6185
Loop-powered isolator
6185
– 1-, 2- and 4-channel galvanic isolation
– Slimline channel width of less than 6 mm
– No separate supply necessary
– Low response time
– High noise suppression
Application
• Galvanic separation of analog current signals.
• Elimination of ground loops and measurement of floating
signals.
• A competitive choice in terms of both price and technology for
galvanic isolation of current signals to SCADA systems or
PLC equipment.
• Especially useful in applications necessitating an
unproblematic transmission of current signals according to
NAMUR (sensor error detection).
Connections
Technical characteristics
• PR 6185 is powered by the measured signal and loads the
loop with max. 1.8 VDC.
• The input is protected against overvoltage and polarity error.
• The drop voltage for each channel can be calculated
according to the following expression: Vdrop = 1.8 + (Iout. *
Rload.
• The output is voltage-limited to 15 VDC.
• Inputs and outputs are floating and galvanically separated.
Mounting / installation
• Mounted vertically or horizontally on a DIN rail. As the devices
can be mounted without distance between neighboring units,
up to 168 channels can be mounted per meter.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Output specifications
-20°C to +60°C
20...28°C
< 95% RH (non-cond.)
IP20
Mechanical specifications
Dimensions (HxWxD)..................................... 109 x 23.5 x 104 mm
Weight approx................................................ 155 / 180 / 230 g (1 / 2 / 4
channels)
DIN rail type................................................... DIN 46277
Wire size........................................................ 1 x 2.5 mm2 stranded wire
Screw terminal torque.................................... 0.5 Nm
Common specifications
Isolation voltage
Test voltage.................................................... 2 kVAC
Current output
Signal range...................................................
Min. signal range............................................
Load (@ current output).................................
Load stability..................................................
Current limit....................................................
0...23 mA
1:1
≤ 600 Ω
< 0.03% of span / 100 Ω
50 mA
Voltage limit.................................................... 15 VDC
*of span.......................................................... = of the presently selected
range
Observed authority requirements
EMC............................................................... 2014/30/EU
Approvals
EAC................................................................ TR-CU 020/2011
Response time
Response time (0...90%, 100...10%)............. < 4 ms
Internal consumption, per
channel........................................................... 40 mW
Voltage drop................................................... < 1.8 VDC, min.
Voltage drop................................................... 1.8 V + (Iout.*Rload), max.
Signal / noise ratio......................................... Min. 60 dB (0...100 kHz)
Accuracy........................................................ Better than 0.1% of selected
range
EMC immunity influence................................ < ±0.5% of span
Input specifications
Current input
Measurement range....................................... 0...23 mA
Input resistance.............................................. ≈ 90 Ω + Rload (@ 20 mA)
6185-042016