CWC 2P-4P_AGU_MSL102E-0105 03
APPLICATION
GUIDE
CHILLED
WATER CASSETTE
CWC - 2P/4P
English/03-2005
INDEX
Index AGU CWC-2P/4P
General Description
2
Specifications
3
4-8
Performances tables
8
Sound levels
9-10
Options
Dimensions
11-12
Unit installation
13-14
Electrical connections
15-16
Drain pipework
16
Installation of diffuser and inlet grille
17
18-20
Maintenance
Air distribution
20
Fault analysis
20
Our company is a member of the Eurovent Certification Programme.
Our products comply with European standards.
Lennox have been providing environmental solutions since 1895, our range of Chilled Water Cassette CWC-2P/4P continues
to meet the standards that have made LENNOX a household name. Flexible design solutions to meet YOUR needs and
uncompromising attention to detail. Engineered to last, simple to maintain and Quality that comes as standard.
Information on local contacts at www.lennoxeurope.com.
All the technical and technological information contained in this manual, including any drawing and technical descriptions
provided by us, remain the property of Lennox and must not be utilised (except in the operation of this product), reproduced,
issued to or made available to third parties without the prior written agreement of Lennox.
1
GENERAL DESCRIPTION
CWC
020 (030-040-050-070-090)
Model
Chilled Water Cassette
Models 600x600: 020-030-040-050
Models 600x1200: 070-090
Close cooling capacity in W x 100
X
Y
1: 2 Pipes units
4: 4 Pipes units
1: Plastic diffuser
2: Metallic diffuser
The CEILING CASSETTES are designed to operate with chilled and hot water. They provide both cooling and
dehumidification in cooling mode and heating in the latter, cleaning and filtering the air in the process. Electrical
heating elements are available as an option on some units. The units are available with cooling capacities from
1950 to 8450 W and heating capacities from 1400 to 10600 W.
CABINET
The unit chassis is made of galvanised steel and is fully insulated inside.
The units have been designed in order to install them in high ceilings where standard plates 600x600 mm or
600x1200 mm will be used.
DIFFUSER PANEL
Two alternatives can be chosen:
- Plastic diffuser: Made in decorative plastic, with a smooth finish. Internal insulation prevents condensation from
forming. 4 louvres for MODELS 600x600 and 6 louvres for MODELS 600x1200 ensure air distribution.
- Metallic diffuser.
HEAT EXCHANGER
Made of copper tubes and aluminium fins. Coils have been designed and manufactured to ensure maximum
efficiency.
FAN
The units are supplied with one (models 600x600) or two (models 600x1200) 3-speed centrifugal fans. The impeller
blades have been designed specifically for this type of units ensuring exceptionally low sound levels and the motor
is protected with internal thermal protection.
AIR DISTRIBUTION
The position of the louvres can be adjusted manually (only for plastic diffuser).
AIR FILTER
A polypropylene washable air filter is incorporated in the unit; it is easily accessible for maintenance.
INTERNAL COMPONENTS
The unit is designed with serviceability in mind, and all components are easily accessible. A drip tray collects
condensate which is removed by means of a condensate pump.
ELECTRIC CIRCUIT
The electrical panel is provided with a terminal block which provides connection to mains power or to a control box
(depending on model).
A fused isolator is not included and where required shall be installed by others.
OPTIONS
• Electric heater (depending on model).
• Fresh air kit.
- Duct connection.
- Fresh air fan.
- Duct supports.
• Air supply to an adjacent room kit.
- Duct connection.
- Duct supports.
• Water control valve kit with 2 way or 3 way
proportional control valves.
• Auxiliary drip tray.
• Thermostat.
• Float switch.
• Master Slave.
• Fitting & testing valves.
• Water evacuation security.
2
SPECIFICATIONS
CWC - 2P / 4P
CWC 020 CWC 030 CWC 040 CWC 050 CWC 070 CWC 090
m3/h
L
M
H
445
550
650
400
517
598
553
670
779
650
791
920
987
1164
1342
1126
1323
1569
Total cooling capacity (2)
(2 pipes system)
W
L
M
H
1480
1690
1870
2580
3090
3410
3240
3690
4080
4190
4820
5330
6290
7040
7740
6940
7770
8710
Total cooling capacity (2)
(4 pipes system)
W
L
M
H
1620
1840
2030
2150
2540
2790
2980
3370
3690
3700
4210
4620
5320
5920
6470
6350
7070
7880
Sensible cooling capacity (2)
(2 pipes system)
W
L
M
H
1150
1320
1480
2000
2440
2730
2470
2850
3190
3020
3530
3960
4370
4950
5510
5040
5710
6490
Sensible cooling capacity (2)
(4 pipes system)
W
L
M
H
1380
1590
1770
1580
1900
2110
2250
2590
2880
2840
3280
3650
4000
4520
5010
4910
5540
6260
Heating capacity (3)
(4 pipes system)
W
L
M
H
1290
1420
1510
1830
2240
2530
2900
3220
3500
3530
4010
4410
5670
6240
6750
6170
6910
7670
Heating capacity (4)
(2 pipes system)
W
L
M
H
2010
2330
2600
2980
3620
4050
3610
4160
4650
5290
6170
6940
6650
7430
8260
8700
9860
1123
Pressure drop (water) (2)
cooling circuit
(2 pipes system)
kPa
L
M
H
9.3
11.8
14.2
13.3
18.4
22.0
25.2
31.8
38.0
24.2
31.0
37.2
18.1
22.1
26.2
13.6
16.7
20.6
Pressure drop (water) (2)
cooling circuit
(4 pipes system)
kPa
L
M
H
8.9
11.3
14.1
24.8
33.7
39.8
18.3
22.8
27.0
24.5
30.8
36.5
12.9
15.7
18.4
21.0
25.4
31.0
Pressure drop (water) (3)
heating circuit
(4 pipes system)
kPa
L
M
H
1.9
2.3
2.5
5.3
7.6
9.4
24.9
30.2
34.9
25.4
32.0
38.0
19.8
23.4
27.0
17.3
21.1
25.5
Pressure drop (water) (4)
heating circuit
(2 pipes system)
kPa
L
M
H
11.2
14.2
17.0
13.2
18.2
21.8
26.3
33.3
39.7
28.9
37.0
44.4
20.4
25.0
29.7
16.4
20.1
24.8
Power electrical heater (5)
kW
1.5
2
2
N/A
2.5-4
2.5-4
48
0.17
0.20
0.22
48
0.17
0.20
0.22
66
0.26
0.28
0.30
82
0.29
0.30
0.34
2x66
2x0.26
2x0.28
2x0.30
2x82
2x0.29
2x0.30
2x0.34
Nominal air flow (1)
(6) W
Fan-motor performance
A
L
M
H
Weight unit
Kg
21
22
23
24
43
45
Weight Plastic diffuser
Kg
3
3
3
3
5
5
Weight Metallic diffuser
Kg
5
5
5
5
11
11
(1) Values for 0 Pa air available pressure.
(2) Inlet Air temperature 27ºC DB-19ºC WB. Water temperature 7ºC-12ºC.
(3) Inlet Air temperature 20ºC. Water temperature 70ºC-60ºC.
(4) Inlet Air temperature 20ºC. Water temperature 50ºC/* - Same water flow (2).
(5) Capacity 1-Capacity 2.
(6) Absorbed power (high speed).
3
DB.- Dry bulb
WB.- Wet bulb
N/A: Not available
PERFORMANCES TABLES
COOLING CAPACITIES
CWC 020 2P
Speed
Water
temp. Air flow
ºC
Inlet Air Temperature
in/out
Relative humidity
6 / 11
3 Rows Coil
7 / 12
8 / 13
9 / 14
m3/h
ºC
Low Speed
445
22
%
CWC 020 4P
Medium Speed
550
25
27
50 +/-10%
22
High Speed
650
25
27
50 +/-10%
22
25
27
50 +/-10%
Low Speed
445
Medium Speed
550
22
25
27
50 +/-10%
22
25
27
50 +/-10%
High Speed
650
22
25
27
50 +/-10%
Total capacity
kW
0,87
1,30
1,66
1,00
1,47
1,89
1,12
1,63
2,09
0,95
1,41
1,81
1,09
1,61
2,06
1,22
1,78
2,28
Sensible capacity
kW
0,87
1,08
1,22
1,00
1,24
1,40
1,12
1,38
1,57
1,05
1,29
1,47
1,20
1,49
1,68
1,34
1,66
1,88
Outlet Air Temperature
ºC
16,07 17,66 18,68
16,48 18,16 19,26
16,79 18,55 19,70
14,88 16,19 17,02
15,38 16,79 17,72
15,75 17,26 18,24
Water flow
l/h
156
229
291
180
261
332
200
288
368
169
249
317
195
284
361
218
314
400
Water press. drop
kPa
3,7
7,4
11,4
4,8
9,4
14,5
5,8
11,2
17,4
3,5
7,1
10,9
4,6
9,0
13,9
5,8
11,2
17,3
Total capacity
kW
0,80
1,12
1,48
0,91
1,27
1,69
1,02
1,41
1,87
0,87
1,22
1,62
1,00
1,39
1,84
1,11
1,53
2,03
Sensible capacity
kW
0,80
1,01
1,15
0,91
1,16
1,32
1,02
1,29
1,48
0,95
1,21
1,38
1,10
1,39
1,59
1,22
1,55
1,77
Outlet Air Temperature
ºC
16,58 18,14 19,17
16,96 18,62 19,71
17,25 18,97 20,12
15,50 16,77 17,60
15,96 17,34 18,26
16,30 17,76 18,74
Water flow
l/h
143
199
261
164
226
298
184
250
329
155
216
284
179
246
324
199
272
358
Water press. drop
kPa
3,1
5,7
9,3
4,1
7,2
11,8
4,9
8,6
14,2
3,0
5,5
8,9
3,9
6,9
11,3
4,9
8,6
14,1
Total capacity
kW
0,72
0,94
1,30
0,83
1,09
1,48
0,92
1,22
1,64
0,78
1,03
1,42
0,90
1,19
1,62
1,00
1,33
1,78
Sensible capacity
kW
0,72
0,93
1,08
0,83
1,09
1,24
0,92
1,22
1,39
0,86
1,12
1,29
0,99
1,31
1,49
1,11
1,46
1,66
Outlet Air Temperature
ºC
17,10 18,64 19,66
17,45 18,98 20,16
17,71 19,31 20,54
16,12 17,36 18,19
16,54 17,78 18,79
16,85 18,18 19,25
Water flow
l/h
130
168
230
149
195
262
167
218
290
141
182
250
162
212
285
181
237
315
Water press. drop
kPa
2,6
4,2
7,4
3,4
5,5
9,3
4,1
6,7
11,2
2,5
4,0
7,1
3,2
5,3
8,9
4,1
6,7
11,1
Total capacity
kW
0,64
0,87
1,12
0,74
1,01
1,27
0,82
1,12
1,40
0,70
0,95
1,22
0,80
1,10
1,38
0,90
1,22
1,53
Sensible capacity
kW
0,64
0,87
1,01
0,74
1,01
1,16
0,82
1,12
1,29
0,77
1,05
1,21
0,89
1,21
1,39
0,99
1,35
1,55
Outlet Air Temperature
ºC
17,62 19,05 20,14
17,93 19,46 20,61
18,17 19,77 20,97
16,74 17,86 18,77
17,12 18,36 19,33
17,40 18,72 19,76
Water flow
l/h
117
156
198
134
180
225
150
201
249
126
170
215
146
196
245
162
219
271
Water press. drop
kPa
2,2
3,6
5,6
2,8
4,7
7,1
3,4
5,8
8,5
2,1
3,5
5,4
2,7
4,5
6,8
3,4
5,7
8,4
Eurovent conditions
CWC 030 2P
Speed
Water
temp. Air flow
ºC
Inlet Air Temperature
in/out
Relative humidity
6 / 11
3 Rows Coil
7 / 12
8 / 13
9 / 14
m3/h
ºC
%
Low Speed
400
22
CWC 030 4P
Medium Speed
517
25
27
50 +/-10%
22
High Speed
598
25
27
50 +/-10%
22
25
27
50 +/-10%
Low Speed
400
Medium Speed
517
22
25
27
50 +/-10%
22
25
27
50 +/-10%
High Speed
598
22
25
27
50 +/-10%
Total capacity
kW
1,46
2,23
2,77
1,73
2,67
3,32
1,99
2,94
3,67
1,22
1,87
2,33
1,43
2,21
2,76
1,78
2,65
3,31
Sensible capacity
kW
1,47
1,82
2,05
1,80
2,22
2,50
2,11
2,48
2,79
1,28
1,59
1,79
1,55
1,91
2,15
1,63
1,95
2,19
Outlet Air Temperature
ºC
10,86 11,20 11,49
11,46 11,96 12,36
11,29 12,42 12,88
12,27 12,96 13,47
12,92 13,78 14,40
13,72 15,13 15,92
Water flow
l/h
256
390
482
304
466
579
351
513
639
215
328
407
253
388
483
315
463
577
Water press. drop
kPa
5,1
10,8
15,9
6,9
15,0
22,1
9,0
17,8
26,4
8,0
17,0
25,1
10,7
23,1
34,2
13,6
27,3
40,6
Total capacity
kW
1,43
2,04
2,58
1,73
2,43
3,09
1,93
2,68
3,41
1,18
1,69
2,15
1,40
1,99
2,54
1,55
2,18
2,79
Sensible capacity
kW
1,52
1,77
2,00
1,83
2,17
2,44
2,05
2,42
2,73
1,18
1,40
1,58
1,40
1,69
1,90
1,55
1,87
2,11
Outlet Air Temperature
ºC
10,48 11,56 11,83
11,25 12,29 12,67
11,63 12,71 13,15
13,07 14,41 15,03
13,79 15,12 15,84
14,14 15,52 16,30
Water flow
l/h
252
357
450
305
426
539
340
469
595
209
296
375
248
350
445
275
384
489
Water press. drop
kPa
4,5
8,7
13,3
6,4
11,9
18,4
7,7
14,1
22,0
8,4
16,0
24,8
11,5
21,7
33,7
13,8
25,5
39,8
Total capacity
kW
1,25
1,70
2,25
1,51
2,02
2,69
1,68
2,21
2,96
1,08
1,46
1,92
1,28
1,72
2,27
1,42
1,88
2,49
Sensible capacity
kW
1,33
1,58
1,81
1,60
1,94
2,21
1,78
2,16
2,47
1,08
1,30
1,49
1,28
1,57
1,79
1,42
1,75
1,99
Outlet Air Temperature
ºC
11,95 13,01 13,26
12,64 13,66 14,02
12,99 14,04 14,46
13,82 15,13 15,74
14,49 15,78 16,48
14,81 16,15 16,91
Water flow
l/h
221
298
393
266
354
469
297
389
517
192
256
337
228
302
398
252
331
437
Water press. drop
kPa
3,9
6,6
10,9
5,4
9,0
15,0
6,6
10,7
17,8
7,2
12,3
20,2
9,7
16,5
27,3
11,7
19,4
32,3
Total capacity
kW
1,14
1,42
1,98
1,36
1,79
2,35
1,52
1,99
2,58
0,98
1,22
1,69
1,16
1,52
1,99
1,29
1,68
2,18
Sensible capacity
kW
1,20
1,46
1,69
1,45
1,90
2,07
1,61
2,11
2,32
0,98
1,21
1,39
1,16
1,52
1,68
1,29
1,68
1,87
Outlet Air Temperature
ºC
12,88 13,94 14,16
13,52 13,89 14,85
13,85 14,29 15,27
14,57 15,86 16,44
15,18 16,10 17,14
15,48 16,47 17,54
Water flow
l/h
201
249
346
242
315
411
269
351
452
175
215
296
207
268
350
230
298
383
Water press. drop
kPa
3,2
4,8
8,6
4,5
7,2
11,7
5,5
8,8
13,9
6,0
8,8
15,9
8,1
13,1
21,4
9,7
15,8
25,2
Eurovent conditions
4
PERFORMANCES TABLES
COOLING CAPACITIES
CWC 040 2P
Speed
Water
temp. Air flow
ºC
Inlet Air Temperature
in/out
Relative humidity
6 / 11
3 Rows Coil
