Tech Guide DF 36-72

Tech Guide DF 36-72
036-21504-006-A-1105
®
DESCRIPTION
SINGLE PACKAGE GAS/ELECTRIC UNITS
YORK® Sunline Plus™ units are convertible single package
air conditioners with a common cabinet and a common roof
curb for the 3, 4, 5 and 6 ton sizes. The units were designed
for light commercial and commercial applications. They can
easily be installed on a roof curb, slab, roof jack or frame.
AND SINGLE PACKAGE
All units include:
AIR CONDITIONERS
•
Powder Paint finish that meets ASTM-B-117 1000 hour
salt spray standards
DF 036, 048, 060 and 072
•
Permanently lubricated motors
•
Bottom or side air discharge configuration capability
(field convertible)
•
Manufactured under the quality standards of ISO9001
•
SimplicityTM Control Board
•
Copper tube/aluminum fin coils
•
Easy access to all components
•
Rigging holes in base rails for lifting
•
Fork lift slots on three sides
•
Single point power connection
•
Complete factory package - tested, charged and wired
•
CSA agency listing on all units
TECHNICAL GUIDE
3, 4, 5 and 6 NOMINAL TONS
11.0 - 11.5 SEER
10.0 - 10.4 EER
WARRANTY
•
Factory Limited Parts Warranty
•
One-year parts warranty
•
A Five-year parts warranty on the compressor and
electric heat elements.
•
Ten-year parts warranty on the gas-fired heat
exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
036-21504-006-A-1105
TABLE OF CONTENTS
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . 12
FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 13
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 43
10 SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . 21
11 SUPPLY AIR BLOWER PERFORMANCE (5,6 TON
BELT DRIVE) - SIDE DUCT APPLICATION . . . . . . . 22
12 SUPPLY AIR BLOWER PERFORMANCE (3 - 5 TON
DIRECT DRIVE) - SIDE DUCT APPLICATION . . . . 23
13 BELT DRIVE BLOWER MOTOR AND DRIVE
DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
14 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . 24
15 ELECTRIC HEATER CFM LIMITATIONS . . . . . . . . . 24
LIST OF FIGURES
Fig. #
Pg. #
16 ELECTRICAL DATA - DF036 & 048 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . . . . 25
1
UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2
TYPICAL FIELD POWER & CONTROL WIRING . . . 36
17 ELECTRICAL DATA - DF060 DIRECT DRIVE WITHOUT
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 26
3
UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/
ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . . 37
18 ELECTRICAL DATA - DF036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET . . . . . . . . . 27
4
UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT)
FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
19 ELECTRICAL DATA - DF060 BELT DRIVE WITHOUT
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 28
5
UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . . . 38
20 ELECTRICAL DATA - DF072 BELT DRIVE WITHOUT
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 29
6
UNIT WITH FIXED OUTDOOR AIR/MOTORIZED
DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . . 38
7
UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . . 39
8
DISCONNECT/BLOWER ACCESS LOCATION . . . . 39
9
TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . 40
10
FOUR AND SIX POINT LOADING . . . . . . . . . . . . . . 41
11
ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . 42
LIST OF TABLES
Tbl. #
Pg. #
21 ELECTRICAL DATA - DF036 & 048 DIRECT DRIVE
WITH POWR’D CONVENIENCE OUTLET . . . . . . . . 30
22 ELECTRICAL DATA - DF060 DIRECT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 31
23 ELECTRICAL DATA - DF036 & 048 BELT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 32
24 ELECTRICAL DATA - DF060 BELT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 33
25 ELECTRICAL DATA - DF072 BELT DRIVE WITH
POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 34
26 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
1
SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . . 15
2
CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . . . 15
27
ELECTRIC HEAT CORRECTION FACTORS . . . . . . 35
28 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . 35
3
GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . 15
4
2 STAGE GAS HEAT RATINGS . . . . . . . . . . . . . . . . . 15
5
DF036 COOLING CAPACITIES (3 TON) . . . . . . . . . . 16
6
DF048 COOLING CAPACITIES (4 TON) . . . . . . . . . . 17
31 DF 4 AND 6 POINT LOADS WEIGHT
DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
7
DF060 COOLING CAPACITIES (5 TON) . . . . . . . . . . 18
32 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 41
8
DF072 COOLING CAPACITIES (6 TON) . . . . . . . . . . 19
33 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . 42
9
SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT
DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . 20
2
29 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
30 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . 39
Unitary Products Group
036-21504-006-A-1105
PRODUCT NOMENCLATURE
7RQ6XQOLQH0RGHO1XPEHU1RPHQFODWXUH
' ) 1 $ $ $$ 3URGXFW*HQHUDWLRQ
3URGXFW&DWHJRU\
)LUVW*HQHUDWLRQ
6HFRQG*HQHUDWLRQ
' $LU&RQG6LQJOH3DFNDJH
9ROWDJH
3URGXFW,GHQWLILHU
) 50HGLXP(IILFLHQF\'(*'((
1RPLQDO&RROLQJ
&DSDFLW\0%+
,QVWDOODWLRQ2SWLRQV
$ 1R2SWLRQV,QVWDOOHG
% 2SWLRQ
& 2SWLRQ
' 2SWLRQV
( 2SWLRQ
) 2SWLRQ
* 2SWLRQV
+ 2SWLRQV
- 2SWLRQV
. 2SWLRQV
/ 2SWLRQV
0 2SWLRQV
1 2SWLRQV
3 2SWLRQV
4 2SWLRQV
5 2SWLRQV
6 2SWLRQ
7 2SWLRQV
8 2SWLRQV
9 2SWLRQV
: 2SWLRQV
; 2SWLRQV
< 2SWLRQV
= 2SWLRQV
7RQ
7RQ
7RQ
7RQ
+HDW7\SH1RPLQDO+HDW&DSDFLW\
& &RROLQJ2QO\6XLWDEOHIRUILHOGLQVWDOOHGHOHFWULFKHDW
*DV+HDW2SWLRQV
1
1
1
1
'
'
6
6
6
6
7
7
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW$OXPLQL]HG6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
0%+2XWSXW6WDLQOHVV6WHHO6WDJH
6HH1H[W3DJH
2SWLRQV
(OHFWULF+HDW2SWLRQV
(
(
(
(
(
(
$GGLWLRQDO2SWLRQV
N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW
N:(OHFWULF+HDW
'LVFRQQHFW
1RQ3ZU
G&RQY2XOWHW
6PRNH'HWHFWRU6$
6PRNH'HWHFWRU5$
3ZU
G&RQY2XWOHW
'7 0%+2XWSXWRQ0RGHOV
$LUIORZ
$ 'LUHFW'ULYH
% 'LUHFW'ULYH6LQJOH,QSXW(FRQR
' 'LUHFW'ULYH0RWRUL]HG'DPSHU
/ 'LUHFW'ULYH%$65HDG\(FRQ1R%$6&RQWUROOHU3OHDWHG)LOWHUV([WUD[IUPUFLUFXLWENU
1 %HOW'ULYH
3 %HOW'ULYH6LQJOH,QSXW(FRQR
5 %HOW'ULYH0RWRUL]HG'DPSHU
< %HOW'ULYH%$65HDG\(FRQ1R%$6&RQWUROOHUZ3OHDWHG)LOWHUV
Unitary Products Group
3
036-21504-006-A-1105
PRODUCT NOMENCLATURE - Continued
3-6T Sunline Model Number Nomenclature
Standard Cabinet
AA
AB
AC
AD
AE
AF
AG
AH
AJ
AK
AL
AM
AN
AS
CA
CB
CC
CD
CE
CF
CG
CH
CJ
CK
CL
CM
CN
CP
CQ
CR
CS
CT
CU
CV
CW
CX
JA
JB
JC
JD
JE
JF
JG
JH
JJ
JK
JL
JM
JN
JP
4
None
Phase Monitor
Coil Guard
Dirty Filter Switch
Phase Monitor & Coil Guard
Phase Monitor & Dirty Filter Switch
Coil Guard & Dirty Filter Switch
Phase Monitor, Coil Guard, & Dirty Filter Switch
SS Drain Pan
SS Drain Pan & Phase Monitor
SS Drain Pan & Coil Guard
SS Drain Pan & Dirty Filter Switch
SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch
Bottom Drain Connection
CPC Controller with Dirty Filter Switch & Air Proving Switch
CPC Controller, DFS, APS & Phase Monitor
CPC Controller, DFS, APS & Coil Guard
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Cond. Coil
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Evap. Coil
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS, SS Drain Pan
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch
Johnson UNT Controller, DFS, APS & Phase Monitor
Johnson UNT Controller, DFS, APS & Coil Guard
Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Unitary Products Group
036-21504-006-A-1105
Standard Cabinet
JQ
JR
JS
JT
JU
JV
JW
JX
HA
HB
HC
HD
HE
HF
HG
HH
HJ
HK
HL
HM
HN
HP
HQ
HR
HS
HT
HU
HV
HW
HX
NA
NB
NC
ND
NE
NF
NG
NH
NJ
NK
NL
NM
NN
NP
NQ
NR
NS
NT
NU
NV
NW
NX
TA
TB
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS, SS Drain Pan
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch
Honeywell Excel 10 Controller, DFS, APS & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch
Novar ETC-3 Controller, DFS, APS & Phase Monitor
Novar ETC-3 Controller, DFS, APS & Coil Guard
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS, SS Drain Pan
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Technicoat Condenser Coil
Technicoat Condenser Coil & Phase Monitor
Unitary Products Group
5
036-21504-006-A-1105
Standard Cabinet
TC
TD
TE
TF
TG
TH
TJ
TK
TL
TM
TN
TP
TQ
TR
TS
TT
TU
TV
TW
TX
TY
TZ
T1
T3
T4
T6
T7
T9
LA
LB
LC
LD
LE
LF
LG
LH
LJ
LK
LL
LM
LN
LP
LQ
LR
LS
LT
LU
LV
LW
LX
WA
WB
WC
WD
6
Technicoat Condenser Coil & Coil Guard
Technicoat Condenser Coil & Dirty Filter Switch
Technicoat Condenser Coil, Phase Monitor, & Coil Guard
Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch
Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch
Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator Coil
Technicoat Evaporator Coil & Phase Monitor
Technicoat Evaporator Coil & Coil Guard
Technicoat Evaporator Coil & Dirty Filter Switch
Technicoat Evaporator Coil, Phase Monitor, & Coil Guard
Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch
Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils
Technicoat Evaporator & Condenser Coils & Phase Monitor
Technicoat Evaporator & Condenser Coils & Coil Guard
Technicoat Evaporator & Condenser Coils & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard
Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Condenser & SS Drain Pan
Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & SS Drain Pan
Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Technicoat Evaporator & Condenser Coils & SS Drain Pan
Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch
Simplicity Intelli-Comfort Controller
Simplicity Intelli-Comfort Controller, & Phase Monitor
Simplicity Intelli-Comfort Controller, & Coil Guard
Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, SS Drain Pan
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Intelli-Comfort w/Mod Link Controller
Intelli-Comfort w/Mod Link Controller, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard
Unitary Products Group
036-21504-006-A-1105
Standard Cabinet
WE
WF
WG
WH
WJ
WK
WL
WM
WN
WP
WQ
WR
WS
WT
WU
WV
WW
WX
Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard
Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, SS Drain Pan
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils
Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
Hinged Filter Door & Toolless Access Cabinet
BA
BB
BC
BD
BE
BF
BG
BH
BJ
BK
BL
BM
BN
BS
DA
DB
DC
DD
DE
DF
DG
DH
DJ
DK
DL
DM
DN
DP
DQ
DR
DS
DT
DU
DV
Hinged Filter Door & Toolless Access Panels
Phase Monitor, Hinged Filter Door & Toolless Access Panels
Coil Guard, Hinged Filter Door & Toolless Access Panels
Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels
Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Phase Monitor, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Coil Guard, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
SS Drain Pan & Phase Monitor & Coil Guard, Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
Bottom Drain Connection, Hinged Filter Door & Toolless Access Panels
CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
Unitary Products Group
7
036-21504-006-A-1105
Hinged Filter Door & Toolless Access Cabinet
DW CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
DX CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless
Access Panels
EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door &
Toolless Access Panels
ES Johnson UNT Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels
ET Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
EU Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
EV Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
EW Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
EX Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access
Panels
GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless
Access Panels
GS Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan
GT Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
GU Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
GV Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
GW Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
GX Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels
8
Unitary Products Group
036-21504-006-A-1105
Hinged Filter Door & Toolless Access Cabinet
PB
PC
PD
PE
PF
PG
PH
PJ
PK
PL
PM
PN
PP
PQ
PR
Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels
PS Novar ETC-3 Controller, DFS, APS, SS Drain Pan
PT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard
PU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils
PV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil
PW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils
PX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils
UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels
UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels
UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels
UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels
UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels
UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels
UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U1 Technicoat Condenser & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U4 Technicoat Evaporator & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels
U7 Technicoat Evaporator & Condenser Coils & SS Drain Pan, Hinged Filter Door & Toolless Access Panels
U9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless
Access Panels
QA Simplicity Intelli-Comfort Controller with Hinged Filter Door & Toolless Access Panels
QB Simplicity Intelli-Comfort Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Unitary Products Group
9
036-21504-006-A-1105
Hinged Filter Door & Toolless Access Cabinet
QC
QD
QE
QF
QG
QH
QJ
QK
QL
QM
QN
QP
QQ
QR
QS
QT
QU
QV
QW
QX
Simplicity Intelli-Comfort Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless
Simplicity Intelli-Comfort Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
XA Intelli-Comfort w/Mod Link Controller, Hinged Filter Door & Toolless Access Panels
XB Intelli-Comfort w/Mod Link Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XC Intelli-Comfort w/Mod Link Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels
XF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels
XK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels
XL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
XN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels
XP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan
XQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels
XR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless
XS Intelli-Comfort w/Mod Link Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels
XT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels
XU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels
XV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels
XW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels
XX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door &
Toolless Access Panels
10
Unitary Products Group
036-21504-006-A-1105
FEATURES
gas valve, if applicable, and the temperature limit
switch on gas heat units. The unit control board will
alarm on ignition failures, compressor lockouts and
repeated limit switch trips.
All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers,
electric heaters, phase monitor, convenience outlet, dirty filter
switch, disconnect switch, smoke detectors, and coil guard to
make them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged
and tested at the factory to simplify the field installation and to
provide years of dependable operation.
All models (including those with an economizer) are suitable
for either bottom or horizontal duct connections. For bottom
duct, remove the sheet metal panels from the supply and
return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear
of the unit.
All models are available with these “factory mounted” outdoor
air damper options:
•
Nuisance Trip Protection- To prevent nuisance
trouble calls, the control board uses a “three strikes,
you’re out” philosophy. The high and low-pressure
switches and the freezestats must trip three times
within two hours before the unit control board will
lock out the compressor.
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
All units have long lasting powder paint cabinets with 1000
hour salt spray test approval under ASTM-B117 procedures.
•
Single enthalpy economizer
All models are CSA listed.
•
Motorized outdoor air damper
•
Warranty - All models include a one-year limited parts
warranty on the complete unit. Compressors and electric
heater elements carry a five-year warranty. Gas heat
exchangers carry a 10-year parts warranty.
•
Gas Heat Operation - All single phase models with gas
heat have minimum annual fuel utilization efficiency
(AFUE) of 80%. All three phase models with gas heat
have minimum steady state efficiency of 80%. Each section includes a durable heat exchanger with aluminized
steel or optional stainless steel tubes, a redundant gas
valve, spark ignition, power venting, an ignition module for
100% shut-off and all of the safety controls required to
meet the latest ANSI standards.
Supply air blowers are equipped with either a direct drive or a
belt drive that can be adjusted to meet the exact requirements of the job.
All compressors are equipped with internal pressure relief.
Every refrigerant circuit includes a liquid line filter-drier, a high
pressure switch and a suction line with a freezestat and low
pressure/loss of charge switch to protect all system components.
•
Simplicity™ Controls - Simplicity™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•
•
•
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the
outdoor air temperature is low or when free cooling
is available.
The gas supply piping can be routed into the heating
compartment through a hole in the base pan of the unit
or through a knockout in the piping panel on the front of
the unit.
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti short cycle delay can be temporarily
overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
Unitary Products Group
Electric Heat Operation - All electric heat models are
wired for a single power source and include a bank of
nickel chromium elements mounted at the discharge of
the supply air blower to provide a high velocity and uniform distribution of air across the heating elements.
Every element is fully protected against excessive temperature by thermal limit switches.
The power supply wiring can be routed into the control
box through a threaded pipe connection (field supplied)
in the base pan of the unit or through a knockout in the
wiring panel on the side of the unit.
•
BAS Controls - York’s Sunline™ series units offer factory
mounted BAS controls such as SImplicity™ INTELLIComfort™, Novar, Honeywell, Johnson, and CPC.
11
036-21504-006-A-1105
FIGURE 1 - UNIT CUTAWAY
FACTORY-INSTALLED OPTIONS
•
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a
pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
12
PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes
Technicoat 10-1TM processes. Coating is applied by total
immersion of the complete coil for maximum protection.
•
ELECTRIC HEATERS - Wired for single point power
supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
•
FILTER OPTIONS - Standard units are shipped with 1”
throw-away filters installed. 2” pleated filters are offered
as a factory installed option.
•
CONVENIENCE OUTLET - This 110 volt outlet can be
“powered” by the unit with a stepdown transformer or the
unit may be ordered with a “non-powered” convenience
outlet that can be wired in the field.
•
DISCONNECT SWITCH - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
•
BAS - Building Automation System Controls
Simplicity™ INTELLI-Comfort™ CONTROL - The
York® Simplicity™ INTELLI-Comfort™ control is factory
installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a
field installed dirty filter indicator switch, an air-proving
switch, an Outside Air Humidity sensor, a Return Air
Humidity sensor, an Inside IAQ sensor, and an Outside
Air IAQ sensor. Construction mode operation, 365-day
real time clock with 7 day programming plus holiday
Unitary Products Group
036-21504-006-A-1105
scheduling is built-in. Two different modes of demand
ventilation are achieved through the INTELLI-Comfort™
using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside
CO2 sensor to perform Differential Demand Ventilation.
It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the
equipment when harsh operating conditions exist.
Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the
on-board connection for hot gas re-heat system. It uses
the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the
Occupied Time Period to begin. The Simplicity™
INTELLI-Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate
comfort.
•
Simplicity™ INTELLI-Comfort™ with MOD LINK CONTROL - The York® Simplicity™ INTELLI-Comfort™ with
Mod Link control is factory installed. It includes all the
features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
•
Novar® BAS CONTROL - The Novar® ETC-3 building
automation system controller is factory installed.
Includes supply air sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
•
JOHNSON CONTROLS BAS CONTROL - The Johnson
Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor,
return air sensor, dirty filter indicator switch, and air proving switch.
•
•
•
STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a
full stainless steel heat exchanger assembly.
•
STAINLESS STEEL DRAIN PAN - An optional rustproof stainless steel drain pan is available to provide
years of trouble-free operation in corrosive environments.
•
BOTTOM DRAIN CONNECTION - An optional bottom
drain connection is available for inside the curb connections for applications in cold environments to reduce
freezing drain lines.
•
PHASE MONITORS - Designed to prevent unit damage.
The phase monitor will shut the unit down in an out-ofphase condition.
•
DIRTY FILTER SWITCH - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND
ACCESS PANELS (not hinged) - This option allows for
easy access and maintenance.
NOTE:Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for
tool-less operation.
FIELD-INSTALLED ACCESSORIES
•
CPC BAS CONTROL - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
HONEYWELL BAS CONTROL - The Honeywell
W7750C building automation system controller is factory
installed. Includes air supply sensor, return air sensor,
dirty filter indicator switch, and air proving switch.
•
SMOKE DETECTORS - (supply air & return air) The
smoke detectors stop operation of the unit by interrupting
power to the control board if smoke is detected within the
air compartment.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
Unitary Products Group
SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly
with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal
1% leakage type dampers.
The enthalpy system contains one sensor that monitors
the outdoor air and determines when the air is cool
enough and dry enough to provide free cooling.
The rainhood is painted to match the basic unit and must
be field-assembled before installing.
•
MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to
some pre-set position whenever the supply air blower is
operating and will drive fully closed when the blower unit
shuts down.
The rain hood is painted to match the basic unit and
must be field assembled before installing.
•
ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent
operation at excessive temperatures.
13
036-21504-006-A-1105
•
•
•
•
ROOF CURBS - Eight and fourteen-inch high roof curbs
provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association
(NRCA) and are shipped knocked-down for field assembly.
•
Roof curbs are designed to fit inside the base rails of the
unit and include both a wood nailing strip and duct
hanger supports.
BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure
on units with an economizer without power exhaust. This
accessory includes a rain hood, a bird screen and a fully
assembled damper. With bottom duct connections, the
damper should be mounted over the opening in the
return air panel. With horizontal ductwork, the accessory
should be mounted on the return air duct.
•
HIGH ALTITUDE NATURAL GAS - Burner orifices and
pilot orifices are provided for proper furnace operation at
altitudes up to 6,000 feet.
ENTHALPY ACCESSORY CONTROL KIT - This kit
contains the required components to convert a single
enthalpy economizer to dual enthalpy.
•
BURGLAR BARS - Mount in the supply and return
openings to prevent entry into the duct work.
•
FLUE EXHAUST EXTENSION KIT - In locations with
wind or weather conditions which may interfere with
proper exhausting of furnace combustion products, this
kit can be installed to prevent the flue exhaust from
entering nearby fresh air intakes.
•
CO2 SENSOR - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
present limits.
•
COIL GUARD - Customers can purchase a coil guard kit
to protect the condenser coil from damage. This is not a
hail guard kit.
•
HAIL GUARD - Hail guard kit is available to prevent unit
from hail damage. This is a sloped hood that fits above
the coil.
•
GAS PIPING KIT - This kit supplies all necessary fittings
and shut off valve.
PROPANE - Burner orifices, pilot orifices and gas valve
parts are provided to convert a natural gas furnace to
propane.
HIGH ALTITUDE PROPANE - Burner orifices and pilot
orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the
basic propane conversion kit.
•
LOW NOX KIT- Required to reduce the emission of
nitrogen oxides below 40 nanograms per joule.
•
POWER EXHAUST - Our single input economizer
options are available with power exhaust. Whenever the
outdoor air intake dampers are opened for free cooling,
the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation.
The power exhaust option can only be used on bottom duct configurations.
14
Unitary Products Group
036-21504-006-A-1105
TABLE 1: SOUND POWER RATING1
UNIT
SIZE
ESP
SOUND POWER (db 10-12 Watts)
BLOWER
Octave Band Centerline Frequency (Hz)
CFM
IWG
SPEED
KW
63
125
250
500
1,000
2,000
4,000
8,000
SWL
dB(A)
dB(A)
@
10Ft.2
036
1,200
0.6
LOW
0.60
84
84
74
67
69
62
57
52
74
41
048
1,600
0.55
HIGH
0.80
85
85
75
68
70
63
58
53
75
42
060
2,000
0.45
HIGH
1.00
86
86
76
69
71
64
59
54
76
43
072
2,200
0.3
HIGH
1.35
87
87
77
70
72
65
60
55
77
44
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The
dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan
manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
TABLE 2: CAPACITY RATINGS - (ARI 210/240)1
TABLE 3: GAS HEAT RATINGS1
MODEL
MBH
EER2
SEER3
DF036
42.5
10.1
11.5
DF048
49.5
10.0
11.0
DF060
58.5
10.05
11.0
DF072
70.5
10.4
-
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling
capacity in Btu’s per hour (Btuh) divided by the power
input in watts, expressed in Btuh per watt (Btuh/watt).
3. SEER = Seasonal Energy Efficiency Ratio.
MODEL
MBH
INPUT
MBH
OUTPUT
AFUE
(%)
TEMP
RISE ºF
DF036N04
DF036N08
50
100
40
80
80.9
80.5
15 - 45
40 - 70
DF048N06
DF048N10
75
125
60
100
80.9
80.3
25 - 55
45 - 75
DF060N08
DF060N10
100
125
80
100
80.5
80.3
25 - 55
35 - 65
DF072N08
DF072N10
100
125
80
100
80.5
80.3
25 - 55
35 - 65
1. All units are single-stage heating.
TABLE 4: 2 STAGE GAS HEAT RATINGS
MODEL1
MBH INPUT
MBH OUTPUT
1ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE
STEADY STATE EFFICIENCY
1ST STAGE
2ND STAGE
RISE
MIN.
MAX.
MINIMUM HEATING
AIRFLOW (CFM)
DF036D06
45
75
35.8
60.8
79.4
81.1
35
70
790
DF036D10
69
115
55.2
92
80.0
80.2
55
90
950
DF048D06
45
75
35.7
60.8
79.4
81.1
25
70
790
DF048D10
75
125
60.4
100.6
80.5
80.5
45
75
1230
DF060D06
45
75
35.8
60.8
79.4
81.1
35
70
1010
DF060D10
75
125
60.4
100.6
80.5
80.5
45
75
1230
DF072D06
45
75
35.8
60.8
79.4
81.1
35
70
1230
DF072D10
75
125
60.4
100.6
80.5
80.5
45
75
1230
1. Models are 3Ø only.
Unitary Products Group
15
036-21504-006-A-1105
TABLE 5: DF036 COOLING CAPACITIES (3 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
TOTAL
1
CFM
1500
1350
1200
1050
900
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
55
52
42
42
51
49
39
40
48
46
36
37
46
44
35
36
45
42
34
35
3.4
3.3
3.2
3.2
3.3
3.3
3.2
3.2
3.2
3.3
3.2
3.2
3.3
3.3
3.2
3.2
3.3
3.2
3.2
3.1
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
35
47
42
42
32
42
39
40
28
37
36
37
26
34
35
36
24
31
34
35
31
42
42
42
28
38
39
40
24
34
36
37
23
31
34
35
21
29
32
33
26
38
42
42
24
34
37
38
21
30
33
35
19
28
31
32
18
26
26
30
22
33
37
38
20
30
33
34
17
27
29
31
16
25
28
29
15
23
26
27
18
29
33
33
16
26
29
30
14
23
26
27
13
22
24
26
13
20
23
25
24
28
29
22
25
26
19
22
24
18
21
23
17
20
22
20
24
24
18
21
22
16
19
20
15
18
20
15
18
19
51
48
39
39
49
47
37
38
48
46
36
37
45
43
34
35
43
40
32
33
3.7
3.6
3.5
3.5
3.6
3.5
3.5
3.5
3.6
3.5
3.5
3.4
3.6
3.5
3.4
3.4
3.5
3.5
3.4
3.4
86
83
80
77
74
71
68
35
45
39
39
32
42
37
38
29
39
36
37
26
35
34
35
23
30
32
33
30
41
39
39
28
38
37
38
25
36
36
37
23
32
33
34
20
28
30
32
26
36
39
39
24
34
37
38
22
32
35
37
20
28
31
33
17
25
28
29
21
32
34
35
20
30
33
34
18
38
31
33
16
25
28
30
15
22
25
26
17
28
30
30
16
26
29
30
15
25
28
30
13
22
25
27
12
19
22
24
23
25
26
22
25
26
21
24
26
19
22
23
16
19
21
19
21
21
18
21
22
18
21
22
16
19
20
14
17
18
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
INPUT2 kW
CFM
WB °F
CAP.1
MBH
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
47
44
36
36
44
42
34
34
42
40
32
32
40
38
30
31
38
36
29
30
3.9
3.8
3.7
3.7
3.9
3.8
3.7
3.7
3.8
3.8
3.7
3.7
3.8
3.7
3.7
3.6
3.8
3.7
3.6
3.6
1500
1350
1200
1050
900
105°F
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
TOTAL
86
83
80
77
74
71
68
CAP.1
MBH
33
43
36
36
30
39
34
34
27
36
32
32
24
32
30
31
22
29
29
30
29
39
36
36
26
36
34
34
23
32
32
32
21
29
30
31
19
26
28
29
25
35
36
36
22
32
33
34
20
29
31
33
18
26
28
30
16
23
26
27
20
30
31
31
18
28
29
30
16
25
28
29
15
23
25
27
13
20
23
24
16
26
27
27
14
24
25
26
12
22
24
26
12
19
22
24
11
17
20
21
22
22
23
20
21
22
18
20
22
16
19
20
15
17
19
17
18
18
16
17
18
14
17
19
13
16
17
12
15
16
43
40
33
33
39
37
30
30
36
34
27
28
35
33
27
27
34
32
26
26
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
INPUT2 kW
4.1
4.1
4.0
3.9
4.1
4.0
4.0
3.9
4.1
4.0
3.9
3.9
4.1
4.0
3.9
3.9
4.0
4.0
3.9
3.9
86
83
80
77
74
71
68
32
40
33
33
28
36
30
30
24
33
27
28
22
30
27
27
20
27
26
26
28
38
33
33
24
33
30
30
21
29
27
28
19
26
27
27
18
24
26
26
23
33
33
33
20
29
30
31
17
25
28
29
16
23
26
27
15
21
24
25
19
29
28
28
16
25
26
27
14
22
24
26
13
20
22
24
12
18
21
22
14
24
24
24
12
21
22
23
10
18
20
22
10
17
19
21
9
16
18
19
20
19
20
17
18
19
15
17
18
14
16
17
13
15
17
16
15
15
13
14
15
11
13
15
11
13
14
10
13
14
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
16
Unitary Products Group
036-21504-006-A-1105
TABLE 6: DF048 COOLING CAPACITIES (4 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
TOTAL
1
CFM
2000
1800
1600
1400
1200
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
64
57
54
54
62
55
52
52
59
54
50
50
58
52
49
49
57
50
48
48
3.9
3.8
3.8
3.8
3.9
3.8
3.8
3.8
3.9
3.8
3.7
3.7
3.8
3.8
3.7
3.7
3.8
3.8
3.7
3.7
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
45
55
54
54
42
51
52
52
38
48
50
50
35
44
48
49
32
40
47
48
39
49
54
54
36
46
52
52
33
43
50
50
31
39
47
48
29
36
44
45
33
43
53
54
31
40
49
51
29
38
46
47
27
35
43
44
25
32
40
41
27
37
47
48
25
35
44
45
24
33
41
42
23
31
39
40
21
29
36
37
21
31
41
42
20
30
39
40
19
29
36
38
18
27
34
36
17
25
33
34
25
35
36
24
33
35
24
32
33
22
30
31
21
29
30
19
29
30
19
28
29
19
27
28
18
26
27
17
25
26
60
53
50
50
58
52
49
49
57
52
47
47
55
49
46
46
53
47
45
45
4.2
4.1
4.0
4.0
4.2
4.1
4.1
4.1
4.2
4.2
4.1
4.1
4.2
4.2
4.1
4.1
4.2
4.2
4.1
4.1
86
83
80
77
74
71
68
44
53
50
50
41
50
49
49
38
47
47
47
34
42
46
46
31
38
45
45
38
47
50
50
35
44
49
49
33
42
47
47
30
38
45
46
28
35
42
43
32
41
50
50
30
39
47
49
28
37
45
46
26
34
42
43
24
31
38
39
26
35
44
46
24
34
42
44
23
32
40
41
22
30
37
38
20
27
34
35
20
29
38
40
19
28
37
38
18
28
35
37
17
26
33
34
16
23
31
32
23
32
34
23
31
33
23
31
32
21
29
30
20
27
28
17
26
28
18
26
27
18
26
27
17
25
26
16
23
24
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
INPUT2 kW
CFM
WB °F
CAP.1
MBH
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
56
50
47
47
54
49
46
46
53
48
44
44
51
46
43
43
50
44
42
42
4.7
4.6
4.5
4.5
4.7
4.6
4.5
4.5
4.7
4.6
4.6
4.5
4.7
4.6
4.5
4.5
4.7
4.6
4.5
4.5
2000
1800
1600
1400
1200
105°F
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
TOTAL
86
83
80
77
74
71
68
CAP.1
MBH
42
50
47
47
39
47
46
46
36
45
44
44
33
41
43
43
30
37
42
42
36
45
47
47
34
43
46
46
31
40
44
44
29
37
42
43
27
33
41
41
30
39
47
47
29
37
45
46
27
35
43
44
25
33
40
41
23
30
37
38
25
33
41
44
23
32
40
42
22
31
38
39
21
28
36
37
19
26
33
34
19
28
35
38
17
27
34
36
17
26
33
34
16
24
31
32
16
22
29
30
22
29
32
21
29
31
21
29
30
20
27
28
19
26
27
16
23
26
16
23
26
16
24
25
16
23
24
15
22
23
53
47
44
44
51
46
43
43
49
44
41
41
48
43
40
40
47
42
39
39
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
INPUT2 kW
5.2
5.1
5.0
5.0
5.1
5.1
5.0
5.0
5.1
5.1
5.0
5.0
5.1
5.0
5.0
5.0
5.1
5.0
5.0
5.0
86
83
80
77
74
71
68
41
47
44
44
38
45
43
43
35
43
41
41
32
40
40
40
30
36
39
39
35
44
44
44
33
41
43
43
30
39
41
41
28
35
40
40
26
32
39
39
29
38
44
44
27
36
43
43
25
34
41
41
24
31
38
39
22
29
35
36
23
32
38
42
22
31
37
40
21
29
36
37
20
27
34
35
18
25
32
33
17
26
32
36
17
25
32
34
16
24
31
32
15
23
30
31
15
21
28
29
20
26
30
20
26
29
19
26
28
19
25
26
18
24
25
14
20
24
14
21
24
15
22
23
14
21
22
14
21
22
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
Unitary Products Group
17
036-21504-006-A-1105
TABLE 7: DF060 COOLING CAPACITIES (5 TON)
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
85°F
TOTAL
1
CFM
2500
2250
2000
1750
1500
POWER
CAP.
MBH
INPUT2 kW
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
75
67
62
56
74
67
61
55
73
66
60
55
72
65
60
54
71
63
59
53
4.6
4.5
4.5
4.4
4.6
4.5
4.5
4.4
4.5
4.5
4.4
4.4
4.5
4.5
4.4
4.4
4.5
4.5
4.4
4.4
95°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
TOTAL
1
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
83
80
77
74
71
68
CAP.
MBH
INPUT2 kW
86
53
64
62
56
51
62
61
55
49
60
60
55
45
55
60
54
41
50
59
53
46
56
62
56
44
55
61
55
43
54
60
55
40
50
59
53
37
46
57
52
38
49
62
56
37
48
61
55
37
48
60
54
34
44
56
50
32
41
52
47
31
41
54
48
31
42
54
48
31
42
54
48
29
39
50
45
27
36
47
42
23
34
47
41
24
35
47
41
25
36
48
42
24
34
45
40
23
32
43
38
26
39
33
28
40
35
30
42
36
29
40
34
27
38
33
19
32
26
21
34
28
24
36
30
23
35
29
22
34
28
73
65
60
55
72
64
59
53
70
63
58
52
68
61
56
50
66
58
54
49
5.0
4.9
4.9
4.8
5.0
5.0
4.9
4.8
5.0
5.0
4.9
4.8
5.0
4.9
4.9
4.8
5.0
4.9
4.9
4.8
86
83
80
77
74
71
68
53
64
60
55
50
61
59
53
47
58
58
52
43
53
56
50
40
48
54
49
46
56
60
55
43
54
59
53
41
52
58
52
38
47
56
50
35
43
54
49
38
49
60
55
37
47
59
53
35
46
57
61
33
42
53
48
30
39
49
44
31
41
53
47
30
41
52
46
29
40
51
45
27
37
48
42
26
34
44
40
23
34
46
40
23
34
45
39
23
34
45
39
22
32
42
37
21
29
40
35
26
38
32
27
38
33
28
39
33
26
27
32
25
35
30
19
31
25
20
32
26
22
33
27
21
32
27
20
31
26
TEMPERATURE OF AIR ON CONDENSER COIL
AIR ON
EVAPORATOR
COIL
TOTAL
INPUT2 kW
CFM
WB °F
CAP.1
MBH
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
66
59
55
49
65
58
54
48
63
58
52
47
62
55
51
46
60
53
49
44
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.4
5.5
5.5
5.4
5.4
2500
2250
2000
1750
1500
105°F
115°F
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
TOTAL
86
83
80
77
74
71
68
CAP.1
MBH
51
58
55
49
48
57
54
48
45
55
52
47
42
50
51
46
38
46
49
44
44
54
55
49
42
52
54
48
39
50
52
47
36
45
51
46
33
41
49
44
36
46
55
49
35
45
54
48
33
44
52
47
31
40
50
45
29
37
47
42
29
39
47
42
28
38
48
42
28
38
48
43
26
35
45
40
24
32
42
37
21
31
40
35
21
31
41
36
22
32
42
37
21
30
40
35
19
27
37
33
24
32
27
25
34
29
26
36
31
24
35
30
23
33
28
16
25
20
18
28
22
20
30
25
19
29
24
18
28
23
60
53
49
44
58
52
48
44
57
52
47
43
55
50
46
41
53
47
44
40
SENSIBLE CAPACITY1
ENTERING DRY BULB, °F
POWER
INPUT2 kW
6.0
6.0
5.9
5.9
6.0
6.0
5.9
5.9
6.0
6.0
5.9
5.9
6.1
6.0
6.0
5.9
6.1
6.1
6.0
6.0
86
83
80
77
74
71
68
49
53
49
44
46
52
48
44
44
52
47
43
40
48
46
41
36
44
44
40
41
51
49
44
40
49
48
44
38
48
47
43
35
43
46
41
32
39
44
40
34
43
49
44
33
43
48
44
32
42
47
43
30
38
46
41
27
35
44
40
26
36
42
37
26
36
44
39
26
36
46
41
24
33
43
38
23
30
39
35
19
28
34
29
20
29
37
32
20
30
40
35
19
28
37
33
18
25
35
30
21
27
22
22
30
25
24
34
29
22
32
27
21
30
26
13
19
15
16
24
19
18
28
23
17
27
22
16
25
21
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
18
Unitary Products Group
036-21504-006-A-1105
TABLE 8: DF072 COOLING CAPACITIES (6 TON)
OUTDOOR AMBIENT TEMPERATURE (°F)
85°F
RETURN AIR
CFM
2750
2475
2200
1925
1650
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
GROSS
POWER
CAP.
INPUT1 Kw
MBH
83.1
79.5
72.7
66.7
82.4
78.8
72.1
66.1
81.7
78.1
71.4
65.5
79.3
75.8
69.4
63.6
77
73.6
67.3
61.7
5.24
5.15
5.08
5.04
5.25
5.16
5.10
5.05
5.26
5.18
5.11
5.06
5.24
5.15
5.08
5.04
5.21
5.12
5.06
5.01
95°F
GROSS SENSIBLE CAPACITY1 (MBh)
RETURN AIR DRY BULB TEMP. (°F)
86
83
80
77
74
71
68
54.6
67.8
72.7
66.7
52.1
65.0
72.1
66.1
49.6
62.3
71.4
65.5
45.6
57.5
67.7
63.6
41.6
52.7
64.0
61.7
46.4
59.6
72.7
66.7
44.8
57.7
70.7
66.1
43.2
55.8
68.7
65.5
40.0
51.9
64.0
62.3
36.9
48.0
59.3
59.2
38.2
51.4
64.8
64.6
37.5
50.4
63.5
63.4
36.8
49.4
62.3
62.1
34.5
46.4
58.5
58.3
32.2
43.3
54.6
54.5
30.0
43.2
56.6
56.4
30.2
43.1
56.2
56.1
30.3
43.0
55.9
55.7
28.9
40.8
52.9
52.7
27.5
38.6
49.9
49.8
21.8
35.0
48.4
48.2
22.9
35.8
48.9
48.8
23.9
36.6
49.5
49.3
23.4
35.3
47.3
47.2
22.8
33.9
45.2
45.0
26.8
40.2
40.0
28.5
41.6
41.5
30.2
43.1
42.9
29.7
41.8
41.6
29.2
40.5
40.3
18.6
32.0
31.8
21.2
34.3
34.1
23.8
36.6
36.5
24.1
36.2
36.1
24.5
35.8
35.6
GROSS
POWER
CAP.
INPUT1 Kw
MBH
80.2
75.3
68.3
65.8
79.9
75.0
68.0
65.5
79.6
74.7
67.7
65.2
77.1
72.3
65.6
63.2
74.5
69.9
63.4
61.1
5.92
5.80
5.74
5.77
5.89
5.78
5.72
5.74
5.87
5.75
5.69
5.72
5.86
5.74
5.68
5.71
5.85
5.73
5.67
5.70
GROSS SENSIBLE CAPACITY1 (MBh)
RETURN AIR DRY BULB TEMP. (°F)
86
83
80
77
74
71
68
53.1
66.6
68.3
65.8
50.5
63.8
68.0
65.5
48.0
60.9
67.7
65.2
43.9
56.0
64.5
63.2
39.8
51.0
61.3
61.1
44.9
58.4
68.3
65.8
43.2
56.5
67.3
65.5
41.6
54.5
66.3
65.2
38.4
50.4
61.5
61.7
35.1
46.3
56.6
58.2
36.7
50.2
62.5
64.5
35.9
49.1
61.2
63.1
35.2
48.1
59.9
61.8
32.8
44.9
55.9
57.7
30.4
41.6
51.9
53.5
28.5
42.0
54.3
56.3
28.6
41.8
53.9
55.8
28.7
41.7
53.5
55.4
27.2
39.3
50.3
52.1
25.7
36.9
47.2
48.8
20.3
33.8
46.1
48.1
21.3
34.5
46.6
48.5
22.3
35.3
47.1
49.0
21.7
33.8
44.8
46.5
21.0
32.2
42.5
44.1
25.6
37.9
39.9
27.2
39.3
41.2
28.9
40.7
42.6
28.2
39.2
41.0
27.5
37.7
39.4
17.4
29.7
31.7
19.9
32.0
33.9
22.4
34.3
36.2
22.6
33.7
35.4
22.8
33.0
34.7
OUTDOOR AMBIENT TEMPERATURE (°F)
105°F
RETURN AIR
CFM
2750
2475
2200
1925
1650
WB °F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
GROSS
POWER
CAP.
INPUT1 Kw
MBH
76.3
70.2
62.2
61.2
76.1
70.0
62.0
61.0
75.9
69.8
61.9
60.9
73.1
67.2
59.6
58.6
70.3
64.6
57.3
56.4
6.66
6.55
6.48
6.50
6.63
6.52
6.45
6.47
6.59
6.48
6.41
6.43
6.58
6.47
6.40
6.42
6.57
6.46
6.39
6.41
115°F
GROSS SENSIBLE CAPACITY1 (MBh)
RETURN AIR DRY BULB TEMP. (°F)
86
83
80
77
74
71
68
51.5
64.2
62.2
61.2
49.0
61.4
62.0
61.0
46.4
58.6
61.9
60.9
42.3
53.5
59.1
58.6
38.1
48.5
56.3
56.4
43.3
56.0
62.2
61.2
41.7
54.1
61.7
61.0
40.0
52.2
61.2
60.9
36.7
48.0
57.0
57.3
33.4
43.8
52.8
53.8
35.1
47.8
58.8
60.1
34.3
46.8
57.5
58.8
33.6
45.7
56.2
57.5
31.1
42.4
52.2
53.3
28.7
39.1
48.1
49.1
26.9
39.6
50.6
51.9
27.0
39.5
50.2
51.5
27.2
39.3
49.8
51.0
25.6
36.9
46.6
47.7
24.0
34.4
43.4
44.4
18.7
31.5
42.4
43.7
19.7
32.2
42.9
44.2
20.7
32.9
43.4
44.6
20.0
31.3
41.0
42.2
19.3
29.7
38.7
39.7
23.3
34.2
35.5
24.9
35.6
36.9
26.5
37.0
38.2
25.7
35.5
36.6
25.0
34.0
35.0
15.1
26.0
27.3
17.6
28.3
29.5
20.1
30.6
31.8
20.2
29.9
31.0
20.3
29.2
30.3
GROSS
POWER
CAP.
INPUT1 Kw
MBH
72.4
65.0
56.1
56.7
72.3
65.0
56.1
56.6
72.2
64.9
56.0
56.5
69.1
62.1
53.6
54.1
66.1
59.4
51.2
51.7
7.40
7.31
7.22
7.24
7.36
7.26
7.18
7.19
7.31
7.22
7.13
7.15
7.30
7.20
7.12
7.13
7.28
7.19
7.11
7.12
GROSS SENSIBLE CAPACITY1 (MBh)
RETURN AIR DRY BULB TEMP. (°F)
86
83
80
77
74
71
68
50.0
61.9
56.1
56.7
47.4
59.1
56.1
56.6
44.8
56.2
56.0
56.5
40.6
51.1
53.6
54.1
36.4
45.9
51.2
51.7
41.8
53.7
56.1
56.7
40.1
51.7
56.1
56.6
38.4
49.8
56.0
56.5
35.0
45.5
52.5
53.0
31.7
41.2
49.0
49.4
33.6
45.5
55.2
55.7
32.8
44.4
53.9
54.4
32.0
43.4
52.6
53.1
29.5
40.0
48.4
48.9
26.9
36.5
44.3
44.7
25.4
37.3
47.0
47.5
25.5
37.1
46.6
47.1
25.6
37.0
46.2
46.7
23.9
34.4
42.9
43.3
22.2
31.8
39.6
40.0
17.2
29.1
38.8
39.3
18.2
29.8
39.2
39.8
19.2
30.5
39.7
40.3
18.4
28.8
37.3
37.8
17.5
27.1
34.9
35.3
20.9
30.6
31.1
22.5
31.9
32.5
24.1
33.3
33.9
23.3
31.7
32.2
22.4
30.2
30.6
12.7
22.4
22.9
15.2
24.6
25.2
17.7
26.9
27.4
17.7
26.2
26.7
17.7
25.5
25.9
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE
Table, multiply this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input
is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
Unitary Products Group
19
036-21504-006-A-1105
TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
3
12
UNIT
TONNAGE
3
12
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
843
860
880
925
919
1005
956
1065
993
1145
1030
1195
1067
1235
1900
817
775
854
850
893
920
930
995
970
1065
1008
1125
1046
1170
1800
790
700
828
760
867
840
906
905
944
980
985
1040
1025
1100
1700
-
-
802
670
840
745
881
815
920
900
961
970
1001
1030
1600
-
-
-
-
818
665
858
740
898
820
940
890
980
950
1500
-
-
-
-
-
-
842
695
882
755
922
835
962
895
1400
-
-
-
-
-
-
833
650
867
705
904
765
942
820
1300
-
-
-
-
-
-
-
-
858
665
893
725
932
785
1200
-
-
-
-
-
-
-
-
847
640
880
680
916
730
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
1.10
1.20
1.30
0.80
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
1103
1270
-
-
-
-
-
-
-
-
-
-
-
-
1900
1085
1210
-
-
-
-
-
-
-
-
-
-
-
-
1800
1064
1145
1102
1180
-
-
-
-
-
-
-
-
-
-
1700
1040
1075
1081
1115
1121
1140
-
-
-
-
-
-
-
-
1600
1020
1005
1060
1050
1100
1085
-
-
-
-
-
-
-
-
1500
1003
945
1044
995
1086
1035
-
-
-
-
-
-
-
-
1400
982
880
1024
920
1067
965
1107
1000
-
-
-
-
-
-
1300
970
835
1010
870
1053
920
1099
960
-
-
-
-
-
-
1200
953
780
992
815
1034
855
1080
905
-
-
-
-
-
-
0.90
1.00
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
20
Unitary Products Group
036-21504-006-A-1105
TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
4
12
UNIT
TONNAGE
4
12
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
843
860
880
925
919
1005
956
1065
993
1145
1030
1195
1067
1235
1900
817
775
854
850
893
920
930
995
970
1065
1008
1125
1046
1170
1800
790
700
828
760
867
840
906
905
944
980
985
1040
1025
1100
1700
-
-
802
670
840
745
881
815
920
900
961
970
1001
1030
1600
-
-
-
-
818
665
858
740
898
820
940
890
980
950
1500
-
-
-
-
-
-
842
695
882
755
922
835
962
895
1400
-
-
-
-
-
-
833
650
867
705
904
765
942
820
1300
-
-
-
-
-
-
-
-
858
665
893
725
932
785
1200
-
-
-
-
-
-
-
-
847
640
880
680
916
730
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
1.10
1.20
1.30
0.80
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2000
1103
1270
-
-
-
-
-
-
-
-
-
-
-
-
1900
1085
1210
-
-
-
-
-
-
-
-
-
-
-
-
1800
1064
1145
1102
1180
-
-
-
-
-
-
-
-
-
-
1700
1040
1075
1081
1115
1121
1140
-
-
-
-
-
-
-
-
1600
1020
1005
1060
1050
1100
1085
-
-
-
-
-
-
-
-
1500
1003
945
1044
995
1086
1035
-
-
-
-
-
-
-
-
1400
982
880
1024
920
1067
965
1107
1000
-
-
-
-
-
-
1300
970
835
1010
870
1053
920
1099
960
-
-
-
-
-
-
1200
953
780
992
815
1034
855
1080
905
-
-
-
-
-
-
0.90
1.00
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
Unitary Products Group
21
036-21504-006-A-1105
TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (5,6 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
5, 61 2
UNIT
TONNAGE
5, 61 2
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
0.60
0.40
0.50
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2500
1059
1560
1077
1590
1095
1630
1114
1650
1134
1660
1158
1685
1181
1720
2400
1032
1405
1054
1470
1074
1525
1094
1560
1116
1595
1140
1620
1167
1640
2300
1005
1260
1024
1275
1049
1370
1069
1440
1090
1475
1116
1505
1142
1535
2200
980
1160
1002
1170
1022
1190
1044
1250
1066
1350
1090
1410
1117
1440
2100
930
1060
957
1070
983
1080
1010
1100
1039
1160
1064
1260
1092
1340
2000
877
950
908
975
941
1000
976
1020
1009
1050
1040
1100
1070
1225
1900
-
-
-
-
894
885
940
940
980
980
1014
1020
1047
1095
1800
-
-
-
-
855
815
903
860
950
905
988
940
1022
970
1700
-
-
-
-
-
-
884
815
925
850
964
880
1001
910
1600
-
-
-
-
-
-
864
770
908
805
948
835
987
870
1500
-
-
-
-
-
-
-
-
882
740
926
780
965
830
0.20
0.30
0.70
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3
1.10
1.20
1.30
0.80
AIR
FLOW
CFM
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
RPM
WATTS
2500
-
-
-
-
-
-
-
-
-
-
-
-
-
-
2400
1193
1665
-
-
-
-
-
-
-
-
-
-
-
-
2300
1170
1580
1202
1620
-
-
-
-
-
-
-
-
-
-
2200
1148
1480
1180
1530
-
-
-
-
-
-
-
-
-
-
2100
1121
1385
1155
1425
1190
1475
-
-
-
-
-
-
-
-
2000
1100
1285
1133
1340
1169
1385
1205
1445
-
-
-
-
-
-
1900
1079
1180
1110
1240
1143
1280
1178
1330
1222
1375
-
-
-
-
1800
1058
1060
1090
1135
1122
1190
1158
1240
1196
1295
-
-
-
-
1700
1035
960
1071
1030
1103
1100
1134
1140
1164
1175
1197
1205
-
-
1600
1020
900
1056
965
1088
1035
1118
1065
1145
1105
1170
1130
1198
1150
1500
1004
860
1038
880
1070
925
1101
980
1130
1045
1158
1075
1184
1110
0.90
1.00
1.40
1.50
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for
resistance values on applications other than gas / electric units with side duct airflows.
22
Unitary Products Group
036-21504-006-A-1105
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (3 - 5 TON DIRECT DRIVE) - SIDE DUCT APPLICATION
UNIT
TONNAGE
3
4
5
1
1
1
UNIT
TONNAGE
3
4
5
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2
MOTOR SPEED
0.20
1
1
0.40
0.50
0.60
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
HI
-
-
-
-
1699
825
1650
785
1570
755
MED
1684
800
1631
780
1582
750
1524
720
1410
690
LOW
1487
710
1464
690
1421
670
1367
650
1315
620
HI
1996
960
1933
936
1868
910
1795
880
1722
845
MED
1804
838
1765
810
1714
785
1650
765
1589
735
LOW
1681
760
1640
738
1604
715
1541
695
1490
670
HI
2400
1155
2338
1125
2274
1095
2167
1045
2096
1010
MED
2290
1105
2214
1065
2145
1030
2071
990
1990
950
LOW
2150
1020
2100
990
2029
950
1965
910
1905
880
MOTOR SPEED
1
0.30
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2
0.80
0.90
0.70
WATTS
1.00
CFM
WATTS
CFM
WATTS
CFM
WATTS
CFM
WATTS
HI
1430
725
1360
700
1280
680
1180
655
MED
1324
650
1260
630
1185
610
1100
590
LOW
1246
605
1185
590
1110
570
1020
545
HI
1635
820
1544
790
1419
765
1300
740
MED
1508
705
1407
675
1306
645
1195
625
LOW
1416
645
1337
620
1230
595
1120
575
HI
1990
980
1887
945
1771
905
1629
855
MED
1911
920
1828
885
1724
835
1604
798
LOW
1816
838
1724
800
1644
770
1531
710
1. Side Duct application (230/460/575 Volts)
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance
values.
TABLE 13: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
MOTOR1
ADJUSTABLE MOTOR PULLEY
BELT
(NOTCHED)
FIXED BLOWER PULLEY
MODEL
SIZE
BLOWER
RANGE
(RPM)
HP
FRAME
DESIGNATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIGNATION
OUTSIDE
DIA.
(IN.)
PITCH
DIA.
(IN.)
BORE
(IN.)
DESIGNATION
PITCH
LENGTH
(IN.)
QTY.
3 TON
790/1120
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK61
5.9
5.7
1
A36
37.3
1
4 TON
790/1120
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK61
5.9
5.7
1
A36
37.3
1
5, 6 TON
850/1220
1 1/2
56
1VL40
2.7-3.7
2.4-3.4
5/8
AK56
5.4
5.2
1
A36
37.3
1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located
in the moving air, upstream of any heating device.
Unitary Products Group
23
036-21504-006-A-1105
TABLE 14: STATIC RESISTANCES
RESISTANCE, IWG
DESCRIPTION
CFM
1000
1200
1400
1600
1800
2000
2200
2400
2600
2800
3000
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
0.30
7-15KW
0.04
0.05
0.06
0.07
0.08
0.10
0.12
0.14
0.16
0.19
0.22
20-30KW
0.06
0.07
0.08
0.09
0.11
0.13
0.15
0.17
0.20
0.23
0.26
BOTTOM DUCT CONNECTIONS1
0.06
0.07
0.08
0.09
0.10
0.11
0.12
0.14
0.16
0.19
0.22
COOLING ONLY2
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.23
0.26
0.29
0.32
ECONOMIZER1 3
ELECTRIC
HEATERS1
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air
duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 15: ELECTRIC HEATER CFM LIMITATIONS
MINIMUM SUPPLY AIR CFM
UNITMODEL SIZE NOMINAL
TONS
VOLTAGE
HEATER SIZE NOMINAL KW
5
7
10
15
20
30
208/230-1-60
1100
1100
1200
1200
1300
-
208/230-3-60
1100
1100
1200
1200
1300
-
460-3-60
-
1100
1200
1200
1300
-
575-3-60
-
-
1200
1200
1300
-
208/230-1-60
1300
1300
1300
1300
1300
-
208/230-3-60
1300
1300
1300
1300
1300
-
460-3-60
-
1300
1300
1300
1300
-
575-3-60
-
-
1300
1300
1400
-
208/230-1-60
1600
1600
1600
1600
1600
1600
208/230-3-60
1600
1600
1600
1600
1600
1600
460-3-60
-
1600
1600
1600
1600
1600
575-3-60
-
-
1600
1600
1600
1800
208/230-3-60
1800
1800
1800
1800
1800
1800
460-3-60
-
1800
1800
1800
1800
1800
575-3-60
-
-
1800
1800
1800
1800
3
4
5
6
24
Unitary Products Group
036-21504-006-A-1105
TABLE 16: ELECTRICAL DATA - DF036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
16.7
87
2.3
4.4
0.0
230-1-60
16.7
87
2.3
4.4
0.0
208-3-60
13.1
110
2.3
4.4
0.0
230-3-60
13.1
110
2.3
4.4
0.0
460-3-60
6.7
54
1.3
2.2
0.0
575-3-60
5.1
44
1.3
2.2
0.0
208-1-60
25.0
135
2.3
5.0
0.0
230-1-60
25.0
135
2.3
5.0
0.0
208-3-60
14.7
130
2.3
5.0
0.0
230-3-60
14.7
130
2.3
5.0
0.0
460-3-60
7.7
64
1.3
2.2
0.0
575-3-60
6.4
52
1.3
2.2
0.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Max Fuse /
1
BRKR Size
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2CE045105252
2CE045107252
2CE04511525
2CE04512025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
27.5
30.7
39.2
53.6
77.0
101.1
27.5
33.1
44.6
60.7
88.3
115.9
23.1
24.3
24.9
33.3
46.8
60.7
23.1
24.3
28.1
37.4
53.3
69.2
12.0
13.0
17.9
23.2
32.1
10.7
14.9
21.3
27.7
38.5
38.5
39.9
54.3
77.8
101.8
38.5
38.5
45.3
61.5
89.1
116.7
25.7
25.7
25.7
34.0
47.5
61.4
25.7
25.7
28.8
38.1
54.1
70.0
13.1
13.1
17.9
23.2
32.1
10.8
14.9
21.3
27.7
45
45
45
60
80
110
45
45
45
70
90
125
35
35
35
35
50
70
35
35
35
40
60
70
15
15
20
25
35
15
15
25
30
60
60
60
60
80
110
60
60
60
70
90
125
40
40
40
40
50
70
40
40
40
40
60
70
20
20
20
25
35
15
15
25
30
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
25
036-21504-006-A-1105
TABLE 17: ELECTRICAL DATA - DF060 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
32.1
148
2.3
6.6
0.0
230-1-60
32.1
148
2.3
6.6
0.0
208-3-60
19.3
123
2.3
6.6
0.0
230-3-60
19.3
123
2.3
6.6
0.0
460-3-60
9.1
62
1.3
3.3
0.0
575-3-60
7.9
50
1.3
3.3
0.0
5
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Max Fuse /
1
BRKR Size
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2CE04512046 2
2
2CE04513046
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
49.0
49.0
49.0
56.3
79.8
103.8
141.7
49.0
49.0
49.0
63.5
91.1
118.7
162.4
33.0
33.0
33.0
36.0
49.5
63.4
85.3
33.0
33.0
33.0
40.1
56.1
72.0
97.3
16.0
16.0
19.3
24.6
33.4
47.4
13.6
16.0
22.4
28.8
39.9
80
80
80
80
80
110
150
80
80
80
80
100
125
175
50
50
50
50
50
70
90
50
50
50
50
60
80
100
25
25
25
25
35
50
20
20
25
30
40
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
26
Unitary Products Group
036-21504-006-A-1105
TABLE 18: ELECTRICAL DATA - DF036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
16.7
87
2.3
7.6
0.0
230-1-60
16.7
87
2.3
7.6
0.0
208-3-60
13.1
110
2.3
5.2
0.0
230-3-60
13.1
110
2.3
5.2
0.0
460-3-60
6.7
54
1.3
2.6
0.0
575-3-60
5.1
44
1.3
2
0.0
208-1-60
25.0
135
2.3
7.6
0.0
230-1-60
25.0
135
2.3
7.6
0.0
208-3-60
14.7
130
2.3
5.2
0.0
230-3-60
14.7
130
2.3
5.2
0.0
460-3-60
7.7
64
1.3
2.6
0.0
575-3-60
6.4
52
1.3
2
0.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Max Fuse /
1
BRKR Size
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510525
2CE04510725 2
2CE04511525
2CE04512025
NONE
2
2CE04510746
2CE04511046 2
2CE04511546 2
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2CE04511046 2
2CE04511546 2
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
30.1
33.9
43.2
57.6
81.0
105.1
30.1
37.1
48.6
64.7
92.3
119.9
23.9
25.1
25.9
34.3
47.8
61.7
23.9
25.1
29.1
38.4
54.3
70.2
12.4
13.5
18.4
23.7
32.6
9.8
14.7
21.1
27.5
41.2
41.2
43.2
57.6
81.0
105.1
41.2
41.2
48.6
64.7
92.3
119.9
25.9
25.9
25.9
34.3
47.8
61.7
25.9
25.9
29.1
38.4
54.3
70.2
13.5
13.5
18.4
23.7
32.6
10.6
14.7
21.1
27.5
50
50
50
60
90
110
50
50
50
70
100
125
35
35
35
35
50
70
35
35
35
40
60
80
15
15
20
25
35
15
15
25
30
60
60
60
60
90
110
60
60
60
70
100
125
40
40
40
40
50
70
40
40
40
40
60
80
20
20
20
25
35
15
15
25
30
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
27
036-21504-006-A-1105
TABLE 19: ELECTRICAL DATA - DF060 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
32.1
148
2.3
7.6
0.0
230-1-60
32.1
148
2.3
7.6
0.0
208-3-60
19.3
123
2.3
5.2
0.0
230-3-60
19.3
123
2.3
5.2
0.0
460-3-60
9.1
62
1.3
2.6
0.0
575-3-60
7.9
50
1.3
2
0.0
5
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2
2CE04510746
2CE04511046 2
2
2CE04511546
2
2CE04512046
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
50.0
50.0
50.0
57.6
81.0
105.1
142.9
50.0
50.0
50.0
64.7
92.3
119.9
163.7
31.6
31.6
31.6
34.3
47.8
61.7
83.5
31.6
31.6
31.6
38.4
54.3
70.2
95.5
15.3
15.3
18.4
23.7
32.6
46.6
12.5
14.7
21.1
27.5
38.6
Max Fuse /
BRKR1 Size
Amps
80
80
80
80
90
110
150
80
80
80
80
100
125
175
50
50
50
50
50
70
90
50
50
50
50
60
80
100
20
20
20
25
35
50
15
15
25
30
40
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
28
Unitary Products Group
036-21504-006-A-1105
TABLE 20: ELECTRICAL DATA - DF072 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motors
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-3-60
18.6
156
2.3
5.2
0.0
230-3-60
18.6
156
2.3
5.2
0.0
460-3-60
9.0
75
1.3
2.6
0.0
573-3-60
7.4
54
1.3
2.0
0.0
6
Electric Heater
Model No.
3
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2CE04511046 2
2
2CE04511546
2
2CE04512046
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
30.8
30.8
30.8
34.1
47.9
61.7
83.6
30.8
30.8
30.8
38.4
54.3
70.2
95.5
15.2
15.2
18.4
23.7
32.6
46.6
12.6
15.2
21.6
28.0
39.1
Max Fuse /
BRKR1 Size
Amps
45
45
45
45
50
70
90
45
45
45
45
60
80
100
20
20
20
25
35
50
15
20
25
30
40
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code, the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
29
036-21504-006-A-1105
TABLE 21: ELECTRICAL DATA - DF036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
16.7
87
2.3
4.4
10.0
230-1-60
16.7
87
2.3
4.4
10.0
208-3-60
13.1
110
2.3
4.4
10.0
230-3-60
13.1
110
2.3
4.4
10.0
460-3-60
6.7
54
1.3
2.2
5.0
575-3-60
5.1
44
1.3
2.2
4.0
208-1-60
25.0
135
2.3
5.0
10.0
230-1-60
25.0
135
2.3
5.0
10.0
208-3-60
14.7
130
2.3
5.0
10.0
230-3-60
14.7
130
2.3
5.0
10.0
460-3-60
7.7
64
1.3
2.2
5.0
575-3-60
6.4
52
1.3
2.2
4.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Max Fuse /
1
BRKR Size
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2
2CE04510525
2CE04510725 2
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2CE04512046 2
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2
2CE04512046
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
37.5
42.0
51.7
66.1
89.5
113.6
37.5
45.6
57.1
73.2
100.8
128.4
33.4
34.3
37.4
45.8
59.3
73.2
33.4
34.3
40.6
49.9
65.8
81.7
17.1
19.2
24.2
29.4
38.3
12.9
19.9
26.3
32.7
48.5
48.5
52.4
66.8
90.3
114.3
48.5
48.5
57.8
74.0
101.6
129.2
35.7
35.7
38.2
46.5
60.0
73.9
35.7
35.7
41.3
50.6
66.6
82.5
18.1
19.2
24.2
29.4
38.3
14.8
19.9
26.3
32.7
50
50
60
70
90
125
50
50
60
80
110
150
45
45
45
50
60
80
45
45
45
50
70
90
20
20
25
30
40
15
20
30
35
70
70
70
70
100
125
70
70
70
80
110
150
50
50
50
50
70
80
50
50
50
60
70
90
25
25
25
30
40
20
20
30
35
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
30
Unitary Products Group
036-21504-006-A-1105
TABLE 22: ELECTRICAL DATA - DF060 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
32.1
148
2.3
6.6
10.0
230-1-60
32.1
148
2.3
6.6
10.0
208-3-60
19.3
123
2.3
6.6
10.0
230-3-60
19.3
123
2.3
6.6
10.0
460-3-60
9.1
62
1.3
3.3
5.0
575-3-60
7.9
50
1.3
3.3
4.0
5
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
Max Fuse /
1
BRKR Size
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2
2CE04510525
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2
2CE04510746
2
2CE04511046
2
2CE04511546
2CE04512046 2
2
2CE04513046
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
59.0
59.0
59.0
68.8
92.3
116.3
154.2
59.0
59.0
59.8
76.0
103.6
131.2
174.9
43.0
43.0
43.0
48.5
62.0
75.9
97.8
43.0
43.0
43.3
52.6
68.6
84.5
109.8
21.0
21.0
25.6
30.8
39.7
53.7
17.6
21.0
27.4
33.8
44.9
90
90
90
90
100
125
175
90
90
90
90
110
150
175
60
60
60
60
70
80
100
60
60
60
60
70
90
110
30
30
30
35
40
60
20
25
30
35
45
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
31
036-21504-006-A-1105
TABLE 23: ELECTRICAL DATA - DF036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
16.7
87
2.3
7.6
10.0
230-1-60
16.7
87
2.3
7.6
10.0
208-3-60
13.1
110
2.3
5.2
10.0
230-3-60
13.1
110
2.3
5.2
10.0
460-3-60
6.7
54
1.3
2.6
5.0
575-3-60
5.1
44
1.3
2
4.0
208-1-60
25.0
135
2.3
7.6
10.0
230-1-60
25.0
135
2.3
7.6
10.0
208-3-60
14.7
130
2.3
5.2
10.0
230-3-60
14.7
130
2.3
5.2
10.0
460-3-60
7.7
64
1.3
2.6
5.0
575-3-60
6.4
52
1.3
2
4.0
3
4
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE04510525
2CE045105252
2CE045107252
2CE04511525
2CE04512025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
2CE04511058
2CE04511558
2CE04512058
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045105252
2CE045107252
2CE04511025
2CE04511525
2CE04512025
NONE
2CE045107462
2CE045110462
2CE045115462
2CE045120462
NONE
2CE04511058
2CE04511558
2CE04512058
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
4.0
5.6
8.0
11.9
15.9
0.0
5.3
7.5
10.6
15.9
21.2
0.0
6.8
10.1
13.6
19.5
0.0
10.6
15.9
21.2
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
0.0
19.2
26.9
38.5
57.2
76.4
0.0
22.1
31.3
44.2
66.3
88.3
0.0
11.1
15.5
22.2
33.0
44.1
0.0
12.7
18.0
25.5
38.2
51.0
0.0
8.2
12.1
16.4
23.5
0.0
10.2
15.3
20.4
41.0
46.0
55.7
70.1
93.5
117.6
41.0
49.6
61.1
77.2
104.8
132.4
34.4
35.1
38.4
46.8
60.3
74.2
34.4
35.1
41.6
50.9
66.8
82.7
17.6
19.7
24.7
29.9
38.8
14.0
19.7
26.1
32.5
51.2
51.2
55.7
70.1
93.5
117.6
51.2
51.2
61.1
77.2
104.8
132.4
35.9
35.9
38.4
46.8
60.3
74.2
35.9
35.9
41.6
50.9
66.8
82.7
18.5
19.7
24.7
29.9
38.8
14.6
19.7
26.1
32.5
Max Fuse /
BRKR1 Size
Amps
60
60
60
80
100
125
60
60
70
80
110
150
45
45
45
50
70
80
45
45
45
60
70
90
20
20
25
30
40
15
20
30
35
70
70
70
80
100
125
70
70
70
80
110
150
50
50
50
50
70
80
50
50
50
60
70
90
25
25
25
30
40
20
20
30
35
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
32
Unitary Products Group
036-21504-006-A-1105
TABLE 24: ELECTRICAL DATA - DF060 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motor
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-1-60
32.1
148
2.3
7.6
10.0
230-1-60
32.1
148
2.3
7.6
10.0
208-3-60
19.3
123
2.3
5.2
10.0
230-3-60
19.3
123
2.3
5.2
10.0
460-3-60
9.1
62
1.3
2.6
5.0
575-3-60
7.9
50
1.3
2
4.0
5
Electric Heater
Model No.
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510506
2CE04510706
2CE04511006
2CE04511506
2CE04512006
2CE04513006
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2CE04510725 2
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2
2CE04510746
2CE04511046 2
2
2CE04511546
2
2CE04512046
2CE04513046 2
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
19.2
26.9
38.5
57.2
76.4
106.7
0.0
22.1
31.3
44.2
66.3
88.3
123.3
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
60.0
60.0
60.0
70.1
93.5
117.6
155.4
60.0
60.0
61.1
77.2
104.8
132.4
176.2
41.6
41.6
41.6
46.8
60.3
74.2
96.0
41.6
41.6
41.6
50.9
66.8
82.7
108.0
20.3
20.3
24.7
29.9
38.8
52.8
16.5
19.7
26.1
32.5
43.6
Max Fuse /
BRKR1 Size
Amps
90
90
90
90
100
125
175
90
90
90
90
110
150
200
60
60
60
60
70
80
100
60
60
60
60
70
90
110
25
25
25
30
40
60
20
20
30
35
45
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories
2FB04700825 and 2FB04700846 are available for field installation.
Unitary Products Group
33
036-21504-006-A-1105
TABLE 25: ELECTRICAL DATA - DF072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
Compressors
Voltage
RLA
Each
LRA
Each
OD Fan
Motors
FLA
ID Blower
Motor
FLA
Conv
Outlet
Amps
208-3-60
18.6
156
2.3
5.2
10.0
230-3-60
18.6
156
2.3
5.2
10.0
460-3-60
9.0
75
1.3
2.6
5.0
573-3-60
7.4
54
1.3
2.0
4.0
6
Electric Heater
Model No.
3
NONE
2
2CE04510525
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510525 2
2
2CE04510725
2CE04511025
2CE04511525
2CE04512025
2CE04513025
NONE
2CE04510746 2
2
2CE04511046
2CE04511546 2
2
2CE04512046
2
2CE04513046
NONE
2CE04511058
2CE04511558
2CE04512058
2CE04513058
Heater
kW
Heater
Amps
Minimum
Circuit
Ampacity
Amps
0.0
4.0
5.6
8.0
11.9
15.9
22.2
0.0
5.3
7.5
10.6
15.9
21.2
29.6
0.0
6.8
10.1
13.6
19.5
28.8
0.0
10.6
15.9
21.2
30.4
0.0
11.1
15.5
22.2
33.0
44.1
61.6
0.0
12.7
18.0
25.5
38.2
51.0
71.2
0.0
8.2
12.1
16.4
23.5
34.6
0.0
10.2
15.3
20.4
29.3
40.8
40.8
40.8
46.6
60.4
74.2
96.1
40.8
40.8
41.6
50.9
66.8
82.7
108.0
20.2
20.2
24.7
29.9
38.8
52.8
16.6
20.2
26.6
33.0
44.1
Max Fuse /
BRKR1 Size
Amps
50
50
50
50
70
80
100
50
50
50
60
70
90
110
25
25
25
30
40
60
20
25
30
35
45
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block
accessories 2FB04700825 and 2FB04700846 are available for field installation.
34
Unitary Products Group
036-21504-006-A-1105
TABLE 26: PHYSICAL DATA
DF
MODELS
Centrifugal Blower (Dia. x Wd. in.)
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
048
060
072
12 X 10
12 X 10
12 X 10
12 X 10
Fan Motor HP (Direct Drive)
1/2
3/4
1
N/A
Fan Motor HP (Belt Drive)
1 1/2
1 1/2
1 1/2
1 1/2
Rows Deep
3
3
3
4
Fins Per Inch
13
13
13
13
Face Area (Sq. Ft.)
3.6
4.3
5.1
5.1
Propeller Dia. (in.)
22
22
22
24
Fan Motor Hp
1/2
1/2
1/2
1/2
4200
Nom. CFM
4500
4200
4500
Rows Deep
2
2
2
2
Fins Per Inch
18
18
18
18
Face Area (Sq. Ft.)
17.1
17.1
17.1
17.1
Recip Type
1
1
1
1
Quantity Per Unit (15” X 20” X 1” or 2“)
2
2
2
2
Quantity Per Unit (14” X 25” X 1” or 2“)
1
1
1
1
Total Face Area (sq. ft.)
6.6
6.6
6.6
6.3
Refrigerant 22
(lbs./oz.)
9/12
9/8
9/8
11/0
CONDENSER
COILS
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS
036
CHARGE
TABLE 27: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE
VOLTAGE
kW CAP. MULTIPLIER
208
208
1.00
240
230
0.92
480
460
0.92
600
575
0.92
TABLE 28: VOLTAGE LIMITATIONS1
VOLTAGE
POWER SUPPLY
MIN.
MAX.
208/230-1-60
187
252
208/230-3-60
187
252
460-3-60
432
504
575-3-60
540
630
1. Utilization Range “A” in accordance with ARI Standard
110.
Unitary Products Group
35
036-21504-006-A-1105
TYPICAL POWER WIRING
REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTECTION AND WIRING.
TYPICAL CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
COOLING ONLY (24 VOLT THERMOSTAT)
THERMOSTAT 1
TERMINALS
THERMOSTAT1 UNIT TERMINAL
TERMINALS
STRIP TB1
ADD
JUMPER
R
RV
UNIT TERMINAL
STRIP TB1
RC
R
Y
Y1
24 VOLT
TRANSFORMER
Y1
YC
RH
24 VOLT
TRANSFORMER
Y2
Y2
W
W1
G
GF
W2
C
G
G
C
1
24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224.
COOLING / HEATING (ELECTRONIC THERMOSTAT)
MULTI STAGE
THERMOSTAT1
TERMINALS
ADD
JUMPER
RC
UNIT TERMINAL
STRIP TB1
RH
R
Y1
W1
ADD
JUMPER
24 VOLT
TRANSFORMER
G
C
LED 1
X
NOT
USED
RH
W2
B
OCC
ADD
JUMPER
4
A1
A2
T
T
ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE).
2
SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3
SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE
ELECTRIC HEATER OR 2 STAGE GAS HEAT.
REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.
UNIT TERMINAL
STRIP TB1
RC
R
Y
Y1
W
W1
G
G
C
TO REMOTE SENSOR
2TH040702224 IF USED
1
4
THERMOSTAT1
TERMINALS
Y2
G
COM
COOLING / HEATING (ELECTRONIC THERMOSTAT)
SINGLE STAGE
W1
3
W2
LED 2
24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF
HEAT, USE THERMOSTAT 2TH0471024.
Y1
2
Y2
4
1
24 VOLT
TRANSFORMER
1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE).
TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT
2TH04700224.
FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING
36
Unitary Products Group
036-21504-006-A-1105
FIGURE 3 - UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW
FIGURE 4 - UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW
Unitary Products Group
37
036-21504-006-A-1105
DETAIL “A”
FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD
DETAIL “B”
FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
38
Unitary Products Group
036-21504-006-A-1105
FIGURE 7 - UNIT DIMENSIONS (REAR VIEW)
TABLE 30: MINIMUM CLEARANCES
FILTER
ACCESS
LOCATION
CLEARANCE
Front
24” (Cooling/Electric Heat)
32” (Gas Heat)
Rear
12” (Less Economizer)
36” (With Economizer or Fixed Air/
Motorized Damper)
Left Side (Filter Access)
24” (Less Economizer)
36” (With Economizer)
Right Side (Cond. Coil)
24”
BLOWER MOTOR
ACCESS
DOT PLUGS
FIELD-SUPPLIED
DISCONNECT SWITCH
LOCATION
MOUNTING BRACKET
FOR DICONNECT SWITCH
(Shipped attached to the
blower housing inside
the blower compartment)
A,B
WIRING ENTRY
(See Detail “B”)
CONTROL BOX
ACCESS
DISCONNECT SWITCH LOCATION
AND MOTOR ACCESS PANEL FOR
UNIT WITH “BELT-DRIVE” OPTION
FIGURE 8 - DISCONNECT/BLOWER ACCESS
LOCATION
Below Unit1
0”
Above Unit2
72” (For
Condenser Air Discharge)
1. Units may be installed on combustible floors made
from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet.
TABLE 29: UTILITIES ENTRY
HOLE
OPENING SIZE (DIA.)
USED FOR
A
7/8” KO1
Control Wiring2
B
2” KO1
Power Wiring
C
1-5/8” KO
Gas Piping (Front)
D
1-1/2” KO
Gas Piping (Bottom)
Side
Bottom
Side
Bottom
1. Opening in the bottom to the unit can be located by the
side in the insulation.
2. Do not remove the 2” knockout ring.
Unitary Products Group
39
036-21504-006-A-1105
FIGURE 9 - TYPICAL APPLICATIONS
40
Unitary Products Group
036-21504-006-A-1105
BACK OF UNIT
A
447/8
BACK OF UNIT
A
447/8
821/4
821/4
D
B
F
X
X
B
APPROXIMATE
CENTER OF GRAVITY
CONDENSER COIL
END OF UNIT
C
Y
FRONT OF UNIT
C
E
APPROXIMATE
CENTER OF GRAVITY
CONDENSER COIL
END OF UNIT
D
Y
FRONT OF UNIT
FIGURE 10 - FOUR AND SIX POINT LOADING
TABLE 31: DF 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT
TOTAL
4-Point Loading (lb)
6-Point Loading (lb)
A
B
C
D
A
B
C
D
E
F
DF036 Cooling/ Electric
565
125
123
157
160
84
83
82
104
105
107
DF036N04
605
134
132
168
171
90
89
88
112
113
114
DF036D06
615
137
134
171
174
91
90
89
113
115
116
DF036N08
625
139
136
173
177
93
92
91
115
117
118
DF036D10
635
141
138
176
179
94
93
92
117
119
120
DF048 Cooling/ Electric
615
137
134
171
174
91
90
89
113
115
116
DF048(D,N)06
665
148
145
184
188
99
98
96
123
124
126
DF048(D,N)10
685
152
149
190
194
102
100
99
126
128
129
DF060 Cooling/ Electric
640
142
140
178
181
95
94
93
118
119
121
DF060D06
690
153
150
191
195
102
101
100
127
129
130
DF060N08
700
155
153
194
198
104
103
101
129
131
132
DF060(D,N)10
710
158
155
197
201
105
104
103
131
132
134
DF072 Cooling/ Electric
660
147
144
183
186
98
97
96
122
123
125
DF072D06
710
158
155
197
201
105
104
103
131
132
134
DF072N08
720
160
157
200
203
107
106
104
133
134
136
DF072(D,N)10
730
162
159
202
206
108
107
106
135
136
138
TABLE 32: CENTER OF GRAVITY
DIMENSION
3 - 5 TON
6 TON
X
40-¾”
44”
Y
19-¾”
22”
Unitary Products Group
41
036-21504-006-A-1105
TABLE 33: OPERATING WEIGHTS (LBS.)
MODEL SIZE
3 TON
4 TON
5 TON
6 TON
565
615
640
660
N04
605
-
-
-
N06
-
665
-
-
N08
625
-
700
720
N10
-
685
710
730
D06
615
665
690
760
D10
635
685
710
730
DF (Cooling Only)
BASIC
UNIT
DF
(Gas/Electric)
Economizer
50
Motorized Damper
OPTIONS
Electric Heater
ACCY.
26
5 - 7 kW
18
10 - 15 kW
23
20 - 30 kW
28
Roof Curb
92
Barometric Relief / Fixed Air Damper
10
Belt-Drive Blower
5
FIGURE 11 - ROOF CURB DIMENSIONS
42
Unitary Products Group
036-21504-006-A-1105
GUIDE SPECIFICATIONS
GENERAL
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility.
York's Sunline PlusTM units are convertible single packageunits.
Although the units are primarily designed for curb mounting on a
roof, they can also be slab-mounted at ground level or set on
steel beams above a finished roof. Cooling only, cooling with
gas heat and cooling with electric heat models are available with
a wide variety of factory-mounted options and field-installed
accessories to make them suitable for almost every application.
All units are self-contained and assembled on full perimeter
base rails with holes in the four corners for overhead rigging.
Every unit is completely piped, wired, charged and tested at the
factory to simplify the field installation and to provide years of
dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct
connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of
the unit. For horizontal duct, remove the supply and return air
panels on the rear of the unit.
All compressors include crankcase heaters and all compressors have internal pressure relief. Every refrigerant circuit
includes a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch.The unit control circuit includes a
75 VA transformer, a 24-volt circuit breaker and a relay board
with a compressor lockout circuit, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify
the interface of additional field controls. All units have long
lasting powder paint cabinets with 1000 hour salt spray test
approval under ASTMB117 procedures. All models are CSA
listed. All models include a 1-year limited warranty on the
complete unit. Compressors and electric heater elements
carry a 5-year warranty. Aluminized steel and Stainless steel
tubular heat exchangers carry a 10-year warranty.
DESCRIPTION
Units shall be factory-assembled, single packaged, Electric
Cooling/Gas Heat, Electric Cooling/Optional Electric Heat
and designed for outdoor mounted installation.
The 4 and 5 ton units have SEER ratings of 11.0, the 3 ton unit
is rated at 11.5 SEER and the 6 ton unit is rated at 10.4 EER.
They shall have built-in field convertible duct connections for
down discharge supply/return or horizontal discharge supply/
return, and be available with factory installed options or field
installed accessories. The units shall be factory wired, piped,
charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded.
All units the cooling performance shall be rated in accordance
with DOE and ARI test procedures. Units shall be CSA listed,
classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.
Unitary Products Group
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel,
with exterior surfaces coated with a non-chalking, powdered
paint finish, certified at 1000 hours salt spray test per
ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the
furnace compartment and be fastened with ridged fasteners
to prevent insulation from entering the air stream. Cabinet
panels shall be “large” size, easily removable for servicing
and maintenance. Full perimeter base rails shall be provided
to assure reliable transit of equipment, overhead rigging and
proper sealing on roof curb applications. Disposable 1" filters
shall be furnished and be accessible through a removable
access door, sealed airtight. Units filter track shall be
designed to accommodate either 1” or 2” filters. Fan performance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating air bypass of the coils. Condensate pan shall be internally sloped
and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female
and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi-speed, or a factory
installed belt drive assembly that includes an adjustable pitch
motor pulley. Job site selected (B.H.P.) brake horsepower
shall not exceed the motors nameplate horsepower rating,
plus the service factor. Units shall be designed not to operate
above service factor. Fan wheel shall be double-inlet type
with forward-curved blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant air volume. Bearings shall be sealed
and permanently lubricated for longer life and no maintenance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shall be of the direct-driven propeller type,
discharge air vertically, have aluminum blades riveted to a
corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor
shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and
staged independently.
REFRIGERANT COMPONENTS
Compressor:
a.
Shall be internally protected with internal high-pressure relief and over temperature protection.
b.
Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent
mounting.
43
036-21504-006-A-1105
Coils:
GAS HEATING SECTION (SINGLE OR 2 STAGE)
a.
Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless
internally enhanced copper tubes with all joints
brazed. Special Phenolic coating shall be available
as a factory option.
b.
Evaporator and Condenser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a.
Thermal expansion devices (TXV’s).
• DF072 uses a fixed orifice distributor.
b.
Filter drier/strainer to eliminate any moisture or foreign matter.
c.
Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary
servicing or troubleshooting without losing charge.
d.
The refrigeration system shall provide at least 15°F
of sub-cooling at design conditions.
UNIT CONTROLS
a.
Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit
breaker on the 24-volt transformer side.
b.
Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or
base unit, should any of the following standard
safety devices trip and shut off compressor.
c.
Loss-of-charge/Low-pressure switch.
d.
High-pressure switch.
e.
Freeze-protection thermostat, evaporator coil.
f.
If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped.
g.
Unit shall incorporate “AUTO RESET” compressor
over temperature, over current protection.
h.
Unit shall operate with conventional thermostat
designs and have a low voltage terminal strip for
easy hook-up.
i.
Unit control board shall have on-board diagnostics
and fault code display.
j.
Standard controls shall include anti-short cycle and
low voltage protection, and permit cooling operation
down to 0°F.
k.
l.
44
Control board shall monitor each refrigerant safety
switch independently.
Control board shall retain last 5 fault codes in non
volatile memory, which will not be lost in the event of
a power loss.
Shall be designed with induced draft combustion with post
purge logic, energy saving direct spark ignition, and redundant main gas valve. Venter wheel shall be constructed of
stainless steel for corrosion resistance. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 25°F. Burners shall be of the
inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit
cabinet at a single location through either the side or curb,
without any field modifications. Integrated control boards
shall provide timed control of evaporator fan functioning and
burner ignition. Heating section shall be provided with the following minimum protection:
a.
Primary and auxiliary high-temperature limit switches.
b.
Induced draft motor speed sensor.
c.
Flame roll out switch.
d.
Flame proving controls.
ELECTRIC HEATING SECTION
An electric heating section, with nickel chromium elements,
shall be provided in a range of 5 thru 30 KW, offering two
stages of capacity - 16 KW and above on 208/230 volt heaters
and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limit control(s) and automatic
reset to prevent the heating element system from operating at
an excessive temperature. The heating section assembly
shall slide out of the unit for easy maintenance and service.
Units with Electric Heating shall be wired for a single point
power supply with branch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
a.
Unit shall be capable of starting and running at 125°F
outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compressor, with
standard controls, shall be capable of operation down
to 0°F outdoor temperature. Unit shall be provided
with fan time delay to prevent cold air delivery before
heat exchanger warms up (Gas heat only).
ELECTRICAL REQUIREMENTS
All unit power wiring shall enter unit cabinet at a single factory
provided location and be capable of side or bottom entry, to
minimize roof penetrations and avoid unit field modifications.
Separate side and bottom openings shall be provided for the
control wiring.
STANDARD LIMITED WARRANTIES
•
Compressor 5 Years
•
Heat Exchanger 10 Years
•
Electric Heat Element 5 Years
•
Other Parts 1 Year
Unitary Products Group
036-21504-006-A-1105
OPTIONAL OUTDOOR AIR (Shall be made available by
either/or):
•
ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return
air damper assembly to take in CFM of outdoor air to
meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall
modulate the outdoor and return air damper assembly to
prevent the supply air temperature from dropping below
55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy
control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood
that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully
close on power loss.
•
HIGH ALTITUDE - PROPANE GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude. Must be used with propane conversion kit.
•
LOW NOX - Required to reduce the emission of nitrogen
oxides below 40 nanograms per joule.
•
GAS PIPING - Contains 1/2” pipe nipples, fittings and
gas cock (including panel assess gaskets) required for
bottom gas supply connection with external shut off.
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
ELECTRIC HEATERS
•
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD Contains all hood panels and the hardware for assembling.
•
MANUAL OUTDOOR AIR DAMPER
•
COIL GUARD KIT - Guard for cooling coil.
•
HAIL GUARD
•
FLUE EXHAUST EXTENSION
OTHER FACTORY INSTALLED OPTIONS
•
POWER EXHAUST OPTION - To work in conjunction
with economizers.
•
STAINLESS STEEL HEAT EXCHANGER
•
STAINLESS STEEL DRAIN PAN
•
BOTTOM DRAIN CONNECTION
•
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COIL
•
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
•
DIRTY FILTER SWITCH
•
PHASE MONITOR
•
COIL GUARD
•
POWERED GFI CONVENIENCE OUTLET
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
NON-POWERED GFI CONVENIENCE OUTLET
•
ROOF CURB - 14"and 8” high, full perimeter curb with
wood nailer (shipped knocked-down).
•
BAS CONTROLS (Simplicity™ INTELLI- Comfort™,
CPC, JOHNSON, HONEYWELL, NOVAR)
•
BAROMETRIC RELIEF DAMPER - Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit.
•
BAS READY ECONOMIZER (BELIMO ACTUATOR
WITHOUT A CONTROLLER)
•
HINGED FILTER DOOR ACCESS AND TOOLESS
ACCESS PANELS
•
2" PLEATED FILTERS
•
DISCONNECT SWITCH
•
SUPPLY AIR SMOKE DETECTOR
•
RETURN AIR SMOKE DETECTOR
•
•
•
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air
dampers are positioned by a 2-position, spring-return
damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when
dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper
assembly to take in the design CFM of outdoor air to
meet the ventilation requirements of the conditioned
space during normal operation. Whenever the indoor fan
motor is energized, the dampers open up to one of two
pre-selected positions - regardless of the outdoor air
enthalpy. Dampers return to the fully closed position
when the indoor fan motor is de-energized. Dampers
shall fully close on power loss.
PROPANE CONVERSION KIT - Contains new orifices
and gas valve parts to convert from natural to L.P. gas.
One per unit required.
HIGH ALTITUDE - NATURAL GAS - Contains orifices
required for applications between 2000 and 6000 feet
altitude.
Unitary Products Group
45
036-21504-006-A-1105
46
Unitary Products Group
036-21504-006-A-1105
Unitary Products Group
47
Subject to change without notice. Printed in U.S.A.
Copyright © 2005 by Unitary Products Group. All rights reserved.
Unitary
Products
Group
5005
York
Drive
036-21504-006-A-1105
Supersedes: 036-21504-005-A-1005