Omega PX2150, PX2151 Series Owner Manual
Omega PX2150, PX2151 Series are ultra high purity pressure transducers and transmitters designed for use in critical applications where purity is of utmost importance. These devices are ideal for measuring pressure in industries such as pharmaceutical, biotechnology, food and beverage, and chemical processing. The PX2150 Series offers voltage output, while the PX2151 Series provides a current output. Both series are available in a wide range of pressure ranges, from 0 to 15 psi up to 0 to 5000 psi.
The PX2150 and PX2151 Series are constructed of high-quality materials that are compatible with ultra-high purity media. The wetted parts are made of 316L stainless steel, which is resistant to corrosion and contamination. The devices are also designed to meet the requirements of USP Class VI and FDA CFR Title 21.
Advertisement
Advertisement
User’s Guide
http://www.omega.com
email: [email protected]
MODEL PX2150
Ultra High Purity Transducers and Transmitters
OMEGAnet
On-Line Service http://www.omega.com
Internet e-mail [email protected]
USA:
ISO 9001 Certified
Tel: (203) 359-1660 e-mail: [email protected]
Canada:
Laval (Quebec) H7L 5A1
Tel: (514) 856-6928 e-mail: [email protected]
Servicing North America:
One Omega Drive, Box 4047
Stamford, CT 06907-0047
FAX: (203) 359-7700
976 Bergar
FAX: (514) 856-6886
USA and Canada
Customer Service:
Engineering Service:
TELEX:996404
Mexico and Latin America:
Benelux:
Tel: (31) 20 6418405
Czech Republic
Tel: 420 (69) 6311899
France:
Tel: (33) 130-621-400
Germany/Austria:
Tel: 49 (07056) 3017
United Kingdom:
ISO 9002 Certified
For immediate techincal or application assistance:
Sales Service: 1-800-826-6342/1-800-TC-OMEGASM
1-800-622-2378/1-800-622-BESTSM
1-800-872-9436/1-800-USA-WHENSM
EASYLINK: 62968934 CABLE: OMEGA
Tel: (95) 800-826-6342 FAX: (95) 203-359-7807
En Espan ~ ol: (95) 203-359-7803 email: [email protected]
Servicing Europe:
Postbus 8034, 1180 LA Amstelveen, The Netherlands
FAX: (31) 20 6434643
Toll Free in Benelux: 0800 0993344 e-mail: [email protected]
ul. Rude armady 1868, 733 01 Karvina-Hranice
FAX: 420 (69) 611114
Toll Free: 0800-1-66342
9, rue Denis Papin, 78190 Trappes e-mail: [email protected]
FAX: (33) 130-699-120
Toll Free in France: 0800-4-06342 e-mail: [email protected]
Daimlerstrasse 26, D-75392 Deckenpfronn, Germany
FAX: 49 (07056) 8540
Toll Free in Germany: 0130 11 21 66 e-mail: [email protected]
One Omega Drive, River Bend Technology Centre
Northbank, Irlam, Manchester
M44 5EX, England
Tel: 44 (161) 777-6611 FAX: 44 (161) 777-6622
Toll Free in the United Kingdom: 0800-488-488 e-mail: [email protected]
It is the policy of OMEGA to comply with all worldwide safety and EMC/EMI regulations that apply.
OMEGA is constantly pursuing certification of its products to the European New Approach Directives.
OMEGA will add the CE mark to every appropriate device upon certification.
The information contained in this document is believed to be correct, but OMEGA Engineering, Inc. accepts no liability for any errors it contains, and reserves the right to alter specifications without notice.
WARNING: These products are not designed for use in, and should not be used for, patient-connected applications.
SS2042 02/26/99 Rev.A
General Information
The PX2150 Series Ultra High Purity Pressure Transducer and Transmitter has been factory tested and calibrated prior to shipment. Specific details of the performance not listed herein can be obtained from the product specification bulletin.
Environmental Conditions
The PX2150 Series are designed to be operated and stored under the following environmental conditions:
Temperature
Operating:
Storage:
-40 to 180
°
F (-40 to 82
°
C)
-65 to 260
°
F (-54 to 126
°
C)
Electrical Connections
Voltage Output Transducers
The voltage output transducers are a three (3) wire device where the negative output and excitation are commoned together internally on the PX2150 circuit board. Four (4) wires are provided for the users convenience. The PX2150 is provided with either a 6 foot cable or a bayonet style connector. The connections are shown below and depicted in Figure 1A and 1B:
Cable Pin Bayonet Pin
Red A
Green
White
Black
B
C
D
Shield
Function
+ Excitation; connects to a 12 VDC+/-10% Power supply
+ Output; connects to controller or monitoring device
- Output; connects to controller or monitoring device
- Excitation; connects to return of 12 VDC power supply
Connects to system or Earth ground
PX 2150
Transducer
(0 to 5 VDC)
Power
Supply
Red Black White Green
+ +
Load
(Monitor)
_ _
Figure 1A
PX 2150
Transducer
(0 to 5 VDC)
Power
Supply
Pin A Pin D Pin C Pin B
+
_
+
_
Load
(Monitor)
Figure 1B
Current Output Transmitters
The current output transmitters are a true two (2) wire device and delivers current into any external load of 0 to 800 ohms (see Figure 2). The unit has been factory calibrated at 24 VDC into a 250 ohm load. The voltage limits and power supply requirements are shown in Figure 3. The PX2150 has a 6ft. cable where red is positive and black is negative. For those units with the Bayonet style connector, Pin A is positive and Pin B or Pin D is negative.
Min Supply Voltage (VDC) = 16 + 0.02 x (Resistance of receiver plus line)
Max Supply Voltage (VDC) = 30 + 0.004 x (Resistance of receiver plus line)
Figure 2
PX 2150
Transmitter
(4 to 20 mA)
+
_
+ +
Power
Supply
Load
(Monitor)
_ _
Loop Power Supply vs.
Loop Resistance for 4 to 20mA Transmitters
Figure 3
Operating
Range
16
Loop Supply Voltage (Vdc)
30
Mounting and Pressure Fitting
Mounting
The PX2150 is mounted via it’s pressure fitting. No other provisions are made for mounting.
Fittings
The PX2150 comes standard with a #4 male Swivel Face Seal.
Calibration
The PX2150 Series transducers and transmitters are tested and calibrated to the specific input pressure verses output voltage so little or no field calibrating is necessary. Zero and span adjustments can be made by turning the rotatable cover to expose zero and span pots.
Zero Adjustment – Voltage
For Gage units, monitor the voltage between the positive output (+ OUT) and common
(-OUT). Adjust the output until a reading as close as practical to 0.20 VDC is achieved.
For Compound calibrations, open the pressure port to atmosphere and monitor the voltage between the positive output (+ OUT) and common (- OUT). Table 1 shows the voltage level required to be read at 0 psig. Turn the zero potentiometer until this voltage level, or as close as practical, is achieved.
Zero Adjustment – Current
For Gage units, monitor the current output and turn the zero adjustment screw until a reading as close as practical to 4 mA is achieved.
For Compound calibrations, open the pressure port to atmosphere and monitor the current output of the device in test. Table 1 shows the relationship between the current level and the output at 0 psig. Adjust the zero potentiometer until this level, or as close as practical, is achieved.
Compound Range
-14.7 to 50 psig
-14.7 to 100 psig
-14.7 to 250 psig
-14.7 to 500 psig
-14.7 to 1000 psig
-14.7 to 3000 psig
TABLE 1
Voltage Output
1.336 VDC
0.841 VDC
0.477 VDC
0.343 VDC
0.272 VDC
0.224 VDC
Current Output
7.64 mA
6.05 mA
4.89 mA
4.46 mA
4.23 mA
4.08 mA
Span Adjustment – Voltage
Span or full scale output adjustments should only be performed by using an accurate pressure standard (electronic manometer, digital pressure gage, etc.) with at least comparable accuracy as the PX2150 Series. With full scale pressure applied to the pressure port, adjust span for full scale electrical output of 5.2 VDC.
Example 1: Pressure range of 0 to 100 psi and 0.2 to 5.2 VDC output
Apply 100 psi to the pressure port and adjust span as close as practical to 5.200 VDC.
Span Adjustment – Current
Span or full scale output adjustments should only be performed by using an accurate pressure standard (electronic manometer, digital pressure gage, etc.) with at least comparable accuracy as the PX2150 Series. With full scale pressure applied to the pressure port, adjust span for full scale electrical output of 20 mA.
Example 1: Pressure range of 0 to 250 psi and 4 to 20 mA output
Apply 250 psi to the pressure port and adjust span as close as practical to 20 mA.
WARRANTY/DISCLAIMER
OMEGA ENGINEERING, INC. warrants this unit to be free of defects in materials and workmanship for a period of
13 months from date of purchase. OMEGA Warranty adds an additional one (1) month grace period to the normal one
(1) year product warranty to cover handling and shipping time. This ensures that OMEGA’s customers receive maximum coverage on each product.
If the unit malfunctions, it must be returned to the factory for evaluation. OMEGA’s Customer Service Department will issue an Authorized Return (AR) number immediately upon phone or written request. Upon examination by
OMEGA, if the unit is found to be defective, it will be repaired or replaced at no charge. OMEGA’s WARRANTY does not apply to defects resulting from any action of the purchaser, including but not limited to mishandling, improper interfacing, operation outside of design limits, improper repair, or unauthorized modification. This WARRANTY is
VOID if the unit shows evidence of having been tampered with or shows evidence of having been damaged as a result of excessive corrosion; or current, heat, moisture or vibration; improper specification; misapplication; misuse or other operating conditions outside of OMEGA’s’s control. Components which wear are not warranted, including but not limited to contact points, fuses , and triacs.
