Installation instructions for the optical detector with built-in
control unit, TBLZ-1-72-a
GOLD/COMPACT
1. General
The TBLZ-1-72-a optical smoke detector with built-in
control unit is used for measuring smoke gases in ventilation ducts.
It consists of an optical detector mounted in an adapter
system in which both the tube and enclosure are designed
for optimum airflow through the detector. The system
meets all fire safety requirements at air speeds between
0.2m/s and 20m/s. The smoke detector also has a built-in
control unit for controlling fans, fire and combustion gas
dampers.
Accessories
Use an installation bracket when installing on circular or
insulated ducts.
2. Function
A green LED is lit on the control unit's circuit card when
the unit is operating in the normal mode. All the relays are
activated.
When combustion gas is detected, a red LED lights up on
the circuit card and detector.
If the smoke detector becomes dirty, it becomes more
sensitive and slowly switches to alarm mode. To prevent
false alarms if dirty, the detector is equipped with a service
alarm (green LED on the smoke detector and yellow LED
on the circuit card of the control unit). This indicates that
the detector requires cleaning.
If a malfunction arises, the green LED will be off and no
relays will be activated. Example: If the smoke detector is
removed or a power failure occurs.
A tripped alarm can be reset on the rear side of the smoke
detector. See illustration.
Dimensions
Venturi tube length of 600 mm or 1500 mm.
150
85
180
146
154
Reset button
27
3. Technical Data
Type of detector
Optical
Operating voltage
24 V AC/DC +/- 10%
Power consumption:
Operation
About 165 mA
Ambient temperature -10°C to +55°C
Atmospheric humidity Max. 99% rH
Enclosure class
IP54
Tested and passed
To VdS
We reserve the right to alter specifications without notice.
35
(All dimensions are given in mm)
4. Maintenance
When the smoke detector becomes dirty, it becomes more
sensitive and may trigger the service alarm. This can be
delayed by vacuuming the detector once a year.
www.swegon.com
1
ØD
dh =
GB.TBLZ172.150702
2xHxB
H+B H
B
5. Installation and location
Examples of sources of disturbance
MIN 3xdh
MIN 5xdh
MIN 3xdh
GX
DAMPER
MIN 5xdh
MIN 3xdh
GX
GX
MIN 5xdh
GX
GX
SILENCER
MIN 3xdh
GX
GX
COIL
MIN 5xdh
GX
GX
Hydraulic diameter
CIRCULAR DUCT
MIN 5xdh
GX
MIN 3xdh
BRANCH
dh = D
MIN 3xdh
GX
ØD
MIN 3xdh
2xHxB
H+B H
MIN 3xdh
GX
MIN 5xdh
EXTRACT AIR
SUPPLY AIR
MIN 5xdh
GX
GX
MIN 5xdh
MIN 3xdh
GX
MIN 5xdh
GX
GX
MIN 3xdh
GX
GX
GX
GX
AIR HANDLING UNIT
MIN 5xdh
GX
MIN 3xdh
GX
ADAPTER
B
MIN 3xdh
MIN 5xdh
GX
RECTANGULAR DUCT
MIN 3xdh
MIN 5xdh
GX
FAN
BEND
dh =
MIN 3xdh
GX
GX
MIN 3xdh
Position the smoke detector in the direction of flow, according to the arrow on the cover. The smoke detector is location-independent and can be installed on any side of the
duct.
In the event of large temperature differences, e.g. outside
or in cold attics, the detector must be insulated from the
surrounding air (due to the risk of condensation build-up in
the detector housing).
To ensure optimum combustion gas detection the smoke
detector must be positioned so that the distance to the
nearest interfering source in the duct (see example of interfering sources below), in the direction of airflow, is the
same as 3 x the duct’s hydraulic diameter. Nearest location
after an interfering source must be at least 5 x the duct’s
hydraulic diameter.
MIN 5xdh
GX
GX
MIN 5xdh
GX
MIN 3xdh
MIN 3xdh
2
www.swegon.com
MIN 3xdh
MIN 5xdh
GX
GX
We reserve the right to alter specifications without notice.
GB.TBLZ172.150702
1
Drill holes in the duct.
• Make holes without 38 mm installation bracket.
• Make holes with 51 mm installation bracket
(see point 9).
5
Flow indicator.
The detector is equipped with an indicator, a red
plastic tab, which, when the detector is correctly
installed, swings out due to the air flow.
Important!
If the indicator does not
move, consider moving
the detector or install a
fan tube.
Do not cut this end!
