TEC 704 ( 3 / 16 DIN) PDF

TEC 704 ( 3 / 16 DIN) PDF
Temperature Controllers
Model TEC-704 3/16 DIN
Model TEC-704 3/16 DIN Temperature Controller
✴ 3/16 DIN size – 72 mm × 72 mm
✴ Laser trimmed ASIC components
✴ Short panel depth – only 2-9/16" (65 mm) required
✴ On-off or time proportional selection
✴ Digital display, 0.4" (10 mm) red LEDs
✴ Wide selection of output options
✴ High precision wire wound dial/potentiometer setpoint
✴ Sensor break protection
✴ Good performance at a very low price
✴ Agency Approval:
Design Features
Simple Setpoint and Display!
2
1
3
4
5
Hardware Code: TEC-704-
6
7
0
8
0
A Part Number based on the hardware code and any software
pre-programming will be issued at time of order.
Standard lead time is stock to 2 weeks.
box 1
4 = 90-264 VAC 50/60 Hz
Power Input
=
=
=
=
=
box 2
Thermocouple: Type J
Thermocouple: Type K
RTD: 100 ohm PT, DIN 0.00385
RTD: 100 ohm PT, JIS 0.00392
Other
Signal Input
1
2
3
4
9
4 = 0 to 300°C
6 = 0 to 600°C
box 3
C = 50 to 550°F
E = 50 to 850°F
F = 50 to 1100°F
Standard Range Code
Below available for large volume orders.
Consult Tempco for more information.
2 = 0 to 100°C
A = 50 to 200°F
3 = 0 to 200°C
B = 50 to 400°F
5 = 0 to 400°C
D = 50 to 750°F
7 = 0 to 800°C
G = 50 to 1400°F
8 = 0 to 1200°C H = 0 to 2200°F
9 = Other
1 = On - Off
2 = Proportional
Control Mode
13-32
Rev 2 (10-5-15)
box
=
=
=
=
=
=
box 5
Relay: 5A / 240 VAC
Pulse DC for SSR drive: 20 VDC (20 mA max)
4-20 mA, linear (max load 500 ohms)
0-20 mA, linear (max load 500 ohms)
0-10 VDC, linear (min. impedance 500K ohms)
Other
Output 1
1
2
3
4
5
9
box 6
0 = Not Available
Output 2
box 7
0 = None
1 = Relay: 2A / 240 VAC Deviation alarm
Alarm
0 = Not Available
Communication
box
8
4
View Product Inventory @ www.tempco.com
Temperature Controllers
Model TEC-704 Specifications (3/16 DIN)
Standard: 90 - 264 VAC, 50/60 Hz, 5VA
Power Input
Accuracy: ±1.0% of full scale at 77°F/25°C
Thermocouple: Type J or K
RTD: 3-wire Pt100 DIN or JIS
Sampling Rate: 3 samples per second
Cold Junction Compensation: ±0.1°C / 1°C
Common Mode Rejection Ratio (CMRR): 120 dB
Normal Mode Rejection Ratio (NMRR): 60 dB
Sensor Break Protection: Upscale
Signal Input
Relay Rating: 240 VAC, 5 Amp
SSR drive: Pulsed DC, 20 V at 20 mA maximum
Current: 4 - 20 mA, 0 - 20 mA, maximum load: 500Ω
Voltage: 0 - 10 VDC, minimum load: 500KΩ
Output
Proportional Band: 2.2% of span
ON-OFF Hysteresis: 1% of span
Cycle Time: 20 seconds for relay output, 1 second for pulsed voltage output, 0.02 second for linear current or voltage
output
Control Action: Reverse Action
Control
Setpoint: Single turn wirewound potentiometer
Manual Reset: Adjustable up to 2.6% of span
Setpoint Resolution: 0.2% of span
Accuracy of Setpoint: ±2% of span
Repeatability of Setpoint: ± 0.1% of span
Adjustment
Type: Deviation ± 10% of span Relay: 2A / 240 VAC
Alarm
Process Indicator: 3-1/2 digit, 0.4" / 10 mm red LED display
Output Status Indicator: Red LED lamp
Alarm Status Indicator: Red LED lamp
Display
Operating Temperature: 32 to 122°F (0 to 50°C)
Humidity: 0 to 90% RH, non-condensing
Dielectric Strength: 2000 VAC, 50/60 Hz for 1 minute
Vibration: 10 - 55 Hz, amplitude 1mm
Shock: 200 m/s2 (20g)
Dimensions: 2-27/32 × 2-27/32 × 3" (72 × 72 × 78 mm) H×W×D
Depth behind panel: 2-9/16" (65 mm)
Panel Cutout: 2-11/16" × 2-11/16" (68 × 68 mm) H×W
Weight: 0.53 lb. (240 grams)
Environmental and Physical
Safety Standards: EN61326
Protective Class: Front panel: IP 30
Housing and Terminals: IP 20
Approval Standards
Rear Terminal Connections
Stock and Common Part Numbers
(Power Input: 90-264 VAC, Proportional mode)
Part
Number
TEC43401
TEC43402
TEC43403
TEC43404
TEC43405
TEC43406
TEC43407
TEC43408
TEC43409
TEC43410
TEC43411
TEC43412
TEC43413
TEC43414
TEC43415
(800) 323-6859 • Email: [email protected]
Signal
Input
J tc
J tc
K tc
K tc
J tc
K tc
RTD
RTD
J tc
J tc
J tc
K tc
K tc
RTD
RTD
50-850°F
50-550°F
50-850°F
50-550°F
50-850°F
50-850°F
50-550°F
50-550°F
0-300°C
0-600°C
0-300°C
0-300°C
0-600°C
0-300°C
0-600°C
Range
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
relay
Output
none
none
none
none
relay
relay
none
relay
none
none
relay
none
relay
none
relay
Alarm
13-33
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement