Digital indicator, model DI35-D Operating instructions EN Digital indicator for panel mounting

Digital indicator, model DI35-D Operating instructions EN Digital indicator for panel mounting
Operating instructions
Digital indicator, model DI35-D
Digital indicator for panel mounting
EN
Page
3 - 63
© 2016 WIKA Alexander Wiegand SE & Co. KG
All rights reserved.
WIKA® is a registered trademark in various countries.
Prior to starting any work, read the operating instructions!
Keep for later use!
2
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
EN Operating instructions model DI35-D
Contents
Contents
1. General information
8
2. Design and function
2.1 Overview, version for panel mounting .
2.2 Overview, version in desktop case .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
9
. 9
10
2.3 Description . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.4 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . 12
3. Safety13
3.1 Explanation of symbols . . . . . . . . . . . . . . . . . . . . . 13
3.2 Intended use . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.3 Improper use . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.4 Personnel qualification .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
14
3.5 Labelling, safety marks . . . . . . . . . . . . . . . . . . . . . 15
4. Transport, packaging and storage
16
4.1 Transport . . . . . . . . . . . . . . . . . . . . . . . . . . 16
4.2 Packaging and storage . . . . . . . . . . . . . . . . . . . . . 16
5. Commissioning17
5.1 Requirements for the installation location . . . . . . . . . . . . . . . 17
5.2 Mounting, version for panel mounting .
5.3 Mounting, version in desktop case .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
17
18
5.4 Electrical connection . . . . . . . . . . . . . . . . . . . . . . 18
5.4.1 Notes on installation . . . . . . . . . . . . . . . . . . . . 18
5.4.2 Pin assignment, version for panel mounting . . . . . . . . . . . . 19
5.5 Interface connector .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
21
5.6 Switching on the digital indicator . . . . . . . . . . . . . . . . . . 21
5.7 Connection examples, version for panel mounting . . . . . . . . . . . . 22
6. Operation24
6.1 Key functions . . . . . . . . . . . . . . . . . . . . . . . . . 24
14053540.01 03/2016 EN
6.2 Accessing and exiting programming mode . . . . . . . . . . . . . . . 24
6.3 Menu navigation .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
25
6.4 Changing numerical values . . . . . . . . . . . . . . . . . . . . 25
6.5 Accessing or clearing MIN/MAX values . . . . . . . . . . . . . . . . 25
6.6 Switching the display between measuring inputs .
WIKA operating instructions digital indicator, model DI35-D
.
.
.
.
.
.
.
.
.
.
.
26
3
EN
Contents
7. Description of program numbers
27
7.1 Setting measuring inputs . . . . . . . . . . . . . . . . . . . . . 27
7.1.1 Input signal . . . . . . . . . . . . . . . . . . . . . . . 27
EN
7.1.2 Start and end value . . . . . . . . . . . . . . . . . . . . 28
7.1.3 Number of decimal places . . . . . . . . . . . . . . . . . . 29
7.1.4 Offset adjustment .
7.2 General settings .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
29
29
7.2.1 Default display . . . . . . . . . . . . . . . . . . . . . . 29
7.2.2 Switching of measuring inputs . . . . . . . . . . . . . . . . 30
7.2.3 Refresh rate .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
31
7.2.4 Measuring time . . . . . . . . . . . . . . . . . . . . . 31
7.2.5 Display brightness . . . . . . . . . . . . . . . . . . . . 31
7.3 Arithmetic function . . . . . . . . . . . . . . . . . . . . . . . 31
7.4 Setting the analogue output (option) . . . . . . . . . . . . . . . . . 32
7.4.1 Start and end value . . . . . . . . . . . . . . . . . . . . 32
7.4.2 Reference value . . . . . . . . . . . . . . . . . . . . . 33
7.4.3 Output signal . . . . . . . . . . . . . . . . . . . . . . 33
7.4.4 Example . . . . . . . . . . . . . . . . . . . . . . . . 33
7.5 Setting the serial interface (option) . . . . . . . . . . . . . . . . . 34
7.6 Setting user authorisations . . . . . . . . . . . . . . . . . . . . 35
7.6.1 Authorisation levels . . . . . . . . . . . . . . . . . . . . 35
7.6.2 Cancelling the password protection .
.
.
.
.
.
.
.
.
.
.
.
.
.
35
7.7.1 Function of the digital input .
.
.
.
.
.
.
.
.
.
.
.
.
.
36
7.7 Setting special functions . . . . . . . . . . . . . . . . . . . . . 36
.
.
.
7.7.2 Function of the multi-function key . . . . . . . . . . . . . . . 36
7.7.3 TARE function . . . . . . . . . . . . . . . . . . . . . . 36
7.7.4 HOLD function .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
37
7.8 Setting the switching outputs . . . . . . . . . . . . . . . . . . . 38
7.8.1 Flashing display on reaching the switch points . . . . . . . . . . . 38
7.8.3 Switch points . . . . . . . . . . . . . . . . . . . . . . 39
7.8.4 Switch behaviour . . . . . . . . . . . . . . . . . . . . . 39
7.9 Linearising sensors .
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
44
7.10 Reading the serial number . . . . . . . . . . . . . . . . . . . . 46
7.11 Restore factory settings . . . . . . . . . . . . . . . . . . . . . 46
4
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
7.8.2 Reference value . . . . . . . . . . . . . . . . . . . . . 38
Contents
8. Faults46
9. Maintenance and cleaning
49
9.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 49
9.2 Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . 49
10.Dismounting, return and disposal
50
10.1 Dismounting, version for control panel . . . . . . . . . . . . . . . . 50
10.2 Return . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
10.3 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . 50
11.Specifications51
Appendix 1: Overview of program numbers
57
63
14053540.01 03/2016 EN
Appendix 2: EC declaration of conformity
WIKA operating instructions digital indicator, model DI35-D
5
EN
1. General information
1.General information
■■ The digital indicator described in these operating instructions has been designed and
manufactured using state-of-the-art technology. All components are subject to stringent quality and environmental criteria during production. Our management systems
are certified to ISO 9001 and ISO 14001.
■■ These operating instructions contain important information on handling the instru-
ment. Working safely requires that all safety instructions and work instructions are
observed.
■■ Observe the relevant local accident prevention regulations and general safety regula-
tions for the instrument’s range of use.
■■ The operating instructions are part of the product and must be kept in the immediate
vicinity of the instrument and readily accessible to skilled personnel at any time. Pass
the operating instructions onto the next user or owner of the instrument.
■■ Skilled personnel must have carefully read and understood the operating instructions
prior to beginning any work.
■■ The general terms and conditions contained in the sales documentation shall apply.
■■ Subject to technical modifications.
■■ Further information:
- Internet address:
www.wika.de / www.wika.com
- Relevant data sheet:
AC 80.03
- Application consultant: Tel.: +49 9372 132-0
Fax: +49 9372 132-406
[email protected]
14053540.01 03/2016 EN
EN
6
WIKA operating instructions digital indicator, model DI35-D
2. Design and function
2.Design and function
2.1 Overview, version for panel mounting




14053540.01 03/2016 EN
Designation
EN




Description

[☼] key
Programming mode is accessed
Changes to a deeper parameter level

[▼] key
MIN memory is accessed
Changes lower limit values
Changes between parameters
Changes parameter values

[▲] key
MAX memory is accessed
Changes lower limit values
Changes between parameters
Changes parameter values

Key [○]
Multi-function key

Switch point display
Displays the status of the switching outputs

Mounting element with clamping screw
Used for fixing

7-segment display
Displays measured values, program numbers or
parameters

Product label
Contains product information
WIKA operating instructions digital indicator, model DI35-D
7
2. Design and function
2.2 Overview, version in desktop case
EN
7
y
pla
dis
ler
up
co
l.
inc
wi
82
82,0 mm97)
(with
feet
(mit Füßen 97 mm)
aufgestellt
127127)
mm)
(feet (Füße
folded
out
(26
l.
inc
d
an
m
7m
(26
rs
0
25 ecto
nn
co
u
tho
n
ati
tm
r)
cke
nste
ge
Ge
ne
h
o
ker
mm tec
0,0 sss
25 chlu
ns
dA
n
eu
zeig
An
)
tor
ec
nn
o
gc

11770,0 m
0m

Plug A Plug C
3
4
2
1
3
4
2
6
5
1

I
0
82,0 mm

3
4
2
1

425
1
3
687
Plug B Plug D

Designation






8
Digital indicator (→ for description see chapter 2.1)
Mains connector with switch
Plug A (measuring input 1)
Plug B (measuring input 2)
Plug C (switching outputs)
Plug D (transmitter power supply, analogue output, serial interface)
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
170,0 mm
2. Design and function
2.3 Description
The model DI35 digital indicator is a multi-function and very accurate instrument for a
wide variety of measuring tasks.
The DI35-D is equipped with two inputs for standard signals (0/4 … 20 mA and
DC 0 … 10 V) that can be used in any combination. The display can show one of the two
input signals or a calculated value. Calculations can be made by means of the four basic
arithmetic operations (+ - * /) and an additional constant multiplier.
In addition, both versions offer the possibility to calibrate sensors and linearise using up
to 30 points. This allows further adaptation of the displayed values to different sensor
signals and application requirements. The standard features are completed by a transmitter power supply, a HOLD function and a TARE function for the correction of offset
shifts and sensor drifts. The sampling rate and display time can be configured and the
display can be dimmed. Unauthorised alteration of the set instrument parameters can
be prevented via different user levels, in conjunction with a freely selectable access
code.
Optionally available are up to four freely configurable switch contacts, an analogue
output signal and a serial interface.
Functions
Calculation function (4 basic calculation types, constant multiplier)
Analogue output
Retrieval of the MIN/MAX value
HOLD and TARE function
Linearisation of the measuring input
Semiconductor switching outputs (option)
Switch point display (option)
Adjustable switch points (option)
14053540.01 03/2016 EN
■■
■■
■■
■■
■■
■■
■■
■■
WIKA operating instructions digital indicator, model DI35-D
9
EN
2. Design and function
2.4 Scope of delivery
Version in desktop case
■■ Digital indicator
■■ Mains connection cable with connector per CEE 7/4
■■ Operating instructions
■■ Unit characters
■■ Mating connector connections
In place of the mains connection cable supplied, other mains connection cables can be
used so long as they fulfil the following characteristics:
■■ Connector per IEC 60320 C13 for connection to the instrument
■■ Protective conductor available
■■ Cable is certified and approved by a recognised notified body for the country of
operation
Cross-check scope of delivery with delivery note.
14053540.01 03/2016 EN
EN
Version for panel mounting
Digital indicator
Sealing
2 mounting elements
Operating instructions
Unit characters
■■
■■
■■
■■
■■
10
WIKA operating instructions digital indicator, model DI35-D
3. Safety
3.Safety
3.1 Explanation of symbols
EN
DANGER!
... identifies hazards caused by electrical power. Should the safety
instructions not be observed, there is a risk of serious or fatal injury.
WARNING!
... indicates a potentially dangerous situation that can result in serious
injury or death, if not avoided.
CAUTION!
... indicates a potentially dangerous situation that can result in light
injuries or damage to property or the environment, if not avoided.
Information
... points out useful tips, recommendations and information for efficient
and trouble-free operation.
3.2 Intended use
The DI35 digital indicator is designed for the evaluation and display of sensor signals.
With the switching outputs, it is possible to realise simple control functions.
The digital indicator is suitable only for indoor applications with pollution degree 2 and
overvoltage category II.
Only use the digital indicator in applications that lie within its technical performance
limits (e.g. max. ambient temperature).
14053540.01 03/2016 EN
→ Performance limits see chapter 11 “Specifications”.
The instrument has been designed and built solely for the intended use described here,
and may only be used accordingly.
The manufacturer shall not be liable for claims of any type based on operation contrary
to the intended use.
WIKA operating instructions digital indicator, model DI35-D
11
3. Safety
3.3 Improper use
WARNING!
Injuries through improper use
Improper use of the instrument can lead to hazardous situations and
injuries.
▶▶ Refrain from unauthorised modifications to the instrument.
▶▶ Do not open the instrument.
▶▶ Do not use the instrument within hazardous areas.
EN
Any use beyond or different to the intended use is considered as improper use.
3.4 Personnel qualification
WARNING!
Risk of injury should qualification be insufficient
Improper handling can result in considerable injury and damage to equipment.
▶▶ The activities described in these operating instructions may only be
carried out by personnel who have the qualifications described below.
14053540.01 03/2016 EN
Skilled electrical personnel
Skilled electrical personnel are understood to be personnel who, based on their
technical training, know-how and experience as well as their knowledge of countryspecific regulations, current standards and directives, are capable of carrying out work
on electrical systems and independently recognising and avoiding potential hazards.
The skilled electrical personnel have been specifically trained for the work environment
they are working in and know the relevant standards and regulations. The skilled
electrical personnel must comply with current legal accident prevention regulations.
12
WIKA operating instructions digital indicator, model DI35-D
3. Safety
3.5 Labelling, safety marks
Product label, panel mounting


 Pin assignment
 Serial number
 Specifications
18...30V / 10...40V (max. 15VA)
2 x DC 0...10V ; DC 0/4...20mA
46855373
DI35-D-2Y5C32B-Z
Power supply:
Input:
Product no:
Product code:
Serial no:
Serial No.
Alarm outputs
EN
Interface
RS-232
(not insulated)
V
mA
RxD
GND
(RS)
TxD
S2
Internal bridge
L/L-
N/L+
-
-
+
Made in Germany
Power supply
24V
Digital input
Transmitter supply
DC 24V, < 50mA
Analogue output
DC 0/4...20mA
DC 0...10V
-
0-5/10V
Input2
0-5/10V
Input1
+
0/4-20mA
+
+
0/4-20mA
+
-
+
1 2 3 4 5 6 7 8 9 10 11 12 13 14
+

S1
21 22 23 24 25 26 27 28 29 30 31 32 41 42 43
Product label, desktop case
S2
V
mA
L
+
N
-
-
+
+
-
+
Made in Germany
Power supply
100... 240V
0-5/10V
Digital input
0-5/10V
Transmitter supply
DC 24V, < 50mA
0/4-20mA
-
0 ...
10V
0/4-20mA
+
0/4...
20mA
+
Internal bridge
1 2 3 4 5 6 7 8 9 10 11 12 13 14
Input2
+
Digital input
4...20mA
425
1
3
687
21 22 23 24 25 26 27 28 29 30 31 32
S1
Alarm outputs
NC
1
-
2
+
NC
4
S2
Plug D (Digital input,
Analogue output)
1 2 3 4 5 6 7 8
Plug B (Input 2)
1 2 3 4
3
S1
+

3
4
2
6
5
1
Serial no.
Alarm outputs
+
4...20mA
Serial no:
Plug C (Relais)
1 2 3 4 5 6
Input1
NC
+
-
1
NC
4
2
100..240V (max. 15VA)
2 x DC 0...10V ; DC 0/4...20mA
46857171
DI35-D-2W5CZJB-Z
Analogue output
DC 0/4...20mA
DC 0...10V
100... 240V (max. 15VA;Fuse 0,5A MT)
Plug A (Input 1)
1 2 3 4
Power supply:
Input:
Product no:
Product code:
NC
NC
NC
Power supply :
3
Made in
Germany
:
-
Serial no.
Analogue
output

Product code : DI35-D-2W5CZJB-Z
Product no. : 46857171
14053540.01 03/2016 EN
 Pin assignment
 Serial number
Symbols
Before mounting and commissioning the instrument, ensure you read the
operating instructions!
WIKA operating instructions digital indicator, model DI35-D
13
4. Transport, packaging and storage
4.Transport, packaging and storage
4.1 Transport
Check the digital indicator for any damage that may have been caused by transport.
Obvious damage must be reported immediately.
CAUTION!
Damage through improper transport
With improper transport, damage to property can occur.
▶▶ When unloading packed goods upon delivery as well as during internal
transport, proceed carefully and observe the symbols on the packaging.
▶▶ With internal transport, observe the instructions in chapter 4.2
“Packaging and storage”.
4.2 Packaging and storage
Do not remove packaging until just before mounting.
Keep the packaging as it will provide optimum protection during transport (e.g. change
in installation site, sending for repair).
Permissible conditions at the place of storage:
■■ Storage temperature: -20 ... +80 °C
■■ Humidity: 0 ... 75 % relative humidity (no condensation)
Avoid exposure to the following factors:
■■ Direct sunlight or proximity to hot objects
■■ Mechanical vibration, mechanical shock (putting it down hard)
■■ Soot, vapour, dust and corrosive gases
Store the digital indicator in its original packaging in a location that fulfils the conditions
listed above. If the original packaging is not available, pack and store the instrument as
described below:
1. Wrap the instrument in a plastic film.
2. Place the instrument, along with shock-absorbent material, in the packaging.
14053540.01 03/2016 EN
EN
14
WIKA operating instructions digital indicator, model DI35-D
5. Commissioning
5.Commissioning
If the instrument is transported from a cold into a warm environment, the formation of
condensation may result in instrument malfunction. Before putting it into operation, wait
for the instrument temperature and the room temperature to equalise.
5.1 Requirements for the installation location
■■ In the vicinity there should be no magnetic or electrical fields, e.g. from transformers,
radio-telephones or electrostatic discharges.
■■ In the vicinity there should be no strong heat sources. The permissible operating
■■
■■
■■
■■
temperature must not be exceeded (max. 50 °C).
The installation location must conform to pollution degree 2.
No direct sunlight or proximity to hot objects
No mechanical vibration, mechanical shock (putting it down hard)
No soot, vapour, dust and corrosive gases
5.2 Mounting, version for panel mounting
10
7,0
0,0
12
48,0
3,0

96
,0
9,0
13

14053540.01 03/2016 EN
 Mounting element with clamping screw
 Sealing
Cutting out the control panel
■■ Control panel thickness max. 50 mm
■■ Panel cutout 92.0+0.6 x 45.0+0.3 mm
Recommended mounting grid: 120 mm horizontal, 96 mm vertical
WIKA operating instructions digital indicator, model DI35-D
15
EN
5. Commissioning
Installing the digital indicator
1. As required, slide the unit characters into the window provided via the lateral channel.
1. Remove the mounting elements.
2. Slide the seal over the digital indicator.
3. Slide the digital indicator into the control panel from the front.
Check the seal is properly seated.
4. Lock the mounting elements into place and tighten the clamping screws (max. 0.1 Nm).
5.3 Mounting, version in desktop case
▶▶ Connect the digital indicator to the socket using the mains connection cable.
5.4 Electrical connection
5.4.1 Notes on installation
■■ The supply must comply with overvoltage category II.
■■ Protect the power supply with a slow fuse of max. 0.5 A.
■■ For the panel-mounting version, a suitable isolation device must be provided.
■■ Route the signal input lines and signal output lines separately.
■■ Route outward and return lines side-by-side.
■■ Galvanically isolated potentials must be connected to a suitable point (e.g. earth or
plant ground).
■■ For high-accuracy requirements and small measurement signals, the sensor wires
must be shielded and twisted. The shield should be connected at one end only to a
suitable equipotential bonding (e.g. measurement ground).
■■ Avoid electrostatic discharges in the area of the terminals.
14053540.01 03/2016 EN
EN
16
WIKA operating instructions digital indicator, model DI35-D
5. Commissioning
5.4.2 Pin assignment, version for panel mounting
Terminal assignment (upper terminal block)
1 2 3 4 5 6 7 8 9 10 11 12 1314
l
0 ... 10 V
+
0/4 ... 20 mA
+
l
0 ... 10 V
+
l
L
N
Voltage supply
Measuring inputs
+
l
Transmitter power supply
0/4 ... 20 mA
+
l
Digital input
+
l
Analogue output
+
For further information see chapter 11 “Specifications”
Terminal assignment (lower terminal block)
Switching outputs
Serial interface
RxD
TxD
Data A (-)
GND
(RS)
GND
(RS)
Data B (+)
S4
S3
RS 232
RS 485
For further information see chapter 11 “Specifications”
14053540.01 03/2016 EN
S2
S1
21 22 23 24 25 26 27 28 29 30 31 32 41 42 43
WIKA operating instructions digital indicator, model DI35-D
17
EN
5. Commissioning
Pin assignment, version in desktop case
1 2 3 4
1 2 3 4 5 6
3
4
2
1
NC
Plug C (switching outputs)
+
NC
-
3
4
2
6
5
1
4 ... 20 mA
2
S2
4
1
425
1
3
6 87
0... 10 V
GND
1 2 3 4 5 6 7 8
TxD
1 2 3 4
RxD
Plug D (transmitter power supply,
analogue output, serial interface)
NC
Plug B (measuring input 2)
+
NC
-
3
S1
+
EN
Plug A (measuring input 1)
Analogue output
Digital input
4 ... 20 mA
RS-232
Suitable mating connectors are included in the delivery.
14053540.01 03/2016 EN
Depending on the version, not all connections are available (instruments without switch
points do not feature a plug C, instruments without analogue output and serial interface
do not feature plug D).
18
WIKA operating instructions digital indicator, model DI35-D
5. Commissioning
5.5 Interface connector
RS-232
The RS-232 interface cables must be connected 1:1 (TxD to TxD and RxD to RxD).
PC or
PLC
EN
DI35
RS-465
The RS-485 interface is connected via a shielded data cable with twisted pairs. At
each end of the bus segment, a termination of the bus lines must be connected. This is
needed in order to ensure safe data transfer over the bus. For this, a resistor (120 Ω) is
inserted between data B (+) and data A (-).
PC or PLC
DATA B (+)
DATA A (―)
DI35
14053540.01 03/2016 EN
Where interfaces are not galvanically isolated, the potential reference
between the interface and the measuring input can lead to a compensating current. This compensating current can influence the measuring
signals.
5.6 Switching on the digital indicator
▶▶ Connect the power supply.
⇒⇒Segment test is carried out. Check the correct operation of all LEDs
⇒⇒Software type and software version are displayed.
⇒⇒Digital indicator is ready for operation.
WIKA operating instructions digital indicator, model DI35-D
19
5. Commissioning
5.7 Connection examples, version for panel mounting
Input 1
Input 2
Analogue
output
Transmitter power
supply
Digital input
2-channel measurement with current signals, 2-wire transmitter, AC 100 ... 240 V supply
Power
supply
AC 100 ... 240 V
2-channel measurement with voltage signals, 3-wire transmitter, DC 10 ... 40 V supply
Input 2
Transmitter power
supply
Power
supply
DC 10 ... 40 V
20
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
Input 1
Analogue
output
Digital input
EN
5. Commissioning
Input 1
Input 2
Analogue
output
Transmitter power
supply
Digital input
1-channel measurement with current signal in conjunction with digital signal and transmitter
power supply, 2-wire transmitter, DC 100 ... 240 V supply
EN
Power
supply
14053540.01 03/2016 EN
AC 100 ... 240 V
WIKA operating instructions digital indicator, model DI35-D
21
6. Operation
6.Operation
6.1 Key functions
Key
Function
[☼] key
Programming mode is accessed
Pressing < 1 s: Changes the cursor position
Pressing > 1 s: Saves all parameters
Key [☼] + [▼] [▲]
Scrolls through the program numbers (PN)
Pressing > 1 s: Automatically starts cycle
[▼] key
Pressing < 1 s: Selects or changes parameter
Pressing > 1 s: Switches the input channel display
[▲] key
Pressing < 1 s: Selects or changes parameter
Pressing > 1 s: Switches the input channel display
Key [○]
Multi-function key
Selects functions (e.g. HOLD or TARE)
6.2 Accessing and exiting programming mode
Accessing programming mode
▶▶ Press [☼].
⇒⇒Digital indicator is in programming mode
⇒⇒Lowest available program number is displayed.
→ Available program numbers are dependent upon the authorisation level, see chapter
7.6.1 “Authorisation levels”.
Exiting the programming mode
If no keys are pressed within 7 seconds, the digital indicator switches back to display
mode.
14053540.01 03/2016 EN
EN
22
WIKA operating instructions digital indicator, model DI35-D
6. Operation
6.3 Menu navigation
[☼]
[☼] 1s
[▲/▼]
PN0
[☼]+[▲]
[☼]+[▼]
[☼]+[▲]
[▲]
[▼]
EN
Parameter 2
Parameter 3
[☼] 1s
[▲/▼]
PN1
Parameter 1
-9999 … 99999
[☼]+[▼]
PN...
6.4 Changing numerical values
Parameter
[☼]
1. Zahl
[☼]
[▲] [▼]
2. Zahl
[▲] [▼]
[☼] 1s
6.5 Accessing or clearing MIN/MAX values
Accessing MIN value
▶▶ Press [▼].
⇒⇒MIN value is displayed 7 s.
14053540.01 03/2016 EN
Accessing MAX value
▶▶ Press [▲].
⇒⇒MAX value is displayed 7 s.
Clearing MIN/MAX values
▶▶ Press [▼] + [▲].
⇒⇒Horizontal bars are displayed.
⇒⇒MIN/MAX values are cleared.
The MIN/MAX values are lost when the instrument is switched off.
WIKA operating instructions digital indicator, model DI35-D
23
6. Operation
The following methods are supported:
Method
Description
Triggered
With each trigger pulse, the measuring input is switched
further (series Ch1, Ch2, Ar).
Cyclic
The change is made cyclically over a preset time interval
(series Ch1, Ch2, Ar).
Static
A preset display value is shown for the duration of the
trigger signal.
For the trigger signal, the multi-function button or the digital input can be used (for
programming, see chapter 7.6 “Switching of measuring inputs”)
Before each change, the description of the measuring input is displayed.
■■ Measuring input 1 = Ch1
■■ Measuring input 2 = Ch2
■■ Arithmetic calculation = Ar
14053540.01 03/2016 EN
EN
6.6 Switching the display between measuring inputs
The switching of measuring inputs changes between the display values of the measuring inputs and the display value of the arithmetic calculation. The display value of the
arithmetic calculation is only displayed when this has been configured.
24
WIKA operating instructions digital indicator, model DI35-D
7. Description of program numbers
7.Description of program numbers
For an overview of the program numbers see appendix 1 “Overview of program
numbers”
EN
7.1 Setting measuring inputs
7.1.1 Input signal
The digital indicator features two measuring inputs. Each measuring input can be set for
a different input signal.
PN
Function
Input signal of measuring input 1
Factory calibration
1 = DC 0 ... 10 V
2 = 0 ... 20 mA
3 = 4 ... 20 mA
5
Input signal of measuring input 2
Sensor calibration
4 = DC 0 ... 10 V
5 = 0 ... 20 mA
6 = 4 ... 20 mA
0
Parameters
Parameters 1 ... 3 Used for standardised input signals. There must be no signal applied
to the measuring input. The corresponding display values can be
manually assigned.
→ For assigning display values, see chapter 7.1.2 “Start and end
value”
Parameters 4 ... 6 Used for non-standardised input signals. The signal must be
applied to the measuring input and the corresponding display value
manually assigned.
14053540.01 03/2016 EN
→ For assigning display values, see chapter 7.1.2 “Start and end
value”
WIKA operating instructions digital indicator, model DI35-D
25
7. Description of program numbers
7.1.2 Start and end value
With this value pair, the measurement signal is assigned the desired indication value.
PN
Function
Parameters
1
End value (end of measuring range)
Measuring input 1
-9999 ... 99999
2
Start value (start of measuring range)
Measuring input 1
-9999 ... 99999
6
End value (end of measuring range)
Measuring input 2
-9999 ... 99999
7
Start value (start of measuring range)
Measuring input 2
-9999 ... 99999
Procedure for standard signals
▶▶ Set the corresponding display values.
Procedure for non-standard input signals.
1. Apply the end value of the input signal to the measuring input.
2. Select PN1/PN6.
3. Set the display value.
4. Press [☼].
⇒⇒Input signal is associated with display value.
5. Apply the start value of the input signal to the measuring input.
6. Select PN2/PN7.
7. Set the display value.
8. Press [☼].
⇒⇒Input signal is associated with display value.
⇒⇒Display values are assigned.
14053540.01 03/2016 EN
EN
26
WIKA operating instructions digital indicator, model DI35-D
7. Description of program numbers
7.1.3 Number of decimal places
Specifies the number of decimal places that are displayed on the screen. This
parameter has no influence on the scaling of the indication value.
PN
Function
Parameters
8
Number of decimal places, measuring input
2
00000 ... 0.0000
3
Number of decimal places, measuring input
1
EN
00000 ... 0.0000
7.1.4 Offset adjustment
The input signal is shifted in parallel by the offset value.
PN
Function
Parameters
9
Offset value, measuring input 2
-9999 ... 99999
4
Offset value, measuring input 1
-9999 ... 99999
This parameter can be altered directly by making a tare if this was
triggered through the multi-function button or the digital input.
7.2 General settings
7.2.1 Default display
Defines the measuring input which should be displayed as standard.
PN
10
Function
Default display
Parameters
1 = Measuring input 1
2 = Measuring input 2
3 = Arithmetic function
14053540.01 03/2016 EN
→ For arithmetic function see chapter 7.3 “Arithmetic function”.
WIKA operating instructions digital indicator, model DI35-D
27
7. Description of program numbers
The following methods are supported:
Method
Description
Triggered
With each trigger pulse, the measuring input is switched
further (series Ch1, Ch2, Ar).
Cyclic
The change is made cyclically over a preset time interval
(series Ch1, Ch2, Ar).
Static
A preset display value is shown for the duration of the
trigger signal.
For the trigger signal, the multi-function button or the digital input can be used (→ see
chapter 7.7 “Setting special inputs”, PN53/PN54)
Before each change, the description of the measuring input is displayed.
■■ Measuring input 1 = Ch1
■■ Measuring input 2 = Ch2
■■ Arithmetic calculation = Ar
PN
11
Function
Switching of measuring inputs
Parameters
0 = Key [▼] [▲] (triggered)
1 = Measuring input 1 (static)
2 = Measuring input 2 (static)
3 = Arithmetic function (static)
4 = Multi-function key (triggered)
5 = Cyclic (5 s)
6 = Cyclic (10 s)
7 = Cyclic (20 s)
14053540.01 03/2016 EN
EN
7.2.2 Switching of measuring inputs
The switching of measuring inputs changes between the display values of the
measuring inputs and the display value of the arithmetic calculation. The display value of
the arithmetic calculation is only displayed when this has been configured.
28
WIKA operating instructions digital indicator, model DI35-D
7. Description of program numbers
7.2.3 Refresh rate
The refresh rate determines how often the display values are updated. With strongly
fluctuating input signals, it is recommended that the refresh rate is adjusted (refresh rate
> 1s).
The refresh rate acts only on the presentation of the display values. Switching outputs
and other functions are not affected.
PN
13
Function
Parameters
Refresh rate
0.1 ... 10.0 s (default 1 s)
7.2.4 Measuring time
PN
14
Function
Measuring time
Parameters
0.4 ... 10.0 s (two measuring inputs)
0.2 ... 10.0 s (one measuring input)
7.2.5 Display brightness
PN
19
Function
Display brightness
Parameters
0 ... 9 (0 = bright, 9 = dark)
7.3 Arithmetic function
Calculation type
Formula
Subtraction
(Measuring input 1 + measuring input 2) ∙ constant
Multiplication
(Measuring input 1 ∙ measuring input 2) ∙ constant
Ratio
(Measuring input 1 / measuring input 2) ∙ constant
Percent
(Measuring input 1 ∙100 ) / measuring input 2
Calculation type
Example applications
Subtraction
Differential measurement (e.g. differential pressure)
Multiplication
Power and energy measurement
Ratio
Mixing ratios
Percent
Percentage ratios
Addition
14053540.01 03/2016 EN
Addition
(Measuring input 1 + measuring input 2) ∙ constant
Incharge and discharge quantities, weighing technology
WIKA operating instructions digital indicator, model DI35-D
29
EN
7. Description of program numbers
PN
15
Function
Parameters
Calculation type
1 = Measuring input 1 ∙ constant
2 = Measuring input 2 ∙ constant
EN
3 = Addition
4 = Subtraction
5 = Multiplication
6 = Ratio
7 = Percent
16
Constant
-9999 ... 99999
17
Number of decimal places of constants
00000 ... 0.0000
18
Number of decimal places of calculation
00000 ... 0.0000
With the calculation of the arithmetic function, all set decimal points are
included (PN3, PN8, PN17, PN18)
7.4 Setting the analogue output (option)
The analogue output gives the measured values of the digital indicator as a standard
signal (DC 0 ... 10 V, 0 ... 20 mA, 4 ... 20 mA).
7.4.1 Start and end value
The analogue output can be assigned any measuring input. The output signal is
updated simultaneously with the measuring input. The refresh rate is determined by
the configured measuring time. The start and end value for the analogue signal can be
assigned user-defined measured values.
The start and end value define at which display value the minimum and maximum
output signal will be given. The display value is dependent upon the setting of the input
signal (→ see chapter 7.1.1 “Input signal”)
PN
Function
Parameters
21
Start value
-9999 ... 99999
30
Full scale
-9999 ... 99999
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
20
7. Description of program numbers
7.4.2 Reference value
The reference value is the value which is given via the analogue output.
PN
22
Function
Reference value
Parameters
EN
0 = Analogue output deactivated
1 = Measuring input 1
2 = Measuring input 2
3 = Arithmetic function
7.4.3 Output signal
PN
23
Function
Output signal
Parameters
0 = DC 0 ... 10 V
1 = 0 ... 20 mA
2 = 4 ... 20 mA
In addition, the output signal must be set via the DIP switch on the rear of
the instrument.
DC 0 ... 10 V = Switch set to the right
0/4 ... 20 mA = Switch set to the left
7.4.4 Example
A rotational speed of 0 ... 3,000 min-1 should be transmitted to a control room via 4 ... 20
mA. The rotational speed sensor is connected to measuring input 1.
1. Set the end value to 3,000.
2. Set the start value to 0.
3. Set the reference value to 1.
14053540.01 03/2016 EN
4. Set the output signal to 2.
5. Set the DIP switch.
⇒⇒Analogue output is set.
WIKA operating instructions digital indicator, model DI35-D
31
7. Description of program numbers
7.5 Setting the serial interface (option)
PN
34
Parameters
Interface properties
0 = Standard mode
1 = Sending mode
Interface properties
Standard mode
(= Configuration mode)
Description
In this mode, the digital indicator can be configured. Responses
will only be transmitted on request.
The current measured value can be queried via “A↵”.
Sending mode
Measured values are sent cyclically. The cycle corresponds to
the set measuring time.
Cancel sending mode
The sending mode is cancelled on receipt of “> ↵” and the instrument returns to standard mode.
Activate sending mode
Restart the digital indicator or transmit the command “S ↵”.
Protocol structure
Display values are transmitted in ASCII format. Minus signs and decimal points can be
displayed directly on a terminal display or processed by a PLC. Leading spaces are
disabled with transmission. With an over- or underflow, hyphens are transmitted “- - - - ↵”.
Example: “0.00 ↵”; “-9.99 ↵” ; “999.99 ↵”; “-123.45”; “ - - - - - ↵”; “Lbr ↵”
The display values can be processed or stored on a PC via a terminal program.
Settings
Point-to-point connection
Transmission rate 9,600 baud
8 data bits
without parity
1 stop bit
■■
■■
■■
■■
■■
14053540.01 03/2016 EN
EN
Function
32
WIKA operating instructions digital indicator, model DI35-D
7. Description of program numbers
7.6 Setting user authorisations
7.6.1 Authorisation levels
Via the user authorisation, it is possible to limit which settings can be made by the
operator. The authorisations can be allocated in different authorisation levels.
Function
PN
Authorisation level
1
2
3
4
5
6
EN
7
8
Changing the display brightness
19








Allocating the locking code
50








Reading the serial number
200








Changing switch points
61, 71, 81, 91







-
Setting the switching output
59 ... 95






-
-
Setting the interface
32 ... 34




-
-
-
-
Setting the analogue output
20 ... 22




-
-
-
-
Setting measuring inputs
0 ... 18



-
-
-
-
-
Carrying out a linearisation
100 ... 170



-
-
-
-
-
Inputting a release code
51

-
-
-
-
-
-
-
Changing the authorisation level
52
-
-
-
-
-
-
-
-
The authorisation levels can only be changed if the release code corresponds to the
locking code (password protection). On delivery, both parameters are set to the value
0000, whereby the programming lockout is deactivated.
PN
Function
Parameters
51
Release code
0000 ... 9999
52
Authorisation level
0 ... 8
50
Locking code
0000 ... 9999
14053540.01 03/2016 EN
7.6.2 Cancelling the password protection
The password protection is cancelled when the release code corresponds to the locking
code.
If the locking code is lost, the instrument can be reset by the
manufacturer.
WIKA operating instructions digital indicator, model DI35-D
33
7. Description of program numbers
7.7 Setting special functions
7.7.1 Function of the digital input
PN
53
Function
Function of the digital input
Parameters
0 = Deactivated
1 = Switching the measuring input
2 = HOLD
3 = TARE
7.7.2 Function of the multi-function key
PN
54
Function
Function of the multi-function key
Parameters
0 = Deactivated
1 = Switching the measuring input
2 = HOLD
3 = TARE
7.7.3 TARE function
The TARE function sets the display value of the stored measuring input to zero. The
difference between zero and the display value is stored as an offset value.
The TARE function overrides a previously programmed offset shift of the
measuring inputs (PN4/9). Should the TARE function be used during a
measurement, the offset shift has to be reprogrammed.
The TARE function can be activated through the multi-function key or the digital input
(→ see chapter 7.7 “Setting special functions”). The key must be activated for at least 3
seconds.
The tare operation is represented as follows:
14053540.01 03/2016 EN
EN
34
WIKA operating instructions digital indicator, model DI35-D
7. Description of program numbers
PN
55
Function
Parameters
TARE function
0 = Deactivated
1 = Measuring input 1
EN
2 = Measuring input 2
3 = Measuring input 1 + 2
7.7.4 HOLD function
The HOLD function freezes the current display value. This is signalled via a flashing
display.
The HOLD function can be activated through the multi-function key or the digital input
(→ see chapter 7.7 “Setting special functions”).
The HOLD function can be switched statically or triggered.
Method
Description
Triggered
The display value is frozen as soon the trigger is activated for
a short time. The function is reset when the trigger is activated
again.
Static
PN
56
A display value is frozen for the duration of the trigger signal.
Function
HOLD function
Parameters
0 = Deactivated
1 = Triggered
14053540.01 03/2016 EN
2 = Static
WIKA operating instructions digital indicator, model DI35-D
35
7. Description of program numbers
7.8.1 Flashing display on reaching the switch points
A switch point being exceeded can be signalled via a simultaneous flashing of the
7-segment display and switch point display.
PN
59
Function
Parameters
Flashing display
0 = not flashing
1 = at switch point 1
2 = at switch point 2
3 = at switch point 3
4 = at switch point 4
5 = at switch point 1 + 2
6 = at switch point 3 + 4
7 = at switch point 1 + 2 + 3 + 4
Reading the switching status
The switching status of the switching outputs can be read from the switch point display.
Switch point display
7.8.2 Reference value
The reference value is the value to which the switching output reacts.
PN
Function
70
Reference value, switching output 2
80
Reference value, switching output 3
90
Reference value, switching output 4
60
36
Reference value, switching output 1
Parameters
0 = Deactivated
1 = Measuring input 1
2 = Measuring input 2
3 = Arithmetic function
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
EN
7.8 Setting the switching outputs
The switching outputs can be configured independently. Each switching output can be
assigned a separate measuring input. The switching outputs react to the measuring
input at any time, regardless of which measuring input is shown on the digital display.
7. Description of program numbers
7.8.3 Switch points
PN
Function
Parameters
71
Switch point, switching output 2
-9999 ... 99999
81
Switch point, switching output 3
-9999 ... 99999
91
Switch point, switching output 4
-9999 ... 99999
61
Switch point, switching output 1
-9999 ... 99999
EN
7.8.4 Switch behaviour
PN
Function
72
Hysteresis, switching output 2
82
Hysteresis, switching output 3
92
Hysteresis, switching output 4
63
Switching function, switching output 1
73
Switching function, switching output 2
83
Switching function, switching output 3
93
Switching function, switching output 4
64
Switching delay, switching output 1
74
Switching delay, switching output 2
84
Switching delay, switching output 3
94
Switching delay, switching output 4
65
Delay type, switching output 1
75
Delay type, switching output 2
85
Delay type, switching output 3
95
Delay type, switching output 4
Hysteresis, switching output 1
Parameters
1 ... 99999
0 = Normally closed
1 = Normally open
0 ... 10 seconds
0 = none
1 = Switch-on delay
2 = Switch-off delay
3 = Switch-on and switch-off delay
14053540.01 03/2016 EN
62
WIKA operating instructions digital indicator, model DI35-D
37
7. Description of program numbers
Measured value
Messwert
Switch point
Schaltpunkt
Hysterese
Hysteresis
Time
Zeit
Switching status
Schaltzustand
on
ein
aus
off
Time
Zeit
14053540.01 03/2016 EN
EN
Normally open
Below the switch point, the switching output is switched off. On reaching the switch
point, the switching output is switched on.
The switching output is switched off only when the switch point, less the hysteresis, is
reached.
38
WIKA operating instructions digital indicator, model DI35-D
7. Description of program numbers
Normally closed
Below the switch point, the switching output is switched on. On reaching the switch
point, the switching output is switched off.
The switching output is switched on only when the switch point, less the hysteresis, is
reached.
Measured value
Messwert
Schaltpunkt
Switch point
Hysterese
Hysteresis
Time
Zeit
Switching status
Schaltzustand
on
ein
Time
Zeit
14053540.01 03/2016 EN
aus
off
WIKA operating instructions digital indicator, model DI35-D
39
EN
7. Description of program numbers
Measured value
Messwert
Schaltpunkt
Switch point
Time
Zeit
Switching status
Schaltzustand
on
ein
aus
off
Time
Zeit
Einschaltverzögerung
Switching delay
14053540.01 03/2016 EN
EN
Switch-on delay
The switching output is switched on only when the input signal remains above the switch
point for at least the set switching delay.
This function prevents an unwanted switching of the switching output as a result of a
short-term fluctuation of the input signal.
40
WIKA operating instructions digital indicator, model DI35-D
7. Description of program numbers
Switch-off delay
The switching output is switched off only when the input signal remains under the switch
point for at least the set switching delay.
This function prevents an unwanted switching of the switching output as a result of a
short-term fluctuation of the input signal.
Measured value
Messwert
Schaltpunkt
Switch point
Time
Zeit
Switching status
Schaltzustand
on
ein
aus
off
Time
Zeit
14053540.01 03/2016 EN
Ausschaltverzögerung
Switching delay
WIKA operating instructions digital indicator, model DI35-D
41
EN
7. Description of program numbers
Each interpolation point must have a higher input signal than the previous. The corresponding display values can be freely assigned.
PN
Function
Parameters
101 ... 130
Display value for interpolation point,
measuring input 1
-9999 ... 99999
140
Number of interpolation points, measuring
input 2
0 ... 30
141 ... 170
Display value for interpolation point,
measuring input 2
-9999 ... 99999
100
Number of interpolation points, measuring
input 1
0 ... 30
Procedure
1. Set the number of interpolation points under PN100/PN140.
2. Apply the input signal for the first interpolation point, PN101/PN141, at the
measuring input.
3. Set the desired display value under PN101/PN141.
⇒⇒Input signal is associated with display value.
4. Repeat steps 2 + 3 for all interpolation points.
⇒⇒Input signal is linearised.
14053540.01 03/2016 EN
EN
7.9 Linearising sensors
Non-linear sensors can be linearised with up to 30 interpolation points per measuring
input.
At each interpolation point, the input signal is assigned a new display value manually.
The analogue output is also linearised since it is proportional to the display values.
42
WIKA operating instructions digital indicator, model DI35-D
7. Description of program numbers
Example
Linearisation of a pressure transmitter for 0 ... 100 mbar with an output signal of 0 ... 20 mA.
■■ Programming with 5 interpolation points.
■■ Non-linear range 0 ... 75 mbar.
Interpolation
point
Pressure
[mbar]
Transmitter
output signal
[mA]
Display value [mbar]
PN2
0
0.5
PN101
15
PN102
PN103
before
linearisation
after linearisation
2.5
0.0
3.3
16.5
15.0
30
6.2
31.0
30.0
40
9.2
46
40.0
PN104
60
11.4
57
60.0
PN105
75
14.7
73.5
75.0
PN1
100
20
100.0
100.0
For PN101 this means:
With a pressure of 15 mbar, the transmitter delivers an output signal of 3.3 mA instead
of 3.0 mA. Therefore, before correction, the display shows 16.5 mbar. This value is
adjusted to 15.0 mbar using the interpolation point.
Anzeigewert
Display value
100
90
80
105
70
60
104
50
40
30
14053540.01 03/2016 EN
Mit Linearisierung
With
linearisation
103
Ohne Linearisierung
Without
linearisation
102
20
Stützpunkte points
Interpolation
101
10
10
20
30
40
50
60
70
80
90
WIKA operating instructions digital indicator, model DI35-D
100
110
Druck
Measured
value
43
EN
7. Description of program numbers / 8. Faults
7.10 Reading the serial number
PN
200
Parameters
Serial number
0 ... 99999
7.11 Restore factory settings
The factory settings can only be restored if the programming lock PN50 allows access
to all PNs or HELP is displayed. All application-specific data will be lost.
1. Switch off the power supply.
2. Press the multi-function key.
3. Apply power supply and hold the multi-function key for 2 s.
⇒⇒Factory settings are restored.
8.Faults
CAUTION!
Physical injuries and damage to property and the environment
If faults cannot be eliminated by means of the measures listed above,
the instrument must be taken out of service immediately.
▶▶ Ensure that pressure or signal is no longer present and protect against
accidental commissioning.
▶▶ Contact the manufacturer.
▶▶ If a return is needed, follow the instructions given in chapter 10.2
“Returns”.
Faults
Instrument shows permanent
overflow
Causes
One of the measuring inputs
has a very high measured
value
Measures
Check measuring path
With a measuring input with
a small voltage signal, this is
only connected on one side or
the input is open
Not all activated interpolation
points are parameterised
Check relevant parameter
The arithmetic result gives an
overflow
44
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
EN
Function
8. Faults
Faults
Instrument shows a permanent underflow
Causes
One of the measuring inputs
has a very small measured
value
Measures
Check measuring path
EN
With a measuring input with
a small voltage signal, this is
only connected on one side or
the input is open
Not all activated interpolation
points are parameterised
Check relevant parameter
The arithmetic result gives an
underflow
Instrument displays “HELP”
Error in the configuration
memory
Restore factory settings and
re-enter the settings
Display values are changing in
very large jumps
With a division, the measured
value of the divisor is very
small
Check measuring path
Program numbers are not
available
Access through user authorisation denied
Set sensor type is preventing
the desired program number
from being parameterised.
The analogue output is an
option. If this is not implemented, then the
program numbers are hidden
Contact the manufacturer
Digital input does not react
Measure input current of
digital input. It should lie
between 1 ... 3 mA.
14053540.01 03/2016 EN
Instrument displays “Err1”
WIKA operating instructions digital indicator, model DI35-D
45
8. Faults
Overflow and underrflow display
Each over- or underflow of a measuring input relates to a defined display. This definition
ensures that the appropriate switch points go to a defined state.
Calculation type
Addition
Subtraction
Multiplication
Division
Percent
Channel 1
Channel 2
Results
Underflow
OK or underflow
Underflow
OK or overflow
Overflow
Overflow
OK or underflow
Underflow
Underflow
Overflow
Underflow
Overflow
Overflow
OK or overflow
Overflow
Underflow
OK or underflow
Underflow
OK or overflow
Overflow
Overflow
OK or underflow
Underflow
Underflow
Overflow
Underflow
Overflow
Overflow
OK or overflow
Overflow
Underflow
OK or underflow
Underflow
OK or overflow
Overflow
Overflow
OK or underflow
Underflow
Underflow
Overflow
Underflow
Overflow
Overflow
as required
Overflow
Underflow
as required
Underflow
OK
Overflow
Underflow
OK
Underflow
Underflow
Overflow
as required
Overflow
Underflow
as required
Underflow
OK
Overflow
Underflow
OK
Underflow
Underflow
Overflow
Illustration of overflow
46
OK or overflow
Overflow
Illustration of underflow
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
EN
9. Maintenance and cleaning
9.Maintenance and cleaning
9.1 Maintenance
This digital indicator is maintenance-free.
Repairs must only be carried out by the manufacturer.
EN
9.2 Cleaning
DANGER!
Danger to life caused by electric current
Upon contact with live parts, there is a direct danger to life.
▶▶ Only clean the case and contacts when the current is disconnected.
CAUTION!
Unsuitable cleaning agents
Cleaning with unsuitable cleaning agents may damage the instrument
and the product label.
▶▶ Do not use any aggressive cleaning agents.
▶▶ Do not use any hard or pointed objects.
▶▶ Do not use any abrasive cloths or sponges.
14053540.01 03/2016 EN
1. Disconnect the digital indicator from the supply.
2. Wipe the instrument surface using a soft, damp cloth.
WIKA operating instructions digital indicator, model DI35-D
47
10. Dismounting, return and disposal
10.Dismounting, return and disposal
10.1 Dismounting, version for control panel
1.
2.
3.
4.
Disconnect the digital indicator from the supply.
Disconnect the electrical connection.
Remove the mounting elements.
Pull the digital indicator out of the control panel.
10.2 Return
Strictly observe the following when shipping the instrument:
All instruments delivered to WIKA must be free from any kind of hazardous substances
(acids, bases, solutions, etc.) and must therefore be cleaned before being returned.
When returning the instrument, use the original packaging or a suitable transport
packaging.
Information on returns can be found under the heading “Service” on our
local website.
10.3 Disposal
Incorrect disposal can put the environment at risk.
Dispose of instrument components and packaging materials in an environmentally
compatible way and in accordance with the country-specific waste disposal regulations.
14053540.01 03/2016 EN
EN
48
WIKA operating instructions digital indicator, model DI35-D
11. Specifications
11.Specifications
Specifications
Digital indicator
Principle
7-segment LED, red, 5-digit, brightness adjustable in 10
gradations
Character size
14 mm
Indication range
-9999 ... 99999
Display rate
0.1 ... 10.0 seconds
Memory
EEPROM (parameter memory), data preservation > 100 years
Inputs
Inputs
2 x input for standard signals
Input signals, version for
panel mounting
0 ... 20 mA, Ri ≈ 50 Ω
4 ... 20 mA, Ri ≈ 50 Ω
DC 0 ... 10 V, Ri ≈ 150 kΩ
Input signals, version in
desktop case
4 ... 20 mA, Ri ≈ 50 Ω
Input configuration
Selectable via terminal connections and menu-driven
programming
Accuracy
See the following tables “Accuracy/measuring errors of the input
signals”
Temperature error
50 ppm/K, at ambient temperature TU < 20 °C or
TU > 40 °C
Measuring principle
Sigma/delta
Resolution
24 bit (with 1 second measuring time)
Measuring time
0.02 ... 10.0 s, with 1-channel measurement
0.04 ... 10.0 s, with 2-channel measurement
Transmitter power supply
DC 24 V, max. 50 mA, galvanically isolated incl. one
digital input
Analogue output (option)
14053540.01 03/2016 EN
EN
Number and type
1 analogue output (galvanically isolated)
Output signal
4 ... 20 mA (12-bit), load ≤ 500 Ω
0 ... 20 mA (12-bit), load ≤ 500 Ω
DC 0 ... 10 V (12-bit), load ≥ 100 kΩ
Error
0.1 % in the range 20 ... 40 °C
50 ppm/K outside temperature error
Internal resistance
100 Ω (with measuring input DC 0 ... 10 V)
WIKA operating instructions digital indicator, model DI35-D
49
11. Specifications
Specifications
Switching output (option)
2 or 4 switch contacts (relays), freely programmable
Load capacity
AC 230 V, 5 A (resistive load)
DC 30 V, 5 A (resistive load)
Number of switching
operations
0.5 ∙105 at max. contact load
5 ∙ 106 mechanical
Isolation in accordance with DIN EN 50178
Parameters in accordance with DIN EN 60255
Voltage supply
Power supply
See product label
Power supply galvanically isolated
AC 100 ... 240 V, 50/60 Hz, DC 100 ... 240 V
DC 10...40 V, AC 18 ... 30 V, 50/60 Hz
Overvoltage category II
Power consumption
Max. 15 VA
Electrical connection
Removable plug-in terminal
Wire cross-section up to 2.5 mm²
Fuse
Integrated fuse
0.5 A medium-acting (not to be changed by operator)
Serial interface (option)
Interface
See product label
■■ RS-232 (not galvanically isolated)
■■ RS-232 (galvanically isolated)
■■ RS-485 (not galvanically isolated, only for point-to-point
connection)
■■ RS-485 (galvanically isolated, only for point-to-point
connection)
Protocol
Manufacturer-specific ASCII
Baud rate
9,600 baud, no parity, 8 data bits, 1 stop bit
Cable length
RS-232: max. 3 m
RS-485: max. 1,000 m
Case, panel mounting
Material
Glass-fibre reinforced polycarbonate, black
Ingress protection
Front: IP65, rear: IP00 (per IEC 60529 / EN 60529)
Weight
approx. 450 g
Recommended mounting grid
120 mm horizontal, 96 mm vertical
Mounting
Sliding mounting elements, fixed via screws, for wall thicknesses up to 50 mm
50
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
EN
Number and type
11. Specifications
Specifications
Case, desktop case
Material
Front, rear, side plates: aluminium, black, powder-coated
Cover, base plate: hard paper, black (Pertinax)
Ingress protection
IP40
Weight
approx. 1.6 kg
Operating conditions
EN
Permissible ambient
temperatures
Operation: 0 ... 50 °C
Storage: -20 ... +80 °C
Humidity
0 ... 75 % r. h. annual mean, without condensation
Requirements for the
installation location
■■ Pollution degree 2
■■ No direct sunlight or proximity to hot objects
■■ No mechanical vibration, mechanical shock (putting it down
hard)
■■ No soot, vapour, dust or corrosive gases
CE conformity
EMC directive
2004/108/EC, interference emission and interference immunity
in accordance with EN 61326-1, emission (group 1, class B)
und interference immunity (industrial application)
Low voltage directive
2006/95/EC, EN 61010-1
Accuracy/measuring errors of the input signals
Inputs with factory calibration
Input signals
Measuring error in Minimum measuring
% of the measur- time
ing span 1)
1-channel
2-channel
measurement
measurement
0 ... 20 mA
±0.02 % ±1 digit
0.02 s
0.04 s
4 ... 20 mA
±0.02 % ±1 digit
0.02 s
0.04 s
14053540.01 03/2016 EN
Current signals
Measuring
span
WIKA operating instructions digital indicator, model DI35-D
51
11. Specifications
Measuring
span
EN
Voltage signals
Thermocouples
Measuring error in Minimum measuring
% of the measur- time
ing span 1)
1-channel
2-channel
measurement
measurement
DC 0 ... 18 mV
±0.06 % ±1 digit
-
-
DC 0 ... 35 mV
±0.06 % ±1 digit
-
-
DC 0 ... 75 mV
±0.04 % ±1 digit
-
-
DC 0 ... 150 mV
±0.03 % ±1 digit
-
-
DC 0 ... 300 mV
±0.03 % ±1 digit
-
-
DC 0 ... 600 mV
±0.03 % ±1 digit
-
-
DC 0 ... 1,250 mV
±0.03 % ±1 digit
-
-
DC 0 ... 2,500 mV
±0.03 % ±1 digit
-
-
DC 0 ... 5 V
±0.02 % ±1 digit
-
-
DC 0 ... 10 V
±0.01 % ±1 digit
0.02 s
0.04 s
Type B, PtRh-PtRh
-100 ... +1,810 °C
±0.10 % ±1 digit
-
-
Type E, NiCr-CuNi
-260 ... +1,000 °C
±0.06 % ±1 digit
-
-
Type J, Fe-CuNi
-210 ... +1,200 °C
±0.05 % ±1 digit
-
-
Type K, NiCr-Ni
-250 ... +1,271 °C
±0.05 % ±1 digit
-
-
Type L, Fe-CuNi
-200 ... +900 °C
±0.06 % ±1 digit
-
-
Type N, NiCrSi-NiSI
-250 ... +1,300 °C
±0.06 % ±1 digit
-
-
Type R, PtRh-Pt
0 ... 1,760 °C
±0.07 % ±1 digit
-
-
Type S, PtRh-Pt
0 ... 1,760 °C
±0.06 % ±1 digit
-
-
Type T, Cu-CuNi
-240 ... +400 °C
±0.07 % ±1 digit
-
-
Resistance thermometer 2)
Pt100 (2-/4-wire)
-200 ... +850 °C
±0.04 % ±1 digit
-
-
Pt100 (3-wire)
-200 ... +850 °C
±0.04 % ±1 digit
-
-
Pt200 (2-/4-wire)
-200 ... +850 °C
±0.04 % ±1 digit
-
-
Pt200 (3-wire)
-200 ... +850 °C
±0.04 % ±1 digit
-
-
Pt500 (2-/4-wire)
-200 ... +850 °C
±0.04 % ±1 digit
-
-
Pt500 (3-wire)
-200 ... +850 °C
±0.04 % ±1 digit
-
-
Pt1000 (2-/4-wire)
-200 ... +850 °C
±0.04 % ±1 digit
-
-
Pt1000 (3-wire)
-200 ... +850 °C
±0.04 % ±1 digit
-
-
1) The indication of the measuring error applies to ambient temperatures 20 ... 40 °C and the measuring time of
1 second.
2) The indications for Pt100 3-/4-wire apply at a max. lead resistance of 10 Ω.
52
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
Input signals
11. Specifications
Inputs for sensor calibration
Input signals
Current signals
Voltage signals
Resistance (2-,
3-, or 4-wire)
Measuring span
Measuring error in Minimum measuring
% of the measurtime
ing span 1)
1-channel
2-channel
measurement
measurement
0 ... 2 mA
±0.02 % ±1 digit
-
-
0 ... 5 mA
±0.02 % ±1 digit
-
-
0 ... 20 mA
±0.02 % ±1 digit
0.02 s
0.04 s
4 ... 20 mA
±0.02 % ±1 digit
0.02 s
0.04 s
DC -18 ... +18 mV
±0.06 % ±1 digit
-
-
DC -35 ... +35 mV
±0.06 % ±1 digit
-
-
DC -75 ... +75 mV
±0.04 % ±1 digit
-
-
DC -150 ... +150 mV
±0.03 % ±1 digit
-
-
DC -300 ... +300 mV
±0.03 % ±1 digit
-
-
DC -500 ... +600 mV
±0.03 % ±1 digit
-
-
DC -500 ... +1,250 mV
±0.03 % ±1 digit
-
-
DC -500 ... +2,500 mV
±0.03 % ±1 digit
-
-
DC -1 ... +5 V
±0.02 % ±1 digit
-
-
DC -1 ... +10 V
±0.01 % ±1 digit
0.02 s
0.04 s
0 Ω ... 100 Ω
±0.04 % ±1 digit
-
-
0 Ω ... 1 kΩ
±0.04 % ±1 digit
-
-
0 Ω ... 10 kΩ
±0.04 % ±1 digit
-
-
14053540.01 03/2016 EN
1) The indication of the measuring error applies to ambient temperatures 20 ... 40 °C and the measuring time of
1 second.
WIKA operating instructions digital indicator, model DI35-D
53
EN
11. Specifications
Dimensions in mm
Digital indicator
EN
inc
luedins
inchglie 10
fißxlich 7,0
ingBe
afettstig
acung
hm
e
0,0
12
nts
DI3
5
3,0
DS
ice
hta
unli
gn
48,0
g
om
cktlie
uess
cnhnl
s
o
n
gh Ac
dßilnic
hlulie ,0
nnscc 139
i
i
e
h
efte
tip
adue
innb
rtiEo
96
,0
l
na
mi
er
nmte
e
Ins
Desktop case
7
y
pla
dis
ler
up
co
l.
inc
w
14053540.01 03/2016 EN
82
82,0
mm97)
(with
feet
(mit Füßen 97 mm)
aufgestellt
127 mm)
(feet(Füße
folded
out
127)
(26
l.
inc
d
an
m
7m
(26
rs
0
25 ecto
nn
co
ut
o
ith
tin
ma
r)
cke
nste
ge
Ge
ne
h
o
ker
mm tec
0,0 sss
25 chlu
ns
dA
n
eu
zeig
An
)
tor
ec
nn
o
gc
11770,0 m
0m
54
WIKA operating instructions digital indicator, model DI35-D
Appendix 1: Overview of program numbers
Appendix 1: Overview of program numbers
PN
Function
Measuring input 1
0
Measuring input
Parameter
Factory
setting
Authorisation level
0 = N/A
0
2
Factory calibration
1 = DC 0 ... 10 V
2 = 0 ... 20 mA
3 = 4 ... 20 mA
Sensor calibration
4 = DC 0 ... 10 V
5 = 0 ... 20 mA
6 = 4 ... 20 mA
1
Full scale
-9999 ... 99999
10000
2
2
Start value
-9999 ... 99999
0
2
3
Decimal places
00000 ... 0.0000
00000
2
4
Offset adjustment
-9999 ... 99999
0
2
0 = N/A
0
2
Measuring input 2
5
Measuring input
Factory calibration
1 = DC 0 ... 10 V
2 = 0 ... 20 mA
3 = 4 ... 20 mA
14053540.01 03/2016 EN
Sensor calibration
4 = DC 0 ... 10 V
5 = 0 ... 20 mA
6 = 4 ... 20 mA
6
Full scale
-9999 ... 99999
10000
2
7
Start value
-9999 ... 99999
0
2
8
Decimal places
00000 ... 0.0000
00000
2
9
Offset adjustment
-9999 ... 99999
0
2
WIKA operating instructions digital indicator, model DI35-D
55
EN
PN
EN
Function
General settings
Parameter
Factory
setting
Authorisation level
10
Default display
1 = Measuring input 1
2 = Measuring input 2
3 = Arithmetic function
3
2
11
Switching of measuring
inputs
0 = Key [▼] [▲] (triggered)
1 = Measuring input 1
(static)
2 = Measuring input 2
(static)
3 = Arithmetic function
(static)
4 = Multi-function key
(triggered)
5 = Cyclic (5 s)
6 = Cyclic (10 s)
7 = Cyclic (20 s)
0
2
13
Refresh rate
0.1 ... 10.0 s
1.0
2
14
Measuring time
0.4 ... 10.0 s (two measuring inputs)
0.2 ... 10.0 s (one measuring input)
0.2
2
19
Display brightness
0 ... 9
3
8
Arithmetic function
15
Calculation type
1 = Measuring input 1 ∙
constant
2 = Measuring input 2 ∙
constant
3 = Addition
4 = Subtraction
5 = Multiplication
6 = Ratio
7 = Percent
3
2
16
Constant
-9999 ... 99999
1
2
17
Number of decimal
places of constants
00000 ... 0.0000
00000
2
18
Number of decimal
places of calculation
00000 ... 0.0000
00000
2
56
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
Appendix 1: Overview of program numbers
Appendix 1: Overview of program numbers
PN
Function
Analogue output (option)
Factory
setting
Authorisation level
20
Full scale
-9999 ... 99999
10000
2
21
Start value
-9999 ... 99999
0
2
22
Reference value
0 = Deactivated
1 = Measuring input 1
2 = Measuring input 2
3 = Arithmetic function
3
2
23
Output signal
0 = DC 0 ... 10 V
1 = 0 ... 20 mA
2 = 4 ... 20 mA
2
4
0 = Standard mode
1 = Transmission mode
0
4
Interface
34
Interface properties
User authorisation
50
Locking code
0000 ... 9999
0000
8
51
Release code
0000 ... 9999
0000
0
52
Authorisation level
0 ... 8
8
0
Special functions
14053540.01 03/2016 EN
Parameter
53
Function of the digital
input
0 = Deactivated
1 = Switching the measuring input
2 = HOLD
3 = TARE
0
2
54
Function of the multifunction key
0 = Deactivated
1 = Switching the measuring input
2 = HOLD
3 = TARE
0
2
55
TARE function
0 = Deactivated
1 = Measuring input 1
2 = Measuring input 2
3 = Measuring input 1 + 2
0
2
56
HOLD function
0 = Deactivated
1 = Triggered
2 = Static
0
2
WIKA operating instructions digital indicator, model DI35-D
EN
57
Appendix 1: Overview of program numbers
Function
Parameter
59
Flashing display
0 = Deactivated
1 = at switch point 1
2 = at switch point 2
1 = at switch point 1 + 2
4 = at switch point 3 + 4
5 = at switch point 1 + 2 +
3+4
0
6
Switching output 1
Factory
setting
Authorisation level
60
Reference value
0 = Deactivated
1 = Measuring input 1
2 = Measuring input 2
3 = Arithmetic function
1
6
61
Switch point
-9999 ... 99999
1000
6
62
Hysteresis
1 ... 99999
1
6
63
Switching function
0 = Normally closed
1 = Normally open
1
6
64
Switching delay
0 ... 10.0 seconds
0.0
6
65
Delay type
0 = none
1 = Switch-on delay
2 = Switch-off delay
3 = Switch-on and switchoff delay
1
6
Switching output 2
70
Reference value
0 = Deactivated
1 = Measuring input 1
2 = Measuring input 2
3 = Arithmetic function
1
6
71
Switch point
-9999 ... 99999
1000
6
72
Hysteresis
1 ... 99999
1
6
73
Switching function
0 = Normally closed
1 = Normally open
1
6
74
Switching delay
0 ... 10.0 seconds
0.0
6
75
Delay type
0 = none
1 = Switch-on delay
2 = Switch-off delay
3 = Switch-on and switchoff delay
1
6
58
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
EN
PN
Appendix 1: Overview of program numbers
PN
Function
Switching output 3
Parameter
Factory
setting
Authorisation level
80
Reference value
0 = Deactivated
1 = Measuring input 1
2 = Measuring input 2
3 = Arithmetic function
1
6
81
Switch point
-9999 ... 99999
1000
6
82
Hysteresis
1 ... 99999
1
6
83
Switching function
0 = Normally closed
1 = Normally open
1
6
84
Switching delay
0 ... 10.0 seconds
0.0
6
85
Delay type
0 = none
1 = Switch-on delay
2 = Switch-off delay
3 = Switch-on and switchoff delay
1
6
Switching output 4
Reference value
0 = Deactivated
1 = Measuring input 1
2 = Measuring input 2
3 = Arithmetic function
1
6
91
Switch point
-9999 ... 99999
1000
6
92
Hysteresis
1 ... 99999
1
6
93
Switching function
0 = Normally closed
1 = Normally open
1
6
94
Switching delay
0 ... 10.0 seconds
0.0
6
95
Delay type
0 = none
1 = Switch-on delay
2 = Switch-off delay
3 = Switch-on and switchoff delay
1
6
14053540.01 03/2016 EN
90
EN
WIKA operating instructions digital indicator, model DI35-D
59
Appendix 1: Overview of program numbers
PN
Linearisation
Parameter
Factory
setting
Authorisation level
0
2
100
Number of interpolation
points
Measuring input 1
0 ... 30
101
...
130
Display value for interpolation point
Measuring input 1
-9999 ... 99999
140
Number of interpolation
points
Measuring input 2
0 ... 30
141
...
170
Display value for interpolation point
Measuring input 2
-9999 ... 99999
2
0 ... 99999
8
Serial number
200
Reading the serial
number
2
0
2
14053540.01 03/2016 EN
EN
Function
60
WIKA operating instructions digital indicator, model DI35-D
Appendix 2: EC declaration of conformity
14053540.01 03/2016 EN
EN
WIKA operating instructions digital indicator, model DI35-D
61
14053540.01 03/2016 EN
EN
62
WIKA operating instructions digital indicator, model DI35-D
14053540.01 03/2016 EN
EN
WIKA operating instructions digital indicator, model DI35-D
63
14053540.01 03/2016 EN
WIKA Alexander Wiegand SE & Co. KG
Alexander-Wiegand-Straße 30
63911 Klingenberg • Germany
Tel. +49 9372 132-0
Fax +49 9372 132-406
[email protected]
www.wika.de
64