7 / 12
8 / 13
9 / 14
m3/h
ºC
Low Speed
553
22
%
25
27
50 +/-10%
CWC 040 4P
Medium Speed
670
22
High Speed
779
25
27
50 +/-10%
22
25
27
50 +/-10%
Low Speed
553
Medium Speed
670
22
25
27
50 +/-10%
22
25
27
50 +/-10%
High Speed
779
22
25
27
50 +/-10%
Total capacity
kW
1,88
2,87
3,57
2,13
3,27
4,07
2,34
3,61
4,50
1,75
2,59
3,24
2,02
2,93
3,67
2,24
3,21
4,03
Sensible capacity
kW
1,89
2,33
2,62
2,18
2,69
3,03
2,44
3,01
3,38
1,75
2,07
2,33
2,02
2,39
2,68
2,24
2,66
2,98
Outlet Air Temperature
ºC
11,66 12,23 12,65 12,13 12,82 13,32
12,52 13,30 13,87
12,39
13,65 14,25
12,88 14,21 14,89 13,29 14,66 15,41
Water flow
l/h
333
503
623
377
573
711
414
632
785
311
454
566
357
513
641
397
563
704
Water press. drop
kPa
9,7
20,5
30,1
12,2
25,9
38,1
14,4
30,9
45,6
7,5
14,9
22,1
9,6
18,5
27,6
11,6
21,8
32,6
Total capacity
kW
1,74
2,54
3,24
2,00
2,89
3,69
2,23
3,18
4,08
1,67
2,33
2,98
1,91
2,62
3,37
2,12
2,87
3,69
Sensible capacity
kW
1,82
2,18
2,47
2,10
2,52
2,85
2,34
2,82
3,19
1,67
1,99
2,25
1,91
2,30
2,59
2,12
2,56
2,88
Outlet Air Temperature
ºC
12,03 13,04 13,46 12,51 13,59 14,09
12,91 14,04 14,61
12,86
14,07 14,67
13,35 14,62 15,30 13,73 15,04 15,79
Water flow
l/h
308
446
567
354
507
645
395
558
712
296
410
522
339
462
589
377
506
647
Water press. drop
kPa
8,4
16,4
25,2
10,8
20,6
31,8
13,2
24,5
38,0
6,4
11,7
18,3
8,2
14,6
22,8
10,0
17,2
27,0
Total capacity
kW
1,59
2,19
2,90
1,83
2,49
3,30
2,04
2,73
3,64
1,53
2,00
2,66
1,75
2,25
3,00
1,94
2,46
3,28
Sensible capacity
kW
1,66
2,03
2,32
1,92
2,35
2,68
2,14
2,62
3,00
1,53
1,86
2,12
1,75
2,14
2,44
1,94
2,39
2,72
Outlet Air Temperature
ºC
12,88 13,88 14,27 13,33 14,38 14,86
13,69 14,79 15,34
13,63
14,81 15,39
14,09 15,30 15,96 14,44 15,70 16,42
Water flow
l/h
282
386
508
325
438
578
362
482
637
272
354
467
311
397
526
345
434
576
Water press. drop
kPa
7,1
12,6
20,6
9,2
15,8
25,9
11,2
18,7
30,9
5,5
8,9
14,8
7,0
11,0
18,4
8,4
12,9
21,7
Total capacity
kW
1,44
1,83
2,55
1,66
2,17
2,89
1,84
2,42
3,18
1,39
1,81
2,32
1,59
2,08
2,62
1,76
2,31
2,86
Sensible capacity
kW
1,51
1,87
2,17
1,74
2,28
2,51
1,93
2,54
2,81
1,39
1,81
1,99
1,59
2,08
2,29
1,76
2,31
2,55
Outlet Air Temperature
ºC
13,74 14,73 15,09 14,15 14,70 15,63
14,49 15,12 16,07
14,41
15,09 16,11
14,83 15,61 16,64 15,16 16,02 17,06
Water flow
l/h
257
324
447
295
384
507
328
428
558
248
320
409
283
367
460
314
409
503
Water press. drop
kPa
6,0
9,1
16,3
7,7
12,4
20,4
9,3
15,0
24,2
4,6
7,4
11,6
5,8
9,5
14,3
7,0
11,4
16,8
Eurovent conditions
CWC 050 2P
Speed
Water
temp. Air flow
ºC
Inlet Air Temperature
in/out
Relative humidity
6 / 11
3 Rows Coil
7 / 12
8 / 13
9 / 14
m3/h
ºC
%
Low Speed
650
22
25
27
50 +/-10%
CWC 050 4P
Medium Speed
791
22
High Speed
920
25
27
50 +/-10%
22
25
27
50 +/-10%
Low Speed
650
Medium Speed
791
22
25
27
50 +/-10%
22
25
27
50 +/-10%
High Speed
920
22
25
27
50 +/-10%
Total capacity
kW
2,45
3,73
4,61
2,80
4,27
5,31
3,08
4,73
5,88
2,12
3,28
4,09
2,52
3,72
4,65
2,79
4,09
5,12
Sensible capacity
kW
2,31
2,86
3,20
2,70
3,33
3,74
3,03
3,74
4,19
2,17
2,68
3,01
2,61
3,10
3,47
2,90
3,44
3,86
Outlet Air Temperature
ºC
11,23 11,69 12,06
12,01 12,69
13,20
11,90 12,51 12,97
11,65 12,23 12,68
12,01 13,14 13,69
12,46 13,65 14,28
Water flow
l/h
433
652
805
493
747
925
544
827
1025
377
575
714
445
653
813
494
717
894
Water press. drop
kPa
9,4
19,7
28,8
11,9
25,2
37,0
14,2
30,2
44,5
9,3
19,8
29,3
12,5
24,9
37,0
15,1
29,5
43,9
Total capacity
kW
2,26
3,30
4,19
2,63
3,78
4,82
2,94
4,17
5,33
2,01
2,89
3,70
2,31
3,28
4,21
2,57
3,59
4,62
Sensible capacity
kW
2,26
2,67
3,02
2,63
3,12
3,53
2,94
3,50
3,96
2,08
2,51
2,84
2,40
2,90
3,28
2,66
3,23
3,65
Outlet Air Temperature
ºC
11,47 12,55 12,91
12,30 13,47
13,97
12,30 13,32 13,76
11,92 13,05 13,48
12,81 13,89 14,44
13,23 14,37 14,98
Water flow
l/h
400
579
733
465
662
841
521
731
930
357
508
648
410
576
736
456
632
809
Water press. drop
kPa
8,1
15,8
24,2
10,7
20,1
31,0
13,1
24,1
37,2
8,4
15,8
24,5
10,8
19,8
30,8
13,0
23,4
36,5
Total capacity
kW
2,07
2,85
3,76
2,41
3,26
4,31
2,69
3,59
4,76
1,83
2,48
3,30
2,11
2,81
3,75
2,34
3,07
4,11
Sensible capacity
kW
2,07
2,48
2,84
2,41
2,90
3,32
2,69
3,26
3,72
1,90
2,33
2,67
2,19
2,70
3,09
2,43
3,01
3,44
Outlet Air Temperature
ºC
12,36 13,43 13,76
13,13 14,26
14,74
13,14 14,12 14,56
Water flow
l/h
367
502
658
426
573
753
477
631
832
327
438
579
375
495
657
417
542
721
Water press. drop
kPa
6,9
12,2
19,8
9,1
15,4
25,2
11,1
18,4
30,2
7,1
12,0
19,9
9,1
15,0
24,9
11,0
17,7
29,5
Total capacity
kW
1,88
2,38
3,31
2,18
2,71
3,78
2,44
3,19
4,16
1,66
2,18
2,89
1,91
2,52
3,27
2,11
2,79
3,58
Sensible capacity
kW
1,88
2,29
2,66
2,18
2,68
3,11
2,44
3,19
3,48
1,72
2,26
2,50
1,98
2,61
2,89
2,19
2,90
3,22
Outlet Air Temperature
ºC
13,25 14,31 14,62
13,96 14,48
15,52
13,99 14,46 15,35
12,77 13,87 14,29
13,63 14,72 15,10
13,61 14,65 15,18
14,42 15,00 15,92
14,00 15,09 15,68
14,78 15,46 16,39
Water flow
l/h
334
421
580
388
479
662
434
563
730
296
386
508
340
445
575
378
495
630
Water press. drop
kPa
5,8
8,8
15,7
7,6
11,1
19,9
9,3
14,9
23,7
5,9
9,6
15,6
7,6
12,3
19,5
9,2
14,9
23,0
Eurovent conditions
5
PERFORMANCES TABLES
COOLING CAPACITIES
CWC 070 2P
Speed
Water
temp. Air flow
ºC
Inlet Air Temperature
in/out
Relative humidity
6 / 11
3 Rows Coil
7 / 12
8 / 13
9 / 14
m3/h
ºC
Low Speed
987
22
%
CWC 070 4P
Medium Speed
1164
25
27
50 +/-10%
22
High Speed
1342
25
27
50 +/-10%
22
25
27
50 +/-10%
Low Speed
987
Medium Speed
1164
22
25
27
50 +/-10%
22
25
27
50 +/-10%
High Speed
1342
22
25
27
50 +/-10%
Total capacity
kW
3,66
5,58
6,92
4,08
6,24
7,76
4,46
6,86
8,54
3,20
4,71
5,88
3,61
5,24
6,56
3,99
5,72
7,17
Sensible capacity
kW
3,35
4,13
4,64
3,79
4,68
5,25
4,22
5,19
5,83
3,20
3,78
4,24
3,61
4,27
4,78
3,99
4,73
5,30
Outlet Air Temperature
ºC
11,73 12,32 12,77
12,13 12,82 13,33 12,48 13,27
13,84
12,17 13,40 13,98
12,60 13,89 14,54 12,98 14,32 15,03
Water flow
l/h
639
969
1200
711
1084
1345
779
1191
1480
560
819
1021
631
911
1138
698
995
1245
Water press. drop
kPa
6,9
14,7
21,6
8,4
18,0
26,5
9,9
21,3
31,5
5,3
10,5
15,6
6,5
12,7
18,9
7,8
14,9
22,2
Total capacity
kW
3,39
4,94
6,29
3,83
5,51
7,04
4,24
6,05
7,74
2,95
4,14
5,32
3,32
4,60
5,92
3,67
5,01
6,47
Sensible capacity
kW
3,23
3,87
4,37
3,65
4,38
4,95
4,05
4,87
5,51
2,95
3,54
4,00
3,32
4,00
4,52
3,67
4,43
5,01
Outlet Air Temperature
ºC
12,08 13,13 13,57
12,49 13,60 14,10 12,85 14,01
14,57
12,94 14,14 14,71
13,35 14,59 15,23 13,71 14,99 15,68
Water flow
l/h
592
858
1091
669
959
1221
741
1052
1343
517
722
925
582
801
1029
643
874
1124
Water press. drop
kPa
6,0
11,7
18,1
7,5
14,3
22,1
9,0
16,9
26,2
4,5
8,3
12,9
5,6
10,0
15,7
6,7
11,7
18,4
Total capacity
kW
3,10
4,27
5,63
3,50
4,75
6,30
3,88
5,21
6,91
2,70
3,55
4,74
3,03
3,93
5,26
3,35
4,28
5,74
Sensible capacity
kW
2,96
3,60
4,11
3,34
4,08
4,66
3,70
4,54
5,18
2,70
3,29
3,76
3,03
3,73
4,25
3,35
4,14
4,72
Outlet Air Temperature
ºC
12,92 13,95 14,37
13,30 14,38 14,86 13,64 14,75
15,30
13,73 14,89 15,44
14,10 15,30 15,92 14,43 15,65 16,34
Water flow
l/h
542
743
978
613
828
1093
679
907
1200
473
620
825
532
686
916
588
747
999
Water press. drop
kPa
5,1
9,0
14,7
6,4
10,9
18,0
7,7
12,9
21,3
3,8
6,3
10,5
4,8
7,5
12,6
5,7
8,8
14,8
Total capacity
kW
2,81
3,56
4,95
3,18
3,96
5,52
3,52
4,60
6,05
2,44
3,20
4,13
2,74
3,61
4,58
3,03
4,00
4,99
Sensible capacity
kW
2,68
3,33
3,85
3,03
3,77
4,37
3,36
4,40
4,85
2,44
3,20
3,53
2,74
3,61
3,99
3,03
4,00
4,43
Outlet Air Temperature
ºC
13,76 14,79 15,18
14,11 15,17 15,63 14,42 15,07
16,05
14,51 15,16 16,17
14,85 15,59 16,62 15,16 15,97 17,00
Water flow
l/h
493
621
860
556
691
959
616
803
1052
429
560
720
482
632
799
532
699
870
Water press. drop
kPa
4,3
6,5
11,6
5,3
7,8
14,2
6,4
10,3
16,7
3,2
5,2
8,2
4,0
6,4
9,8
4,7
7,7
11,5
Eurovent conditions
CWC 090 2P
Speed
Water
temp. Air flow
ºC
Inlet Air Temperature
in/out
Relative humidity
6 / 11
3 Rows Coil
7 / 12
8 / 13
9 / 14
m3/h
ºC
%
Low Speed
1126
22
CWC 090 4P
Medium Speed
1323
25
27
50 +/-10%
22
High Speed
1569
25
27
50 +/-10%
22
25
27
50 +/-10%
Low Speed
1126
Medium Speed
1323
22
25
27
50 +/-10%
22
25
27
50 +/-10%
High Speed
1569
22
25
27
50 +/-10%
Total capacity
kW
4,03
6,15
7,64
4,48
6,88
8,56
5,00
7,72
9,62
3,66
5,62
7,00
4,06
6,26
7,80
4,75
6,97
8,71
Sensible capacity
kW
3,85
4,75
5,34
4,36
5,39
6,05
4,97
6,13
6,88
3,76
4,64
5,20
4,24
5,23
5,86
4,98
5,91
6,62
Outlet Air Temperature
ºC
11,65 12,21 12,63 12,01 12,66 13,14 12,41 13,16
13,72
11,89 12,53
12,99
12,30 13,03 13,58
12,38 13,59 14,21
Water flow
l/h
704
1069
1325
783
1196
1485
874
1341
1669
641
979
1215
710
1088
1354
831
1214
1513
Water press. drop
kPa
5,2
11,1
16,3
6,3
13,5
20,0
7,7
16,7
24,7
7,9
17,0
25,1
9,6
20,6
30,5
12,7
25,1
37,2
Total capacity
kW
3,74
5,44
6,94
4,23
6,08
7,77
4,79
6,80
8,71
3,45
4,96
6,35
3,88
5,51
7,07
4,37
6,13
7,88
Sensible capacity
kW
3,74
4,45
5,04
4,23
5,04
5,71
4,79
5,73
6,49
3,62
4,34
4,91
4,07
4,89
5,54
4,59
5,54
6,26
Outlet Air Temperature
ºC
11,94 13,03 13,44 12,32 13,45 13,93 12,75 13,92
14,46
12,27 13,32
13,78
12,68 13,79 14,32
13,14 14,31 14,91
Water flow
l/h
654
947
1204
739
1057
1348
838
1183
1513
605
865
1103
679
961
1227
766
1069
1369
Water press. drop
kPa
4,5
8,8
13,6
5,7
10,8
16,7
7,1
13,2
20,6
7,1
13,5
21,0
8,8
16,4
25,4
10,9
19,8
31,0
Total capacity
kW
3,42
4,70
6,21
3,87
5,23
6,94
4,38
5,84
7,77
3,15
4,27
5,67
3,55
4,74
6,30
4,00
5,26
7,02
Sensible capacity
kW
3,42
4,14
4,73
3,87
4,69
5,37
4,38
5,34
6,10
3,31
4,04
4,62
3,72
4,56
5,21
4,19
5,16
5,89
Outlet Air Temperature
ºC
12,79 13,87 14,26 13,14 14,25 14,71 13,54 14,68
15,21
13,10 14,13
14,56
13,48 14,56 15,07
13,91 15,03 15,62
Water flow
l/h
600
819
1079
677
912
1206
768
1019
1351
554
747
987
622
827
1096
701
919
1221
Water press. drop
kPa
3,9
6,8
11,1
4,8
8,2
13,6
6,0
10,0
16,7
6,0
10,3
17,1
7,4
12,4
20,6
9,2
15,0
25,0
Total capacity
kW
3,11
3,91
5,45
3,51
4,35
6,08
3,97
5,20
6,79
2,86
3,74
4,97
3,21
4,21
5,51
3,61
4,75
6,12
Sensible capacity
kW
3,11
3,82
4,43
3,51
4,34
5,02
3,97
5,20
5,72
3,00
3,92
4,32
3,37
4,42
4,88
3,79
4,99
5,53
Outlet Air Temperature
ºC
13,64 14,72 15,08 13,97 15,07 15,49 14,33 14,96
15,95
13,93 14,44
15,36
14,29 14,88 15,83
14,68 15,37 16,33
Water flow
l/h
545
684
949
615
760
1058
697
909
1183
503
655
866
564
737
960
636
832
1067
Water press. drop
kPa
3,2
4,9
8,8
4,0
5,9
10,7
5,0
8,1
13,0
5,0
8,1
13,4
6,2
10,0
16,1
7,7
12,5
19,5
Eurovent conditions
6
PERFORMANCES TABLES
HEATING CAPACITIES
CWC 020
45 / 40
4 Pipes
90 / 70
80 / 60
70 / 60
60 / 50
m3/h
ºC
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
CWC 030
L
M
H
445
550
20
2,33
32,8
298
14,2
1,98
30,9
333
17,8
1,76
29,7
74
0,9
1,34
27,4
56
0,6
1,42
27,8
119
2,3
1,02
25,6
84
1,2
650
2,01
33,7
261
11,2
1,71
31,6
288
13,7
1,60
30,9
67
0,8
1,22
28,3
51
0,5
1,29
28,8
108
1,9
0,93
26,3
77
1,1
Water
temp.
ºC
in/out
2,60
32,1
329
17,0
2,21
30,3
372
21,8
1,87
28,7
78
1,0
1,43
26,7
59
0,6
1,51
27,1
126
2,5
1,08
25,1
89
1,4
50 / (*)
2 Pipes
2 Pipes
50 / (*)
Speed
Air flow
Inlet Air Temperature
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
45 / 40
90 / 70
4 Pipes
Water
temp.
ºC
in/out
80 / 60
70 / 60
60 / 50
Speed
Air flow
Inlet Air Temperature
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
m3/h
ºC
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
L
M
H
400
517
20
3,62
41,2
539
18,2
3,03
37,8
514
20,0
2,70
35,9
115
3,6
2,52
34,8
107
2,7
2,24
33,1
189
7,6
1,74
30,2
146
4,9
598
2,98
42,6
450
13,2
2,49
38,8
422
14,0
2,22
36,8
94
2,5
2,07
35,7
88
1,9
1,83
33,9
154
5,3
1,42
30,8
120
3,4
4,05
40,5
595
21,8
3,40
37,2
576
24,5
3,05
35,4
129
4,5
2,83
34,4
120
3,3
2,53
32,8
213
9,4
1,96
29,9
164
6,1
Eurovent conditions
(*) Water outlet temperature for same water flow than cooling mode
CWC 040
45 / 40
4 Pipes
90 / 70
80 / 60
70 / 60
60 / 50
m3/h
ºC
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
CWC 050
L
M
H
553
670
20
4,16
38,8
645
33,3
3,48
35,7
588
35,0
4,25
39,2
180
13,3
3,37
35,2
142
9,3
3,22
34,6
272
30,2
2,42
31,0
203
18,5
779
3,61
39,8
567
26,3
3,01
36,5
508
26,9
3,82
40,9
162
11,0
3,03
36,6
128
7,7
2,90
35,9
244
24,9
2,18
31,9
183
15,3
Water
temp.
ºC
in/out
4,65
38,1
712
39,7
3,89
35,1
658
42,9
4,61
37,9
195
15,4
3,65
34,2
154
10,7
3,50
33,6
295
34,9
2,63
30,2
220
21,4
50 / (*)
2 Pipes
2 Pipes
50 / (*)
Speed
Air flow
Inlet Air Temperature
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
45 / 40
90 / 70
4 Pipes
Water
temp.
ºC
in/out
80 / 60
70 / 60
60 / 50
Eurovent conditions
(*) Water outlet temperature for same water flow than cooling mode
7
Speed
Air flow
Inlet Air Temperature
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
m3/h
ºC
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
L
M
H
650
791
20
6,17
43,6
841
37,0
5,17
39,8
877
41,0
5,32
40,4
226
14,8
4,38
36,8
185
10,6
4,01
35,4
339
32,0
3,09
31,8
260
20,3
920
5,29
44,7
733
28,9
4,42
40,6
749
30,9
4,69
41,9
199
11,8
3,87
38,0
163
8,5
3,53
36,5
298
25,4
2,73
32,7
229
16,2
6,94
42,9
930
44,4
5,82
39,2
987
50,7
5,84
39,2
248
17,6
4,80
35,8
203
12,6
4,41
34,5
373
38,0
3,40
31,2
285
24,1
PERFORMANCES TABLES
HEATING CAPACITIES
CWC 070
45 / 40
4 Pipes
90 / 70
80 / 60
70 / 60
60 / 50
m3/h
ºC
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
CWC 090
L
M
H
987
1164
20
7,43
39,3
1221
25,0
6,14
36,0
1046
23,4
8,18
41,3
349
10,6
6,63
37,3
283
7,4
6,24
36,2
531
23,4
4,73
32,3
402
14,5
1342
6,65
40,4
1091
20,4
5,50
36,9
938
18,6
7,45
42,9
318
9,0
6,05
38,6
258
6,3
5,67
37,4
483
19,8
4,31
33,2
366
12,3
Water
temp.
ºC
in/out
8,26
38,7
1343
29,7
6,83
35,4
1164
28,3
8,84
40,0
377
12,2
7,16
36,2
305
8,5
6,75
35,2
575
27,0
5,11
31,5
434
16,7
50 / (*)
2 Pipes
2 Pipes
50 / (*)
Speed
Air flow
Inlet Air Temperature
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
45 / 40
90 / 70
4 Pipes
Water
temp.
ºC
in/out
80 / 60
70 / 60
60 / 50
Speed
Air flow
Inlet Air Temperature
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
Total capacity
Outlet Air Temperature
Water flow
Water pressure drop
m3/h
ºC
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
kW
ºC
l/h
kPa
L
M
H
400
517
20
9,86
42,6
1348
20,1
8,25
38,9
1406
22,3
9,16
41,0
391
9,8
7,50
37,2
319
7,0
6,91
35,8
588
21,1
5,29
32,1
449
13,3
598
8,70
43,4
1204
16,4
7,26
39,6
1238
17,7
8,20
42,1
350
8,0
6,72
38,1
286
5,7
6,17
36,6
525
17,3
4,73
32,7
402
10,9
11,23
41,7
1513
24,8
9,41
38,2
1604
28,3
10,15
39,6
433
11,8
8,30
36,0
353
8,4
7,67
34,8
653
25,5
5,87
31,3
497
16,1
Eurovent conditions
(*) Water outlet temperature for same water flow than cooling mode
WATER PRESSURE DROP WITH GLYCOL
As the percentage of glycol increases, the standard pump flow decreases due to the increased pressure characteristics. This
means that the cooling and heating duties will decrease. As a result, the pressure drop must be multiplied by the coefficient
shown in the following table:
10%
20%
30%
Ethylene glycol %
Pressure drop
x 1.07
x 1.12
x 1.20
SOUND LEVELS
CWC SOUND POWER LEVEL SPECTRA dB ref. 1pW
MODEL
CWC 020
CWC 030
CWC 040
CWC 050
CWC 070
CWC 090
FAN
SPEED
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
125
36,1
38,4
39,5
32,7
40,7
41,6
39,3
44,3
47,2
49,9
49,4
50,1
42,5
45,9
48,7
46,0
49,0
53,1
250
39,9
45,3
47,8
39,4
44,2
47,5
45,9
49,2
52,1
51,0
54,4
60,6
49,6
53,2
56,7
53,4
56,5
61,0
FREQUENCY (Hz)
500
1K
2K
41,1
45,7
49,9
39,7
44,9
48,5
46,0
49,8
52,2
50,2
53,4
59,0
49,4
54,0
57,6
54,1
57,4
61,0
34,4
41,3
46,1
33,4
40,4
44,6
41,4
47,1
50,3
47,0
51,4
56,3
46,5
52,0
55,8
51,1
55,3
59,3
25,9
36,6
40,9
27,0
36,1
41,7
36,7
44,6
49,0
45,9
49,8
55,1
42,3
49,8
54,2
50,4
54,7
58,6
4K
21,7
32,8
31,8
22,2
23,1
28,1
24,4
32,9
40,1
37,2
44,3
50,8
28,4
38,1
45,2
39,5
45,8
51,9
8K
23,9
27,5
26,2
23,5
23,6
23,9
23,8
24,4
27,7
26,1
31,8
39,9
23,8
26,0
32,3
27,7
34,4
42,8
Lw
dB(A)
41
47
51
40
46
50
47
52
55
53
56
62
51
56
60
56
60
64
Lp
dB(A)
32
38
42
31
37
41
38
43
46
44
47
53
42
47
51
47
51
55
NR
GUIDE
28
33
37
27
32
36
33
39
43
40
44
49
38
44
48
44
48
52
Lw dB(A): Sound power level dB(A) ref 10 (-12) W EUROVENT conditions.
Lp dB(A): Sound pressure level dB(A) ref 2x10 (-5) N/m2 calculated in a room of 100m3 and 0,5 seconds reverberation time.
Room NR guide: The NR figures above are calculated in a room of 100m3 and 0,5 seconds reverberation time.
8
OPTIONS
ELECTRIC HEATER (only for CWC 020-030-040-070-090 2P). TECHNICAL DATA
POWER
CWC 020 2P
VOLTAGE
1.5 kW
230 V 1Ph -50Hz
CWC 030-040 2P
2 kW
CWC 070-090 2P
2.5 kW / 4 kW
230 V 1Ph -50Hz
230 V / 400 V 3Ph-50Hz
• Side knockouts panel are provided. One to connect a fresh air inlet duct, and another to connect an air distribution
duct to deliver air to an adjacent room.
FRESH AIR MAKE UP (FIG. 5)
INSTALLATION
• Remove the 68 mm insulation material and cut out the prepunched side knockouts.
• Secure the duct connection flange to the unit. Conducts can be of flexible polyester type or corrugate aluminium,
externally covered with anticorrosion material.
• Install a supplementary fresh air fan for the introduction of fresh air into the unit. The fan motor must be controlled
by an ON-OFF switch.
• Fresh air flow must be less than 10% of the total air flow, to avoid operating problems. A speed controller should
be installed in the supplementary fan motor, for adjusting the air flow.
AIR SUPPLY TO AN ADJACENT ROOM (FIG. 6)
INSTALLATION
• Remove the 150 mm insulation material and cut out the prepunched side knockouts. For models 600x600, the
two prepunched side knockouts must not be used at the same time to provide conditioned air to an adjacent
room. For models 600x1200, do not use the same fan to provide air conditioned to both ducts.
• Cut away the polystyrene around the inside edge of the opened panel, remove the polystyrene.
• Use a duct connection flange and a suitable duct.
• Air supply to an adjacent room requires that outlet corresponding with the duct is closed.
• An air inlet grille must be fitted (if possible near the floor) between the air conditioned room (where the unit is
situated) and the adjacent room.
• Conducts can be of flexible polyester type or corrugate aluminium, externally covered with anticorrosion material.
The duct length can be calculated by taking into account the pressure drop through the unit, using the following
table:
Air flow supplied to an adjacent room in m3/h, fresh air fan at high speed:
CWC 020-030 2P
UNIT/MODELS CWC 020-030 4P
Air flow
m3/h
Available Pa
pressure
600x600
175 100 25
0
8
Air inlet grille and filter
CWC 040 2P
CWC 040 4P
CWC 050 2P
CWC 050 4P
CWC 070 2P
CWC 070 4P
CWC 090 2P
CWC 090 4P
200 100
250 125 25
400 200 50
500
250 50
0
20 30
15
600x1200
0
10
25
20
0
Duct connection Ø75 mm (*)
20 30
600x600
Duct connection
Ø150mm flange
and clip (*)
Duct connection Ø75 mm (*)
Reduction
125-75mm (*)
0
10
Insulated flexible
duct Ø150
20
600x1200
Duct connection Ø150mm
flange and clip (*)
Reduction
125-75mm (*)
Duct Ø125mm
Duct Ø125mm
Fan (*)
Air intake
FIG. 5
Duct Ø150mm
Grille
Conic tapping
150x125 (*)
Fan (*)
Air inlet grille
and filter
FIG. 6
Air intake
(*) Elements included in optional kit
9
Grille
Insulated flexible
duct Ø150
OPTIONS
WATER CONTROL VALVE KIT (2 AND 3 WAYS, ON/OFF AND PROPORTIONAL)
MODEL 600x600
2 PIPES SYSTEM
Air vent
Water control valve
(3 ways)
Coupling
NOTE THE CORRECT
POSITION OF THE
WATER CONTROL
VALVE
Condensate
pump flexible
hose
4 PIPES SYSTEM
Hot water control valve
Air vent
Water control valve
Cool water control valve
Condensate
pump flexible
hose
Main wire
Main wire
CAUTION
Connect each valve ON/OFF
to its corresponding connector
(cooling connector and
heating connector).
Auxiliary drip tray
Auxiliary drip tray
MODEL 600x1200
Water control valve
(3 ways) proportional
2 PIPE SYSTEM
Water connection
4 PIPE SYSTEM
Water control valve
Auxiliary drip tray
Main wire
Connecting
flexible hose
Drain tube from
auxiliary drip tray
Drain tube from
drip tray
Main wire
Auxiliary
drip tray
Hot water
control valve
Auxiliary
drip tray
NOTE THE CORRECT
POSITION OF THE
WATER CONTROL
VALVE
AUXILIARY DRIP TRAY
Cool water
control valve
Auxiliary drip tray
• Install the auxiliary drip tray as shown in the illustration.
• Connect the drain tube from drip tray to the auxiliary drip tray.
• The condensate drains from auxiliary drip tray will be pumped away.
NOTE: Proportional valves, must be connected to a proportional
flow regulation control (not included in optional kit)
Drain tube from
drip tray
Drain tube from
auxiliary drip tray
FITTING & TESTING VALVES
It includes fitting and testing valves and in addition auxiliary drip tray is included too.
WATER EVACUATION SECURITY
With this option, water pump works if there is an over flow in the drip tray.
10
Connecting flexible hose
DIMENSIONS
MODELS 600 x 600
72
23.5
Inlet hot water
connection 1/2” G
247
247
121
Inlet water
connection 1/2” G
91
121
32
Outlet hot water
connection 1/2” G
61
Outlet water
connection 1/2” G
91
23.5
32
72
Inlet cool water
connection 1/2” G
Outlet cool water
connection 1/2” G
2 PIPES SYSTEM
4 PIPES SYSTEM
40
40
PLASTIC DIFFUSER
METALLIC DIFFUSER
575
4 x hanging brackets (M 8)
Air vent
Air vent
4 x hanging
brackets (M 8)
15
0
Electrical cable
entry point
Ø
Ø
15
0
Electrical cable
entry point
Drain tube 16mm OD
Drain tube 16mm OD
Condensate pump flexible
hose 10mm ID 15mm OD
Condensate pump flexible
hose 10mm ID 15mm OD
720
489.74
54.66
489.74
30.6
619
30
619
720
17.5
540
17.5
30.6
575
575
68
196
123
143
Ø
Ø
15
15
0
0
298
196
273
68
Ø
123
Fresh air knockout panel
for branch duct
CASSETTE UNIT
46.5
298
CASSETTE UNIT
46.5
143
284
Ø
284
273
54.66
PLASTIC DIFFUSER PANEL
Branch duct knockout hole, to supply air
into adjacent area
Fresh air knockout panel
for branch duct
11
METALLIC DIFFUSER PANEL
Branch duct knockout hole, to supply air
into adjacent area
DIMENSIONS
MODELS 600 x 1200
Outlet hot water
connection 1/2''G
90
30
152
197
Outlet cool water
connection 3/4''G
Outlet cool water
connection 3/4''G
Inlet cool water
connection 3/4''G
Inlet cool water
connection 3/4''G
Inlet hot water
connection 1/2''G
2 PIPES SYSTEM
4 PIPES SYSTEM
PLASTIC DIFFUSER
METALLIC DIFFUSER
Condensate pump flexible hose
10 mm ID 15 mm OD
1140
Condensate pump flexible hose
10 mm ID 15 mm OD
284.8
24
Ø
Ø
15
0
0
24
15
123
75
251
251
123
75
284.8
4x Hanging brackets
63
Drain tube 16 mm OD
Branch duct knockout hole, to supply
air into adjacent area
1140
63
Electrical cable entry point
Drain tube 16 mm OD
Branch duct knockout hole, to supply
air into adjacent area
1140
17.5
29.5
527
527
1219
37
121
1320
619
Main electrical board
Auxiliary electrical board
720
493.6
51.9
17.5
4x Hanging brackets
Electrical cable entry point
575
575
Fresh air knockout panel
for branch duct
Fresh air knockout panel
for branch duct
CASSETTE UNIT
PLASTIC DIFFUSER PANEL
298
196
273
Ø6
8
298
143
46.5
196
273
Ø6
8
143
46.5
CASSETTE UNIT
METALLIC DIFFUSER PANEL
12
UNIT INSTALLATION
1. The unit should be positioned centrally within the room. The ceiling must be horizontal to ensure that the unit
is on level and that condensate water can drain away thoroughly. The unit must be installed in a position where
there is sufficient strength in the structure to support the weight of the unit. The false ceiling must have at less a
height of 308 mm.
MODEL 600x1200
MODEL 600x600
Cassette
unit
308
308
Cassette
unit
Diffuser panel
Diffuser panel
2. Ensure there is sufficient space around the unit to service it. Where there is a false ceiling, ensure that there is
enough space to provide access. Where there is a false panelled ceiling ensure that there is sufficient adjacent
space to remove the panels.
