036-21504-006-A-1105 ® DESCRIPTION SINGLE PACKAGE GAS/ELECTRIC UNITS YORK® Sunline Plus™ units are convertible single package air conditioners with a common cabinet and a common roof curb for the 3, 4, 5 and 6 ton sizes. The units were designed for light commercial and commercial applications. They can easily be installed on a roof curb, slab, roof jack or frame. AND SINGLE PACKAGE All units include: AIR CONDITIONERS • Powder Paint finish that meets ASTM-B-117 1000 hour salt spray standards DF 036, 048, 060 and 072 • Permanently lubricated motors • Bottom or side air discharge configuration capability (field convertible) • Manufactured under the quality standards of ISO9001 • SimplicityTM Control Board • Copper tube/aluminum fin coils • Easy access to all components • Rigging holes in base rails for lifting • Fork lift slots on three sides • Single point power connection • Complete factory package - tested, charged and wired • CSA agency listing on all units TECHNICAL GUIDE 3, 4, 5 and 6 NOMINAL TONS 11.0 - 11.5 SEER 10.0 - 10.4 EER WARRANTY • Factory Limited Parts Warranty • One-year parts warranty • A Five-year parts warranty on the compressor and electric heat elements. • Ten-year parts warranty on the gas-fired heat exchangers. FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE 036-21504-006-A-1105 TABLE OF CONTENTS DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 PRODUCT NOMENCLATURE . . . . . . . . . . . . . . . . . 3 FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . 12 FIELD-INSTALLED ACCESSORIES . . . . . . . . . . . 13 GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . 43 10 SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . 21 11 SUPPLY AIR BLOWER PERFORMANCE (5,6 TON BELT DRIVE) - SIDE DUCT APPLICATION . . . . . . . 22 12 SUPPLY AIR BLOWER PERFORMANCE (3 - 5 TON DIRECT DRIVE) - SIDE DUCT APPLICATION . . . . 23 13 BELT DRIVE BLOWER MOTOR AND DRIVE DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23 14 STATIC RESISTANCES . . . . . . . . . . . . . . . . . . . . . . 24 15 ELECTRIC HEATER CFM LIMITATIONS . . . . . . . . . 24 LIST OF FIGURES Fig. # Pg. # 16 ELECTRICAL DATA - DF036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET . . . . 25 1 UNIT CUTAWAY . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 2 TYPICAL FIELD POWER & CONTROL WIRING . . . 36 17 ELECTRICAL DATA - DF060 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 26 3 UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ ELECTRIC HEAT) FRONT VIEW . . . . . . . . . . . . . . . 37 18 ELECTRICAL DATA - DF036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET . . . . . . . . . 27 4 UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37 19 ELECTRICAL DATA - DF060 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 28 5 UNIT WITH ECONOMIZER RAINHOOD . . . . . . . . . . 38 20 ELECTRICAL DATA - DF072 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 29 6 UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD . . . . . . . . . . . . . . . . . . . . . . . . 38 7 UNIT DIMENSIONS (REAR VIEW) . . . . . . . . . . . . . . 39 8 DISCONNECT/BLOWER ACCESS LOCATION . . . . 39 9 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . . . . . 40 10 FOUR AND SIX POINT LOADING . . . . . . . . . . . . . . 41 11 ROOF CURB DIMENSIONS . . . . . . . . . . . . . . . . . . . 42 LIST OF TABLES Tbl. # Pg. # 21 ELECTRICAL DATA - DF036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET . . . . . . . . 30 22 ELECTRICAL DATA - DF060 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 31 23 ELECTRICAL DATA - DF036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 32 24 ELECTRICAL DATA - DF060 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 33 25 ELECTRICAL DATA - DF072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET . . . . . . . . . . . . . 34 26 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 1 SOUND POWER RATING . . . . . . . . . . . . . . . . . . . . . 15 2 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . . . . . 15 27 ELECTRIC HEAT CORRECTION FACTORS . . . . . . 35 28 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . 35 3 GAS HEAT RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . 15 4 2 STAGE GAS HEAT RATINGS . . . . . . . . . . . . . . . . . 15 5 DF036 COOLING CAPACITIES (3 TON) . . . . . . . . . . 16 6 DF048 COOLING CAPACITIES (4 TON) . . . . . . . . . . 17 31 DF 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41 7 DF060 COOLING CAPACITIES (5 TON) . . . . . . . . . . 18 32 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . . . 41 8 DF072 COOLING CAPACITIES (6 TON) . . . . . . . . . . 19 33 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . . . . . 42 9 SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION . . . . . . . . . . . . 20 2 29 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . . . . . 39 30 MINIMUM CLEARANCES . . . . . . . . . . . . . . . . . . . . . 39 Unitary Products Group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nitary Products Group 3 036-21504-006-A-1105 PRODUCT NOMENCLATURE - Continued 3-6T Sunline Model Number Nomenclature Standard Cabinet AA AB AC AD AE AF AG AH AJ AK AL AM AN AS CA CB CC CD CE CF CG CH CJ CK CL CM CN CP CQ CR CS CT CU CV CW CX JA JB JC JD JE JF JG JH JJ JK JL JM JN JP 4 None Phase Monitor Coil Guard Dirty Filter Switch Phase Monitor & Coil Guard Phase Monitor & Dirty Filter Switch Coil Guard & Dirty Filter Switch Phase Monitor, Coil Guard, & Dirty Filter Switch SS Drain Pan SS Drain Pan & Phase Monitor SS Drain Pan & Coil Guard SS Drain Pan & Dirty Filter Switch SS Drain Pan, Phase Monitor, Coil Guard & Dirty Filter Switch Bottom Drain Connection CPC Controller with Dirty Filter Switch & Air Proving Switch CPC Controller, DFS, APS & Phase Monitor CPC Controller, DFS, APS & Coil Guard CPC Controller, DFS, APS, Phase Monitor, & Coil Guard CPC Controller, DFS, APS & Technicoat Cond. Coil CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard CPC Controller, DFS, APS & Technicoat Evap. Coil CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard CPC Controller, DFS, APS, SS Drain Pan CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch Johnson UNT Controller, DFS, APS & Phase Monitor Johnson UNT Controller, DFS, APS & Coil Guard Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor Unitary Products Group 036-21504-006-A-1105 Standard Cabinet JQ JR JS JT JU JV JW JX HA HB HC HD HE HF HG HH HJ HK HL HM HN HP HQ HR HS HT HU HV HW HX NA NB NC ND NE NF NG NH NJ NK NL NM NN NP NQ NR NS NT NU NV NW NX TA TB Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard Johnson UNT Controller, DFS, APS, SS Drain Pan Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch Honeywell Excel 10 Controller, DFS, APS & Phase Monitor Honeywell Excel 10 Controller, DFS, APS & Coil Guard Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch Novar ETC-3 Controller, DFS, APS & Phase Monitor Novar ETC-3 Controller, DFS, APS & Coil Guard Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard Novar ETC-3 Controller, DFS, APS, SS Drain Pan Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Technicoat Condenser Coil Technicoat Condenser Coil & Phase Monitor Unitary Products Group 5 036-21504-006-A-1105 Standard Cabinet TC TD TE TF TG TH TJ TK TL TM TN TP TQ TR TS TT TU TV TW TX TY TZ T1 T3 T4 T6 T7 T9 LA LB LC LD LE LF LG LH LJ LK LL LM LN LP LQ LR LS LT LU LV LW LX WA WB WC WD 6 Technicoat Condenser Coil & Coil Guard Technicoat Condenser Coil & Dirty Filter Switch Technicoat Condenser Coil, Phase Monitor, & Coil Guard Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch Technicoat Evaporator Coil Technicoat Evaporator Coil & Phase Monitor Technicoat Evaporator Coil & Coil Guard Technicoat Evaporator Coil & Dirty Filter Switch Technicoat Evaporator Coil, Phase Monitor, & Coil Guard Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch Technicoat Evaporator & Condenser Coils Technicoat Evaporator & Condenser Coils & Phase Monitor Technicoat Evaporator & Condenser Coils & Coil Guard Technicoat Evaporator & Condenser Coils & Dirty Filter Switch Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch Technicoat Condenser & SS Drain Pan Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch Technicoat Evaporator & SS Drain Pan Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch Technicoat Evaporator & Condenser Coils & SS Drain Pan Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch Simplicity Intelli-Comfort Controller Simplicity Intelli-Comfort Controller, & Phase Monitor Simplicity Intelli-Comfort Controller, & Coil Guard Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard Simplicity Intelli-Comfort Controller, SS Drain Pan Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Intelli-Comfort w/Mod Link Controller Intelli-Comfort w/Mod Link Controller, & Phase Monitor Intelli-Comfort w/Mod Link Controller, & Coil Guard Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard Unitary Products Group 036-21504-006-A-1105 Standard Cabinet WE WF WG WH WJ WK WL WM WN WP WQ WR WS WT WU WV WW WX Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard Intelli-Comfort w/Mod Link Controller, SS Drain Pan Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Cabinet BA BB BC BD BE BF BG BH BJ BK BL BM BN BS DA DB DC DD DE DF DG DH DJ DK DL DM DN DP DQ DR DS DT DU DV Hinged Filter Door & Toolless Access Panels Phase Monitor, Hinged Filter Door & Toolless Access Panels Coil Guard, Hinged Filter Door & Toolless Access Panels Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels Phase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels Phase Monitor & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels SS Drain Pan & Hinged Filter Door & Toolless Access Panels SS Drain Pan & Phase Monitor, Hinged Filter Door & Toolless Access Panels SS Drain Pan & Coil Guard, Hinged Filter Door & Toolless Access Panels SS Drain Pan & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels SS Drain Pan & Phase Monitor & Coil Guard, Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels Bottom Drain Connection, Hinged Filter Door & Toolless Access Panels CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels Unitary Products Group 7 036-21504-006-A-1105 Hinged Filter Door & Toolless Access Cabinet DW CPC Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels DX CPC Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels EF Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels EN Johnson UNT Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels ER Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels ES Johnson UNT Controller, DFS, APS, SS Drain Pan Hinged Filter Door & Toolless Access Panels ET Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels EU Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels EV Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels EW Johnson UNT Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels EX Johnson UNT Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels GF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels GN Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels GR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels GS Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan GT Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard GU Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils GV Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil GW Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils GX Honeywell Excel 10 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels 8 Unitary Products Group 036-21504-006-A-1105 Hinged Filter Door & Toolless Access Cabinet PB PC PD PE PF PG PH PJ PK PL PM PN PP PQ PR Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels PS Novar ETC-3 Controller, DFS, APS, SS Drain Pan PT Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, & Coil Guard PU Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Cond Coils PV Novar ETC-3 Controller, DFS, APS, SS Drain Pan, & Technicoat Evap Coil PW Novar ETC-3, DFS, APS, SS Drain Pan, & Technicoat Evap and Cond Coils PX Novar ETC-3 Controller, DFS, APS, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels UB Technicoat Condenser Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UE Technicoat Condenser Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels UF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UH Technicoat Condenser Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Access Panels UK Technicoat Evaporator Coil & Phase Monitor, Hinged Filter Door & Toolless Access Panels UL Technicoat Evaporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UN Technicoat Evaporator Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels UP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UR Technicoat Evaporator Coil, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels US Technicoat Evaporator & Condenser Coils, Hinged Filter Door & Toolless Access Panels UT Technicoat Evaporator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Access Panels UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels UV Technicoat Evaporator & Condenser Coils & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UY Technicoat Evaporator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels U1 Technicoat Condenser & SS Drain Pan, Hinged Filter Door & Toolless Access Panels U3 Technicoat Condenser Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels U4 Technicoat Evaporator & SS Drain Pan, Hinged Filter Door & Toolless Access Panels U6 Technicoat Evaporator Coil, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels U7 Technicoat Evaporator & Condenser Coils & SS Drain Pan, Hinged Filter Door & Toolless Access Panels U9 Technicoat Evaporator & Condenser Coils, SS Drain Pan, Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels QA Simplicity Intelli-Comfort Controller with Hinged Filter Door & Toolless Access Panels QB Simplicity Intelli-Comfort Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels Unitary Products Group 9 036-21504-006-A-1105 Hinged Filter Door & Toolless Access Cabinet QC QD QE QF QG QH QJ QK QL QM QN QP QQ QR QS QT QU QV QW QX Simplicity Intelli-Comfort Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Simplicity Intelli-Comfort Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Simplicity Intelli-Comfort Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Simplicity Intelli-Comfort Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels Simplicity Intelli-Comfort Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels XA Intelli-Comfort w/Mod Link Controller, Hinged Filter Door & Toolless Access Panels XB Intelli-Comfort w/Mod Link Controller, & Phase Monitor, Hinged Filter Door & Toolless Access Panels XC Intelli-Comfort w/Mod Link Controller, & Coil Guard, Hinged Filter Door & Toolless Access Panels XD Intelli-Comfort w/Mod Link Controller, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels XE Intelli-Comfort w/Mod Link Controller, & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels XF Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels XG Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels XH Intelli-Comfort w/Mod Link Controller, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access XJ Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels XK Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels XL Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels XM Intelli-Comfort w/Mod Link Controller, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access XN Intelli-Comfort w/Mod Link Controller, & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels XP Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Pan XQ Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels XR Intelli-Comfort w/Mod Link Controller, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Tooless XS Intelli-Comfort w/Mod Link Controller, SS Drain Pan Hinged Filter Door & Toolless Access Panels XT Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, & Coil Guard Hinged Filter Door & Toolless Access Panels XU Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Cond Coils Hinged Filter Door & Toolless Access Panels XV Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap Coil Hinged Filter Door & Toolless Access Panels XW Intelli-Comfort w/Mod Link Controller, SS Drain Pan, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels XX Intelli-Comfort w/Mod Link Controller, SS Drain Pan, Phase Monitor, Coil Guard, & Technicoat Evap and Cond Coils Hinged Filter Door & Toolless Access Panels 10 Unitary Products Group 036-21504-006-A-1105 FEATURES gas valve, if applicable, and the temperature limit switch on gas heat units. The unit control board will alarm on ignition failures, compressor lockouts and repeated limit switch trips. All models are available with a wide variety of factorymounted options such as stainless steel heat exchangers, electric heaters, phase monitor, convenience outlet, dirty filter switch, disconnect switch, smoke detectors, and coil guard to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit. All models are available with these “factory mounted” outdoor air damper options: • Nuisance Trip Protection- To prevent nuisance trouble calls, the control board uses a “three strikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the unit control board will lock out the compressor. • On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power. All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTM-B117 procedures. • Single enthalpy economizer All models are CSA listed. • Motorized outdoor air damper • Warranty - All models include a one-year limited parts warranty on the complete unit. Compressors and electric heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts warranty. • Gas Heat Operation - All single phase models with gas heat have minimum annual fuel utilization efficiency (AFUE) of 80%. All three phase models with gas heat have minimum steady state efficiency of 80%. Each section includes a durable heat exchanger with aluminized steel or optional stainless steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet the latest ANSI standards. Supply air blowers are equipped with either a direct drive or a belt drive that can be adjusted to meet the exact requirements of the job. All compressors are equipped with internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch to protect all system components. • Simplicity™ Controls - Simplicity™ control boards have standardized a number of features previously available only as options or by utilizing additional controls. • • • • Low Ambient - An integrated low-ambient control allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assistance. Optionally, the control board can be programmed to lockout the compressors when the outdoor air temperature is low or when free cooling is available. The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the piping panel on the front of the unit. • Anti-Short Cycle Protection - To aid compressor life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti short cycle delay can be temporarily overridden with the push of a button. Fan Delays - Fan on and fan off delays are fully programmable and are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat. Safety Monitoring - The control board monitors the high and low-pressure switches, the freezestats, the Unitary Products Group Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium elements mounted at the discharge of the supply air blower to provide a high velocity and uniform distribution of air across the heating elements. Every element is fully protected against excessive temperature by thermal limit switches. The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the side of the unit. • BAS Controls - York’s Sunline™ series units offer factory mounted BAS controls such as SImplicity™ INTELLIComfort™, Novar, Honeywell, Johnson, and CPC. 11 036-21504-006-A-1105 FIGURE 1 - UNIT CUTAWAY FACTORY-INSTALLED OPTIONS • SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. The rainhood is painted to match the basic unit and must be field-assembled before installing. • MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to a pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. • 12 PHENOLIC COATED EVAPORATOR AND CONDENSER COILS - Special coating process that utilizes Technicoat 10-1TM processes. Coating is applied by total immersion of the complete coil for maximum protection. • ELECTRIC HEATERS - Wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures. • FILTER OPTIONS - Standard units are shipped with 1” throw-away filters installed. 2” pleated filters are offered as a factory installed option. • CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit with a stepdown transformer or the unit may be ordered with a “non-powered” convenience outlet that can be wired in the field. • DISCONNECT SWITCH - For gas heat units and cooling units with electric heat, a HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only. • BAS - Building Automation System Controls Simplicity™ INTELLI-Comfort™ CONTROL - The York® Simplicity™ INTELLI-Comfort™ control is factory installed. It includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Outside Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Construction mode operation, 365-day real time clock with 7 day programming plus holiday Unitary Products Group 036-21504-006-A-1105 scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™ using CO2 sensors. It uses an inside CO2 sensor to perform Demand Ventilation. It can also use an Outside CO2 sensor to perform Differential Demand Ventilation. It uses a Patented Comfort Ventilation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on-board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity™ INTELLI-Comfort™ balances space temperature, ventilation air temperature, CO2 and humidity for ultimate comfort. • Simplicity™ INTELLI-Comfort™ with MOD LINK CONTROL - The York® Simplicity™ INTELLI-Comfort™ with Mod Link control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol. • Novar® BAS CONTROL - The Novar® ETC-3 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch. • JOHNSON CONTROLS BAS CONTROL - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch. • • • STAINLESS STEEL HEAT EXCHANGER - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly. • STAINLESS STEEL DRAIN PAN - An optional rustproof stainless steel drain pan is available to provide years of trouble-free operation in corrosive environments. • BOTTOM DRAIN CONNECTION - An optional bottom drain connection is available for inside the curb connections for applications in cold environments to reduce freezing drain lines. • PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-ofphase condition. • DIRTY FILTER SWITCH - This kit includes a differential pressure switch that energizes the fault light on the unit thermostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory. • HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS PANELS (not hinged) - This option allows for easy access and maintenance. NOTE:Knobs are shipped inside the unit to prevent shipping damage. These must be field installed for tool-less operation. FIELD-INSTALLED ACCESSORIES • CPC BAS CONTROL - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch. HONEYWELL BAS CONTROL - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch. • SMOKE DETECTORS - (supply air & return air) The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment. • COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. Unitary Products Group SINGLE INPUT ELECTRONIC ENTHALPY ECONOMIZERS - Includes a slide-in / plug-in damper assembly with fully modulating spring-return motor actuator capable of introducing up to 100% outdoor air with nominal 1% leakage type dampers. The enthalpy system contains one sensor that monitors the outdoor air and determines when the air is cool enough and dry enough to provide free cooling. The rainhood is painted to match the basic unit and must be field-assembled before installing. • MOTORIZED OUTDOOR AIR INTAKE DAMPER Includes a slide-in / plug-in damper assembly with a 2position, spring return motor actuator which opens to some pre-set position whenever the supply air blower is operating and will drive fully closed when the blower unit shuts down. The rain hood is painted to match the basic unit and must be field assembled before installing. • ELECTRIC HEATERS wired for single point power supply. These nickel chromium heater elements are provided with limit and automatic reset capability to prevent operation at excessive temperatures. 13 036-21504-006-A-1105 • • • • ROOF CURBS - Eight and fourteen-inch high roof curbs provide a water-tight seal between the unit and the finished roof. These full perimeter curbs meet the requirements of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assembly. • Roof curbs are designed to fit inside the base rails of the unit and include both a wood nailing strip and duct hanger supports. BAROMETRIC RELIEF DAMPER - This damper accessory can be used to relieve internal building air pressure on units with an economizer without power exhaust. This accessory includes a rain hood, a bird screen and a fully assembled damper. With bottom duct connections, the damper should be mounted over the opening in the return air panel. With horizontal ductwork, the accessory should be mounted on the return air duct. • HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy. • BURGLAR BARS - Mount in the supply and return openings to prevent entry into the duct work. • FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes. • CO2 SENSOR - Senses CO2 levels and automatically overrides the economizer when levels rise above the present limits. • COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit. • HAIL GUARD - Hail guard kit is available to prevent unit from hail damage. This is a sloped hood that fits above the coil. • GAS PIPING KIT - This kit supplies all necessary fittings and shut off valve. PROPANE - Burner orifices, pilot orifices and gas valve parts are provided to convert a natural gas furnace to propane. HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provided for proper furnace operation at altitudes up to 6,000 feet. This accessory supplements the basic propane conversion kit. • LOW NOX KIT- Required to reduce the emission of nitrogen oxides below 40 nanograms per joule. • POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be energized to prevent the conditioned space from being over-pressurized during economizer operation. The power exhaust option can only be used on bottom duct configurations. 14 Unitary Products Group 036-21504-006-A-1105 TABLE 1: SOUND POWER RATING1 UNIT SIZE ESP SOUND POWER (db 10-12 Watts) BLOWER Octave Band Centerline Frequency (Hz) CFM IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000 SWL dB(A) dB(A) @ 10Ft.2 036 1,200 0.6 LOW 0.60 84 84 74 67 69 62 57 52 74 41 048 1,600 0.55 HIGH 0.80 85 85 75 68 70 63 58 53 75 42 060 2,000 0.45 HIGH 1.00 86 86 76 69 71 64 59 54 76 43 072 2,200 0.3 HIGH 1.35 87 87 77 70 72 65 60 55 77 44 1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guarantee requiring a dBA value or sound data in any other form than sound power level ratings. 2. At a distance of 10 feet from the blower. TABLE 2: CAPACITY RATINGS - (ARI 210/240)1 TABLE 3: GAS HEAT RATINGS1 MODEL MBH EER2 SEER3 DF036 42.5 10.1 11.5 DF048 49.5 10.0 11.0 DF060 58.5 10.05 11.0 DF072 70.5 10.4 - 1. 80/67°F Indoor and 95°F outdoor. 2. EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt). 3. SEER = Seasonal Energy Efficiency Ratio. MODEL MBH INPUT MBH OUTPUT AFUE (%) TEMP RISE ºF DF036N04 DF036N08 50 100 40 80 80.9 80.5 15 - 45 40 - 70 DF048N06 DF048N10 75 125 60 100 80.9 80.3 25 - 55 45 - 75 DF060N08 DF060N10 100 125 80 100 80.5 80.3 25 - 55 35 - 65 DF072N08 DF072N10 100 125 80 100 80.5 80.3 25 - 55 35 - 65 1. All units are single-stage heating. TABLE 4: 2 STAGE GAS HEAT RATINGS MODEL1 MBH INPUT MBH OUTPUT 1ST STAGE 2ND STAGE 1ST STAGE 2ND STAGE STEADY STATE EFFICIENCY 1ST STAGE 2ND STAGE RISE MIN. MAX. MINIMUM HEATING AIRFLOW (CFM) DF036D06 45 75 35.8 60.8 79.4 81.1 35 70 790 DF036D10 69 115 55.2 92 80.0 80.2 55 90 950 DF048D06 45 75 35.7 60.8 79.4 81.1 25 70 790 DF048D10 75 125 60.4 100.6 80.5 80.5 45 75 1230 DF060D06 45 75 35.8 60.8 79.4 81.1 35 70 1010 DF060D10 75 125 60.4 100.6 80.5 80.5 45 75 1230 DF072D06 45 75 35.8 60.8 79.4 81.1 35 70 1230 DF072D10 75 125 60.4 100.6 80.5 80.5 45 75 1230 1. Models are 3Ø only. Unitary Products Group 15 036-21504-006-A-1105 TABLE 5: DF036 COOLING CAPACITIES (3 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL 85°F TOTAL 1 CFM 1500 1350 1200 1050 900 POWER CAP. MBH INPUT2 kW WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 55 52 42 42 51 49 39 40 48 46 36 37 46 44 35 36 45 42 34 35 3.4 3.3 3.2 3.2 3.3 3.3 3.2 3.2 3.2 3.3 3.2 3.2 3.3 3.3 3.2 3.2 3.3 3.2 3.2 3.1 95°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F TOTAL 1 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER 83 80 77 74 71 68 CAP. MBH INPUT2 kW 86 35 47 42 42 32 42 39 40 28 37 36 37 26 34 35 36 24 31 34 35 31 42 42 42 28 38 39 40 24 34 36 37 23 31 34 35 21 29 32 33 26 38 42 42 24 34 37 38 21 30 33 35 19 28 31 32 18 26 26 30 22 33 37 38 20 30 33 34 17 27 29 31 16 25 28 29 15 23 26 27 18 29 33 33 16 26 29 30 14 23 26 27 13 22 24 26 13 20 23 25 24 28 29 22 25 26 19 22 24 18 21 23 17 20 22 20 24 24 18 21 22 16 19 20 15 18 20 15 18 19 51 48 39 39 49 47 37 38 48 46 36 37 45 43 34 35 43 40 32 33 3.7 3.6 3.5 3.5 3.6 3.5 3.5 3.5 3.6 3.5 3.5 3.4 3.6 3.5 3.4 3.4 3.5 3.5 3.4 3.4 86 83 80 77 74 71 68 35 45 39 39 32 42 37 38 29 39 36 37 26 35 34 35 23 30 32 33 30 41 39 39 28 38 37 38 25 36 36 37 23 32 33 34 20 28 30 32 26 36 39 39 24 34 37 38 22 32 35 37 20 28 31 33 17 25 28 29 21 32 34 35 20 30 33 34 18 38 31 33 16 25 28 30 15 22 25 26 17 28 30 30 16 26 29 30 15 25 28 30 13 22 25 27 12 19 22 24 23 25 26 22 25 26 21 24 26 19 22 23 16 19 21 19 21 21 18 21 22 18 21 22 16 19 20 14 17 18 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL TOTAL INPUT2 kW CFM WB °F CAP.1 MBH 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 47 44 36 36 44 42 34 34 42 40 32 32 40 38 30 31 38 36 29 30 3.9 3.8 3.7 3.7 3.9 3.8 3.7 3.7 3.8 3.8 3.7 3.7 3.8 3.7 3.7 3.6 3.8 3.7 3.6 3.6 1500 1350 1200 1050 900 105°F 115°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER TOTAL 86 83 80 77 74 71 68 CAP.1 MBH 33 43 36 36 30 39 34 34 27 36 32 32 24 32 30 31 22 29 29 30 29 39 36 36 26 36 34 34 23 32 32 32 21 29 30 31 19 26 28 29 25 35 36 36 22 32 33 34 20 29 31 33 18 26 28 30 16 23 26 27 20 30 31 31 18 28 29 30 16 25 28 29 15 23 25 27 13 20 23 24 16 26 27 27 14 24 25 26 12 22 24 26 12 19 22 24 11 17 20 21 22 22 23 20 21 22 18 20 22 16 19 20 15 17 19 17 18 18 16 17 18 14 17 19 13 16 17 12 15 16 43 40 33 33 39 37 30 30 36 34 27 28 35 33 27 27 34 32 26 26 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER INPUT2 kW 4.1 4.1 4.0 3.9 4.1 4.0 4.0 3.9 4.1 4.0 3.9 3.9 4.1 4.0 3.9 3.9 4.0 4.0 3.9 3.9 86 83 80 77 74 71 68 32 40 33 33 28 36 30 30 24 33 27 28 22 30 27 27 20 27 26 26 28 38 33 33 24 33 30 30 21 29 27 28 19 26 27 27 18 24 26 26 23 33 33 33 20 29 30 31 17 25 28 29 16 23 26 27 15 21 24 25 19 29 28 28 16 25 26 27 14 22 24 26 13 20 22 24 12 18 21 22 14 24 24 24 12 21 22 23 10 18 20 22 10 17 19 21 9 16 18 19 20 19 20 17 18 19 15 17 18 14 16 17 13 15 17 16 15 15 13 14 15 11 13 15 11 13 14 10 13 14 1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit. 2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING 16 Unitary Products Group 036-21504-006-A-1105 TABLE 6: DF048 COOLING CAPACITIES (4 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL 85°F TOTAL 1 CFM 2000 1800 1600 1400 1200 POWER CAP. MBH INPUT2 kW WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 64 57 54 54 62 55 52 52 59 54 50 50 58 52 49 49 57 50 48 48 3.9 3.8 3.8 3.8 3.9 3.8 3.8 3.8 3.9 3.8 3.7 3.7 3.8 3.8 3.7 3.7 3.8 3.8 3.7 3.7 95°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F TOTAL 1 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER 83 80 77 74 71 68 CAP. MBH INPUT2 kW 86 45 55 54 54 42 51 52 52 38 48 50 50 35 44 48 49 32 40 47 48 39 49 54 54 36 46 52 52 33 43 50 50 31 39 47 48 29 36 44 45 33 43 53 54 31 40 49 51 29 38 46 47 27 35 43 44 25 32 40 41 27 37 47 48 25 35 44 45 24 33 41 42 23 31 39 40 21 29 36 37 21 31 41 42 20 30 39 40 19 29 36 38 18 27 34 36 17 25 33 34 25 35 36 24 33 35 24 32 33 22 30 31 21 29 30 19 29 30 19 28 29 19 27 28 18 26 27 17 25 26 60 53 50 50 58 52 49 49 57 52 47 47 55 49 46 46 53 47 45 45 4.2 4.1 4.0 4.0 4.2 4.1 4.1 4.1 4.2 4.2 4.1 4.1 4.2 4.2 4.1 4.1 4.2 4.2 4.1 4.1 86 83 80 77 74 71 68 44 53 50 50 41 50 49 49 38 47 47 47 34 42 46 46 31 38 45 45 38 47 50 50 35 44 49 49 33 42 47 47 30 38 45 46 28 35 42 43 32 41 50 50 30 39 47 49 28 37 45 46 26 34 42 43 24 31 38 39 26 35 44 46 24 34 42 44 23 32 40 41 22 30 37 38 20 27 34 35 20 29 38 40 19 28 37 38 18 28 35 37 17 26 33 34 16 23 31 32 23 32 34 23 31 33 23 31 32 21 29 30 20 27 28 17 26 28 18 26 27 18 26 27 17 25 26 16 23 24 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL TOTAL INPUT2 kW CFM WB °F CAP.1 MBH 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 56 50 47 47 54 49 46 46 53 48 44 44 51 46 43 43 50 44 42 42 4.7 4.6 4.5 4.5 4.7 4.6 4.5 4.5 4.7 4.6 4.6 4.5 4.7 4.6 4.5 4.5 4.7 4.6 4.5 4.5 2000 1800 1600 1400 1200 105°F 115°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER TOTAL 86 83 80 77 74 71 68 CAP.1 MBH 42 50 47 47 39 47 46 46 36 45 44 44 33 41 43 43 30 37 42 42 36 45 47 47 34 43 46 46 31 40 44 44 29 37 42 43 27 33 41 41 30 39 47 47 29 37 45 46 27 35 43 44 25 33 40 41 23 30 37 38 25 33 41 44 23 32 40 42 22 31 38 39 21 28 36 37 19 26 33 34 19 28 35 38 17 27 34 36 17 26 33 34 16 24 31 32 16 22 29 30 22 29 32 21 29 31 21 29 30 20 27 28 19 26 27 16 23 26 16 23 26 16 24 25 16 23 24 15 22 23 53 47 44 44 51 46 43 43 49 44 41 41 48 43 40 40 47 42 39 39 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER INPUT2 kW 5.2 5.1 5.0 5.0 5.1 5.1 5.0 5.0 5.1 5.1 5.0 5.0 5.1 5.0 5.0 5.0 5.1 5.0 5.0 5.0 86 83 80 77 74 71 68 41 47 44 44 38 45 43 43 35 43 41 41 32 40 40 40 30 36 39 39 35 44 44 44 33 41 43 43 30 39 41 41 28 35 40 40 26 32 39 39 29 38 44 44 27 36 43 43 25 34 41 41 24 31 38 39 22 29 35 36 23 32 38 42 22 31 37 40 21 29 36 37 20 27 34 35 18 25 32 33 17 26 32 36 17 25 32 34 16 24 31 32 15 23 30 31 15 21 28 29 20 26 30 20 26 29 19 26 28 19 25 26 18 24 25 14 20 24 14 21 24 15 22 23 14 21 22 14 21 22 1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit. 2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING Unitary Products Group 17 036-21504-006-A-1105 TABLE 7: DF060 COOLING CAPACITIES (5 TON) TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL 85°F TOTAL 1 CFM 2500 2250 2000 1750 1500 POWER CAP. MBH INPUT2 kW WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 75 67 62 56 74 67 61 55 73 66 60 55 72 65 60 54 71 63 59 53 4.6 4.5 4.5 4.4 4.6 4.5 4.5 4.4 4.5 4.5 4.4 4.4 4.5 4.5 4.4 4.4 4.5 4.5 4.4 4.4 95°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F TOTAL 1 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER 83 80 77 74 71 68 CAP. MBH INPUT2 kW 86 53 64 62 56 51 62 61 55 49 60 60 55 45 55 60 54 41 50 59 53 46 56 62 56 44 55 61 55 43 54 60 55 40 50 59 53 37 46 57 52 38 49 62 56 37 48 61 55 37 48 60 54 34 44 56 50 32 41 52 47 31 41 54 48 31 42 54 48 31 42 54 48 29 39 50 45 27 36 47 42 23 34 47 41 24 35 47 41 25 36 48 42 24 34 45 40 23 32 43 38 26 39 33 28 40 35 30 42 36 29 40 34 27 38 33 19 32 26 21 34 28 24 36 30 23 35 29 22 34 28 73 65 60 55 72 64 59 53 70 63 58 52 68 61 56 50 66 58 54 49 5.0 4.9 4.9 4.8 5.0 5.0 4.9 4.8 5.0 5.0 4.9 4.8 5.0 4.9 4.9 4.8 5.0 4.9 4.9 4.8 86 83 80 77 74 71 68 53 64 60 55 50 61 59 53 47 58 58 52 43 53 56 50 40 48 54 49 46 56 60 55 43 54 59 53 41 52 58 52 38 47 56 50 35 43 54 49 38 49 60 55 37 47 59 53 35 46 57 61 33 42 53 48 30 39 49 44 31 41 53 47 30 41 52 46 29 40 51 45 27 37 48 42 26 34 44 40 23 34 46 40 23 34 45 39 23 34 45 39 22 32 42 37 21 29 40 35 26 38 32 27 38 33 28 39 33 26 27 32 25 35 30 19 31 25 20 32 26 22 33 27 21 32 27 20 31 26 TEMPERATURE OF AIR ON CONDENSER COIL AIR ON EVAPORATOR COIL TOTAL INPUT2 kW CFM WB °F CAP.1 MBH 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 66 59 55 49 65 58 54 48 63 58 52 47 62 55 51 46 60 53 49 44 5.5 5.5 5.4 5.4 5.5 5.5 5.4 5.4 5.5 5.5 5.4 5.4 5.5 5.5 5.4 5.4 5.5 5.5 5.4 5.4 2500 2250 2000 1750 1500 105°F 115°F SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER TOTAL 86 83 80 77 74 71 68 CAP.1 MBH 51 58 55 49 48 57 54 48 45 55 52 47 42 50 51 46 38 46 49 44 44 54 55 49 42 52 54 48 39 50 52 47 36 45 51 46 33 41 49 44 36 46 55 49 35 45 54 48 33 44 52 47 31 40 50 45 29 37 47 42 29 39 47 42 28 38 48 42 28 38 48 43 26 35 45 40 24 32 42 37 21 31 40 35 21 31 41 36 22 32 42 37 21 30 40 35 19 27 37 33 24 32 27 25 34 29 26 36 31 24 35 30 23 33 28 16 25 20 18 28 22 20 30 25 19 29 24 18 28 23 60 53 49 44 58 52 48 44 57 52 47 43 55 50 46 41 53 47 44 40 SENSIBLE CAPACITY1 ENTERING DRY BULB, °F POWER INPUT2 kW 6.0 6.0 5.9 5.9 6.0 6.0 5.9 5.9 6.0 6.0 5.9 5.9 6.1 6.0 6.0 5.9 6.1 6.1 6.0 6.0 86 83 80 77 74 71 68 49 53 49 44 46 52 48 44 44 52 47 43 40 48 46 41 36 44 44 40 41 51 49 44 40 49 48 44 38 48 47 43 35 43 46 41 32 39 44 40 34 43 49 44 33 43 48 44 32 42 47 43 30 38 46 41 27 35 44 40 26 36 42 37 26 36 44 39 26 36 46 41 24 33 43 38 23 30 39 35 19 28 34 29 20 29 37 32 20 30 40 35 19 28 37 33 18 25 35 30 21 27 22 22 30 25 24 34 29 22 32 27 21 30 26 13 19 15 16 24 19 18 28 23 17 27 22 16 25 21 1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit. 2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING 18 Unitary Products Group 036-21504-006-A-1105 TABLE 8: DF072 COOLING CAPACITIES (6 TON) OUTDOOR AMBIENT TEMPERATURE (°F) 85°F RETURN AIR CFM 2750 2475 2200 1925 1650 WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 GROSS POWER CAP. INPUT1 Kw MBH 83.1 79.5 72.7 66.7 82.4 78.8 72.1 66.1 81.7 78.1 71.4 65.5 79.3 75.8 69.4 63.6 77 73.6 67.3 61.7 5.24 5.15 5.08 5.04 5.25 5.16 5.10 5.05 5.26 5.18 5.11 5.06 5.24 5.15 5.08 5.04 5.21 5.12 5.06 5.01 95°F GROSS SENSIBLE CAPACITY1 (MBh) RETURN AIR DRY BULB TEMP. (°F) 86 83 80 77 74 71 68 54.6 67.8 72.7 66.7 52.1 65.0 72.1 66.1 49.6 62.3 71.4 65.5 45.6 57.5 67.7 63.6 41.6 52.7 64.0 61.7 46.4 59.6 72.7 66.7 44.8 57.7 70.7 66.1 43.2 55.8 68.7 65.5 40.0 51.9 64.0 62.3 36.9 48.0 59.3 59.2 38.2 51.4 64.8 64.6 37.5 50.4 63.5 63.4 36.8 49.4 62.3 62.1 34.5 46.4 58.5 58.3 32.2 43.3 54.6 54.5 30.0 43.2 56.6 56.4 30.2 43.1 56.2 56.1 30.3 43.0 55.9 55.7 28.9 40.8 52.9 52.7 27.5 38.6 49.9 49.8 21.8 35.0 48.4 48.2 22.9 35.8 48.9 48.8 23.9 36.6 49.5 49.3 23.4 35.3 47.3 47.2 22.8 33.9 45.2 45.0 26.8 40.2 40.0 28.5 41.6 41.5 30.2 43.1 42.9 29.7 41.8 41.6 29.2 40.5 40.3 18.6 32.0 31.8 21.2 34.3 34.1 23.8 36.6 36.5 24.1 36.2 36.1 24.5 35.8 35.6 GROSS POWER CAP. INPUT1 Kw MBH 80.2 75.3 68.3 65.8 79.9 75.0 68.0 65.5 79.6 74.7 67.7 65.2 77.1 72.3 65.6 63.2 74.5 69.9 63.4 61.1 5.92 5.80 5.74 5.77 5.89 5.78 5.72 5.74 5.87 5.75 5.69 5.72 5.86 5.74 5.68 5.71 5.85 5.73 5.67 5.70 GROSS SENSIBLE CAPACITY1 (MBh) RETURN AIR DRY BULB TEMP. (°F) 86 83 80 77 74 71 68 53.1 66.6 68.3 65.8 50.5 63.8 68.0 65.5 48.0 60.9 67.7 65.2 43.9 56.0 64.5 63.2 39.8 51.0 61.3 61.1 44.9 58.4 68.3 65.8 43.2 56.5 67.3 65.5 41.6 54.5 66.3 65.2 38.4 50.4 61.5 61.7 35.1 46.3 56.6 58.2 36.7 50.2 62.5 64.5 35.9 49.1 61.2 63.1 35.2 48.1 59.9 61.8 32.8 44.9 55.9 57.7 30.4 41.6 51.9 53.5 28.5 42.0 54.3 56.3 28.6 41.8 53.9 55.8 28.7 41.7 53.5 55.4 27.2 39.3 50.3 52.1 25.7 36.9 47.2 48.8 20.3 33.8 46.1 48.1 21.3 34.5 46.6 48.5 22.3 35.3 47.1 49.0 21.7 33.8 44.8 46.5 21.0 32.2 42.5 44.1 25.6 37.9 39.9 27.2 39.3 41.2 28.9 40.7 42.6 28.2 39.2 41.0 27.5 37.7 39.4 17.4 29.7 31.7 19.9 32.0 33.9 22.4 34.3 36.2 22.6 33.7 35.4 22.8 33.0 34.7 OUTDOOR AMBIENT TEMPERATURE (°F) 105°F RETURN AIR CFM 2750 2475 2200 1925 1650 WB °F 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 72 67 62 57 GROSS POWER CAP. INPUT1 Kw MBH 76.3 70.2 62.2 61.2 76.1 70.0 62.0 61.0 75.9 69.8 61.9 60.9 73.1 67.2 59.6 58.6 70.3 64.6 57.3 56.4 6.66 6.55 6.48 6.50 6.63 6.52 6.45 6.47 6.59 6.48 6.41 6.43 6.58 6.47 6.40 6.42 6.57 6.46 6.39 6.41 115°F GROSS SENSIBLE CAPACITY1 (MBh) RETURN AIR DRY BULB TEMP. (°F) 86 83 80 77 74 71 68 51.5 64.2 62.2 61.2 49.0 61.4 62.0 61.0 46.4 58.6 61.9 60.9 42.3 53.5 59.1 58.6 38.1 48.5 56.3 56.4 43.3 56.0 62.2 61.2 41.7 54.1 61.7 61.0 40.0 52.2 61.2 60.9 36.7 48.0 57.0 57.3 33.4 43.8 52.8 53.8 35.1 47.8 58.8 60.1 34.3 46.8 57.5 58.8 33.6 45.7 56.2 57.5 31.1 42.4 52.2 53.3 28.7 39.1 48.1 49.1 26.9 39.6 50.6 51.9 27.0 39.5 50.2 51.5 27.2 39.3 49.8 51.0 25.6 36.9 46.6 47.7 24.0 34.4 43.4 44.4 18.7 31.5 42.4 43.7 19.7 32.2 42.9 44.2 20.7 32.9 43.4 44.6 20.0 31.3 41.0 42.2 19.3 29.7 38.7 39.7 23.3 34.2 35.5 24.9 35.6 36.9 26.5 37.0 38.2 25.7 35.5 36.6 25.0 34.0 35.0 15.1 26.0 27.3 17.6 28.3 29.5 20.1 30.6 31.8 20.2 29.9 31.0 20.3 29.2 30.3 GROSS POWER CAP. INPUT1 Kw MBH 72.4 65.0 56.1 56.7 72.3 65.0 56.1 56.6 72.2 64.9 56.0 56.5 69.1 62.1 53.6 54.1 66.1 59.4 51.2 51.7 7.40 7.31 7.22 7.24 7.36 7.26 7.18 7.19 7.31 7.22 7.13 7.15 7.30 7.20 7.12 7.13 7.28 7.19 7.11 7.12 GROSS SENSIBLE CAPACITY1 (MBh) RETURN AIR DRY BULB TEMP. (°F) 86 83 80 77 74 71 68 50.0 61.9 56.1 56.7 47.4 59.1 56.1 56.6 44.8 56.2 56.0 56.5 40.6 51.1 53.6 54.1 36.4 45.9 51.2 51.7 41.8 53.7 56.1 56.7 40.1 51.7 56.1 56.6 38.4 49.8 56.0 56.5 35.0 45.5 52.5 53.0 31.7 41.2 49.0 49.4 33.6 45.5 55.2 55.7 32.8 44.4 53.9 54.4 32.0 43.4 52.6 53.1 29.5 40.0 48.4 48.9 26.9 36.5 44.3 44.7 25.4 37.3 47.0 47.5 25.5 37.1 46.6 47.1 25.6 37.0 46.2 46.7 23.9 34.4 42.9 43.3 22.2 31.8 39.6 40.0 17.2 29.1 38.8 39.3 18.2 29.8 39.2 39.8 19.2 30.5 39.7 40.3 18.4 28.8 37.3 37.8 17.5 27.1 34.9 35.3 20.9 30.6 31.1 22.5 31.9 32.5 24.1 33.3 33.9 23.3 31.7 32.2 22.4 30.2 30.6 12.7 22.4 22.9 15.2 24.6 25.2 17.7 26.9 27.4 17.7 26.2 26.7 17.7 25.5 25.9 1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.425 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit. 2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor. NOMINAL RATING Unitary Products Group 19 036-21504-006-A-1105 TABLE 9: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION UNIT TONNAGE 3 12 UNIT TONNAGE 3 12 AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3 0.60 0.40 0.50 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170 1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100 1700 - - 802 670 840 745 881 815 920 900 961 970 1001 1030 1600 - - - - 818 665 858 740 898 820 940 890 980 950 1500 - - - - - - 842 695 882 755 922 835 962 895 1400 - - - - - - 833 650 867 705 904 765 942 820 1300 - - - - - - - - 858 665 893 725 932 785 1200 - - - - - - - - 847 640 880 680 916 730 0.20 0.30 0.70 AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3 1.10 1.20 1.30 0.80 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 - - - - - - - - - - - - 1900 1085 1210 - - - - - - - - - - - - 1800 1064 1145 1102 1180 - - - - - - - - - - 1700 1040 1075 1081 1115 1121 1140 - - - - - - - - 1600 1020 1005 1060 1050 1100 1085 - - - - - - - - 1500 1003 945 1044 995 1086 1035 - - - - - - - - 1400 982 880 1024 920 1067 965 1107 1000 - - - - - - 1300 970 835 1010 870 1053 920 1099 960 - - - - - - 1200 953 780 992 815 1034 855 1080 905 - - - - - - 0.90 1.00 1.40 1.50 1. 230/460/575 Volts 2. For 208 Volts multiply values by 0.95. 3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows. 20 Unitary Products Group 036-21504-006-A-1105 TABLE 10: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION UNIT TONNAGE 4 12 UNIT TONNAGE 4 12 AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3 0.60 0.40 0.50 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235 1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170 1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100 1700 - - 802 670 840 745 881 815 920 900 961 970 1001 1030 1600 - - - - 818 665 858 740 898 820 940 890 980 950 1500 - - - - - - 842 695 882 755 922 835 962 895 1400 - - - - - - 833 650 867 705 904 765 942 820 1300 - - - - - - - - 858 665 893 725 932 785 1200 - - - - - - - - 847 640 880 680 916 730 0.20 0.30 0.70 AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3 1.10 1.20 1.30 0.80 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2000 1103 1270 - - - - - - - - - - - - 1900 1085 1210 - - - - - - - - - - - - 1800 1064 1145 1102 1180 - - - - - - - - - - 1700 1040 1075 1081 1115 1121 1140 - - - - - - - - 1600 1020 1005 1060 1050 1100 1085 - - - - - - - - 1500 1003 945 1044 995 1086 1035 - - - - - - - - 1400 982 880 1024 920 1067 965 1107 1000 - - - - - - 1300 970 835 1010 870 1053 920 1099 960 - - - - - - 1200 953 780 992 815 1034 855 1080 905 - - - - - - 0.90 1.00 1.40 1.50 1. 230/460/575 Volts 2. For 208 Volts multiply values by 0.95. 3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows. Unitary Products Group 21 036-21504-006-A-1105 TABLE 11: SUPPLY AIR BLOWER PERFORMANCE (5,6 TON BELT DRIVE) - SIDE DUCT APPLICATION UNIT TONNAGE 5, 61 2 UNIT TONNAGE 5, 61 2 AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3 0.60 0.40 0.50 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720 2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640 2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535 2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 1440 2100 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 1340 2000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 1225 1900 - - - - 894 885 940 940 980 980 1014 1020 1047 1095 1800 - - - - 855 815 903 860 950 905 988 940 1022 970 1700 - - - - - - 884 815 925 850 964 880 1001 910 1600 - - - - - - 864 770 908 805 948 835 987 870 1500 - - - - - - - - 882 740 926 780 965 830 0.20 0.30 0.70 AVAILABLE EXTERNAL STATIC PRESSURE-IWG 3 1.10 1.20 1.30 0.80 AIR FLOW CFM RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS 2500 - - - - - - - - - - - - - - 2400 1193 1665 - - - - - - - - - - - - 2300 1170 1580 1202 1620 - - - - - - - - - - 2200 1148 1480 1180 1530 - - - - - - - - - - 2100 1121 1385 1155 1425 1190 1475 - - - - - - - - 2000 1100 1285 1133 1340 1169 1385 1205 1445 - - - - - - 1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 - - - - 1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 - - - - 1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 - - 1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150 1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110 0.90 1.00 1.40 1.50 1. 230/460/575 Volts 2. For 208 Volts multiply values by 0.95. 3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows. 22 Unitary Products Group 036-21504-006-A-1105 TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (3 - 5 TON DIRECT DRIVE) - SIDE DUCT APPLICATION UNIT TONNAGE 3 4 5 1 1 1 UNIT TONNAGE 3 4 5 AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2 MOTOR SPEED 0.20 1 1 0.40 0.50 0.60 WATTS CFM WATTS CFM WATTS CFM WATTS CFM HI - - - - 1699 825 1650 785 1570 755 MED 1684 800 1631 780 1582 750 1524 720 1410 690 LOW 1487 710 1464 690 1421 670 1367 650 1315 620 HI 1996 960 1933 936 1868 910 1795 880 1722 845 MED 1804 838 1765 810 1714 785 1650 765 1589 735 LOW 1681 760 1640 738 1604 715 1541 695 1490 670 HI 2400 1155 2338 1125 2274 1095 2167 1045 2096 1010 MED 2290 1105 2214 1065 2145 1030 2071 990 1990 950 LOW 2150 1020 2100 990 2029 950 1965 910 1905 880 MOTOR SPEED 1 0.30 CFM AVAILABLE EXTERNAL STATIC PRESSURE-IWG 2 0.80 0.90 0.70 WATTS 1.00 CFM WATTS CFM WATTS CFM WATTS CFM WATTS HI 1430 725 1360 700 1280 680 1180 655 MED 1324 650 1260 630 1185 610 1100 590 LOW 1246 605 1185 590 1110 570 1020 545 HI 1635 820 1544 790 1419 765 1300 740 MED 1508 705 1407 675 1306 645 1195 625 LOW 1416 645 1337 620 1230 595 1120 575 HI 1990 980 1887 945 1771 905 1629 855 MED 1911 920 1828 885 1724 835 1604 798 LOW 1816 838 1724 800 1644 770 1531 710 1. Side Duct application (230/460/575 Volts) 2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values. TABLE 13: BELT DRIVE BLOWER MOTOR AND DRIVE DATA MOTOR1 ADJUSTABLE MOTOR PULLEY BELT (NOTCHED) FIXED BLOWER PULLEY MODEL SIZE BLOWER RANGE (RPM) HP FRAME DESIGNATION OUTSIDE DIA. (IN.) PITCH DIA. (IN.) BORE (IN.) DESIGNATION OUTSIDE DIA. (IN.) PITCH DIA. (IN.) BORE (IN.) DESIGNATION PITCH LENGTH (IN.) QTY. 3 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1 4 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1 5, 6 TON 850/1220 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK56 5.4 5.2 1 A36 37.3 1 1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device. Unitary Products Group 23 036-21504-006-A-1105 TABLE 14: STATIC RESISTANCES RESISTANCE, IWG DESCRIPTION CFM 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0.30 7-15KW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.22 20-30KW 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 BOTTOM DUCT CONNECTIONS1 0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.14 0.16 0.19 0.22 COOLING ONLY2 0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.23 0.26 0.29 0.32 ECONOMIZER1 3 ELECTRIC HEATERS1 1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables. 2. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables. 3. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation. TABLE 15: ELECTRIC HEATER CFM LIMITATIONS MINIMUM SUPPLY AIR CFM UNITMODEL SIZE NOMINAL TONS VOLTAGE HEATER SIZE NOMINAL KW 5 7 10 15 20 30 208/230-1-60 1100 1100 1200 1200 1300 - 208/230-3-60 1100 1100 1200 1200 1300 - 460-3-60 - 1100 1200 1200 1300 - 575-3-60 - - 1200 1200 1300 - 208/230-1-60 1300 1300 1300 1300 1300 - 208/230-3-60 1300 1300 1300 1300 1300 - 460-3-60 - 1300 1300 1300 1300 - 575-3-60 - - 1300 1300 1400 - 208/230-1-60 1600 1600 1600 1600 1600 1600 208/230-3-60 1600 1600 1600 1600 1600 1600 460-3-60 - 1600 1600 1600 1600 1600 575-3-60 - - 1600 1600 1600 1800 208/230-3-60 1800 1800 1800 1800 1800 1800 460-3-60 - 1800 1800 1800 1800 1800 575-3-60 - - 1800 1800 1800 1800 3 4 5 6 24 Unitary Products Group 036-21504-006-A-1105 TABLE 16: ELECTRICAL DATA - DF036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 16.7 87 2.3 4.4 0.0 230-1-60 16.7 87 2.3 4.4 0.0 208-3-60 13.1 110 2.3 4.4 0.0 230-3-60 13.1 110 2.3 4.4 0.0 460-3-60 6.7 54 1.3 2.2 0.0 575-3-60 5.1 44 1.3 2.2 0.0 208-1-60 25.0 135 2.3 5.0 0.0 230-1-60 25.0 135 2.3 5.0 0.0 208-3-60 14.7 130 2.3 5.0 0.0 230-3-60 14.7 130 2.3 5.0 0.0 460-3-60 7.7 64 1.3 2.2 0.0 575-3-60 6.4 52 1.3 2.2 0.0 3 4 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps Max Fuse / 1 BRKR Size Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE045105252 2CE045107252 2CE04511025 2CE04511525 2CE04512025 NONE 2CE04510525 2CE045105252 2CE045107252 2CE04511525 2CE04512025 NONE 2CE045107462 2CE045110462 2CE045115462 2CE045120462 NONE 2CE04511058 2CE04511558 2CE04512058 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE045105252 2CE045107252 2CE04511025 2CE04511525 2CE04512025 NONE 2CE045105252 2CE045107252 2CE04511025 2CE04511525 2CE04512025 NONE 2CE045107462 2CE045110462 2CE045115462 2CE045120462 NONE 2CE04511058 2CE04511558 2CE04512058 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 27.5 30.7 39.2 53.6 77.0 101.1 27.5 33.1 44.6 60.7 88.3 115.9 23.1 24.3 24.9 33.3 46.8 60.7 23.1 24.3 28.1 37.4 53.3 69.2 12.0 13.0 17.9 23.2 32.1 10.7 14.9 21.3 27.7 38.5 38.5 39.9 54.3 77.8 101.8 38.5 38.5 45.3 61.5 89.1 116.7 25.7 25.7 25.7 34.0 47.5 61.4 25.7 25.7 28.8 38.1 54.1 70.0 13.1 13.1 17.9 23.2 32.1 10.8 14.9 21.3 27.7 45 45 45 60 80 110 45 45 45 70 90 125 35 35 35 35 50 70 35 35 35 40 60 70 15 15 20 25 35 15 15 25 30 60 60 60 60 80 110 60 60 60 70 90 125 40 40 40 40 50 70 40 40 40 40 60 70 20 20 20 25 35 15 15 25 30 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. Unitary Products Group 25 036-21504-006-A-1105 TABLE 17: ELECTRICAL DATA - DF060 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 32.1 148 2.3 6.6 0.0 230-1-60 32.1 148 2.3 6.6 0.0 208-3-60 19.3 123 2.3 6.6 0.0 230-3-60 19.3 123 2.3 6.6 0.0 460-3-60 9.1 62 1.3 3.3 0.0 575-3-60 7.9 50 1.3 3.3 0.0 5 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps Max Fuse / 1 BRKR Size Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2 2CE04510525 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2 2CE04510525 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2 2CE04510746 2 2CE04511046 2 2CE04511546 2CE04512046 2 2 2CE04513046 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 19.2 26.9 38.5 57.2 76.4 106.7 0.0 22.1 31.3 44.2 66.3 88.3 123.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 49.0 49.0 49.0 56.3 79.8 103.8 141.7 49.0 49.0 49.0 63.5 91.1 118.7 162.4 33.0 33.0 33.0 36.0 49.5 63.4 85.3 33.0 33.0 33.0 40.1 56.1 72.0 97.3 16.0 16.0 19.3 24.6 33.4 47.4 13.6 16.0 22.4 28.8 39.9 80 80 80 80 80 110 150 80 80 80 80 100 125 175 50 50 50 50 50 70 90 50 50 50 50 60 80 100 25 25 25 25 35 50 20 20 25 30 40 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. 26 Unitary Products Group 036-21504-006-A-1105 TABLE 18: ELECTRICAL DATA - DF036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 16.7 87 2.3 7.6 0.0 230-1-60 16.7 87 2.3 7.6 0.0 208-3-60 13.1 110 2.3 5.2 0.0 230-3-60 13.1 110 2.3 5.2 0.0 460-3-60 6.7 54 1.3 2.6 0.0 575-3-60 5.1 44 1.3 2 0.0 208-1-60 25.0 135 2.3 7.6 0.0 230-1-60 25.0 135 2.3 7.6 0.0 208-3-60 14.7 130 2.3 5.2 0.0 230-3-60 14.7 130 2.3 5.2 0.0 460-3-60 7.7 64 1.3 2.6 0.0 575-3-60 6.4 52 1.3 2 0.0 3 4 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps Max Fuse / 1 BRKR Size Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2 2CE04510525 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2CE04510525 2 2CE04510525 2CE04510725 2 2CE04511525 2CE04512025 NONE 2 2CE04510746 2CE04511046 2 2CE04511546 2 2CE04512046 2 NONE 2CE04511058 2CE04511558 2CE04512058 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2 2CE04510525 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510525 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510746 2CE04511046 2 2CE04511546 2 2CE04512046 2 NONE 2CE04511058 2CE04511558 2CE04512058 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 30.1 33.9 43.2 57.6 81.0 105.1 30.1 37.1 48.6 64.7 92.3 119.9 23.9 25.1 25.9 34.3 47.8 61.7 23.9 25.1 29.1 38.4 54.3 70.2 12.4 13.5 18.4 23.7 32.6 9.8 14.7 21.1 27.5 41.2 41.2 43.2 57.6 81.0 105.1 41.2 41.2 48.6 64.7 92.3 119.9 25.9 25.9 25.9 34.3 47.8 61.7 25.9 25.9 29.1 38.4 54.3 70.2 13.5 13.5 18.4 23.7 32.6 10.6 14.7 21.1 27.5 50 50 50 60 90 110 50 50 50 70 100 125 35 35 35 35 50 70 35 35 35 40 60 80 15 15 20 25 35 15 15 25 30 60 60 60 60 90 110 60 60 60 70 100 125 40 40 40 40 50 70 40 40 40 40 60 80 20 20 20 25 35 15 15 25 30 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. Unitary Products Group 27 036-21504-006-A-1105 TABLE 19: ELECTRICAL DATA - DF060 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 32.1 148 2.3 7.6 0.0 230-1-60 32.1 148 2.3 7.6 0.0 208-3-60 19.3 123 2.3 5.2 0.0 230-3-60 19.3 123 2.3 5.2 0.0 460-3-60 9.1 62 1.3 2.6 0.0 575-3-60 7.9 50 1.3 2 0.0 5 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2 2CE04510746 2CE04511046 2 2 2CE04511546 2 2CE04512046 2CE04513046 2 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 19.2 26.9 38.5 57.2 76.4 106.7 0.0 22.1 31.3 44.2 66.3 88.3 123.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 50.0 50.0 50.0 57.6 81.0 105.1 142.9 50.0 50.0 50.0 64.7 92.3 119.9 163.7 31.6 31.6 31.6 34.3 47.8 61.7 83.5 31.6 31.6 31.6 38.4 54.3 70.2 95.5 15.3 15.3 18.4 23.7 32.6 46.6 12.5 14.7 21.1 27.5 38.6 Max Fuse / BRKR1 Size Amps 80 80 80 80 90 110 150 80 80 80 80 100 125 175 50 50 50 50 50 70 90 50 50 50 50 60 80 100 20 20 20 25 35 50 15 15 25 30 40 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. 28 Unitary Products Group 036-21504-006-A-1105 TABLE 20: ELECTRICAL DATA - DF072 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motors FLA ID Blower Motor FLA Conv Outlet Amps 208-3-60 18.6 156 2.3 5.2 0.0 230-3-60 18.6 156 2.3 5.2 0.0 460-3-60 9.0 75 1.3 2.6 0.0 573-3-60 7.4 54 1.3 2.0 0.0 6 Electric Heater Model No. 3 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510746 2 2CE04511046 2 2 2CE04511546 2 2CE04512046 2CE04513046 2 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 Heater kW Heater Amps Minimum Circuit Ampacity Amps 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 30.8 30.8 30.8 34.1 47.9 61.7 83.6 30.8 30.8 30.8 38.4 54.3 70.2 95.5 15.2 15.2 18.4 23.7 32.6 46.6 12.6 15.2 21.6 28.0 39.1 Max Fuse / BRKR1 Size Amps 45 45 45 45 50 70 90 45 45 45 45 60 80 100 20 20 20 25 35 50 15 20 25 30 40 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code, the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. Unitary Products Group 29 036-21504-006-A-1105 TABLE 21: ELECTRICAL DATA - DF036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 16.7 87 2.3 4.4 10.0 230-1-60 16.7 87 2.3 4.4 10.0 208-3-60 13.1 110 2.3 4.4 10.0 230-3-60 13.1 110 2.3 4.4 10.0 460-3-60 6.7 54 1.3 2.2 5.0 575-3-60 5.1 44 1.3 2.2 4.0 208-1-60 25.0 135 2.3 5.0 10.0 230-1-60 25.0 135 2.3 5.0 10.0 208-3-60 14.7 130 2.3 5.0 10.0 230-3-60 14.7 130 2.3 5.0 10.0 460-3-60 7.7 64 1.3 2.2 5.0 575-3-60 6.4 52 1.3 2.2 4.0 3 4 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps Max Fuse / 1 BRKR Size Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2 2CE04510525 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 NONE 2CE04510525 2 2CE04510525 2CE04510725 2 2CE04511525 2CE04512025 NONE 2 2CE04510746 2 2CE04511046 2 2CE04511546 2CE04512046 2 NONE 2CE04511058 2CE04511558 2CE04512058 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2 2CE04510525 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510525 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 NONE 2 2CE04510746 2 2CE04511046 2 2CE04511546 2 2CE04512046 NONE 2CE04511058 2CE04511558 2CE04512058 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 37.5 42.0 51.7 66.1 89.5 113.6 37.5 45.6 57.1 73.2 100.8 128.4 33.4 34.3 37.4 45.8 59.3 73.2 33.4 34.3 40.6 49.9 65.8 81.7 17.1 19.2 24.2 29.4 38.3 12.9 19.9 26.3 32.7 48.5 48.5 52.4 66.8 90.3 114.3 48.5 48.5 57.8 74.0 101.6 129.2 35.7 35.7 38.2 46.5 60.0 73.9 35.7 35.7 41.3 50.6 66.6 82.5 18.1 19.2 24.2 29.4 38.3 14.8 19.9 26.3 32.7 50 50 60 70 90 125 50 50 60 80 110 150 45 45 45 50 60 80 45 45 45 50 70 90 20 20 25 30 40 15 20 30 35 70 70 70 70 100 125 70 70 70 80 110 150 50 50 50 50 70 80 50 50 50 60 70 90 25 25 25 30 40 20 20 30 35 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. 30 Unitary Products Group 036-21504-006-A-1105 TABLE 22: ELECTRICAL DATA - DF060 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 32.1 148 2.3 6.6 10.0 230-1-60 32.1 148 2.3 6.6 10.0 208-3-60 19.3 123 2.3 6.6 10.0 230-3-60 19.3 123 2.3 6.6 10.0 460-3-60 9.1 62 1.3 3.3 5.0 575-3-60 7.9 50 1.3 3.3 4.0 5 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps Max Fuse / 1 BRKR Size Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2 2CE04510525 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2 2CE04510525 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2 2CE04510746 2 2CE04511046 2 2CE04511546 2CE04512046 2 2 2CE04513046 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 19.2 26.9 38.5 57.2 76.4 106.7 0.0 22.1 31.3 44.2 66.3 88.3 123.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 59.0 59.0 59.0 68.8 92.3 116.3 154.2 59.0 59.0 59.8 76.0 103.6 131.2 174.9 43.0 43.0 43.0 48.5 62.0 75.9 97.8 43.0 43.0 43.3 52.6 68.6 84.5 109.8 21.0 21.0 25.6 30.8 39.7 53.7 17.6 21.0 27.4 33.8 44.9 90 90 90 90 100 125 175 90 90 90 90 110 150 175 60 60 60 60 70 80 100 60 60 60 60 70 90 110 30 30 30 35 40 60 20 25 30 35 45 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. Unitary Products Group 31 036-21504-006-A-1105 TABLE 23: ELECTRICAL DATA - DF036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 16.7 87 2.3 7.6 10.0 230-1-60 16.7 87 2.3 7.6 10.0 208-3-60 13.1 110 2.3 5.2 10.0 230-3-60 13.1 110 2.3 5.2 10.0 460-3-60 6.7 54 1.3 2.6 5.0 575-3-60 5.1 44 1.3 2 4.0 208-1-60 25.0 135 2.3 7.6 10.0 230-1-60 25.0 135 2.3 7.6 10.0 208-3-60 14.7 130 2.3 5.2 10.0 230-3-60 14.7 130 2.3 5.2 10.0 460-3-60 7.7 64 1.3 2.6 5.0 575-3-60 6.4 52 1.3 2 4.0 3 4 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE045105252 2CE045107252 2CE04511025 2CE04511525 2CE04512025 NONE 2CE04510525 2CE045105252 2CE045107252 2CE04511525 2CE04512025 NONE 2CE045107462 2CE045110462 2CE045115462 2CE045120462 NONE 2CE04511058 2CE04511558 2CE04512058 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 NONE 2CE045105252 2CE045107252 2CE04511025 2CE04511525 2CE04512025 NONE 2CE045105252 2CE045107252 2CE04511025 2CE04511525 2CE04512025 NONE 2CE045107462 2CE045110462 2CE045115462 2CE045120462 NONE 2CE04511058 2CE04511558 2CE04512058 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 4.0 5.6 8.0 11.9 15.9 0.0 5.3 7.5 10.6 15.9 21.2 0.0 6.8 10.1 13.6 19.5 0.0 10.6 15.9 21.2 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 0.0 19.2 26.9 38.5 57.2 76.4 0.0 22.1 31.3 44.2 66.3 88.3 0.0 11.1 15.5 22.2 33.0 44.1 0.0 12.7 18.0 25.5 38.2 51.0 0.0 8.2 12.1 16.4 23.5 0.0 10.2 15.3 20.4 41.0 46.0 55.7 70.1 93.5 117.6 41.0 49.6 61.1 77.2 104.8 132.4 34.4 35.1 38.4 46.8 60.3 74.2 34.4 35.1 41.6 50.9 66.8 82.7 17.6 19.7 24.7 29.9 38.8 14.0 19.7 26.1 32.5 51.2 51.2 55.7 70.1 93.5 117.6 51.2 51.2 61.1 77.2 104.8 132.4 35.9 35.9 38.4 46.8 60.3 74.2 35.9 35.9 41.6 50.9 66.8 82.7 18.5 19.7 24.7 29.9 38.8 14.6 19.7 26.1 32.5 Max Fuse / BRKR1 Size Amps 60 60 60 80 100 125 60 60 70 80 110 150 45 45 45 50 70 80 45 45 45 60 70 90 20 20 25 30 40 15 20 30 35 70 70 70 80 100 125 70 70 70 80 110 150 50 50 50 50 70 80 50 50 50 60 70 90 25 25 25 30 40 20 20 30 35 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. 32 Unitary Products Group 036-21504-006-A-1105 TABLE 24: ELECTRICAL DATA - DF060 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motor FLA ID Blower Motor FLA Conv Outlet Amps 208-1-60 32.1 148 2.3 7.6 10.0 230-1-60 32.1 148 2.3 7.6 10.0 208-3-60 19.3 123 2.3 5.2 10.0 230-3-60 19.3 123 2.3 5.2 10.0 460-3-60 9.1 62 1.3 2.6 5.0 575-3-60 7.9 50 1.3 2 4.0 5 Electric Heater Model No. Heater kW Heater Amps Minimum Circuit Ampacity Amps NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510506 2CE04510706 2CE04511006 2CE04511506 2CE04512006 2CE04513006 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2CE04510725 2 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2 2CE04510746 2CE04511046 2 2 2CE04511546 2 2CE04512046 2CE04513046 2 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 19.2 26.9 38.5 57.2 76.4 106.7 0.0 22.1 31.3 44.2 66.3 88.3 123.3 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 60.0 60.0 60.0 70.1 93.5 117.6 155.4 60.0 60.0 61.1 77.2 104.8 132.4 176.2 41.6 41.6 41.6 46.8 60.3 74.2 96.0 41.6 41.6 41.6 50.9 66.8 82.7 108.0 20.3 20.3 24.7 29.9 38.8 52.8 16.5 19.7 26.1 32.5 43.6 Max Fuse / BRKR1 Size Amps 90 90 90 90 100 125 175 90 90 90 90 110 150 200 60 60 60 60 70 80 100 60 60 60 60 70 90 110 25 25 25 30 40 60 20 20 30 35 45 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. Unitary Products Group 33 036-21504-006-A-1105 TABLE 25: ELECTRICAL DATA - DF072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET Model Tonnage Compressors Voltage RLA Each LRA Each OD Fan Motors FLA ID Blower Motor FLA Conv Outlet Amps 208-3-60 18.6 156 2.3 5.2 10.0 230-3-60 18.6 156 2.3 5.2 10.0 460-3-60 9.0 75 1.3 2.6 5.0 573-3-60 7.4 54 1.3 2.0 4.0 6 Electric Heater Model No. 3 NONE 2 2CE04510525 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510525 2 2 2CE04510725 2CE04511025 2CE04511525 2CE04512025 2CE04513025 NONE 2CE04510746 2 2 2CE04511046 2CE04511546 2 2 2CE04512046 2 2CE04513046 NONE 2CE04511058 2CE04511558 2CE04512058 2CE04513058 Heater kW Heater Amps Minimum Circuit Ampacity Amps 0.0 4.0 5.6 8.0 11.9 15.9 22.2 0.0 5.3 7.5 10.6 15.9 21.2 29.6 0.0 6.8 10.1 13.6 19.5 28.8 0.0 10.6 15.9 21.2 30.4 0.0 11.1 15.5 22.2 33.0 44.1 61.6 0.0 12.7 18.0 25.5 38.2 51.0 71.2 0.0 8.2 12.1 16.4 23.5 34.6 0.0 10.2 15.3 20.4 29.3 40.8 40.8 40.8 46.6 60.4 74.2 96.1 40.8 40.8 41.6 50.9 66.8 82.7 108.0 20.2 20.2 24.7 29.9 38.8 52.8 16.6 20.2 26.6 33.0 44.1 Max Fuse / BRKR1 Size Amps 50 50 50 50 70 80 100 50 50 50 60 70 90 110 25 25 25 30 40 60 20 25 30 35 45 1. HACR Type per NEC. 2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation. 34 Unitary Products Group 036-21504-006-A-1105 TABLE 26: PHYSICAL DATA DF MODELS Centrifugal Blower (Dia. x Wd. in.) EVAPORATOR BLOWER EVAPORATOR COIL CONDENSER FANS 048 060 072 12 X 10 12 X 10 12 X 10 12 X 10 Fan Motor HP (Direct Drive) 1/2 3/4 1 N/A Fan Motor HP (Belt Drive) 1 1/2 1 1/2 1 1/2 1 1/2 Rows Deep 3 3 3 4 Fins Per Inch 13 13 13 13 Face Area (Sq. Ft.) 3.6 4.3 5.1 5.1 Propeller Dia. (in.) 22 22 22 24 Fan Motor Hp 1/2 1/2 1/2 1/2 4200 Nom. CFM 4500 4200 4500 Rows Deep 2 2 2 2 Fins Per Inch 18 18 18 18 Face Area (Sq. Ft.) 17.1 17.1 17.1 17.1 Recip Type 1 1 1 1 Quantity Per Unit (15” X 20” X 1” or 2“) 2 2 2 2 Quantity Per Unit (14” X 25” X 1” or 2“) 1 1 1 1 Total Face Area (sq. ft.) 6.6 6.6 6.6 6.3 Refrigerant 22 (lbs./oz.) 9/12 9/8 9/8 11/0 CONDENSER COILS COMPRESSOR (Qty. Per Unit) AIR FILTERS 036 CHARGE TABLE 27: ELECTRIC HEAT CORRECTION FACTORS NOMINAL VOLTAGE VOLTAGE kW CAP. MULTIPLIER 208 208 1.00 240 230 0.92 480 460 0.92 600 575 0.92 TABLE 28: VOLTAGE LIMITATIONS1 VOLTAGE POWER SUPPLY MIN. MAX. 208/230-1-60 187 252 208/230-3-60 187 252 460-3-60 432 504 575-3-60 540 630 1. Utilization Range “A” in accordance with ARI Standard 110. Unitary Products Group 35 036-21504-006-A-1105 TYPICAL POWER WIRING REFER TO THE ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, OVERCURRENT PROTECTION AND WIRING. TYPICAL CONTROL WIRING COOLING / HEATING (24 VOLT THERMOSTAT) COOLING ONLY (24 VOLT THERMOSTAT) THERMOSTAT 1 TERMINALS THERMOSTAT1 UNIT TERMINAL TERMINALS STRIP TB1 ADD JUMPER R RV UNIT TERMINAL STRIP TB1 RC R Y Y1 24 VOLT TRANSFORMER Y1 YC RH 24 VOLT TRANSFORMER Y2 Y2 W W1 G GF W2 C G G C 1 24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THE THERMOSTAT 2TH0401224. COOLING / HEATING (ELECTRONIC THERMOSTAT) MULTI STAGE THERMOSTAT1 TERMINALS ADD JUMPER RC UNIT TERMINAL STRIP TB1 RH R Y1 W1 ADD JUMPER 24 VOLT TRANSFORMER G C LED 1 X NOT USED RH W2 B OCC ADD JUMPER 4 A1 A2 T T ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET04700224 (INCLUDES SUBBASE). 2 SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER. 3 SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE ELECTRIC HEATER OR 2 STAGE GAS HEAT. REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE THERMOSTAT SWITCHES TO THE SET-BACK POSITION. UNIT TERMINAL STRIP TB1 RC R Y Y1 W W1 G G C TO REMOTE SENSOR 2TH040702224 IF USED 1 4 THERMOSTAT1 TERMINALS Y2 G COM COOLING / HEATING (ELECTRONIC THERMOSTAT) SINGLE STAGE W1 3 W2 LED 2 24 VOLT THERMOSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO STAGES OF HEAT, USE THERMOSTAT 2TH0471024. Y1 2 Y2 4 1 24 VOLT TRANSFORMER 1 ELECTRONIC PROGRAMMABLE THERMOSTAT 2ET07701024 (INCLUDES SUBBASE). TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, USE THERMOSTAT 2TH04700224. FIGURE 2 - TYPICAL FIELD POWER & CONTROL WIRING 36 Unitary Products Group 036-21504-006-A-1105 FIGURE 3 - UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT) FRONT VIEW FIGURE 4 - UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW Unitary Products Group 37 036-21504-006-A-1105 DETAIL “A” FIGURE 5 - UNIT WITH ECONOMIZER RAINHOOD DETAIL “B” FIGURE 6 - UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD 38 Unitary Products Group 036-21504-006-A-1105 FIGURE 7 - UNIT DIMENSIONS (REAR VIEW) TABLE 30: MINIMUM CLEARANCES FILTER ACCESS LOCATION CLEARANCE Front 24” (Cooling/Electric Heat) 32” (Gas Heat) Rear 12” (Less Economizer) 36” (With Economizer or Fixed Air/ Motorized Damper) Left Side (Filter Access) 24” (Less Economizer) 36” (With Economizer) Right Side (Cond. Coil) 24” BLOWER MOTOR ACCESS DOT PLUGS FIELD-SUPPLIED DISCONNECT SWITCH LOCATION MOUNTING BRACKET FOR DICONNECT SWITCH (Shipped attached to the blower housing inside the blower compartment) A,B WIRING ENTRY (See Detail “B”) CONTROL BOX ACCESS DISCONNECT SWITCH LOCATION AND MOTOR ACCESS PANEL FOR UNIT WITH “BELT-DRIVE” OPTION FIGURE 8 - DISCONNECT/BLOWER ACCESS LOCATION Below Unit1 0” Above Unit2 72” (For Condenser Air Discharge) 1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material. 2. Units must be installed outdoors. Overhanging structures or shrubs should not obstruct condenser air discharge outlet. TABLE 29: UTILITIES ENTRY HOLE OPENING SIZE (DIA.) USED FOR A 7/8” KO1 Control Wiring2 B 2” KO1 Power Wiring C 1-5/8” KO Gas Piping (Front) D 1-1/2” KO Gas Piping (Bottom) Side Bottom Side Bottom 1. Opening in the bottom to the unit can be located by the side in the insulation. 2. Do not remove the 2” knockout ring. Unitary Products Group 39 036-21504-006-A-1105 FIGURE 9 - TYPICAL APPLICATIONS 40 Unitary Products Group 036-21504-006-A-1105 BACK OF UNIT A 447/8 BACK OF UNIT A 447/8 821/4 821/4 D B F X X B APPROXIMATE CENTER OF GRAVITY CONDENSER COIL END OF UNIT C Y FRONT OF UNIT C E APPROXIMATE CENTER OF GRAVITY CONDENSER COIL END OF UNIT D Y FRONT OF UNIT FIGURE 10 - FOUR AND SIX POINT LOADING TABLE 31: DF 4 AND 6 POINT LOADS WEIGHT DISTRIBUTION UNIT TOTAL 4-Point Loading (lb) 6-Point Loading (lb) A B C D A B C D E F DF036 Cooling/ Electric 565 125 123 157 160 84 83 82 104 105 107 DF036N04 605 134 132 168 171 90 89 88 112 113 114 DF036D06 615 137 134 171 174 91 90 89 113 115 116 DF036N08 625 139 136 173 177 93 92 91 115 117 118 DF036D10 635 141 138 176 179 94 93 92 117 119 120 DF048 Cooling/ Electric 615 137 134 171 174 91 90 89 113 115 116 DF048(D,N)06 665 148 145 184 188 99 98 96 123 124 126 DF048(D,N)10 685 152 149 190 194 102 100 99 126 128 129 DF060 Cooling/ Electric 640 142 140 178 181 95 94 93 118 119 121 DF060D06 690 153 150 191 195 102 101 100 127 129 130 DF060N08 700 155 153 194 198 104 103 101 129 131 132 DF060(D,N)10 710 158 155 197 201 105 104 103 131 132 134 DF072 Cooling/ Electric 660 147 144 183 186 98 97 96 122 123 125 DF072D06 710 158 155 197 201 105 104 103 131 132 134 DF072N08 720 160 157 200 203 107 106 104 133 134 136 DF072(D,N)10 730 162 159 202 206 108 107 106 135 136 138 TABLE 32: CENTER OF GRAVITY DIMENSION 3 - 5 TON 6 TON X 40-¾” 44” Y 19-¾” 22” Unitary Products Group 41 036-21504-006-A-1105 TABLE 33: OPERATING WEIGHTS (LBS.) MODEL SIZE 3 TON 4 TON 5 TON 6 TON 565 615 640 660 N04 605 - - - N06 - 665 - - N08 625 - 700 720 N10 - 685 710 730 D06 615 665 690 760 D10 635 685 710 730 DF (Cooling Only) BASIC UNIT DF (Gas/Electric) Economizer 50 Motorized Damper OPTIONS Electric Heater ACCY. 26 5 - 7 kW 18 10 - 15 kW 23 20 - 30 kW 28 Roof Curb 92 Barometric Relief / Fixed Air Damper 10 Belt-Drive Blower 5 FIGURE 11 - ROOF CURB DIMENSIONS 42 Unitary Products Group 036-21504-006-A-1105 GUIDE SPECIFICATIONS GENERAL Units shall be manufactured by York International Unitary Products Group in an ISO 9001 certified facility. York's Sunline PlusTM units are convertible single packageunits. Although the units are primarily designed for curb mounting on a roof, they can also be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed accessories to make them suitable for almost every application. All units are self-contained and assembled on full perimeter base rails with holes in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the factory to simplify the field installation and to provide years of dependable operation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal panels from the supply and return air openings through the base of the unit. For horizontal duct, remove the supply and return air panels on the rear of the unit. All compressors include crankcase heaters and all compressors have internal pressure relief. Every refrigerant circuit includes a liquid line filter-drier, a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch.The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board with a compressor lockout circuit, a terminal strip for thermostat wiring, plus an additional set of pin connectors to simplify the interface of additional field controls. All units have long lasting powder paint cabinets with 1000 hour salt spray test approval under ASTMB117 procedures. All models are CSA listed. All models include a 1-year limited warranty on the complete unit. Compressors and electric heater elements carry a 5-year warranty. Aluminized steel and Stainless steel tubular heat exchangers carry a 10-year warranty. DESCRIPTION Units shall be factory-assembled, single packaged, Electric Cooling/Gas Heat, Electric Cooling/Optional Electric Heat and designed for outdoor mounted installation. The 4 and 5 ton units have SEER ratings of 11.0, the 3 ton unit is rated at 11.5 SEER and the 6 ton unit is rated at 10.4 EER. They shall have built-in field convertible duct connections for down discharge supply/return or horizontal discharge supply/ return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and factory tested prior to shipment. All unit wiring shall be both numbered and color coded. All units the cooling performance shall be rated in accordance with DOE and ARI test procedures. Units shall be CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236 standards. Unitary Products Group UNIT CABINET Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 1000 hours salt spray test per ASTMB117 standards. Indoor blower section shall be insulated with a minimum 1/2” thick insulation, coated on the airside. Aluminum foil faced insulation shall be used in the furnace compartment and be fastened with ridged fasteners to prevent insulation from entering the air stream. Cabinet panels shall be “large” size, easily removable for servicing and maintenance. Full perimeter base rails shall be provided to assure reliable transit of equipment, overhead rigging and proper sealing on roof curb applications. Disposable 1" filters shall be furnished and be accessible through a removable access door, sealed airtight. Units filter track shall be designed to accommodate either 1” or 2” filters. Fan performance measuring ports shall be provided on the outside of the cabinet to allow accurate air measurements of evaporator fan performance without removing panels or creating air bypass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self-draining standards. Condensate connection shall be a minimum of 3/4” I.D. female and be a ridged mount connection. INDOOR (EVAPORATOR) FAN ASSEMBLY The indoor fan shall be direct drive, multi-speed, or a factory installed belt drive assembly that includes an adjustable pitch motor pulley. Job site selected (B.H.P.) brake horsepower shall not exceed the motors nameplate horsepower rating, plus the service factor. Units shall be designed not to operate above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically balanced to operate smoothly throughout the entire range of operation. Airflow design shall be constant air volume. Bearings shall be sealed and permanently lubricated for longer life and no maintenance. OUTDOOR (CONDENSER) FAN ASSEMBLY The outdoor fan shall be of the direct-driven propeller type, discharge air vertically, have aluminum blades riveted to a corrosion resistant steel spider bracket and shall be dynamically balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bearings, internally protected against overload conditions and staged independently. REFRIGERANT COMPONENTS Compressor: a. Shall be internally protected with internal high-pressure relief and over temperature protection. b. Shall have internal spring isolation and sound muffling to minimize vibration and noise, and be externally isolated on a dedicated, independent mounting. 43 036-21504-006-A-1105 Coils: GAS HEATING SECTION (SINGLE OR 2 STAGE) a. Evaporator and condenser coils shall have aluminum plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option. b. Evaporator and Condenser coils shall be of the direct expansion, draw-thru, design. Refrigerant Circuit and Refrigerant Safety Components shall include: a. Thermal expansion devices (TXV’s). • DF072 uses a fixed orifice distributor. b. Filter drier/strainer to eliminate any moisture or foreign matter. c. Accessible service gage connections on both suction and liquid lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting without losing charge. d. The refrigeration system shall provide at least 15°F of sub-cooling at design conditions. UNIT CONTROLS a. Unit shall be complete with self-contained low-voltage control circuit protected by a resetable circuit breaker on the 24-volt transformer side. b. Unit shall incorporate a lockout circuit which provides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor. c. Loss-of-charge/Low-pressure switch. d. High-pressure switch. e. Freeze-protection thermostat, evaporator coil. f. If any of the above safety devices trip, a LED (lightemitting diode) indicator shall flash a diagnostic code that indicates which safety switch has tripped. g. Unit shall incorporate “AUTO RESET” compressor over temperature, over current protection. h. Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy hook-up. i. Unit control board shall have on-board diagnostics and fault code display. j. Standard controls shall include anti-short cycle and low voltage protection, and permit cooling operation down to 0°F. k. l. 44 Control board shall monitor each refrigerant safety switch independently. Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss. Shall be designed with induced draft combustion with post purge logic, energy saving direct spark ignition, and redundant main gas valve. Venter wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25°F. Burners shall be of the inshot type, constructed of aluminum coated steel and contain air mixture adjustments. All gas piping shall enter the unit cabinet at a single location through either the side or curb, without any field modifications. Integrated control boards shall provide timed control of evaporator fan functioning and burner ignition. Heating section shall be provided with the following minimum protection: a. Primary and auxiliary high-temperature limit switches. b. Induced draft motor speed sensor. c. Flame roll out switch. d. Flame proving controls. ELECTRIC HEATING SECTION An electric heating section, with nickel chromium elements, shall be provided in a range of 5 thru 30 KW, offering two stages of capacity - 16 KW and above on 208/230 volt heaters and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limit control(s) and automatic reset to prevent the heating element system from operating at an excessive temperature. The heating section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating shall be wired for a single point power supply with branch circuit fusing (where required). UNIT OPERATING CHARACTERISTICS a. Unit shall be capable of starting and running at 125°F outdoor temperature, exceeding maximum load criteria of ARI Standard 210/240. The compressor, with standard controls, shall be capable of operation down to 0°F outdoor temperature. Unit shall be provided with fan time delay to prevent cold air delivery before heat exchanger warms up (Gas heat only). ELECTRICAL REQUIREMENTS All unit power wiring shall enter unit cabinet at a single factory provided location and be capable of side or bottom entry, to minimize roof penetrations and avoid unit field modifications. Separate side and bottom openings shall be provided for the control wiring. STANDARD LIMITED WARRANTIES • Compressor 5 Years • Heat Exchanger 10 Years • Electric Heat Element 5 Years • Other Parts 1 Year Unitary Products Group 036-21504-006-A-1105 OPTIONAL OUTDOOR AIR (Shall be made available by either/or): • ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER- Outdoor and return air dampers that are interlocked and positioned by a fully-modulating, spring return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor and return air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the conditioned space during normal operation. During economizer operation, a mixed-air temperature control shall modulate the outdoor and return air damper assembly to prevent the supply air temperature from dropping below 55°F. Changeover from compressor to economizer operation shall be provided by an integral electronic enthalpy control that feeds input into the basic module. The outdoor intake opening shall be covered with a rain hood that matches the exterior of the unit. Water eliminator/filters shall be provided. Simultaneous economizer/compressor operation is also possible. Dampers shall fully close on power loss. • HIGH ALTITUDE - PROPANE GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Must be used with propane conversion kit. • LOW NOX - Required to reduce the emission of nitrogen oxides below 40 nanograms per joule. • GAS PIPING - Contains 1/2” pipe nipples, fittings and gas cock (including panel assess gaskets) required for bottom gas supply connection with external shut off. • POWER EXHAUST OPTION - To work in conjunction with economizers. • ELECTRIC HEATERS • ECONOMIZER/MOTORIZED DAMPER RAIN HOOD Contains all hood panels and the hardware for assembling. • MANUAL OUTDOOR AIR DAMPER • COIL GUARD KIT - Guard for cooling coil. • HAIL GUARD • FLUE EXHAUST EXTENSION OTHER FACTORY INSTALLED OPTIONS • POWER EXHAUST OPTION - To work in conjunction with economizers. • STAINLESS STEEL HEAT EXCHANGER • STAINLESS STEEL DRAIN PAN • BOTTOM DRAIN CONNECTION • TECHNICOAT PHENOLIC COATED CONDENSER AND EVAPORATOR COIL • ELECTRONIC SINGLE ENTHALPY ECONOMIZER • DIRTY FILTER SWITCH • PHASE MONITOR • COIL GUARD • POWERED GFI CONVENIENCE OUTLET OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE • NON-POWERED GFI CONVENIENCE OUTLET • ROOF CURB - 14"and 8” high, full perimeter curb with wood nailer (shipped knocked-down). • BAS CONTROLS (Simplicity™ INTELLI- Comfort™, CPC, JOHNSON, HONEYWELL, NOVAR) • BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to relieve internal air pressure through the unit. • BAS READY ECONOMIZER (BELIMO ACTUATOR WITHOUT A CONTROLLER) • HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS • 2" PLEATED FILTERS • DISCONNECT SWITCH • SUPPLY AIR SMOKE DETECTOR • RETURN AIR SMOKE DETECTOR • • • MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air dampers are positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the outdoor air intake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potentiometer shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventilation requirements of the conditioned space during normal operation. Whenever the indoor fan motor is energized, the dampers open up to one of two pre-selected positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully close on power loss. PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required. HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude. Unitary Products Group 45 036-21504-006-A-1105 46 Unitary Products Group 036-21504-006-A-1105 Unitary Products Group 47 Subject to change without notice. Printed in U.S.A. Copyright © 2005 by Unitary Products Group. All rights reserved. Unitary Products Group 5005 York Drive 036-21504-006-A-1105 Supersedes: 036-21504-005-A-1005 Norman OK 73069
* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project
advertisement