2
Flow indicator
End plug
• Measure the ventilation duct.
• Cut the tube.
• The tubes must cover at least 90% of the duct’s width.
Detectors with venturi tubes of 600 mm are intended for
ducts with a max. duct width of 600 mm.
• Insert the end plug.
3
Venturi tube with auxiliary fan
6
Electrical installation.
Stop screw
Seal
• Insert the seal onto the tube.
• Insert the tube into the bottom of the detector box.
• Lock the tube using the stop screw
4
• Open the cover above the junction hood by lifting the
catch.
• Insert the cable through any cable grommet.
When using another type of grommet, remove them
premounted by first pressing through one side and then
through the other (1-2).
• Connect the cables according to the wiring diagram in
Section 6.
7
• Install the tube and detector on the duct.
• Secure the detector box at 3 points at the markings of
the arrows.
Important! IMPORTANT!
The direction arrows (see the shape
of the detector’s base or the top of
the housing) must point in the same
direction as the air flow in the duct.
We reserve the right to alter specifications without notice.
Performance checks.
Check the detector using the smoke detector
tester in spray form.
• Move the "test hole plug" to the
side and then quickly spray.
In the event of a tripped alarm, the
LED shines red on the circuit board
and the detector. In the event of a
tripped service alarm, the LED shines
green on the detector and yellow
on the circuit board.
• Reinstall the test hole plug.
Important!
Do NOT drill holes for signs or similar
in the plastic cover. This can cause
leakage that seriously affects the
function of the detector.
www.swegon.com
3
GB.TBLZ172.150702
8
Installing different tubes in different duct widths.
Venturi tube 600 mm.
Hole
ø 38 mm
Cut the venturi
tube to the correct
length
For ducts less than 600 mm use venturi tube of 600 mm, standard.
For ducts between 600 mm and 1400
mm, use venturi tube of 1500 mm.
9
Venturi tube 1200 mm.
Hole
ø 38 mm
The Venturi tube
must go through
the entire duct.
Important!
Hole ø 51 mm
• Cut the tube to the
correct length.
• Insert the end plug.
• Install the seal
• Install rubber seal TET
26-35 as a bearing.
Max. tube of 30 mm outside the duct.
Installation bracket TBLZ-1-53 for circular ducts or
insulated flat ducts.
The duct diameter can be as small as 100 mm
using the bracket.
Secure the bracket’s
legs to the duct.
The installation bracket is supplied flat.
Hole ø 51
mm.
Rubber
seal
Rubber
seal
The installation bracket is easy to
bend/shape so that it fits circular or
flat ducts.
Circular duct.
Insulated flat duct.
checks
10 •Final
Check that the direction of the arrows is towards the direction of flow.
• Check that the plug for the test hole is properly installed.
• Check that the flow indicator shows flow (rocks).
• Full scale tests with smoke generator are recommended to check the function.
Troubleshooting.
The smoke detector deploys without any smoke
present.
• The smoke detector is faulty, dirty or positioned so that
condensation can build up, see point 8. The detector
insert must be replaced.
4
www.swegon.com
We reserve the right to alter specifications without notice.
GB.TBLZ172.150702
6. Electrical connections
The electrical connections should be wired by a qualified
electrician in accordance with local electrical safety regulations.
SMOKE FUNCTION
Smoke detector, supervisory unit
GOLD RX/PX/CX/SD
Wiring terminals
on the control
unit and on
the electrical
equipm. cubicle.
31
32
1
2
6
7
3
4
Ext. alarm 212
13
5
6
Ext. fire alarm
1
1
2
2
3
7
4
8
5
9
6
10
Power supply: 24V AC/DC
Smoke alarm relay
Service alarm relay
3
NO Smoke alarm relay
GOLD LP/COMPACT
4
C
Free change-over contact
Wiring terminals on the
control unit
5
NC 9
10
1
2
*
5
6
3
4
**
7
8
5
6
Max. 250V. 5A.
* Should be selected for ext. fire alarm in the
micro terminal.
** Should be selected for ext. alarm in the
micro terminal.
Function:
If the smoke detector in the duct
trips, the alarm is forwarded to
GOLD/COMPACT, external fire
alarm.
When the smoke detectors become
dirty, a service alarm is initiated and
is forwarded to GOLD/COMPACT
via the external alarm 2.
Alarms can be reset on the smoke
detector and in the hand-held
micro terminal.
We reserve the right to alter specifications without notice.
www.swegon.com
5
GB.TBLZ172.150702
6
www.swegon.com
We reserve the right to alter specifications without notice.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement