General Motors 60 kWe Gaseous Generator Set 208 600 Volt Standby

Add to my manuals
4 Pages

advertisement

General Motors 60 kWe Gaseous Generator Set 208 600 Volt Standby | Manualzz

Gaseous Product Line

GM60-02

60 kWe

Ratings

Phase

PF

Hz

Generator Model

Connection

Standby kWe Nat (LP)

AMPS Nat (LP)

Temp Rise

240V

1

1.0

60

362CSL1604

12 LEAD ZIG-ZAG

60 (60)

250 (250)

130˚C / 27˚C

208V

3

0.8

60

361CSL1602

12 LEAD WYE

60 (60)

208 (208)

130˚C / 27˚C

208-600 Volt

60 Hz / 1800 RPM

Standby

240V

3

0.8

60

361CSL1602

12 LEAD DELTA

60 (60)

181 (181)

130˚C / 27˚C

480V

3

0.8

60

361CSL1601

12 LEAD WYE

60 (60)

90 (90)

130˚C / 27˚C

600V

3

0.8

60

361PSL1633

4 LEAD WYE

60 (60)

72 (72)

130˚C / 27˚C

Standard Equipment

Engine

„

Radiator Cooled Unit Mounted (50˚C)

„

Blower Fan & Fan Drive

„

Starter & Alternator

„

Oil Pump & Filter

„

Oil Drain Extension w/Valve

„

Governor - Electronic Isochronous

„

12V Battery System & Cables

„

Air Cleaner (Dry Single Stage)

„

Flexible Fuel Connector

„

EPA Certified

Listing Certifications

„

UL 2200 Listed

„ cUL Listed

„

CSA Certified

„

Seismic Certified to IBC 2012

Generator

„

Brushless Single Bearing

„

Automatic Voltage Regulator

„

± 1% Voltage Regulation

„

4 Pole, Rotating Field

„

130˚C Standby Temperature Rise

„

100% of Rated Load - One Step

„

5% Maximum Harmonic Content

„

NEMA MG 1, IEEE and ANSI Standards

Compliance for Temperature Rise

Additional

„

Microprocessor Based Digital Control

„

Interface Connection Box

„

Control Panel Mounted in NEMA 12 Enclosure

„

Base - Formed Steel

„

Main Line Circuit Breaker Mounted & Wired

„

Critical Grade Silencer Mounted

„

Battery Charger 12V 6 Amp

„

Jacket Water Heater -20˚F 1500W 120V w/Isolation Valves

„

Vibration Isolation Mounts

„

Radiator Duct Flange (OPU Only)

„

Single Source Supplier

„

2YR / 2000HR Standby Warranty

„

Standard Colors - White / Tan / Gray

GM60-02

Gaseous Product Line

60 kWe

Application Data

Engine

Manufacturer: General Motors

Model: GM 5.7L EPA

Type: 4-Cycle

Aspiration: Natural

Cylinder Arrangement: 8 Cylinder Vee

Displacement - Cu. In. (lit):

Bore - in. (cm) x Stroke - in. (cm):

Compression Ratio:

Rated RPM:

Max HP Stby (kWm):

350 (5.70)

4.00 (10.2) x 3.5 (8.80)

9.40:1

1800

113 (78.1)

Exhaust System

Gas Temp. (Stack): °F (°C)

Gas Volume at Stack Temp: CFM (m³/min)

Maximum Allowable Exhaust Restriction: in. H

2

O (kPa)

Cooling System

Ambient Capacity of Radiator: °F (°C)

Maximum Allowable Static Pressure on Rad. Exhaust: in. H

2

O (kPa)

Water Pump Flow Rate: GPM (lit/min)

Heat Rejection to Coolant: BTUM (kW)

Heat Rejection to CAC: BTUM (kW)

Heat Radiated to Ambient: BTUM (kW)

Air Requirements

Aspirating: CFM (m³/min)

Air Flow Required for Rad. Cooled Unit: CFM (m³/min)

Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)

Fuel Consumption

At 100% of Power Rating: ft3/hr (m3/hr)

At 75% of Power Rating: ft3/hr (m3/hr)

At 50% of Power Rating: ft3/hr (m3/hr)

Fuel Inlet Size: NPT

Fuel Pressure Required: in. H20 (kPa)

Fluids Capacity

Total Oil System: gal (lit)

Engine Jacket Water Capacity: gal (lit)

System Coolant Capacity: gal (lit)

All calculations based on natural gas fuel.

Deration Factors: Temperature: Derate 1% Per 10 o F Over 77 o F Air Inlet Temperature | Altitude: Derate 3% Per 1,000 ft Over 328 ft

GM60-02

173 (4.90)

7,400 (209)

Consult Factory For Remote Cooled Applications

Natural Gas

859 (24.3)

725 (20.5)

LP

363 (10.3)

305 (8.63)

578 (16.4) 244 (6.91)

1.00”

7.00 - 11.0 (1.75 - 2.75)

1.25 (4.73)

2.03 (7.68)

6.00 (22.7)

Standby

1,350 (732)

553 (15.7)

40.8 (10.2)

122 (50.0)

0.50 (0.12)

36.6 (139)

3,120 (54.6)

N/A

854 (14.9)

Gaseous Product Line

60 kWe

DGC-2020 Control Panel

Standard Features

„

Digital Metering

„

Engine Parameters

„

Generator Protection Functions

„

Engine Protection

„

CAN Bus ECU Communications

„

Windows-Based Software

„

Multilingual Capability

„

Remote Communications to RDP-110 Remote Annunciator

„

16 Programmable Contact Inputs

„

Up to 15 Contact Outputs (7 standard)

„

UL Recognized, CSA Certified, CE Approved

„

Event Recording

„

IP 54 Front Panel Rating with Integrated Gasket

„

NFPA 110 Level 1 Compatible

Weights / Dimensions / Sound Data

L x W x H Weight lbs

OPU

80 x 38 x 52 in 1,675

Level 1

90 x 38 x 60 in 2,150

Level 2

90 x 38 x 60 in 2,175

Level 3

120 x 38 x 60 in 2,325

Please allow 6-12 inches for height of exhaust stack.

OPU

Level 1

Level 2

Level 3

No Load

76 dBA

71 dBA

66 dBA

63 dBA

Full Load

79 dBA

73 dBA

68 dBA

64 dBA

Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice.

Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.

GM60-02

Gaseous Product Line

60 kWe

Enclosures

All enclosures are 150 MPH Wind Rated.

Level 2 & 3 enclosures include sound attenuation foam.

Level 3 enclosure includes frontal sound & exhaust hood.

*Enclosure height does not include exhaust stack.

All specification sheet dimensions are represented in inches.

Materials and specifications subject to change without notice.

Distributed By:

GM60-02

Blue Star Power Systems, Inc.

52146 Ember Road

Lake Crystal, Minnesota 56055

Phone + 1 507 726 2508 bluestarps.com

quote.bluestarps.com

[email protected]

4 of 4

advertisement

Was this manual useful for you? Yes No
Thank you for your participation!

* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project

Download PDF

advertisement