63
1.80 3944 1.75
2.47 4950 2.20
3.27
4.21 12056 4.30
5.20 14091 5.32
6.39 15825 6.42
7.86 17223 7.66
CATALOG NUMBER
TYPE
RPM
HP
Fan Efficiency Grade = FEG71
Outlet Area = 5.41 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
13598 3.72 12777 3.84 11929 3.97 10967 4.05 9764 4.03 6712 3.51
16605 4.73 15888 4.97 15105 5.14 14232 5.22 13130 5.26 11656 5.23
19734 6.12 18952 6.36 18143 6.57 17329 6.74 16388 6.86 14930 6.88
22600 8.35 21789 8.58 20925 8.78 20019 8.93 19010 9.03 17646 9.11 13393 8.62
25341 10.61 24442 10.80 23474 10.93 22427 10.97 21248 10.96 19763 10.93 15448 10.34
6-BLADE
Fan Efficiency Grade = FEG63
13342 6.11 12754 6.28 12097 6.39 11338 6.41 10370 6.32 9221 6.21 7031 6.14
17221 7.64 16784 7.93 16297 8.19 15735 8.42 15034 8.58 14076 8.64 9063 7.60
20638 9.36 20195 9.68 19715 10.00 19188 10.31 18597 10.63 17907 10.97
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
CU. FT. PER MIN. & HP @ STATIC PRESSURE
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
1 9254 0.84 8293 0.88 7086 0.89
11⁄2 11423 1.08 10546 1.14 9444 1.16 7726 1.15
11⁄2 13602 1.38 12693 1.46 11716 1.51 10026 1.51
2
15614 1.87 14645 1.94 13571 1.99 11947 2.01 9441 1.90
3
17514 2.36 16426 2.41 15175 2.42 13434 2.40 10895 2.28
3
19231 2.96 18025 2.96 16632 2.93 14692 2.86 12224 2.77
5
20685 3.60 19508 3.58 17763 3.48 15519 3.35
6-BLADE
Fan Efficiency Grade = FEG63
11⁄2 9174 1.37 8438 1.41 7473 1.40 6169 1.37
4959 1.35
2
11976 1.72 11430 1.82 10722 1.89 9527 1.90 6390 1.67
3
14384 2.11 13846 2.22 13215 2.33 12416 2.45 11190 2.50
3
16994 2.80 16436 2.92 15794 3.05 14999 3.16 13920 3.25
5
19409 3.56 18765 3.68 18027 3.80 17108 3.91 15924 3.99 14474 4.03
5
21811 4.53 21090 4.64 20246 4.74 19087 4.82 17673 4.86 16429 4.84
71⁄2 24207 5.83 23452 5.92 22526 5.98 20895 5.98 19185 5.88 17858 5.74
Size 090A ATAD – 1160 RPM
11⁄2" SP
CFM BHP
Outlet Area = 6.85 ft2
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
2
3
5
5
71⁄2
71⁄2
10
090A607 090A612 090A617 090A622 090A627
090A632 090A637 ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
3
5
71⁄2
71⁄2
10
15
15
Outlet Area = 6.85 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
1/8" SP
1/4" SP
3/8" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
12874 1.94 12182 1.99 11473 2.06 10699 2.10 8564 2.07
15694 2.46 15094 2.57 14444 2.66 13737 2.72 11831 2.74
18647 3.18 17988 3.30 17304 3.40 16620 3.49 14954 3.60 11832 3.46
21347 4.35 20665 4.46 19944 4.56 19188 4.64 17438 4.74 14438 4.70
23934 5.53 23180 5.62 22374 5.69 21511 5.73 19485 5.72 16368 5.60
26286 7.01 25451 7.01 24558 7.01 23600 7.00 21343 6.91 18069 6.67
28168 8.55 27403 8.54 26544 8.50 25535 8.44 22643 8.14 18821 7.82
Fan Efficiency Grade = FEG63
6-BLADE
12611 3.18 12119 3.27 11579 3.33 10970 3.35 9323 3.27 7378 3.23 5690 3.15
16248 3.98 15884 4.11 15483 4.24 15032 4.36 13825 4.50 10452 4.19 7145 3.94
19466 4.87 19094 5.02 18696 5.17 18264 5.32 17256 5.63 15859 5.91
22958 6.49 22570 6.67 22157 6.84 21713 7.01 20694 7.33 19340 7.61 17289 7.73
26226 8.32 25777 8.48 25300 8.64 24788 8.80 23616 9.10 22060 9.38 20127 9.55
29465 10.61 28968 10.76 28435 10.91 27857 11.05 26493 11.31 24473 11.49 22570 11.52
32672 13.74 32159 13.86 31603 13.97 30988 14.06 29447 14.20 26477 14.05 24563 13.77
Size 090A ATAD – 1750 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
090A307
090A312
090A317
090A322
090A327 090A332 090A337 ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
1750
1750
71⁄2
10
15
15
20
25
30
090A607
090A612
090A617
090A622
090A627
ATAD
ATAD
ATAD
ATAD
ATAD
1750
1750
1750
1750
1750
15
15
20
25
30
PerformanceData
PerformanceData
ATAD, Arrangement 4 - Direct Drive
Outlet Area = 6.85 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG71
3-BLADE
19546 6.62 18635 6.80 17701 6.98 16728 7.16 15636 7.26 14356 7.26
23782 8.39 22997 8.75 22157 9.05 21256 9.25 20266 9.36 19089 9.43 15735 9.34
28250 10.88 27381 11.24 26485 11.56 25574 11.84 24659 12.07 23646 12.26 20352 12.27
32325 14.89 31430 15.23 30491 15.54 29504 15.80 28484 16.00 27380 16.16 24224 16.37 19343 15.56
36241 18.96 35252 19.24 34206 19.47 33094 19.63 31912 19.69 30619 19.67 27217 19.57 22215 18.62
39803 24.05 38708 24.08 37550 24.09 36317 24.06 35003 24.00 33562 23.89 29765 23.28 24978 22.59
42627 29.35 41632 29.32 40536 29.25 39302 29.11 37798 28.83 35874 28.35 31457 27.28
6-BLADE
Fan Efficiency Grade = FEG63
19110 10.88 18469 11.15 17775 11.37 17010 11.49 16149 11.51 15115 11.41 12533 11.12 10103 11.02 7887 10.63
24576 13.59 24100 14.01 23585 14.41 23019 14.77 22382 15.09 21625 15.34 19342 15.48 13080 13.63
29433 16.67 28945 17.13 28428 17.58 27877 18.03 27281 18.48 26630 18.93 25059 19.88 22706 20.36
34704 22.22 34195 22.75 33658 23.27 33088 23.78 32478 24.28 31817 24.76 30254 25.68 28144 26.39
39644 28.49 39056 28.99 38436 29.47 37778 29.95 37075 30.42 36317 30.88 34508 31.76 32176 32.47 29377 32.80
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
12
Twin City Fan Catalog AX210
www.tcf.com
13
Size 100A ATAD – 870 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
100A307
100A312
100A317
100A322
100A327
100A332
100A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
11⁄2
2
3
5
5
5
71⁄2
100A607
100A612
100A617
100A622
100A627
100A632
100A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
3
3
5
5
71⁄2
71⁄2
10
ATAD, Arrangement 4 - Direct Drive
Outlet Area = 8.45 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
12980 1.41 11936 1.47 10772 1.52 9221 1.50
15934 1.80 14996 1.91 13933 1.96 12525 1.97 10510 1.95
18952 2.32 17951 2.43 16932 2.52 15722 2.58 13681 2.56
21730 3.16 20681 3.27 19556 3.34 18271 3.40 16321 3.42 13602 3.28
24369 4.01 23202 4.08 21913 4.12 20418 4.11 18366 4.09 15563 3.92
26761 5.04 25468 5.04 24036 5.02 22371 4.98 20088 4.85 17471 4.74
28739 6.14 27516 6.11 25970 6.04 23779 5.87 21250 5.69
6-BLADE
Fan Efficiency Grade = FEG63
12800 2.31 12025 2.39 11108 2.41 9878 2.36 8415 2.33 7057 2.31
16610 2.90 16035 3.04 15357 3.15 14464 3.23 12990 3.23 9219 2.86
19927 3.55 19350 3.70 18705 3.86 17957 4.01 17033 4.18 15737 4.26
23524 4.72 22925 4.90 22261 5.07 21506 5.23 20590 5.39 19414 5.51
26870 6.03 26178 6.19 25413 6.36 24545 6.51 23484 6.66 22177 6.78
30192 7.67 29421 7.83 28556 7.97 27551 8.10 26188 8.22 24585 8.27
33496 9.91 32694 10.02 31771 10.12 30643 10.19 28619 10.17 26659 10.03
Size 112A ATAD – 870 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
112A307
112A312
112A317
112A322
112A327
112A332
112A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
3
5
5
71⁄2
71⁄2
10
10
112A607
112A612
112A617
112A622
112A627
112A632
112A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
5
71⁄2
71⁄2
10
15
15
20
Outlet Area = 10.60 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
18469 2.45 17313 2.53 16112 2.62 14732 2.67 12935 2.63
22568 3.12 21555 3.28 20445 3.39 19192 3.44 17561 3.46 15397 3.43
26823 4.03 25720 4.20 24581 4.33 23428 4.45 22037 4.53 19821 4.51
30722 5.50 29577 5.66 28356 5.79 27072 5.89 25608 5.95 23538 6.00
34449 6.99 33180 7.11 31808 7.20 30319 7.22 28617 7.21 26410 7.19 20151 6.72
37833 8.83 36427 8.84 24906 8.83 33250 8.80 31355 8.73 28884 8.57
40571 10.77 39271 10.74 37771 10.69 35845 10.54 33331 10.30 30546 10.04
6-BLADE
Fan Efficiency Grade = FEG63
18132 4.03 17301 4.14 16366 4.21 15276 4.22 13851 4.14 12221 4.08 9209 4.03
23418 5.04 22801 5.23 22108 5.41 21301 5.56 20271 5.66 18806 5.69 11733 5.00
28068 6.17 27442 6.39 26762 6.60 26012 6.82 25162 7.04 24158 7.27 20902 7.41
33114 8.21 32461 8.46 31758 8.71 30990 8.95 30134 9.18 29134 9.40 26418 9.72
37826 10.51 37072 10.75 36260 10.98 35376 11.20 34392 11.42 33234 11.63 30294 11.96
42500 13.40 41662 13.62 40752 13.83 39747 14.03 38604 14.21 37134 14.38 33688 14.51
47134 17.33 46268 17.50 45312 17.65 44227 17.78 42938 17.88 40857 17.88 36604 17.51
Size 112A ATAD – 1160 RPM
Size 100A ATAD – 1160 RPM
CATALOG NUMBER
PROP
TYPE
RPM HP
100A307
100A312
100A317
100A322
100A327
100A332
100A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
5
5
71⁄2
71⁄2
10
15
15
100A607
100A612
100A617
100A622
100A627
100A632
100A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
71⁄2
71⁄2
10
15
15
20
25
Outlet Area = 8.45 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
17135 3.36 15553 3.52 13691 3.61 10518 3.38
21096 4.31 19660 4.56 17963 4.66 15462 4.66
25107 5.54 23594 5.83 22035 6.04 19740 6.13 16055 5.87
28805 7.53 27207 7.80 25476 7.98 23226 8.10 19655 7.97
32306 9.52 30522 9.71 28516 9.76 25983 9.73 22302 9.50
35475 11.94 33498 11.94 31267 11.88 28436 11.68 24672 11.34
38129 14.54 36231 14.46 33612 14.18 30106 13.71 25626 13.31
Fan Efficiency Grade = FEG63
6-BLADE
16945 5.51 15749 5.68 14275 5.70 12212 5.53 10052 5.50 8177 5.39
22057 6.92 21170 7.27 20077 7.55 18487 7.68 13974 7.04 10296 6.74
26478 8.46 25595 8.87 24586 9.28 23366 9.71 21724 10.07 11525 8.12
31270 11.24 30354 11.71 29321 12.17 28098 12.59 26523 12.97 24353 13.17
35716 14.34 34659 14.78 33469 15.21 32060 15.61 30257 15.98 28133 16.23
40133 18.23 38953 18.64 37601 19.02 35903 19.36 33556 19.57 31434 19.62
44535 23.52 43302 23.82 41840 24.07 39773 24.20 36306 23.90 34197 23.53
Size 100A ATAD – 1750 RPM
Outlet Area = 8.45 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
CATALOG NUMBER
11⁄2" SP
2" SP
21⁄2" SP
3" SP
31⁄2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
PROP TYPE RPM HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
100A307 ATAD 1750
15 27135 11.22 26132 11.46 25101 11.70 24057 11.96 22963 12.20 21756 12.34 18731 12.25
100A312 ATAD 1750
15 32928 14.16 32071 14.68 31168 15.13 30211 15.51 29199 15.77 28107 15.92 25352 16.07 21417 15.89
100A317 ATAD 1750
20 39102 18.40 38145 18.91 37163 19.37 36156 19.79 35144 20.17 34129 20.50 31763 20.99 27781 20.87
100A322 ATAD 1750
25 44716 25.24 43733 25.72 42712 26.17 41651 26.57 40547 26.92 39416 27.20 36887 27.62 33100 27.87 27802 26.86
100A327 ATAD 1750
30 50128 32.19 49044 32.59 47913 32.94 46727 33.22 45480 33.43 44171 33.52 41224 33.46 37217 33.30 31741 32.07
100A332 ATAD 1750
40 55058 40.94 53858 40.99 52605 41.01 51291 41.01 49907 40.96 48452 40.88 45170 40.54 40702 39.58 35557 38.69
CATALOG NUMBER
PROP
TYPE
RPM
HP
112A307
112A312
112A317
112A322
112A327
112A332
112A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
71⁄2
71⁄2
10
15
20
20
25
112A607
112A612
112A617
112A622
112A627
112A632
112A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
10
15
20
25
30
40
40
PerformanceData
PerformanceData
ATAD, Arrangement 4 - Direct Drive
Outlet Area = 10.60 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
24437 5.83 22694 6.06 20828 6.27 18570 6.32 14793 5.94
29928 7.45 28382 7.86 26665 8.09 24600 8.20 21686 8.17 17421 7.91
35583 9.61 33916 10.03 32209 10.38 30389 10.65 27680 10.75 23735 10.46
40777 13.10 39039 13.50 37179 13.82 35171 14.04 32562 14.20 28710 14.12
45727 16.61 43796 16.92 41687 17.10 39342 17.11 36425 17.07 32474 16.84
50217 20.93 48078 20.95 45738 20.91 43127 20.79 39865 20.49 35658 19.98
53889 25.52 51891 25.44 49502 25.24 46166 24.71 42207 24.05 37348 23.41
6-BLADE
Fan Efficiency Grade = FEG63
24044 9.58 22771 9.88 21306 10.01 19498 9.95 17126 9.70 14674 9.65 10433 9.30
31125 11.99 30181 12.51 29096 12.97 27764 13.32 25915 13.47 21929 13.07 13098 11.73
37323 14.69 36370 15.26 35320 15.84 34137 16.41 32744 17.03 30988 17.58
44046 19.54 43054 20.21 41972 20.86 40767 21.49 39373 22.08 37667 22.63 32160 22.94
50313 24.98 49166 25.61 47917 26.22 46532 26.81 44924 27.38 42958 27.91 38076 28.54
56531 31.82 55256 32.40 53851 32.96 52265 33.48 50313 33.94 47721 34.28 42911 34.37
62706 41.13 61385 41.57 59897 41.96 58155 42.28 55742 42.44 51679 42.05 46699 40.90
Size 112A ATAD – 1750 RPM
Outlet Area = 10.60 ft2
CU. FT. PER MIN. AND HORSEPOWER AT STATIC PRESSURE
CATALOG NUMBER
11⁄2" SP
2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
PROP TYPE RPM HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
112A307 ATAD 1750
20 38291 19.59 37177 19.93 36039 20.26 34879 20.61 33710 20.97 32497 21.31 29771 21.70
112A312 ATAD 1750
30 46362 24.64 45417 25.39 44433 26.07 43406 26.68 42329 27.20 41204 27.58 38730 28.00
112A317 ATAD 1750
40 55042 32.09 53979 32.81 52894 33.49 51788 34.12 50657 34.71 49523 35.25 47237 36.15
112A322 ATAD 1750
50 62912 44.10 61823 44.78 60703 45.43 59548 46.04 58356 46.59 57124 47.10 54578 47.87
21⁄2" SP
3" SP
31⁄2" SP
CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG71
26274 21.49 16420 17.99
35544 28.18 31304 27.98
44521 36.81 40220 36.77 34740 35.60
51699 48.43 47690 48.86 42300 48.24
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
14
Twin City Fan Catalog AX210
www.tcf.com
15
Size 100A ATAD – 870 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
100A307
100A312
100A317
100A322
100A327
100A332
100A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
11⁄2
2
3
5
5
5
71⁄2
100A607
100A612
100A617
100A622
100A627
100A632
100A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
3
3
5
5
71⁄2
71⁄2
10
ATAD, Arrangement 4 - Direct Drive
Outlet Area = 8.45 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
12980 1.41 11936 1.47 10772 1.52 9221 1.50
15934 1.80 14996 1.91 13933 1.96 12525 1.97 10510 1.95
18952 2.32 17951 2.43 16932 2.52 15722 2.58 13681 2.56
21730 3.16 20681 3.27 19556 3.34 18271 3.40 16321 3.42 13602 3.28
24369 4.01 23202 4.08 21913 4.12 20418 4.11 18366 4.09 15563 3.92
26761 5.04 25468 5.04 24036 5.02 22371 4.98 20088 4.85 17471 4.74
28739 6.14 27516 6.11 25970 6.04 23779 5.87 21250 5.69
6-BLADE
Fan Efficiency Grade = FEG63
12800 2.31 12025 2.39 11108 2.41 9878 2.36 8415 2.33 7057 2.31
16610 2.90 16035 3.04 15357 3.15 14464 3.23 12990 3.23 9219 2.86
19927 3.55 19350 3.70 18705 3.86 17957 4.01 17033 4.18 15737 4.26
23524 4.72 22925 4.90 22261 5.07 21506 5.23 20590 5.39 19414 5.51
26870 6.03 26178 6.19 25413 6.36 24545 6.51 23484 6.66 22177 6.78
30192 7.67 29421 7.83 28556 7.97 27551 8.10 26188 8.22 24585 8.27
33496 9.91 32694 10.02 31771 10.12 30643 10.19 28619 10.17 26659 10.03
Size 112A ATAD – 870 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
112A307
112A312
112A317
112A322
112A327
112A332
112A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
3
5
5
71⁄2
71⁄2
10
10
112A607
112A612
112A617
112A622
112A627
112A632
112A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
5
71⁄2
71⁄2
10
15
15
20
Outlet Area = 10.60 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
1/8" SP
1/4" SP
3/8" SP
1/2" SP
5/8" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
18469 2.45 17313 2.53 16112 2.62 14732 2.67 12935 2.63
22568 3.12 21555 3.28 20445 3.39 19192 3.44 17561 3.46 15397 3.43
26823 4.03 25720 4.20 24581 4.33 23428 4.45 22037 4.53 19821 4.51
30722 5.50 29577 5.66 28356 5.79 27072 5.89 25608 5.95 23538 6.00
34449 6.99 33180 7.11 31808 7.20 30319 7.22 28617 7.21 26410 7.19 20151 6.72
37833 8.83 36427 8.84 24906 8.83 33250 8.80 31355 8.73 28884 8.57
40571 10.77 39271 10.74 37771 10.69 35845 10.54 33331 10.30 30546 10.04
6-BLADE
Fan Efficiency Grade = FEG63
18132 4.03 17301 4.14 16366 4.21 15276 4.22 13851 4.14 12221 4.08 9209 4.03
23418 5.04 22801 5.23 22108 5.41 21301 5.56 20271 5.66 18806 5.69 11733 5.00
28068 6.17 27442 6.39 26762 6.60 26012 6.82 25162 7.04 24158 7.27 20902 7.41
33114 8.21 32461 8.46 31758 8.71 30990 8.95 30134 9.18 29134 9.40 26418 9.72
37826 10.51 37072 10.75 36260 10.98 35376 11.20 34392 11.42 33234 11.63 30294 11.96
42500 13.40 41662 13.62 40752 13.83 39747 14.03 38604 14.21 37134 14.38 33688 14.51
47134 17.33 46268 17.50 45312 17.65 44227 17.78 42938 17.88 40857 17.88 36604 17.51
Size 112A ATAD – 1160 RPM
Size 100A ATAD – 1160 RPM
CATALOG NUMBER
PROP
TYPE
RPM HP
100A307
100A312
100A317
100A322
100A327
100A332
100A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
5
5
71⁄2
71⁄2
10
15
15
100A607
100A612
100A617
100A622
100A627
100A632
100A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
71⁄2
71⁄2
10
15
15
20
25
Outlet Area = 8.45 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
17135 3.36 15553 3.52 13691 3.61 10518 3.38
21096 4.31 19660 4.56 17963 4.66 15462 4.66
25107 5.54 23594 5.83 22035 6.04 19740 6.13 16055 5.87
28805 7.53 27207 7.80 25476 7.98 23226 8.10 19655 7.97
32306 9.52 30522 9.71 28516 9.76 25983 9.73 22302 9.50
35475 11.94 33498 11.94 31267 11.88 28436 11.68 24672 11.34
38129 14.54 36231 14.46 33612 14.18 30106 13.71 25626 13.31
Fan Efficiency Grade = FEG63
6-BLADE
16945 5.51 15749 5.68 14275 5.70 12212 5.53 10052 5.50 8177 5.39
22057 6.92 21170 7.27 20077 7.55 18487 7.68 13974 7.04 10296 6.74
26478 8.46 25595 8.87 24586 9.28 23366 9.71 21724 10.07 11525 8.12
31270 11.24 30354 11.71 29321 12.17 28098 12.59 26523 12.97 24353 13.17
35716 14.34 34659 14.78 33469 15.21 32060 15.61 30257 15.98 28133 16.23
40133 18.23 38953 18.64 37601 19.02 35903 19.36 33556 19.57 31434 19.62
44535 23.52 43302 23.82 41840 24.07 39773 24.20 36306 23.90 34197 23.53
Size 100A ATAD – 1750 RPM
Outlet Area = 8.45 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
CATALOG NUMBER
11⁄2" SP
2" SP
21⁄2" SP
3" SP
31⁄2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
PROP TYPE RPM HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
100A307 ATAD 1750
15 27135 11.22 26132 11.46 25101 11.70 24057 11.96 22963 12.20 21756 12.34 18731 12.25
100A312 ATAD 1750
15 32928 14.16 32071 14.68 31168 15.13 30211 15.51 29199 15.77 28107 15.92 25352 16.07 21417 15.89
100A317 ATAD 1750
20 39102 18.40 38145 18.91 37163 19.37 36156 19.79 35144 20.17 34129 20.50 31763 20.99 27781 20.87
100A322 ATAD 1750
25 44716 25.24 43733 25.72 42712 26.17 41651 26.57 40547 26.92 39416 27.20 36887 27.62 33100 27.87 27802 26.86
100A327 ATAD 1750
30 50128 32.19 49044 32.59 47913 32.94 46727 33.22 45480 33.43 44171 33.52 41224 33.46 37217 33.30 31741 32.07
100A332 ATAD 1750
40 55058 40.94 53858 40.99 52605 41.01 51291 41.01 49907 40.96 48452 40.88 45170 40.54 40702 39.58 35557 38.69
CATALOG NUMBER
PROP
TYPE
RPM
HP
112A307
112A312
112A317
112A322
112A327
112A332
112A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
71⁄2
71⁄2
10
15
20
20
25
112A607
112A612
112A617
112A622
112A627
112A632
112A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
10
15
20
25
30
40
40
PerformanceData
PerformanceData
ATAD, Arrangement 4 - Direct Drive
Outlet Area = 10.60 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
24437 5.83 22694 6.06 20828 6.27 18570 6.32 14793 5.94
29928 7.45 28382 7.86 26665 8.09 24600 8.20 21686 8.17 17421 7.91
35583 9.61 33916 10.03 32209 10.38 30389 10.65 27680 10.75 23735 10.46
40777 13.10 39039 13.50 37179 13.82 35171 14.04 32562 14.20 28710 14.12
45727 16.61 43796 16.92 41687 17.10 39342 17.11 36425 17.07 32474 16.84
50217 20.93 48078 20.95 45738 20.91 43127 20.79 39865 20.49 35658 19.98
53889 25.52 51891 25.44 49502 25.24 46166 24.71 42207 24.05 37348 23.41
6-BLADE
Fan Efficiency Grade = FEG63
24044 9.58 22771 9.88 21306 10.01 19498 9.95 17126 9.70 14674 9.65 10433 9.30
31125 11.99 30181 12.51 29096 12.97 27764 13.32 25915 13.47 21929 13.07 13098 11.73
37323 14.69 36370 15.26 35320 15.84 34137 16.41 32744 17.03 30988 17.58
44046 19.54 43054 20.21 41972 20.86 40767 21.49 39373 22.08 37667 22.63 32160 22.94
50313 24.98 49166 25.61 47917 26.22 46532 26.81 44924 27.38 42958 27.91 38076 28.54
56531 31.82 55256 32.40 53851 32.96 52265 33.48 50313 33.94 47721 34.28 42911 34.37
62706 41.13 61385 41.57 59897 41.96 58155 42.28 55742 42.44 51679 42.05 46699 40.90
Size 112A ATAD – 1750 RPM
Outlet Area = 10.60 ft2
CU. FT. PER MIN. AND HORSEPOWER AT STATIC PRESSURE
CATALOG NUMBER
11⁄2" SP
2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
PROP TYPE RPM HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
112A307 ATAD 1750
20 38291 19.59 37177 19.93 36039 20.26 34879 20.61 33710 20.97 32497 21.31 29771 21.70
112A312 ATAD 1750
30 46362 24.64 45417 25.39 44433 26.07 43406 26.68 42329 27.20 41204 27.58 38730 28.00
112A317 ATAD 1750
40 55042 32.09 53979 32.81 52894 33.49 51788 34.12 50657 34.71 49523 35.25 47237 36.15
112A322 ATAD 1750
50 62912 44.10 61823 44.78 60703 45.43 59548 46.04 58356 46.59 57124 47.10 54578 47.87
21⁄2" SP
3" SP
31⁄2" SP
CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG71
26274 21.49 16420 17.99
35544 28.18 31304 27.98
44521 36.81 40220 36.77 34740 35.60
51699 48.43 47690 48.86 42300 48.24
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
14
Twin City Fan Catalog AX210
www.tcf.com
15
Size 125A ATAD – 870 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
125A307
125A312
125A317
125A322
125A327
125A332
125A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
5
71⁄2
71⁄2
10
15
15
20
125A607
125A612
125A617
125A622
125A627
125A632
125A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
71⁄2
10
15
20
20
25
30
Outlet Area = 13.21 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
1/8" SP
1/4" SP
3/8" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
26072 4.23 24795 4.35 23486 4.48 22104 4.59 18618 4.62
31741 5.37 30639 5.61 29454 5.80 28178 5.93 24998 6.03 19941 5.93
37708 6.96 36491 7.20 35233 7.41 33961 7.59 31172 7.86 26182 7.79
43154 9.52 41898 9.75 40577 9.95 39190 10.12 36148 10.34 31333 10.44
48383 12.12 46995 12.31 45522 12.45 43952 12.55 40407 12.56 35317 12.46 28042 11.69
53139 15.36 51601 15.38 49970 15.38 48228 15.36 44282 15.23 38646 14.77
56920 18.75 55519 18.73 53967 18.67 52202 18.57 47180 18.02 40705 17.29
Fan Efficiency Grade = FEG63
6-BLADE
25506 6.96 24605 7.14 23623 7.28 22536 7.35 19750 7.25 16101 7.10 12822 7.01
32821 8.70 32153 8.97 31425 9.24 30620 9.48 28584 9.83 24738 9.82 16331 8.70
39313 10.66 38628 10.97 37900 11.27 37120 11.57 35337 12.18 33028 12.80 29102 12.90
46357 14.21 45643 14.56 44887 14.91 44082 15.25 42270 15.90 39984 16.50 36819 16.92
52956 18.22 52130 18.55 51257 18.87 50328 19.19 48246 19.81 45601 20.39 42226 20.82
59496 23.24 58581 23.55 57607 23.86 56562 24.15 54173 24.68 50791 25.12 46961 25.26 43209 25.06
65964 30.11 65023 30.35 64009 30.57 62903 30.78 60267 31.10 55302 31.01 51029 30.47
Size 125A ATAD – 1160 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
125A307
125A312
125A317
125A322
125A327
125A332
125A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
10
15
20
25
30
40
50
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
20
25
30
40
50
125A607
125A612
125A617
125A622
125A627
ATAB, Arrangement 9 - Belt Driven
Outlet Area = 13.21 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG71
3-BLADE
34553 10.07 32625 10.39 30644 10.72 28458 10.96 25879 11.01 22103 10.60
42143 12.81 40468 13.42 38650 13.89 36657 14.14 34291 14.27 31111 14.25
50077 16.57 48241 17.19 46336 17.73 44432 18.18 42367 18.54 39525 18.72 30307 17.74
57334 22.65 55432 23.24 53417 23.75 51306 24.15 49036 24.44 46253 24.67 37389 24.16
64284 28.79 62180 29.27 59927 29.62 57506 29.80 54850 29.79 51698 29.73 42517 28.81
70601 36.43 68271 36.47 65773 36.46 63085 36.37 60126 36.20 56606 35.82 47296 34.54
75668 44.43 73529 44.37 71114 44.19 68224 43.81 64358 43.02 59987 42.11 48526 40.46
6-BLADE
Fan Efficiency Grade = FEG63
33863 16.56 32491 17.01 30973 17.33 29252 17.43 27178 17.32 24536 16.92 19182 16.77 14518 16.19
43654 20.70 42636 21.43 41512 22.11 40237 22.72 38710 23.19 36725 23.43 25857 21.05 18228 20.42
52306 25.37 51268 26.17 50153 26.98 48941 27.78 47600 28.58 46073 29.43 41960 30.81
61693 33.79 60611 34.73 59455 35.65 58209 36.54 56847 37.41 55318 38.25 51389 39.71 44758 39.32
70474 43.28 69222 44.15 67888 45.02 66452 45.86 64886 46.68 63124 47.48 58642 48.91 53057 49.69
Size 125A ATAD – 1750 RPM
Outlet Area = 13.21 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
CATALOG NUMBER
2" SP
21⁄2" SP
3" SP
31⁄2" SP 4" SP
1/4" SP 1/2" SP 3/4" SP
1" SP
11⁄4" SP 11⁄2" SP
PROP TYPE RPM HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
125A307 ATAD 1750
40 5370833.985247234.455121434.934993435.404863735.884733336.394459737.314149937.793775837.643210435.95
125A312 ATAD 1750
50 6491642.636387243.706279544.696168245.616052946.455933247.195680248.215399548.755056049.064612048.884070848.34
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
040 A 3 27 ATAB 2093 1/2
Catalog Numbering System
To identify a specific fan for ordering or engineering
specifications, it is necessary to show the complete
information listed in the tables below under “catalog
number.” All performance data is available in curve
form upon request.
The model ATAB fans shown herein have been
tested in accordance with ASHRAE 51-85 and
AMCA 210-85 Test Code and are guaranteed by the
manufacturer to deliver rated performance.
Wheel Dia. (cm)
Wheel Design
No. Blades
Blade Angle (Degrees)
Fan Type
Fan RPM
Motor HP
Outlet Area = 1.35 ft2
Fan Efficiency Grade = FEG50
Size 040A327 ATAB
CATALOG NUMBER
PROP
TYPE
RPM
040A327
ATAB
2093
040A327
ATAB
2396
040A327
ATAB
2637
040A327
ATAB
3018
040A327
ATAB
3322
040A327
ATAB
3803
HP
1/2
3/4
1
11⁄2
2
3
1/4"
CFM
2857
3383
3790
4419
4914
5688
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.55 2344 0.54
0.82 2990 0.82 2459 0.80
1.09 3453 1.10 3038 1.09 2465 1.03
1.63 4143 1.64 3826 1.65 3448 1.63 2969 1.57
2.17 4671 2.18 4401 2.20 4095 2.19 3735 2.16 3297 2.10
3.24 5482 3.27 5261 3.28 5021 3.30 4756 3.30 4459 3.27 3714 3.14
Outlet Area = 2.11 ft2
Fan Efficiency Grade = FEG60
Size 050A327 ATAB
CATALOG NUMBER
PROP
TYPE
RPM
050A327
ATAB
1380
050A327
ATAB
1579
050A327
ATAB
1738
050A327
ATAB
1990
050A327
ATAB
2190
050A327
ATAB
2507
050A327
ATAB
2973
HP
1/2
3/4
1
11⁄2
2
3
5
1/4"
CFM
4040
4864
5481
6426
7159
8303
9960
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.55
0.82 3868 0.78
1.09 4727 1.08 3569 0.98
1.63 5880 1.65 5057 1.59
2.17 6708 2.20 6085 2.18 5226 2.07
3.24 7938 3.28 7498 3.30 6923 3.26 6175 3.15 5409 3.01
5.37 9671 5.43 9351 5.48 8983 5.50 8532 5.48 8002 5.41 6707 5.10
Outlet Area = 3.36 ft2
Fan Efficiency Grade = FEG60
Size 063A327 ATAB
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
CATALOG NUMBER
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
PROP
TYPE
RPM
HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
063A327
ATAB
1075
3/4 6233 0.82
063A327
ATAB
1183
1 7155 1.10 5357 1.02
063A327
ATAB
1354
11⁄2 8505 1.64 7247 1.62
063A327
ATAB
1490
2 9534 2.18 8542 2.19 7014 2.07
063A327
ATAB
1706
3
11128 3.25 10387 3.30 9351 3.26 7940 3.09
063A327
ATAB
2023
5
13415 5.39 12851 5.47 12177 5.50 11302 5.45 10179 5.29 8985 5.08
063A327
ATAB
2315
71⁄2 15492 8.05 15023 8.15 14499 8.21 13887 8.24 13132 8.19 12238 8.06 10128 7.57
063A327
ATAB
2548
10 17137 10.71 16721 10.82 16269 10.91 15769 10.97 15188 10.98 14497 10.93 12751 10.54 10807 9.98
Outlet Area = 4.26 ft2
Fan Efficiency Grade = FEG56
Size 071A327 ATAB
PerformanceData
PerformanceData
ATAD, Arrangement 4 - Direct Drive
CATALOG NUMBER
PROP
TYPE
RPM
071A327
ATAB
881
071A327
ATAB
969
071A327
ATAB
1110
071A327
ATAB
1221
071A327
ATAB
1398
071A327
ATAB
1657
071A327
ATAB
1897
071A327
ATAB
2088
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3/4 6952 0.82
1 8107 1.10
11⁄2 9781 1.65 7762 1.57
2
11015 2.19 9485 2.17 7100 1.96
3
12915 3.27 11808 3.30 10135 3.18
5
15618 5.40 14810 5.48 13771 5.48 12380 5.35 10713 5.10
71⁄2 18077 8.07 17414 8.17 16650 8.23 15693 8.22 14512 8.09 13028 7.79
10 20016 10.73 19432 10.86 18784 10.95 18037 10.99 17120 10.94 16043 10.80 13423 10.18
Power ratings (BHP) do not include transmission losses.
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
16
Twin City Fan Catalog AX210
www.tcf.com
17
Size 125A ATAD – 870 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
125A307
125A312
125A317
125A322
125A327
125A332
125A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
5
71⁄2
71⁄2
10
15
15
20
125A607
125A612
125A617
125A622
125A627
125A632
125A637
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
870
870
870
870
870
870
870
71⁄2
10
15
20
20
25
30
Outlet Area = 13.21 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
1/8" SP
1/4" SP
3/8" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
26072 4.23 24795 4.35 23486 4.48 22104 4.59 18618 4.62
31741 5.37 30639 5.61 29454 5.80 28178 5.93 24998 6.03 19941 5.93
37708 6.96 36491 7.20 35233 7.41 33961 7.59 31172 7.86 26182 7.79
43154 9.52 41898 9.75 40577 9.95 39190 10.12 36148 10.34 31333 10.44
48383 12.12 46995 12.31 45522 12.45 43952 12.55 40407 12.56 35317 12.46 28042 11.69
53139 15.36 51601 15.38 49970 15.38 48228 15.36 44282 15.23 38646 14.77
56920 18.75 55519 18.73 53967 18.67 52202 18.57 47180 18.02 40705 17.29
Fan Efficiency Grade = FEG63
6-BLADE
25506 6.96 24605 7.14 23623 7.28 22536 7.35 19750 7.25 16101 7.10 12822 7.01
32821 8.70 32153 8.97 31425 9.24 30620 9.48 28584 9.83 24738 9.82 16331 8.70
39313 10.66 38628 10.97 37900 11.27 37120 11.57 35337 12.18 33028 12.80 29102 12.90
46357 14.21 45643 14.56 44887 14.91 44082 15.25 42270 15.90 39984 16.50 36819 16.92
52956 18.22 52130 18.55 51257 18.87 50328 19.19 48246 19.81 45601 20.39 42226 20.82
59496 23.24 58581 23.55 57607 23.86 56562 24.15 54173 24.68 50791 25.12 46961 25.26 43209 25.06
65964 30.11 65023 30.35 64009 30.57 62903 30.78 60267 31.10 55302 31.01 51029 30.47
Size 125A ATAD – 1160 RPM
CATALOG NUMBER
PROP
TYPE
RPM
HP
125A307
125A312
125A317
125A322
125A327
125A332
125A337
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
1160
1160
10
15
20
25
30
40
50
ATAD
ATAD
ATAD
ATAD
ATAD
1160
1160
1160
1160
1160
20
25
30
40
50
125A607
125A612
125A617
125A622
125A627
ATAB, Arrangement 9 - Belt Driven
Outlet Area = 13.21 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
Fan Efficiency Grade = FEG71
3-BLADE
34553 10.07 32625 10.39 30644 10.72 28458 10.96 25879 11.01 22103 10.60
42143 12.81 40468 13.42 38650 13.89 36657 14.14 34291 14.27 31111 14.25
50077 16.57 48241 17.19 46336 17.73 44432 18.18 42367 18.54 39525 18.72 30307 17.74
57334 22.65 55432 23.24 53417 23.75 51306 24.15 49036 24.44 46253 24.67 37389 24.16
64284 28.79 62180 29.27 59927 29.62 57506 29.80 54850 29.79 51698 29.73 42517 28.81
70601 36.43 68271 36.47 65773 36.46 63085 36.37 60126 36.20 56606 35.82 47296 34.54
75668 44.43 73529 44.37 71114 44.19 68224 43.81 64358 43.02 59987 42.11 48526 40.46
6-BLADE
Fan Efficiency Grade = FEG63
33863 16.56 32491 17.01 30973 17.33 29252 17.43 27178 17.32 24536 16.92 19182 16.77 14518 16.19
43654 20.70 42636 21.43 41512 22.11 40237 22.72 38710 23.19 36725 23.43 25857 21.05 18228 20.42
52306 25.37 51268 26.17 50153 26.98 48941 27.78 47600 28.58 46073 29.43 41960 30.81
61693 33.79 60611 34.73 59455 35.65 58209 36.54 56847 37.41 55318 38.25 51389 39.71 44758 39.32
70474 43.28 69222 44.15 67888 45.02 66452 45.86 64886 46.68 63124 47.48 58642 48.91 53057 49.69
Size 125A ATAD – 1750 RPM
Outlet Area = 13.21 ft2
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
CATALOG NUMBER
2" SP
21⁄2" SP
3" SP
31⁄2" SP 4" SP
1/4" SP 1/2" SP 3/4" SP
1" SP
11⁄4" SP 11⁄2" SP
PROP TYPE RPM HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3-BLADE
Fan Efficiency Grade = FEG71
125A307 ATAD 1750
40 5370833.985247234.455121434.934993435.404863735.884733336.394459737.314149937.793775837.643210435.95
125A312 ATAD 1750
50 6491642.636387243.706279544.696168245.616052946.455933247.195680248.215399548.755056049.064612048.884070848.34
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
040 A 3 27 ATAB 2093 1/2
Catalog Numbering System
To identify a specific fan for ordering or engineering
specifications, it is necessary to show the complete
information listed in the tables below under “catalog
number.” All performance data is available in curve
form upon request.
The model ATAB fans shown herein have been
tested in accordance with ASHRAE 51-85 and
AMCA 210-85 Test Code and are guaranteed by the
manufacturer to deliver rated performance.
Wheel Dia. (cm)
Wheel Design
No. Blades
Blade Angle (Degrees)
Fan Type
Fan RPM
Motor HP
Outlet Area = 1.35 ft2
Fan Efficiency Grade = FEG50
Size 040A327 ATAB
CATALOG NUMBER
PROP
TYPE
RPM
040A327
ATAB
2093
040A327
ATAB
2396
040A327
ATAB
2637
040A327
ATAB
3018
040A327
ATAB
3322
040A327
ATAB
3803
HP
1/2
3/4
1
11⁄2
2
3
1/4"
CFM
2857
3383
3790
4419
4914
5688
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.55 2344 0.54
0.82 2990 0.82 2459 0.80
1.09 3453 1.10 3038 1.09 2465 1.03
1.63 4143 1.64 3826 1.65 3448 1.63 2969 1.57
2.17 4671 2.18 4401 2.20 4095 2.19 3735 2.16 3297 2.10
3.24 5482 3.27 5261 3.28 5021 3.30 4756 3.30 4459 3.27 3714 3.14
Outlet Area = 2.11 ft2
Fan Efficiency Grade = FEG60
Size 050A327 ATAB
CATALOG NUMBER
PROP
TYPE
RPM
050A327
ATAB
1380
050A327
ATAB
1579
050A327
ATAB
1738
050A327
ATAB
1990
050A327
ATAB
2190
050A327
ATAB
2507
050A327
ATAB
2973
HP
1/2
3/4
1
11⁄2
2
3
5
1/4"
CFM
4040
4864
5481
6426
7159
8303
9960
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
0.55
0.82 3868 0.78
1.09 4727 1.08 3569 0.98
1.63 5880 1.65 5057 1.59
2.17 6708 2.20 6085 2.18 5226 2.07
3.24 7938 3.28 7498 3.30 6923 3.26 6175 3.15 5409 3.01
5.37 9671 5.43 9351 5.48 8983 5.50 8532 5.48 8002 5.41 6707 5.10
Outlet Area = 3.36 ft2
Fan Efficiency Grade = FEG60
Size 063A327 ATAB
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
CATALOG NUMBER
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
PROP
TYPE
RPM
HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
063A327
ATAB
1075
3/4 6233 0.82
063A327
ATAB
1183
1 7155 1.10 5357 1.02
063A327
ATAB
1354
11⁄2 8505 1.64 7247 1.62
063A327
ATAB
1490
2 9534 2.18 8542 2.19 7014 2.07
063A327
ATAB
1706
3
11128 3.25 10387 3.30 9351 3.26 7940 3.09
063A327
ATAB
2023
5
13415 5.39 12851 5.47 12177 5.50 11302 5.45 10179 5.29 8985 5.08
063A327
ATAB
2315
71⁄2 15492 8.05 15023 8.15 14499 8.21 13887 8.24 13132 8.19 12238 8.06 10128 7.57
063A327
ATAB
2548
10 17137 10.71 16721 10.82 16269 10.91 15769 10.97 15188 10.98 14497 10.93 12751 10.54 10807 9.98
Outlet Area = 4.26 ft2
Fan Efficiency Grade = FEG56
Size 071A327 ATAB
PerformanceData
PerformanceData
ATAD, Arrangement 4 - Direct Drive
CATALOG NUMBER
PROP
TYPE
RPM
071A327
ATAB
881
071A327
ATAB
969
071A327
ATAB
1110
071A327
ATAB
1221
071A327
ATAB
1398
071A327
ATAB
1657
071A327
ATAB
1897
071A327
ATAB
2088
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
3/4 6952 0.82
1 8107 1.10
11⁄2 9781 1.65 7762 1.57
2
11015 2.19 9485 2.17 7100 1.96
3
12915 3.27 11808 3.30 10135 3.18
5
15618 5.40 14810 5.48 13771 5.48 12380 5.35 10713 5.10
71⁄2 18077 8.07 17414 8.17 16650 8.23 15693 8.22 14512 8.09 13028 7.79
10 20016 10.73 19432 10.86 18784 10.95 18037 10.99 17120 10.94 16043 10.80 13423 10.18
Power ratings (BHP) do not include transmission losses.
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
16
Twin City Fan Catalog AX210
www.tcf.com
17
Size 080A327 ATAB
Outlet Area = 5.41 ft2
Fan Efficiency Grade = FEG67
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
CATALOG NUMBER
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
PROP
TYPE
RPM
HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
080A327
ATAB
815
1 9859 1.10
080A327
ATAB
933
11⁄2 11925 1.64 8916 1.60
080A327
ATAB
1027
2
13487 2.19 11365 2.19
080A327
ATAB
1175
3
15869 3.26 14352 3.29 11771 3.21
080A327
ATAB
1393
5
19273 5.39 18094 5.46 16731 5.49 14539 5.40
080A327
ATAB
1595
71⁄2 22364 8.0621381 8.16 20298 8.22 19066 8.24 17246 8.15 14860 7.94
080A327
ATAB
1756
10 24800 10.73 23930 10.84 22986 10.93 21966 10.99 20795 11.00 19116 10.89
080A327
ATAB
2010
15 28614 16.05 27872 16.19 27087 16.30 26251 16.40 25366 16.46 24400 16.50 21619 16.30 17624 15.65
Size 090A327 ATAB
CATALOG NUMBER
PROP
TYPE
RPM
HP
090A327
ATAB
768
11⁄2
090A327
ATAB
845
2
090A327
ATAB
967
3
090A327
ATAB
1147
5
090A327
ATAB
1313
71⁄2
090A327
ATAB
1445
10
090A327
ATAB
1654
15
090A327
ATAB
1820
20
Outlet Area = 6.85 ft2
Fan Efficiency Grade = FEG67
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
13549 1.65
15422 2.19 11827 2.14
18270 3.27 16027 3.29 11432 3.07
22317 5.41 20657 5.49 18510 5.48 14840 5.27
25957 8.09 24581 8.19 23037 8.24 21006 8.21 17831 7.98
28813 10.75 27601 10.87 26268 10.96 24776 11.00 22714 10.92 19788 10.66
33292 16.07 32266 16.22 31165 16.35 29983 16.44 28697 16.49 27152 16.46 22291 15.94
36823 21.37 35906 21.55 34937 21.70 33906 21.82 32817 21.92 31644 21.97 28459 21.80 23740 21.10
Size 100A327 ATAB
CATALOG NUMBER
PROP
TYPE
RPM
HP
100A327
ATAB
643
11⁄2
100A327
ATAB
708
2
100A327
ATAB
810
3
100A327
ATAB
960
5
100A327
ATAB
1099
71⁄2
100A327
ATAB
1210
10
100A327
ATAB
1385
15
100A327
ATAB
1525
20
CATALOG NUMBER
PROP
TYPE
RPM
HP
112A327
ATAB
672
3
112A327
ATAB
796
5
112A327
ATAB
912
71⁄2
112A327
ATAB
1003
10
112A327
ATAB
1149
15
112A327
ATAB
1264
20
112A327
ATAB
1362
25
112A327
ATAB
1447
30
Outlet Area = 13.21 ft2
Fan Efficiency Grade = FEG67
Size 125A327 ATAB
CATALOG NUMBER
PROP
TYPE
RPM
HP
125A327
ATAB
558
3
125A327
ATAB
662
5
125A327
ATAB
758
71⁄2
125A327
ATAB
834
10
125A327
ATAB
955
15
125A327
ATAB
1051
20
125A327
ATAB
1132
25
125A327
ATAB
1203
30
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
26580 3.29
33254 5.46 28215 5.47
39143 8.15 35487 8.25 29371 8.07
43695 10.82 40536 10.96 36553 10.97 29722 10.59
50818 16.17 48199 16.37 45269 16.49 41542 16.45 35574 16.03
56398 21.50 54087 21.74 51552 21.91 48736 22.00 44997 21.88 39455 21.39
61073 26.81 58965 27.09 56684 27.30 54221 27.44 51423 27.48 47514 27.26
65150 32.14 63191 32.44 61096 32.69 58847 32.87 56417 32.98 53561 32.95 44494 32.00
Power ratings (BHP) do not include transmission losses.
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Dimensional Data
Inlet Bell
C
FLANGES BOLTED
Outlet Area = 8.45 ft2
Fan Efficiency Grade = FEG67
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
15089 1.65
17362 2.20
20715 3.28 17207 3.26
25429 5.42 23140 5.49 19427 5.39
29668 8.09 27790 8.20 25593 8.24 21945 8.06
32999 10.77 31353 10.90 29518 10.98 27261 10.97 23586 10.72
38190 16.09 36805 16.26 35300 16.39 33668 16.47 31759 16.48 28891 16.27
42306 21.43 41073 21.63 39757 21.80 38347 21.92 36834 22.00 35091 22.00 29552 21.43
Size 112A327 ATAB
ATAB, Arrangement 9 - Belt Driven
Power ratings (BHP) do not include transmission losses.
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
FAN
SIZE
035
040
050
063
071
080
090
100
112
125
AIRFLOW
A
B
A
B
C
WT.
13.78
15.75
19.68
24.80
27.95
31.50
35.43
39.37
44.09
49.21
N/A
23.75
27.68
32.80
38.00
41.50
45.40
49.40
54.10
63.20
N/A
4.00
4.00
4.00
5.00
5.00
5.00
5.00
5.00
7.00
N/A
10
13
14
19
20
24
28
38
48
Dimensions are not to be used for
construction.
FAN (REF.)
Outlet Area = 10.60 ft2
Fan Efficiency Grade = FEG67
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
23569 3.29 17819 3.20
29138 5.43 25849 5.49 19727 5.25
34158 8.13 31548 8.24 28076 8.22 22134 7.86
38021 10.78 35738 10.92 33110 10.98 28978 10.81 22851 10.22
44132 16.14 42228 16.33 40133 16.46 37765 16.51 34366 16.36 29758 15.95
48894 21.44 47204 21.66 45375 21.83 43401 21.95 41155 21.97 38012 21.80
52927 26.78 51383 27.03 49734 27.23 47967 27.39 46069 27.48 43883 27.48 36933 26.77
56411 32.08 54973 32.35 53451 32.58 51830 32.77 50117 32.90 48257 32.97 43026 32.64 35461 31.47
Twin City Fan Catalog AX210
AC16554
INLET BELL
Inlet & Outlet Cone
CL
FF
EE
AA
BB
FAN
SIZE
035
040
050
063
071
080
090
100
112
125
AA
18.0
20.0
24.0
32.0
36.0
40.0
44.0
50.0
56.0
62.0
BB
CL
18.63 8.5
21.13 8.5
25.13 8.5
33.50
13.0
37.50
14.0
41.50
16.0
45.50
18.0
51.50
20.0
57.50
22.0
63.50
25.0
Dimensions are not to be used for construction.
18
PerformanceData
PerformanceData
ATAB, Arrangement 9 - Belt Driven
www.tcf.com
EE
FF
GA.
WT.
