S19-310DCBF

S19-310DCBF
Installation
S19-310DCBF
Barrier Free Stainless Steel
Eyewash
Table of Contents
Pre-Installation Information . . . . . . . . . . . . . . . . . . . . . .
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Assembly of Components . . . . . . . . . . . . . . . . . . . . . . .
Parts List . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
215-619DCBF Rev. S; ECN 08-512
© 2008 Bradley Corporation
Page 1 of 5
9/11/08
2
3
4
5
P.O. Box 309, Menomonee Falls, WI USA 53052-0309
PHONE 800.BRADLEY (800.272.3539) FAX 262.251.5817
bradleycorp.com
S19-310DCBF
Installation
WARNING
Read this installation manual completely to ensure proper installation, then file it
with the owner or maintenance department. Compliance and conformity to drain
requirements and other local codes and ordinances is the responsibility of the installer.
Installation
Packing List
IS
TH
SIDE
UP
•
•
•
•
Separate parts from packaging and make sure all parts are accounted for before
discarding any packaging material. If any parts are missing, do not begin installation
until you obtain the missing parts.
Flush the water supply lines before beginning installation and after installation is
complete. Test the unit for leaks and adequate water flow. Main water supply to the
eyewash should be “ON” at all times. Provisions shall be made to prevent unauthorized
shutoff.
Da
Da te
Da tum
te
Sig ned
Sig ned
ned
P.O
TES
. Box
DIE
ESS SEST THI
309
Tes AI
S
, Me
Rep t-op HEBGER UNI
Ven ort
nom
DO ÄT T EAC
1ST
dur til(e anyera
te MA
one
H
Tes ch )
val DAI WÖ WE
e
sig
Un wö ma ve( RE CHE EK
Fal
un ne t le
ters che lfun s)
ls,
NTL
rap en fon
WI
chr ntli ctio eac
ICH
por basctio
530
ns h
ift. ch
t imm. nne
ZU
immwe
Jeg im
51
S'il
ek
me
PRÜ
Tes
edi and
édi y à nt lich
tbe
FEN
Sig
ate
ate que des e Stö
trie
Un ned
.
ly. sig
me lqu val
n
Sig ter
nt. e ves run b prü
bel
g
cho
ne sch
ow
sof fen
rift
.
se cha
ort , bes
qui que
Da
me
ne sem ldetäti
Da te
va ain n. gt
Da te
pas e
te
Sig
fait et
R
The ANSI Z358.1 standard requires an uninterruptible supply of flushing fluid at a
minimum 30 PSI (0.21 MPa) flowing pressure. Flushing fluid should be tepid per ANSI
Z358.1.
P.O. BOX 309, MENOMONEE FALLS, WI 53052-0309 USA
TEL: 1-800-BRADLEY FAX: (262-251-5817)
http://www.bradleycorp.com
114-051
The inspection and testing results of this equipment should be recorded weekly
to verify proper operation. This equipment should be inspected annually to ensure
compliance with ANSI Z358.1.
Workers who may come in contact with potentially hazardous materials should be
trained regarding the placement and proper operation of emergency equipment per
ANSI Z358.1.
For questions regarding the operation or installation of this product, visit www.
bradleycorp.com or call 1-800-BRADLEY.
Product warranties and service parts information may also be found under ”Products”
on our web site at www.bradleycorp.com.
2
9/11/08
Bradley Corporation • 215-619DCBF Rev. S; ECN 08-512
Installation
S19-310DCBF
Installation
33-3/8"
(846mm)
Supplies Required:
• (3) 3/8" floor anchors and bolts
• Pipe sealant and teflon tape
• Piping to 1-1/4" NPT water supply inlet and 1-1/4"
NPT drain outlet
• Adequate supply pipe supports
• Minimum 4" (102mm) drain to accommodate 30
gallons (115 liters) per minute discharge for shower
waste
• OPTIONAL: Sign-mounting hardware
NOTE: Local codes may require the installation of
a backflow prevention valve to complete proper
installation. Compliance with local codes is the
responsibility of the installer. Valve must be tested
annually to verify that it is functioning properly.
Backflow prevention valves are not included with
the fixture and may be supplied by the contractor
or purchased from Bradley Corporation.
4-1/2"
(114mm)
Ø 3.1"
(78.7mm)
7'-1"
(2160mm)
to floor
65-1/2"
(1664mm)
to floor
Step 1: Secure base to floor
1. Install three suitable anchors (supplied by
installer) for 3/8" bolts in the floor.
2. Bolt the base to the floor anchors using 3/8"
bolts (supplied by installer).
Step 2: Assemble eyewash
1. Assemble eyewash components as shown on
6-1/2"
(165mm)
48"
(1219mm)
page 4.
• Apply pipe sealant (supplied by installer) to
all male-threaded pipe joints.
• Thread the jam nut onto the threaded end
of the pull rod. Thread the pull rod onto
the coupling and tighten the jam nut. The
triangular end of the pull rod must be in
line with the hook end (see page 4).
• Use the rubber grip pad provided or a strap
wrench around pipes when tightening to
prevent marring. Place the grip pad on the
pipe, then put the wrench over the grip pad
and turn the pipe with the wrench.
6" (152mm)
• The bottom edge of the showerhead should
be 7'-1" (2160mm) from floor.
Ø 10-3/4"
(273mm)
Step 3: Connect water supply
18-3/4"
(476mm)
IMPORTANT: Do not rely on Bradley’s
Combination Unit to support supply
piping.
1. Connect the water supply piping (supplied
by installer) to the 1-1/4" NPT inlet. Provide
adequate supports (by installer) for supply
pipe using pipe hangers or other means.
10-3/8"
(264mm)
Ø 9" (229mm)
Flange with (3) Ø
3/8" (10mm) Holes
on Ø 8" (203mm)
Bolt Circle
2. Connect the drain piping (supplied by
installer) to the 1-1/4" NPT drain outlet.
3. Hang the safety sign from the unit with the
curtain hooks provided (or mount it to the wall
using sign-mounting hardware by installer).
Bradley Corporation • 215-619DCBF Rev. S; ECN 08-512
31"
(787mm)
27"
(686mm)
NOTE:
All dimensions assume standard thread engagement.
Variations in manufacturing allow for +/- 1/8”
(3mm) per threaded joint. To find the tolerance of
a dimension, add the number of thread joints in
between a dimension and multiply it by 1/8” (3mm).
9/11/08
3
S19-310DCBF
Installation
Assembly of Components
NOTE: If tee (Item 7) is used as a supply
inlet, use plug (Item 8) on tee (Item 2)
8
7
Optional 1-1/4" NPT Supply
Inlet (best for rigid support)
9
10
10.1
10.2
6
11
10.3
12
10.4
10.5
10.11
13
1-1/4" NPT
Supply Inlet
2
14.1
14
4
NOTE: Use
teflon tape
only.
4.7
5
4.6
Align
handle
pieces as
shown.
4.5
15
4.4
4.3
4.14
4.8
4.17
4.9
4.15
4.11
4.18
4.13
Handle Note:
Close the cover
and put the pin
through the clip to
keep closed.
4.15
4.2
16.3
4.12
16.1
16
16.2
4.11 4.16
Use caution when connecting
Items 3, 4.2 & 5. Hand tight
plus 1/8 turn is sufficient.
3
4.161
1-1/4" NPT
Drain Outlet
2
NOTE: Items 4.1–4.9 come preassembled as Item 4.
Items 10.1–10.5 come preassembled as Item 10.
4
9/11/08
1
Bradley Corporation • 215-619DCBF Rev. S; ECN 08-512
Installation
S19-310DCBF
Parts List
Item
Part No.
Qty
Description
Item
Part No.
Qty
Description
1
131-059
1
Base
7
169-722
1
Reducing Tee
2
169-727
2
Pipe Tee 1-1/4"
8
169-724
1
Square-Head Pipe Plug
3
113-1101
1
Pipe 1-1/4" NPT x 19-3/4"
9
269-434
1
Pipe 1" NPT x 17"
4
S90-371
1
Dust Cover/EFW Assembly
10
S30-059
1
Stay-Open Ball Valve Assy. 1" NPT
4.1
S39-562
1
Eyewash Pipe Sub-Assy.
10.1
S27-278
1
Ball Valve 1" NPT with Nut
4.11
169-025
2
90° Street Elbow 1/2" NPT
10.11 110-214
1
Jam Nut only
4.12
111-084
1
Emergency Eyewash Inlet
10.2
140-720
1
Stop Bracket
4.13
113-1104
1
Pipe 1-1/4" x 16-1/2"
10.3
124-048
1
Washer, Flat Friction
4.14
169-1020
1
Emergency Eyewash Hub
10.4
128-129
1
Handle
4.15
113-006LQ
2
Pipe 1-1/2" x 3-1/2"
10.5
142-002DC
1
Lockwasher
4.16
S27-282
1
1/2" Ball Valve with Nut
11
113-006LK
1
Pipe 1" NPT x 12"
4.161 110-215
1
Jam Nut only
12
169-847
1
90° Street Elbow 1"
4.17
269-1829
1
Pipe 1/2" NPT x 13-1/4"
13
151-001
2
Curtain Hook
4.18
169-726
1
Union, 1/2" Female
14
S24-188
1
Plastic Showerhead Assembly
4.2
124-028
1
Gasket
14.1
S24-187
1
Flow Control Assembly, 23 GPM
4.3
S90-009
1
Dust Cover Assembly
15
S90-365D
1
Pull Rod 45" Long (2 pieces)
4.4
173-009
1
Cup Strainer
16
S30-087
1
Handle Prepack
4.5
113-1150
1
Pipe Stem
16.1
S08-056
1
Handle Assembly
4.6
S05-091P
1
Eye/Face Sprayhead Yoke
16.2
142-002DA
1
Lockwasher
4.7
S05-135
2
EFW Sprayhead
16.3
153-372R
1
Adapter
4.8
269-447
1
Bumper
17
114-052
1
Safety Sign
4.9
161-025
1
Nut
18
204-421
1
Emergency Inspection Tag
5
113-006NE
1
Pipe 1-1/4" NPT x 32-1/2"
19
269-915
1
Grip Pad (not shown)
6
113-006LW
1
Pipe 1-1/4" NPT x 22-1/2"
Bradley Corporation • 215-619DCBF Rev. S; ECN 08-512
9/11/08
5
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement