05-2014:D

05-2014:D
Product data sheet
Sheet No.: 1.601.00 - Rev: F
December 2015
Date:
FieldQ
Contents
FieldQ Valve Actuator 3
General Overview....................................................................................................... 3
FieldQ Actuator Torque 6
Double Acting Actuators.. - Nm & lbf.in....................................................................... 6
Spring Return Actuators.. - Nm................................................................................... 7
Spring Return Actuators.. - lbf.in................................................................................. 8
FieldQ Valve Actuator Dimensions 9
Metric Actuators............... - ISO5211........................................................................... 9
Metric Actuators............... - DIN3337........................................................................ 10
Imperial Actuators............ - ISO5211......................................................................... 11
Metric Actuators............... - ISO5211 / NAMUR plate................................................ 12
Imperial Actuators............ - ISO5211 / NAMUR plate................................................ 13
Metric Actuators............... - DIN3337 / NAMUR plate............................................... 14
FieldQ Valve Actuator Options
15
Drive Inserts............................................................................................................. 15
Position Indication - Center Plate............................................................................. 16
NAMUR Plate........................................................................................................... 17
Smart - Control Modules 18
QC01: (24VDC) & QC02: (85-254VAC).................................................................... 18
QC03: IS, QC04: IS-NAMUR, Intrinsically safe........................................................ 21
QC34: FOUNDATION™ fieldbus............................................................................... 24
QC30: AS-Interface ................................................................................................ 29
QC31: DeviceNet .................................................................................................... 31
Integrated Base Control Module 34
QC11, QC12 and QC13 (IP65/NEMA4X & NI/Ex nA).............................................. 34
QC14 Intrinsic Safe.................................................................................................. 38
Integrated Control modules
41
QC41, QC42 and QC43........................................................................................... 41
Pneumatic Control.................................................................................................... 43
Position feedback..................................................................................................... 45
Control Module Options............................................................................................ 48
Hazardous area specifications................................................................................. 49
Corrosion protection................................................................................................. 50
Control Module Configuration................................................................................... 51
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.601.00 - Rev: F
December 2015
Date:
FieldQ
Contents
Integrated Control modules
52
QC54........................................................................................................................ 52
Pneumatic Control.................................................................................................... 55
Switch Point Setting................................................................................................. 57
Control Module Options............................................................................................ 58
Wiring and Quick Connectors................................................................................... 59
Diagnostics and PlantWeb Alerts............................................................................. 60
Control Module Configuration................................................................................... 62
Namur NE-107 Alarms ............................................................................................ 63
Control Module Options
64
Electrical entry options ........................................................................................... 64
Manual Control......................................................................................................... 64
Pneumatic Module
65
Pneumatic Module.................................................................................................... 65
Speed Control on FieldQ actuators.......................................................................... 67
Miscellaneous Information
69
Parts and materials Actuator and Modules............................................................... 69
Corrosion protection system..................................................................................... 71
Failure modes........................................................................................................... 72
Double acting assembly codes................................................................................. 73
Single acting (Spring Return) assembly codes........................................................ 74
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.601.01 - Rev: D, page 1 of 3
Date:
July, 2012
FieldQ
FieldQ "fully integrated"
actuator and control modules
General Overview
Description
3 Control Modules
The Control Modules contain the terminal connections for
control and feedback signals, the pilot valve for directly
controlling the Pneumatic Module and indirectly controlling
the basic actuator. Three ranges of control modules are
available:
1.
“Smart” Control Modules: These processor based
modules have additional electronics and a button board.
This button board enables start of the auto-initialization
procedure, which automatically sets the feedback switch
points for the actuator's position limits.
Included in this range of “Smart” Control Modules are the
modules with bus communication protocols like Foundation Fieldbus™, DeviceNet and ASI.
2.
The “Integrated Base” Control Modules are conventionally wired control modules which include a pilot valve
and switches for control and position feedback.
3.
The “XP” control modules are the newest range with
further integration to comply with the Explosion proof
(XP) or Flame proof (Ex d) protection methods as required by FM, CSA, ATEX or IECEx. These XP Control
Modules are conventionally wired control modules which
include easily exchangeable switch and pilot valve
cartridges, all integrated into one single housing. A new
optional feature of the XP control modules is the Fail In
Last Position control function for double acting actuators.
The FieldQ package consists of an actuator with one or two
modules, which form an integrated concept for “On/Off” valve
automation. These components are:
1 Basic actuators
The basic actuator supplies the torque, required to open
and close valves and is available in various sizes (rated
47 to 1676Nm at 5.5barg or 413 to 14874 In.lb. at 80pisg).
Double acting and spring return executions are available.
The spring return execution can be equipped with multiple
spring sets to cover a pressure range from 2 to 8 barg (30
to 120 psig).
2 Pneumatic Modules
The Pneumatic Module is the pneumatic interface between
the basic actuator and the Control Module. It contains a
booster block which is controlled by a pilot valve in the
Control Module. Optionally, the Pneumatic Module can be
equipped with integrated Speed Control throttles.
Note: “Smart”, “Integrated Base” and” Bus communication”
Control Modules require a separate pneumatic module.
FieldQ valve actuator with
“Smart” or "Integrated Base"
Control Modules
8
7
4
FieldQ valve actuator with
single piece Explosion Proof
Control Module
1
4
7
1
6
5
9
2
3
6
5
2
9
8
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
1 Basic Actuator
2 Control Module
3 Pneumatic Module
4 Limit stop screws for
“Open” and “Closed” position
5 G1/4” or 1/4”NPT air connections
6 Optional: Built-in speed
control
7 Visual position indication
8 Optional: Manual Control
9 Electrical entries
Product data sheet
Sheet No.: 1.601.01 - Rev: D, page 2 of 3
Date:
July, 2012
FieldQ
Actuator specifications:
Construction
- Ingress protection rated IP65 / NEMA4X and suitable for
indoor and outdoor installation.
Finish
- Housing:
Anodized with a polyester non-TGIC based
powder coating
Chromate treatment.
Hard anodized
- Pistons:
- Pinion:
Lubrication
- Factory lubricated for the normal life of the actuator.
Temperature
- Depends on the Control Module used. See applicable data
sheets 1.604.xxx.
European Directives
- The basic actuator complies to PED 97/23/EC, Machinery
Directive 2006/42/EC and to ATEX 94/9/EC and is marked:
II 2 GD c IIC TX
Rotation
- Factory set at 90°±0.5°. Adjustable range: -3° to +15° and
+75° to 93°
- Clockwise fail-to-close action, see sheet 1.606.04 for optional fail-to-open action (assembly codes).
- See 1.606.03 for other double acting assembly codes.
- For more info on failure modes see 1.606.02
Cycle life
- 500.000 cycles minimum
NAMUR plate
The top flange of the FieldQ actuator is equipped with a
NAMUR (VDE/VDI 3845) drilling pattern.
The addition of a NAMUR plate makes the FieldQ actuator
suitable for mounting all kinds of NAMUR compatible control
accessories like solenoids. For more info on NAMUR plate,
see sheet 1.605.03.
Pressure
- Double acting:
2 to 8 bar / 30 to 120 psi
- Spring return - with maximum spring set: 6 to 8 bar / 87 to 120 psi
- with reduced spring set: 3 to 8 bar / 43 to 120 psi
Operating media
- Dry air or inert gasses, filtered to 50 microns.
- The following Control Modules require air filtered to 5 microns: QC03, QC04 and QC34 (see applicable data sheets
1.604.xx).
- Dew point 10K below operating temperature. For subzero
applications take appropriate measures to protect the
installation.
Torque
- 40 to 1600 Nm. (300 to 11000 lbf.in ) See sheets 1.602.01,
1.602.02 or 1.602.03.
+15°
-3°
90°
±0.5
+75°
+93°
FieldQ Valve Actuator:
Rotation and adjustable
range
Actuator data
Bore
Stroke
Weight:
Double acting
Spring return
mm.
inch
mm.
inch
kg.
lb.
kg.
lb.
sec.
Operating time
Air consumption per stroke
at 1 atm (litres)
Central air chamber
Endcap air chambers
at 1 atm (cu. in.)
Central air chamber
Endcap air chambers
Q40
70
2,76
18,8
0,74
1,8
4,0
2,4
5,3
0,7
Q65
80
3,15
22,0
0,87
2,4
5,3
3,6
7,9
1,1
Q100
91
3,58
25,1
0,99
3,1
6,8
4,6
10
1,2
Q150
103
4,06
31,4
1,24
4,5
9,8
6,9
15,1
1,8
Q200
110
4,33
37,7
1,48
5,8
13
9,1
20
2,3
Q350
145
5,71
37,7
1,48
10,4
23
17
37
3,6
Q600
175
6,89
44,0
1,73
19
43
28
61
4,5
0,16
0,22
10
13
0,33
0,36
20
22
0,35
0,49
21
30
0,84
0,78
51
48
0,8
1
49
61
1,8
1,9
110
116
2,9
3,1
177
189
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Q950 Q1600
200
230
7,87
9,06
50,3
62,8
1,98
2,47
26
43
58
94
39
66
85
145
5,4
6,9
4,7
4,9
287
299
7,3
8,0
445
488
Product data sheet
Sheet No.: 1.601.01 - Rev: D, page 3 of 3
Date:
July, 2012
FieldQ
Control Modules
Pneumatic Modules
Smart and
Intergrated Base
Modules
Pneumatic Modules
- “Smart”, “Integrated Base” and” Bus communication” Control Modules require a separate pneumatic module.
- “Explosion proof” Control Modules have a build-in pneumatic booster block and do not require a separate pneumatic
module.
Explosion Proof
(XP) Modules
Functions :
Double or Single Acting (spring return)
Fail-in-Last position (Only on XP control modules)
Actuator range :
Suitable for Q40 to Q1600 (see note below).
The following version of Control modules are available:
Smart modules
- QC01 24VDC,
- QC02 85-254VAC
- QC03 Intrinsically safe
- QC04 Intrinsically safe with NAMUR feedback
Sheet nr.
1.604.01
1.604.01
1.604.011
1.604.011
Bus communication modules
- QC30 AS-Interface
- QC31 DeviceNet
- QC34 Foundation™ Fieldbus 1.604.04
1.604.09
1.604.02
Integrated Base modules
- QC11 24VDC
- QC12 115VAC
- QC13 230VAC - QC14 Intrinsically safe
1.604.06
1.604.06
1.604.06
1.604.07
Explosion proof (XP) Control modules
- QC41 24VDC
- QC42 115VAC
- QC43 230VAC
1.604.10
1.604.10
1.604.10
Enclosure :
IP65 / NEMA4X
Pneumatic connections:
G1/4” or 1/4”NPT
“Breather” function:
Standard for single acting actuators
Options :
Speed control, exhaust port filters or silencers.
Technical specifications
See sheets 1.605.xx
Options
Manual Control, IECEx, ATEX, FM or CSA approvals, glands,
plugs and connector plugs. www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.602.01 - Rev: B
February, 2012
Date:
FieldQ
FieldQ Actuator Torque
Double Acting Actuators
Actuator
type
QD
QD
QD
QD
QD
QD
QD
QD
QD
40
65
100
150
200
350
600
950
1600
Actuator
type
QD
QD
QD
QD
QD
QD
QD
QD
QD
40
65
100
150
200
350
600
950
1600
2
17
25
38
60
82
143
243
363
600
30
153
233
344
551
754
1310
2226
3323
5493
3
25
38
57
91
124
216
368
549
907
45
231
352
520
833
1140
1981
3366
5025
8307
3.5
29
45
66
106
146
253
430
642
1061
50
257
391
579
927
1269
2205
3747
5593
9245
- Nm & lbf.in
4
34
51
76
122
167
290
492
735
1214
Torque (Nm)
Supply Pressure (bar g)
4.5
5
5.5
38
42
47
58
64
71
86
95
105
137
153
168
188
209
230
326
363
400
554
617
679
828
921
1014
1368
1522
1676
6
51
77
115
183
251
436
741
1107
1829
6.5
55
84
124
199
272
473
804
1200
1983
7
59
90
134
214
293
510
866
1293
2137
8
68
104
153
245
335
583
991
1479
2444
60
309
471
696
1115
1526
2652
4507
6727
11121
Torque (lbf.in)
Supply pressure (psig)
65
70
75
335
361
387
511
550
590
755
814
873
1209
1303
1397
1655
1784
1913
2876
3100
3323
4887
5267
5647
7295
7862
8430
12059
12998
13936
80
413
630
931
1491
2041
3547
6028
8997
14874
90
465
709
1049
1680
2299
3994
6788
10132
16750
100
518
789
1166
1868
2556
4442
7548
11267
18626
120
622
948
1401
2244
3071
5337
9069
13537
22379
Double acting torque diagram
START
START
END
TORQUE
END
ROTATION
Note:
1.Emerson Process Management recommends that the valve manufacturer supply the maximum required torque values
(Including any adjustments or suggested safety factors for valve service conditions or application). Additionally, the valve
manufacturer must identify at which position(s) and direction(s) of rotation (Counter Clock Wise or Clock Wise) these maximum requirements occur.
2.If in doubt, or you require any assistance with sizing actuators, do not hesitate to contact your nearest Emerson’s
Valve Automation representative.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.602.02 - Rev: C
December 2015
Date:
FieldQ
FieldQ Actuator Torque
Spring Return Actuators
Spring set
nr.
Actuator
Size
QS 40
2
3
4
5
6
QS65
2
3
4
5
6
QS 100
2
3
4
5
6
QS 150
2
3
4
5
6
QS 200
2
3
4
5
6
QS 350
2
3
4
5
6
QS 600
2
3
4
5
6
QS 950
2
3
4
5
6
QS 1600 2
3
4
5
6
C
17
12
26
18
39
29
63
46
85
61
144
101
249
179
375
272
617
445
-
3
D
11
4
17
4
27
10
41
14
57
19
96
30
166
54
248
82
416
144
-
3.5
C
D
22
16
17
8
12
1
32
23
25
11
49
37
39
20
28
3
79
58
62
30
107 79
84
41
60
4
183 135
140 68
97
2
315 232
245 120
174
8
474 347
371 181
268 14
780 579
608 307
436 35
-
- Nm
Air Torque (Nm)
Supply pressure (bar g)
4
4.5
5
5.5
C
D
C
D
C
D
C
D
26
21
31
25
35
30
40
34
21
13
26
17
31
22
35
27
17
5
21
10
26
14
30
19
17
2
21
7
26
11
21
4
39
30
46
37
53
44
60
51
32
18
39
25
45
32
52
39
24
6
31
13
38
20
45
27
23
1
30
8
37
15
30
3
60
47
70
57
80
67
90
78
49
30
59
40
70
51
80
61
39
13
49
24
59
34
69
44
38
7
49
17
59
27
38
0
48
11
95
74 112 90 128 107 144 123
79
47
95
63 111 79 128 96
62
19
78
36
94
52 111 68
78
24
94
41
130 101 152 124 174 146 197 168
106 64 129 86 151 109 173 131
83
26 105 49 127 71 150 93
82
11 104 33 126 56
103 18
221 174 260 213 299 251 338 290
179 107 217 146 256 185 295 224
136 41 175 80 214 118 252 157
132 13 171 52 210 91
167 24
381 298 447 364 513 430 579 496
311 186 377 252 443 318 509 384
240 74 306 140 372 206 438 272
236 28 302 94 368 160
298 48
572 446 671 544 769 643 868 741
469 279 568 378 666 476 765 575
366 113 465 211 563 310 662 408
362 45 460 143 559 242
455 75
943 742 1106 905 1269 1068 1432 1231
771 470 934 633 1097 796 1260 959
599 198 762 361 925 523 1088 686
590 88 753 251 916 414
744 142
6
C
D
44
39
40
31
35
23
30
16
25
8
67
58
59
46
52
34
44
22
36
10
100 88
90
71
79
54
69
38
59
21
161 139
144 112
127 85
110 57
94
30
219 191
196 153
172 116
149 78
125 41
377 329
334 263
291 196
248 130
206 63
645 562
575 450
504 338
434 226
364 114
966 840
863 673
760 507
657 340
554 174
1594 1394
1423 1121
1251 849
1079 577
907 305
7
C
D
53
48
49
40
44
32
39
25
34
17
81
72
73
60
65
48
58
35
50
23
121 108
110 91
100 75
89
58
79
41
193 172
177 145
160 117
143 90
126 62
264 236
240 198
217 160
193 123
170 85
454 407
412 340
369 274
326 207
283 141
777 694
707 582
636 470
566 358
496 246
1163 1037
1060 870
957 704
854 537
751 371
1920 1719
1748 1447
1576 1175
1405 903
1233 630
Spring
Torque
(Nm)
E
F
13
8
20
12
26
17
33
21
40
25
21
13
32
20
42
26
53
33
63
40
29
18
44
27
58
36
73
46
88
55
48
29
72
44
95
58
119 73
143 88
65
41
98
61
131 82
163 102
196 123
116 74
174 112
232 149
289 186
347 223
195 122
292 183
389 245
487 306
584 367
290 179
434 269
579 359
724 448
869 538
474 299
711 449
947 598
1184 748
1421 897
Spring return
torque diagrams
C=
Start
Air stroke
D=
End
Torque
Rotation Counter
Clockwise
E=
Start
Spring stroke
F=
End
Torque
Rotation Clockwise
Note:
1.Emerson Process Management recommends that the valve manufacturer supply the maximum required torque values (Including any adjustments or suggested safety factors for valve service conditions or application).
Additionally, the valve manufacturer must identify at which position(s) and direction(s) of rotation (Counter Clock Wise or
Clock Wise) these maximum requirements occur.
2.If in doubt, or you require any assistance with sizing actuators, do not hesitate to contact your nearest Emerson’s
Valve Automation representative.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.602.03 - Rev: C
December 2015
Date:
FieldQ
FieldQ Actuator Torque
Spring Return Actuators
Spring set
nr.
Actuator
Size
QS 40
2
3
4
5
6
QS 65
2
3
4
5
6
QS 100
2
3
4
5
6
QS 150
2
3
4
5
6
QS 200
2
3
4
5
6
QS 350
2
3
4
5
6
QS 600
2
3
4
5
6
QS 950
2
3
4
5
6
QS 1600 2
3
4
5
6
C
133
196
303
211
485
656
1105
1920
2898
4765
-
40
D
82
117
192
44
297
406
684
1183
1777
2988
-
C
243
201
159
364
297
230
552
460
367
884
735
587
1201
994
786
2053
1675
1297
3531
2909
2287
5303
4391
3479
8741
7220
5699
-
60
D
193
125
58
285
178
71
441
293
144
696
453
210
952
619
287
1632
1043
454
2794
1804
814
4182
2709
1236
6964
4554
2144
-
- lbf.in
Air Torque (lbf.in)
Supply pressure (psig)
80
90
C
D
C
D
354
303
409
358
312
236
367
291
270
169
325
224
227
101
283
156
241
89
533
454
617
538
466
347
550
431
398
240
482
324
331
133
415
217
348
110
801
690
926
814
709
541
833
666
616
393
740
518
523
245
648
369
430
96
555
221
1283 1094 1482 1294
1134
852 1333 1051
985
609
1185
808
837
366 1036 565
887
322
1747 1497 2020 1770
1539 1165 1812 1438
1332 832 1604 1105
1124
500 1396 772
1189
440
3001 2580 3475 3054
2623 1991 3097 2465
2245 1402 2719 1877
1866 814 2340 1288
1962 699
5142 4405 5947 5211
4520 3415 5325 4221
3898 2425 4703 3230
3276 1434 4081 2240
3459 1250
7708 6587 8910 7789
6796 5114 7998 6316
5883 3641 7086 4844
4971 2168 6174 3371
5262 1898
12716 10939 14704 12927
11195 8530 13183 10517
9675 6120 11662 8108
8154 3711 10141 5698
8621 3289
100
C
D
464
414
422
346
380
279
338
212
296
144
701
622
634
515
567
408
499
301
432
194
1050 939
957
790
865
642
772
494
679
345
1681 1493
1533 1250
1384 1007
1235 764
1087 522
2293 2043
2085 1710
1877 1378
1669 1045
1462 713
3949 3528
3571 2939
3193 2351
2814 1762
2436 1173
6753 6016
6131 5026
5509 4036
4887 3046
4265 2055
10113 8992
9201 7519
8288 6046
7376 4573
6464 3100
16692 14915
15171 12505
13650 10096
12129 7686
10608 5277
120
C
D
575
524
533
457
491
390
448
322
406
255
870
790
802
683
735
576
668
470
601
363
1299 1188
1206 1039
1114
891
1021 743
928
594
2080 1892
1931 1649
1783 1406
1634 1163
1485 920
2838 2589
2631 2256
2423 1923
2215 1591
2007 1258
4897 4476
4519 3887
4141 3299
3762 2710
3384 2121
8364 7628
7742 6637
7120 5647
6498 4657
5876 3666
12518 11396
11606 9924
10693 8451
9781 6978
8869 5505
20668 18890
19147 16481
17626 14071
16105 11662
14584 9252
Spring
Torque
(lbf.in)
E
F
117
73
176
110
234
146
293
183
351
220
186
117
279
176
372
234
465
292
558
351
258
161
387
242
516
323
646
403
775
484
423
259
634
388
845
517
1056 647
1268 776
579
362
868
542
1158
723
1447 904
1736 1085
1025 658
1537 987
2049 1317
2561 1646
3074 1975
1723 1082
2585 1624
3446 2165
4308 2706
5169 3247
2563 1587
3844 2381
5125 3175
6407 3968
7688 4762
4193 2646
6289 3970
8385 5293
10481 6616
12578 7939
Spring return
torque diagrams
C=
Start
Air stroke
D=
End
Torque
Rotation Counter
Clockwise
E=
Start
Spring stroke
F=
End
Torque
Rotation Clockwise
Note:
1.Emerson Process Management recommends that the valve manufacturer supply the maximum required torque values (Including any adjustments or suggested safety factors for valve service conditions or application).
Additionally, the valve manufacturer must identify at which position(s) and direction(s) of rotation (Counter Clock Wise or
Clock Wise) these maximum requirements occur.
2.If in doubt, or you require any assistance with sizing actuators, do not hesitate to contact your nearest Emerson’s
Valve Automation representative.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.603.01 - Rev: D
June, 2012
Date:
FieldQ
FieldQ Valve Actuator Dimensions
Metric Actuators - ISO5211
T
M5x8
limit stops on
Q40 & Q65
30
P2
P1
Pinion drive
details
Ra
Ps
N±0.5
M1 M2
BSP
Rb
K
D
4
G1/4"
C'
Ra
C
Ps
BSP
Rb
H
145
203
Note:
1.Dimensions are metric (mm).
2.The limit stop screws on the Q40 and
Q65 are on the opposite side to those
on the larger actuators.
3.Top flange according VDI/VDE 3845
(NAMUR)
I
A (QD)
B (QS)
145 = Integrated Smart Module
203 = Integrated Base Module
W
V1
W1
V
O
P
+0.5
-0
S
R
Flange for
Q40 - Q950
280
234.6
97.2
M16
x25
*) Four holes of the F25
ISO Drilling pattern
132
Flange for
Q1600
FieldQ™ actuator models
Dim
in mm.
Q40
Q65
Q100
Q150
Q200
Q 350
Q600
Q950
Q1600
A QD
145
168
181
217
242
262
327
366
447
B QS
202
249
254
311
358
391
419
460
568
C
104
117
141
150
161
191
245
276
337
C’
137
150
175
184
194
225
289
319
380
D
20
20
20
20
20
20
30
30
30
E
56
56
56
65
66
66
84
88
95
F
16
18
18
22
30
30
35
35
45
G
9,5
9
11
10
9
10
19,5
19
28,5
H
90
102
115
129
135
177
209
234
268
I
75
81
88
97
99
119
134
147
164
J
40
40
34
46
45
46
53
40
70
K
33
33
38
55
55
55
68
75
95
M1
34.5
34.5
34.5
50
50
50
52
64
82
M2
27
37
37
N
1
1
1.5
1.0
1.5
1.5
1.5
1.5
1.5
O max. 14.11
14.11
19.13
19.13
22.13
27.13
27.13
36.16
46.16
O min.
14.00
14.00
19.00
19.00
22.00
27.00
27.00
36.00
46.00
P
18.1
18.1
25.2
25.2
28.2
36.2
36.2
48.2
60.2
P1
18.1
18.1
23.1
28.5
32.1
32.1
36.5
48.5
60.5
P2
25.2
36.2
36.2
R
65
70
70
90
90
114
124
130
154
S
65
70
70
90
90
114
124
142
280
T
80
80
80
80
80
80
130
130
130
PCD F05/F07 F05/F07 F05/F07 F07/F10 F07/F10 F07/F10 F10/F12 F10/F14 F16/F25*
V
50
50
50
70
70
70
102
102
165
V1
70
70
70
102
102
102
125
140
W
M6x10 M6x10 M6x10 M8x13 M8x13 M8x13 M10x16 M10x16 M20x30
W1
M8x13 M8x13 M8x13 M10x16 M10x16 M10x16 M12x20 M16x25
-
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.603.02 - Rev: D
June, 2012
Date:
FieldQ
FieldQ Valve Actuator Dimensions
Metric Actuators - DIN3337
T
M5x8
limit stops on
Q40 & Q65
30
P2
P1
Pinion drive details
and center plate
dimensions
Ra
Ps
N ±0.5
M1 M2
BSP
Rb
Max. 5
øK
øK1
D
4
G1/4"
C'
Ra
C
Ps
BSP
Rb
Note:
1.Dimensions are metric (mm).
2.The limit stop screws on the Q40 and
Q65 are on the opposite side to those
on the larger actuators.
3.Top flange according VDI/VDE 3845
(NAMUR)
H
145
I
203
A (QD)
B (QS)
145 = Integrated Smart Module
203 = Integrated Base Module
V
W
O
P
S
+0.5
-0
R
Flange for
Q40 - Q950
280
234.6
97.2
M16
x25
*) Four holes of the F25
Drilling pattern
132
Flange for
Q1600
Dim
in mm.
A QD
B QS
C
C’
D
E
F
G
H
I
J
K
K1
M1
M2
N
O max.
O min.
P
P1
P2
Q
R
S
T
PCD
V
W
Q40
145
202
104
137
20
56
16
9,5
86
128
40
33
32
34.5
1
14.11
14.00
18.1
18.1
35
65
65
80
F05
50
M6x10
Q65
168
249
116,5
150,4
20
56
18
14
102
141,8
40
33
32
34.5
1
14.11
14.00
18.1
18.1
70
70
80
50
F05
50
M6x10
K1’
Q’
PCD
V’
W’
40
55
F07
70
M8x13
40
35
F07
70
M8x13
FieldQ™ actuator models
Q150
Q200
Q350
Q600
Q950
Q1600
217
242
262
327
366
447
311
358
391
419
460
568
150
161
191
245
276
337
184
194
225
289
319
380
20
20
20
30
30
30
65
66
66
84
88
95
22
30
30
35
35
45
10
9
10
19,5
19
28,5
129
128
173
207
231
265
97
149
171
187
200
217
46
45
46
53
40
70
55
55
55
68
75
95
50
54
54
68
75
95
50
50
50
52
64
82
37
37
1
1.5
1.5
1.5
1.5
1.5
17.13
22.13
22.13
27.13
36.16
46.16
17.00
22.00
22.00
27.00
36.00
46.00
22.2
28.2
28.2
36.2
48.2
60.2
28.5
32.1
32.1
36.5
48.5
60.5
36,2
36,2
55
70
70
85
100
130
90
90
114
124
130
154
90
90
114
124
142
280
80
80
80
130
130
130
F07
F10
F10
F12
F14
F16
70
102
102
125
140
165
M8x13 M10x16 M10x16 M12x20 M16x25 M20x30
Optional dimensions
32
54
50
50
35
70
55
55
F05
F10
F07
F07
F10
F10
F25*
50
102
70
70
102
102
M6x10 M10x16 M8x13 M8x13 M10x16 M10x16
Q100
181
254
141
175
20
56
18
11
108
141
34
38
40
34.5
27
1.5
17.13
17.00
22.2
23.1
25,2
55
70
70
80
F07
70
M8x13
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.603.04 - Rev: D
June, 2012
Date:
FieldQ
FieldQ Valve Actuator Dimensions
Imperial Actuators - ISO5211
T
10-24x .31
limit stops on
Q40 & Q65
1.18
P2
P1
Pinion drive
details
N
±0.02
M1 M2
K
D
0.16
1/4"NPT
C'
Ra
C
Ps
BSP
Rb
H
5.71
I
7.99
A (QD)
B (QS)
5.71 = Integrated Smart Module
7.99 = Integrated Base Module
W
V1
W1
V
O
P +0.02
-0
Note:
1.Dimensions are in inches.
2.The limit stop screws on the Q40 and
Q65 are on the opposite side to those
on the larger actuators.
3.Top flange according VDI/VDE 3845
(NAMUR)
S
R
Flange for
Q40 - Q950
11.02
9.23
3.83
5/8"11x.98
*) Four holes of the F25
ISO Drilling pattern
5.20
Flange for
Q1600
Dim. in
inches
Q40
Q65
Q100
A QD
5.71
6.61
7.13
B QS
7.94
9.79
9.99
C
4.09
4.59
5.55
C’
5.39
5.92
6.89
D
0.79
0.79
0.79
E
2.20
2.20
2.20
F
0.63
0.71
0.71
G
0.37
0.35
0.43
H
3.54
4.02
4.53
I
2.95
3.19
3.46
J
1.56
1.56
1.32
K
1.30
1.30
1.50
M1
1.36
1.36
1.36
M2
1.06
N
0.04
0.04
0.06
O max. 0.556
0.556
0.753
O min.
0.551
0.551
0.748
P
0.71
0.71
0.99
P1
0.71
0.71
0.91
P2
0.99
R
2.56
2.76
2.76
S
2.56
2.76
2.76
T
3.15
3.15
3.15
PCD F05/F07 F05/F07 F05/F07
V
1.969
1.969
1.969
V1
2.756
2.756
2.756
1/4”1/4”1/4”W
20x.39 20x.39 20x.39
5/16”5/16”5/16”W1
18x.39 18x.39 18x.39
FieldQ™ actuator models
Q150
Q200
Q 350
Q600
Q950
Q1600
8.54
9.54
10.31
12.87
14.40
17.58
12.24
14.09
15.38
16.50
18.09
22.34
5.91
6.34
7.52
9.65
10.87
13.27
7.24
7.64
8.86
11.38
12.56
14.96
0.79
0.79
0.79
1.18
1.18
1.18
2.56
2.60
2.60
3.31
3.46
3.74
0.87
1.18
1.18
1.38
1.38
1.77
0.39
0.35
0.39
0.77
0.75
1.12
5.08
5.31
6.97
8.23
9.21
10.55
3.82
3.90
4.69
5.28
5.79
6.46
1.81
1.78
1.81
2.08
1.58
2.75
2.17
2.17
2.17
2.68
2.95
3.74
1.97
1.97
1.97
2.05
2.52
3.23
1.46
1.46
0.04
0.06
0.06
0.06
0.06
0.06
0.753
0.871
1.068
1.068
1.424
1.817
0.748
0.866
1.063
1.063
1.417
1.811
0.99
1.11
1.43
1.43
1.90
2.37
1.12
1.26
1.26
1.44
1.91
2.38
1.43
1.43
3.54
3.54
4.49
4.88
5.12
6.06
3.54
3.54
4.49
4.88
5.59
11.02
3.15
3.15
3.15
5.12
5.12
5.12
F07/F10 F07/F10 F07/F10 F10/F12 F10/F14 F16/F25*
2.756
2.756
2.756
4.016
4.016
6.496
4.016
4.016
4.016
4.921
5.512
5/16”5/16”5/16”3/8”3/8”3/4”18x.39 18x.39 18x.39 16x.63 16x.63 10x1.14
3/8”3/8”3/8”1/2”5/8”16x.63 16x.63 16x.63 13x.79 11x.98
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.603.05 - Rev: C
June, 2012
Date:
FieldQ
FieldQ Valve Actuator Dimensions
Metric Actuators
M6x12
- ISO5211 / NAMUR plate
M5x8
T
E
30
F
2x 1/4"BSP
4
4
90
G
32
D
M5x8
D
4
24
60
P2
P1
C'
C
H
A (QD)
B (QS)
W1
O
P
+0.5
-0
R
S
280
234.6
92.7
K
I
W
V
±0.5
M1 M2
J
V1
N
132
M16
x 25
Note:
1.Dimensions are in mm.
2.The limit stop screws on the Q40 and Q65
are on the opposite side to those on the
larger actuators.
Dim
FieldQ™ actuator models
in mm.
Q40
Q65
Q100
Q150
Q200
Q 350
Q600
Q950
Q1600
A QD
145
168
181
217
242
262
327
366
447
B QS
202
249
254
311
358
391
419
460
568
C
104
117
141
150
161
191
245
276
337
C’
137
150
175
184
194
225
289
319
380
D
20
20
20
20
20
20
30
30
30
E
56
56
56
65
66
66
84
88
95
F
16
18
18
22
30
30
35
35
45
G
9,5
9
11
10
9
10
19,5
19
28,5
H
90
102
115
129
135
177
209
234
268
I
75
81
88
97
99
119
134
147
164
J
40
40
34
46
45
46
53
40
70
K
33
33
38
55
55
55
68
75
95
M1
34.5
34.5
34.5
50
50
50
52
64
82
M2
27
37
37
N
1
1
1.5
1.0
1.5
1.5
1.5
1.5
1.5
O max. 14.11
14.11
19.13
19.13
22.13
27.13
27.13
36.16
46.16
O min.
14.00
14.00
19.00
19.00
22.00
27.00
27.00
36.00
46.00
P
18.1
18.1
25.2
25.2
28.2
36.2
36.2
48.2
60.2
P1
18.1
18.1
23.1
28.5
32.1
32.1
36.5
48.5
60.5
P2
25.2
36.2
36.2
R
65
70
70
90
90
114
124
130
154
S
65
70
70
90
90
114
124
142
280
T
80
80
80
80
80
80
130
130
130
PCD F05/F07 F05/F07 F05/F07 F07/F10 F07/F10 F07/F10 F10/F12 F10/F14 F16/F25*
V
50
50
50
70
70
70
102
102
165
V1
70
70
70
102
102
102
125
140
M6x
M6x
M6x
M8x
M8x
M8x
M10x
M10x
M20x
W
10
10
10
13
13
13
16
16
30
M8x
M8x
M8x
M10x
M10x
M10x
M12x
M16x
W1
13
13
13
16
16
16
20
25
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.603.06 - Rev: C
June, 2012
Date:
FieldQ
FieldQ Valve Actuator Dimensions
Imperial Actuators
M6x0.47"
- ISO5211 / NAMUR plate
10-24x0.31"
T
E
1.18"
F
0.16"
0.16"
G
2x 1/4"NPT
D
3.56" 1.26"
10-24x0.31"
0.94"
2.36"
D
0.16"
P2
P1
C'
C
H
A (QD)
B (QS)
W1
O R
P
+0.02"
S
11.02"
9.23"
3.82"
K
I
W
V
±0.02
M1 M2
J
V1
N
5.19"
5/8"-11
x.98
Note:
1.Dimensions are in inches.
2.The limit stop screws on the Q40 and
Q65 are on the opposite side to those on
the larger actuators.
Dim. in
inches
Q40
Q65
Q100
A QD
5.71
6.61
7.13
B QS
7.94
9.79
9.99
C
4.09
4.59
5.55
C’
5.39
5.92
6.89
D
0.79
0.79
0.79
E
2.20
2.20
2.20
F
0.63
0.71
0.71
G
0.37
0.35
0.43
H
3.54
4.02
4.53
I
2.95
3.19
3.46
J
1.56
1.56
1.32
K
1.30
1.30
1.50
M1
1.36
1.36
1.36
M2
1.06
N
0.04
0.04
0.06
O max. 0.556
0.556
0.753
O min.
0.551
0.551
0.748
P
0.71
0.71
0.99
P1
0.71
0.71
0.91
P2
0.99
R
2.56
2.76
2.76
S
2.56
2.76
2.76
T
3.15
3.15
3.15
PCD F05/F07 F05/F07 F05/F07
V
1.969
1.969
1.969
V1
2.756
2.756
2.756
1/4”1/4”1/4”W
20x.39 20x.39 20x.39
5/16”5/16”5/16”W1
18x.39 18x.39 18x.39
FieldQ™ actuator models
Q150
Q200
Q350
Q600
Q950
Q1600
8.54
9.54
10.31
12.87
14.40
17.58
12.24
14.09
15.38
16.50
18.09
22.34
5.91
6.34
7.52
9.65
10.87
13.27
7.24
7.64
8.86
11.38
12.56
14.96
0.79
0.79
0.79
1.18
1.18
1.18
2.56
2.60
2.60
3.31
3.46
3.74
0.87
1.18
1.18
1.38
1.38
1.77
0.39
0.35
0.39
0.77
0.75
1.12
5.08
5.31
6.97
8.23
9.21
10.55
3.82
3.90
4.69
5.28
5.79
6.46
1.81
1.78
1.81
2.08
1.58
2.75
2.17
2.17
2.17
2.68
2.95
3.74
1.97
1.97
1.97
2.05
2.52
3.23
1.46
1.46
0.04
0.06
0.06
0.06
0.06
0.06
0.753
0.871
1.068
1.068
1.424
1.817
0.748
0.866
1.063
1.063
1.417
1.811
0.99
1.11
1.43
1.43
1.90
2.37
1.12
1.26
1.26
1.44
1.91
2.38
1.43
1.43
3.54
3.54
4.49
4.88
5.12
6.06
3.54
3.54
4.49
4.88
5.59
11.02
3.15
3.15
3.15
5.12
5.12
5.12
F07/F10 F07/F10 F07/F10 F10/F12 F10/F14 F16/F25*
2.756
2.756
2.756
4.016
4.016
6.496
4.016
4.016
4.016
4.921
5.512
5/16”5/16”5/16”3/8”3/8”3/4”18x.39 18x.39 18x.39 16x.63 16x.63 10x1.14
3/8”3/8”3/8”1/2”5/8”16x.63 16x.63 16x.63 13x.79 11x.98
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.603.07 - Rev: C
June, 2012
Date:
FieldQ
FieldQ Valve Actuator Dimensions
Metric Actuators
- DIN3337 / NAMUR plate
E
M6x12
F
M5x8
T
30
2x 1/4"BSP
4
4
32
G
D
M5x8
24
60
D
4
P2
P1
C'
C
M1 M2
J
H
A (QD)
B (QS)
V
W
P
+0.5
-0
R
S
280
234.6
M16
x25
Max. 5
I
O
97.2
N ±0.5
132
Dim
in mm.
A QD
B QS
C
C’
D
E
F
G
H
I
J
K
K1
M1
M2
N
O max.
O min.
P
P1
P2
Q
R
S
T
PCD
V
W
K1’
Q’
PCD
V’
W’
Q40
145
202
104
137
20
56
16
9,5
86
128
40
33
32
34.5
1
14.11
14.00
18.1
18.1
35
65
65
80
F05
50
M6x
10
Q65
168
249
116,5
150,4
20
56
18
14
102
141,8
40
33
32
34.5
1
14.11
14.00
18.1
18.1
70
70
80
50
F05
50
M6x
10
Q100
181
254
141
175
20
56
18
11
108
141
34
38
40
34.5
27
1.5
17.13
17.00
22.2
23.1
25.2
55
70
70
80
F07
70
M8x
13
40
55
F07
70
M8x
13
40
35
F07
70
M8x
13
32
35
F05
50
M6x
10
øK
øK1
FieldQ™ actuator models
Q150
Q200
Q350
217
242
262
311
358
391
150
161
191
184
194
225
20
20
20
65
66
66
22
30
30
10
9
10
129
128
173
97
149
171
46
45
46
55
55
55
50
54
54
50
50
50
37
37
1
1.5
1.5
17.13
22.13
22.13
17.00
22.00
22.00
22.2
28.2
28.2
28.5
32.1
32.1
36.2
36.2
55
70
70
90
90
114
90
90
114
80
80
80
F07
F10
F10
70
102
102
M8x
M10x
M10x
13
16
16
Optional dimensions
54
50
50
70
55
55
F10
F07
F07
102
70
70
M10x
M8x
M8x
16
13
13
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Q600
327
419
245
289
30
84
35
19,5
207
187
53
68
68
52
1.5
27.13
27.00
36.2
36.5
85
124
124
130
F12
125
M12x
20
Q950
366
460
276
319
30
88
35
19
231
200
40
75
75
64
1.5
36.16
36.00
48.2
48.5
100
130
142
130
F14
140
M16x
25
Q1600
447
568
337
380
30
95
45
28,5
265
217
70
95
95
82
1.5
46.16
46.00
60.2
60.5
130
154
280
130
F16
165
M20x
30
F10
102
M10x
16
F10
102
M10x
16
F25*
-
Product data sheet
Sheet No.: 1.603.03 - Rev: B
September, 2006
Date:
FieldQ
FieldQ Valve Actuator Options
Drive Inserts
Description
All actuators are fitted with drive inserts. This enables actuators to be directly mounted onto suitable valves and eliminates the need for a bracket and coupling type mounting kit.
The use of direct mounts significantly cuts the cost of the
valve/actuator assembly.
Standard actuators are fitted with square drive inserts in
accordance with ISO 5211 (or DIN 3337), but a wide variety
of other inserts are also available. Special inserts may have
oversize or undersize squares, double-D and shaft key way
forms.
Standard available
insert shapes
Drive inserts can be supplied on factory built actuators or as
loose items and are easily replaceable at distributor or end
user level.
Where direct mounts are not possible, for instance on valves
with exposed gland packing, the use of inserts often simplifies
the design of the mounting kit.
Material :
Finish:
Optional available
insert shapes
D
Max.
sq
Max.
M1
Aluminum alloy
Anodized
Insert mounting
Insert mounting
acc. ISO 5211
acc. DIN 3337
Ø P2
Ø P2
Ø P1
Ø P1
M2
D
Max.
Q40
mm. inch
ISO5211
DIN3337
M1
M2
P1
P2
Sq max.
D max.
Q65
mm. inch
14
14
0.551
0.551
14
14
0.551
0.551
10
12
-
0.394
0.472
-
10
12
-
0.394
0.472
-
34.5
18.1
16
21
1.36
0.71
0.630
0.827
34.5
21.2
16
21
1.36
0.83
0.630
0.827
M1
M2
Center
plate
Inserts with inner-square-dimensions per actuator type
Q100
Q150
Q200
Q350
Q600
Q950
Q1600
mm. inch mm. inch mm. inch mm. inch mm. inch mm. inch mm. inch
Standard inserts dimensions
19 0.748 19 0.748 22 0.866 27 1.063 27 1.063 36 1.417 46 1.811
17 0.669 17 0.669 22 0.866 22 0.866 27 1.063 36 1.417 46 1.811
Optional insert dimensions
12 0.472 14 0.551 14 0.551 14 0.551 14 0.551 22 0.866
14 0.551 16 0.630 16 0.630 16 0.630 16 0.630
16 0.630 22 0.866 17 0.669 17 0.669 17 0.669
24 0.945 19 0.748 19 0.748 19 0.748
27 1.063 24 0.945 24 0.945 24 0.945
Maximum insert dimensions
34.5 1.36
50
1.97
50
1.97
50
1.97
50
1.97
65
2.56
81
3.19
27
1.06 37.0 1.46 37.0 1.46 37.0 1.46
23.5 0.93 28.5 1.12 32.2 1.27 32.2 1.27 36.8 1.45 48.3 1.90 60.5 2.38
25.2 0.99 36.2 1.43 36.3 1.43 36.3 1.43
19 0.748 27.0 1.063 27.0 1.063 27.0 1.063 27.0 1.063 36.0 1.417 46.0 1.811
23.6 0.929 33.6 1.323 33.6 1.323 33.6 1.323 33.6 1.323 45.0 1.772 60.0 2.362
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.606.05 - Rev: A
April 2006
Date:
FieldQ
FieldQ Valve Actuator Options
Position Indication - Center Plate
Visual position indicator
“In line”
FieldQ valve actuators can be equipped with a large visual
position indicator which allows clear indication of the valves
position at almost any position.
The FieldQ indicator is designed for position indication of
actuators mounted “in line” with the pipe line and mounted
“cross line” with the pipe line. To do this the inner part can be
removed, turned 90° and pushed back in place.
When supplied, the position indicator will be mounted “in
line” as standard. See data sheet 1.606.04 for other indicator
mounting options.
Specifications:
Material disk
:
Material arrow :
“Cross line”
Nylon PA6, Black
Nylon PA6, Yellow
Center plate for DIN3337 applications
FieldQ actuators can be equipped with a centre plate which
takes care that actuator and valve (or valve mounting kit) are
aligned when mounted. For most of the actuator sizes two
center plates are available.
Specifications:
Material plate
:
Nylon PA6, Black
Center plate
FieldQ™ actuator models
Q40
Q65
Q100 Q200 Q350 Q600 Q950 Q1600
Std
F05
F05
F07
F10
F10
F12
F14
F16
Option
F07
F07
F05
F07
F07
-/-
-/-
-/-
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.605.03 - Rev: C
May, 2006
Date:
FieldQ
FieldQ Valve Actuator Options
NAMUR Plate
Description
The top flange of the FieldQ actuator is standard equipped
with a NAMUR drilling pattern. The addition of a NAMUR
adaptation plate makes the FieldQ actuator suitable for
mounting all kinds of NAMUR compatible control and feedback accessories like solenoids, switch boxes or positioners.
Backwards compatibility
Where the FieldQ is meant to be a integrated concept for
valve automation, there are a number of reasons for also having NAMUR interfaces:
Emergency repairs
- When the Control Module requires immediate repair and
the process can only be stopped for a limited time, it would
be easy to mount standard available NAMUR accessories.
Future updates
- When a plant is not yet ready for digital (bus) communication, but will be upgraded in the (near) future towards this
technology, it is easy to change from NAMUR accessories
to a FieldQ with bus communication.
Available equipment
- NAMUR compatible accessories are easy to acquire. Many
suppliers offer accessories that can be fitted to NAMUR
actuator interfaces.
Q40 - Q350 = 80 (3.15")
Q600 - Q1600 = 130 (5.12")
Construction
The NAMUR adaptation plate is fitted in front of the actuator
part of the FieldQ and replaces in fact the Pneumatic Module.
Specifications:
Material
:Aluminum
Air connection : 1/4” BSP or 1/4” NPT
Finish
: Housing :Anodized with a polyester nonTGIC based powder coating
:Pistons :Chromatized
Fasteners
: Stainless Steel
Seals
: Nitrile Rubber O-rings
Optional Temperature ranges
Special selected O-ring seals and grease makes it possible
to utilize the FieldQ actuator, with NAMUR plate, for various
temperature ranges. Three temperature ranges are available:
-
-
-
Option code ST:80°C (176°F) / -20°C ( -4°F)
O-ring seals
:Nitrile rubber
Grease
:Castrol LMX
Option code HT:120°C(248°F) / -20°C ( -4°F)
O-ring seals
:Fluoro rubber (FPM) Viton®
Grease
:Castrol LMX
Option code LT:80°C (176°F) / -40°C (-40°F)
O-ring seals
:Silicone MVQ 70
Grease
:Castrol Optitemp TT1
Note:
FieldQ actuators fitted with Pneumatic Modules and Control
Modules are not available for high temperature or low temperature applications.
Detailed Dimensions
See data sheets 1.603.05, 1.603.06 and 1.603.07.
30
(1.18")
90.5 (3.56")
2x 1/4"BSP (1/4"NPT)
32
(1.26")
M5x8
(10-24x0.31")
24 (0.94")
60 (2.36")
28 (1.10")
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.01 - Rev: G
October, 2008
Date:
Page 1 of 3
FieldQ
Smart - Control Modules
QC01: (24VDC) & QC02: (85-254VAC/VDC)
Description:
These FieldQ QC01 and QC02 Smart Control Modules offer
an integrated concept for “On/Off” valve automation. Its
compact and robust construction incorporates IPT technology
with auto-initialization for easy setting of feedback switches.
Construction:
The Control Module is mounted at the side of the Pneumatic
Module in front of the basic actuator housing. Inside are
terminals available for connecting control and feedback
wiring. Two cable entries are available for this purpose.
Features:
- Supports both single and double acting actuators.
- One entry for all wiring (control and feedback).
- IPT-technology (Intelligent Position Tracking).
- Automatic initialization for easy setup of the actuator.
Pressing 4 seconds simultaneously the “Open” and
“Closed” reassignment buttons starts auto-initialization procedure and sets automatically the feedback limit switches.
- Readjustable or Reversible position feedback using the
reassignment buttons.
- Three indication LED’s for “Status”, “Open” and “Closed”
position. Status LED indicates:
Initialization procedure running
Blinking
Successful initialization procedure
LED is on
No or failed initialization
Flashing
- Control Module is easily plugged in the Pneumatic
Module.
- Modular functionality for easy update towards present and
future bus systems.
- The power supply and all inputs and outputs are
galvanic isolated which offers greater flexibility for systems connection.
General Specifications:
Material housing
:Aluminium alloy
Cable entries
:2x M20x1.5 or 2x 1/2”NPT
Electrical connections :Internal terminal strip.
Enclosure
:IP65 / NEMA 4X
Finish
:Polyester non-TGIC based powder
coating.
Operating media
:Air or inert gasses, filtered at 50
micron
Temperature
:-20° to +80°C / -4° to 176°F
Dimensions
:See data sheet :
1.603.01 - metric
1.603.04 - imperial/UNC
1.603.02 - DIN 3337
FieldQ Button
board
Closed reassignment button
Closed LED
Push
4 seconds
Status LED
Open LED
Open reassignment button
Status LED:
on
off
LED = Flashing
on
off
LED = Blinking
Time
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.01 - Rev: G - Page 2 of 3
October, 2008
Date:
FieldQ
Smart - Control Modules
QC01: (24VDC) & QC02: (85-254VAC/VDC)
Options:
Manual Control
Can be added as kit or factory option in 2 versions,
“Push button” or a “Push and lock” button.
Glands and plugs
FieldQ Control Modules QC01 or QC02 can be shipped with
plastic or metal glands (M20x1.5 or 1/2”NPT) and rated IP65/
NEMA4X or higher.
Hazardous area modules:
- Non-Incendive of Non-Sparking
Control Modules QC01 and QC02 are available with optional Non-Incendive of Non-Sparking approvals as listed
below:
-IECEx
:ExnA II T4
:Ex tD A22 T90°C / IP65
:Certificate : KEM 07.0046X
-ATEX
: II 3 G Ex nA II T4
: II 3 D Ex tD A22 T90°C / IP65
:Certificate : KEMA 02ATEX1258X
-FM
:Non-Incendive, Class I, II, III, Div.2,
Group ABCDFG T4, Type 4X/IP65
:Class I, Zone 2, IIC T4
-CSA
:Non Incendive: Class I, II, III, Div.2,
Groups ABCDFG, T4
:Ex nA II T4 (Class I, Zone 2)
:Certificate: 1477696
Ambient temperature:
T4 @ Ta = : QC01: -20°C…+75°C (-4°F…167°F)
: QC02: -20°C…+73°C (-4°F…163°F)
- Intrinsically safe:
For information about intrinsically safe Control Modules,
see 1.604.011
- Short circuit monitoring and line break detection
For information about Control Modules with short circuit
monitoring and line break detection (IEC 60947 part 5-6,
NAMUR switch characteristics), see 1.604.011
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.01 - Rev: G - Page 3 of 3
October, 2008
Date:
FieldQ
Wiring & Electrical Specifications QC01 & QC 02
QC01
Field wiring
1-2Feedback 2
0-30 VDC
0.5 Amax. 15VAmax.
3-4Feedback 1
0-30 VDC
5-6Control supply voltage
24 VDC +/- 15%
7-8Power supply voltage
24 VDC +/- 15%
Unit wiring
0.5 Amax. 15VAmax.
+
1
2
3
4
5
6
7
8
QC01,24VDC electric connections, separate circuits
Field wiring
1-2Feedback 2,
0.5 Amax. 15VAmax.
3-4Feedback 1
0.5 Amax. 15VAmax.
Unit wiring
5-6Control
7-8Power supply voltage
24 VDC +/- 15%
+
1
2
3
4
5
6
7
8
Electrical data QC01 : 24VDC Power supply input:
Voltage
24 VDC (±15%)
Maximum current
125 mA
Power (nominal)
2.5 W
Control signal input:
Voltage
24 VDC (±15%)
Maximum current
5 mA
Contacts
Potential free
Feedback switches output:
Voltage
0-30 VDC
Current DC
500 mA (maximum)
1 mA (advised minimum)
Resistance (nom.)
0.5 Ohm (On state)
Maximum power
15 W
Electric contacts
Potential free
Polarity:
Dependent
Power supply
Independent
Control signal + feedback switches.
- For Non-Incendive (Cl. I Div2) or Non-Sparking (Zone 2) hazardous area applications, see Installation Guide : DOC.IG.QC01.1
QC01,24VDC electric connections, common “-”
QC02
1-2Power supply voltage
3-4Control supply voltage
5-6Feedback 1
7-8Feedback 2
Field wiring Unit wiring
85-254 VAC/VDC
85-254 VAC/VDC
85-254 VAC/VDC
85-254 VAC/VDC
0-254VAC/VDC
0-254VAC/VDC
150mAmax. 15VAmax.
150mAmax. 15VAmax.
0-254VAC/VDC
0-254VAC/VDC
150mAmax. 15VAmax.
150mAmax. 15VAmax.
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
N (-)
N (-)
L (+)
L (+)
QC02,85-254 VAC/VDC electric connections, separate circuits
Field wiring Unit wiring
1-2Power supply voltage
3-4Control supply voltage
85-254 VAC/VDC
85-254 VAC/VDC
5-6Feedback 1
7-8Feedback 2
150mAmax. 15VAmax.
150mAmax. 15VAmax.
150mAmax. 15VAmax.
150mAmax. 15VAmax.
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
N (-)
N (-)
L (+)
L (+)
Electrical data QC02 - 85-254 VAC/VDC
Power supply input:
Voltage
85-254 VAC/VDC (rated mains 95-230V)
50/60Hz
60 mA
2.8 W
Maximum current (*
Power (nominal)
Control signal input:
Voltage
85-254 VAC/VDC, 50/60Hz
Maximum current
2.5mA at 115 V
5mA at 230 V
Feedback output:
Voltage
0-254 VAC/VDC, 50/60Hz
Maximum current
150mA (AC or DC)
Maximum power
15 W
Electric contacts
Potential free
The QC02 module has a fuse in the supply live line. It is not allowed to replace this fuse in the field.
- For Non-Incendive (Cl. I Div2) or Non-Sparking (Zone 2) hazardous area applications, see Installation Guide : DOC.IG.QC02.1
(*
QC02,85-254 VAC/VDC electric connections, single power
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.011 - Rev: D - Page 1 of 3
January, 2008
Date:
FieldQ
Smart - Control Modules
QC03: IS, QC04: IS-NAMUR, Intrinsically safe
Description:
These variations of the FieldQ Smart Control Module offers,
an intrinsically safe concept for “On/Off” valve automation.
Its compact and robust construction incorporates the same
IPT technology and same functionalities as all the other
FieldQ Smart Modules have.
Construction:
The Control Module is mounted at the side of the Pneumatic
Module in front of the basic actuator housing. Inside are terminals available for connecting control and feedback wiring.
Two cable entries are available for this purpose.
Features:
- Supports both single and double acting actuators.
- One entry for all wiring (control and feedback).
- IPT-technology (Intelligent Position Tracking).
- Automatic initialization for easy setup of the actuator.
Pressing 4 seconds simultaneously the “Open” and
“Closed” reassignment buttons starts auto-initialization procedure and sets automatically the feedback limit switches.
- Readjustable or Reversible position feedback using the
reassignment buttons.
- Three indication LED’s for “Status”, “Open” and “Closed”
position. Status LED indicates:
- Initialization procedure running
(blinking)
- Successful initialization procedure (LED is on)
- No or failed initialization
(flashing)
- Control Module is easily plugged in the Pneumatic Module.
- Modular functionality for easy update towards present and
future bus systems.
- The power supply and all inputs and outputs are galvanic isolated which offers greater flexibility for systems
connection.
General Specifications:
Material housing
:Aluminium alloy
Cable entries
:2x M20x1.5 or 2x 1/2”NPT
Electrical connections :Internal terminal strip.
Enclosure
:IP65 / NEMA4X
Finish
:Polyester non-TGIC based powder
coating.
Temperature
:-20° to +50°C / -4° to 122°F
Operating media
:Air or inert gasses, filtered at 5 micron
Dimensions
:See 1.603.01 for ISO 5211 (metric)
See 1.603.04 for ISO 5211 (Imperial,
UNC). See 1.603.02 for DIN 3337
FieldQ Button board
Closed reassignment button
Push
4 sec.
Closed LED
Status LED
Open LED
Open reassignment button
Status LED:
off
on
LED = Flashing
LED = Blinking
off
Time
on
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.011 - Rev: D - Page 2 of 3
January, 2008
Date:
FieldQ
Smart - Control Modules
QC03: IS, QC04: IS-NAMUR, Intrinsically safe
QC04 Short circuit monitoring and line break detection
Control Module QC04 is additionally equipped with NAMUR
feedback according IEC 60947 part 5-6 (VDE 0660 sec. 212).
In combination with a switch amplifier according this same
standard, it offers next to feedback short circuit monitoring
and line break detection.
I / mA
6
5
4
Nominal Voltage
Short circuit
8.2 VDC
R < 100 Ohm
3
Switch activated
> 2.1 mA
2
1
Switch deactivated < 1.2 mA
0
Line break
< 0.05 mA
Switch characteristics of NAMUR feedback outputs according
IEC60947-5-6.
Options:
Manual Control
- Can be added as kit or factory option in 2 versions,
“Push button” or a “Push and lock” button.
Glands and plugs
- FieldQ Control Modules QC03 or QC04 can be shipped
with plastic or metal glands (M20x1.5 or 1/2”NPT) and
rated IP65/NEMA4X or higher.
Intrinsically safe approvals:
Control Modules QC03 and QC04 have standard intrinsically
safe approvals as listed below:
- IECEx
:Ga Ex ia IIC T4
:Ex iaD 20 T80°C / IP65
:Certificate : KEM 07.0045X
- ATEX
: II 1 G Ex ia IIC T4
: II 1 D Ex iaD 20 T80°C / IP65
:Certificate : KEMA 02ATEX1242X
- FM
:Intrinsically safe, Class I, II, III Div.1,
Groups ABCDEFG, T4, Type 4X/IP65
:Class I, Zone 0, AEx ia IIC T4, IP65,
-CSA
:Intrinsically safe, Class I, II, III Div.1,
Groups ABCDEFG, T4
:Ex ia IIC T4, IP65, (Class I, Zone 0/1)
:Ta = -20°C…+50°C (-4°F…122°F)
:Certificate: 1477696
Ambient temperature:
T4 @ Ta = :-20°C...+50°C
Note: * The assembly of a FieldQ Actuator with the intrinsically safe
QC03 or QC04 Control Module, may be used in (ATEX)
classified Zones 1, 2 (Gasses) and/or 21, 22 (Dust).
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.011 - Rev: D - Page 3 of 3
January, 2008
Date:
FieldQ
Wiring & Electrical Specifications QC03 & QC04
QC03 IS
Electrical data Unclassified or Non Hazardous or ClassiHazardous Location fied Location
1-2Feedback 2
3-4Feedback 1
5-6Control supply
voltage
7-8Power supply
voltage
Barrier
IS Approved
1
Barrier
IS Approved
3
1
4
2
5
3
6
2
Barrier
IS Approved
Barrier
FieldQ Control
+
4
7
5
8
6
Module
QC03
IS Approved
Barrier
FieldQ
Control
- circuits
QC03,Terminal connections, with separate
7
+
8
Unclassified or Non Hazardous 1or ClassiHazardous Location fied Location
2
1-2Feedback 2
3-4Feedback 1
+
5-6Control
7-8Power supply
voltage
Module QC03
IS Approved
+
3
1
4
2
5
3
6
4
7
5
8
6
7
8
Power supply input:
Voltage
Maximum current (@14V)
Maximum Power
Capacity Ci (max.)
Inductivity Li
Control signal input:
Voltage
Maximum current
Capacity Ci (max.)
Inductivity Li
Contacts
Feedback outputs:
Maximum voltage
Maximum current
Resistance (nom.)
Switch resistance
(off-state)
Maximum power
Electric contacts
Temperature
QC03 - IS
QC04 - IS-N
13.5 - 27.6 V
26 mA
1.2 W
15 nF
0 mH
13.5 - 27.6 V
26 mA
1.2 W
15 nF
0 mH
6 - 30 V
5 mA
3.2 nF
0 mH
Potential free
6 - 30 V
5 mA
3.2 nF
0 mH
Potential free
30 VDC
32 mA
440 Ohm
300kOhm
IEC 60947-5-6
IEC 60947-5-6
440 Ohm
10440 Ohm
1.2 W
IEC 60947-5-6
Potential free
IEC 60947-5-6
-20°C to +50°C (-4°F to +122°F)
QC03,Terminal connections with common “-”
QC04 IS-N (with NAMUR feedback)
Unclassified or Non Hazardous or ClassiHazardous Location fied Location
1-2Feedback 2*
(EN60947-5-6)
3-4Feedback 1*
(EN60947-5-6)
5-6Control supply
voltage
7-8Power supply
voltage
IS Approved
Barrier
1
IS Approved
Barrier
IS Approved
Barrier
IS Approved
3
14
Barrier
FieldQ Control
module
2
QC04
Unclassified
25
36
+
47
5
8
6
7
QC04,Terminal connections with seperate- circuits
+
8
Hazardous 1or
or Non Hazardous
ClassiLocation fied Location
2
1-2Feedback 2*
3-4Feedback 1*
5-6Control
7-8Power supply
voltage
IS Approved Barrier
3
14
25
IS Approved
Barrier
IS Approved
Barrrier
FieldQ Control
module
+
+
3
6
4
7
5
8
6
QC04
7
Cable range:
Wire range
: 2.5mm2 max.
Solid / Stranded wire :0.2-3.3mm2 or 24-12 AWG
Feedback 1 and 2 on QC03:
- Use approved barriers.
Feedback 1 and 2 on QC04:
- Use barrier according EN60947-5-6 (NAMUR) for appropriate signal level. Un = 8.2VDC
QC03 / QC04 Intrinsically Safe Entity Parameters
Circuit
Power Supply
Control input
Feedback 1
Feedback 2
Terminal
7-8
5-6
3-4
1-2
Ui
30VDC
30VDC
30VDC
30VDC
Ii
300mA
300mA
300mA
300mA
Pi
1.2W
1.2W
1.2W
1.2W
Ci
15 nF
15 nF
18 nF
18 nF
For more detailed information on Intrinsically safe
(Cl. I Div1 / Zone 1) installations, see Installation Guide
DOC.IG.QC01.1
8
QC04,Terminal connections with common “-” for control &
power supply
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Li
0
0
0
0
Product data sheet
Sheet No.: 1.604.02 - Rev: 0 Page 1 of 5
January, 2013
Date:
FieldQ
Smart - Control Modules
QC34: FOUNDATION™ fieldbus
Description:
This FieldQ Control Module offers an integrated concept for
valve automation. Its compact and robust construction incorporates basic control and feedback functionality and communicates through the FOUNDATION™ fieldbus protocol.
Construction
The Control Module is mounted at the side of the Pneumatic
Module in front of the basic actuator housing. Inside are terminals available, for connecting the bus wiring and a button
board. Two cable entries are available for this purpose.
Features
- FOUNDATION™-Fieldbus digital communication.
- Supports PlantWeb Alerts.
- Supports NAMUR NE-107 Alarms
- Supports both single and double acting actuators.
- One entry for all wiring (control and feedback).
- IPT-technology (Intelligent Position Tracking).
- Initialization by FOUNDATION fieldbus or Push-button for
easy setup of the actuator.
Pressing 4 seconds simultaneously the “Open” and
“Closed” reassignment buttons starts auto-initialization procedure and sets automatically the feedback limit switches.
- Readjustable or Reversible position feedback using the
re-reassignment buttons or by
FOUNDATION fieldbus.
- Adjustable switch points can be adjusted from 5% to
30% before the end of the stroke by
FOUNDATION fieldbus.
- Three indication LED’s for “Status”, “Open” and “Closed”
position. Status LED indicates:
- Initialization procedure running
(blinking),
- Successful initialization procedure (LED is on) or
- No or failed initialization
(flashing)
- Control Module can be easily plugged in the Pneumatic
Module.
Closed reassignment button
FieldQ
terminal
compartment
Status LED
Push
4 sec.
on
off
Status LED:
Open reassignment button
LED = Flashing
on
off
Time
LED = Blinking
General specifications
Material housing
:Aluminium alloy
Cable entries
:2x M20x1.5 or 2x 1/2”NPT
Electrical connections :Internal terminal strip.
:Optional quick connectors: 7/8” or
M12 connector (see page 2)
Enclosure
:IP65 / NEMA 4X
Finish
:Polyester non-TGIC based powder
coating.
Operating media
:Air or inert gasses, filtered at 5 micron.
Temperature
:-20° to +50°C / -4° to 122°F
Dimensions
:See 1.603.01 metric
See 1.603.04 imperial/UNC
See 1.603.02 DIN 3337
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.02 - Rev: 0 Page 2 of 5
January, 2013
Date:
FieldQ
Communication Protocol:
Hazardous area executions:
Protocol
:FOUNDATION™ fieldbus
Transmission
:H1, IEC 61158-2
Maximum current
:18mA from bus
Required external :Restrict the power supply
protection current to <600mA.
Control Module QC34 with FOUNDATION fieldbus is available
with optional intrinsically safe (IS) or Non-Incendive/Non
Sparking (NI) approvals as listed below:
Function blocks
The Control Module provides the following function blocks:
- Resource Block (RB)
- Transducer Block (TB)
- Analog Input (AI) Function Block
- Discrete Output (DO) Function Block
- 2x Discrete Input (DI) Function Block
- PID Function Block
Diagnostics and Alerts
Standard FOUNDATION fieldbus diagnostics and alerts provided meets Emerson PlantWeb Alerts standard.
Applicable diagnostics include:
- Travel times for the Open stroke, Close stroke and Average
travel times.
- Cycle Counters for Control Module, Pneumatic Module,
Actuator and Valve
- Time in Position
- Various internal electronic health tests.
- Instrument temperature.
For more detailed information on diagnostics see page 3
and 4.
Options:
Manual Control
- Can be added as kit or factory option in 2 versions,
“Push button” or a “Push and lock” button.
Glands, plugs and quick connectors
- FieldQ Control Modules can be shipped with plastic or
metal glands (M20x1.5 or 1/2”NPT) and rated IP65 or
higher or a prewired quick connector.
- IECEx:Certificate : KEM 07.0045X
:Intrinsically safe*
:Ga Ex ia IIC T4
:Ex iaD 20 T80° / IP65
:Certificate : KEM 07.0046X
:Non-Sparking
:Ex nA II T4
:Ex nL IIC T4
: Ex tD A22 T80°C
- ATEX :Certificate : KEMA 02ATEX1242X
:Intrinsically safe*
: II 1 G Ex ia IIC T4
: II 1 D Ex iaD 20 T80° / IP65
:Certificate : KEMA 02ATEX1258X
:Non-Sparking
: II 3 G Ex nA II T4
: II 3 G Ex nL IIC T4
: II 3 D Ex tD A22 T80°C
- FM :Intrinsically safe, Class I, II, III Div.1,
Groups ABCDEFG, T4, Type4X/IP65
:Class I, Zone 0, AEx ia IIC T4
:Non Incendive, Class I, II, III, Division 2,
:Groups ABCDFG, T4, Type 4X/IP65
:Class I, Zone 2, IIC T4, Type 4X/IP65
-CSA :Certificate: 1477696
:Intrinsically safe, Class I, II, III Div.1,
Groups ABCDEFG, T4
:Ex ia IIC T4, IP65, (Class I, Zone 0/1)
:
Non Incendive: Class I, II, III Div.2,
Groups ABCDFG, T4
:Ex nA II T4 (Class I, Zone 2)
:Ex nL II T4 (Class I, Zone 2)
Ambient temperature:
T4 @ Ta = :-20°C...+50°C IP65
Note: * The assembly of a FieldQ Actuator with the intrinsically safe
QC34 Control Module, may be used in (ATEX) classified
Zones 1, 2 (Gasses) and/or 21, 22 (Dust).
FISCO & FNICO systems
The FieldQ QC34 is suitable for use in a FISCO or FNICO
system in accordance with IEC 60079-27 :2005
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.02 - Rev: 0 Page 3 of 5
January, 2013
Date:
FieldQ
FOUNDATION™ fieldbus terminal wiring
Standard PI-filter present.
Detailed Intrinsically safe or Non-Incendive/Non-Sparking wiring instructions, will be shipped with the product, see Installation Guide : DOC.IG.QC34.1
Field wiring
Actuator wiring
+
FF
Power
supply
-
1
2
3
Quick connector pinouts:
(male chassis part)
1
2
7/8" UNC
3
4
4
1
3
2
2
4
1
Brown
Green / Yellow
Blue
M12
Quick
connector
1
2
3
Terminal
Diagnostics and PlantWeb Alerts QC34
FOUNDATION fieldbus
The FieldQ Control Module with FOUNDATION fieldbus communication has diagnostic capabilities. These process parameters can give information about communication condition,
valve and/or actuator unit. It enables to predict failures in
advance and makes maintenance easier to schedule. The
following diagnostics are available for the FieldQ:
1 Timer parameters:
1.Open and Closed travel time
2.High and low limits of Open and Closed travel time
3.Average travel times of last 30 strokes of Open and
Closed travel.
4.High and low limits of average Open and Closed travel
time
2 Cycle Counters
1.Control Module - Counts how many times the Control
Module cycles (read only).
2.Pneumatic Module - Counts how many times the Pneumatic Module cycles.
3.Actuator - Counts how many times the actuator cycles.
4.Valve - Counts how many times the valve cycles.
3 Time In Position
4 Various internal electronic health tests.
PlantWeb Alerts
Wiring dimensions
Solid wire :2.5mm2 max.
Stranded wire :0.2-3.3mm2 or 24-12 AWG
PlantWeb Alerts are alerts that have been predefined and
categorized for the user. These device alerts can be used to
help troubleshoot the instrument (see also page 4). There are
three categories:
Quick connector pinouts:
- The FOUNDATION fieldbus Module can optionally be
equipped with prewired quick connectors. Two versions are
available: 7/8” or M12 (male chassis part).
- Quick connectors, as shown below are excluded for nonIncendive or non-sparking use in hazardous area’s classified
as Zone 2 or 22 or Cl I, II, III, Div. 2.
- Maintenance alerts
A maintenance alert indicates that the device, or some
part of the device, needs maintenance soon.
- Failed alerts,
A failed alert indicates a failure within the device that will
make the device, or some part of the device, non-operational.
- Advisory alerts
An advisory alert indicates a condition that does not have
a direct impact on the device’s primary function. If the
condition is ignored, the device will eventually fail.
These alerts, when enabled, can participate in the DeltaV
alarm interface tools such as the alarm banner, alarm list, and
alarm summary.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.02 - Rev: 0 Page 4 of 5
January, 2013
Date:
FieldQ
Diagnostics and PlantWeb Alerts
Alerts & recommended actions
Alert default setting
Advisory
Alerts
Recommended actions
bit 0
Reserved
bit 1
Internal alerts, bad position sensor
bit 2
Internal alerts, bad temperature
sensor
bit 4
Internal alerts, Specified system
temperature exceeded
Internal alerts, Software error
bit 5
Internal alert, travel deviation
bit 6
Internal alerts, Shutdown is set
bit 7
Internal alerts, Undefined error
Counter alerts, Control Module life
cycle exceeded
bit 3
enable
Feedback problem, replace control
n
module when possible
Temperature sensor problem,
replace Control Module when
n
possible
Take corrective actions to bring
n
temperature within specified range.
n
Maintenance
mask *
enable
Fail
mask *
enable
n
y
y
n
n
y
y
n
n
y
y
n
mask *
n
n
n
n
y
n
n
n
Lost position, Check air pressure y
Internal communications problem,
check shutdown configuration for n
restart, Replace Control Module.
n
Control Module life cycle exceedn
ed, Replace Control Module
Pneumatic Module life cycle
exceeded, Replace Pneumatic
n
Module.
Actuator life cycle exceeded, Ren
place actuator.
Valve life cycle exceeded, take
n
Valve requires maintenance.
Time in position exceeded, appron
priate action.
Open travel timer exceeded, check
n
valve system.
Close travel timer exceeded, check
n
valve system.
Check air pressure, check actuator
y
sizing, check valve system.
y
n
n
n
n
n
n
n
y
n
y
n
n
n
y
y
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
y
n
n
n
n
n
n
n
n
y
y
n
n
n
bit 22 Reserved RB NV Memory Failure
y
y
n
n
n
n
bit 23 Reserved TB Electronics Failure
y
n
n
n
n
n
bit 24 Reserved RB Electronics Failure
y
y
n
n
n
n
bit 8
bit 9
Counter alerts, Pneumatic Module
life cycle exceeded
Counter alerts, Actuator life cycle
exceeded
Counter alerts, Valve life cycle
bit 11
exceeded
bit 10
bit 12 Timer alerts: time in position limit
Timer alerts: open travel time limit
exceeded
Timer alerts: close travel time limit
bit 14
exceeded
Initialization Failed (reason from
bit 15
AUTO_INITIALIZATION STATUS)
bit 16 Reserved Primary Value Failure
bit 13
bit 18 Reserved HW/SW Incompatibility
bit 19
Reserved IO Failure (FF card lost
IO board)
Internal communications are lost,
device will act according to shutdown configuration.
y
n
n
n
n
n
n
n
n
n
n
n
bit 20 Reserved Mechanical Failure
bit 21 Reserved TB NV Memory Failure
*) Mask “n” indicates masked out (not visible).
For more detailed information about the configuration of the QC34 FOUNDATION™ fieldbus Module see Reference Manual DOC.RM.QC34.E. This manual is
available for download from www.FieldQ.com.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.02 - Rev: 0 Page 5 of 5
Date:
January, 2013
FieldQ
Namur NE-107 Alarms
This section describes the parameter interaction to implement
a FieldQ™ QC34 Control module to the NAMUR NE-107
requirements as a parameter group in the Resource Block.
There are four alarm categories defined as per the NE-107
specification, Failed, Off Specification, Maintenance, and
Check function.
Maintenance Although the output signal is valid, the wear
reserve is nearly exhausted or a functions will soon be restricted due to operational conditions e.g. build-up of deposits
Off Specification Off-spec means that the device is operating outside its specified range or an internal diagnostic indicates deviations from measured or set values due to internal
problems in the device or process characteristics (e.g. bubble
formation in flow metering or valve sticking).
Check Function Output signal temporarily invalid (e.g.
frozen) due to on-going work on the device.
Failed Output signal invalid due to malfunction in the field
device or its peripherals.
Parameter
Mnemonic
FD_CHECK_ACTIVE
Obj
Type
S
Data Type/
Structure
Bit String
Use/Model
Store
Each of these categories share 32 conditions that can be
defined by the device manufacturer. Each condition may be
mapped or not mapped for each category. If a condition is
mapped then it is indicated in the* ACTIVE parameter. If the
condition in the * ACTIVE parameter is not masked by the
corresponding bit in the *_MASK parameter then the condition will be queued for broadcast using the corresponding
*ALM parameter at the associated priority indicated by *PRI
parameter. The 4 categories are defined below.
The conditions are not expected to identify explicitly the root
cause of the condition, but rather to identify it in terms of:
• Replace the device
• Replace a part of the device
• Correct a configuration problem
• Fix something outside of the device
The above list is all that the operator needs to know to restore
his process functionality and if there are more than 31 device
conditions they should be grouped by definition into these bit
Size
Valid
Range
Initial
Value
C/FD Active
D
4
FD_CHECK_ALM
R
DS-87
C/Alarm
D
15
FD_CHECK_MAP
S
Bit String
C/Contained
S
4
FD_CHECK_MASK
S
Bit String
C/Contained
S
4
FD_CHECK_PRI
S
Unsigned8
C/Alert Priority
S
1
FD_EXTENDED_ACTIVE_n
S
Bit String
C/Contained
D
4
FD_EXTENDED_MAP_n
S
Bit String
C/Contained
S
4
FD_FAIL_ACTIVE
S
Bit String
C/FD Active
D
4
FD_FAIL_ALM
R
DS-87
C/Alarm
D
15
FD_FAIL_MAP
S
Bit String
C/Contained
S
4
FD_FAIL_MASK
S
Bit String
C/Contained
S
4
FD_FAIL_PRI
S
Unsigned8
C/Alert Priority
S
1
FD_MAINT_ACTIVE
S
Bit String
C/FD Active
D
4
FD_MAINT_ALM
R
DS-87
C/Alarm
D
15
FD_MAINT_MAP
S
Bit String
C/Contained
S
4
FD_MAINT_MASK
S
Bit String
C/Contained
S
4
FD_MAINT_PRI
S
Unsigned8
C/Alert Priority
S
1
FD_OFFSPEC_ACTIVE
S
Bit String
C/FD Active
D
4
FD_OFFSPEC_ALM
R
DS-87
C/Alarm
D
15
FD_OFFSPEC_MAP
S
Bit String
C/Contained
S
4
FD_OFFSPEC_MASK
S
Bit String
C/Contained
S
4
FD_OFFSPEC_PRI
S
Unsigned8
C/Alert Priority
S
1
0 - 15
0
FD_RECOMMEN_ACT
S
Unsigned16
C/Contained
D
2
0
FD_SIMULATE
R
DS-89
C/FD Simulate
D
9
1 – manf
spec
FD_VER
S
Unsigned16
C/Contained
S
2
Permission
Other
Read only
Range
Check
ALARM
ALARM
0 - 15
0
ALARM
Yes
Read only
Read only
ALARM
ALARM
0 - 15
0
ALARM
Yes
Read only
ALARM
ALARM
0 - 15
0
ALARM
Yes
Read only
ALARM
ALARM
ALARM
Yes
Read only
disabled
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Read only
Product data sheet
Sheet No.: 1.604.04 - Rev: E, Page 1 of 2
January, 2008
Date:
FieldQ
Smart - Control Modules
QC30: AS-Interface
Description:
This FieldQ Control Module offers an integrated concept for
valve automation. Its compact and robust construction incorporates basic control and feedback functionality and communicates through the ASI 2 or ASI 1 protocol.
Construction
The Control Module is mounted at the side of the Pneumatic
Module in front of the basic actuator housing. Inside are terminals available for connecting ASI wiring. Two cable entries
are available for this purpose.
Features
- ASI digital communication..
- Supports both single and double acting actuators.
- One entry for all wiring (control and feedback).
- IPT-technology (Intelligent Position Tracking).
- Up to 62 devices per segment for ASI-2 protocol
- IPT-technology (Intelligent Position Tracking).
- Automatic initialization for easy setup of the actuator.
Pressing 4 seconds simultaneously the “Open” and
“Closed” reassignment buttons starts auto-initialization procedure and sets automatically the feedback limit switches.
- Readjustable or Reversible position feedback using the
reassignment buttons.
- Three indication LED’s for “Status”, “Open” and “Closed”
position. Status LED indicates:
- Initialization procedure running
(blinking)
- Successful initialization procedure (LED is on)
- No or failed initialization
(flashing)
- Control Module is easily plugged in the Pneumatic Module.
- Modular functionality for easy update towards present and
future bus systems.
- The power supply and all inputs and outputs are galvanic isolated which offers greater flexibility for systems
connection.
General specifications
Material housing
:Aluminium alloy
Electrical connections :Internal terminal strip
:Optional 4-pole quick connector
M12x1
Cable entries
:2x M20x1.5 or 2x 1/2”NPT
Enclosure
:IP65 / NEMA 4X
Finish
:Polyester non-TGIC based powder
coating.
Operating media
:Air or inert gasses, filtered at 50
micron.
Temperature
:-20° to +80°C / -4° to +176°F
Dimensions
:See 1.603.01 metric
See 1.603.04 imperial/UNC
See 1.603.02 DIN 3337
Communication Protocol:
Protocol
:AS-Interface
Number of devices :31 for ASI-1 protocol
:62 for ASI-2 protocol
Current Minimum :30 mA (pilot valve off)
Maximum :127 mA (at 26.5V and 25°C and pilot
valve on)
Protection
:250mA from AS-Interface, by an internal automatic, resetable fuse.
ASI-Profile V3.0
:S-6.A.E (other profiles optional)
Factory settings:
Factory address :00
IO code
:6
ID code
:A
FieldQ Button board
EID1
EID2
Parameter
:7
:E
:00
Closed reassignment button
Push
4 sec.
Closed LED
Status LED
Open LED
Open reassignment button
FieldQ data bits
Type
D0 Input
D1 Bi-directional
D2 Bi-directional
D3 Bi-directional
Functions
DI’s
DO’s
Feedback “Closed” -/Feedback “Open” Solenoid Control
Not used
Not used
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.04 - Rev: E, Page 2 of 2
January, 2008
Date:
FieldQ
Smart - Control Modules
QC30: AS-Interface
ASI status feedback
ASI terminal wiring connections:
Status feedback is provided according to the ASI standard
For more detailed information on button board functionality
and LED indications, see Installation Guide : DOC.IG.QC30.1
Detailed Non-Incendive / Non-sparking wiring instructions, will
be shipped with the product, see control drawing: see Installation Guide : DOC.IG.QC30.1
Wiring dimensions
Cable range
:
ASI slave status LEDs
Quick connector:
- The ASI Module can optionally be equipped with prewired
quick connectors. Two versions are available: 7/8” or M12
(male chassis part)
- Quick connectors, as shown below, are excluded for nonIncendive or non-sparking use in hazardous area’s classified as Zone 2 or 22 or Cl I, II, III, Div. 2.
Green
Red
1 2 3 4
Status LED
on
off
0.14 - 1.5mm2 or 28-16 AWG
LED = Flashing
on
off
LED = Blinking
Time
Options
Manual Control
- Can be added as kit or factory option in 2 versions,
“Push button” or a “Push and lock” button.
Glands and plugs
- FieldQ Control Modules can be shipped with plastic or metal glands (M20x1.5 or 1/2”NPT) and rated IP65 or higher.
ASI terminal wiring connections:
Hazardous area executions:
- The ASI Control Module QC30 is available with optional
Non-Incendive or Non-Sparking approvals as listed below:
-IECEx
:Ex nA II T4
:Ex tD A22 T90° / IP65
:Certificate : KEM 07.0046x
-ATEX
: II 3 G Ex nA II T4
: II 3 D Ex tD A22 T90° / IP65
:Certificate : KEMA 02ATEX1258X
-FM
:Non-Incendive, Class I, II, III, Div.2,
Groups ABCDFG, T4, Type 4X/IP65
:Class I, Zone 2, IIC T4
-CSA
:Non Incendive: Class I, II, III, Div.2,
Groups ABCDFG, T4
:Ex nA II T4 (Class I, Zone 2)
:Certificate: 1477696
1
2
3
4
ASI +
ASI -
QC30 ASI
control
module
Note:
Terminal 1 and 2 may be used for shield.
Quick connector pinouts:
(male chassis part)
1
3
2
4
7/8" UNC
4
1
3
2
4
1
3
2
M12
Ambient temperature:
T4 @ Ta =
: -20°C…+75°C (-4°F…167°F)
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Quick
connector
shield
shield
brown
blue
1
2
3
4
Terminal
Product data sheet
Sheet No.: 1.604.09 - Rev: A, Page 1 of 3
March, 2010
Date:
FieldQ
Smart - Control Modules
QC31: DeviceNet
Description:
This FieldQ Control Module offers an integrated concept for
valve automation. Its compact and robust construction incorporates basic control and feedback functionality and communicates through the DeviceNet™ protocol.
Construction
The Control Module is mounted at the side of the Pneumatic
Module in front of the basic actuator housing. Inside are
terminals available for connecting DeviceNet™ wiring. Two
cable entries are available for this purpose.
Features
-ODVA DeviceNet™ digital communication.
- Supports both single and double acting actuators.
- One entry for all wiring (control and feedback), using
DeviceNet cabling.
- IPT-technology (Intelligent Position Tracking).
- Automatic initialization for easy setup of the actuator.
Pressing 4 seconds simultaneously the “Open” and
“Closed” reassignment buttons starts auto-initialization procedure and sets automatically the feedback limit switches.
- Readjustable or Reversible position feedback using the
reassignment buttons.
- Three indication LED’s for “Status”, “Open” and “Closed”
position. Status LED indicates:
Initialization procedure running
Blinking
Successful initialization procedure
LED is on
No or failed initialization
Flashing
Material housing
:Aluminium alloy
Electrical connections :Internal terminal strip
:Optional quick connector
Cable entries
:2x M20x1.5 or 2x 1/2”NPT
Enclosure
:IP65 / NEMA 4X
Finish
:Polyester non-TGIC based powder
coating.
Operating media
:Air or inert gasses, filtered at 50
micron.
Temperature
:-20° to +80°C / -4° to +176°F
Dimensions
:See 1.603.01 metric
See 1.603.04 imperial/UNC
See 1.603.02 DIN 3337
FieldQ Button board and wiring compartment
Automatic initialization:
Push 4 seconds
Closed reassignment button
Closed LED
DeviceNet™
status LEDs
1 2 3 4 5
- Control Module is easily plugged in the Pneumatic Module.
- Modular functionality for easy update towards present and
future bus systems.
- The power supply and all inputs and outputs are galvanic isolated which offers greater flexibility for systems
connection.
General specifications
- Module
Main Status LED
Open LED
Open reassignment
button
- Network
Main Status LED
on
off
LED = Flashing
on
off
LED = Blinking
Time
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.09 - Rev: A, Page 2 of 3
March, 2010
Date:
FieldQ
Communication Protocol:
General purpose discrete I/O, Class 7 with objects
Table 1:Protocol details and specifications
Common and DeviceNet
Class ID Instance ID(s)
specific Objects
Identity Object
1
1
Message Router Object
2
1
DeviceNet Object
3
1
Assembly Object
4
100, 101
Connection Object
5
1, 2, 4, 5, 6, 7
Discrete Input Point Object
8
100, 101
Discrete Output Point Object
9
100
Analog Input Point Object
10
100
Controller Object
100
1
Monitor Object
101
1
ODVA DeviceNet Spec Vol.I Rev 3.7 &
Device Conformance
Vol. III Rev 1.8
Prefined Master/Slave Connection
Communications
Set, Group 2 Server.
Polled I/O, Change of State (COS),
I/O Protocols
Cyclic, Explicit and Dynamic Explicit
connection objects.
Default set to "Auto-baud
Baud Rate
Can be set to 125, 250 or 500kb/sec
Refresh rate
400 ms (2.5 kHz) minimum
DeviceNet Connection
5 pole terminal, or quick connector
Voltage isolation
None
120mA @ 11VDC
Nominal Power
75mA @ 25VDC
Maximum Power
2.0 W
1
2
3
4
5
CAN_H
+V
Manual Control
- Can be added as kit or factory option in 2 versions,
“Push button” or a “Push and lock” button.
Glands and plugs
- FieldQ Control Modules can be shipped with plastic or metal glands (M20x1.5 or 1/2”NPT) and rated IP65 or higher.
Hazardous area executions:
- The DeviceNet™ Control Module QC31 is available with
optional Non-Incendive or Non-Sparking approvals as listed
below:
-FM : Non-Incendive, Class I, II, III, Div.2,
Groups ABCDEFG, T4, Type 4X/IP65
: Class I, Zone 2, IIC T4
: Certificate : 3017626
-CSA : Non Incendive: Class I, II, III, Div.2,
Groups ABCDEFG, T4
: Ex nA II T4 (Class I, Zone 2)
: DIP A22 TA 90°C
: Certificate : 1477696
Ambient temperature:
T4 @ Ta =
: -20°C…+80°C (-4°F…176°F)
DeviceNet™ terminal wiring connections:
Detailed Non-Incendive / Non-sparking wiring instructions, will
be shipped with the product, see control drawing: see Installation Guide : DOC.IG.QC31.1
Wiring dimensions
Cable range
:
DeviceNet™ terminal wiring connections:
-V
CAN_L
Options
0.2 - 2.5mm2 or 30-12 AWG
Quick connector:
-The DeviceNet™ Module can optionally be equipped with
prewired quick connectors. Two versions are available: 7/8”
or M12 (male chassis part)
- Quick connectors, as shown below, are excluded for nonIncendive or non-sparking use in hazardous area’s classified as Zone 2 or 22 or Cl I, II, III, Div. 2.
QC31
DeviceNet™
control module
Shield
Quick connector pinouts:
(male chassis part)
3
2
4
5
1
7/8" UNC
4
1
3
2
5
M12
3
5
1
4
2
Quick
connector
Black
Blue
Grey
White
Red
1
2
3
4
5
Terminal
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.09 - Rev: A, Page 3 of 3
March, 2010
Date:
DeviceNet™ status LEDs
Status feedback is provided according to the DeviceNet™
standard. For more detailed information on button board functionality and LED indications, see Installation Guide :
DOC.IG.QC31.1
Diagnostics on QC31 DeviceNet™ Control
module
The FieldQ Control Module with DeviceNet™ communication
has diagnostic capabilities. These process parameters can
give information about communication condition, valve and/
or actuator unit. It enables to predict failures in advance and
makes maintenance easier to schedule.
Monitor Object
The QC31 DeviceNet™ Control module presents its diagnostics through the Instance Attributes of the Monitor Object,
Class ID 101 (65hex) as shown in table 2 and 3.
FieldQ
Table 2:Monitor Object Instance Attributes
Attribute
ID
1
2
3
4
5
6
7
8
9
10
11
Name
Device Status
Zero power condition: 1 = Open, 0 = Close
Recognize unit status
Position
Time in position
Open travel timer
Close travel timer
Cycle counter
Average Open travel timer
Average Close travel timer
Selected FieldQ command to open and close
Table 3:Device Status Attributes
Bit
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Description
Internal communications lost (set by DeviceNet firmware)
GMR_error
Temp_sensor_error
System_temp_exceeded
Software_error
travel_deviation
Shutdown_set
Unknown error
Init_bad_repeatability
Init_running
Init_stopped
Init_range_error
Init_timed_out
n/a
Init_ok
Init_default
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.06 - Rev: C, Page 1 of 4
Date:
December, 2008
FieldQ
Integrated Base Control Module
QC11, QC12 and QC13 (IP65/NEMA4X & NI/Ex nA)
Description:
These variations of the FieldQ conventionally wired control
modules offer an integrated concept for valve automation. Its
compact and robust construction incorporates basic control
and feedback functionality. The modules are available as
weather proof (IP65/NEMA4X) or Non-Incendive/Non-Sparking for use in hazardous area’s classified as Zone 2 or 22 or
Class I, II, III, Division 2.
Features:
- Basic actuator functions for fail safe (spring return) or
double acting applications.
- Robust IP65/NEMA4X enclosure, protecting the IPT
system, the pilot valve’s coil, the feedback switches and
terminals, suitable for indoor and outdoor use.
- All the control and feedback connections can be wired to
the Control Module.
-IPT-technology.
- Easy to set feedback signals.
- Control module can be easily plugged in the pneumatic
module.
- IECEx, ATEX, FM and CSA Non-Incendive or Non Sparking
approvals.
General specifications:
Material housing
:Aluminium alloy
Electrical connections :Internal 9 pole terminal strip.
Cable entries
:3x M20x1.5 or 3x 1/2”NPT
Operating media
:Air or inert gasses, filtered at 50µm
Switch point
:Factory set at 15° maximum before
each end of travel (open and closed
position).
- Adjustable range
:Between -3° to 15° and +75° to +93°
of the end position.
Enclosure
:IP65 / NEMA 4X
Finish
:Polyester non-TGIC based powder
coating.
Temperature
:Depends on the applied switches
and/or Hazardous Area approvals
(See section Feedback switches
QC11, QC12 & QC13)
Dimensions
:See 1.603.01 metric
See 1.603.04 imperial/UNC
See 1.603.02 DIN 3337
Pilot valve specifications
The pilot valve inside the Control Module sends the actuator
to its open or closed position. The following pilot valves are
available for the weather proof versions:
Module:
QC11
QC12
QC13
Voltages Un:
24VDC*
115 VAC*
230 VAC*
* T ambient:
-20°C to +60°C (-4°F to +140°F)
+60°C to +80°C (+140°F to +176°F)
Power:
1.3W
1.3VA
1.9VA
Un:
:+10% / -15%
:+0% / -10%
Wiring diagram:
- Pilot valves
FieldQ Control Module
Field wiring Actuator wirring
Construction:
The Control Module is mounted at the side of the Pneumatic
Module in front of the basic actuator housing. Inside, wiring
terminals are available for connecting control signal to the
pilot valve and feedback signals to the switches. Three cable
entries are available.
1
2
COM NO
3
4
5
NC COM NO
6
NC
8
9
GND (-)
(+)
7
N
Switch specifications:
- See section “Feedback
switches”
Cable range : 0.2 - 2.5mm2 or 30-12AWG
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
L
Pilot valve voltages:
QC1124Vdc
QC12 115 Vac
QC13 230 Vac
Product data sheet
Sheet No.: 1.604.06 - Rev: C, Page 2 of 4
Date:
December, 2008
FieldQ
Feedback switches QC11, QC12 and QC13 Control Modules
The feedback switches inside the module senses the open or closed position and are prewired to the terminal strip. The following feedback switches are available:
Mechanical switches
Option code
Option code
Type
Voltage
Contacts
Mechanical life
Temperature
Maximum currents:
Load :
125 VAC
250 VAC
30 VDC
125 VDC
250 VDC
M
G (gold plated)
Mechanical V4
M: 250 VAC or 250VDC (maximum)
G: 125 VAC or 30VDC (maximum)
NO and NC
107 operations (depends on electrical load).
-20°C to +80°C (-4°F to +176°F)
Non Inductive
5 A (100 mA)1
3A
4 A (100 mA)1
0.4 A
0.2 A
Inductive
3A
2A
3A
0.4 A
0.2 A
1 Values in parentheses are for the “G” type switch
Field wiring Actuator wirring
COM NO
3
4
5
NC COM NO
6
NC
Inductive
5 A (Cos φ ≥ 0.9)
5 A (Cos φ ≥ 0.9)
5A
0.06 A
0.03 A
The mechanical (G-type) and hermetically sealed (D-type)
switches have gold contacts. For applications where the
benefits of gold contacts are required, the maximum current
is 100mA. When the current is higher than 100mA, the gold
plating will evaporate.
8
9
GND (-)
(+)
7
N
Open
Close
Switch Connections
Non Inductive
5A
5A
5A
0.5 A
0.25 A
Important
ATEX
FieldQ Control Module
2
Maximum currents:
Load :
125 VAC
250 VAC
30 VDC
125 VDC
250 VDC
Hazardous area executions:
The Conventional Modules QC11, QC12 and QC13, with
the Hermetically sealed switches, are available with IECEx,
ATEX, FM and CSA Non-Incendive or Enclosed Break approvals for use in Zone 2 or 22 or Class 1 Div. 2 and for all
gas and dust groups.
Wiring diagram:
- Mechanical switches
- Hermetically sealed switches
1
Hermetically sealed switches
Option code
D
Type
Hermetically sealed V3
Voltage
250 VAC or 250VDC (maximum)
Contacts
Gold plated, NO and NC
Mechanical life
107 operations (depends on electrical load).
Temperature
-20°C to +80°C (-4°F to +176°F)
L
Pilot valve1
Cable range : 0.2 - 2.5mm2 or 30-12AWG
1 See secton “Pilot valve specifications”
2 For Non-Incendive (Cl. I Div2) or Non-Sparking (Zone 2) hazardous area
applications, see Installation Guide : DOC.IG.QC11.1
3 Wiring diagram is shown in the actuators mid-stroke position.
II 3 G Ex d nA II T4/T5
II 3 D Ex tD A22 T90°C IP65
Certificate:TÜV 07 ATEX 553926X
APPROVED
N.I. Cl I, DIV2, GPS A,B,C,D
S CL II, III, DIV2, GPS E,F,G, Type 4X
Temp Class T4/T5, Class I, Zone 2, IIC
FM Approval 3031376
Class I,II,III, Div.2,
Groups ABCDEFG, T4/T5, Type 4X
Ex d nA IIC, T4/T5, IP65
DIP A22 TA 90°C
Certificate: 1638508
Temperature range:
T4 @ Ta = -20°C(-4°F) to 80°C (176°F)
T5 @ Ta = -20°C(-4°F) to 45°C (113°F)
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.06 - Rev: C, Page 3 of 4
Date:
December, 2008
FieldQ
Feedback switches QC11, QC12 and QC13 Control Modules
The feedback switches inside the module senses the open or closed position and are prewired to the terminal strip. The following feedback switches are available:
3-Wire proximity switches
Option code
O, V3 PNP
Option code
C, V3 NPN
Function
Make
Voltage
10 - 30V
Current
100 mA maximum
Off-state current
0 ... 0.5 mA typical
Temperature
-20°C to +70°C (-4°F to +158°F)
Wiring diagram:
Wiring diagram:
1 2 3 4 5 6
L+
L- L+
Open
Close
Switch Connections
L-
7
8
9
GND (-) (+)
N L
Pilot valve1
Cable range : 0.2 - 2.5mm2 or 30-12AWG
1 See secton “Pilot valve specifications”
2 For Non-Incendive (Cl. I Div2) or Non-Sparking (Zone 2) hazardous area
applications, see Installation Guide : DOC.IG.QC11.1
1 2 3 4 5 6
L+
L
3
blue
4
black
1
brown
3
blue
4
black
1
brown
Actuator wirring
3
Wir-
4
blue
1
black
3
brown
4
blue
black
1
3-Wire proximity switches NPN
Field wiring
Field wiring
Actuator wirring
3-Wire proximity switches PNP
L- L+
L-
Open
Close
Switch Connections
7
8
9
GND (-) (+)
N L
Pilot valve1
3 Wiring diagram is shown in the actuators mid-stroke position.
brown
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
1
(+)
L
Product data sheet
Sheet No.: 1.604.06 - Rev: C, Page 4 of 4
December, 2008
Date:
FieldQ
Feedback switches QC11, QC12 and QC13 Control Modules
The feedback switches inside the module senses the open or closed position and are prewired to the terminal strip. The following feedback switches are available:
2-Wire NAMUR proximity switches
Option code
N
Type
2-wire inductive
Voltage
8 VDC nominal
Ouput
Unswitched , > 3mA
Switched , < 1mA
Temperature
-20°C to +80°C (-4°F to +176°F)
Compliant to
DIN EN 60947-5-6 (NAMUR)
2-Wire 115V proximity switches
Option code
H
Voltage
20...140 Vac / 10...140 Vdc (47...63 Hz AC)
Current
Continuous
200 mA,
Peak
0,9A (20ms / 0,5Hz),
Leakage current
< 0,8 mA
Temperature
-20°C to +80°C (-4°F to +176°F)
Hazardous area executions:
The Conventional Modules QC11, QC12 and QC13 in combination with the 2-Wire NAMUR proximity switches have
IECEx, ATEX, FM and CSA Non-Incendive or Non Sparking
approvals for use in Zone 2 or 22 or Class 1 Div. 2 and for all
gas and dust groups.
3
6
L-
7
8
9
GND (-) (+)
N L
4
Wiring diagram:
3
1 2 3 4 5 6
L+
L- L+
Temperature range:
T4 @ Ta = -20°C(-4°F) to 80°C (176°F)
T5 @ Ta = -20°C(-4°F) to 45°C (113°F)
L-
2-Wire NAMUR proximity switches
2-Wire 115V proximity switches
7
8
9
GND (-) (+)
N L
L+
L-
L+
Cable
Temperature range:
T4 @ Ta = -20°C(-4°F) to 80°C
1
4 (176°F)
3
1
T5 @ Ta = -20°C(-4°F) to 45°C (113°F)
Class I,II,III, Div.2,
Groups ABCDEFG, T4/T5, Type 4X
Ex nA II T4/T5, IP65,
DIP A22 TA 90°C
Certificate: 1638508
blue
Class I,II,III, Div.2,
Groups ABCDEFG, T4/T5, Type 4X
Ex nA II T4/T5, IP65,
DIP A22 TA 90°C
Certificate: 1638508
brown
N.I. CL I, DIV2, GPS A,B,C,D
S CL II,III, DIV2, GPS E,F,G, Type 4X
Temp Class T4/T5; Class I, Zone 2, IIC
FM Approval : 3031376
N.I. CL I, DIV2, GPS A,B,C,D
S CL II,III, DIV2, GPS E,F,G, Type 4X
Temp Class T4/T5; Class I, Zone 2, IIC
FM Approval : 3031376
blue
APPROVED
APPROVED
Actuator wirring
II 3 G Ex nA II T4/T5
II 3 D Ex tD A22 T90°C IP65
Certificate: TÜV 07 ATEX 553926X
Field wiring
ATEX
Hazardous area executions:
The Conventional Modules QC11, QC12 and QC13 in combination with the 2-Wire 115V proximity switches have FM and
CSA Non-Incendive approvals for use in Class 1, Div. 2 and
for all gas and dust groups.
L-
1 2 3 4 5 6
(+)
L
(-)
N
(+)
L
(-)
N
Open
Close
Switch Connections
7
8
GND (-) (+)
N L
Pilot valve1
brown
range : 0.2 - 2.5mm2 or 30-12AWG
1 See secton “Pilot valve specifications”.
2 For Non-Incendive (Cl. I Div2) or Non-Sparking (Zone 2) hazardous area applications,
see Installation Guide : DOC.IG.QC11.1
3 Wiring diagram is shown in the actuators mid-stroke position.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
9
Product data sheet
Sheet No.: 1.604.07 - Rev: C, Page 1 of 3
Date:
December, 2008
FieldQ
Integrated Base Control Module
QC14 Intrinsic Safe
Description:
The Intrinsic Safe FieldQ conventionally wired control modules offer an integrated concept for valve automation. Its
compact and robust construction incorporates basic control
and feedback functionality.
Features:
- Basic actuator functions for fail safe (spring return) or
double acting applications.
- Robust IP65/NEMA4X enclosure, protecting the IPT
system, the pilot valve’s coil, the feedback switches and
terminals, suitable for indoor and outdoor use.
- All the control and feedback connections can be wired to
the Control Module.
-IPT-technology.
- Easy to set feedback signals.
- Control module can be easily plugged in the pneumatic
module.
- ATEX and CSA Intrinsically Safe approvals.
General specifications:
Material housing
:Aluminium alloy
Electrical connections :Internal 9 pole terminal strip.
Cable entries
:3x M20x1.5 or 3x 1/2”NPT
Operating media
:Air or inert gasses, filtered at 5µm
Switch point
:Factory set at 15° before each end of
travel (open and closed position).
- Adjustable range
:Between -3° to 15° and +75° to +93°
of the end position.
Enclosure
:IP65 / NEMA 4X
Finish
:Polyester non-TGIC based powder
coating.
Temperature
:-20°C ... +50°C (-4°F ... +122°F)
Dimensions
:See 1.603.01 metric
See 1.603.04 imperial/UNC
See 1.603.02 DIN 3337
Pilot valve specifications
The pilot valve inside the Control Module sends the actuator
to its open or closed position.
Typical functional ratings Pilot Valves
Voltage
Turn on
V
Turn off
V
Current
Peak
mA
Hold
mA
Resistance
Barrier+Cable
Ohm
Safety parameters Pilot Valves
Voltage
Ui
Maximum
Li
Power
Pi
Capacity maximum
Ci
Inductivity
Li
21.6 ... 28
5
10
1.9
1200
V
mA
W
nF
mH
30
200
0.9
0
0
Wiring diagram:
- Pilot valves
FieldQ Control Module
Unclassified or Non Hazardous or ClassiHazardous Location fied Location
Construction:
The Control Module is mounted at the side of the Pneumatic
Module in front of the basic actuator housing. Inside, wiring
terminals are available for connecting control signal to the
pilot valve and feedback signals to the switches. Three cable
entries are available.
1
2
COM NO
3
4
5
NC COM NO
6
NC
Switch specifications:
- See section “Feedback
switches”
Cable range : 0.2 - 2.5mm2 or 30-12AWG
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
7
8
9
-
+
NC
IS Approved
Barrier
Product data sheet
Sheet No.: 1.604.07 - Rev: C, Page 2 of 3
December, 2008
Date:
FieldQ
Feedback switches QC14 Intrinsically Safe Control Module
The feedback switches inside the module senses the open or closed position and are prewired to the terminal strip. The following feedback switches are available:
Mechanical switches
Option code
Type
Contacts
Mechanical life
Temperature
M or G
Mechanical V4
NO and NC (G = Goldplated)
107 operations (depends on electrical load).
-20°C to +50°C (-4°F to +122°F)
Hermetically sealed switches
Option code
D
Type
Hermetically sealed V3
Contacts
Gold plated, NO and NC
Mechanical life
107 operations (depends on electrical load).
Temperature
-20°C to +50°C (-4°F to +122°F)
Hazardous area executions:
The Conventional Modules QC14 in combination with the mechanical gold plated and hermetically sealed switches, have
an ATEX and CSA Intrinsically Safe approval as listed below:
Wiring diagram:
- Mechanical switches
- Hermetically sealed switches
Unclassified or Non Hazardous or
Hazardous Location Classified Location
ATEX
0344
: II 1 G Ex ia IIC T4...T6,
II 1 D Ex tD A20 T80°C
Optional for D type switch:
II 1 G Ex ib d IIC T4...T6
:Certificate : TÜV 07 ATEX 553928X
1
2
3
COM NO
IS barrier3
NC
4
5
6
COM NO
NC
7
NC
8
9
-
+
IS barrier3
Pilot valve1
Open
Close
Switch Connections
Cable range : 0.2 - 2.5mm2 or 30-12AWG
1 See secton “Pilot valve specifications”
2 For Intrinsically Safe (Cl. I Div1 or Zone 1 or 21) hazardous area applications, see Installation Guide : DOC.IG.QC14.1
3 IS Approved barrier
4 Wiring diagram is shown in the actuators mid-stroke position.
IS barrier3
:Intrinsically safe, Class I, II, III, Division 1,
Groups ABCDEFG T4...T6, Type 4X
:Ex ia IIC, T6, IP65
: DIP A20 TA 80°C
:Certificate : 1638508
Temperature range:
T4..T6 @ Ta = -20°C(-4°F) to +50°C (122°F)
QC14 Intrinsically Safe Entity Parameters Feedback switches
Circuit Terminal
Ui
Ii
Pi
Ci
Li
M-type, 1 - 2 - 3,
30Vdc 300mA
1.2W
0
0
D type
4-5-6
1 - 2 - 3,
G-type
30Vdc 100mA
1.2W
0
0
4-5-6
ATEX classified hazardous areas:
Base FieldQ actuators do not comply to all Zone 0 requirement. Please contact our sales for these Zone 0 appplications.
The combination of basic actuator and the above control
module QC14 is allowed to be used up to Zone 1 or 21.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.07 - Rev: C, Page 3 of 3
December, 2008
Date:
FieldQ
Feedback switches QC14 Intrinsically Safe Control Module
The feedback switches inside the module senses the open or closed position and are prewired to the terminal strip. The following feedback switches are available:
2-Wire NAMUR proximity switches
Option code
N
Type
2-wire inductive, normally closed
Voltage
8 VDC nominal
Ouput
Unswitched , > 3mA
Switched , < 1mA
Temperature
-20°C to T* (-4°F to +T*)
Compliant to
DIN EN 60947-5-6 (NAMUR)
QC14 Intrinsically Safe Entity Parameters Feedback switches
Circuit
Terminal
Ui
Ii
Pi
Ci
Li
Type 1
1 – 2, 4 - 5 16Vdc 25mA 34mW 100nF 100μH
Type 2
1 – 2, 4 - 5 16Vdc 25mA 64mW 100nF 100μH
Type 3
1 – 2, 4 - 5 16Vdc 52mA 169mW 100nF 100μH
Type 4
1 – 2, 4 - 5 16Vdc 76mA 242mW 100nF 100μH
* a cable length of 10 m is considered.
Hazardous area executions:
The Conventional Modules QC14 in combination with the
NAMUR proximity switches, have an ATEX and CSA Intrinsically Safe approval as listed below:
Unclassified or
Non Hazardous Location
Hazardous or
Classified Location
Wiring diagram:
2-Wire NAMUR proximity switches
L+
1
L-
2
IS
barrier3
(+)
L
(-)
N
L+
3
4
L-
5
IS
barrier3
(+)
L
ATEX: 0344
:
II 1 G Ex iaT*
II 1 G Ex tD A20 T80°C IP65
:Certificate : TÜV 07 ATEX 553928X
(-)
N
Open
Close
Switch Connections1
6
7
8
9
IS
barrier3
(-)
N
(+)
L
Pilot valve1
Cable range : 0.2 - 2.5mm2 or 30-12AWG
1 See secton “Pilot valve specifications”
2 For Intrinsically Safe (Cl. I Div1 or Zone 1 or 21) hazardous area applications, see Installation Guide : DOC.IG.QC14.1
3 IS Approved barrier
4 Wiring diagram is shown in the actuators mid-stroke position.
:Intrinsically safe, Class I, II, III, Division 1,
Groups ABCDEFG T*, Type 4X
:Ex ia IIC, T*, IP65
: DIP A20 TA 80°C
:Certificate : 1638508
Temperature range:
T4...T6 @ Ta = -20°C(-4°F) to +50°C (122°F)
T* ambient at T class:
Connection
T6
Type 1
50°C / 122°F
Type 2
46°C / 114°F
Type 3
25°C / 77°F
Type 4
10°C / 50°F
T5
50°C / 122°F
50°C / 122°F
37°C / 98°F
22°C / 71°F
T4 – T1
50°C / 122°F
50°C / 122°F
50°C / 122°F
50°C / 122°F
ATEX classified hazardous areas:
Base FieldQ actuators do not comply to all Zone 0 requirement. Please contact our sales for these Zone 0 appplications.
The combination of basic actuator and the above control
module QC14 is allowed to be used up to Zone 1 or 21.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.10 - Rev: 6, Page 1 of 11
Date:
April 2015
FieldQ
Integrated Control modules
QC41, QC42 and QC43
Features:
- Basic actuator functions for:
- Spring return applications, or
- Double acting applications or,
- Double acting Fail in Last Position applications.
APPROVED
- Suitable for all FieldQ actuator sizes.
- Available as "Weather Proof" for indoors or outdoors
use and "Explosion Proof" for areas with a potential
explosion hazard.
- The robust aluminum alloy enclosure (IP66 /
NEMA4X rated), protects the IPT system, pneumatic
components, the feedback switches and terminals and
makes it suitable for indoor and outdoor use.
- The Explosion Proof version is available with ATEX /
IECEx Ex d approval for use in Zone 1, 2, 21 and 22
and/or FM / CSA Explosion proof approval for use in
Class I, Division 1.
- Various feedback switch options available.
- Non-Intrusive switch point adjustment of the feedback
switches. Allows to adjust switch points without
opening the Control Module.
- Lockable Control Module cover.
- All the control and feedback connections can be wired
through one single entry to the Control Module.
- One larger entry (3/4"NPT) is available for larger multicore cables on imperial units.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.10 - Rev: 6, Page 2 of 11
Date:
April 2015
Description:
Electrical safety requirements:
These FieldQ conventionally wired control modules are the
next step for the integrated concept of valve automation.
Next to the components for feedback switches, also all
the pneumatic control components are located inside one
module housing.
Its compact and robust construction incorporates basic
control and feedback functionality and is suitable for indoor
and outdoor use.
These modules are available with ATEX and IECEx
certification for use in Zone 1, 2, 21 and 22, and additionally
FM and CSA certified for use in Class I, Division 1.
Construction:
The Control Module is mounted at the side of the basic
actuator housing. Inside, wiring terminals are available for
connecting control and feedback signals. Two cable entries
are available.
The pilot valves inside the control module are used to send
the actuator to its open or closed position. One pneumatic
connection is available to feed the control module.
General specifications:
Material housing:
Operating media:
Pneumatic entry:
Electrical connections:
Cable entries:
Enclosure:
Switch points:
- Adjustable range:
Finish:
Temperature range:
Dimensions:
FieldQ
Aluminium alloy
Air or inert gasses, filtered at 50µm
Metric units: G1/4"
Imperial units:1/4”NPT
Pilot valve(s): 6 pole terminal strip.
Switches:
6 pole terminal strip.
Metric units: 2x M20x1.5
Imperial units:1/2” and 3/4"NPT
Rated IP66 - NEMA4X
Factory set at 15° before each end
of travel (open and closed position).
Between -3° to 15° and +75° to
+93° of the end position.
Chromated, polyurethane based
coating.
Depends on the switches inside
the module and or Hazardous Area
approvals (See section "Position
feedback"
Metric:1.603.08
Imperial/UNC:1.603.09
DIN 3337:
1.603.10
Use
Altitude
: In- and outdoor.
: Operating full power available up to 2000 meter (6000 feet).
Maximum relative
: 80% for temperatures up to 31°C
humidity (87.8°F) decreasing linearly to 50% relative humidity at 40°C (104°F).
Mains supply
: Up to ±10% of nominal voltage
fluctuation
Over voltage category : II
Pollution degree
: 2
(3 when the cover remains closed)
Terminal
compartment
Control Module
Type Label
Option: 1 or 2
speed control
throttles
Lockable
Module cover
Pneumatic connections:
1/4”BSP or 1/4”NPT
Option: Additional Local
Manual Control for “Fail in
Last Position”
Electrical entries:
3/4”NPT
or M20
Option: Local Manual
Control
1/2”NPT
or M20
Switch
terminals
Pilot valve
terminals
Control module overview
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Non-Intrusive switch
point adjustment
Product data sheet
Sheet No.: 1.604.10 - Rev: 6, Page 3 of 11
Date:
April 2015
FieldQ
Pneumatic control
Pneumatic control variations
The Control Module contains all the necessary pneumatic
components to control the actuator and control the
incoming and outgoing airflow. Pneumatically the modules
are available for three applications:
1 Spring return or
2 Double acting or
3 Double Acting - "Fail-in-Last-Position".
To achieve these functions, each Control Module can be
fitted with one or two pilot valves depending on the required
functionality:
Pilot valve 1
Cable range:
0.2 - 2.5mm2 or
30-12AWG
One default pilot valve and wiring connections
1 One pilot valve is default and suitable for normal
operation of double acting or spring return actuators
2 Two pilot valves are required to achieve a "Fail-in-LastPosition" functionality on double acting actuators.
Pilot valve 1
Table 1: Pilot valve specifications
Module
Voltages
Power
QC41
24VDC (±10%)
1W
Frequency
NA
QC42
115 VAC (±10%)
3VA
50/60Hz
QC43
230 VAC (±10%)
3VA
50/60Hz
Pilot valve 2
Cable range:
0.2 - 2.5mm2 or
30-12AWG
FILP = Fail in Last Position
Wiring diagram shown, is applicable for actuators with assembly code “CW”.
For actuators with assembly code “CC” (reverse acting) the “Open” and
“Closed” pilot valve connections are also reversed.
Pneumatic cartridge
Pilot valve cartridge
Pilot valve
terminals
Two pilot valves and wiring connections for Fail in Last
Position
Pilot valve and pneumatic cartridge
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.10 - Rev: 6, Page 4 of 11
Date:
April 2015
Pneumatic components
The pneumatic components inside the module consist
out of one or two pilot valves and a 3/2 spool valve or 5/2
bistable spool valve. The spool valves are pneumatically
operated by the pilot valves.
To assure trouble-free operation, the spool valves are
equipped with big ports. This enables a large air flow and
makes it less sensitive for contamination of the internals.
The large air flow also fast cycle times and enables it to be
utilized for the entire FieldQ actuator range.
Internal corrosion protection:
The spring return models have standard a built in “Breather”
function. During the spring stroke, the exhaust air from the
center chamber (A-Port) is first fed to the spring chamber
(B-port) preventing air from outside from being sucked into
the spring chamber. This reduces the possibility of internal
corrosion and maximizes the actuators’ working life.
Pneumatic options
FieldQ
Fail safe
(spring return)
A-port
B-port
Option: Throttle 1
3/2 Spool valve
Option: LMC
Ps
Ra
Pilot valve 1
Double acting
Speed Control
The FieldQ can be supplied with a Speed Control option.
One throttle is required for Spring Return actuators and up
to two for Double Acting actuators.
The speed control throttle controls the air flow in and out
of an air chamber and as such limits the speed of the
“Opening” and “Closing” stroke simultaneously.
Silencers and vents
A-port
B-port
Option:
Throttle 1
Option:
Throttle 2
5/2 Spool valve
Option: LMC
Rb
Ps
Ra
The exhaust ports Ra and Rb on the module are shipped
from the factory with transport protection.
The module can be equipped with either silencers or vents.
Pilot valve 1
Manual Control
For commissioning, emergency or maintenance purposes,
the FieldQ can be supplied with Manual Control options.
These options can operate the actuator when there is air
pressure available, but no control signal or power supply.
- For normal operation the module should be fitted with
one Manual Control.
- For Double Acting with a Fail-in-Last-Position function,
two Manual Control can be fitted.
Double Acting
Fail in Last
Position
A-port
Option:
Throttle 1
Maximum Flow rates of Q-Series modules
The maximum flow rates depends mainly on the flow rates
of the FieldQ XP modules. You can use Kv 0.33 (m3/h)
or Cv value of 0.28 (US gall/min 1Psi) for approximate
operating speed calculations.
B-port
Option:
Throttle 2
5/2 Spool valve
Option: LMC 1
Option: LMC 2
Ps
Rb
Ra
Pilot valve 1
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Pilot valve 2
Product data sheet
Sheet No.: 1.604.10 - Rev: 6, Page 5 of 11
Date:
April 2015
FieldQ
Position feedback
Non-Intrusive switch point adjustment
The position feedback is achieved by switch cartridges in
the module. These cartridges contain switching elements
which sense the open or closed position and are pre
wired to the terminal strip. These easily exchangeable
switch cartridges are available with various mechanical or
proximity switching elements.
If required the switches can be adjusted without opening the
module. This, so called, Non-Intrusive switch adjustment is
located at the front of the module behind a locable (1) shield
(2). Two adjustment screws are available for adjusting the
Closed (3) and Open (4) position indication.
N WHEN E
NING N
PE
O WAR
!-
G
ER
IZED
DO NO
T
Switch cartridges
Terminal strip position
feedback switches
3
4
1
2
Switch cartridge
Switch cartridges
"Closed"
Switch point adjustment
"Open"
Switch point adjustment
Non-Intrusive switch point adjustment
Important:
- The above "Closed" and "Open" marked adjustment
screws will adjust the valve's "Closed" or "Open" switch
point, if the valve closes after a Clock Wise (CW) rotation.
- If the valve closes after a Counter Clock Wise (CCW)
rotation, the "Closed" marked adjustment screw will adjust
the "Open" switch point. Similar, the "Open" marked
adjustment screw will adjust the "Closed" switch point.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.10 - Rev: 6, Page 6 of 11
Date:
April 2015
FieldQ
Mechanical switches
2-Wire Proximity switches
Specification
Description
Specification
Description
Option code
M
Option code
N
Option code
G (gold contacts)
Type
2-wire inductive, normally closed
Type
Mechanical
Voltage
8 VDC nominal
Voltage
M: 277 VAC or 250VDC (maximum)
Output
Unswitched , > 3 mA
Temperature range
Switched , < 1 mA
-25°C to +65°C / -13°C to +149°F
For use in hazardous areas, see table 7
DIN EN 60947-5-6 (NAMUR)
Table 2: Mechanical switches
Table 4: 2-wire NAMUR proximity switches
G: 125 VAC or 30VDC (maximum)
Contacts
Temperature range
NO and NC
-25°C to +65°C / -13°C to +149°F
For use in hazardous areas, see table 7
Table 3: Maximum currents
Switch voltage
M type switch
G type switch
125 VAC
10 A (3 A1)
0.1 A 2
250 VAC
10 A (3 A1)
-
30 VDC
0.5 A
0.1 A 2
125 VDC
0.5 A
-
250 VDC
0.25 A
-
Note:
1. The mechanical (M-type) switches are rated for 3 A with
inductive load.
2 The mechanical (G-type) switches have gold contacts.
For applications where the benefits of gold contacts are
required, the maximum current is 1 A.
3. For applications below -20°C (-4°F), the base actuator
must be equipped with Low temperature seals.
Compliant to
Table 5: 2-Wire 230V proximity switches
Specification
Description
Option code
H
20...250VAC / 10...300VDC
(50...60 Hz AC)
Maximum
100 mA
Voltage
Current
Peak
Leakage
Temperature range
Note:
1 For applications below -20°C (-4°F), the base actuator
must be equipped with Low temperature seals.
Wiring diagram:
Wiring diagram:
- 2-Wire NAMUR proximity switches
- 2-Wire 115V proximity switches
- M = Mechanical
- G = Mechanical, gold contacts
1 L- 2
Open
0,9A (20ms / 0,5Hz),
< 1.7 mA
-25°C to +65°C / -13°C to +149°F
For use in hazardous areas, see table 7
Close
Cable range : 0.2 - 2.5mm2 or 30-12AWG
Wiring diagram is shown in the actuators mid-stroke position.
Wiring diagram for mechanical switches
L+ 3
4 L- 5
2
2
1
1
Open
L+ 6
Close
Cable range : 0.2 - 2.5mm or 30-12AWG
2
Wiring diagram for 2-Wire proximity switches
Important:
- The above "Closed" and "Open" marked adjustment terminals will indicate the valve's "Closed" or "Open" switch
point, if the valve closes after a Clock Wise (CW) rotation.
- If the valve closes after a Counter Clock Wise (CCW) rotation, the "Closed" marked adjustment terminals will indicate
the "Open" switch point. Similar, the "Open" marked adjustment terminals will indicate the "Closed" switch point.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.10 - Rev: 6, Page 7 of 11
Date:
April 2015
FieldQ
3-Wire Proximity switches
Table 4: 3-wire proximity switches
Specification
Description
Option code
O, V3 PNP
Option code
C, V3 NPN
Function
Make
Voltage
10 - 30V
Current
100 mA maximum
Off-state current
0 ... 0.5 mA typical
-25°C to +65°C / -13°C to +149°F
For use in hazardous areas, see table 7
Temperature range
Note:
1 For applications below -20°C (-4°F), the base actuator
must be equipped with Low temperature seals.
Wiring diagram:
3-Wire proximity "O" type switches PNP
L-
2
1
L+
3
L-
5
4
3
4
1
L+
6
L+
6
3
4
1
PNP
Open
Close
Wiring diagram:
3-Wire proximity "C" type switches NPN
L-
2
1
L+
3
3
4
1
L-
5
4
3
4
1
NPN
Open
Close
Cable range : 0.2 - 2.5mm2 or 30-12AWG
Wiring diagram for 3-Wire proximity switches
Important:
- The above "Closed" and "Open" marked adjustment terminals will indicate the valve's "Closed" or "Open" switch
point, if the valve closes after a Clock Wise (CW) rotation.
- If the valve closes after a Counter Clock Wise (CCW) rotation, the "Closed" marked adjustment terminals will indicate
the "Open" switch point. Similar, the "Open" marked adjustment terminals will indicate the "Closed" switch point.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.10 - Rev: 6, Page 8 of 11
Date:
April 2015
FieldQ
Control Module Options
QC41, QC42 and QC43
Local Manual Control
Speed Control
Description
Description
For commissioning, emergency or maintenance purposes,
the FieldQ can be supplied with one or two Manual Control
options. These can operate the pilot valve(s) inside the
module and as such operate the actuator, when there
is air pressure available, but no control signal or power
supply.
The FieldQ can be supplied with a Speed Control option.
One throttle is required for Spring Return actuators and up
to two for Double Acting actuators.
The speed control throttle controls the air flow in and
out of an air chamber and as such limits the speed of
the “Opening” and “Closing” stroke simultaneously. This
throttle consists of :
1 Nut cover
2 Main throttle with set screw.
Notes:
- One Local Manual Control is required for normal
operation of Double acting or Spring return actuators.
- For Double acting actuator with a Fail-in-last position
function, a second Local Manual Control can be
mounted.
- These options can be ordered together with the Control
Module or as a kit to be mounted later.
- For option ordering codes, see page 7
Note:
- For Spring Return actuators with one speed control
throttle, it is not possible to set both the stroke cycle
times to an equal time.
- Four Double Acting actuators it is possible to mount two
speed control throttles.
- The actual stroke cycle times depend on the actual load
on the actuator during the different strokes.
Spring Return:
Top entry only.
Double Acting:
Bottom and/or top entries.
Location for 2nd
Local Manual Control
Lock
45°
Default location of
Local Manual Control
Unlock
On
1
Off
Local Manual Control option
Speed control options
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
2
Product data sheet
Sheet No.: 1.604.10 - Rev: 6, Page 9 of 11
Date:
April 2015
FieldQ
Hazardous area specifications
Modules QC41, QC42 and QC43
Below specification are applicable for QC41, QC42 and QC43 modules with a hazardous area approval.
Hazardous area product marking;
FM hazardous or Classified Location:
IECEx hazardous or Classified Location:
APPROVED
Ex d IIB+H2 T4/T6 Gb
Ex t IIIC T80°C Db
IECEx DEK 15.0034X
CL I, II, III, DIV 1
Groups BCDEFG, T4/T6, Type 4X/6
CL l, ZN 1, IIB+H2, T4/T6
CSA hazardous or Classified Location:
ATEX hazardous or Classified Location:
Class I, II, III, DIV 1
Groups CDEFG, T4/T6, Type 4X/6
Ex d IIB+H2 T4/T6
DIP A21 TA 80°C
1180
II 2G Ex db IIB+H2 T4/T6
II 2D Ex tb IIIC T80°C
DEKRA 15ATEX0055X
Notes:
1 Each control module is marked with the applicable ambient temperature marking.
2 Metric control modules are marked with ATEX and IECEx markings.
3 Imperial control modules are marked with ATEX, IECEx, FM and CSA markings.
Temperature rating
Table 7: Temperature rating for use in areas with a potential explosion hazard.
Configuration
Module type
Switch cartridge
QC41 (24VDC)
QC42, QC43 (115 or 230VAC)
QC42, QC43 (115 or 230VAC)
Notes:
M, G
O, C, N, H
Temperature (°C)
Pneumatic
Max. Power
Min.
Max.
Max.
action
dissipation
ambient
ambient
Surface
S,D,F
3.6W (2
-25°C (-13°F)
+60
+80
T6/T4
S,D
3.6W (2
-25°C (-13°F)
+60
+80
T6/T4
F
7.2W (3
-25°C (-13°F)
+60
+80
T6/T4
1 1x or 2x 24VDC pilot valves, or 1x 115/230 VAC
pilot valve
2 2x 115 or 230 VAC pilot valves
Switch cartridge
M = Mechanical switches
G = Mechanical switches (gold contacts)
C = 3 wire PNP proximity switch
O = 3 wire NPN proximity switch
N = 2 wire proximity switch
H = 2 wire proximity switch
Pneumatic action
S = Spring Return (Single acting).
D = Double acting.
F = Double acting (Fail in Last Position)
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Class
Product data sheet
Sheet No.: 1.604.10 - Rev: 6, Page 10 of 11
Date:
April 2015
FieldQ
Corrosion protection FieldQ
Modules QC41, QC42 and QC43
Description
Technical data base actuator
The corrosion protection system of FieldQ actuators
consist of the following treatments or materials:
Finish:
Polyurethane powder coating
Thickness:
80 to 160 micrometer (3.1 to 6.2 mils).
Salt spray test: 1000 hours (ASTM B117)
Color:Yellow
Materials:
Housing:
Anodized aluminium alloy
Pistons:Chromatized
Pinion: High grade aluminum alloy,
hard anodized
Fasteners: Stainless steel or coated
alloy steel.
Type plate: Stainless steel
1 Pretreatment
The actuator housings are anodized inside and outside, to
give them a durable and superb protection against wear
and corrosion.
2 De-greasing.
All aluminum parts are de-greased before the coating is
applied by washing with an alkaline solution to assure
the best bonding between the aluminum surface and the
coating.
3 Finish
3.1 Actuator
Polyurethane powder coating for exterior use.
The powder coating is applied cold using automatic
electrostatic spray equipment and is cured for about 10
minutes at minimum 200°C (392°F) offering excellent light
and weather resistance.
3.2 Module
Polyurethane coating for exterior use.
The coating offers excellent light and weather resistance.
Good chemical resistance against most bases, acids,
solvents, alkalis and oils at normal temperatures.
Excellent exterior mechanical durability.
4 High grade & hard anodized aluminum pinion.
Technical data Control Module
Finish:
2 Component with an epoxy primer and
polyurethane enamel top coating.
Thickness: 80 to 160 micrometer (3.1 to 6.2 mils).
Salt spray test: 1000 hours (ASTM B117)
Color: Yellow
Materials: Housing: Anodized aluminium alloy
Fasteners: Stainless steel or coated
alloy steel.
Type plate: Vinyl
Base
actuator
Actuators with high grade & hard anodized aluminum
pinions, passed a 1000 hours salt spray test.
Module
5 Stainless steel or coated steel parts.
External parts are stainless steel or coated alloy steel.
6 Corrosion protected springs on Spring Return
actuators
All the springs of spring return actuator are Deltatone®
or epoxy (black) coated to prevent the corrosion of the
springs and assure a long cycle life.
Stainless steel
Fasteners
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.10 - Rev: 6, Page 11 of 11
Date:
April 2015
FieldQ
Control Module Configuration:
Modules QC41, QC42 and QC43
Sample code:
QC41 • UWPM S A 1 • 0040 INS 0 IP
Pneumatic exhaust
Manual Control
Speed control
Mounting Options
IPT Device size actuator
Language Code
Future Expansions Code
Action
Control module options
Protection method
Conduit connections
Control module
Control module
QC41
Control module with 24 VDC pilot valve
QC42
Control module with 115 VAC pilot valve
QC43
Control module with 230 VAC pilot valve
Connections
M
Metric
U
NPT
Protection method
WP
Weather Proof IP66/NEMA4X
P5
Flame- or Explosion proof approval (see note 1)
Control module options (position feedback)
M
Mechanical switch
G
Mechanical switch (Gold Plated)
O
3-wire prox. switch PNP
C
3-wire prox. switch NPN
N
2-wire prox. switch (NAMUR)
H
2-wire prox. switch (20-140 VAC/10-140 VDC)
Action
S
D
F
Single acting actuator
Double acting actuator
Double acting - Fail-In-Last-Position
Future Expansions Code
A
Standard
Language Code
1
English
QC41 • UWPMSA1 • 0150INS0IP
- Control module with 24 VDC pilot valve
•
- Imperial unit with 1/2"NPT and 3/4"NPT
electrical entries and 1/4"NPT pneumatic
entry.
- Weather proof module (IP66/NEMA4x)
- Mechanical feedback switches
- Suitable for Spring Return actuators
•
- With IPT probe for Q150 size actuator
- Not installed to actuator (separate
Control module)
- No speed control option
- No manual control option
- With IP65/NEMA4 exhaust
IPT Device size for actuator:
0040
Q40 actuator
0065
Q65 actuator
0100
Q100 actuator
0150
Q150 actuator
0200
Q200 actuator
0350
Q350 actuator
0600
Q600 actuator
0950
Q950 actuator
1600
Q1600 actuator
0000
No IPT probe
Mounting Options
U
Uninstalled
I
Installed/Tested to actuator
Speed control
NS
No Speed Control
N1
Spring Return (1x throttle)
N2
Double acting (2x throttle)
Manual Control
0
No Manual Control
1
1x "Push&Lock", anodized aluminum
2
2x "Push&Lock", anodized aluminum
Pneumatic exhaust
IP
IP65/NEMA4 rated exhaust
IN
Non metalic exhaust / Check valve
ZZ
Special exhaust
Note: 1 Metric control modules are marked with ATEX and IECEx markings.
2 Imperial control modules are marked with ATEX, IECEx, FM and CSA markings.
3 The options below are all options available. Not all options apply to all configurations.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 1 of 12
October 2015
Date:
FieldQ
Integrated Control modules
QC54 with FOUNDATION™ Fieldbus digital communication.
Features:
- Basic actuator functions for:
- Spring return applications, or
- Double acting applications or,
- Double acting Fail in Last Position applications.
- Suitable for all Q-Series actuator sizes.
- FOUNDATION™-Fieldbus digital communication.
- IPT-technology (Intelligent Position Tracking).
- Initialization by FOUNDATION™- Fieldbus or Push
Button for easy setup of the actuator.
- Press and confirm press the "Auto-Init" button starts
auto-initialization procedure.
- Initialization sets automatically the switch points for the
position feedback of the actuator.
- Initialization checks if the actuator and control
module configuration match. This procedure will
detect the action type (Fail-Open, Fail-Close or Fail
in last position) and generate an alert if there is a
configuration issue.
- Readjustable or Reversible position feedback using
the re-reassignment buttons or by FOUNDATION™
Fieldbus.
- Adjustable switch points can be adjusted from 5% to
30% before the end of the stroke by FOUNDATION™
Fieldbus.
- Three indication LED's for "Status", "Open" and
"Closed" position. Status LED indicates:
- Initialization procedure running (blinking),
- Successful initialization procedure (LED is on) or
- No or failed initialization (flashing) or
- A particular unit in the field.
Fig. 1. Control module QC54 with
FOUNDATION™-Fieldbus bus communication
- Available as "Weather Proof" for indoors or
outdoors use.
- The robust aluminum alloy enclosure (IP66/
NEMA4X rated), protects the IPT system, pneumatic
components, the feedback switches and terminals and
makes it suitable for indoor and outdoor use.
- Lockable Control Module cover.
- One larger entry (3/4"NPT) is available for larger multicore cables on imperial units.
- Control Module can be easily mounted to the actuator
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 2 of 12
October 2015
Date:
FieldQ
Description:
This Q-Series QC54 Control Module offers an
integrated concept for valve automation. Its compact
and robust construction incorporates basic control and
feedback functionality and communicates through the
FOUNDATION™- Fieldbus protocol.
All electrical and pneumatic control components are
located inside one module housing making it a compact
and robust construction incorporating basic control and
feedback functionality and is suitable for indoor and
outdoor use.
Construction:
The Control Module is mounted at the side of the basic
actuator housing. Inside, wiring terminals are available
for connecting the FOUNDATION™- Fieldbus signals. Two
cable entries are available.
One pneumatic connection is available to feed the control
module. The pilot valves inside the control module are
used to send the actuator to its open or closed position.
Terminal
compartment
Control Module
Type Label
Option: 1 or 2
speed control
throttles
Lockable
Module cover
Pneumatic connections:
1/4”BSP or 1/4”NPT
Button board
Electrical entries:
3/4”NPT
or M20
1/2”NPT
or M20
Terminals
bus signal
Option: Local
Manual Control
Option: Additional Local
Manual Control for “Fail in
Last Position”
Fig. 2. Control module overview
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 3 of 12
October 2015
Date:
FieldQ
General specifications:
Communication Protocol:
Material housing:
Aluminium alloy
Operating media:
Air or inert gasses, filtered at 5µm
Pneumatic entry:
Metric units: G1/4"
Imperial units:1/4”NPT
Electrical connections : Internal 3 pole terminal strip for
bus signal
Internal and external earth
connection
Optional quick connectors: 7/8" or
M12 connector (see page 9)
Cable entries:
Metric units: 2x M20x1.5
Imperial units:1/2” and 3/4"NPT
Enclosure:
Rated IP66 - NEMA4X
Switch points:
Factory set at 15° before each
end of travel (open and closed
position).
- Adjustable range:
Between -3° to 15° and +75° to
+93° of the end position.
Finish:
Chromated with polyurethane
based coating.
Temperature range: -20°C to +50°C (-4°F to +122°F)
Protocol :
Transmission : Maximum current : Required external : protection current Dimensions:
Metric:
Imperial/UNC:
DIN 3337:
See data sheet 1.603.08
See data sheet 1.603.09
See data sheet 1.603.10
Electrical safety requirements:
Use:
Altitude:
Maximum relative:
humidity
In- and outdoor.
Operating full power available up
to 2000 meter (6000 feet).
80% for temperatures up to 31°C
(87.8°F) decreasing linearly to
50% relative humidity at 40°C
(104°F).
Up to ±10% of nominal voltage
FOUNDATION™-Fieldbus
H1, IEC 61158-2
18mA from bus
Restrict the power supply
to <600mA.
Function blocks
The Control Module provides the following function blocks:
- Resource Block (RB)
- Transducer Block (TB)
- Analog Input (AI) Function Block
- Discrete Output (DO) Function Block
- 2x Discrete Input (DI) Function Block
- PID Function Block
Diagnostics and Alerts
Standard FOUNDATION™- Fieldbus diagnostics and
alerts provided meets Emerson PlantWeb Alerts standard.
Applicable diagnostics include:
- Travel times for the Open stroke, Close stroke and
Average travel times.
- Cycle Counters for Control Module, Pneumatic
Module, Actuator and Valve
- Time in Position
- Various internal electronic health tests.
- Instrument temperature.
For more detailed information on diagnostics see page 10
and 11.
Mains supply:
fluctuation
Over voltage category: II
Pollution degree:
2 (3 when the cover remains
closed)
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 4 of 12
October 2015
Date:
FieldQ
Pneumatic control
Pneumatic control variations
The Control Module contains all the necessary pneumatic
components to control the actuator and control the
incoming and outgoing airflow. Pneumatically the modules
are available for three applications:
1 Spring return or
2 Double acting or
3 Double Acting - "Fail-in-Last-Position".
To achieve these functions, each Control Module can
be fitted with one or two pilot valves depending on the
required functionality:
1 One pilot valve is default and suitable for normal
operation of double acting or spring return actuators
2 Two pilot valves are required to achieve a "Fail-inLast-Position" functionality on double acting actuators.
Terminals
FOUNDATION
Field bus
Cartridge
Pilot valve 1
Cable range:
0.2 - 2.5mm2 or 30-12AWG
Fig. 4. One pilot valve and wiring connections for standard
Double Acting or Spring Return applications
Terminals
FOUNDATION
Field bus
Cartridge
Pilot valve 1
Pilot valve 2
Cable range:
0.2 - 2.5mm2 or 30-12AWG
Pneumatic cartridge
FOUNDATION™
Fieldbus cartridge
Terminals
bus signal
Fig. 5. Two pilot valves and wiring connections for Double
Acting "Fail in Last Position" applications
Fig. 3. Pilot valve and pneumatic cartridge
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 5 of 12
October 2015
Date:
Pneumatic components
The pneumatic components inside the module consist
out of one or two pilot valves and a 3/2 spool valve or 5/2
bistable spool valve. The spool valves are pneumatically
operated by the pilot valves.