13.78
15.75
19.68
24.80
27.95
31.50
35.43
39.37
44.09
49.21
15.31
17.38
21.31
26.68
29.85
33.38
37.31
41.25
46.00
51.09
18
18
18
18
18
18
18
16
16
14
16
19
22
32
37
45
53
63
75
90
AC16562-A
19
Size 080A327 ATAB
Outlet Area = 5.41 ft2
Fan Efficiency Grade = FEG67
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
CATALOG NUMBER
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
PROP
TYPE
RPM
HP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
080A327
ATAB
815
1 9859 1.10
080A327
ATAB
933
11⁄2 11925 1.64 8916 1.60
080A327
ATAB
1027
2
13487 2.19 11365 2.19
080A327
ATAB
1175
3
15869 3.26 14352 3.29 11771 3.21
080A327
ATAB
1393
5
19273 5.39 18094 5.46 16731 5.49 14539 5.40
080A327
ATAB
1595
71⁄2 22364 8.0621381 8.16 20298 8.22 19066 8.24 17246 8.15 14860 7.94
080A327
ATAB
1756
10 24800 10.73 23930 10.84 22986 10.93 21966 10.99 20795 11.00 19116 10.89
080A327
ATAB
2010
15 28614 16.05 27872 16.19 27087 16.30 26251 16.40 25366 16.46 24400 16.50 21619 16.30 17624 15.65
Size 090A327 ATAB
CATALOG NUMBER
PROP
TYPE
RPM
HP
090A327
ATAB
768
11⁄2
090A327
ATAB
845
2
090A327
ATAB
967
3
090A327
ATAB
1147
5
090A327
ATAB
1313
71⁄2
090A327
ATAB
1445
10
090A327
ATAB
1654
15
090A327
ATAB
1820
20
Outlet Area = 6.85 ft2
Fan Efficiency Grade = FEG67
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
13549 1.65
15422 2.19 11827 2.14
18270 3.27 16027 3.29 11432 3.07
22317 5.41 20657 5.49 18510 5.48 14840 5.27
25957 8.09 24581 8.19 23037 8.24 21006 8.21 17831 7.98
28813 10.75 27601 10.87 26268 10.96 24776 11.00 22714 10.92 19788 10.66
33292 16.07 32266 16.22 31165 16.35 29983 16.44 28697 16.49 27152 16.46 22291 15.94
36823 21.37 35906 21.55 34937 21.70 33906 21.82 32817 21.92 31644 21.97 28459 21.80 23740 21.10
Size 100A327 ATAB
CATALOG NUMBER
PROP
TYPE
RPM
HP
100A327
ATAB
643
11⁄2
100A327
ATAB
708
2
100A327
ATAB
810
3
100A327
ATAB
960
5
100A327
ATAB
1099
71⁄2
100A327
ATAB
1210
10
100A327
ATAB
1385
15
100A327
ATAB
1525
20
CATALOG NUMBER
PROP
TYPE
RPM
HP
112A327
ATAB
672
3
112A327
ATAB
796
5
112A327
ATAB
912
71⁄2
112A327
ATAB
1003
10
112A327
ATAB
1149
15
112A327
ATAB
1264
20
112A327
ATAB
1362
25
112A327
ATAB
1447
30
Outlet Area = 13.21 ft2
Fan Efficiency Grade = FEG67
Size 125A327 ATAB
CATALOG NUMBER
PROP
TYPE
RPM
HP
125A327
ATAB
558
3
125A327
ATAB
662
5
125A327
ATAB
758
71⁄2
125A327
ATAB
834
10
125A327
ATAB
955
15
125A327
ATAB
1051
20
125A327
ATAB
1132
25
125A327
ATAB
1203
30
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
26580 3.29
33254 5.46 28215 5.47
39143 8.15 35487 8.25 29371 8.07
43695 10.82 40536 10.96 36553 10.97 29722 10.59
50818 16.17 48199 16.37 45269 16.49 41542 16.45 35574 16.03
56398 21.50 54087 21.74 51552 21.91 48736 22.00 44997 21.88 39455 21.39
61073 26.81 58965 27.09 56684 27.30 54221 27.44 51423 27.48 47514 27.26
65150 32.14 63191 32.44 61096 32.69 58847 32.87 56417 32.98 53561 32.95 44494 32.00
Power ratings (BHP) do not include transmission losses.
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
Dimensional Data
Inlet Bell
C
FLANGES BOLTED
Outlet Area = 8.45 ft2
Fan Efficiency Grade = FEG67
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
15089 1.65
17362 2.20
20715 3.28 17207 3.26
25429 5.42 23140 5.49 19427 5.39
29668 8.09 27790 8.20 25593 8.24 21945 8.06
32999 10.77 31353 10.90 29518 10.98 27261 10.97 23586 10.72
38190 16.09 36805 16.26 35300 16.39 33668 16.47 31759 16.48 28891 16.27
42306 21.43 41073 21.63 39757 21.80 38347 21.92 36834 22.00 35091 22.00 29552 21.43
Size 112A327 ATAB
ATAB, Arrangement 9 - Belt Driven
Power ratings (BHP) do not include transmission losses.
Performance certified is for installation type D: Ducted inlet, ducted outlet.
Performance ratings do not include the effects of appurtenances (accessories).
FAN
SIZE
035
040
050
063
071
080
090
100
112
125
AIRFLOW
A
B
A
B
C
WT.
13.78
15.75
19.68
24.80
27.95
31.50
35.43
39.37
44.09
49.21
N/A
23.75
27.68
32.80
38.00
41.50
45.40
49.40
54.10
63.20
N/A
4.00
4.00
4.00
5.00
5.00
5.00
5.00
5.00
7.00
N/A
10
13
14
19
20
24
28
38
48
Dimensions are not to be used for
construction.
FAN (REF.)
Outlet Area = 10.60 ft2
Fan Efficiency Grade = FEG67
CUBIC FEET PER MINUTE AND HORSEPOWER AT STATIC PRESSURE
11⁄2" SP
2" SP
21⁄2" SP
3" SP
1/4" SP
1/2" SP
3/4" SP
1" SP
11⁄4" SP
CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP
23569 3.29 17819 3.20
29138 5.43 25849 5.49 19727 5.25
34158 8.13 31548 8.24 28076 8.22 22134 7.86
38021 10.78 35738 10.92 33110 10.98 28978 10.81 22851 10.22
44132 16.14 42228 16.33 40133 16.46 37765 16.51 34366 16.36 29758 15.95
48894 21.44 47204 21.66 45375 21.83 43401 21.95 41155 21.97 38012 21.80
52927 26.78 51383 27.03 49734 27.23 47967 27.39 46069 27.48 43883 27.48 36933 26.77
56411 32.08 54973 32.35 53451 32.58 51830 32.77 50117 32.90 48257 32.97 43026 32.64 35461 31.47
Twin City Fan Catalog AX210
AC16554
INLET BELL
Inlet & Outlet Cone
CL
FF
EE
AA
BB
FAN
SIZE
035
040
050
063
071
080
090
100
112
125
AA
18.0
20.0
24.0
32.0
36.0
40.0
44.0
50.0
56.0
62.0
BB
CL
18.63 8.5
21.13 8.5
25.13 8.5
33.50
13.0
37.50
14.0
41.50
16.0
45.50
18.0
51.50
20.0
57.50
22.0
63.50
25.0
Dimensions are not to be used for construction.
18
PerformanceData
PerformanceData
ATAB, Arrangement 9 - Belt Driven
www.tcf.com
EE
FF
GA.
WT.
13.78
15.75
19.68
24.80
27.95
31.50
35.43
39.37
44.09
49.21
15.31
17.38
21.31
26.68
29.85
33.38
37.31
41.25
46.00
51.09
18
18
18
18
18
18
18
16
16
14
16
19
22
32
37
45
53
63
75
90
AC16562-A
19
ATAD, Arrangement 4 - Direct Drive
Fans, where indicated on drawings and schedules, shall be AXIPAL®, Model ATAD, Arrangement 4, direct drive,
axial flow type with fan blades being capable of individual manual pitch adjustment while the fan is stopped.
Fans shall be as manufactured by Twin City Fan & Blower, Minneapolis, Minnesota, and shall be of the size
and capacity as indicated in the fan schedules.
C DIA.
B DIA. B.C.
A DIA. I.D.
D
PERFORMANCE — Performance ratings shall conform to AMCA Standard 205 (fan efficiency grade), 211 (air
performance) and 311 (sound performance). Fans shall be tested in accordance with ANSI/AMCA Standard 210
(air performance) and 300 (sound performance) in an AMCA accredited laboratory. Fans shall be licensed to
bear the AMCA certified ratings seal for both sound and air, and fan efficiency grade (FEG).
E GA.
AIRFLOW
CONSTRUCTION — Fan casings shall be welded of ASTM A-569 low carbon, commercial quality 14-gauge hot
rolled steel in sizes through 14" diameter, 12-gauge hot rolled steel in sizes through 20" diameter, 10-gauge
hot rolled steel from 24" diameter through 28" diameter, and 7-gauge hot rolled steel on sizes above 30" in
diameter. Inlet and outlet flanges shall be integrally rolled mechanically from fan casing sheet steel to insure
concentricity and alignment. Accuracy and uniformity of the fan casing shall be insured through the use of
welding jigs and fixtures. A fabricated steel motor support base of minimum 3∕16" thick plate steel shall be
welded into the inlet end of the fan casing.
PROPELLERS — Fan blades shall be permanent mold A319 aluminum precision alloy castings. Fan center hub
boss shall be cast iron bolted to stamped steel hub halves coated by electrodeposition. Blade tip clearance
shall be within tolerance to meet certified performance. Fan blade pitch angle shall be individually manually
adjustable when fan is stopped. The fan propeller shall be secured directly to the motor shaft with knurled cup
point set screws in all sizes to 20" diameter and split taper lock bushings in all larger sizes. The motor and
propeller assembly shall be enclosed entirely within the fan casing.
(H) 7/16 DIA. HOLES (EA. END)
FAN
E
A
B
C
D
H
SIZE
(GA.)
155⁄16
1625⁄32
18
14 8
035
1325⁄32
173⁄8
183⁄4
18
12 8
040
153⁄4
215⁄16
2211⁄16
20
12 8
050
1911⁄16
2611⁄16
285⁄16
24
10 8
063
2413⁄16
297⁄8
3115⁄32
28
10
12
071
2731⁄32
333⁄8
341⁄2
28 7
12
080
311⁄2
375⁄16
387⁄16
36 7
12
090
357⁄16
411⁄4
423⁄8
36 7
12
100
393⁄8
4531⁄32
473⁄32
38 7
16
112
443⁄32
513⁄32
527⁄32
40 7
16
125
497⁄32
Dimensions are not to be used for construction.
*LESS MOTOR
TypicalSpecifications
DimensionalData
ATAD, Arrangement 4 - Direct Drive
MAX.
WEIGHT
MOTOR
(LBS.)*
FRAME
145T/U 25
145T/U 37
184T/U 51
215T/U
104
254T/U
127
254T/U
191
326T/U
275
326T/U
353
326T/U
394
365T/U
465
AC16551
BALANCING — The fan propeller assembly shall be statically and dynamically balanced in accordance with ANSI/
AMCA 204-96 “Balance Quality and Vibration Levels for Fans” to Fan Application Category BV-3, Balance Quality
Grade G6.3. In addition, direct drive fan propellers shall be balanced on the motor shaft after final assembly in
the fan casing, in the manufacturing facility to the following peak velocity values, filter-in, at the fan test speed:
Fan Application Category
BV-3
Rigidly Mounted (In/Sec)
0.15
Flexibly Mounted (In/Sec)
0.20
Final test room vibration levels in the axial, vertical, and horizontal planes shall be recorded and a written copy
shall be available upon request.
MOTORS — Fan motors shall be manufactured in accordance with current applicable standards of IEEE and
NEMA. They shall be foot-mounted, NEMA standard, open drip-proof (ODP), continuous duty, ball bearing with
class “B” insulation. External grease fittings with extended grease leads shall be supplied for lubrication of the
motor bearings on all motors that provide grease fittings. Motor bearings shall have a minimum L-10 life as
defined by AFBMA of at least 40,000 hours (200,000 hours average life).
FINISH — The units, after fabrication, shall be cleaned and chemically pretreated by a phosphatizing process
and shall be painted inside and out with two coats of air dry enamel. The fan shall be coated with the following
optional finishes:
qCarbocoat 30 (Replaces Sanitile 550)
qPlasite 4310 – Vinyl Ester
qPlasite 7122L – Air Dry Epoxy Phenolic
qHeresite VR506 – Air Dry Phenolic
qHot Dip Galvanizing
qPlasite 9500 (Replaces Plasite 1246)
qPlasite 3070 (Replaces Plasite 3066)
qDupont ASA – 70 Gray – Polyester (Replaces Farboil)
GUARANTEE — The manufacturer shall guarantee the workmanship and materials for its AXIPAL®, Model ATAD
fans for at least one (1) year from startup or eighteen (18) months from shipment, whichever occurs first.
20
Twin City Fan Catalog AX210
www.tcf.com
21
ATAD, Arrangement 4 - Direct Drive
Fans, where indicated on drawings and schedules, shall be AXIPAL®, Model ATAD, Arrangement 4, direct drive,
axial flow type with fan blades being capable of individual manual pitch adjustment while the fan is stopped.
Fans shall be as manufactured by Twin City Fan & Blower, Minneapolis, Minnesota, and shall be of the size
and capacity as indicated in the fan schedules.
C DIA.
B DIA. B.C.
A DIA. I.D.
D
PERFORMANCE — Performance ratings shall conform to AMCA Standard 205 (fan efficiency grade), 211 (air
performance) and 311 (sound performance). Fans shall be tested in accordance with ANSI/AMCA Standard 210
(air performance) and 300 (sound performance) in an AMCA accredited laboratory. Fans shall be licensed to
bear the AMCA certified ratings seal for both sound and air, and fan efficiency grade (FEG).
E GA.
AIRFLOW
CONSTRUCTION — Fan casings shall be welded of ASTM A-569 low carbon, commercial quality 14-gauge hot
rolled steel in sizes through 14" diameter, 12-gauge hot rolled steel in sizes through 20" diameter, 10-gauge
hot rolled steel from 24" diameter through 28" diameter, and 7-gauge hot rolled steel on sizes above 30" in
diameter. Inlet and outlet flanges shall be integrally rolled mechanically from fan casing sheet steel to insure
concentricity and alignment. Accuracy and uniformity of the fan casing shall be insured through the use of
welding jigs and fixtures. A fabricated steel motor support base of minimum 3∕16" thick plate steel shall be
welded into the inlet end of the fan casing.
PROPELLERS — Fan blades shall be permanent mold A319 aluminum precision alloy castings. Fan center hub
boss shall be cast iron bolted to stamped steel hub halves coated by electrodeposition. Blade tip clearance
shall be within tolerance to meet certified performance. Fan blade pitch angle shall be individually manually
adjustable when fan is stopped. The fan propeller shall be secured directly to the motor shaft with knurled cup
point set screws in all sizes to 20" diameter and split taper lock bushings in all larger sizes. The motor and
propeller assembly shall be enclosed entirely within the fan casing.
(H) 7/16 DIA. HOLES (EA. END)
FAN
SIZE
035
040
050
063
071
080
090
100
112
125
A
1325⁄32
153⁄4
1911⁄16
2413⁄16
2731⁄32
311⁄2
357⁄16
393⁄8
443⁄32
497⁄32
B
155⁄16
173⁄8
215⁄16
2611⁄16
297⁄8
333⁄8
375⁄16
411⁄4
4531⁄32
513⁄32
C
1625⁄32
183⁄4
2211⁄16
285⁄16
3115⁄32
341⁄2
387⁄16
423⁄8
473⁄32
527⁄32
TypicalSpecifications
DimensionalData
ATAD, Arrangement 4 - Direct Drive
E
D
H
(GA.)
18
14 8
18
12 8
20
12 8
24
10 8
28
10
12
28 7
12
36 7
12
36 7
12
38 7
16
40 7
16
Dimensions are not to be used for construction.
*LESS MOTOR
MAX.
WEIGHT
MOTOR
(LBS.)*
FRAME
145T/U 25
145T/U 37
184T/U 51
215T/U
104
254T/U
127
254T/U
191
326T/U
275
326T/U
353
326T/U
394
365T/U
465
AC16551
BALANCING — The fan propeller assembly shall be statically and dynamically balanced in accordance with ANSI/
AMCA 204-96 “Balance Quality and Vibration Levels for Fans” to Fan Application Category BV-3, Balance Quality
Grade G6.3. In addition, direct drive fan propellers shall be balanced on the motor shaft after final assembly in
the fan casing, in the manufacturing facility to the following peak velocity values, filter-in, at the fan test speed:
Fan Application Category
BV-3
Rigidly Mounted (In/Sec)
0.15
Flexibly Mounted (In/Sec)
0.20
Final test room vibration levels in the axial, vertical, and horizontal planes shall be recorded and a written copy
shall be available upon request.
MOTORS — Fan motors shall be manufactured in accordance with current applicable standards of IEEE and
NEMA. They shall be foot-mounted, NEMA standard, open drip-proof (ODP), continuous duty, ball bearing with
class “B” insulation. External grease fittings with extended grease leads shall be supplied for lubrication of the
motor bearings on all motors that provide grease fittings. Motor bearings shall have a minimum L-10 life as
defined by AFBMA of at least 40,000 hours (200,000 hours average life).
FINISH — The units, after fabrication, shall be cleaned and chemically pretreated by a phosphatizing process
and shall be painted inside and out with two coats of air dry enamel. The fan shall be coated with the following
optional finishes:
qCarbocoat 30 (Replaces Sanitile 550)
qPlasite 4310 – Vinyl Ester
qPlasite 7122L – Air Dry Epoxy Phenolic
qHeresite VR506 – Air Dry Phenolic
qHot Dip Galvanizing
qPlasite 9500 (Replaces Plasite 1246)
qPlasite 3070 (Replaces Plasite 3066)
qDupont ASA – 70 Gray – Polyester (Replaces Farboil)
GUARANTEE — The manufacturer shall guarantee the workmanship and materials for its AXIPAL®, Model ATAD
fans for at least one (1) year from startup or eighteen (18) months from shipment, whichever occurs first.
20
Twin City Fan Catalog AX210
www.tcf.com
21
ATAB, Arrangement 9 - Belt Driven
Fans, where indicated on drawings and schedules, shall be AXIPAL®, Model ATAB, Arrangement 9, V-belt
driven, axial flow type with fan blades capable of individual manual pitch adjustment while the fan is stopped.
Fans shall be as manufactured by Twin City Fan & Blower, Minneapolis, Minnesota, and shall be of the size
and capacity as indicated in the fan schedules.
PERFORMANCE — Performance ratings shall conform to AMCA Standard 205 (fan efficiency grade), 211 (air
performance) and 311 (sound performance). Fans shall be tested in accordance with ANSI/AMCA Standard 210
(air performance) and 300 (sound performance) in an AMCA accredited laboratory. Fans shall be licensed to
bear the AMCA certified ratings seal for both sound and air, and fan efficiency grade (FEG).
7/16 DIA. "G" HOLES
MIN.
MAX.
CONSTRUCTION — Fan casings shall be welded of ASTM A-569 low carbon, commercial quality 12-gauge hot
rolled steel in sizes through 20" diameter, 10-gauge hot rolled steel from 24" diameter through 28" diameter,
and 7-gauge hot rolled steel on sizes greater than 30" in diameter. Inlet and outlet flanges shall be integrally
rolled mechanically from fan casing sheet steel to insure concentricity and alignment. Accuracy and uniformity
of the fan casing shall be insured through the use of welding jigs and fixtures. The motor base plate shall be
fabricated of minimum 3/16" steel plate and welded to the exterior of the fan casing. The adjustment of belt
tension shall be accomplished with an adjustable slide rail base.
TypicalSpecifications
DimensionalData
ATAB, Arrangement 9 - Belt Driven
PROPELLERS — Fan blades shall be permanent mold A319 aluminum alloy precision castings. Fan center hub
boss shall be cast iron bolted to stamped steel hub halves coated by electrodeposition. Blade tip clearance
shall be within tolerance to meet certified performance. Fan blade pitch angle shall be individually manually
adjustable when fan is stopped. The fan propeller shall be secured to the fan shaft with knurled cup point set
screws in all sizes to 20" diameter and split taper lock bushings in all larger sizes.
AIRFLOW
E GA.
SHAFT & BEARINGS — All fans shall be supplied with a shaft of AISI 1045 steel material that has been
properly turned, ground, and polished for accuracy. The shaft shall be supported by a matched pair of sealed
pillow block bearings. Grease leads are to be extended from the fan shaft bearings to zerk fittings mounted on
the exterior of the fan casing to facilitate bearing relubrication without the need to gain service access inside
the ductwork or the fan casing. All fan bearings are to have an L-10 minimum life as defined by AFBMA of
at least 20,000 hours. This L-10 minimum life converts to an average bearing life in excess of 100,000 hours.
A DIA. I.D.
B DIA. B.C.
C DIA. O.D.
D
FAN
E
A
B
C
D
G
SIZE
(GA.)
173⁄8
183⁄4
26
12 8
040
153⁄4
215⁄16
2211⁄16
26
12 8
050
1911⁄16
2611⁄16
285⁄16
31
10 8
063
2413⁄16
297⁄8
3115⁄32
36
10
12
071
2731⁄32
333⁄8
341⁄2
36 7
12
080
311⁄2
375⁄16
387⁄16
44 7
12
090
357⁄16
411⁄4
423⁄8
44 7
12
100
393⁄8
4531⁄32
477⁄32
50 7
16
112
443⁄32
513⁄32
527⁄32
52 7
16
125
497⁄32
Dimensions are not to be used for construction.
*LESS MOTOR
MAX.
WEIGHT
MOTOR
(LBS.)*
FRAME
184T/U 69
215T/U 82
215T/U
134
256T/U
165
256T/U
277
326T/U
373
326T/U
418
326T/U
516
365T/U
638
AC16552-A
DRIVES — Fan drives shall include cast iron sheaves and non-static conducting belts. Fans equipped with
motors up to and including five horsepower will be furnished with a variable pitch type drive sheave to allow
for minor speed adjustment of the fan propeller during system balance. Fans equipped with larger motors will
be furnished with a fixed drive sheave. A belt guard or an optional motor cover is to be provided with all belt
driven fans to afford personnel safety and general traffic protection.
MOTORS — Fan motors shall be manufactured in accordance with current applicable standards of IEEE and
NEMA. They shall be foot-mounted, NEMA standard, open drip-proof (ODP), continuous duty, ball bearing with
class “B” insulation.
BALANCING — The propeller assembly shall be statically and dynamically balanced in accordance with ANSI/
AMCA 204-96 “Balance Quality and Vibration Levels for Fans” to Fan Application Category BV-3, Balance Quality
Grade G6.3. In addition, belt driven fan propellers shall be balanced on the fan shaft after final assembly in
the fan casing, in the manufacturing facility to the following peak velocity values, filter-in, at the fan test speed:
Fan Application Category
BV-3
Rigidly Mounted (In/Sec)
0.15
Flexibly Mounted (In/Sec)
0.20
Final test room vibration levels in the axial, vertical, and horizontal planes shall be recorded and a written copy
shall be available upon request.
FINISH — The units, after fabrication, shall be cleaned and chemically pretreated by a phosphatizing process
and shall be painted inside and out with two coats of air dry enamel. The fan shall be coated with the following
optional finishes:
q Carbocoat 30 (Replaces Sanitile 550)
q Hot Dip Galvanizing
q Plasite 4310 – Vinyl Ester
q Plasite 9500 (Replaces Plasite 1246)
q Plasite 7122L – Air Dry Epoxy Phenolic q Plasite 3070 (Replaces Plasite 3066)
q Heresite VR506 – Air Dry Phenolic
q Dupont ASA – 70 Gray – Polyester (Replaces Farboil)
Guarantee — The manufacturer shall guarantee the workmanship and materials for its AXIPAL®, Model ATAB
fans for at least one (1) year from startup or eighteen (18) months from shipment, whichever occurs first.
22
Twin City Fan Catalog AX210
www.tcf.com
23
ATAB, Arrangement 9 - Belt Driven
Fans, where indicated on drawings and schedules, shall be AXIPAL®, Model ATAB, Arrangement 9, V-belt
driven, axial flow type with fan blades capable of individual manual pitch adjustment while the fan is stopped.
Fans shall be as manufactured by Twin City Fan & Blower, Minneapolis, Minnesota, and shall be of the size
and capacity as indicated in the fan schedules.
PERFORMANCE — Performance ratings shall conform to AMCA Standard 205 (fan efficiency grade), 211 (air
performance) and 311 (sound performance). Fans shall be tested in accordance with ANSI/AMCA Standard 210
(air performance) and 300 (sound performance) in an AMCA accredited laboratory. Fans shall be licensed to
bear the AMCA certified ratings seal for both sound and air, and fan efficiency grade (FEG).
7/16 DIA. "G" HOLES
MIN.
MAX.
CONSTRUCTION — Fan casings shall be welded of ASTM A-569 low carbon, commercial quality 12-gauge hot
rolled steel in sizes through 20" diameter, 10-gauge hot rolled steel from 24" diameter through 28" diameter,
and 7-gauge hot rolled steel on sizes greater than 30" in diameter. Inlet and outlet flanges shall be integrally
rolled mechanically from fan casing sheet steel to insure concentricity and alignment. Accuracy and uniformity
of the fan casing shall be insured through the use of welding jigs and fixtures. The motor base plate shall be
fabricated of minimum 3/16" steel plate and welded to the exterior of the fan casing. The adjustment of belt
tension shall be accomplished with an adjustable slide rail base.
TypicalSpecifications
DimensionalData
ATAB, Arrangement 9 - Belt Driven
PROPELLERS — Fan blades shall be permanent mold A319 aluminum alloy precision castings. Fan center hub
boss shall be cast iron bolted to stamped steel hub halves coated by electrodeposition. Blade tip clearance
shall be within tolerance to meet certified performance. Fan blade pitch angle shall be individually manually
adjustable when fan is stopped. The fan propeller shall be secured to the fan shaft with knurled cup point set
screws in all sizes to 20" diameter and split taper lock bushings in all larger sizes.
AIRFLOW
E GA.
SHAFT & BEARINGS — All fans shall be supplied with a shaft of AISI 1045 steel material that has been
properly turned, ground, and polished for accuracy. The shaft shall be supported by a matched pair of sealed
pillow block bearings. Grease leads are to be extended from the fan shaft bearings to zerk fittings mounted on
the exterior of the fan casing to facilitate bearing relubrication without the need to gain service access inside
the ductwork or the fan casing. All fan bearings are to have an L-10 minimum life as defined by AFBMA of
at least 20,000 hours. This L-10 minimum life converts to an average bearing life in excess of 100,000 hours.
A DIA. I.D.
B DIA. B.C.
C DIA. O.D.
D
FAN
E
A
B
C
D
G
SIZE
(GA.)
173⁄8
183⁄4
26
12 8
040
153⁄4
215⁄16
2211⁄16
26
12 8
050
1911⁄16
2611⁄16
285⁄16
31
10 8
063
2413⁄16
297⁄8
3115⁄32
36
10
12
071
2731⁄32
333⁄8
341⁄2
36 7
12
080
311⁄2
375⁄16
387⁄16
44 7
12
090
357⁄16
411⁄4
423⁄8
44 7
12
100
393⁄8
4531⁄32
477⁄32
50 7
16
112
443⁄32
513⁄32
527⁄32
52 7
16
125
497⁄32
Dimensions are not to be used for construction.
*LESS MOTOR
MAX.
WEIGHT
MOTOR
(LBS.)*
FRAME
184T/U 69
215T/U 82
215T/U
134
256T/U
165
256T/U
277
326T/U
373
326T/U
418
326T/U
516
365T/U
638
AC16552-A
DRIVES — Fan drives shall include cast iron sheaves and non-static conducting belts. Fans equipped with
motors up to and including five horsepower will be furnished with a variable pitch type drive sheave to allow
for minor speed adjustment of the fan propeller during system balance. Fans equipped with larger motors will
be furnished with a fixed drive sheave. A belt guard or an optional motor cover is to be provided with all belt
driven fans to afford personnel safety and general traffic protection.
MOTORS — Fan motors shall be manufactured in accordance with current applicable standards of IEEE and
NEMA. They shall be foot-mounted, NEMA standard, open drip-proof (ODP), continuous duty, ball bearing with
class “B” insulation.
BALANCING — The propeller assembly shall be statically and dynamically balanced in accordance with ANSI/
AMCA 204-96 “Balance Quality and Vibration Levels for Fans” to Fan Application Category BV-3, Balance Quality
Grade G6.3. In addition, belt driven fan propellers shall be balanced on the fan shaft after final assembly in
the fan casing, in the manufacturing facility to the following peak velocity values, filter-in, at the fan test speed:
Fan Application Category
BV-3
Rigidly Mounted (In/Sec)
0.15
Flexibly Mounted (In/Sec)
0.20
Final test room vibration levels in the axial, vertical, and horizontal planes shall be recorded and a written copy
shall be available upon request.
FINISH — The units, after fabrication, shall be cleaned and chemically pretreated by a phosphatizing process
and shall be painted inside and out with two coats of air dry enamel. The fan shall be coated with the following
optional finishes:
q Carbocoat 30 (Replaces Sanitile 550)
q Hot Dip Galvanizing
q Plasite 4310 – Vinyl Ester
q Plasite 9500 (Replaces Plasite 1246)
q Plasite 7122L – Air Dry Epoxy Phenolic q Plasite 3070 (Replaces Plasite 3066)
q Heresite VR506 – Air Dry Phenolic
q Dupont ASA – 70 Gray – Polyester (Replaces Farboil)
Guarantee — The manufacturer shall guarantee the workmanship and materials for its AXIPAL®, Model ATAB
fans for at least one (1) year from startup or eighteen (18) months from shipment, whichever occurs first.
22
Twin City Fan Catalog AX210
www.tcf.com
23
Industrial & Commercial Fans
Centrifugal Fans | Utility Sets | Plenum & Plug Fans | Inline Centrifugal Fans
Mixed Flow Fans | Tubeaxial & Vaneaxial Fans | Propeller Wall Fans | Propeller Roof Ventilators
Centrifugal Roof & Wall Exhausters | Ceiling Ventilators | Gravity Ventilators | Duct Blowers
Radial Bladed Fans | Radial Tip Fans | High Efficiency Industrial Fans | Pressure Blowers
Laboratory Exhaust Fans | Filtered Supply Fans | Mancoolers | Fiberglass Fans | Custom Fans
Twin city fan & blower | www.tcf.com
TwinCity
City FanFan
Companies,
Ltd.
A Twin
Company
1MWG12/10
5959 Trenton Lane N | Minneapolis, MN 55442 | Phone: 763-551-7600 | Fax: 763-551-7601
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement