gtc110701 ARC
AMI Redundant Controller
GAI-TRONICS®
10962-001 and 10962-002
A Hubbell Company
Features
• Allows two GAI-Tronics Audio
Messenger Interface units to be
used in an “active / backup”
configuration
• May be used with either Page/Party® or
public address systems
• Single or dual configurations
Options
• Model 10962-001 — Single AMI Redundant Controller
• Model 10962-002 — Dual AMI Redundant Controller
The model 10962-001 and 10962-002 AMI Redundant
Controllers (ARCs) are designed for use with either GAITronics Page/Party® or public address systems when
redundant alarm tone/speech generators are required.
“active” alarm generator and the other AMI acts as the
“back-up.” Both AMIs are powered up and running. The
ARC module(s) determine which AMI is active and which
is the backup.
ARC modules work in conjunction with a pair of GAITronics Audio Messenger Interfaces (AMIs). Each AMI acts
as an alarm tone/speech generator to produce emergency tones and/or prerecorded speech messages.
During normal alarm operation, input contacts are
applied simultaneously to both the active and back-up
AMIs. The ARC module(s) allow only audio from the active
generator to play over the system speakers. The back-up
AMI is held in standby mode to prevent mixing of the two
AMI tone/speech messages.
The ARC and AMI devices can be connected in two different configurations depending on system requirements. If
both AMIs are to be installed at the same location, one
model 10962-002 ARC Module can be used to control
both AMIs. If the AMIs must be installed at separate locations, one model 10960-001 ARC Module is required at
each location. In either configuration, one AMI acts as the
GAI-TRONICS® A Hubbell Company
In the event of the active AMI failing, the back-up AMI
becomes active and plays its audio over the system
speakers.
1-800-492-1212
www.gai-tronics.com
AMI Redundant Controller | 10962-001 and 10962-002
Typical Applications
Audio to Page/Party®
system or PA amplifier
Audio to Page/Party®
system or PA amplifier










Data
(RS-232/
RS-485)
Data
(RS-232/
RS-485)
Data
(RS-232/
RS-485)

Data (Ethernet)
10962-001
ARC #2



10962-002
Dual ARC



 
10962-001
ARC #1
 


AMI #2



Data
(RS-232/
RS-485)
AMI #1

AMI #2

AMI #1
Data (Ethernet)
Alarm activation
and reset contacts
Alarm activation
and reset contacts
10962-001 Single Redundant Controller application block diagram
10962-002 Dual Redundant Controller application block diagram
Specifications
Power Supply Requirements
Connection to a 12 to 24 V dc (UL-listed) Class 2 power source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.2 amps minimum
Power Consumed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 watts maximum
Electrical
Logic Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sink 100 mA per output to circuit common (must be powered from an
external power supply of the same voltage as the ARC module)
Mechanical
Enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Steel body and cover, black fine-textured paint finish
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Rack-mount, 1U standard 19-inch rack
Dimensions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19.00 W x 5.30 D x 1.75 H inches (431 W x 135 D x 44 H mm) nominal
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 lbs (2.3 kg)
Environmental
Temperature Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . +32°F to +122°F (0°C to +50°C)
Pub. 110701
GAI-Tronics® USA (Corporate) Toll Free: 1 (800) 492-1212 Tel: (610) 777-1374 Fax: (610) 796-5954 www.gai-tronics.com
GAI-Tronics® UK Tel: +44 (0)1283 500500 Fax: +44 (0)1283 500400 www.gai-tronics.co.uk
GAI-Tronics® S.r.l - Italy Tel: +39 02 48601460 Fax: +39 02 93663110 www.gai-tronics.it
GAI-Tronics® Malaysia Tel: +60-3-8945-4035 / 8945-7348 Fax: +60-3-8945-4675 www.gai-tronics.com
GAI-Tronics® Austdac - Australia Tel: 011-61-28-851-5000 Fax: 011-61-29-899-2490 www.austdac.com.au
Quality Management System Certified by DNV - ISO 9001:2008