Quick Start Guide
Web-Enabled Analog Output Module
Basic Setup Steps:
1. Connect unit to power and network.
2. Set up a computer on the same network as the input module. To do this, set the IP address of the computer to 192.168.1.50 with a netmask of
255.255.255.0.
3. Configure the X-317 module using a web browser - In a web browser’s address bar, type http://192.168.1.2/setup.html. Type the default username is admin and password is webrelay (all lower case).
4. Set the permanent IP address in the Network tab and press Sumbit. Restart the X-317 (remove power, then re-apply power).
5. After restarting the unit, set the computer back to its original settings and access the Analog module at its new IP address.
Factory Default Settings
IP Address: 192.168.1.2
Subnet Mask: 255.255.255.0
Control Web Address: http://192.168.1.2
Setup Web Address: http://192.168.1.2/setup.html
Setup Username: admin
Setup Password: webrelay (all lower case)
Control Password: no password set
Pinout
Vin+ : Power Supply Input ( + )
Vin- : Power Supply Input ( - )
Com 1-5 : Analog Common (Isolated from Vin-)
Out 1-5 : 0-5V, ± 5V, 0-10V, ± 10V, 4-20mA Output
Logic
Power
Supply
+
DC/DC
Converter
-
Digital To
Analog
Digital To
Analog
Digital To
Analog
Digital To
Analog
Digital To
Analog
Vin+
Vin-
Com
Out5
Com
Out4
Com
Out3
Com
Out2
Com
Out1
Note: The X-317 Module can be configured to operate at 10Mbps or 100Mbps. For best power savings and long term performance the 10Mbps setting is recommended.
Full Users Manual may be downloaded from http://www.ControlByWeb.com
For technical support, email questions to [email protected]