P2... Series Pressure Independent Characterized Control Valves™ (PICCV)

P2... Series Pressure Independent Characterized Control Valves™ (PICCV)
P2... Series Pressure Independent Characterized Control Valves™ (PICCV)
Chrome Plated Brass Ball and Brass Stem, NPT Female Ends
Application
The Pressure Independent Characterized Control Valve is typically used in air
handling units on heating and cooling coils, and fan coil unit heating or cooling
coils. Some other common applications include unit ventilators and VAV reheat coils. This valve is suitable for use in a hydronic system with constant or
variable flow.
This valve is designed with MFT functionality which facilitates the use of various
control input.
1”
Rangeability
Differential pressure
Valve accuracy
Weight of valve body
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
200
½” body has two different flow capacities (.50 GPM to 2.5 GPM) (3 GPM to 5.5 GPM)
1” body has two different flow capacities (11 GPM to 16 GPM) (17 GPM to 19 GPM)
Tefzel® and Teflon® are registered trademarks of Dupont
800-543-9038 USA
8
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
LRCB24-3 Heat Pump Only
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
20
20
20
20
20
25
25
25
25
25
25
25
25
25
LRX24-MFT
½
½
½
½
½
½
½
½
½
½
½
¾
¾
¾
¾
¾
¾
¾
¾
¾
1
1
1
1
1
1
1
1
1
LRB(X)24-3
0.03
0.06
0.09
0.13
0.16
0.19
0.22
0.25
0.28
0.32
0.35
0.38
0.41
0.44
0.47
0.50
0.54
0.57
0.60
0.63
0.69
0.76
0.82
0.88
0.95
1.01
1.07
1.14
1.20
Non-Spring
Return
TF24-MFT US
0.5
1
1.5
2
2.5
3
3.5
4
4.5
5
5.5
6
6.5
7
7.5
8
8.5
9
9.5
10
11
12
13
14
15
16
17
18
19
LF24-MFT US
P2050B005
P2050B010
P2050B015
P2050B020
P2050B025
P2050B030
P2050B035
P2050B040
P2050B045
P2050B050
P2050B055
P2075B060
P2075B065
P2075B070
P2075B075
P2075B080
P2075B085
P2075B090
P2075B095
P2075B100
PICCV-25-011
PICCV-25-012
PICCV-25-013
PICCV-25-014
PICCV-25-015
PICCV-25-016
PICCV-25-017
PICCV-25-018
PICCV-25-019
Spring
Return
M40019 - 06/10 - Subject to change. © Belimo Aircontrols (USA), Inc.
¾”
0.5 GPM [.03 l/s], 1 GPM [.06 l/s],
1.50 GPM [0.09 l/s], 2 GPM [.13 l/s],
2.5 GPM (0.16 l/s) , 3 GPM [.19 l/s],
3.5 GPM( 0.22 l/s), 4 GPM [.25 l/s],
4.5 GPM (0.28 l/s), 5 GPM [.32 l/s],
5.5 GPM (0.35 l/s)
6 GPM [0.37 l/s], 6.5 GPM (0.41 l/s),
7 GPM [0.44 l/s], 7.5 GPM (0.47 l/s)
8 GPM [0.50 l/s], 8.5 GPM (0.54 l/s),
9 GPM [0.57 l/s], 9.5 GPM (0.60 l/s)
10 GPM [0.63 l/s]
11 GPM (0.69 l/s), 12 GPM [0.76 l/s],
13 GPM (0.82), 14 GPM [0.88 l/s],
15 GPM (0.95 l/s), 16 GPM [1.01 l/s],
17 GPM (1.07 l/s), 18 GPM [1.14 l/s]
19 GPM (1.20 l/s)
100 : 1
5 to 50 PSI operating range
± 10% combination of manufacturing
tolerances and pressure variations
½” = 2.52 lbs
¾” = 2.52 lbs
1” = 4.98 lbs
Close-off
PSI
Flow rate
½”
DN mm
Regulator components
Spring
Body pressure rating
Media temp. range
Close off pressure
Leakage
forged brass, nickel plated
chrome plated brass
chrome plated brass
Viton
fiberglass reinforced Teflon® PTFE
½” & ¾” Brass
1” TEFZEL®
2 EPDM O-rings, lubricated
½” & ¾” silicone and Nomex
1” polyester reinforced silicone
stainless steel/brass/Delrin 500 AF
stainless steel
600 PSI
0°F to 212°F [-18°C to 100°C]
200 PSI
ANSI Class IV (0.01% of rated valve
capacity at 50 psi differential)
Inches
Packing
Diaphragm
chilled or hot water, 60% glycol
equal percentage
½”, ¾”, 1”
female, NPT
Valve Model
Liter/sec
Technical Data
Service
Flow characteristic
Size
Type of end fitting
Materials
Body
Ball
Stem
Seat O-rings
Seat
Characterizing disc
Suitable Actuators
GPM
Flow Rate
Valve
Nominal
Size
LF24-MFT Actuators, Multi-Function Technology
3.78"
[96]
D128
Dimensions with PICCV
7.64"
[194]
2.28"
[58]
4.49"
[114]
C
D
B
Models
Valve
Nominal Size
DN
In.
[mm]
LF24-MFT US
LF24-MFT-S US w/built-in Aux. Switch
Technical Data
Control
Control signal
Power consumption
running
holding
Transformer sizing
Electrical connection
Overload protection
Input impedance
Feedback
Angle of rotation
Direction of rotation
spring
motor
Position indication
Running time
spring
Ambient temperature
Housing
Agency listings
Noise level
Quality standard
LF24-MFT-S US
Auxiliary switch
MFT
2 to 10 VDC
2.5 W
1W
5 VA (class 2 power source)
3 ft, 18 GA appliance cables
(-S model has 2 cables)
½” conduit connector
electronic throughout 0° to 95° rotation
100k Ω for 2 to 10 VDC (0.1 mA)
500 Ω for 4 to 20mA
750 Ω for PWM
500 Ω for on/off and floating point
2 to 10 VDC, 0.5 mA max
95°
reversible with CW/CCW mounting
switch
reversible with built-in
visual indicator
<40 to 75 sec. (on-off)
100 seconds
<25 sec. @-4°F to +122°F [-20°C to +50°C]
<60 sec. @-22°F [-30°C]
-22° F to 122° F [-30° C to 50° C]
NEMA 2
UL 873, CSA C22.2 No. 24 certified, CE
max. 62 dB(A)
ISO 9001
½”
¾”
after 8/2009
¾”
until 8/2009
1”
A
Dimensions (Inches [mm])
A
B
C
D
E
866-805-7089 CANADA
F
15
4.68 [119] 4.47 [114] 4.05 [103] 2.34 [60] 0.99 [25] 0.99 [25]
20
4.90 [125] 4.94 [126] 4.05 [103] 2.34 [60] 0.99 [25] 0.99 [25]
20
5.35 [133] 5.03 [128] 4.22[107] 2.38 [61] 1.04 [26] 1.30 [34]
25
7.05 [179] 6.85 [174] 4.80 [122] 3.23 [82] 1.60 [41] 1.60 [41]
1 x SPDT, 6A (1.5A) @ 250 VAC, UL Listed,
adjustable 0° to 95° (double insulated)
800-543-9038 USA
32
F
M40019 - 06/10 - Subject to change. © Belimo Aircontrols (USA), Inc.
E
203-791-8396 LATIN AMERICA
LF24-MFT Actuators, Multi-Function Technology
Wiring Diagrams
CAUTION Equipment damage!
Actuators may be connected in parallel if not mechanically mounted to
the same shaft. Power consumption and input impedance must be
observed.
3
Actuators may also be powered by 24 VDC.
4
IN4004 or IN4007 diode (IN4007 supplied, Belimo part number 40155).
5
6
7
During installation, testing, servicing and troubleshooting of this
product, it may be necessary to work with live electrical components. Have a
qualified licensed electrician or other individual who has been properly trained
in handling live electrical components perform these tasks. Failure to follow all
electrical safety precautions when exposed to live electrical components could
result in death or serious injury.
W043
2
WARNING Live Electrical Components!
24 VAC/DC Transformer
Line
Volts
(1)
Common
(2)
Hot
(3)
Y Input
(5)
U Output
Triac A and B can also be contact closures.
Position
Control signal may be pulsed from either the Hot (Source) or
Common (Sink) 24 VAC line.
Position feedback cannot be used with Triac sink controller.
The actuators internal common reference is not compatible.
a
(–)
Feedback VDC (+)
CCW CW
…MFT
The ZG-R01 500 Ω resistor converts the 4 to 20 mA control signal to
2 to 10 VDC, up to 2 actuators may be connected in parallel.
W041
On/Off control
24 VAC Transformer (AC only)
(1)
Line
Volts
7
Position
6
(–)
Feedback VDC (+)
Common
(2)
+ Hot
(3)
Y Input
(5)
U Output
CCW CW
…MFT
M40019 - 06/10 - Subject to change. © Belimo Aircontrols (USA), Inc.
W302
PWM, triac source and sink
W303
Floating Point control
Proportional 2 to 10 or 4 to 20 mA control signal
800-543-9038 USA
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
33
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project