Thermal Expansion
TECHNICAL BULLETIN
BULLETIN 45
THERMAL EXPANSION
SYMPTOMS
•
•
•
•
•
•
•
CAUSE
Effects are only noticeable after hot water use followed by periods of no water use.
Relief valve drips during any recovery cycle when no hot or cold water is used.
Hot water pipes creak while heater is recovering and all valves are closed.
Tanks or other components of the water supply system fail prematurely.
A metallic creaking noise might actually be heard in the location of the heater as the
pressure is relieved and the stretched tank returns to a natural shape.
Faucets drips during any recovery cycle when no hot or cold water is used.
Water surges when a valve is first open and then pressure drops.
The water in a water heating system expands when it is heated and has a greater
volume. Since water will not compress (like air), system designers must include
provisions for thermal expansion. (Water in a closed tank at 50 psi, when heated just
10 degrees, will reach a pressure of 250 psi).
Many water supply systems have check valves at the water meter to prevent any
possible contamination of the public water supply by the accidental back-flow of
contaminated water into the supply mains. These check valves are often required by
code, and some cities are even installing the check valves. They serve a useful
purpose. Do not remove them!
The use of pressure reducing valves (PRV) is another cause. PRVs are designed to
conserve water and prolong fixture life. Many PRVs also act as very effective check
valves. Again, do not remove them!
Water softeners in the system may also act as back-flow preventers.
TEST
Follow these easy steps to diagnose thermal expansion:
•
•
•
•
Printed in USA 498
Turn the heater thermostat all the way down, and install a water pressure gauge with dead
hand (AOS part #4798) on the drain valve. Open the drain valve, so the gauge reads system
pressure.
Open a hot water tap and allow 15% to 20% of the tanks volume to run out. Shut off the
drain valve and make sure that no other fixture in the system, hot or cold, is open. Make sure
that outside fixtures, if they are on the same system, are turned off too. Any water leaks or
use will make the test meaningless.
Check the water pressure gauge, and turn the pointer so it lines up with the pressure
indicating needle. Turn the thermostat back up to its normal position, so the heater cycles
on. Watch the pressure gauge.
If the system is closed, the pressure will start to climb steadily and rapidly. A small amount of
thermal expansion control may be built into the system because of trapped air pockets or a
water hammer arrestor. In that case the pressure will increase slightly, hold steady for a
short time and then rapidly increase. The temperature and pressure relief valve (T&P) or
PRV should open and release water once the pressure reaches the maximum setting on the
valve. The valve will close once the pressure falls below the pressure setting of the valve.
Part No. TC-204-45
THE FIX
The ideal fix involves the use of a pressure reducing valve if supply pressures are
above 60 to 70 psi, and a properly sized expansion tank. The PRV reduces supply
pressures to 40 to 60 psi allowing an economically priced and sized expansion tank to
be used. The PRV also offers the benefit of saving water and prolonging the life of
water flow valves. The PRV is not required if the system already has one or if high
supply pressures are desired.
The PRV is installed between the check valve and the water heating system. The
expansion tank is installed between the PRV and the water heating system. Follow the
manufacturers instructions for installing the expansion tank.
Run the thermal expansion check again. The pressure should increase only slightly
then hold steady throughout the recovery cycle. The expanded water is flowing back
from the heater and into the pressurized storage bladder of the expansion tank. Air
pressure will force this water out of the expansion tank into the supply once usage
resumes.
DO NOT DEPEND ON THE T&P VALVE TO HANDLE THERMAL EXPANSION! The
T&P valve, according to the makers of those valves, was designed as an emergency
relief device only. The T&P could be subject to reduced effectiveness or failure.
FIGURE
WARNING
Printed in USA 498
Thermal expansion of water, if not compensated for in system design, will lead to the
early failure of components. These failures are not covered by the manufacturer’s
warranty, so it is extremely important that everyone be aware of the causes, symptoms
and solutions to thermal expansion in a closed water heating system.
Part No. TC-204-45