M-system AS4T is a thermocouple alarm featuring dual or quad alarm trip, with field-configurable parameters. It supports a wide range of input types, including thermocouples K, E, J, T, B, R, S, C, N, U, L, and P, and has a temperature range of -272 to 2416°F (-170 to 1324°C), depending on the thermocouple type. The AS4T offers several programmable features, including alarm setpoints, hysteresis, power-saving mode, and output coil behavior at alarm. It also provides indication of process input, memory errors, and out-of-range conditions.
Advertisement
Advertisement
AS4T
INSTRUCTION MANUAL
THERMOCOUPLE ALARM
(dual or quad alarm trip; field-configurable)
BEFORE USE ....
Thank you for choosing M-System. Before use, please check contents of the package you received as outlined below.
If you have any problems or questions with the product, please contact M-System’s Sales Office or representatives.
■ PACKAGE INCLUDES:
Signal conditioner (body + base socket + CJC sensor) ........ (1)
■ MODEL NO.
Confirm Model No. marking on the product to be exactly what you ordered.
■ INSTRUCTION MANUAL
This manual describes necessary points of caution when you use this product, including installation, connection and basic maintenance procedures.
MODEL
AS4T
■ ENVIRONMENT
• Indoor use
• When heavy dust or metal particles are present in the air, install the unit inside proper housing with sufficient ventilation.
• Do not install the unit where it is subjected to continuous vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH in order to ensure adequate life span and operation.
■ WIRING
• Do not install cables (power supply, input and output) close to noise sources (relay drive cable, high frequency line, etc.).
• Do not bind these cables together with those in which noises are present. Do not install them in the same duct.
■ AND ....
• The unit is designed to function as soon as power is supplied, however, a warm up for 10 minutes is required for satisfying complete performance described in the data sheet.
POINTS OF CAUTION
■ INSULATION CLASS
• This unit is provided with the class of basic insulation.
Prior to installation, check that the insulation class of this unit satisfies the system requirements.
■ CONFORMITY WITH LOW VOLTAGE DIRECTIVE OR UL
• This equipment is suitable for use in a Pollution Degree
2 environment and in Installation Category II, with the maximum operating voltage of 300V.
Basic insulation is maintained between signal input, output and power input. Prior to installation, check that the insulation class of this unit satisfies the system requirements.
• Altitude up to 2000 meters
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate clearance and creepage distances are maintained to conform to CE/UL requirements. Failure to observe these requirements may invalidate the CE/UL conformance.
■ CONFORMITY WITH EMC DIRECTIVE
• Insert a noise filter for the power source connected to the unit. Densei-Lambda Noise Filter Model MZS-1206-33 or equivalent is recommended.
• The actual installation environments such as panel configurations, connected devices, connected wires, may affect the protection level of this unit when it is integrated in a panel system. The user may have to review the CE requirements in regard to the whole system and employ additional protective measures to ensure the CE conformity.
■ POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and confirm its operational range as indicated below:
100 – 240V AC rating: 85 – 264V, 47 – 66 Hz, approx. 6VA
(100 – 240V ±10% for UL)
24V DC rating: 24V ±10%, approx. 3.5W
110V DC rating: 85 – 150V, approx. 3.5W (110V ±10% for UL)
■ GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount it, turn off the power supply and input signal for safety.
COMPONENT IDENTIFICATION
Connection Diagram Base Socket
Specifications
Body
CJC
Sensor
INSTALLATION
Detach the yellow clamps located at the top and bottom of the unit to separate the body from the base socket.
■ DIN RAIL MOUNTING
Set the base socket so that its
DIN rail adaptor is at the bottom. Position the upper hook at the rear side of base socket on the DIN rail and push in the lower. When removing the socket, push down the
DIN rail adaptor utilizing a minus screwdriver and pull.
■ WALL MOUNTING
Refer to “EXTERNAL DI-
MENSIONS.”
Clamp
(top & bottom)
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
Shape and size of the base socket are slightly different with various socket types.
EM-1608 Rev.9
P. 1 / 4
AS4T
FRONT VIEW & PROGRAMMING
■ PROGRAMMING PROCEDURE
1) Press ITEM UP or DOWN key until ITEM display indicates
“01”.
2) Press DATA UP or DOWN key and choose “1” or “2” on DATA display.
1 : Only alarm setpoints are modifiable.
2 : All parameters are modifiable.
3) Press ITEM UP or DOWN key until ITEM display shows the
ITEM No. you need to change.
4) Press DATA UP or DOWN key and choose a DATA No. or value you need on DATA display.
5) Repeat above 3 and 4. (Entered data is stored when you move to a new ITEM.)
6) Press ITEM UP or DOWN key until ITEM display indicates
“01”.
7) Press DATA UP or DOWN key and choose “0” on the display.
8) Press ITEM UP or DOWN key until ITEM display indicates “P”.
DATA display shows process input.
(You can now check data setting by choosing ITEM No.)
Note: DO NOT press UP and DOWN keys simultaneously.
*Monitor LEDs
DATA
ALARM
L4
L3
L2
L1
ITEM
ITEM
DATA
DATA Display
ITEM No. Display
DATA UP-DOWN Keys
ITEM No. UP-DOWN Keys
*L3 or L4 does not turn on for dual output type.
ITEM
P
MDF.
CODE
N/A
DATA
-272 – 2416* 1
CONTENTS
Process input display in engineering unit
L1 1, 2 -272 – 2416* 1 L1 alarm setpoint in engineering unit
L2 1, 2 -272 – 2416* 1 L2 alarm setpoint in engineering unit
L3 1, 2 -272 – 2416* 1 L3 alarm setpoint in engineering unit * 2
L4 1, 2 -272 – 2416* 1 L4 alarm setpoint in engineering unit * 2
01
02 N/A
0, 1, 2
00 – 99
Modification code
0 : Data indication only.
1 : Only ITEM L1 – L4 are modifiable.
2 : All parameters are modifiable.
Status indication (“0” is normally indicated.)
0: Normal 1: Memory error 10: Out of input range -15 – 115%
DEFAULT SETTING
---- * 1
Quad: 20.0 Dual: 20.0 * 1
Quad: 30.0 Dual: 80.0 * 1
Quad: 70.0 * 1
Quad: 80.0 * 1
1
03 N/A
04 2
05
06
07
08
09
10
2
2
2
2
2
2
11
12
13
14
15
2
2
2
2
2
16 N/A
17
18
19
20
21
22
23
2
2
2
2
2
2
2
3
0 – 99
0 – 99
0, 1, 2, 3, 4
0, 1
0, 1
0, 1
0, 1
Input type
Power ON-delay time (seconds)
Alarm ON-delay time (seconds)
Moving average (sampling cycle: 100 msec.)
0: No, 1: 4 samples, 2: 8 samples, 3: 16 samples, 4: 32 samples
L1 trip operation
L2 trip operation
L3 trip operation
L4 trip operation
(0: Lo, 1: Hi)
(0: Lo, 1: Hi)
(0: Lo, 1: Hi) * 2
(0: Lo, 1: Hi) * 2
5
0
0
-1, 0, 1 – 60 Power-saving mode
-1 : Continuous display upon startup
0 : Continuous display after the last access
1 – 60: Time before display turned off (minutes)
0, 1
0, 1
0, 1
0, 1
----
L1 coil at alarm
L2 coil at alarm
L3 coil at alarm
L4 coil at alarm
Version No. indication
10
(0: Energized, 1: De-energized)
(0: Energized, 1: De-energized)
(0: Energized, 1: De-energized) * 2 0
(0: Energized, 1: De-energized) * 2
0
0
0
----
Quad: 0
Quad: 0
Quad: 1
Quad: 1
0.0 – 2416
0.0 – 2416
0.0 – 2416
0.0 – 2416
0, 1
L1 hysteresis (deadband) in engineering unit
L2 hysteresis (deadband) in engineering unit
L3 hysteresis (deadband) in engineering unit
L4 hysteresis (deadband) in engineering unit
Burnout (0: Downscale, 1: Upscale)
-272 – 2416* 1 Upper range temperature limit
Display flashing with higher temperature
-272 – 2416* 1 Lower range temperature limit
Display flashing with lower temperature
24
25
2
2
0, 1, 2
0 – 12
Temperature unit
Thermocouple type
(0: °C, 1: °F, 2: K)
0: (PR), 1: K (CA), 2: E (CRC), 3: J (IC), 4: T (CC), 5: B (RH)
6: R, 7: S, 8: C (WRe 5-26), 9: N, 10: U, 11: L, 12: P (Platinel II)
*1. According to the temperature unit specified in ITEM 24
*2. Quad alarm trip type only
Dual: 0
Dual: 1
1.0
1.0
1.0
1.0
1
999.9* 1
PV flashing at upscale burnout
-100.0* 1
PV flashing at downscale burnout
0
1 (K or CA)
EM-1608 Rev.9
P. 2 / 4
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on top of the unit.
Attach the CJC sensor together with input wiring to the input terminals. The CJC sensor is not interchangeable.
Check that its serial number is the same as that of the unit.
■ N.C. RELAY ■ N.O. RELAY comp. leadwire
T / C
+
+
– metal leg
CJC
SENSOR
–
5
6
4 model: CJM
11 L4 OUTPUT
10 L1 OUTPUT
9 COM
3 L3 OUTPUT
2 L2 OUTPUT
1 COM
7 U(+)
8 V(–)
POWER
11 L4 OUTPUT
10 L1 OUTPUT
9 COM
3 L3 OUTPUT
2 L2 OUTPUT
1 COM
■ SPDT RELAY comp. leadwire
T / C
+
+
5
– metal leg
CJC
SENSOR
–
6
4
11 N.C.
10 N.O.
9 COM
3 N.C.
2 N.O.
1 COM
7 U(+)
8 V(–)
L1 OUTPUT
L2 OUTPUT
POWER
AS4T
CHECKING
1) Terminal wiring: Check that all cables are correctly connected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
7 – 8 with a multimeter.
3) Input: Check across the terminals 5 – 6 with a sensitive voltmeter to show a normal emf voltage value.
If the thermocouple or its extension wires are broken, the
PV display indicates the upper range temperature limit and flashes (the lower range limit with downscale) due to burnout function. Check leadwires in such a case.
4) Alarm operations: Check the alarm operations referring to the figure below.
5) Output load: Check that the output load is 380V AC/120VA or 125V DC/30W (380V AC/600VA or 125V DC/150W for dual alarm, Output Code 5) at the maximum. For maximum relay life with inductive load, external protection is recommended.
Alarm Trip Operation
Terminal No. in parentheses
Example with quad N.O. contacts (LL, L, H, HH)
L1 (9–10)
L2 (1–2)
L3 (1–3)
L4 (9–11)
Input
(%) 0
ON OFF
ON OFF
OFF ON
OFF
LL L
50
H
Trip Operation in Power Failure
• Output code 2: All relays turn off.
• Output code 3: All relays turn on.
• Output code 5: Terminals 1 – 3, 9 – 11 turn on.
HH
ON
100
EM-1608 Rev.9
P. 3 / 4
MAINTENANCE
Regular calibration procedure is explained below:
■ CALIBRATION
Warm up the unit for at least 10 minutes.
• H (HH) Setpoint
Increase the input signal from a value lower than the setpoint and check that the relay trips at the H (or HH) setpoint within the setpoint accuracy described in the data sheet.
• L (LL) Setpoint
Decrease the input signal from a value higher than the setpoint and check that the relay trips at the L (or LL) setpoint within the setpoint accuracy described in the data sheet.
When the setpoints are shifted, please contact M-System’s
Sales Office or representatives.
AS4T
LIGHTNING SURGE PROTECTION
In order to protect the unit from lightning surges entering through power supply cables, use of appropriate lightning surge protectors are recommended. Please contact M-System.
EXTERNAL DIMENSIONS unit: mm (inch)
CLAMP
(top & bottom)
20 (.79)
DIN RAIL
35mm wide
8 7
7.8 (.31)
6 5
4
50 (1.97) 103 (4.06)
132 (5.20)
2–4.5 (.18) dia.
MTG HOLE
25 (.98) deep
11–M3.5
SCREW
[3.3 (.13)]
9
10 11
40 (1.57)
50 (1.97)
3
1 2
• When mounting, no extra space is needed between units.
■ TERMINAL ASSIGNMENTS
CJC SENSOR
(model: CJM)
8 7 6 5
4
9
10 11
3
1 2
M-SYSTEM WARRANTY
M-System warrants such new M-System product which it manufactures to be free from defects in materials and workmanship during the 36-month period following the date that such product was originally purchased if such product has been used under normal operating conditions and properly maintained, M-System’s sole liability, and purchaser’s exclusive remedies, under this warranty are, at M-System’s option, the repair, replacement or refund of the purchase price of any M-System product which is defective under the terms of this warranty. To submit a claim under this warranty, the purchaser must return, at its expense, the defective M-System product to the below address together with a copy of its original sales invoice.
THIS IS THE ONLY WARRANTY APPLICABLE TO M-SYSTEM PRODUCT AND IS IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING ANY IMPLIED
WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. M-SYSTEM SHALL HAVE NO LIABILITY FOR CONSEQUENTIAL, INCIDENTAL OR
SPECIAL DAMAGES OF ANY KIND WHATSOEVER.
M-System Co., Ltd., 5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN, Phone: (06) 6659-8201, Fax: (06) 6659-8510, E-mail: [email protected]
EM-1608 Rev.9
P. 4 / 4