ENVIRONMENTAL CONDITIONS
Please read this document carefully before using this product. The guarantee will be
invalidated if the device is damaged by not following instructions detailed in the
manual. The company shall not be responsible for any damage or losses however
caused, which may be experienced as a result of the installation or use of this product.
Ambient/storage temperature 0 ... +50°C/-25 ... 70°C (with no icing)
80%, up to 31°C decreasing linearly 50% at 40°C
Max. relative humidity
Rated pollution degree
According to EN 60529
Front panel : IP65
Rear panel : IP20
Height
Max. 2000m
Do not use the device in locations subject to corrosive and flammable gasses.
ENDA ET1411 DIGITAL THERMOSTAT
ELECTRICAL CHARACTERISTICS
Thank you for choosing ENDA ET1411 temperature controller.
OUT
°C
SET
SET
ENDA
Safety requirements
OUTPUT
ET1411
OUTPUT
Life expectancy for relay
2
3
4
5
6
7
Equipment is protected throughout
by DOUBLE INSULATION
NOTE:
SUPPLY:
184-253V AC
50/60Hz 3VA
7
Line
8
Neutral
Fuse
F 100 mA
250V AC
8
9 10 11 12
1
2
24V AC/DC ±10%
50/60Hz 3VA
OUTPUT
250V AC 8A
RESISTIVE LOAD
12V AC/DC ±10%
50/60Hz 3VA
230V AC +10% -20%
50/60Hz 3VA
OUTPUT
250V AC 8A
RESISTIVE LOAD
OUTPUT
250V AC 8A
RESISTIVE LOAD
1
3
4
5
6
7
8
9 10 11 12
Holding screw
0.4-0.5Nm.
35mm
SN: XXXXXXXXX
9 10 11 12
ET1411-NTC-230VAC
DIGITAL THERMOSTAT
8
ENDA INDUSTRIAL ELECTRONICS
7
NTC
SENSOR
6
ET1411
Flush mounting
clamp
9 10 11 12
5
SET
SET
8
4
NTC
SENSOR
Push out the flush-mounting
clamp in direction 1 as shown
in the figure below. Then, pull
out the clamp in direction 2.
°C
ENDA
Flush mounting
clamp
Panel cut-out
71mm
1
Note:
Switch
230V AC
Supply
Fuse should
be connected Cable size: 1,5mm²
1) Mains supply cords shall meet the requirements of
IEC 60227 or IEC 60245.
2) In accordance with the safety regulations, the power
supply switch shall bring the identification of the
relevant instrument and it should be easily
accessible by the operator.
5mm
71mm
For removing mounting clamps:
OUT
°F
7
3
NTC
SENSOR
77mm
OUTPUT
250V AC 8A
RESISTIVE LOAD
2
ET1411-NTCH-24
DIGITAL THERMOSTAT
SN: XXXXXXXXX
SN: XXXXXXXXX
NTC
SENSOR
ENDA INDUSTRIAL ELECTRONICS
Depth
Dimensions
230V AC +10% -20%
50/60Hz 3VA
1
ET1411-NTCH-12
DIGITAL THERMOSTAT
Suitable for flush-panel mounting.
W77xH35xD71mm
Approx. 205g (After packing)
Self extinguishing plastics
While cleaning the device, solvents (thinner, benzine, acid etc.) or corrosive materials must not be used.
6
SN: XXXXXXXXX
ENDA INDUSTRIAL ELECTRONICS
Housing type
Dimensions
Weight
Enclosure material
5
ET1411-NTCH-230VAC
DIGITAL THERMOSTAT
HOUSING
4
ENDA INDUSTRIAL ELECTRONICS
Single-setpoint control
On-Off control
Adjustable between 0.1 ... 20.0°C.
3
ENDA ET1411 is intended for installation in control panels. Make sure that the device is used
only for intended purpose. The electrical connections must be carried out by a qualified staff
and must be according to the relevant locally applicable regulations. During an installation, all of the
cables that are connected to the device must be free of electrical power. The device must be
protected against inadmissible humidity, vibrations, severe soiling and make sure that the operation
temperature is not exceeded. The cables should not be close to the power cables or components.
Control type
Control algorithm
Hysteresis
2
Connection Diagram
up to date: 01022014, modification reserved and can be change any time previous notice !
CONTROL
1- Supply Voltage
230VAC.......230V AC
24................24V AC/DC
12................12V AC/DC
1
Relay: 250V AC, 8A (for resistive load), NO+NC;
1/2 HP 240V AC CosF = 0.4 (for inductive load)
Mechanical 30.000.000; Electrical 100.000 operation.
1
Order Code : ET1411-NTCH-
°F
230V AC +10% -20%, 50/60Hz or 12/24V AC/DC ±10%, 50/60Hz.
Max. 3VA
2.5mm² screw-terminal connections.
-60.0 ... +150.0°C (-76.0 ... +302.0°F)
0.1°C / ±1°C
(±1%-1sec)
4 digits, 12.5mm, 7 segment yellow LED
EN 61326-1: 1997, A1: 1998, A2: 2001 (Performance criterion B is satisfied for EMC tests.
The device is designed to operate in controlled electromagnetic environment)
EN 61010-1: 2001 (Pollution degree 2, overvoltage category II)
29mm
* 35 x 77mm sized.
* On-Off control.
* Single contact output for selectable heating
or cooling control.
* Single NTC probe input.
* Offset value can be entered for NTC probe.
* In the case of probe failure, output state can be
selected on, off or periodical running.
* Upper and lower limits of the setpoint can be
adjusted.
* Temperature unit can be selected °C or °F.
* CE marked according to European Norms.
Supply voltage
Power consumption
Wiring
Scale
Sensitivity/Accuracy
Time Accuracy
Indicator
EMC
SURAN Industrieelektronik
Dettinger Str. 9
D-72160 Horb a.N.
Tel.: +49 (0)7451 / 625 617
Fax: +49 (0)7451 / 625 0650
2
Panel
Rubber
packing
Note : 1) Panel thickness
should be maximum
7 mm.
2) If there is no 60mm
free space at the back
side of the device, it
would be difficult to
remove it from the panel.
E-mail : [email protected]
Internet : www.suran-elektronik.de
1./2
ET1411-E
FAHRENHEIT
LED
OUT
LED
Displayed process value in the run mode, parameter name or value in programming mode.
OUT
°F
Used for selecting menu and increasing setpoint value of the parameters in the programming mode and for increasing the setpoint value in the run mode. When held down for a
few seconds, the change rate accelerates.
°C
SET
SET
ENDA
ET1411
Used for selecting parameters and decreasing the setpoint value in the programming mode and for decreasing the setpoint value in the run mode. When held down for a few
seconds, the change rate accelerates.
SET
Used for adjusting the value of the setpoint in the run mode and for adjusting the selected parameter in the programming mode. While holding
selected parameter appears and by using
and
keys the value can be adjusted.
Run Mode
Process
Value
22.0
1000
PARAMETER TABLE
ou
SET
SET
30.0
29.9
30.0
SET
While holding
key OUTPUT setpoint value appears and by using
the value can be adjusted.
If both
keys are pressed and held for 3 seconds,
programming mode is entered.
and
If both
keys
keys are pressed,
run mode is entered.
Programming Mode
ou
o.lol
o.uPl
o.off
o.Hys
Se
Cn
The lower limit
of the setpoint.
The upper limit
of the setpoint.
The offset value
for the output
Output
hysteresis
o.PPn
On time for the output
in the case of
probe failure.
o.PPF
Off time for the output
in the case of
probe failure.
Control mode
C.typ
Unit
S.Cod
Temperature unit
A.-ou
Decimal place
dres
key, setpoint value of the
A.-Cn
A.ou.S.
Access code for security menu.
This parameter should be 321 .
Security parameter
for output menu
o.LoL
o.uPL
o.oFF
o.HYS
o.PPn
o.PPF
Cn
Menu of Output control parameters
DEF.
SET
UNIT
-60.0
o.uPL
°C
-60
The upper limit of the setpoint.
o.LoL
150.0
°C
150
The offset value for the output
-20.0
20.0
°C
0
Output hysteresis
0.1
20.0
°C
2
On time for the output in the case of probe failure.
0
255
Min.
0
Off time for the output in the case of probe failure.
0
255
Min.
1
Menu of Configuration
(Heat
Cool
C.tyP
Control mode
Unit
Temperature unit
dres
Decimal place (no
= no decimal point,
22 °C
yes = with decimal point, 22.3 °C )
SE
MAX
The lower limit of the setpoint.
= Heating cotrol
=Cooling control)
Heat
Cool
Heat
°C
°F
°C
no
yes
no
Menu of Parameter security
A.-ou
Security parameter for
menu of output control
A.-Cn
Security parameter for
menu of configuration
A.ou.S.
Security parameter for
output setpoint value
Security parameter
for configuration menu
Security parameter
for output setpoint value
MIN
NonE = Menu is invisible.
P.yes = Parameters of menu are changeable.
P.no
= Parameters of menu are only visible.
P.yes = Setpoint value is changeable.
P.no = Setpoint value is only visible.
Error Messages
PsC
Means, thermostat probe is short circuit.
Pfa
Means, thermostat probe is broken.
Temperature value is higher than the scale.
Temperature value is lower than the scale.