Protege Standard 16 Zone Input Expander Datasheet

Protege Standard 16 Zone Input Expander Datasheet
PRT-ZXS16-PCB
Protege Standard 16 Zone
Input Expander
The Protege Standard 16 Zone Input Expander provides the
interface of up to 16 zone inputs and 1 programmable output to
the Protege system, an advanced technology security product
providing seamless and powerful integration of access, security
and building automation.
Feature Highlights
Connectivity and System Expansion
Communication
> Connect any combination of normally
closed or normally open zones,
configurable per input
Expanding the Protege System with local
zone (input) and PGM (output) from the
Protege Input Expander allows convenient
cost effective expansion:
Single RS-485 communication interface port
used for all network communication
functions and interconnection to other
modules.
> Utilizes analog to digital processing with 5
over sampling
> 4 state input alarm using resistors to
provide short, alarm, closed and tamper
conditions
> 16 inputs can be assigned in to any 4
areas in the system each being
processed using different options or
features
> Address configuration is achieved using
an 8 way DIP switch
Technical Specifications
Power Supply
DC Input Voltage
12VDC (+/-10%)
Operating Current
48mA (Typical)
Communication
RS-485
Module Network
Outputs
PGM Output
1 (50mA Max) Open Collector
Inputs
Zone Inputs
16 (500ms to 40sec Input Speed)
Tamper
1 (Normally Closed)
Trouble Zone
16
Dimensions
Dimensions (H x W x D)
93 x 130 x 12mm (3.66 x 5.11 x 0.47”)
Weight
165g (5.82oz)
Temperature
Operating
5˚- 55˚ Celsius (41˚ - 131˚ Fahrenheit)
Storage
-10˚- 85˚ Celsius (14˚ - 185˚ Fahrenheit)
Humidity
0%-85% (Non-Condensing)
Disclaimer: Whilst every effort has been made to ensure accuracy in the representation of this product, neither Integrated Control Technology Ltd nor its
employees, shall be liable under any circumstances to any party in respect of decisions or actions they may make as a result of using this information. In
accordance with the Integrated Control Technology policy of enhanced development, design and specifications are subject to change without notice.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement