Electropneumatic Transducer
IP-411 and IP-413
M2073/0303
SPECIFICATIONS
Accuracy
*
:
±
1%
FS
Maximum Supply Pressure: 40 PSIG
Pressure Differential: 0.1 PSIG (supply to branch)
Supply Voltage: 18 to 28 VAC or VDC
Supply Current: 150
M
A
Enclosure: 18 Ga. C.R. steel chassis
Finish: Baked on enamel PMS2GR88B
Conformance: EMC standards EN50082-1(1992),
EN55014(1993)/EN60730-1(1992)
Compensated Temperature Range: 25° F to 150° F (4° C to
65° C )
T. C. Error:
±
0.025%/° F (.03%/° C )
Media Compatibility: Clean dry air or any inert gas
Port Connection: ¼-inch O.D. poly tubing
Environmental: 10 to 90% RH non-condensing
Termination: Screw terminal block
Wire Size: 12 Ga. maximum
Input Impedance: 301 ohms (4 - 20
M A ); 10K ohms
(0 - 5 or 0 - 10 VDC )
Weight: 1.0 lb. (.45 kg)
*
Includes nonlinearity, hysteresis, and non-repeatability.
3. Pull wires through the bottom of the transducer and make the necessary connections.
4. Make the pneumatic connections.
WIRING
Use maximum 12
AWG
wire for wiring terminals and flexible
¼-inch O.D. poly tubing for main and branch pneumatic connections. The electropneumatic transducer can be powered with a 18 to 28 VAC or VDC supply.
1. Connect the power supply voltage wire to the supply
[+] terminal and the power supply common to the common [-] terminal.
2. Connect the controller output wire to the input [I] terminal and the controller common wire to the common [-] terminal.
CALIBRATION
All electropneumatic transducers are factory calibrated to meet or exceed published specifications. If field adjustment is necessary, follow these instructions:
1. Connect air to the Main port.
2. Connect an accurate gauge to the Branch port using a minimum of 6 to 10 feet (1.8 to 3.0 m) of tubing.
3. Connect an 18 to 28 VAC or VDC power source to the
[+] and [-] terminals. The maximum supply voltage should not exceed 30 VAC / VDC .
4. Apply a low input signal to the [-] and [I] terminals
(0
VDC or 4
M A ).
5. Adjust [Z] to obtain the desired low output pressure.
6. Apply a high input signal to the [-] and [I] terminals (5/
10
VDC
or 20
M A
).
7. Adjust [S] to obtain the desired high output pressure.
8. Repeat steps 4 through 7 until the transducer is fully calibrated.
JUMPER CONFIGURATIONS
Jumper configuration varies by output type:
M A or VDC .
DIMENSIONS
INSTALLATION PRECAUTIONS
Do not use on an oxygen service, in an explosive or hazardous environment, or with flammable or combustible material.
Disconnect the power supply before installing the transducer.
Failure to do so can result in electrical shock and equipment damage.
Make all connections in accordance with the job wiring diagram and national and local electrical codes. Use only copper conductors.
Use electrostatic discharge precautions such as wrist straps when installing and wiring the transducer.
Do not exceed ratings for the transducer.
This transducer contains a half-wave rectifier power supply and must not be powered from transformers powering other devices with non-isolated full-wave rectifier power supplies.
Verify that the main supply pressure does not exceed 40 PSIG .
Ensure a minimum of 6 to 10 feet (1.8 to 3.0 m) of tubing between the transducer and the actuator.
For a 24 VAC supply voltage, make sure that the hot and neutral are not reversed. If more than one transducer is being powered from the same transformer, the hot and neutral should be the same for each transducer.
MOUNTING
The electropneumatic transducer must be mounted in an upright position so that the main and branch ports face upwards and the gauge can be read easily.
1. Select the mounting location.
2. Mount the transducer on a vertical surface with three
#8 self-tapping screws (not provided).
CHECKOUT
To verify proper operation of the transducer, adjust the input signal to obtain a maximum output pressure for the appropriate range. The output should be 15 or 20 PSIG . Next, adjust the input signal to obtain a minimum output pressure.
The output should be 0 or 3 PSIG .
Manual REVISION
Benelux:
OMEGAnet Online Service www.omega.com
Czech Republic:
USA:
ISO 9001 Certified
Canada:
Servicing North America:
One Omega Drive, P.O. Box 4047
Stamford, CT 06907-0047
TEL: (203) 359-1660 e-mail: [email protected]
FAX: (203) 359-7700
976 Bergar
Laval (Quebec) H7L 5A1
TEL: (514) 856-6928 e-mail: [email protected]
FAX: (514) 856-6886
France:
Germany/Austria:
United Kingdom:
ISO 9002 Certified
For immediate technical or application assistance:
USA and Canada:
Mexico:
Sales Service: 1-800-826-6342 / 1-800-TC-OMEGA
SM
Customer Service: 1-800-622-2378 / 1-800-622-BEST
SM
Engineering Service: 1-800-872-9436 / 1-800-USA-WHEN
SM
TELEX: 996404 EASYLINK: 62968934 CABLE: OMEGA
SM
TEL: (001) 800-826-6342 FAX: (001) 203-359-7807
En Espanol: (001) 203-359-7803 e-mail: [email protected]
[email protected]
Servicing Europe:
Postbus 8034, 1180 LA Amstelveen, The Netherlands
TEL: +31 (0) 20 6418405 FAX: +31 (0) 20 6434643
Toll Free in Benelux: 06 0993344 e-mail: [email protected]
Rude armady 1868, 73301 Karvina
TEL: +420 (0) 69 6311899 FAX: +420 (0) 69 6311114
Toll Free in Czech Republic: 0800-1-66342 e-mail: [email protected]
9, rue Denis Papin, 78190 Trappes
TEL: +33 (0) 130 621 400 FAX: +33 (0) 130 699 120
Toll Free in France: 0800-4-06342 e-mail: [email protected]
Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
TEL: +49 (0) 7056 3017 FAX: +49 (0) 7056 8540
Toll Free in Germany: 0800 TC OMEGA
SM e-mail: [email protected]
P.O. Box 7, Omega Drive
Irlam, Manchester
M44 5EX, United Kingdom
TEL: +44 (0) 161 777-6611 FAX: +44 (0) 161 777-6622
Toll Free in England: 0800 488 488 e-mail: [email protected]
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply. OMEGA is constantly pursuing certification of its products in the European New Approach Directives. OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient connected applications.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of 13 months from date of purchase. OMEGA Warranty adds an additional one
(1) month grace period to the normal one (1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit should malfunction, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s control. Components which wear are not warranted, including but not limited to contact points, fuses, and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR REPRESENTATIONS OF ANY KIND WHATSOEVER,
EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE, AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE ARE HEREBY DISCLAIMED. LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way,
OMEGA assumes no responsibility as set forth in our basic WARRANTY / DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRIES
Direct all warranty and repair requests/inquiries to the OMEGA Customer Service Department. BEFORE RETURNING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN
AUTHORIZED RETURN (AR) NUMBER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS). The assigned AR number should then be marked on the outside of the return package and on any correspondence.
The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the following information available BEFORE contacting OMEGA:
1. Purchase Order number under which the product was PURCHASED,
2. Model and serial number of the product under warranty, and
3. Repair instructions and/or specific problems relative to the product.
FOR NON-WARRANTY REPAIRS, consult OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1. Purchase Order number to cover the COST of the repair,
2. Model and serial number of the product, and
3. Repair instructions and/or specific problems relative to the product.
OMEGA’s policy is to make running changes, not model changes, whenever an improvement is possible. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
© Copyright 2003 OMEGA ENGINEERING, INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.