OMEGA is pleased to offer suggestions on the use of its various products. However, OMEGA neither assumes responsibility for any omissions or errors nor assumes liability for any damages that result from the use of its products in accordance with information provided by OMEGA, either verbal or written. OMEGA warrants only that the parts manufactured by it will be as specified and free of defects. OMEGA MAKES NO OTHER WARRANTIES OR
REPRESENTATIONS OF ANY KIND WHATSO EVER, EXPRESS OR IMPLIED, EXCEPT THAT OF TITLE,
AND ALL IMPLIED WARRANTIES INCLUDING ANY WARRANTY OF MERCHANTABILITY AND FITNESS
FOR A PARTICULAR PURPOSE ARE HEREBY DISCLAIMED.
LIMITATION OF LIABILITY: The remedies of purchaser set forth herein are exclusive, and the total liability of
OMEGA with respect to this order, whether based on contract, warranty, negligence, indemnification, strict liability or otherwise, shall not exceed the purchase price of the component upon which liability is based. In no event shall
OMEGA be liable for consequential, incidental or special damages.
CONDITIONS: Equipment sold by OMEGA is not intended to be used, nor shall it be used: (1) as a “Basic Component” under 10 CFR 21 (NRC), used in or with any nuclear installation or activity; or (2) in medical applications or used on humans. Should any Product(s) be used in or with any nuclear installation or activity, medical application, used on humans, or misused in any way, OMEGA assumes no responsibility as set forth in our basic WARRANTY/
DISCLAIMER language, and, additionally, purchaser will indemnify OMEGA and hold OMEGA harmless from any liability or damage whatsoever arising out of the use of the Product(s) in such a manner.
RETURN REQUESTS/INQUIRES
Direct all warranty and repair requests/inquires to the OMEGA Customer Service Department. BEFORE RETURN-
ING ANY PRODUCT(S) TO OMEGA, PURCHASER MUST OBTAIN AN AUTHORIZED RETURN (AR) NUM-
BER FROM OMEGA’S CUSTOMER SERVICE DEPARTMENT (IN ORDER TO AVOID PROCESSING DELAYS).
The assigned AR number should then be marked on the outside of the return package and on any correspondence. The purchaser is responsible for shipping charges, freight, insurance and proper packaging to prevent breakage in transit.
FOR WARRANTY RETURNS, please have the following information available
BEFORE contacting OMEGA:
1.
Purchase Order number under which the product was PURCHASED,
2.
Model and serial number of the product under warranty, and
3.
Repair instructions and/or specific problems relative to the product.
FOR NON-WARRANTY REPAIRS, consult
OMEGA for current repair charges. Have the following information available BEFORE contacting OMEGA:
1.
Purchase Order number to cover the COST of the repair,
2.
Model and serial number of the product, and
3.
Repair instructions and/or specific problems relative to the product.
OMEGA’s policy is to make running changes, not model changes. This affords our customers the latest in technology and engineering.
OMEGA is a registered trademark of OMEGA ENGINEERING, INC.
Copyright 1999 OMEGA ENGINEERING INC. All rights reserved. This document may not be copied, photocopied, reproduced, translated, or reduced to any electronic medium or machine-readable form, in whole or in part, without the prior written consent of OMEGA ENGINEERING, INC.
Where Do I Find Everything I Need for
Process Measurement and Control?
OMEGA...Of Course!
TEMPERATURE
● Thermocouple, RTD & Thermistor Probes, Connectors, Panels & Assemblies
● Wire: Thermocouple, RTD & Thermistor
● Calibrators & Ice Point References
● Recorders, Controllers & Process Monitors
● Infrared Pyrometers
PRESSURE, STRAIN AND FORCE
● Transducers & Strain Gauges
● Load Cells & Pressure Gauges
● Displacement Transducers
● Instrumentation & Accessories
FLOW/LEVEL
● Rotameters, Gas Mass Flowmeters & Flow Computers
● Air Velocity Indicators
● Turbine/Paddlewheel Systems
● Totalizers & Batch Controllers pH/CONDUCTIVITY
● pH Electrodes, Testers & Accessories
● Benchtop/Laboratory Meters
● Controllers, Calibrators, Simulators & Pumps
● Industrial pH & Conductivity Equipment
DATA ACQUISITION
● Data Acquisition & Engineering Software
● Communications-Based Acquisition Systems
● Plug-in Cards for Apple, IBM & Compatibles
● Datalogging Systems
● Recorders, Printers & Plotters
HEATERS
● Heating Cable
● Cartridge & Strip Heaters
● Immersion & Band Heaters
● Flexible Heaters
● Laboratory Heaters
ENVIRONMENTAL
MONITORING AND CONTROL
● Metering & Control Instrumentation
● Refractometers
● Pumps & Tubing
● Air, Soil & Water Monitors
● Industrial Water & Wastewater Treatment