COND_W1W3-sw054
CONDUCTOR W1/W3
TM
Technical Manual
Updated: 2012-11-19
SW version < 0.54
Contents
Contents
Introduction and Safety ...................................... 5
About this Manual................................................... 5
Product Design Changes.......................................... 5
Safety Precautions................................................... 5
Technical Description .......................................... 7
About Conductor W1/W3....................................... 7
Controller and Room Unit (thermostat).................... 7
Installation Examples..............................................10
Operating Mode.....................................................11
Operating Modes...................................................13
Functions................................................................14
Technical Data RE Controller...................................16
Technical Data RU room unit..................................17
Installation........................................................ 19
Ordering, Delivery and Electrical Installation............19
Preparations...........................................................20
Step 1, To Mount the Controller..............................21
Step 2, To Connect the Units..................................23
Step 3, Commissioning...........................................24
Step 4, To Install the Room Unit (thermostat)..........26
The Menus of the Room Unit RU (thermostat).... 27
The Main Image and the Key Pad of the RU............27
Overview of the Menu System of the RU................29
Navigating in the Menus of the Room Unit............ 30
Changes in the Main Image....................................31
Changes and Settings in the Service Menu.............32
Service.............................................................. 41
Parameters.............................................................41
System Parameters.................................................41
Application Parameters
W1.........................................................................43
W3.........................................................................45
Indications on the Controller...................................49
Troubleshooting.................................................... 50
ModBus Register W1..............................................52
ModBus Register W3 ............................................ 58
3
Contents
4
Introduction and Safety
Introduction and safety
About this manual
This manual is intended for use by the members of the staff who are
responsible for maintenance of the climate system and it contains the
following information:
• Technical description of the CONDUCTOR W1/W3 controller.
• Installing and commissioning the CONDUCTOR W1/W3 controller .
• Instructions on how the various settings should be entered in the room
unit (thermostat).
The Service section is intended for personnel who are specially trained by
Swegon.
Product design changes
Swegon reserves the right to change the specifications in the manual and
change the design of the product without notice.
Safety precautions
Responsibility
It is the responsibility of the user to do the following:
• Assess all the risks involved in the activities which are related to this
manual.
• Make sure that all necessary safety precautions are made before
starting the activities which are related to this manual.
Safety levels
The following levels of safety warnings are used in this manual:
WARNING:
Used when there is risk of damage to persons or
equipment.
N.B.!
Used to point out important information.
1:5
Introduction and Safety
1:6
Technical Description
Technical Description
About Conductor W1/W3
CONDUCTOR W1/W3 is a controller application in the CONDUCTOR series.
The W designation indicates that the application is applicable to waterborne climate systems.
CONDUCTOR is a control system for the individual control of room
temperature and airflow (W3)., especially adapted for partitioned offices
and hotel rooms. It can operate independently or in combination with a
central system.
Controller and Room Unit (thermostat)
The main components in the CONDUCTOR W1/W3 control system are a
controller and a room unit (thermostat).
Controller
4
3
5
6
2
7
8
1
Figur 1. Overview of the Controller.
Pos 1. Product marking.
Pos 2. Termination resistance.
Pos 3. Modbus RTU units.
Pos 4. Inputs: Wiring terminals for the connection of sensors.
Pos 5. DIP switch for ModBUS RTU.
Pos 6. LED, indicates the status of the controller.
Pos 7. Input and output for signal to external relay.
Pos 8. Outputs: Wiring terminals for the connection of valve and damper actuators.
2:7
Technical Description
The controller is equipped with inputs for connection of a condensation
sensor, carbon dioxide sensor, window switch, presence detector and
outputs for the connection of actuators for valves and air dampers.
Up to twelve pairs of actuators (twelve for cooling + twelve for heating) can
be wired to each controller. Or you can connect up to four complete units
per controller for controlling both the airflow (supply air and central extract
air, 5 damper actuators) and cooling and heating (cooling and heating
circuit, valve actuators).
The controller provides proportional and integral (PI) control. Through
so-called PWM control (pulse width modulation), the I section senses both
the size and the duration of the control deviation and adjusts the actuator
opening time accordingly. It is possible to switch over from PWM control to
0-10 V control, if needed.
The user can easily configure the controller functions and parameters by
means of the room unit (thermostat).
The controller has a built-in communication port that enables connection to
an RS 485 network with ModBus RTU for supervising and override control
via a main control system.
Product Identification Label
The product identification label affixed to the front of the controller,
indicates rated data, the controller ID-number, which you will need when
you install the CONDUCTOR.
1
Conductor RE W1
Modbus
Adress 2
Artnr: 942334001
RF id: 00350
IIIIIIIIIIIIIIIIIIIIIIIIIIIIIII
Figur 2. Product identification label on the controller.
Pos 1. Name of the product.
Pos 2. ModBus RTU address.
Pos 3. Part number.
Pos 4. Controller ID number.
2:8
2
3
4
Technical Description
Room Unit
1
2
3
Figur 3. Overview of the room unit (thermostat).
Pos 1. Display
Pos 2. Keypad.
Pos 3. Temperature sensor.
The room unit is simple to use and has an easy-to-interpret design
that makes it user-friendly. The digital display shows the current preset
temperature and airflow settings.
The function of the room unit is to measure the temperature in the room,
communicate with the controller and to serve as a tool for adjusting the
climate in the room.
The internal communication between the controller and the room unit is
wireless, which makes it easier to find an appropriate spot in the room
where the room unit can be installed.
If requested, the room unit can be wire-connected with a RJ12 cable to the
controller.
2:9
Technical Description
Installation Examples
The illustration below shows a typical arrangement of a complete
installation with the CONDUCTOR W1/W3 control system.
11
10
3
RU
GT
9
24V AC
4
RE
2
8
1
GX
GX
7
GX
6
5
12
11
10
Figur 4. Example of a CONDUCTOR W1/W3 installation.
Item
Quantity
Description
PARASOL 1192-B-HF
1
Comfort module including cooling, heating and
ventilation
2.
CONDUCTOR RE W1/W3
1
Controller
3.
CONDUCTOR RU
1
Room unit
4.
SYST TS-1
1
Transformer
5.
SYST CG
1
Condensation sensor
6.
DETECT Occupancy
1
Presence detector
7.
External
1
Window contact, not supplied by Swegon (W3)
8.
LUNA a AT-2
2
Valve actuator
9.
SYST VD 115-CLC
2
Control valve
10.
SYST CRTc 9-125-2 CM 24
1
Supply air damper 1 including motor (W3)
Extract air damper 1 including motor (W3)
11.
CLA 125-500
1
Sound attenuator
12.
Extract air register
1
Extract air register with given C-Factor
SYST MS
4
Assembly part for suspending the PARASOL
Not necessary if the product is mounted directly
against the ceiling.
Accessories
2 : 10
Component
1.
Technical Description
Operating Mode
Applications
These instructions deal with two different applications: W1 and W3. W
indicates that both the applications are applicable to waterborne climate
systems.
A waterborne system provides the room with waterborne heating and
cooling. The air-based systems which can be controlled in the W3 by means
of connected damper actuators are only used to satisfy the demands on
air quality, while the temperature of the supply air and extract air is kept
constant.
Depending on the status of connected sensors, the controller adjusts the
outputs from any of several possible operating conditions. The various
operating conditions described here are based on occupancy in the room
and the status of the window switch and condensation sensor.
W1
W1 is a standard solution for offi ces, mainly designed for partitioned offi
ces, but which also can be used in large rooms, as with open-plan offi ces.
The application is suitable for so called CAV systems (Constant Air Volume),
which means that the airfl ow in the room is constant and that no damper
actuators are needed. Only two outputs are used, one for actuators that
control cooling and one for actuators that control heating. There is provision
for connecting a condensation sensor, a temperature sensor and an
presence detection sensor.
Table 1. Operating conditions for application W1
Condensation
Cooling
Heating
Yes
Off
Normal
No
Normal
Normal
2 : 11
Technical Description
W3
The W3-application can be used either for offi ces or for hotel rooms. It is
well-suited for systems with variable airfl ow (VAV) with both supply air and
extract air. Four outputs are used to control heating, cooling, supply and
extract air. The damper motors are adjusted depending on the generated
airfl ow and duct pressure in both the supply and extract air ducts.
Three inputs are used; for condensation sensors, window switches and
presence detectors. The principle is to use minimal, normal or high airfl ow,
depending on occupancy and sensor status.
Table 3: Operating conditions for application W3
2 : 12
Occupancy Window Condensation
Cooling Heating
Supply Extract
air
air
Yes
Yes
Yes
Off
Frost protection Min.
Min.
Yes
Yes
No
Off
Frost protection Min.
Min.
Yes
No
Yes
Off
Normal
Max.
Max.
Yes
No
No
Normal
Normal
Normal
Normal
No
Yes
Yes
Off
Frost protection Min.
Min.
No
Yes
No
Off
Frost protection Min.
Min.
No
No
Yes
Off
Normal/Energy
saving
Min.
Min.
No
No
No
Normal
Normal/Energy
saving
Min.
Min.
Technical Description
Operating Modes
There are a variety of functions built into the CONDUCTOR:
• MAN, manual mode.
• AUTO, automatic mode.
• ECON, energy-saving mode.
• Stand-by mode.
• EMERG, emergency mode.
MAN, Manual operating mode.
Whenever the CONDUCTOR registers occupancy in the room in response
to signals from a presence detector, the user can regulate the temperature
and airflow rate by entering settings in the room unit. When the user enters
a new desired setting, the controller switches over to the manual operating
mode (MAN).
AUTO, Automatic operating mode.
When the CONDUCTOR no longer registers occupancy in the room, the
controller automatically decreases the supply air flow to the low airflow
setting and the system automatically returns to the AUTO mode.
The controller also switches automatically to the AUTO mode after a
predefined number of minutes after the most recent change, manually
entered on the room unit.
When the controller is set to the automatic mode, the valve actuators for
chilled water and hot water respectively and the supply air damper and
extract air damper respectively are adjusted in response to occupancy in the
room and the level of carbon dioxide as well as the status of the window
contact and the condensation sensor.
The automatic control system controls the airflow, cooling and heating until
the user manually enters a new airflow or temperature setting.
ECON, energy-saving mode.
When the energy-saving function is enabled, the system switches
automatically to the ECON energy-saving mode, when no occupancy has
been registered for a predefined number of minutes. The system returns to
the AUTO mode when occupancy is registered again.
In the energy-save mode, the valve actuator is controlled for chilled water
and hot water respectively according to the status on other sensors in the
room, but with a greater permissible difference between actual value and
setpoint than in the AUTO mode.
2 : 13
Technical Description
Stand-by mode.
When the control system registers a signal indicating that a window is open,
the controller switches over to the standby mode. When the window is
closed, the controller switches to the AUTO operating mode.
While the controller is in the Stand-by mode, the room temperature is
maintained above the predefined level for the Frost protection function.
EMERG, emergency mode.
In the event of a fire alarm, the air damper in the extract air duct is opened
or closed, depending on the setting entered in the control system. The
cooling and heating functions are shut off while the system is in the EMERG
mode. The supply air is normally shut off.
The EMERG mode can only be managed in control systems that are
connected to a main control system via ModBus RTU.
Functions
There are a variety of functions built into the CONDUCTOR W1/W3:
• Exercising of valves
• First open
• Frost protection
• Change over
• Night cool
• Time-set setpoint restoration
Exercising of valves
The function involves regularly exercising the water valves by utilising
automated functions in order to prevent them from becoming sluggish or
jamming. During the exercising period, all the valves that are wired to the
controller are opened for a maximum of 6 minutes and are then closed.
The valves for the cooling system are exercised first. Then the valves for the
heating system are exercised.
First open
The function means that the water valves are open when the system is
installed, which makes it easier to fill, pressure test and vent the water
system.
The function will be automatically disabled after the actuator has been
energized for approx. 6 minutes. A clicking noise will be heard when the
valves and the dampers change over to the NC mode (=normally closed)
and the normal control function is enabled.
2 : 14
Technical Description
Frost protection
The function involves the following: Heating operation is started at a
predefined room temperature in order to counteract the risk of damage that
otherwise can arise due to freezing.
Change over
The function involves the use of only one valve actuator which should be
wired to the cooling output terminal. This actuator then controls both the
heating water and the cooling water, which are transported in the same
pipe.
In winter, when heating is required, the valve opens if the water in the pipe
is warmer than the temperature setpoint. If the water is colder, the valve
does not open.
In summer, when cooling is required, the valve opens if the water in the pipe
is colder than the temperature setpoint.
In order to be able to use this function, you are required to mount an
external temperature sensor onto the water pipe through which supply
water circulates continuously. Wire the sensor according to the general
wiring diagram shown in the section entitled: Installation
Night cool
The function involves using cold air from outdoors for cooling the room at
night to the predefined level.
The function can only be managed in control systems that are connected to
a main control system via ModBus RTU.
Time-set setpoint restoration
The function involves adjusting the room temperature to the predefined
level when the controller switches to the AUTO operating mode.
The controller also switches automatically to the AUTO mode after a
predefined number of minutes after the most recent change, manually
entered on the room unit.
2 : 15
Technical Description
Technical Data
CONDUCTOR RE Controller
Technical data applicable to the CONDUCTOR RE controller (W1/W3) is
specified below.
Item
Data
Designation
CONDUCTOR RE (W1/W3)
Storage temperature
-40 °C to +80 °C
Operating temperature
-20 °C to +50 °C
Degree of protection
IP 32
Dimensions
121 x 193 x 44 mm
Supply voltage
24V AC ± 10%
Power consumption
1 VA
Control function
PI
P-band, cooling/heating
increments
1K
Dead band, occupancy in
room
Depends on switching in cooling and switching in
heating
Dead band, no occupancy
Depends on switching in cooling and switching in
heating
Frost protection
10 °C
Valve installation
1 time/48h period (fully open for 3 minutes)
Installation
Mounting holes in enclosure or onto DIN rail
Connections
Wiring terminal for 2.5 mm² multicore cable
Data communication
ModBus RTU
Wireless communication
433 MHz band radio modem with room unit
(thermostat)
Inputs
Condensation sensor
Resistance
Temperature sensor
Resistance
Presence detector
No occupancy/NO/NC (optional), default = NC for
occupancy
Window contact (W3)
No occupancy/NO/NC (optional), default = NC for
closed window
Carbon dioxide sensor
2 - 10 V, or 24 V
Pressure sensor / ModBus RTU
sensor
2 - 10 V / RJ12 cable
Modular contact
RJ12 6-pole for connecting up to the room unit
(thermostat)
RJ12 6-pole for connecting up to ModBus RTU
Outputs
2 : 16
Actuator, heating
24 V AC, PWM (on/off or 0 - 10 V) max load: 72
VA = 12 actuators
Actuator, cooling
24 V AC, PWM (on/off or 0 - 10 V) max load: 72
VA = 12 actuators
Supply air damper (W3)
0 - 10 V DC (low/normal/high) max load 25 VA =
5 actuators.
Extract air damper (W3)
0 - 10 V DC (low/normal/high) max load 25 VA =
5 actuators.
Technical Description
CONDUCTOR RU room unit (thermostat)
Item
Data
Designation:
CONDUCTOR RU
Storage temperature
-40 °C to +80 °C (*)
Operating temperature
0 °C to +50°C
Degree of protection
IP 20
Dimensions
86 x 100 x 32 mm
Supply voltage
12 V, 4 size AAA batteries
Actual value, range
+10 °C to +32°C
Installation
Against a wall or in a 70 mm standard junction
box. Must not be exposed to direct sunlight
In-operation LED, temperature
Cooling load
Heating load
In-operation LED, air
Low airflow:
One LED lit
Normal airflow:
Two LEDs lit
High airflow:
Three LEDs lit
In-operation LED, enabled
Lit LED, AUTO
In-operation LED, disabled
Dimmed display, AUTO
Input
Modular contact
RJ12 6-pole for connecting up to the controller
(**)
(*) = Specified storage temperature appies to a room unit WITHOUT batteries.
(**) = Used only if wireless communication is not desired.
2 : 17
Technical Description
2 : 18
Installation
Installation
Ordering, delivery and electrical installation
Ordering key, Control equipment
Item
Data
Controller W1/W3
CONDUCTOR RE (aa)
Room unit (Thermostat)
CONDUCTOR RU
Ordering Key, Accessories
Item
Data
Valve
SYST VD 115-CLC
Valve actuator
LUNA a AT-2
Ventilation damper incl.
damper actuator
SYST CRTc 9 (aaa)-2-CM-24
Adapter, actuator/valve
LUNA a T-VA-(aa)
Condensation sensor
SYST CG
Carbon dioxide sensor
DETECT Quality
Presence detector
DETECT Occupancy
Modular cable
RJ12 6/6, 5 metres long
Transformer
SYST TS-1
External temperature sensor
CONDUCTOR T-TG
(aa) = Fitted to valve type:
32
Tour & Andersson
39
Oventrop
50
Honeywell, Reich, MNG, Böhnisch (H), Cazzaniga
54
Certain MMA-valves
59
Danfoss RAV/L
72
Danfoss RAV
78
Danfoss RA
80
Siemens and more (always included in the LUNA a
AT-2 actuator)
(aaa) =
125 or 160
3 : 19
Installation
Ordering
Specify the desired number of ordered components or refer to drawing.
Delivery
•
•
•
The valves are delivered to the plumbing contractor for installation in
the system.
The room controller is delivered to the electrical contractor, systems
contractor or other contractor for installation onto the junction box.
Controller is normally delivered factory fitted on the comfort module
or climate beam. The controller is delivered to electrical contractor,
systems contractor or other contractor for installation by means of
screws at some other suitable place, if separate components are
supplied.
WARNING:
All electrical installation, including wiring the actuators,
valve actuators and various sensors is to be carried out by
the electrical contractor or the systems contractor.
The electrical contractor or the systems contractor provides a 230 V earthed
outlet for transformer, a fitted junction box for the room unit (thermostat)
and possible external cables.
Preparations
The CONDUCTOR W1/W3 should be installed in steps as follows:
1. To mount the controller.
2. To connect units.
3. Commissioning.
4. To mount the room unit (thermostat).
Check the following before installing the CONDUCTOR W1/W3:
• The comfort module, with pre-fitted valve actuators for chilled and hot
water, are mounted in the ceiling.
• The required sensors (e.g. presence detector, window contact and
condensation sensor) are installed in the room.
• Required actuators are installed.
• Cables from all the units are marked and run up to the comfort
module, or alternative location for the controller.
The following are required for installation:
• ordinary screwdriver or electric screwdriver
• Electric drill.
3 : 20
Installation
Step 1, To mount the controller.
Mounting on a DIN rail
If a DIN rail is mounted on the comfort module or at another suitable
location, the controller should be fastened to this rail.
1
2
3
4
Figur 1. To mount the controller.
Pos 1. Plastic hooks
Pos 2. Supporting surface, for example a comfort module or climate beam.
Pos 3. DIN rail
Pos 4. Snap-on fastener.
1. Fasten the two plastic hooks on the backside of the controller on the
upper control edge on the DIN rail.
2. Press to fasten the snap-on fasteners on the backside of the controller
against the lower control edge on the DIN rail.
3 : 21
Installation
To be installed above a false ceiling
If a DIN rail is NOT available pre-mounted or is not available, the controller
can be appropriately mounted above the false ceiling (not on the module).
1
2
Figur 2. To mount the controller.
Pos 1. Supporting surface, NOT for the comfort module or climate beam.
Pos 2. Screws.
1. Secure the controller by means of screws in the upper left-hand and
the lower right-hand corners. Use screws suitable for the supporting
surface.
3 : 22
Installation
Step 2, Installation of units
The following units should be connected to the detachable wiring terminals
of the controller:
6
5
24 V AC
7
4
8
S
3
1
9
2
Figur 3. Overview of the units.
Pos 1. Valve actuator for cooling water.
Pos 2. Valve actuator for heating water
Pos 3. Presence detector.
Pos 4. Window contact. (W3)
Pos 5. Condensation sensor.
Pos 6. External temperature sensor
Pos 7. Transformer.
Pos 8. Damper motor for extract air. (W3)
Pos 9. Damper motor for supply air. (W3)
1.
Connect the valve actuator for cooling water to wiring terminals 27 (blue
cable) and 29 (brown cable) respectively.
2.
Connect the valve actuator for heating water to wiring terminals 30 (blue
cable) and 32 (brown cable) respectively.
3.
Connect the presence sensor to wiring terminals 12 and 26 respectively.
4.
Connect the window contact (normally closed or normally open) to wiring
terminals 10 and 25 respectively.
5.
Connect the wires of the condensation sensor to wiring terminals 17 and 18
respectively.
6.
Connect the wires of the temperature sensor to wiring terminals 30 and 32
respectively.
7.
Connect the secondary side cables of the transformer to wiring terminals 23
(G) and 24 (GO) respectively.
8.
Connect the damper motor for extract air G0 (blue cable) to wiring terminal no.
36. 0-10 V signal (red cable) to no. 37. and 24 V (brown cable) to no. 38.
9.
Connect the damper motor for supply air G0 (blue cable) to wiring terminal no.
33. 0-10 V signal (red cable to no. 34 and 24 V (brown cable) to no. 35.
3 : 23
Installation
Step 3, Commissioning
To connect the mains power supply cable
1. Connect the transformer’s mains power supply cable to an electric
outlet.
To insert batteries in the room unit (thermostat)
The room unit is normally supplied with electric current from four size AAA
batteries.
As an alternative to batteries, the room unit can be energized from the
controller, via a 6-pole cable with RJ12 modular connectors.
N.B.!
If the room unit is energized via a controller, the cable must be
connected at this point.
1
2
3
Figur 4. To insert batteries in the room unit (thermostat).
Pos 1. To open the snap-on fastener.
Pos 2. Remove the back piece.
Pos 3. To insert batteries.
2. Insert the batteries in the room unit (thermostat) as follows:
• Open the snap-on fastener by pressing a screw driver in the notch
between the front piece and back piece of the room unit.
• Press on the snap-on fastener and remove the back piece.
• Insert the batteries with the poles turned according to the relief
markings in the battery compartment.
3 : 24
Installation
Booting
As soon as the controller and the room unit have been energized, the
system boots up and the main view is shown in the display of the room unit.
The controller is in the AUTO operating mode when the system has finished
booting.
Figur 5. Main view in the display of the room unit.
1. Check that the main view is shown in the display.
Selection of Language
On delivery, the room unit has factory-preset English language settings.
2. Change to desired language in accordance with instructions in the
section: Room unit menus.
Check the factory settings
3. Make sure that the current application setting is in agreement with
units connected to the controller. Check in accordance with instructions
in the section: Room unit menus.
To connect units
In order for the controller to be able to properly communicate with the
room unit, they must be connected up to one another.
N.B.!
If the room unit is operated via the controller, you need not
connect it.
4. Connect the controller and the room unit to one another in accordance
with the instructions in section: Room unit menus. The ID or serial
number of the controller should be given as address when connecting
up.
3 : 25
Installation
Step 4, To install the room unit (thermostat)
The room unit contains a temperature sensor used for measuring the current
room temperature. In order for the controller to regulate the temperature in
relation to the preset setting, the room unit must be installed in such a way
that enables it to correctly measure the temperature. The room unit should,
for example, not be exposed to direct sunlight.
2
3
1
Figur 6. To mount the room unit (thermostat).
Pos 1. Front piece.
Pos 2. Back piece.
Pos 3. Screws suitable for the supporting surface.
1. Select a suitable location in the room for installing the room unit. The
recommended height above the floor is standard height for of a light
switch.
2. Remove the back piece from the room unit.
N.B.!
Tighten the back piece only in the right-hand and the left-hand
fastening holes.
3. Then secure the back piece to the wall by means of two countersink
screws, appropriate for the supporting surface.
3 : 26
The menus of the room unit
The menus of the room unit (thermostat)
The main image and the key pad of the room unit
5
6
7
8
4
9
10
3
11
2
12
1
Figur 1. Overview of the main image of the room unit.
Pos 1. Cursor key for moving DOWN.
Pos 2. Cursor key for moving to the LEFT.
Pos 3. Heating/cooling.
Pos 4. Battery charge status/Window status.
Pos 5. Current airflow.
Pos 6. Operating mode.
Pos 7. Current temperature.
Pos 8. Carbon dioxide content.
Pos 9. Occupancy status
Pos 10.Cursor key for moving UP.
Pos 11.Cursor key for moving to the RIGHT.
Pos 12.OK key.
Heating/Cooling
The field shows whether the climate system is heating or cooling.
Symbol for heating.
Symbol for cooling.
Battery charge status/Window status
The field shows the battery level. If a window is open in the room this will
be visible on the screen.
Symbol for fully charged batteries.
Symbol for half charged batteries.
Symbol for empty batteries.
Symbol for an open window.
4 : 27
The menus of the room unit
Current airflow
The field shows the present airflow setting.
Symbol for low airflow.
Symbol for normal airflow.
Symbol for high airflow.
Operating mode
The field shows the current operating mode. The field is empty if the unit is
operating in the manual mode.
AUTO
Automatic.
ECON
Economy.
STOP
Standby.
EMERG
Emergency.
Current temperature
The field shows the current temperature setting. The temperature is
specified in°C.
Level of carbon dioxide
The symbol is shown in the field when the carbon dioxide content in the
room exceeds the pre-defined content.
Symbol for carbon dioxide content.
Occupancy status
The symbol is shown in the field when someone is in the room.
Symbol for occupancy.
4 : 28
The menus of the room unit
Overview over the menu system of the room unit.
The menu system of the room unit consists of the following menus with
associated submenus.
• Main menu
• Service menu
Main menu and Service menu
Main menu
Setup
Enter code
Service menu
Regulator adjust
Settings
Econ SA % 20
Norm SA % 50
Boost SA % 80
ModBUS
Econ EA % 20
Norm EA % 50
Boost EA % 80
RF pair-up
Temp C
Info
General Param.
Appl. Param.
Enter code
Enter code
Room temp
.
Serial Number
Battery Level
Application
Sw. ver. RE
SW. ver. RU
Parameter
P_101
value
2
Parameter
P_1902
ModBus address
Min 0
Max 79
Alarms
values
1
1 or 2 room units
Min 0
Max 2
RF Quality
Language
FirstTime func
Temp. calibration
4 : 29
The menus of the room unit
Navigating in the menus of the room unit
Go to the main menu
Main menu
Setup
..
Select>
<Exit
Figur 2. Main image and Main menu.
1. Press on the OK key while the main image is shown in the display and
hold the key pressed down for 3 seconds.
Go to the Service menu
A authorization code must be entered in order to reach the Service menu.
Main menu
Press code
Setup
1 9 1 9
<Exit
Select>
<Exit
>
Figur 3. The image for selecting Setup and to enter the code.
1. Go to the Main menu.
2. Highlight Setup.
3. Press OK or on the ►Right key.
4. Enter the first digit in the code by pressing the ▲ UP or ▼ DOWN key.
5. Mark the next digit position by pressing the ► Right key.
6. Enter the remaining three digits in the code.
7. Press OK to confirm the code.
If you have entered the correct code, the Service menu will be shown.
Otherwise the Main menu will be shown.
4 : 30
The menus of the room unit
Changes in the Main image
To set the desired room temperature
Figur 4. The Main image
1. Check that the main image is shown in the display.
2. Press on:
• The ▲ UP key to raise the temperature.
• The ▼ DOWN key to lower the temperature.
3. Press OK or wait 3 seconds to confirm the setting.
To set the desired airflow
Figur 5. Main image.
1. Check that the main image is shown in the display.
2. Press on:
• The ► Right key to increase the airflow.
• The ◄ Left key to decrease the airflow.
3. Press OK or wait 3 seconds to confirm the setting.
Low airflow corresponds to the ECON operating mode. Normal airflow
corresponds to th AUTO operating mode. High airflow corresponds to the
BOOST operating mode.
4 : 31
The menus of the room unit
Changes and settings in the Service menu
To set the air damper for supply air and to change the
K-factor
Regulator
adjust
..
Settings
<Exit
......................
Service.. Menu
..
Select>
Econ SA %
Norm SA %
Boost SA %
<Exit
..
OK select
20
50
80
Next>
Figur 6. Image for selecting Regulator adjustment settnings and view for setting the K-factor
and the damper for supply air in air duct 1.
1. Go to the Service menu.
2. Highlight the Regulator adjustment settings.
3. Press OK or on the ►Right key.
4. Highlight the line of the value you want to change by pressing the
▲ UP key or the ▼ DOWN key.
5. Press OK to highlight the value.
6. To change the value:
• K-factor.
• Norm = the value applicable to normal airflow.
• Boost = the value applicable to high airflow.
7. Press OK to confirm the change.
8. Press the ►Right key for advancing further and changing the values of
K-factor and supply air in air duct 2.
9. Press the ◄ Left key twice to return to the Service menu.
4 : 32
The menus of the room unit
Adjust the air damper for extract air and change the
value for offset
Regulator
adjust
..
Settings
<Exit
......................
Service.. Menu
Select>
Econ EA %
Norm EA %
Boost EA %
20
50
80
<Previous
Next>
OK select
Figur 7. Image for selecting Regulator adjustment settings and image for setting the air
damper for extract air and the value for offset.
1. Go to the Service menu.
2. Highlight the Regulator adjustment settings.
3. Press OK or on the ► Right key.
4. Press the ► Right key twice for showing the image for setting the air
damper for extract air and offset.
5. Highlight the line of the value you want to change by pressing the
▲ UP key or the ▼ DOWN key.
6. Press OK to highlight the value.
7. Change to desired value.
8. Press OK to confirm the change.
9. Press the ◄ Left key twice to return to the Service menu.
4 : 33
The menus of the room unit
To set the existing room temperature
Regulator
adjust
..
Settings
<Exit
......................
Service.. Menu
Select>
Temp C
<Prev.
OK select
20
Next>
Figur 8. Image for selecting Regulator adjustment settings and image for setting the existing
room temperature.
1. Go to the Service menu.
2. Highlight the Regulator adjustment settings.
3. Press OK or on the ►Right key.
4. Press the ► Right key three times to show the image for setting the
existing room temperature.
5. Press OK to highlight and to be able to change the room temperature.
6. Change the room temperature by pressing the ▲ UP key or ▼ DOWN
key.
7. Press OK to confirm the change.
8. Press the ◄ Left key four times to return to the Service menu.
4 : 34
The menus of the room unit
Change ModBus address in room unit for RU
ModBUS
RF pair-up
<Exit
ModBUS
..
[First]
......................
Settings
Select>
<Exit
Figur 9. Image for selecting to change the ModBus address and the MB address image.
The unit must be assigned an adress to enable connecting it up to ModBUS,
when the room unit is connected via cable to the controller.
1. Go to the Service menu.
2. Highlight Settings
3. Press OK or on the ►Right key.
4. Highlight ModBus.
5. Press OK.
6. Make one of the following selections:
• Select First whether the room unit is the first one in the room.
• Select Second if the room unit is the second one in the room.
7. Press OK in order to confirm the selection and return to the Service
menu.
4 : 35
The menus of the room unit
Connect units room unit (RU) to controller (RE)
......................
ModBUS
RF pair-up
RF Quality
<Exit
Select>
RF pair-up
0 0 0 0 0
<Exit
>
Figur 10. Image for selecting RF pair-up and the RF pair-up image.
The units must be connected together in order to control the controller by
means of a hand-held micro terminal. This is done by entering the RF (radio
frequency) ID of the controller, which is specified on the identification plate
of the controller.
1. Go to the Service menu.
2. Highlight Settings.
3. Press OK or on the ► Right key.
4. Mark Connect units.
5. Press OK or on the ► Right key.
6. Enter the first digit in the RF ID number by pressing the ▲ UP key or
▼ DOWN key.
7. Highlight the next digit position by pressing the ► Right key.
8. Enter the remaining four digits in the RF ID number.
9. Press OK to confirm the RF ID number and connect the room unit to
the controller.
If the connection is successful, the text: Connected will be shown.
10. Return to the Settings menu by pressing the ◄ Left key.
11. Return to the Service menu by pressing the ◄ Left key.
4 : 36
The menus of the room unit
Test the radio connection
......................
ModBUS
RF pair. up
Language
<Exit
Select>
RF connection
RF pair up: 100
<Exit
Start
Figur 11. Imaage for selecting the RF pair-up and the RF connection image.
If no cable is connected between the controller and the room unit, the two
will communicate with one another via radio signals.
1. Go to the Service menu.
2. Highlight Settings.
3. Press OK or on the ►Right key.
4. Highlight RF pair up
5. Press OK or on the ►Right key.
6. Start the test by the ► Right key.
During the test, 100 messages are sent between the controller and
the room unit. The room unit calculates the number of successful
transmissions and displays them in the image.
• The test can be cancelled by pressing the ► Right key.
7. Press the ◄ Left key when the test is finished to return to the Settings
menu.
8. Return to the Service menu by pressing the ◄Left key.
4 : 37
The menus of the room unit
Change language
......................
..
Language
FirstTime func
Select>
<Exit
Language
.
RF Quality
.
[Swedish]
<Exit
Figur 12. Image for selecting Language and the Language image.
1. Go to the Service menu.
2. Highlight Settings.
3. Press OK or on the ► Right key.
4. To highlight Language.
5. Press OK or on the ► Right key.
6. Select between the languages Swedish, English and Finnish by pressing
the ▲ UP or ▼ DOWN key.
7. Press OK in order to confirm the change and return to the Settings
menu.
8. Return to the Service menu by pressing the ◄ Left key.
To enable/disable the ”first open” function
Language
..
FirstTime func
.
Temp. calibration
<Exit
FirstTime func
......................
..
Select>
[Off]
<Exit
Figur 13. Image for selecting FirstTime function and the FirstTime function function image.
1. Go to the Service menu.
2. Highlight Settings.
3. Press OK or on the ► Right key.
4. Highlight FirstTime function.
5. Press OK or on the ► Right key.
6. Enable the function by selecting [On], disable by selecting [Off].
7. Press OK in order to confirm the selection and return to the Settings
menu.
8. Return to the Service menu by pressing the ◄ Left key.
4 : 38
The menus of the room unit
Calibrate temperature
FirstTime func
Temp. calibration
Select>
<Exit
Temp. calibration
......................
Language
[0,0]
<Exit
Figur 14. Image for selecting calibrate temperature and the Temp. calibration image .
The purpose of the Calibrate temperature action is to ensure that the
temperature reading is in agreement with the actual room temperature.
1. Go to the Service menu.
2. Highlight Settings
3. Press OK or press on the ► Right key..
4. Highlight Temp. calibration.
5. Press OK or on the ► Right key.
6. Change the number of degrees to which the temperature reading
should be adjusted.
• Increase the number of degrees by pressing the ▲ UP key.
• Decrease the number of degrees by pressing the ▼ DOWN key.
7. Press OK to confirm the calibration and return to the Settings menu.
8. Return to the Service menu by pressing the ◄ Left key.
Show system information
<Exit
Select>
Room temp.
RE RF id
Battery Level
.
Info
General Param.
......................
Settings
22,0 C
23456
5.2V
<Exit
Figur 15. Image for selecting Info and the first image in System information.
1. Go to the Service menu.
2. Highlight Info.
3. Press OK or on the ► Right key.
Current information for the application is shown in the System
information images. Navigate between the images by pressing the ▲UP
or ▼ DOWN key.
4. Return to the Service menu by pressing the ◄ Left key.
4 : 39
The menus of the room unit
Change parameters
......................
General param.
Appl. Param.
Alarms
Select>
<Exit
Parameter
Value
P_1902
1
1 or 2 room units
Min 0
Max 2
<Exit
Change>
Figur 16. Image for selecting changes in the application parameters and typical parameter
image.
1. Go to the Service menu.
2. Depending on which parameters you want to change, highlight the
appropriate General parameter or Application parameter.
3. Press OK or on the ► Right key.
4. Enter the authorization code for General parameters or Application
parameters.
5. Select the parameter to be altered by pressing the ▲ UP or ▼ DOWN
key.
6. Highlight the value by pressing the ► Right key.
7. Highlight the value by pressing the ▲ UP or ▼ DOWN key.
8. Press OK to confirm the new value.
9. Press the ◄ Left key to exit the parameter change image.
10. Highlight:
• Yes to save the changes you’ve made.
• No to not to save the changes.
• Cancel to return to parameter change image.
11. Press OK to return to the Service menu.
Show Alarms
Alarms
<Exit
Alarms
......................
General Param.
Appl. Param.
Select>
No alarms
<Exit
Figur 17. Image for selecting Show Alarms and the Alarm image.
1. Go to the Service menu.
2. Highlight Alarms.
3. Press OK or on the ► Right key.
All active alarms are shown in the image.
4. Return to the Service menu by pressing the ◄ Left key.
4 : 40
Service
Service
This section is intended only for use by personnel who are specially trained
by Swegon.
Parameters
In order to control the functions in the CONDUCTOR W4, there are a
number of parameters, which can be changed in order to optimize the
current installation. In the display of the room unit (thermostat) every
parameter is shown in accordance with the figure below.
2
3
P_xxx
xxxxxx
xxxxxx
Max xx
Min xx
5
1
4
Figur 1. Main image in the display of the room unit
Pos 1. Minimal value.
Pos 2. Parameter number.
Pos 3. Factory-preset value
Pos 4. Maximum value.
Pos 5. Parameter text.
System parameters
System parameters are basic parameters which are common for several
applications.
Display image
Description
P_101
set
2
ID
Indicates the ModBus address.
Modbus Address
min
1
max 247
P_102
set
3
BMS Baudrate, 9.6 19.2 38.4
min
1
max 3
P_103
set
2
BMS Parity 0=Od. 1=Ev. 2=None
min
0
max 2
P_104
1
BMS Stop bits
min
1
Indicates the transmission
speed for connecting up to a
Building Management System
(BMS).
1 = 9.6
2 = 19.2
3 = 38.4
Parity setting for connection
to BMS.
0 = Uneven
1 = Even
2 = None
Number of stop bits for
connection to BMS.
1 = 1 bit
2 = 2 bits
max 2
5 : 41
Service
Display image
Description
P_105
Indicates the current type of
controller.
3
Component type, 2=DC, 3=RC
min
2
max 3
P_106
Indicates which application the
controller is set to run.
1 = W3
2 = W1
2
Application type
min
1
max 14
P_107
Indicates the status of the relay
for the EMERG mode.
0 = Open
1 = Closed
2 = No action
1
Relay at emer. 0=Op. 1=Cl. 2=No act.
min
0
max 2
P_108
48
hour
Valve exercise (h) 0=Not used
min
0
max 96
P_109
20
min
Motion timer delay (min)
min
0
max 60
P_110
60
min
Warning delay from start-up (min)
min
0
max 720
P_111
120 min
Warning delay, PI-overload (min)
min
0
max 720
P_112
120 min
Warning delay, Set point (min)
min
0
max 720
P_113
30
min
Warning delay, pressure sensor (min)
min
0
Indicates how often the valves
should be exercised (how many
hours shall pass between two
exercise runs).
max 720
P_114
Indicates the number of
minutes after which the
controller should switch from
AUTO to ECON after the last
occupant has left the room.
Indicates the number of
minutes after which the
controller shall be permitted
to initiate an alarm following a
start up.
Indicates the number of
minutes after which the system
should initiate an alarm for
a +100% or -100% output
signal.
Indicates the number of
minutes after which the system
should initiate an alarm, if the
temperature, flow or pressure
setpoint has not been reached.
Indicates the number of
minutes after which the system
should initiate an alarm if no
signal is received from the
pressure sensor or flow sensor.
Indicates the room number.
0
Room Number (optional)
min
0
max 32000
P_118
0
h
Zero calibration (h) 0=not used
min
0
max 720
P_119
3
Zero calibration wait (min)
min
5 : 42
1
Zero point calibration of the
Modbus-pressure sensor.
Indicates hours between
calibration.
max 6
min
Indicates the delay before the
calibration starts. (The damper
blade should have time to
close)
Service
Application parameters W1
Application parameters are parameter-specific for the selected application.
Display image
Description
P_1101
Indicates how the climate
system should operate for
heating and cooling.
1 = Heating only
2 = Cooling only
3 = Change-over function
4 = Heating/Cooling
4
System1=H,2=C,3=ChOv,4=HC
min
1
max 4
P_1102
Indicates whether one or
two room units are used. If 2
units are used they should be
connected with a cable.
0 = The controllers temp.
sensor is used, 1 = 1 unit
2 = 2 units
1
0=ext.temp, 1 or 2 room units
min
0
max 2
P_1103
10
C
Frost guard temp.
min
5
max 12
P_1104
4
K
Economy neutral zone (K)
min
Indicates at which temperature
the frost protection should
switch in.
0
max 10
P_1105
22
C
Indicates the temperatur zone
in which the controller is
operating in the Economy
mode.
For example: 4 = ±2 K
Indicates the existing room
temperature setting.
Room temperature Setpoint
min
10
max 32
P_1108
1
Economy mode available
min
0
max 1
P_1109
1
ActuatorCool 1=NC, 2=0-10V, 3=NO
min
1
max 3
P_1110
1
ActuatorHeat 1=NC, 2=0-10V, 3=NO
min
1
max 3
P_1111
0
Window 0=NP
min
0
0
Occupancy 0=NP
0
Indicates which sort of valve
actuator is installed in the
cooling water circuit
(1=24V-NC, 2=0-10V, 3=24VNO)
Indicates which sort of valve
actuator is installed in the
heating water circuit..
(1=24V-NC, 2=0-10V, 3=24VNC)
Indicates whether a window
contact is installed and if so
how it is installed.
0 = No contact installed
max 0
P_1112
min
Indicates whether the Economy
mode is available.
0 = No
1 = Yes
Indicates whether a presence
detector is installed and if so
how it is installed.
0 = No contact installed
max 0
5 : 43
Service
Display image
Description
P_1113
5000
P term Change over
min
1
max 10000
P_1114
50
I term Change over
min
1
max 10000
P_1119
16 C
Room unit’s min temperature
min
0
max 20
P_1120
28 C
Room unit’s max temperature
min
25
max 50
P_1121
20 C
Night cool temp set point
min
10
480
RU back to auto state
0
max 1200
P_1123
3500
P term Cooling Scale 1:100
min
1
10
I term Cooling Scale 1:100
1
3500
P term Heating Scale 1:100
1
10
I term Heating Scale 1:100
5 : 44
1
Indicates the temperature
setpoint applicable to the Night
cool function.
Indicates how long after the
most recent manual room
temperature adjustment that
the controller should return to
the AUTO mode.
0 = Not used
Indicates the value for P for
cooling. A high value denotes
faster control. A low value
denotes slower control
Indicates the value for I for
cooling. A high value denotes
faster control. A low value
denotes slower control.
Indicates the value for P for
heating. A high value denotes
faster control. A low value
denotes slower control.
max 10000
P_1126
min
Indicates which highest
temperature is possible to
adjust manually on the room
unit in the MAN operating
mode.
max 10000
P_1125
min
Indicates which lowest
temperature is possible to
adjust manually on the room
unit in the MAN operating
mode.
max 10000
P_1124
min
Indicates the value for I for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.
max 20
P_1122
min
Indicates the value for P for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.
max 10000
Indicates the value for I for
heating. A high value denotes
faster control. A low value
denotes slower control.
Service
Application parameters W3
Application parameters are parameter-specific for the selected application.
Display image
Description
P_1001
Indicates how the climate
system should operate for
heating and cooling.
1 = Heating only
2 = Cooling only
3 = Change-over function
4 = Heating/Cooling
4
System1=H,2=C,3=ChOv,4=HC
min
1
max 4
P_1002
Indicates whether one or
two room units are used..
(0=The controllers temp. sensor
is used, 1=1 unit, 2=2 units If 2
units are used they should be
connected with a cable.
1
0=ext.temp, 1 or 2 room units
min
0
max 2
P_1003
10
C
Frost guard temp.
min
5
max 12
P_1004
4
K
Economy neutral zone, (K)
min
Indicates at which temperature
the frost protection should
switch in.
0
max 10
P_1005
22
Indicates the temperatur zone
in which the controller is
operating in the Economy
mode.
For example: 4 = ±2 K
C
Indicates the existing room
temperature setting.
%
Indicates the supply airflow for
BOOST.
Room temperature Setpoint
min
10
max 32
P_1008
90
Boost flow SA %
min
0
max 1
P_1010
Indicates which blade position
the damper in the supply air
duct should have in event of
fire.
0 = Closed
1 = Open
0
Emergency func SA damper
min
0
max 1
P_1011
10
%
Indicates the supply airflow for
STOP.
%
Indicates the extract airfl ow for
BOOST.
Stand-by flow SA %
min
0
max 100
P_1012
90
Boost flow EA %
min
0
max 100
P_1014
0
Emergency func exhaust damper
min
0
max 1
Indicates whether the damper
in the extract air duct should be
open or closed in the EMERG
mode.
(0=Closed, 1=Open)
5 : 45
Service
Display image
Description
P_1015
10
%
Indicates the extract airflow
for STOP.
%
Indicates the supply airflow for
AUTO.
%
Indicates the extract airflow for
AUTO.
Stand-by flow EA %
min
0
max 100
P_1016
50
Normal flow SA %
min
0
max 100
P_1017
50
Normal flow EA %
min
0
max 100
P_1018
0
mV
Offset voltage for 0% supply
airflow.
(Dissolution=50mV)
mV
Offset voltage for 100% supply
airflow.
(Dissolution=50mV)
mV
Offset voltage for 0% extract
airflow.
(Dissolution=50mV)
mV
Offset voltage for 100% extract
airflow.
(Dissolution=50mV)
SA mV at 0% output
min
0
max 5000
P_1019
10000
SA mV at 100% output
min
5000
max 10000
P_1020
0
EA mV at 0% output
min
0
max 5000
P_1021
10000
EA mV at 100% output
min
5000
max 10000
P_1022
1
Economy mode available?
min
0
P_1023
max 1
1
ActuatorCool 1=NC,2=0-10V,3=NO
min
1
P_1024
max 3
1
ActuatorHeat 1=NC,2=0-10V,3=NO
min
5 : 46
1
Indicates whether the Economy
mode is available.
0 = No
1 = Yes
max 3
Indicates which sort of valve
actuator is installed in the
cooling water circuit.
(1=24V-NC, 2=0-10V, 3=24VNO)
Indicates which sort of valve
actuator is installed in the
heating water circuit.
(1=24V-NC, 2=0-10V, 3=24VNO)
Service
Display image
Description
P_1025
Indicates whether a window
contact is installed and if so
how it is installed.
0 = No contact installed
1 = Normally closed
2 = Normally open
0
Window 0=NP,1=NC,2=NO
min
0
max 2
P_1026
Indicates whether a presence
detector is installed and if so
how it is installed.
0 = No contact installed
1 = Normally closed
2 = Normally open
0
Occupancy 0=NP,1=NC,2=NO
min
0
max 2
P_1027
Indicates the value for P for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.
5000
P term Change over
min
1
max 10000
P_1028
Indicates the value for I for the
Change Over function. A high
value denotes faster control.
A low value denotes slower
control.
50
I term Change over
min
1
max 10000
P_1029
2
Indicates by how much the
room temperature actual value
should rise above the setpoint
in order for the controller to
switch from AUTO to BOOST.
K
Boost at temp. over setpoint (K)
min
1
max 10
P_1034
Indicates whether time-adjusted
fl ow boost is accessible.
(0=No, 1=Yes)
1
Timer function available?
min
0
max 1
P_1035
5
min
Timer function time (min)
min
1
300
P_1038
16
C
The lowest possible room
temperature setpoint for the
MAN operating mode
C
The highest possible room
temperature setpoint for the
MAN operating mode.
Room unit’s min set point
min
0
max 20
P_1039
28
Room unit’s max set point
min
25
max 50
P_1040
10
%
The lowest possible airflow
setpoint for the MAN operating
mode.
%
The highest possible airflow
setpoint for the MAN operating
mode.
Room unit’s min air flow
min
5
max 50
P_1041
100
Room unit's max air flow
min
Indicates how long the timeadjusted fl ow boost should
be on ON when occupancy is
activated
50
max 100
5 : 47
Service
Display image
Description
P_1042
1
K
Boost temp. below setpoint (K)
0
max 10
P_1043
20
Indicates how much the current
room temperature should differ
from the setpoint in order for
the controller to switch from
BOOST to AUTO.
%
Indicates the supply airflow for
ECON.
%
Indicates the extract airflow for
ECON.
Economy flow SA %
min
0
max 100
P_1044
20
Economy flow EA %
min
0
max 100
P_1045
480
min
RU back to auto state
min
0
max 1200
P_1046
18
C
Indicates the temperature
setpoint applicable to the Night
cool function.
%
Indicates the supply airflow for
“night cool”.
Night cool temp set point
min
10
Indicates how long time after
the latest manual adjustment of
room temperature or airfl
ow that the controller should
return to AUTO.
(0=Is not used)
max 20
P_1047
80
Night cool flow SA %
min
50
max 100
P_1048
80
%
Indicates the extract airflow for
“night cool”.
Night cool flow EA %
min
50
max 100
P_1049
5000
P term Cooling Scale 1:100
min
1
max 10000
P_1050
10
I term Cooling Scale 1:100
min
1
5000
P term Heating Scale 1:100
1
10
I term Heating Scale 1:100
5 : 48
1
Indicates the value for P for
heating. A high value denotes
faster control. A low value
denotes slower control.
max 10000
P_1052
min
Indicates the value for I for
cooling. A high value denotes
faster control. A low value
denotes slower control.
max 10000
P_1051
min
Indicates the value for P for
cooling. A high value denotes
faster control. A low value
denotes slower control.
max 10000
Indicates the value for I for
heating. A high value denotes
faster control. A low value
denotes slower control.
Service
Indication on the controller
There are two indicating LEDs on the controller, one on the front (No.1) and
under the lid (No.2). The indications that can be shown, their importance
and their relation to the DIP switches (DIP) is as follows:
No.
1st
2nd
DIP 1 DIP 2 Explanation
Remarks
1.
Green
flashing
for 1
second.
None.
Off.
Off.
Normal operation.
-
2.
Red and
green
flashing.
None.
Off.
Off.
Normal operation, but:
The room unit or
pressure sensor is
missing.
The temperature sensor
in the room unit is
defectiveive.
KTY sensor missing.
-
3.
Red
flashing
for 1
second.
None.
Off.
Off.
External memory error.
AC output signals are
incorrect.
MB-ID = 0 or higher
than 247.
X1 and X2 are “slaves”
and X3 is a “master”.
MB-ID is 1.
Set DIP 1 and DIP 2
to On.
4.
Orange
flashing
for 1
second.
None.
On.
Off.
Service position.
All MB ports are
“slaves”, 38400n1.
Room unit does not
operate in the service
mode.
5.
-
-
Off.
On.
BMS mode.
The mode is
automatically activated
when required.
6.
Light
orange.
Light
orange.
-
-
The controller lacks
bootloader or is in reset.
-
7.
Green.
Green.
-
-
The controller has
bootloader but lacks
software.
MB-ID is same as in the
parameter file.
8.
Orange.
Green.
On.
-
The controller has
bootloader but lacks
software.
MB-ID is forced to 1.
9.
Fast
green
flashing.
Green.
-
-
The parameter file is
being processed.
See to it that the power
supply is maintained.
10.
-
Red.
-
-
The voltage is low
(Supply voltage is <13V).
Safety measure for the
AC output signals. All
signals are Off.
11.
-
Very rapid
green
flashing.
-
-
Radio Frequency
communication.
-
12.
-
Very
rapid red
flashing.
-
-
Further transmission
of MB.
-
5 : 49
Service
Trouble shooting
An alarm is initiated when an error arises in the control system. There are
two types of alarms:
• General alarms.
• Application alarms.
Trouble shooting of the control system should always begin with
investigating whether any alarm has been initiated and if so which.
Certain alarms are automatically reset (Auto) after the cause of the error has
been remedied, while other alarms have to be manually (Man) reset.
If the control system is connected to a ModBus system, the alarms can be
read within the 10100 – 10139 range.
5 : 50
Alarm
No.
Alarm text
Description /
Cause
Remedial
measure
Resetting
0.
No active alarms
No active alarms present.
No measure required.
-
1.
No room unit 1
The controller has not
received any signal from
the room unit 1 within
the given time (P_110).
Make a new
connection – Radio
Frequency mode.
Check the cable.
Auto
2.
No room unit 2
The controller has not
received any signal from
the room unit 2 within
the given time (P_110).
Check the cable.
Auto
3.
No pressure sensor
Pressure sensor is missing
or is defectiveive. Alarm is
initiated after given time
(P_113).
Install or replace the
sensor.
Auto
4.
No supply flow sensor
Flow sensor is missing or
is defectiveive. Alarm is
initiated after given time
(P_113).
Install or replace the
sensor.
Auto
5.
No exhaust flow sensor
Flow sensor is missing or
is defectiveive. Alarm is
initiated after given time
(P_113).
Install or replace the
sensor.
Auto
6.
Room unit 1
temperature
No temperature from
room unit 1.
Change room unit!
Auto
7.
Room unit 2
temperature
No temperature from
room unit 2.
Change room unit!
Auto
8.
Controller KTY short
circuit
KTY sensor defectiveive.
Replace the KTY
sensor.
Auto
9.
Controller KTY open
circuit
KTY sensor missing.
Check connection of
the KTY sensor.
Auto
10.
Room unit low battery
The level on the battery in
the room unit is low.
Replace the batteries
in the room unit!
Auto
11.
PT-controller overload
The output signal has
been +100% or -100%
during given time
(P_111).
Check water the
temperature and the
water flow.
Auto
12.
Set point not reached
Set temperature, set flow
or pressure has not been
reached within given time
(P_112).
Check the water
temperature, the
water flow and the
airflow.
Auto
13.
TBD
-
-
-
14.
TBD
-
-
-
15.
No device list
-
-
-
16.
AC overload
The supply voltage is too
high.
Check the voltage
source.
Auto
17.
System fault
Component error.
Replace the controller!
-
18.
No serial number
Program error.
Replace the controller!
-
Service
Alarm
No.
Alarm text
Description /
Cause
Remedial
measure
Resetting
19.
TBD
-
-
-
20.
Short circuit X11
Connected component is
defectiveive.
Troubleshoot to find
the faulty component
and replace the
component.
Man.
21.
Short circuit X12
Connected component is
defectiveive.
Troubleshoot to find
the faulty component
and replace the
component.
Man.
22.
Short circuit X13
Connected component is
defective.
Troubleshoot to find
the faulty component
and exchange the
component.
Man.
23.
Short circuit X14
Connected component is
defective.
Troubleshoot to find
the faulty component
and exchange the
component.
Man.
24.
SPI flash broken
Component error.
Replace the controller!
Man.
25.
Radio chip broken
Component error.
Replace the controller!
Man.
26.
Parameter file revision
Parameter file is incorrect.
Update with new
parameter file.
Man.
27.
Parameter file format
Parameter file is incorrect.
Update with new
parameter file.
Man.
28.
No Modbus ID
Parameter file is incorrect.
Update with new
parameter file.
Man.
29.
No application
Parameter file is incorrect.
Update with new
parameter file.
Man.
30.
No parameters
Parameter file is incorrect.
Update with new
parameter file.
Man.
31.
Parameter missing
Parameter file is incorrect.
Update with new
parameter file.
Man.
32.
Parameter value error
Parameter file is incorrect.
Update with new
parameter file.
Man.
33.
Parameter file size
Parameter file is incorrect.
Update with new
parameter file.
Man.
34.
Wrong parameter file
Parameter file is incorrect.
Update with new
parameter file.
Man.
35.
Check duct group SM
-
-
-
36.
Check duct group DC
-
-
-
37.
Previous parameters
are lost
Changes in parameter file
has been lost.
To restart the
controller.
Man.
38.
Factory parameters
take up
Changes in parameter file
have not been approved.
To restart the
controller.
Man.
39.
TBD
-
-
-
40.
TBD
-
-
-
41.
No supply pressure
from AHU
-
-
-
42.
No exhaust pressure
from AHU
-
-
-
43.
Supply duct 100%
open
-
-
-
44.
Exhaust duct 100%
open
-
-
-
45.
Low voltage detect
The voltage for the
controller is low.
Check the voltage
source.
Auto
46.
TBD
-
-
-
47.
Duct group member
missing
-
-
-
48.
Negative pressure
-
-
-
5 : 51
Service
Modbus-register W1
The information listed below applies when the CONDUCTOR W1 is connected to a so-called ModBus system.
ModBus-register W1 applies to software before 0.54
Input Status
Discrete Input (1 bit)
Read
only
Modbus
Name
Min/Max
0x0001
Not used
0x0002
Not used
0/1
0x0003
Not used
0/1
0x0004
Not used
0/1
1= clears alarms
0
0x0005
Economy mode
0/1
0=Unavailable, 1= Available
1
0x0006
Not used
0x0007
Not used
Remarks
Default
Remarks
Default
0
0
0
ModBus-register W1 applies to software before 0.54
Input Status
Discrete Input (1 bit)
Read
only
Modbus
Name
Min/Max
1x0001
Condensation
0/1
1x0002
Relay state
0/1
1x0003
Occupancy switch
0/1
1x0004
Window switch
0/1
1x0005
Motion
0/1
1x0006
No active alarms
0/1
ALARM INFO
1x0007
No Room Unit 1
0/1
ALARM, resets automatically
1x0008
No Room Unit 2
0/1
ALARM, resets automatically
1x0009
No Pressure sensor
0/1
ALARM, resets automatically
1x0010
No Supply Flow sensor
0/1
ALARM, resets automatically
1x0011
No Exhaust Flow sensor
0/1
ALARM, resets automatically
1x0012
Room Unit 1 Temperature
0/1
ALARM, resets automatically
1x0013
Room Unit 2 Temperature
0/1
ALARM, resets automatically
1x0014
Regulator KTY short circuit
0/1
ALARM, resets automatically
1x0015
Regulator KTY open circuit
0/1
ALARM, resets automatically
1x0016
Room Unit Low Battery
0/1
ALARM, resets automatically
1x0017
PI-controller overload
0/1
ALARM, resets automatically
1x0018
Setpoint not reached
0/1
ALARM, resets automatically
1x0019
TBD
0/1
ALARM, resets automatically
1x0020
TBD
0/1
ALARM, resets automatically
1x0021
No device list
0/1
ALARM, resets automatically
1x0022
AC overload
0/1
ALARM, resets automatically
1x0023
System fault
0/1
ALARM
1x0024
No serial number
0/1
ALARM
1x0025
TBD
0/1
ALARM
5 : 52
Service
ModBus-register W1 applies to software before 0.54
Holding
register
16 bit integer register
R/W
Modbus
Name
Min/Max
Remarks
1x0026
Short circuit X11
0/1
ALARM, requires HW reset
1x0027
Short circuit X12
0/1
ALARM, requires HW reset
1x0028
Short circuit X13
0/1
ALARM, requires HW reset
1x0029
Short circuit X14
0/1
ALARM, requires HW reset
1x0030
SPI Flash broken
0/1
ALARM, requires HW reset
1x0031
Radio chip broken
0/1
ALARM, requires HW reset
1x0032
Parameter file revision
0/1
ALARM, requires HW reset
1x0033
Parameter file format
0/1
ALARM, requires HW reset
1x0034
No ModBus ID
0/1
ALARM, requires HW reset
1x0035
No Application
0/1
ALARM, requires HW reset
1x0036
No parameters
0/1
ALARM, requires HW reset
1x0037
Parameter missing
0/1
ALARM, requires HW reset
1x0038
Parameter value error
0/1
ALARM, requires HW reset
1x0039
Parameter file size
0/1
ALARM, requires HW reset
1x0040
Wrong parameter file
0/1
ALARM, requires HW reset
1x0041
Check Duct Group SM
0/1
ALARM, resets after right parameters
1x0042
Check Duct Group DC
0/1
ALARM, resets after right parameters
1x0043
Previous parameters are lost
0/1
ALARM, requires HW reset
1x0044
Factory parameters take up
0/1
ALARM, requires HW reset
1x0045
TBD
0/1
ALARM, requires HW reset
1x0046
TBD
0/1
ALARM, requires HW reset
1x0047
No supply pressure from AHU
0/1
ALARM, resets automatically
1x0048
No exhaust pressure from AHU
0/1
ALARM, resets automatically
1x0049
Supply duct 100% open
0/1
ALARM, resets automatically
1x0050
Exhaust duct 100% open
0/1
ALARM, resets automatically
1x0051
Low voltage detect
0/1
ALARM, resets automatically
1x0052
TBD
0/1
ALARM, resets automatically
1x0053
Duct group member missing
0/1
ALARM, resets automatically
1x0054
Negative pressure
0/1
ALARM, resets automatically
Default
5 : 53
Service
ModBus-register W1 applies to software before 0.54
Holding
register
16 bit integer register
R/W
Modbus
Name
Min/Max
Remarks
4x0001
Relay in Emergency
0/1
0=Close, 1=Open, 2=No Action
4x0002
Application transition RO
Read
Only 1/8
1=Normal, 3=Manual, 4=Stand-by,
5=Emergency, 6=NightCool
4x0003
Room number
4x0004
Valve exercise
0/72
Valve exercise 0=Not used (hours)
0
4x0005
Motion Timer
0/20
Motion timer (minutes)
20
Default
4x0006
General warning time
0/60
Warning delay, general (minutes)
1
4x0007
PI-overload warning time
0/60
Warning delay, PI-overload (minutes)
10
4x0008
Set-point warning time
0/60
Warning delay, Set point (minutes)
10
4x0009
Not used
0/60
Warning delay, pressure sensor
(minutes)
1
4x0010
Not used
4x0011
Not used
4x0012
Not used
4x0013
Not used
4x0014
System type
1/4
1= Heat, 2= Cool, 3= Change Over,
4=Heat+Cool
4
4x0015
Number of Room units
1/2
1=One room unit, 2= Two room units
1
4x0016
Window switch
0/2
0=Not used 1=Normaly Closed
2=Normaly Open
0
4x0017
Occupancy switch
0/2
0=Not used 1=Normaly Closed
2=Normaly Open
1
4x0018
Actuator Type Cool
1/2/3
1=24V-NC,2=0-10V, 1=24V-NO
1
1/2/3
1=24V-NC,2=0-10V, 1=24V-NO
1
4x0019
Actuator Type Heat
4x0020
Not used
4x0021
Not used
4x0022
Not used
4x0023
Frost guard temp.
5/15
4x0024
Economy neutral zone
0/10
10
Ex 4=±2 degC
4
4x0025
Room temperature Setpoint
10/32
22
4x0026
Night cool temp set point
10/20
15
4x0027
Not used
4x0028
Not used
4x0029
Room unit's min set point
0/20
only when room unit is manual state
(degC)
16
4x0030
Room unit's max set point
25/50
only when room unit is manual state
(degC)
28
4x0031
Not used
4x0032
Not used
4x0033
Not used
4x0034
Not used
4x0035
RU back to auto state
0/1200
Time when room unit come back from
manual state to auto
480
4x0036
Not used
5 : 54
Service
ModBus-register W1 applies to software before 0.54
Input register
16 bit integer register
Read only
Modbus
Name
Min/Max
Remarks
Default
4x0037
Not used
4x0038
Not used
4x0039
Not used
4x0040
Not used
4x0041
Not used
4x0042
Not used
4x0043
Not used
4x0044
Not used
4x0045
Not used
4x0046
Not used
4x0047
Not used
4x0048
P term Heat
10/10000
Scale 1:100
3500
4x0049
I term Heat
10/10000
Scale 1:100
10
4x0050
P term Cool
10/10000
Scale 1:100
3500
4x0051
I term Cool
10/10000
Scale 1:100
10
4x0052
P term Change over
10/10000
Scale 1:100
5000
4x0053
I term Change over
10/10000
Scale 1:100
50
4x0054
Not used
4x0055
Not used
4x0056
Not used
4x0057
Not used
4x0058
Not used
4x0059
Not used
4x0060
Not used
4x0061
Not used
4x0062
Not used
4x0063
Manual Temp
0-50
(degC) Only used in Manual state
4x0064
Not used
0/100
(%) Only used in Manual state
4x0065
Not used
0/100
(%) Only used in Manual state
4x0066
Not used
4x0067
Not used
4x0068
Not used
4x0069
Copy of Coil Status 1-16
0/65535
"Bit0=0x0001
Bit1=0x0002
Bit2=0x0003
Bit3=0x0004
Bit4=0x0005
…
Bit15=0x0016"
5 : 55
Service
ModBus-register W1 applies to software before 0.54
Input register
16 bit integer register
Read only
Modbus
Name
Min/Max
Remarks
Default
3x0001
Component Name ID
0/10
ID for type of controller in Conductor and
Wise system
00003
3x0002 - 0017
Component Name
0/999
Name built of max 16 chr, exch chr (ASCII
standard)
0
3x0018
Application ID
3x0019
HW Serial No.
3x0020
SW version
3x0021
Not used
3x0022
Application state
0/8
" 0=Init, 1=Auto Normal, 2=Auto Economy,
3=Manual, 4=Stand-by, 5=Emengency
6=NightCool"
3x0023
Not used
3x0024
Not used
3x0025
Time since last boot (Year)
3x0026
Time since last boot (Hours)
0/8760
After 8760h Year is updated
3x0027
Time since last boot (Minutes)
0/60
After 60min Hour is updated
3x0028
Temp sensor regulator
Cels. Scaling 1:10
3x0029
Temp sensor RU1
Cels. Scaling 1:10
3x0030
Temp sensor RU2
Cels. Scaling 1:10
3x0031
Temp set point RU
Celsius
3x0032
Flow set point RU
3x0033
Battery level RU
3x0034
Not used
3x0035
Not used
3x0036
Not used
3x0037
Input Analog 1
0/10000
(mV)
3x0038
Input Analog 2
0/10000
(mV)
3x0039
Input Analog 3
0/10000
(mV)
3x0040
Input Analog 4
0/10000
(mV)
3x0041
Output PWM 1
0/100
(%)
3x0042
Output PWM 2
0/100
(%)
3x0043
Output PWM 3
0/100
(%)
3x0044
Output PWM 4
0/100
(%)
3x0045
Output Analog 1
0/10000
(mV)
3x0046
Output Analog 2
0/10000
(mV)
3x0047
Output Analog 3
0/10000
(mV)
3x0048
Output Analog 4
0/10000
(mV)
3x0049
PID Water Out
-100/100
(%)
3x0050
PID ChangeOver Out
-100/100
(%)
3x0051
Not used
3x0052
Not used
3x0053
Cool Water
0/100
(%)
3x0054
Warm Water
0/100
(%)
3x0055
Not used
3x0056
Not used
5 : 56
Volts. Scaling 1:10
Service
ModBus-register W1 applies to software before 0.54
Coil Status
Discrete Output (1 bit)
R/W
Modbus
Name
Min/Max
3x0057
Not used
3x0058
Not used
3x0059
Not used
3x0060
Room temp
(degC)
3x0061
Change over temp
(degC)
3x0062
Not used
3x0063
Copy of Input Status 1-16
0/65535
"Bit0=0x0001
Bit1=0x0002
Bit2=0x0003
Bit3=0x0004
Bit4=0x0005
…
Bit15=0x0016"
3x0064
Copy of Input Status 17-32
0/65535
"Bit0=0x0017
Bit1=0x0018
…
Bit15=0x0032"
3x0065
Copy of Input Status 33-48
0/65535
"Bit0=0x0033
Bit1=0x0034
..
Bit15=0x0048"
3x0066
Copy of Input Status 49-64
0/65535
"Bit0=0x0049
Bit1=0x0050
..
Bit15=0x0064"
Remarks
Default
5 : 57
Service
Modbus-register W3
ModBus-register W3 applies to software before 0.54
Input
Status
Discrete Input (1 bit)
Read only
Min/Max
Modbus
Name
0x0001
Not used
Remarks
Default
0x0002
SA Emergency action
0/1
0
0x0003
EA Emergency action
0/1
0
0x0004
Not used
0x0005
Economy mode
0/1
0=Unavailable, 1= Available
1
0x0006
Timer Function
0/1
0=Unavailable, 1= Available
1
0x0007
Not used
ModBus-register W3 applies to software before 0.54
Input
Status
Discrete Input (1 bit)
Read only
Modbus
Name
Min/Max
1x0001
Condensation
0/1
1x0002
Relay state
0/1
1x0003
Occupancy switch
0/1
1x0004
Window switch
0/1
1x0005
Motion
0/1
1x0006
No active alarms
0/1
ALARM INFO
1x0007
No Room Unit 1
0/1
ALARM, resets automatically
1x0008
No Room Unit 2
0/1
ALARM, resets automatically
1x0009
No Pressure sensor
0/1
ALARM, resets automatically
1x0010
No Supply Flow sensor
0/1
ALARM, resets automatically
1x0011
No Exhaust Flow sensor
0/1
ALARM, resets automatically
1x0012
Room Unit 1 Temperature
0/1
ALARM, resets automatically
1x0013
Room Unit 2 Temperature
0/1
ALARM, resets automatically
1x0014
Regulator KTY short circuit
0/1
ALARM, resets automatically
1x0015
Regulator KTY open circuit
0/1
ALARM, resets automatically
1x0016
Room Unit Low Battery
0/1
ALARM, resets automatically
1x0017
PI-controller overload
0/1
ALARM, resets automatically
1x0018
Setpoint not reached
0/1
ALARM, resets automatically
1x0019
TBD
0/1
ALARM, resets automatically
1x0020
TBD
0/1
ALARM, resets automatically
1x0021
No device list
0/1
ALARM, resets automatically
1x0022
AC overload
0/1
ALARM, resets automatically
1x0023
System fault
0/1
ALARM
1x0024
No serial number
0/1
ALARM
1x0025
TBD
0/1
ALARM
1x0026
Short circuit X11
0/1
ALARM, requires HW reset
1x0027
Short circuit X12
0/1
ALARM, requires HW reset
1x0028
Short circuit X13
0/1
ALARM, requires HW reset
1x0029
Short circuit X14
0/1
ALARM, requires HW reset
1x0030
SPI Flash broken
0/1
ALARM, requires HW reset
5 : 58
Remarks
Default
Service
ModBus-register W3 applies to software before 0.54
Input Status
Discrete Input (1 bit)
Read only
Modbus
Name
Min/Max
Remarks
1x0031
Radio chip broken
0/1
ALARM, requires HW reset
1x0032
Parameter file revision
0/1
ALARM, requires HW reset
1x0033
Parameter file format
0/1
ALARM, requires HW reset
1x0034
No ModBus ID
0/1
ALARM, requires HW reset
1x0035
No Application
0/1
ALARM, requires HW reset
1x0036
No parameters
0/1
ALARM, requires HW reset
1x0037
Parameter missing
0/1
ALARM, requires HW reset
1x0038
Parameter value error
0/1
ALARM, requires HW reset
1x0039
Parameter file size
0/1
ALARM, requires HW reset
1x0040
Wrong parameter file
0/1
ALARM, requires HW reset
1x0041
Check Duct Group SM
0/1
ALARM, resets after right parameters
1x0042
Check Duct Group DC
0/1
ALARM, resets after right parameters
1x0043
Previous parameters are lost
0/1
ALARM, requires HW reset
1x0044
Factory parameters take up
0/1
ALARM, requires HW reset
1x0045
TBD
0/1
ALARM, requires HW reset
1x0046
TBD
0/1
ALARM, requires HW reset
1x0047
No supply pressure from AHU
0/1
ALARM, resets automatically
1x0048
No exhaust pressure from AHU
0/1
ALARM, resets automatically
1x0049
Supply duct 100% open
0/1
ALARM, resets automatically
1x0050
Exhaust duct 100% open
0/1
ALARM, resets automatically
1x0051
Low voltage detect
0/1
ALARM, resets automatically
1x0052
TBD
0/1
ALARM, resets automatically
1x0053
Duct group member missing
0/1
ALARM, resets automatically
1x0054
Negative pressure
0/1
ALARM, resets automatically
Default
5 : 59
Service
ModBus-register W3 applies to software before 0.54
Holding
register
16 bit integer register
R/W
Modbus
Name
Min/Max
Remarks
4x0001
Relay in Emergency
0/1
0=Close, 1=Open, 2=No Action
4x0002
Application transition RO
Read Only 1/8
"1=Auto Normal, 2=Auto Economy, 3=Auto
boost, 4=Manual, 5=Timer-function
6=Stand-by, 7=Emergency, 8=Night Cool"
4x0003
Room number
4x0004
Valve exercise
0/72
Valve exercise 0=Not used (hours)
Default
0
4x0005
Motion Timer
0/20
Motion timer (minutes)
20
4x0006
General warning time
0/60
Warning delay, general (minutes)
1
4x0007
PI-overload warning time
0/60
Warning delay, PI-overload (minutes)
10
4x0008
Set-point warning time
0/60
Warning delay, Set point (minutes)
10
0/60
Warning delay, pressure sensor (minutes)
1
1/4
1= Heat, 2= Cool, 3= Change Over,
4=Heat+Cool
4
4x0009
Not used
4x0010
Not used
4x0011
Not used
4x0012
Not used
4x0013
Not used
4x0014
System type
4x0015
Number of Room units
1/2
1=One room unit, 2= Two room units
1
4x0016
Window switch
0/2
0=Not used 1=Normaly Closed 2=Normaly
Open
0
4x0017
Occupancy switch
0/2
0=Not used 1=Normaly Closed 2=Normaly
Open
1
4x0018
Actuator Type Cool
1/2/3
1=24V-NC,2=0-10V, 1=24V-NO
1
1/2/3
1=24V-NC,2=0-10V, 1=24V-NO
1
Ex 4=±2 degC
4
4x0019
Actuator Type Heat
4x0020
Not used
4x0021
Not used
4x0022
Not used
4x0023
Frost guard temp.
5/15
4x0024
Economy neutral zone
0/10
10
4x0025
Room temperature
Setpoint
10/32
22
4x0026
Night cool temp set point
10/20
15
4x0027
Timer function time
1/300
4x0028
Not used
(min) Boost time when occupancy occurs in
room
5
4x0029
Room unit's min set point
0/20
only when room unit is manual state (degC)
16
4x0030
Room unit's max set
point
25/50
only when room unit is manual state (degC)
28
4x0031
Room unit's min air flow
5/50
only when room unit is manual state (%)
10
4x0032
Room unit's max air flow
50/100
only when room unit is manual state (%)
100
4x0033
Boost temp. positive
hysteresis
1/10
Room temperature rise from defined setpoint,
Auto Boost activated
2
4x0034
Boost temp. negative
hysteresis
0/10
Room temperature fall from defined setpoint,
Auto Boost activated
1
4x0035
RU back to auto state
0/1200
Time when room unit come back from manual
state to auto
480
4x0036
Normal flow SA
0/100
(%)
50
5 : 60
Service
ModBus-register W3 applies to software before 0.54
Holding
register
16 bit integer register
R/W
Modbus
Name
Min/Max
Remarks
Default
4x0037
Normal flow EA
0/100
(%)
50
4x0038
Economy flow SA
0/100
(%)
20
4x0039
Economy flow EA
0/100
(%)
20
4x0040
Night cool flow SA
50/100
(%)
80
4x0041
Night cool flow EA
50/100
(%)
80
4x0042
Boost flow SA
0/100
(%)
90
0/100
(%)
90
0/100
(%)
10
4x0043
Boost flow EA
4x0044
Not used
4x0045
Not used
4x0046
Stand-by flow EA
4x0047
Stand-by flow EA
0/100
(%)
10
4x0048
P term Heat
10/10000
Scale 1:100
5000
4x0049
I term Heat
10/10000
Scale 1:100
10
4x0050
P term Cool
10/10000
Scale 1:100
5000
4x0051
I term Cool
10/10000
Scale 1:100
10
4x0052
P term Change over
10/10000
Scale 1:100
5000
Scale 1:100
4x0053
I term Change over
10/10000
4x0054
SA 0% value
0/5000
50
0
4x0055
SA 100% value
5000/10000
10000
4x0056
EA 0% value
0/5000
0
5000/10000
10000
4x0057
EA 100% value
4x0058
Not used
4x0059
Not used
4x0060
Not used
4x0061
Not used
4x0062
Not used
4x0063
Manual Temp
0-50
(degC) Only used in Manual state
4x0064
Manual SA flow
0/100
(%) Only used in Manual state
0/100
(%) Only used in Manual state
0/65535
"Bit0=0x0001
Bit1=0x0002
Bit2=0x0003
Bit3=0x0004
Bit4=0x0005
…
Bit15=0x0016"
4x0065
Manual EA flow
4x0066
Not used
4x0067
Not used
4x0068
Not used
4x0069
Copy of Coil Status 1-16
5 : 61
Service
ModBus-register W3 applies to software before 0.54
Input register
16 bit integer register
Read only
Modbus
Name
Min/Max
Remarks
Default
3x0001
Component Name ID
0/10
ID for type of controller in Conductor and
Wise system
00003
3x0002 - 0017
Component Name
0/999
Name built of max 16 chr, exch chr (ASCII
standard)
0
3x0018
Applacation ID
3x0019
HW Serial No.
3x0020
SW version
3x0021
Not used
3x0022
Application state
0/8
"0=Init, 1=Auto Normal, 2=Auto Economy,
3=AutoBoost, 4=Manual, 5=TimerFunction
6=Stand-by, 7=Emergency, 8=NightCool"
3x0023
Not used
3x0024
Not used
3x0025
Time since last boot (Year)
3x0026
Time since last boot (Hours)
0/8760
After 8760h Year is updated
3x0027
Time since last boot (Minutes)
0/60
After 60min Hour is updated
3x0028
Temp sensor regulator
Cels. Scaling 1:10
3x0029
Temp sensor RU1
Cels. Scaling 1:10
3x0030
Temp sensor RU2
Cels. Scaling 1:10
3x0031
Temp set point RU
Celsius
3x0032
Flow set point RU
3x0033
Battery level RU
3x0034
Not used
3x0035
Not used
3x0036
Not used
3x0037
Input Analog 1
0/10000
(mV)
3x0038
Input Analog 2
0/10000
(mV)
3x0039
Input Analog 3
0/10000
(mV)
3x0040
Input Analog 4
0/10000
(mV)
3x0041
Output PWM 1
0/100
(%)
3x0042
Output PWM 2
0/100
(%)
3x0043
Output PWM 3
0/100
(%)
3x0044
Output PWM 4
0/100
(%)
3x0045
Output Analog 1
0/10000
(mV)
3x0046
Output Analog 2
0/10000
(mV)
3x0047
Output Analog 3
0/10000
(mV)
3x0048
Output Analog 4
0/10000
(mV)
3x0049
PID Water Out
-100/100
(%)
3x0050
PID ChangeOver Out
-100/100
(%)
3x0051
Not used
3x0052
Not used
3x0053
Cool Water
0/100
(%)
3x0054
Warm Water
0/100
(%)
3x0055
SA Damper pos.
0/100
(%)
3x0056
EA Damper pos
0/100
(%)
5 : 62
Volts. Scaling 1:10
Service
ModBus-register W3 applies to software before 0.54
Input register
16 bit integer register
Read only
Modbus
Name
Min/Max
3x0057
Not used
3x0058
Not used
3x0059
Not used
3x0060
Room temp
(degC)
3x0061
Change over temp
(degC)
3x0062
Not used
3x0063
Copy of Input Status 1-16
0/65535
"Bit0=0x0001
Bit1=0x0002
Bit2=0x0003
Bit3=0x0004
Bit4=0x0005
…
Bit15=0x0016"
3x0064
Copy of Input Status 17-32
0/65535
"Bit0=0x0017
Bit1=0x0018
…
Bit15=0x0032"
3x0065
Copy of Input Status 33-48
0/65535
"Bit0=0x0033
Bit1=0x0034
..
Bit15=0x0048"
3x0066
Copy of Input Status 49-64
0/65535
"Bit0=0x0049
Bit1=0x0050
..
Bit15=0x0064"
3x0064
Copy of Input Status 17-32
0/65535
”Bit0=0x0017
Bit1=0x0018
…
Bit15=0x0032”
3x0065
Copy of Input Status 33-48
0/65535
”Bit0=0x0033
Bit1=0x0034
..
Bit15=0x0048”
3x0066
Copy of Input Status 49-64
0/65535
”Bit0=0x0049
Bit1=0x0050
..
Bit15=0x0064”
Remarks
Default
5 : 63
Was this manual useful for you? yes no