TBLZ3112

TBLZ3112
GB.TBLZ3112.050101
INSTALLATION
GOLDen GATE, TBLZ-1/2-1-3-41
1. GENERAL
The TBLZ-1/2-1-3-41 Communication unit is designed for
use together with the GOLD Air handling unit, Version 4,
A and B.
The unit consists of the following components:
1. 4-module standard enclosure for DIN busbar
installation to IP20.
2. 9-pin D-subconnector for connection via serial cable
to the GOLD or modem.
3. Power supply terminals, 10-30 V AC/DC, 50 mA at
12V (see label).
4. RJ-12 jack for connection to the GOLD via special
cable if 2.is used for the modem
5. RJ-12 jack for Ethernet connection.
6. Digital input terminals.
Other features:
Module LED.
RX LED.
Link LED.
GOLD Comm. LED.
4
6
2. SAFETY PRECAUTIONS
3
Be careful whenever you do any wiring to the unit. Never
carry out any work on the unit while the power supply is
switched on. Doing so could harm you and damage the
unit. Observe local electrical safety regulations as you
install the unit.
3. INSTALLATION
1
3.1 General
2
5
Fig. 1
Specifications are subject to alteration without notice.
Connect conductors to the V in+ and V in- terminals (see
Fig. 1) of the GOLDen GATE unit and wire them to a separate power supply unit with the correct capacity or to the
12 V DC or 24 V AC terminals of the GOLD air handling
unit.
Configure the communication unit using the configuration
program GOLDen GATEConfig available from our website
address: http://www.swegon.se. Install the program according to the instructions in the setup window.
www.swegon.se
1
GB.TBLZ3112.050101
This configuration requires the use of a computer with
Windows 98 SE or better and an Ethernet port. Use a
twisted-pair cable or connect both the unit and computer
to the same network. Start the configuration program and
select Ethernet, see Figure 2. The program will now scan
the network to seek the GOLDen GATE unit. All the units
connected are shown on a list, see Figure 3.
Double click on the unit desired and enter the IP addresses. As standard, “admin” is used both as the user name
and the password, see Figure 4. The unit can be configured via our integrated webpage for both mail, master and
PPP function with links to other GOLDen GATE units in the
same network.
If you know the IP address, you can also configure the
unit via its own built-in webpage. After you’ve saved your
settings, you’ll have to reboot the unit before your settings will be effective. Locate the communication unit
next to the junction hood on the GOLD air handling unit.
Depending on the enclosure requirements called for by
the application, an extra enclosure conforming to a higher
enclosure class may be required. Connect the network.
Fig. 2
Fig. 3
Power
Direct with twistedpair cable
Twisted-pair
Ethernet cable
Via network
Power
Straight
Ethernet cable
Hub/Switch
Fig. 4
2
www.swegon.se
Specifications are subject to alteration without notice.
GB.TBLZ3112.050101
3.2 GOLD Version 4/A
Connect the serial cable supplied with 9-pin D-subconnector and circular connector to the socket on the GOLD (see
arrow in Fig. 5).
3.3 GOLD Version B
Run the serial cable supplied through the GOLD air handling unit cable lead-through and connect it to the socket
located inside the GOLD (see Fig. 6 and 7).
Fig. 5
Junction hood viewed from the rear
Power
Cable lead-through
Hub/Switch
For GOLDen GATE cable
Fig. 6
GOLD
1 2 3
4
5 6 7
������
4. COMMISSIONING
4.1 GOLD Version 4/A
��������
�����
����
25 26 27 28 29 30 31 32
Set the LON Communication to “0” in the service menu.
4.2 GOLD Version B
Control unit
Dipswitch
ON
OFF
��������
12 3 4
��������
GOLD units with Program Version 1.11: DIP-switch 3 must
be in the ON position and DIP-switch 4 in the OFF position
on the GOLD AHU control unit: (see Fig. 7).
GOLD units with Program Version 1.12 and better: DIPswitch 3 must be in the OFF position and DIP-switch 4
must be in the in the ON position on the GOLD AHU
control unit (see Fig. 7).
Fig. 7
Specifications are subject to alteration without notice.
www.swegon.se
3
GB.TBLZ3112.050101
5. DIGITAL INPUTS
6. MODEM
(Applicable to Program Version 4.00.0 and newer)
This unit has support for connecting a modem to the
network. An external modem is required, as well as a
special cable for interconnection with the GOLD. In this
way, one or more GOLD air handling units can be monitored via one modem. In the event of an alarm, an alarm
message is e-mailed to the user who can then establish a
connection via modem to the network and use the web
interface available to him. A browser with support for Java
is required. See the web instructions for particulars of how
to configure this function.
5.1 General
The unit is equipped with 2 digital inputs. The status of
the inputs can then be read as 2 parameters in the report
(Digital in 1 and Digital in 2) via the network.
If the built-in web page is used, the inputs are designed
for forwarding alarms. Provision is available for free alarm
text and input inversion. It is also possible to e-mail alarms.
5.2 Electrical connection
The digital input is rated for a 10-30 V DC supply. The control unit of the Version B GOLD units has terminal blocks
for supplying 12 V DC current.
GOLD
Power
Special cable
Digital in 1
Digital in 2
- 10-30VDC +
- 10-30VDC +
Ordinary
modem cable
Modem
Hub/Switch
Modem
17
+
18
19
+
20
TBLZ-1/2-1-2-41 Communication unit
4
www.swegon.se
Specifications are subject to alteration without notice.
GB.TBLZ3112.050101
7. GENERAL EXPLANATIONS
Module LED
LED shines orange during start-up; then shines
green while the unit is energized.
LED flashes green while configuration is in
progress.
LED flashes red if the memory malfunctions.
LED shines red in the event of a serious fault in
the hardware.
GOLD Comm.
LED flashes green while communication
between the GOLD and the GOLDen GATE is
in progress.
LED shines red if an error in communication
occurs between the GOLD and the GOLDen
GATE.
LED is not lit while there is no traffic between
the GOLD and the GOLDen GATE.
RX
LED flashes green while there is traffic on the
Ethernet network.
Link
LED is not lit if a link to the Ethernet network i
is down; shines with a steady green glow if the
unit is connected to a 10 Mbit/s network.
LED shines with a steady orange glow if the
unit is connected to a 100 Mbit/s network.
The various parameters available and protocol-specific
properties are documented in separate product leaflets.
These leaflets can be downloaded from our website:
www.swegon.se.
The GOLD air handling unit operates independently
regardless of whether or not the network is active.
Specifications are subject to alteration without notice.
www.swegon.se
5