[键入文字] [键入文字] TYPE TEST SHEET This Type Test sheet shall be used to record the results of the type testing of Generating unit between 16A per phase and 17KW per phase maximum output at 230V(17KW limit single phase,34KW limit split phase,50KW limit 3 phase) It include the Generating Units supplier declaration of compliance with requirements of Engineering Recommendation G59/3 Type Tested reference number Growatt 4000UE/ Growatt 5000UE/ Growatt 6000UE Generating unit technology Photovoltaic inverter System Supplier name Address Shenzhen Growatt New Energy Co., Ltd 1st East & 3rd Floor, Jiayu Industrial Zone, Xibianling,Shangwu Village, Shiyan, Baoan District, Shenzhen,P.R.China Tel. +86 755 2951 5888 Fax +86 755 2747 2131 E:mail [email protected] Web site www.ginverter.com Connection Option N/A Maximum export capacity kW single phase, single, split or three phase system 4 kW three phase 5 kW three phase 6 kW three phase N/A kW two phases split phase system System supplier declaration. I certify on behalf of the company named above as a supplier of a Generating unit, that all products supplied by the company with the above Type Test reference number will be manufactured and tested to ensure that they perform as stated in this document, prior to shipment to site and that no site modifications are required to ensure that the product meets all the requirements of G59/3. Signed On behalf of Shenzhen Growatt New Energy Co., Ltd Note that testing can be done by the manufacturer of an individual component, by an external test house, or by the supplier of the complete system, or any combination of them as appropriate. Where parts of the testing are carried out by persons or organizations other than the supplier then the supplier shall keep copies of all test records and results supplied to them to verify that the testing has been carried out by people with sufficient technical competency to carry out the tests. The family product model is made by the following products: Growatt 4000UE , Growatt 5000UE , Growatt 6000UE The model Growatt 6000UE is as the representative test models in this report. [键入文字] [键入文字] Power Quality. Harmonics Models: Growatt 6000UE Harmonic %=Measured Value Generating Unit rating per phase(rpp) 2 Harmonic 100% of rated output At45-55% of rated output KVA (Amps) × 23/rating phase(KVA) Limit BS EN 61000-3-2 Average harmonic current results – Phase 1 Measured Value (MV) in Amps % 0.005 0.112 3 0.015 0.345 4 0.010 0.225 5 0.121 2.693 6 0.004 0.098 7 0.054 1.203 8 0.005 0.103 9 0.005 0.107 10 0.004 0.088 11 0.012 0.269 12 0.002 0.054 13 0.029 0.643 THD(At 100% rated output) 2 Measured Value (MV) in Amps % 0.006 0.012 0.008 0.150 0.005 0.091 0.004 0.008 0.003 0.022 0.003 0.007 2.05% 0.069 0.131 0.090 1.688 0.053 1.024 0.046 0.091 0.037 0.250 0.036 0.084 Limit 1.5 0.7 5.5 6.1 3.6 14.4 4.4 0.8 1.1 3.4 0.2 24.9 Result PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS Average harmonic current results – Phase 2 Measured Value (MV) in Amps % 0.007 0.162 3 0.007 0.150 4 0.009 0.206 5 0.126 2.840 6 0.002 0.038 7 0.050 1.128 8 0.004 0.090 9 0.002 0.053 10 0.003 0.078 11 0.013 0.290 12 0.001 0.026 13 0.025 0.575 THD(At 100% rated output) 2 Measured Value (MV) in Amps % 0.008 0.008 0.007 0.153 0.003 0.084 0.004 0.003 0.003 0.025 0.003 0.006 2.08% 0.090 0.086 0.077 1.750 0.034 0.959 0.045 0.038 0.034 0.284 0.032 0.073 Limit 1.5 0.7 5.5 6.1 3.6 14.4 4.4 0.8 1.1 3.4 0.2 24.9 Result PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS Average harmonic current results – Phase 3 Measured % Measured % Limit Result per [键入文字] [键入文字] Value (MV) in Amps Value (MV) in Amps 0.007 0.162 3 0.025 0.565 4 0.002 0.044 5 0.121 2.707 6 0.004 0.088 7 0.052 1.165 8 0.001 0.032 9 0.008 0.173 10 0.001 0.028 11 0.012 0.267 12 0.002 0.044 13 0.028 0.623 THD(At 100% rated output) 2 0.008 0.022 0.002 0.149 0.004 0.089 0.001 0.012 0.001 0.023 0.002 0.007 2.04% 0.085 0.251 0.021 1.686 0.043 1.004 0.015 0.135 0.016 0.262 0.026 0.078 1.5 0.7 5.5 6.1 3.6 14.4 4.4 0.8 1.1 3.4 0.2 24.9 PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS PASS Power Quality. Voltage fluctuations and Flicker. Models: Growatt 6000UE Measured Values at standard impedance L1 Starting Stopping Running L3 dmax 0.153% 0.162% 0.129% 4% dc 0.026% 0.022% 0.029% 3.30% d(t) 0.002s 0.002s 0.002s 0.5s dmax 0.173% 0.151% 0.167% 4% dc 0.027% 0.025% 0.029% 3.30% d(t) 0.002s 0.002s 0.002s 0.5s Pst 0.165 0.225 0.138 1 Plt 2 0.073 0.114 0.058 0.65 Test start date Test Iocation L2 Limits set under BS EN 61000-3-2 15.10.2015 Test end date 15.10.2015 Growatt R&D Laboratories Power quality. DC injection and Power factor. DC injection Test power level Test Value 10% 55% 100% L1 13mA 10.1mA 9.2mA L2 12.1mA 9.6mA 10.3mA L3 14.8mA 12.2mA 10.1mA [键入文字] [键入文字] Limit(0.25% of rated AC current) 21.7mA 21.7mA 21.7mA Power factor Test power level 221Vac 230Vac 256Vac Test Value 0.995 0.996 0.996 Limit >0.95 >0.95 >0.95 Protection. Frequency tests. Function Setting Trip test “No trip tests” Frequency Time delay Frequency Time delay Frequency /time Confirm no trip U/F stage1 47.53Hz 20.09S 47.53Hz 20.19S 47.73Hz/25s No Trip U/F stage2 47Hz 638.2ms 47Hz 749ms 47.2Hz/19.98s No Trip 46.8Hz/0.48s No Trip O/F stage1 51.47Hz 90.36S 51.48Hz 90.44S 51.27Hz/95s No Trip O/F stage2 52Hz 575.7ms 52.01Hz 661ms 51.8Hz/89.98s No Trip 52.2Hz/0.48s No Trip Note. For frequency Trip tests the Frequency requird to trip is the setting ±0.1Hz. In order to measure the time delay a larger deviation than the minimum required to operate the protection can be used. The “No-trip tests” need to be carried out at the setting ±0.2Hz and for the relevant times as shown in the table above to ensure that the protection will not trip in error. Protection. Voltage tests. Function Setting Trip test “No trip tests” Voltage Time delay Voltage Time delay Voltage/time Confirm no trip U/V stage1 201V 2.6S 200.6V 2.65S 205.1V/3.5s No Trip U/V stage2 184.5V 600ms 184.1V 639ms 188.5V/2.48s No Trip 180.5V/0.48s No Trip O/V stage1 262.2V 1.1S 261.4V 1.12S 258.2V/2.0s No Trip O/V stage2 273.7V 600ms 273.1V 633ms 269.7V/0.98s No Trip 277.7V/0.48s No Trip Note. For Voltage tests the Voltage required to trip is the setting ±3.45V. The time delay can be measured at a larger deviation than the minimum required to operate the protection. The No trip tests need to be carried out at the setting ±4V and for the relevant times as shown in the table above to ensure that the protection will not trip in error. Protection. Loss of Mains test Test Power and imbalance 33% -5%Q Test 22 66% -5%Q Test 12 100% -5%P Test 5 33% +5%Q Test 31 66% +5%Q Test 21 100% +5%P Test 10 [键入文字] [键入文字] Trip time. Limit is 0.5s 0.285 0.157 0.126 0.264 0.152 0.173 Protection. Frequency change, Stability test. Start Frequency Change End Frequency Confirm no trip Positive Vector Shift 49.5Hz +9degrees -- No trip Negative Vector Shift 50.5Hz -9degrees -- No trip Positive Frequency drift 49.5Hz +0.19Hz/sec 51.47Hz No trip Negative Frequency drift 50.5Hz -0.19Hz/sec 47.53Hz No trip Protection. Re-connection timer. Time delay setting Measured delay 65s 71.5s Checks on no reconnection when voltage or frequency is brought to just outside stage 1 limits of table 10.5.7.1 Confirmation that the Generating Unit does not re-connect At 266.2V At No reconnection 197V No reconnection At 47.43Hz No reconnection At 51.57Hz No reconnection Fault level contribution. For machines with electro-magnetic output Parameter Peak Short Circuit current Symbol ip Initial Value of aperiodic current A Initial symmetrical short-circuit current Ik Decaying component of short circuit current i Reactance/Resistance Ratio of source Value For Inverter Output Time after fault Volts Amps 20ms 25.8V 1.03 -- 100ms 25.6V 1.12 -- 250ms 25.3V 0.96 -- 500ms 25.3V 0.94 -- Time to trip 20ms In seconds -- DC X/R For rotating machines and linear piston machines the test should produce a 0s-2s plot of the sort circuit current as seen as the Generating Unit terminals
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement