basicDIM DGC en
luxCONTROL lighting control system
basicDIM
basicDIM DGC
Compact control module
Product description
•Compact dimensions for luminaire installation
•For up to 20 DSI or DALI devices (max. 10 per output channel)
•DALI IN input
•2 DALI/DSI output channels with adjustable offset from
channel 2 to channel 1
•1 relais output
•Sensor input for up to 4 basicDIM DGC sensors 5DPI 14
•2 switch inputs for on/off switching and dimming
•Individual adjustment of the parameters with
basicDIM DGC Programmer or
software masterCONFIGURATOR
•5-year guarantee
È
Wiring diagrams and installation examples, page 9
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
1
luxCONTROL lighting control system
basicDIM
basicDIM DGC
Compact control module
Technical data
Mains frequency
50 / 60 Hz
Power
2.5 W
Stand-by power
0.5 W
Current draw, input (DALI bus)
2 mA
Operating temperature
0 ... +60 °C
Storage temperature
-25 ... +70 °C
Type of protection
IP20
Max. casing temperature tc
70 °C
159
147–150
30
220 – 240 V
21
30
Rated supply voltage
Ordering data
Type
Article number
Mounting
basicDIM DGC
28000920
Luminaire installation 10 pc(s).
Packaging carton
Specific technical data
Type
Inputs
Outputs
CH2 as Link Line
Dimming Max. cable Max. basicDIM Max. sensor Digital control Control output Dimming Maximum
switch length at DGC sensors line length at line DALI/DSI per physical
range cable length
1.5 mm²
0.2 – 1.5 mm²
output (devices)
at 1.5 mm²
basicDIM DGC
double
100 m
4
10 m
2
10
1 – 100 %
100 m
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
Voltage DC
13 V
Output, relay (L‘)
Maximum Number of Max. switching Maximum Max.
cable length combinable output (e.g. apparent switching
at 1.5 mm² modules
LCAI)
power
output
100 m
10
2
200 VA
500 W
2
ACCESSORIES
luxCONTROL lighting control system
basicDIM
basicDIM DGC Sensor 5DPI 14f
Product description
•Light measurement and motion detection
•Up to 4 basicDIM DGC sensors on one basicDIM DGC
•Can be remote controlled
•Light measurement and motion detection can be deactivated
•Individual adjustment of the parameters with basicDIM DGC
Programmer or software masterCONFIGURATOR
•Power supply via basicDIM DGC
no
Detection angle
360°
Light measurement at the sensor head 1
10 – 650 lx
Infra-red control range
5m
Max. mounting height
5m
Operating temperature
0 ... +50 °C
Storage temperature
-25 ... +55 °C
Type of protection
IP20
1 The measured value at the sensor head corresponds to approx. 15 to 2,000 lux on the
44,4
2
4m
Swivel design
12,8
Ø of detection range, mounted at a height of 2.5 m
16,4
Technical data
Ø13,9
1,9
3
surface measured.
Ordering data
Type
Article number
Packaging, carton
basicDIM Sensor 5DPI 14f Luminaire installation
28000933
40 pc(s).
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
3
ACCESSORIES
luxCONTROL lighting control system
basicDIM
basicDIM DGC Sensor 5DPI 14rc
Product description
•Light measurement and motion detection
•Up to 4 basicDIM DGC sensors on one basicDIM DGC
•Can be remote controlled
•Light measurement and motion detection can be deactivated
•Individual adjustment of the parameters with basicDIM DGC
Programmer or software masterCONFIGURATOR
•Power supply via basicDIM DGC
4m
Swivel design
no
Detection angle
360°
Light measurement at the sensor head 1
10 – 650 lx
Infra-red control range
5m
Max. mounting height
5m
Operating temperature
0 ... +50 °C
Storage temperature
-25 ... +55 °C
Type of protection
IP20
5,5
Ø of detection range, mounted at a height of 2.5 m
65,4
Technical data
1 The measured value at the sensor head corresponds to approx. 15 to 2,000 lux on the
surface measured.
Ø46,75
Ø58
128
Ordering data
Type
Article number
Packaging, carton
basicDIM Sensor 5DPI 14rc Ceiling installation
28000934
63 pc(s).
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
4
ACCESSORIES
luxCONTROL lighting control system
basicDIM
basicDIM DGC Programmer
Product description
•Optional infra-red programming unit for basicDIM DGC
•Setting of predefined discrete parameter values
•Programmable functions such as light level, time delay,
P.I.R., bright-out, power up
ACCESSORIES
Ordering data
Type
Article number
Dimensions L x W x H Packaging carton
basicDIM DGC Programmer
28000646
130 x 56 x 15 mm
Type
Article number
Dimensions L x W x H Packaging carton
REMOTECONTROL IR6
28000647
86.5 x 40.5 x 7.2 mm 500 pc(s).
1 pc(s).
REMOTECONTROL IR6
Product description
•Optional infra-red remote control
•Switching on and off (On/Off button)
•Dimming (Up/Down button)
•Activation of automatic lighting control
•Setting the threshold control point (Set button)
Ordering data
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
5
ACCESSORIES
luxCONTROL lighting control system
basicDIM
Strain-relief set
Product description
21
•5-year guarantee
50
234
Ordering data
Type
Article number
Packaging carton
Strain-relief set
28000881
10 pc(s).
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
6
luxCONTROL lighting control system
basicDIM
Standards
EN 55015
EN 61000-3-2
EN 61347-1
EN 61347-2-11
EN 61547
EN 62386-101
EN 60598-1
EN 62493
basicDIM DGC
The basic DIM DGC provides the basis for an easy-to-use and cost-effective
lighting system with motion detection.
When the sensor detects movement it triggers a individual adjustable motion
detection profile in the control unit.
As the amount of natural ambient light changes the illuminance from the
artificial lighting system is adjusted.
The connected luminaires can be switched on and off via momentary-action
switch or remote control possible.
Glow-wire test
according to EN 61347-1 passed.
The DALI IN interface allows integration of the basicDIM DGC module also into a
comfortDIM system.
The basicDIM DGC module has 5 preprogrammed profiles which can be selected
using the basicDIM DGC Programmer.
The profiles can be adjusted to your application via the masterCONFIGURATOR
(≥ V2.12) software.
DALI standard
The basicDIM DGC is designed to control control
gear with DALI standard IEC 60929 (DALI V0) and
IEC 62386 (DALI V1).
If the basicDIM DGC module is used in the basic application, the CH2 can be
used as control channel for controlling subordinate basicDIM DGC modules
(basic connection), so that the controlling and the subordinate basicDIM DGC
modules can be programmed and allocated to groups using the
masterCONFIGURATOR software. Every single basicDIM DGC module can be
allocated to a group and respond to the presence of up to 5 groups
(for more detailed information please refer to the masterCONFIGURATOR
documentation).
Installation
•basicDIM DGC can be operated without sensor.
The motion detection must be disabled via masterCONFIGURATOR or
with unique connecting a sensor and basicDIM DGC Programmer.
•DSI/DALI is not SELV. The installation instructions for mains voltage
therefore apply.
•The maximum cable length between the external switch and
basicDIM DGC is 100 m.
•The maximum cable length between the sensor and
basicDIM DGC is 10 m.
•A synchronous operation of DALI and DSI ballasts at the same
control gear is not possible.
•The output channels (for a cable cross-section of 1.5 mm2)
must not be exceeded 100 m.
•If CH2 is used as link line, the maximum cable length must not
exceed 100 m (at 1.5 mm²).
•If a basicDIM DGC is connected to CH2, DALI IN is disabled and CH2
is used as Link-Line (neighbourhood function). No control commands
are transmitted via CH2, to reactivate DALI IN see basicDIM DGC
manual.
• Any number of push to make switches may be connected in parallel to the
inputs.
•Do not connect standard switches to the input.
•Please ensure that the detection range of the sensor lies in the lighting area of
the controlled luminaires.
• Heaters, fans, printers and copiers located in the detection zone may cause
incorrect presence detection.
• To avoid false readings, the sensor should be installed so there is no direct
light from the lamp in the detection zone.
• Sensor wires must be routed separately from the lamp wires and mains
cables otherwise the lighting control system may malfunction.
If separate routing is not possible (for reasons of space) shielded lamp wires
and mains cables must be used.
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
7
luxCONTROL lighting control system
basicDIM
basicDIM DGC sensor
Light level recognition area
Presence / motion detection
Sensor alignment
x2
Example for light and motion detection
area at height of 1.7 m:
y
x2
y
x1
y
y
1m
x1
y
αx2 = 22°
αx1 = 38°
0.7 m
h
α = 78°
h
αy = 30°
x1
x2
1.3 m
h
22°
38°
y
x2
y
x1
y
Light level
recognation area
d
1m
Presence / motion detection
x2
y
2.8 m
y
x1
x2
y
y
x1
h*
x1
x2
y
d
1.7 m
1.3 m
0.7 m
1.0 m
2.8 m
2.0 m
1.6 m
0.8 m
1.2 m
3.2 m
2.3 m
1.8 m
0.9 m
1.3 m
3.7 m
2.5 m
2.0 m
1.0 m
1.4 m
4.0 m
2.7 m
2.1 m
1.1 m
1.6 m
4.4 m
3.0 m
2.3 m
1.2 m
1.7 m
4.9 m
3.5 m
2.7 m
1.4 m
2.0 m
5.7 m
4.0 m
3.1 m
1.6 m
2.3 m
6.5 m
*
The recommended maximum room height for office applications
is 3 m and for corridor applications for example 4 m.
Up to 2 m mounting height presence is detected and
over 2 m motion is detected.
Calculation of the diameter (light area):
x1 = tan(ax1) × h
x2 = tan(ax2) × h
y = tan(ay) × h
Calculation of the diameter (motion area):
d = 2 × tan(0,5 × a) × h
Mounting variants luminair installation sensor
Size of the sheet: 0.8 – 1.8 mm
Size of the sheet: 0.6 – 0.8 mm
1,5 – 2,5
ø14,1+0,2
0
2,2 +0,2
0
19,1
20 +0,1
-0,1
4 +0,2
0
ø1,8 +0,1
0
0
3,2 -0,15
Size of the sheet: 0.8 – 3.0 mm
3,3 – 5,5
14,1+0,2
0
41,1+0,2
0
R1,9 0-0,2
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
8
luxCONTROL lighting control system
basicDIM
Wiring diagram basicDIM DGC
DALI
L
N
DA
DA
2
3
4
6 DA
7 DA
2
3
4
6 DA
7 DA
Uconverter
LCAI
2
3
4
Uconverter
LCAI
6 DA
7 DA
max. 500 W (L')
L
N
L’
*
T1
T2
max. 10
basicDIM DGC Sensor
max. 4
Uconverter
LCAI
max. 10
eD1
Sensor
eD2
basicDIM DGC
DA
DALI IN
DA
CH1
2
3
4
D1
D2
D1
CH2
D2
6 DA
7 DA
Uconverter
LCAI
max. 64 DGC
* must be the same phase as for L
Relais in standby
L
N
L’
DA
DA
max. 10
basicDIM DGC Sensor
2
3
4
The inrush currents of the control gears
must be taken into account when
dimensioning the contactor.
6 DA
7 DA
max. 4
L
N
L’
*
T1
T2
Uconverter
LCAI
max. 10
eD1
Sensor
eD2
basicDIM DGC
DA
DALI IN
DA
CH1
D1
D2
D1
CH2
D2
2
3
4
6 DA
7 DA
Uconverter
LCAI
max. 64 DGC
* must be the same phase as for L
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
9
luxCONTROL lighting control system
basicDIM
Wiring type and cross-sections for basicDIM DGC
Solid wire with a cable cross-section of 0.5 mm² to 1.5 mm².
DALI IN
The DALI IN interface allows integration of the basicDIM DGC module also into a
comfortDIM or other BMS systems.
However, not all DALI commands are supported. The DALI commands supported
are listed in the operating instructions.
wire preparation:
0.5 – 1.5 mm²
By using the DGC in basic configuration (additional DGC‘s connected to
CH2) DALI IN interface will be deactivated.
8.5 – 9.5 mm
Wiring type and cross section basicDIM Sensor 5DPI 14rc
The wiring can be solid wire or stranded wire with a cross-section of 0.2 mm² to
1.5 mm².
DALI/DSI output channels CH1 - CH2
The output channels can be set to DSI or DALI (default) using the basicDIM DGC
Programmer or the masterCONFIGURATOR software.
wire preparation:
0.2 – 1.5 mm²
7.5 – 8.5 mm
Wiring type and cross section basicDIM Sensor 5DPI 14f
The wiring can be solid wire or stranded wire with a cross-section of 0.2 mm² to
0.5 mm².
After mains failure the basicDIM DGC will set new the following
parameters to CH1/CH2:
POWER ON LEVEL
SYSTEM FAILURE LEVEL
FADE TIME
MIN LEVEL
MAX LEVEL
For more detailed information please refer to the manual.
wire preparation:
0.2 – 0.5 mm²
7.5 – 8.5 mm
Switch
basicDIM DGC has two inputs (T1 and T2) for two external switches. Any number of switches can be connected in parallel to the inputs (parallel connection of
T1 and T2 possible).
Short press (< 500 ms):
ON/OFF
Long press (> 500 ms):
Dim up/down
A change in the light value deactivates lighting regulation only temporarily. As soon as the luminaire has been automatically switched on again (motion detection) or manually switched off and on again, regulation is activated again.
2 x short press:
The overwritten setpoint light value is stored (luminaire acknowledges by flashing twice)
Function is lockable via the DSI programmer
Different output channels are controlled, depending on the profile selected.
Relais
The relay can be used in four different operating modes:
•Reduction of standby losses (standby wiring example)
•Independent output channel for switching non-dimmable luminaires (DALI wiring example)
Depending on the profile used, the relay will respond differently. For the 5 main profiles, the two relay profiles used are Standby and OnlyOFF.
The masterCONFIGURATOR software allows to enable or disable the relay profiles as well.
Standby
Standby
OnlyOFF
Energy saving mode
If the basicDIM DGC module is switched off, the relay will switch off (after 10 minutes).
If the basicDIM DGC is switched on, the relay will switch on.
Switching: relay in standby mode
The relay must be switched on using the momentary-action switch, but is switched off by the presence detector.
Only OFF
Active
The relay is switched on or off via the presence detector.
Inactive
The relay must be switched on and off using the momentary-action switch.
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
10
luxCONTROL lighting control system
basicDIM
Depending on the profile used, different operating modes are preprogrammed
for the presence detector. These can be changed using the basicDIM DGC Programmer or the masterCONFIGURATOR software.
ON
OFF
only
OFF
∞
ON / OFF
The light is switched on and off automatically based
on the presence/absence of people.
Only OFF
The presence detector just switches the connected
luminaires off. The luminaires are switched on manually via the connected external momentary-action
switch or the remote control.
Never
OFF
If no presence is detected, the sensor dims down to
the “second light level” parameter and maintains this
setting.
OFF
Presence detector disabled. The light must be switched on and off manually.
OFF
Manual-off delay
If the light is switched off manually via momentary-action switch or remote
control, the presence detector is disabled. After a period of delay without any
presence detected, the presence detector is enabled again. If the sensor detects
presence during the “Manual Off” delay, the delay time will start all over again.
Lighting control
AUTO
Lighting control is started via the Auto key of the basicDIM Programmer or
REMOTECONTROL IR6.
If the basicDIM DGC module has been switched on via the ON key, lighting control is disabled.
If you want to use lighting control, you need to start the DGC module
via the Auto key.
Run-on time
1 min
10min
20min
AUTO
Run-on time of the presence detector, run-on time starts when no presence is
detected.
The run-on time may vary depending on the profile used.
You can choose whether you want the basicDIM DGC module to switch off the
light completely or to dim it down to the absence value after the run-on time.
It can also be changed using the basicDIM DGC Programmer or the
masterCONFIGURATOR software.
Absence value
1%
10%
30%
Lighting control can also be disabled using the masterCONFIGURATOR software.
Set target value
SET
The light level can be set via following options:
• REMOTECONTROL IR6 (press the key for > 3 s)
• basicDIM DGC Programmer (press the key for > 3 s)
• masterCONFIGURATOR software
• external momentary-action switch:
Switch-off delay
0min
1 min
10 min
1 min
SET
∞
30min
The absence value (light level) and the switch-off delay (the period for which the
level is maintained) differ depending on the profile used; these parameters may
be changed using the basicDIM DGC Programmer or the masterCONFIGURATOR
software.
ON
By briefly pressing the momentary-action switch twice the currently
measured light level is saved as new target value.
(Depending on the profile used, this function is enabled or disabled, but it
can be changed using the basicDIM DGC Programmer or
the masterCONFIGURATOR software)
Bright-out
Offset
ON
OFF
- 30%
Depending on the profile used, a negative offset may be enabled between CH2
and CH1. Using the basicDIM DGC Programmer and the masterCONFIGURATOR
software, this parameter may be changed (also positive offset possible).
CH2
40 %
CH1
70 %
If the nominal illuminance level (e.g. 500 lx) is exceeded for 10 minutes at over
150 % (e.g. 750 lx), the light is switched off, even if presence is detected.
The light is switched on again as soon as the measured light level falls below the
target value.
Depending on the profile used, this function is either enabled or disabled and
can be changed using the basicDIM DGC Programmer or
the masterCONFIGURATOR software.
The bright-OUT status can be indicated on the sensor by a slowly flashing green
status LED.
By default this function is disabled, but it can be enabled using the
masterCONFIGURATOR software.
500 LUX
Artificial light
Natural light
CH1 ON
CH2 OFF
Light control incl. brightout activated for CH1. CH2 is not illuminated controlled.
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
11
luxCONTROL lighting control system
basicDIM
Neighbourhood function
Depending on the profile used, the basicDIM DGC can respond to presence
detected in other groups.
These functions can be changed using the basicDIM DGC Programmer or the
masterCONFIGURATOR software.
Switched off
Behaviour after return of power
The basicDIM DGC module features two different types of starting behaviour
after mains failure.
No response to presence detected in other
groups. Default setting for all profiles!
OFF
Switched on
If presence is reported by other groups, the
light level will switch to presence value
ON
Switched on
If presence is reported by other groups, the
light level will switch to absence value
OFF
ON
Power ON behaviour OFF (luminaires remain
switched off)
Power ON behaviour ON (the luminaires are
switched on after return of power).
Default setting for all profiles!
Momentary-action switch inputs
Momentary-action switch 1
T1
Momentary-action switch 2
T2
CH1 CH2
CH1
CH2
Display of outputs controlled by momentaryaction switch (CH1 and CH2, or just CH1 or
CH2)
Basic functions
ON
OFF
Switching on
If the DGC module has been switched on via
ON, lighting control is disabled.
Switching off
Dimming up
Dimming down
Profiles
Profile 1: Individual room
Profile 2: Classroom
Profile 3: Corridor
Profile 4: WC
Profile 5: Free-standing luminaire (default profile)
Profile Test:
You may use the Profile Test to check the profile you selected.
All times relevant to the profile are reduced to 15 s.
The Profile Test will automatically be terminated after 1 h, or by pressing the Auto key of the basicDIM DGC Programmer.
The profiles can be adjusted to your needs via the masterCONFIGURATOR software or the DGC Programmer.
For more detailed information please refer to the masterCONFIGURATOR documentation at www.tridonic.com.
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
12
luxCONTROL lighting control system
basicDIM
Brief description of profiles
Individual room profile
T1
CH1
T2
CH2
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
OFF
SET
ON
Standby
ON
- 30%
Only OFF
ON
- 30%
Standby
ON
Only OFF
CH1 ON
CH2 OFF
10min
10%
20min
10 min
1 min
10%
20min
1 min
10min
10%
1 min
10 min
∞
1 min
1 min
10 min
SET
ON
Classroom profile
T1
CH1 CH2
T2
only
OFF
Corridor profile
T1
CH1 CH2
ON
T2
CH1 CH2
ON
CH1 CH2
ON
ON
OFF
WC profile
T1
OFF
ON
OFF
ON
T2
Free-standing luminaire profile (default)
T1
T2
CH1
CH2
ON
OFF
ON
OFF
ON
OFF
SET
ON
Standby
CH1 ON
CH2 OFF
SET
ON
Data sheet 03/16-CO074-11
Subject to change without notice.
www.tridonic.com
13