MODEL
600x600
MODEL
600x1200
298
500
Min. *)
(*
0
72
500
Min. *)
(*
720
M
0
50
n.
Mi (**)
in
.
(** 50
) 0
(**) INSTALLATION CLEARANCES
3. Models 600x600: cut the false ceiling to a maximum dimension of 625x625mm. For a panelled ceiling remove
one panel of 600x600mm.
Models 600x1200: cut the false ceiling to a maximum dimension of 625x1225mm. For a panelled ceiling remove
two panels of 600x600 or one of 600x1200mm.
4. Install the suspension rods to the ceiling, the rods should
have three nuts and two washers, as in next figure. The
setting up template can be used to indicate the position for
the suspension rods.
1
2
NOTE: Before marking the fixing points to the ceiling,
ensure that the unit is positioned in the correct orientation
taking into account of where the electrical cabinet is required.
Ensure that water pipes can be run easily. When the unit
is fixed it is not easy to change position.
SETTING UP TEMPLATE MODEL 600x600
1
Nut
2
Washers
2
Suspension rods M-8
1
1
SETTING UP TEMPLATE MODEL 600x1200
489.74
30.6
42.5
575
1140
Fixing points
54.66
17.5
489.74
5. The water connections should be positioned before unit is installed.
13
51.2
1225
30.6
42.5
493.6
600
540
54.66
55.2
Fixing
points
17.5
575
UNIT INSTALLATION
6. For Models 600x600, to facilitate the connections of water pipes and the drain tube, is advisable to disassemble
the supporting bracket situated on this corner. Once the installation is completed, the bracket must be reassembled.
7. When lifting the cassette into position care should be taken not to lift the unit by the drip tray, water connection
or drain tube; these elements could be damaged. The cassette should be lifted by the hanging brackets. The hanging
brackets should be insulated with the supplied insulation.
8. The cassette brackets hook over the washer.
Tighten the cassette with the lower nuts.
MODEL 600x600
MODEL 600x1200
9. Check to ensure the unit is level. The drain
will then automatically be lower than the rest of
the drip tray.
10. Tighten the nuts on the suspended rods to ensure a distance of 25 mm between the bottom face of the body
of the unit and false ceiling.
MODEL 600x600
MODEL 600x1200
PLASTIC DIFFUSER
25
25
25
False
ceiling
25
False
ceiling
Plastic diffuser panel
Plastic diffuser panel
METALLIC DIFFUSER
False
ceiling
25
25
25
25
False
ceiling
Metallic diffuser panel
Metallic diffuser panel
14
ELECTRICAL CONNECTIONS
2
1
2
1
POWER SUPPLY WIRING
This equipment must be installed in accordance
with national regulations. A suitable means of
disconnecting all supply poles must be provided
in the power supply wiring. The power supply must
incorporate suitably rated fused or circuit breaker
protection.
Power supply
Thermostat
connections
NUMBER OF WIRES X SECTION
VOLTAGE
50Hz
UNIT
COOL WATER
1
2
230 V / 1Ph 3 X 1.5mm2 7 X 1.5mm2
3 X 1.5mm2
8 X 1.5mm2
2
2
230 V / 1Ph 3 X 1.5mm 7 X 1.5mm
3 X 1.5mm2
7 X 1.5mm2
2
2
230 V / 1Ph 3 X 1.5mm 7 X 1.5mm
3 X 1.5mm2
8 X 1.5mm2
----
3 X 1.5mm2
7 X 1.5mm2
1
CWC020 2P / CWC030 2P
MODELS CWC040 2P/ CWC050 2P
600x600 CWC 020 4P / CWC 030 4P
CWC 040 4P / CWC 050 4P
CWC070 2P / CWC090 2P
MODELS
600x1200 CWC070 4P / CWC090 4P
COOL AND HOT WATER
230 V / 1Ph
2
----
MODELS 600 x 600
CWC 2P
CWC 2P
CHILLED WATER
CHILLED WATER AND HOT WATER
0
1
1
2
1
2
3
4
5
6
7
8
THERMOSTAT
2
2
3
4
5
6
7
8
CASSETTE UNIT
CWC 4P
1
2
1
2
3
4
5
6
7
8
2
2
3
4
5
6
7
8
2
230V/50HZ 1Ph + N
CWC 4P
CHILLED WATER
1
1
ELECTRIC WIRING DIAGRAM
For electrical connection refer to
wiring diagram
in the unit.
230V/50HZ 1Ph + N
0
0
1
CHILLED WATER AND HOT WATER
1
2
3
4
5
6
7
8
2
2
3
4
5
6
7
8
THERMOSTAT
RC 311-X2
CASSETTE UNIT
0
1
230V/50HZ 1Ph + N
1
2
1
2
3
4
5
6
7
8
2
2
3
4
5
6
7
8
230V/50HZ 1Ph + N
MODELS 600 x 1200
CWC 2P-4P
CWC 2P
CHILLED WATER CWC 070-090 2P
CHILLED WATER AND HOT WATER CWC 070-090 4P
CHILLED WATER AND HOT WATER
CWC 070-090 2P
0
1
1
2
1
2
3
4
5
6
7
8
THERMOSTAT
RC-311-X2
2
2
3
4
5
6
7
8
CASSETTE UNIT
230V/50HZ 1Ph + N
0
1
1
2
1
2
3
4
5
6
7
8
2
2
3
4
5
6
7
8
230V/50HZ 1Ph + N
15
ELECTRICAL CONNECTIONS
WARNING
Electric shock hazard can cause
injury or death. Before attempting
to perform any service or
maintenance on the unit, turn OFF
the electrical power, and check that
the fan has stopped.
MODEL 600x600
Cover plate for
electrical box
Terminal
plate
cover
MODEL 600x1200
Cover plate
for auxiliary
electrical box
Cover plate for
electrical box
Terminal
plate
cover
ACCESS TO THE ELECTRICAL COMPONENTS OF THE UNIT
Removing the corresponding plate cover screws gives access to the electrical board and terminal plate, as indicated on the
drawing.
ELECTRICAL WIRING DIAGRAM
For electrical connection refer to wiring diagram in the unit.
1
2
3
1
Electrical inlets, power supply and remote controller.
2
Terminal plate.
3
Electrical connections (it depends on versions).
DRAIN PIPEWORK
MODELS 600 x 600
MODELS 600 x 1200
Condensate
pump flexible
hose
Condensate
pump flexible
hose
Drain tube
Drain tube
CONDENSATE PUMP FLEXIBLE HOSE
• The unit is fitted with a condensate pump to ensure condensate removal.
• To ensure that there is condensate flow, the drain tube must be installed with a fall of 2% without obstructions, or without
rising sections.
• To avoid any unpleasant odours from the drainage system a trap must be fitted with a trap depth of no less than 50 mm.
• The condensate pump has a maximum lift of 200 mm. The rising tube must be always vertical.
• On completion the drain line must be insulated.
Max.200mm
2%
2%
50
DRAIN TUBE
• The drain tube is connected to drip tray.
• This drain tube is supplied with a cap; the cap can be removed when it is necessary to remove any water that accumulates
in the drip tray.
16
INSTALLATION OF DIFFUSER AND INLET GRILLE
WARNING: Electric shock hazard can cause injury or death. Before attempting to perform any service or maintenance
on the unit, turn OFF the electrical power, and check that the fan has stopped.
PLASTIC DIFFUSER PANEL
MOUNTING THE DIFFUSER PANEL TO THE UNIT
Check that the position in which the diffuser is mounted is the right one.
1. - Release the air intake grille.
2. - The diffuser panel can then be provisionally positioned on the cassette using the fixing clips.
3. - The diffuser is fastened with the bolts supplied.
4. - Make sure that the frame has not been deformed in the installation, by an excessive tighten of the bolts. There must be
no recirculation of air between intake and outlet air paths.
The diffuser panel is sealed with insulation to avoid air gaps between the unit and the air panel. The insulation can be compressed
from 8 mm to 3 mm, allowing the panel to be tightened to the cassette by up to 5 mm.
MOUNTING THE AIR INTAKE GRILLE AND FILTER ASSEMBLY
MODEL 600x1200
1.- The grill fixing hooks should be fitted into the holes provided.
2.- The stays need to be placed between the diffuser and the inlet grille.
3.- The grille is mounted on the diffuser via two hand triggers. Initially pull
off the hand triggers, then insert the grille into the diffuser and release
the hand triggers. When this operation is completed the grille is
attached to the diffuser.
Unit
Unit
MODEL 600x600
Diffuser panel
Hooks
DETAIL A
Hooks
Swing motor
Swing
motor
Stays
Stays
Diffuser
panel
A
Swing motor
Air intake grille
Air intake
grille
Hand
triggers
A
Air filter
Hand triggers
Air filter
METALLIC DIFFUSER PANEL
MOUNTING THE DIFFUSER PANEL TO THE UNIT
1.- Release the air intake grille on the unit.
Open the grille by way of one hand trigger, which is close to the Lennox brand. The grille will swing down supported by two
screws located on the opposite side of the hand trigger.
2.- Fix the bolts supplied (Do mot used other kind of bolts), to the unit (Do not fasten at moment).
3.- The diffuser is positioned on the cassette, by introducing the bolts supplied on the hole through the bigger part (see detail
A) and displace the diffuser to the small part of the hole. Then fasten the four bolts supplied to the unit.
4.- Make sure that the frame has not been deformed in the installation, by an excessive tighten of the bolts. There must be no
recirculation of air between intake and outlet air paths.
The diffuser panel is sealed with insulation to avoid air gaps between the unit and the air panel. The insulation can be compressed
from 8 mm to 3 mm, allowing the panel to be tightened to the cassette by up to 5 mm.
Cassette unit
MODEL 600x1200
Cassette unit
MODEL
600x600
Detail A
DETAIL A
Detail A
Diffuser
panel
Air grille
Diffuser
panel
B
Trigger
A
Triggers
DETAIL B
Air filter
Air grille
B
Air filter
17
MAINTENANCE
WARNING: Electric shock hazard can cause injury or death. Before attempting to perform any service or maintenance
on the unit, turn OFF the electrical power, and check that the fan has stopped.
ALWAYS INSTALL THE FILTER
If the unit operates without the filter, there is a risk of damaging the unit through dust contamination.
CLEANING THE AIR FILTER
PLASTIC DIFFUSER PANEL
1.- Stop the unit.
2.- Open the air intake grille on the unit.
Open the grille by way of two hand triggers. The grille will swing down supported by the stays and the hooks.
3.- Release the air intake grille from de unit.
To release the grille pull it down until the stays can be unlock from the diffuser, then pull it back to an angle greater of 90º and
lift it lightly, finally the grille hooks will come away from the diffuser.
4.- Remove the air filter once the air intake grille has been released
Clean the air filter depending on the operation conditions and working time, (approximately once every 6 months).
Use a vacuum cleaner to clean dust off. If the filter is too dirty, wash it with water and neutral detergent. Dry the filter before
re-fitting.
5.- Replace the filter in the right position.
6.- Close the air intake grille.
MODEL 600x1200
Place the hand triggers on position again.
HOOKS
MODEL
600x600
HOOKS
STAYS
A
AIR
FILTER
DETAIL A
AIR INTAKE
GRILLE
AIR INTAKE GRILLE
STAYS
HAND
TRIGGERS
A
HAND
TRIGGERS
AIR FILTER
METALLIC DIFFUSER PANEL
1.- Stop the unit.
2.- Open the air intake grille on the unit.
Open the grille by way of one hand trigger, which is close to the Lennox brand. The grille will swing down supported by two
screws located on the opposite side of the hand trigger.
3.- Remove the air filter .
The filter can be removed from the grille, pulling up from it.
Clean the air filter depending on the operation conditions and working time, (approximately once every 6 months).
Use a vacuum cleaner to clean dust off. If the filter is too dirty, wash it with water and neutral detergent. Dry the filter before
re-fitting.
4.- Replace the filter in the right position.
5.- Close the air intake grille.
MODEL
GRILLE
Place the hand trigger on position again.
600x1200
MODEL
600x600
GRILLE
B
TRIGGER
B
TRIGGER
DETAIL B
AIR FILTER
18
AIR FILTER
MAINTENANCE
COIL CLEANING
Check the coil and make sure it is not blocked with dust or dirt.
Please clean the coil if it is dirty.
ACCESS TO ELECTRICAL COMPONENTS
Access to terminal plate
The terminal plate can be accessed by removing the air intake grille and unscrewing the terminal cover.
PLASTIC DIFFUSER PANEL
MODEL 600x600
MODEL 600x1200
TERMINAL
PLATE
COVER
TERMINAL
PLATE
COVER
METALLIC DIFFUSER PANEL
MODEL 600x600
MODEL 600x1200
TERMINAL PLATE
COVER
TERMINAL PLATE
COVER
Access to electrical panel
To gain access to the electrical panel follow these instructions:
1.- Disassemble the diffuser panel by removing the screws that attaches it to the unit.
2.- Remove the cover of the electrical panel, where is the PCB, (depending on version).
3.- The PCB can be checked or replaced, by loosening the screws that hold it.
MODEL 600x600
MODEL 600x1200
ELECTRICAL PANEL
COVER
ELECTRICAL PANEL
COVER
19
MAINTENANCE
WARNING: Electric shock hazard can cause injury or death. Before attempting to perform any service or maintenance
on the unit, turn OFF the electrical power, and check that the fan has stopped.
ACCESS TO INTERNAL COMPONENTS
When checking or replacing any internal component of the unit, e.g. coil, fan motor, condensate pump, float switch, the drip
tray and volute must be removed.
DISASSEMBLING DRIP TRAY
• Remove the air intake grille and filter.
• Disassemble the diffuser panel by removing the screws that attach it to the unit.
• Detach the volute/s by removing the screws, and the electrical panel cover/s.
• The drip tray can be taken apart by removing its screws, as shown in the figure.
MODEL
600x600
MODEL
600x1200
1
2
1
2
1
Coil
Fan motor
3 Condensate pump
4 Float switch (in option)
2
4
3
Volute
4
3
Drip tray
Volute
Drip tray
AIR DISTRIBUTION
Louvres change position to distribute air according to heating or cooling
operation (only for plastic diffuser).
• In cooling operation the louvres are positioned to distribute air
outwards from the discharge, which allow airflow close to the ceiling.
• In heating mode the louvres are repositioned to blow air in a
downward direction. The air should flow towards to the floor to prevent
layers or stationary hot air forming in the upper part of the room.
2
1
1 Louvre position for correct air flow in heating
mode.
2 Louvre position for correct air flow in cooling
mode.
When the electro-mechanical thermostat is used, the louvres movement
is manual, louvres should be positioned manually.
FAULT ANALYSIS
PROBLEM
1.- Unit not operating.
2.- Indoor unit fan running too
fast without apparent
speed change.
3.- Condensate overflowing.
ACTION
• Check power is available at unit.
• Check wiring.
• Check remote control is functioning and set properly (if any).
• Check the indoor unit filter is clean.
• Check wiring.
• If problem persists then motor may be faulty.
• Check drip tray for blockage, and condensate drains away.
• Check unit is level.
• Check condensate pump is working.
• Check service drain pipework.
20
NOTES
21
NOTES
22
www.lennoxeurope.com
BELGIUM,
LUXEMBOURG :
CZECH REPUBLIC :
FRANCE :
GERMANY :
IRELAND :
NETHERLANDS :
POLAND :
PORTUGAL :
RUSSIA :
SLOVAKIA :
SPAIN :
UKRAINE :
UNITED KINGDOM :
OTHER COUNTRIES :
COD: MSL102E-0105 03-2005
LENNOX BENELUX N.V./S.A.
www.lennoxbelgium.com
LENNOX JANKA a.s.
www.janka.cz
LENNOX FRANCE
www.lennoxfrance.com
LENNOX DEUTSCHLAND GmbH
www.lennoxdeutschland.com
LENNOX IRELAND
www.lennoxireland.com
LENNOX BENELUX B.V.
www.lennoxbenelux.com
LENNOX POLSKA Sp. z o. o.
www.lennoxpolska.com
LENNOX PORTUGAL Lda.
www.lennoxportugal.com
LENNOX DISTRIBUTION MOSCOW
www.lennoxrussia.com
LENNOX SLOVENSKO s.r.o.
www.lennoxdistribution.com
LENNOX REFAC S.A.
www.lennox-refac.com
LENNOX DISTRIBUTION KIEV
www.lennoxrussia.com
LENNOX UK
www.lennoxuk.com
LENNOX DISTRIBUTION
www.lennoxdistribution.com
Due to Lennox's ongoing commitment to quality, Specifications, Ratings and Dimensions subject to change without notice and without incurring liability.
Improper installation, adjustment, alteration, service or maintenance can cause property damage or personal injury.
Installation and service must be performed by a qualified installer and servicing agency.