Veris TEAVSB Wall Temperature Sensor Installation Guide


Add to my manuals
2 Pages

advertisement

Veris TEAVSB Wall Temperature Sensor Installation Guide | Manualzz

ENVIRONMENTAL SENSORS

TM

TEA SEriES

INSTALLATION GUIDE

TEA SEriES

Wall Mount Temperature Transmitters

Installer’s Specifications

Input Power

0-10V

0-5V

Analog Output, mA version

Sensor Type

Accuracy

4-20mA version: loop powered 24VDC only;

2-wire, not polarity sensitive (clipped and capped)

Solid state, integrated circuit (transmitter)

±0.5°C (±01°F) typical

Temperature Range 10° to 35°C (50° to 95°F)

NOTICE

• This product is not intended for life or safety applications.

• Do not install this product in hazardous or classified locations.

• Read and understand the instructions before installing

this product.

• Turn off all power supplying equipment before working on it.

• The installer is responsible for conformance to all applicable codes.

INSTALLATION

1. Disconnect power to the junction box.

2. Remove junction box cover.

3. Wire as shown (see Wiring Diagrams)

4. Screw TEA cover onto junction box.

PRODUCT IDENTIFICATION

TEA

Output US or EU

S

M =4-20mA

V = 0-10VDC

J = 0-5VDC

= Standard

DIMENSIONS

0.3"

(6 mm)

3.2"

(82 mm)

4.5"

(115 mm)

2.8"

(70 mm)

0.5"

(13 mm)

Z204260-0A PAGE 1 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 03121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

TM

WIRING DIAGRAMS

4-20 mA Output Version (2-wire)

TEA SERIES

Orange

Orange

0-10 V Output Version (3-wire)

Red: +24V Power

Black: GND

Orange: 0-10V

TEMP OUT

0-5 V Output Version (3-wire)

Red: +24V Power

Black: GND

Yellow: 0-5V

TEMP OUT

INSTALLATION GUIDE

Z204260-0A PAGE 2 ©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected] 03121

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Related manuals

Frequently Answers and Questions

What is the power requirement for the Veris TEAVSB temperature transmitter?
For the 4-20mA version, it requires a loop-powered 24VDC. For the 0-10V version, it needs a 3-wire, 12-30VDC power supply with observed polarity. And for the 0-5V version, it needs a 3-wire, 24VAC, 12-30VDC power supply with observed polarity.
What type of sensor does the Veris TEAVSB use?
It utilizes a solid-state, integrated circuit (transmitter) sensor.
What is the accuracy of the Veris TEAVSB temperature transmitter?
The accuracy of the transmitter is typically ±0.5°C (±01°F).
What temperature range does the Veris TEAVSB operate in?
The operating temperature range for the transmitter is 10° to 35°C (50° to 95°F).
Is the Veris TEAVSB intended for life or safety applications?
No, this product is not designed for life or safety applications.
Can the Veris TEAVSB be installed in hazardous or classified locations?
No, installation in hazardous or classified locations is not permitted.