To assure trouble-free operation, the spool valves are
equipped with big ports. This enables a large air flow and
makes it less sensitive for contamination of the internals.
The large air flow also fast cycle times and enables it to be
utilized for the entire Q-Series Series actuator range.
Internal corrosion protection:
The spring return models have standard a built in
“Breather” function. During the spring stroke, the exhaust
air from the center chamber (A-Port) is first fed to the
spring chamber (B-port) preventing air from outside from
being sucked into the spring chamber. This reduces
the possibility of internal corrosion and maximizes the
actuators’ working life.
FieldQ
Fail safe
(spring return)
A-port
B-port
Option: Throttle 1
3/2 Spool valve
Option: LMC
Ps
Ra
Pilot valve 1
Double acting
Pneumatic options
Speed Control
The QC54 control module can be supplied with a Speed
Control option. One throttle is required for Spring Return
actuators and up to two for Double Acting actuators.
The speed control throttle controls the air flow in and out
of an air chamber and as such limits the speed of the
“Opening” and “Closing” stroke simultaneously.
A-port
5/2 Spool valve
Rb
Ps
Ra
Pilot valve 1
The exhaust ports Ra and Rb on the module are shipped
from the factory with transport protection.
The module can be equipped with either silencers or
vents.
For commissioning, emergency or maintenance purposes,
the QC54 control module can be supplied with Manual
Control options. These options can operate the actuator
when there is air pressure available, but no control signal
or power supply.
- For normal operation the module should be fitted with
one Manual Control.
- For Double Acting with a Fail-in-Last-Position function,
two Manual Control can be fitted.
Option:
Throttle 2
Option: LMC
Silencers and vents
Manual Control
B-port
Option:
Throttle 1
Double Acting
Fail in Last
Position
A-port
Option:
Throttle 1
B-port
Option:
Throttle 2
5/2 Spool valve
Option: LMC 1
Option: LMC 2
Ps
Rb
Ra
Pilot valve 1
Fig. 6. Pneumatic operation
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Pilot valve 2
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 6 of 12
October 2015
Date:
FieldQ
Switch point setting
The QC54 control modules are equipped with a button
board that allows you to set or readjust the switch points
for the position feed back.
Closed reassignment button
Status LED
Press and
confirm press
Open reassignment button
on
LED = Flashing
off
Auto-Initialization
Initialization sets automatically the switch points for
the position feedback of the actuator and checks if the
actuator and control module configuration match. This
procedure will detect the action type (Fail-Open, FailClose or Fail in last position) and generate an alert if
there are configuration issues.
This process is done automatically, by the module,
however, the user must start it and the unit must be wired
and powered.
Digital communication is not required but power supply is
necessary (9V to 32V DC). The initialization process can
be started in one of two ways:
1. Initialization using the local buttons (see fig. 7).
2. Initialization using a bus command (see Reference
manual QC54, DOC.RM.QC54.E)
Indication LED's
on
LED = Blinking
off
Time
* The default setting of the reassignment buttons is: enabled when
the unit is in “Out of Service”.
* ”Open” and “Closed” LED are disabled.
Fig. 7. Button board
Button board functions:
Initialization button:
Start Auto-Initialization procedure
Re-adjustment of the "Closed" switch point
Close button:
Set to factory settings
Re-adjustment of the "Closed" switch point
Open button:
Set to factory settings
End stop
offsets
End stop offsets
Recognize Function
An additional function of the Status LED is the recognize
function. To recognzie a particular unit in the plant, the
"Recognizing LED" function can be activated in the
transducer block. When this function is activated, the
Status LED will blink for 300 seconds (5 minutes).
Changing Switch Point Setting
Readjustment of switch points
10°max
“Close”
end
position
±40°
±40°
Three indication LED's for "Status", "Open" and "Closed"
position are available. The status LED indicates:
- Initialization procedure running (blinking),
- Successful initialization procedure (LED is on) or
- No or failed initialization (flashing)
10°max
When switch point re-adjustment is required but it is
not allowed that the actuator/valve unit cycles, the new
switch point can be set by pressing the corresponding
"Open" or "Closed" button.
Factory settings
Pressing both the Open and Close reassignment buttons,
while powering up, will set the module back to its factory
settings.
“Open”
end position
Factory settings
Setting after initialization
Fig. 8. Switch point setting
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 7 of 12
October 2015
Date:
FieldQ
Control Module Options
Local Manual Control
Speed Control
Description
Description
For commissioning, emergency or maintenance purposes,
the QC54 control module can be supplied with one or
two Manual Control options. These can operate the
pilot valve(s) inside the module and as such operate the
actuator, when there is air pressure available, but no
control signal or power supply.
The QC54 control module can be supplied with a Speed
Control option. One throttle is required for Spring Return
actuators and up to two for Double Acting actuators.
The speed control throttle controls the air flow in and
out of an air chamber and as such limits the speed of
the “Opening” and “Closing” stroke simultaneously. This
throttle consists of :
1 Nut cover
2 Main throttle with set screw.
Notes:
-
-
-
-
One Local Manual Control is required for normal
operation of Double acting or Spring return actuators.
For Double acting actuator with a Fail-in-last position
function, a second Local Manual Control can be
mounted.
These options can be ordered together with the
Control Module or as a kit to be mounted later.
For option ordering codes, see page 7
Note:
-
-
-
For Spring Return actuators with one speed control
throttle, it is not possible to set both the stroke cycle
times to an equal time.
Four Double Acting actuators it is possible to mount
two speed control throttles.
The actual stroke cycle times depend on the actual
load on the actuator during the different strokes.
Spring Return:
Top entry only.
Double Acting:
Bottom and/or top entries.
Location for 2nd
Local Manual Control
Lock
Default location of
Local Manual Control
45°
Unlock
On
1
Off
Fig. 9. Local Manual Control option
Fig. 10. Speed control options
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
2
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 8 of 12
October 2015
Date:
FieldQ
Wiring and Quick Connectors
FOUNDATION™ Fieldbus terminal wiring
Wiring for hazardous areas
The QC54 module can be connected to the system
by hard wiring the module to the terminals The QC54
Module can optionally be equipped with prewired quick
connectors. Two versions are available: 7/8” or M12 (male
chassis part).
Detailed safe area, Intrinsically safe or Non-Incendive/
Non-Sparking wiring instructions, will be shipped with the
product, see Installation Guide : DOC.IG.QC54.1
Field wiring
Quick connectors, as shown are excluded for nonIncendive or non-sparking use in hazardous area’s
classified as Zone 2 or 22 or Cl I, II, III, Div. 2.
Actuator wiring
+ 1
FF
Power
supply
Quick connectors
Wiring dimensions
2
- 3
Solid wire Stranded wire
:2.5mm2 max.
:0.2-3.3mm2 or 24-12 AWG
Quick connector pinouts:
(male chassis part)
1
3
2
4
7/8" UNC
4
1
3
2
2
4
1
Blue
1
Brown
2
Green/Yellow
M12
Quick
connector
3
Terminal
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 9 of 12
October 2015
Date:
FieldQ
Diagnostics and PlantWeb Alerts
QC54 FOUNDATION™ Fieldbus
Diagnostics
PlantWeb Alerts
The Q-Series QC54 Control Module with FOUNDATION™
Fieldbus communication has diagnostic capabilities.
These process parameters can give information about
communication condition, valve and/or actuator unit.
It enables to predict failures in advance and makes
maintenance easier to schedule. The following diagnostics
are available for the QC54 control module:
PlantWeb Alerts are alerts that have been predefined and
categorized for the user. These device alerts can be used
to help troubleshoot the instrument (see also page 4).
There are three categories:
-
Failed alerts,
A failed alert indicates a failure within the device that
will make the device, or some part of the device, nonoperational.
1 Timer parameters:
1
Open and Closed travel time
2
High and low limits of Open and Closed
travel time
3
Average travel times of last 30 strokes of
Open and Closed travel.
4
High and low limits of average Open and
Closed travel time
-
Maintenance alerts
A maintenance alert indicates that the device, or some
part of the device, needs maintenance soon.
-
Advisory alerts
An advisory alert indicates a condition that does not
have a direct impact on the device’s primary function.
If the condition is ignored, the device will eventually
fail.
2 Cycle Counters
1.
Control Module - Counts how many times
the Control Module cycles (read only).
2.
Pneumatic Module - Counts how many times
the Pneumatic Module cycles.
3.
Actuator - Counts how many times the
actuator cycles.
4.
Valve - Counts how many times the valve
cycles.
These alerts, when enabled, can participate in the DeltaV
alarm interface tools such as the alarm banner, alarm list,
and alarm summary.
3 Time In Position
5 Various internal electronic health tests.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 10 of 12
October 2015
Date:
FieldQ
Diagnostics and PlantWeb Alerts
Alerts & recommended actions
Alert default setting
Advisory
Alerts
Recommended actions
bit 0
Reserved
bit 1
Internal alerts, bad position sensor
bit 4
Internal alerts, bad temperature
sensor
Internal alerts, Specified system
temperature exceeded
Internal alerts, Software error
bit 5
Internal alert, travel deviation
bit 6
Internal alerts, Shutdown is set
bit 7
Internal alerts, Undefined error
Counter alerts, Control Module life
cycle exceeded
Counter alerts, Pneumatic Module
life cycle exceeded
Counter alerts, Actuator life cycle
exceeded
Counter alerts, Valve life cycle
exceeded
bit 2
bit 3
bit 8
bit 9
bit 10
bit 11
bit 12
Timer alerts: time in position limit
bit 16
Timer alerts: open travel time limit
exceeded
Timer alerts: close travel time limit
exceeded
Initialization Failed (reason from
AUTO_INITIALIZATION STATUS)
Reserved Primary Value Failure
bit 18
Reserved HW/SW Incompatibility
bit 13
bit 14
bit 15
Feedback problem, replace control
module when possible
Temperature sensor problem, replace
Control Module when possible
Take corrective actions to bring temperature within specified range.
Lost position, Check air pressure
Internal communications problem,
check shutdown configuration for
restart, Replace Control Module.
Control Module life cycle exceeded,
Replace Control Module
Pneumatic Module life cycle exceeded, Replace Pneumatic Module.
Actuator life cycle exceeded, Replace actuator.
Valve life cycle exceeded, take Valve
requires maintenance.
Time in position exceeded, appropriate action.
Open travel timer exceeded, check
valve system.
Close travel timer exceeded, check
valve system.
Check air pressure, check actuator
sizing, check valve system.
Internal communications are lost,
Reserved IO Failure (FF card lost IO
bit 19
device will act according to shutdown
board)
configuration.
bit 20
Reserved Mechanical Failure
Maintenance
Fail
enable
mask *
enable
mask *
enable
mask *
n
n
y
y
n
n
n
y
y
n
n
n
y
y
n
n
n
y
n
n
n
y
y
n
n
n
n
n
n
n
n
y
n
n
y
n
n
n
n
y
y
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
y
y
n
n
n
n
n
n
n
n
y
y
n
n
n
n
n
n
y
n
n
n
n
n
n
n
n
n
n
n
bit 21
Reserved TB NV Memory Failure
bit 22
Reserved RB NV Memory Failure
y
y
n
n
n
n
bit 23
Reserved TB Electronics Failure
y
n
n
n
n
n
bit 24
Reserved RB Electronics Failure
y
y
n
n
n
n
(*) Mask “n” indicates masked out (not visible).
For more detailed information about the configuration of the QC54 Foundation Fieldbus Module see Reference Manual
DOC.RM.QC54.E. This manual is available for download from www.FieldQ.com.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 11 of 12
October 2015
Date:
FieldQ
Control Module Configuration:
QC54.UWPG SA1.0040 INS0 IP 01
Sample code:
QC54 • UWPSSA1 • 0150INS0IP01
Top entry glands and plugs
-Control module with
Bottom entry glands and plugs
FOUNDATION™ Fieldbus
Pneumatic exhaust
•
Manual Control
-Imperial unit with 1/2"NPT and
Speed control
3/4"NPT electrical entries and
Mounting Options
1/4"NPT pneumatic entry.
-Weather Proof
IPT Device size actuator
-Standard control module
Language
-Suitable for Spring Return actuators
Future Expansions
•
Action
-With IPT probe for Q0150 size
Control module options
actuator
-Installed to actuator.
Protection method
-No speed control option
Conduit connections
-No manual control option
Control module
-With IP65/NEMA4 exhaust
-Transport plug in bottom entry
-Metal blind plug in top entry
Control Module Type
QC54 Foundation Fieldbus communication
●
Conduit connections
M
2x M20 x 1.5
U
Top: 3/4"NPT, Bottom: 1/2" NPT
Protection method
WP
Weatherproof: IP66/NEMA4X (no approvals)
Control Module Switch Type
S
Standard configuration (only for QC54)
Module Action
S
Single acting
D
Double acting
F
Double Acting Fail in Last Position
Future Expansion
A
Standard Yellow
Language Code
1
English
●
IPT probe size for actuator
0040 Q40 actuator
0065 Q65 actuator
0100 Q100 actuator
0150 Q150 actuator
0200 Q200 actuator
0350 Q350 actuator
0600 Q600 actuator
0950 Q950 actuator
1600 Q1600 actuator
0000 No IPT probe
Mounting Options
I
Installed On Actuator
U
Uninstalled
Speed control
NS
No Speed Control
N1
Spring Return (1x throttle)
N2
Double acting (2x throttle)
Manual Control
0
No Manual Control
1
1 x Manual Control (Push&Lock)
2
2 x Manual Control (Push&Lock)
Pneumatic exhaust
IP
IP65/NEMA4 rated exhaust
IN
Non metalic exhaust / Check valve
ZZ
Special exhaust
Glands & Plugs (see note 1)
Bottom entry
0
Transport plug
1
Metal blind plug
2
Plastic Gland
3
Metal Gland
4
Eurofast (M12)
5
Minifast (7/8”)
Top entry
0
Transport plug
1
Metal blind plug
2
Plastic Gland
3
Metal Gland
4
Eurofast (M12)
5
Minifast (7/8”)
Note:
1 The options below are all options available. Not all options apply to
all configurations.
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.604.12 - Rev: 0, Page 12 of 12
Date:
October 2015
FieldQ
Namur NE-107 Alarms
This section describes the parameter interaction to implement
a FieldQ™ QC54 Control module to the NAMUR NE-107
requirements as a parameter group in the Resource Block.
There are four alarm categories defined as per the NE-107
specification, Failed, Off Specification, Maintenance, and
Check function.
Maintenance Although the output signal is valid, the wear
reserve is nearly exhausted or a functions will soon be restricted due to operational conditions e.g. build-up of deposits
Off Specification Off-spec means that the device is operating outside its specified range or an internal diagnostic indicates deviations from measured or set values due to internal
problems in the device or process characteristics (e.g. bubble
formation in flow metering or valve sticking).
Check Function Output signal temporarily invalid (e.g.
frozen) due to on-going work on the device.
Failed Output signal invalid due to malfunction in the field
device or its peripherals.
Parameter
Mnemonic
FD_CHECK_ACTIVE
Obj
Type
S
Data Type/
Structure
Bit String
Use/Model
Store
Each of these categories share 32 conditions that can be
defined by the device manufacturer. Each condition may be
mapped or not mapped for each category. If a condition is
mapped then it is indicated in the* ACTIVE parameter. If the
condition in the * ACTIVE parameter is not masked by the
corresponding bit in the *_MASK parameter then the condition will be queued for broadcast using the corresponding
*ALM parameter at the associated priority indicated by *PRI
parameter. The 4 categories are defined below.
The conditions are not expected to identify explicitly the root
cause of the condition, but rather to identify it in terms of:
• Replace the device
• Replace a part of the device
• Correct a configuration problem
• Fix something outside of the device
The above list is all that the operator needs to know to restore
his process functionality and if there are more than 31 device
conditions they should be grouped by definition into these bit
Size
Valid
Range
Initial
Value
C/FD Active
D
4
FD_CHECK_ALM
R
DS-87
C/Alarm
D
15
FD_CHECK_MAP
S
Bit String
C/Contained
S
4
FD_CHECK_MASK
S
Bit String
C/Contained
S
4
FD_CHECK_PRI
S
Unsigned8
C/Alert Priority
S
1
FD_EXTENDED_ACTIVE_n
S
Bit String
C/Contained
D
4
FD_EXTENDED_MAP_n
S
Bit String
C/Contained
S
4
FD_FAIL_ACTIVE
S
Bit String
C/FD Active
D
4
FD_FAIL_ALM
R
DS-87
C/Alarm
D
15
FD_FAIL_MAP
S
Bit String
C/Contained
S
4
FD_FAIL_MASK
S
Bit String
C/Contained
S
4
FD_FAIL_PRI
S
Unsigned8
C/Alert Priority
S
1
FD_MAINT_ACTIVE
S
Bit String
C/FD Active
D
4
FD_MAINT_ALM
R
DS-87
C/Alarm
D
15
FD_MAINT_MAP
S
Bit String
C/Contained
S
4
FD_MAINT_MASK
S
Bit String
C/Contained
S
4
FD_MAINT_PRI
S
Unsigned8
C/Alert Priority
S
1
FD_OFFSPEC_ACTIVE
S
Bit String
C/FD Active
D
4
FD_OFFSPEC_ALM
R
DS-87
C/Alarm
D
15
FD_OFFSPEC_MAP
S
Bit String
C/Contained
S
4
FD_OFFSPEC_MASK
S
Bit String
C/Contained
S
4
FD_OFFSPEC_PRI
S
Unsigned8
C/Alert Priority
S
1
0 - 15
0
FD_RECOMMEN_ACT
S
Unsigned16
C/Contained
D
2
0
FD_SIMULATE
R
DS-89
C/FD Simulate
D
9
1 – manf
spec
FD_VER
S
Unsigned16
C/Contained
S
2
Permission
Other
Read only
Range
Check
ALARM
ALARM
0 - 15
0
ALARM
Yes
Read only
Read only
ALARM
ALARM
0 - 15
0
ALARM
Yes
Read only
ALARM
ALARM
0 - 15
0
ALARM
Yes
Read only
ALARM
ALARM
ALARM
Yes
Read only
disabled
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Read only
Product data sheet
Sheet No.: 1.604.50 - Rev: A
September, 2006
Date:
FieldQ
Control Module Options
Electrical entry options
Manual Control
Description
Description
FieldQ Control Modules are shipped from factory with plugs
in the electrical entries. These transport plugs avoid moisture
or particles entering the module during transport and installation.
For installation purposes, FieldQ Control Modules can be fitted with glands, plugs or connectors in the electrical entries.
Option ordering codes
Modules QC01, QC02, QC03 and QC04
Code : Bottom entry
Code :
0X
Transport plug
X0
1X
Metal blind plug
X1
2X
Plastic gland
X2
3X
Metal Gland
X3
Module QC30 and QC34
Code : Bottom entry
Code :
0X
Transport plug
X0
1X
Metal blind plug
X1
2X
Plastic gland
X2
3X
Metal Gland
X3
4X
Eurofast (M12)
X4
5X
Minifast (7/8”)
X5
Top entry
Transport plug
Metal blind plug
Plastic gland
Metal Gland
Top entry
Transport plug
Metal blind plug
Plastic gland
Metal Gland
Eurofast (M12)
Minifast (7/8”)
Notes:
- The glands are suitable for cables from 6 to 12mm (1/4” to
1/2”).
- Standard plastic glands will be black. For Intrinsically safe
units, these glands will be blue.
- For Quick Connector details see data sheets 1.604.02
(QC34;FF) or 1.604.04 (QC30;ASI).
Electrical entry
options
For commissioning, emergency or maintenance purposes, the
FieldQ can be supplied with Manual Control options. These
options can operate the actuator when there is air pressure
available, but no control signal or power supply. Two versions
are available:
1 “Push” version. Pressing the spring return button will operate the actuator. Releasing the button will bring back the
actuator in its original position.
2 “Push & Lock” version. To operate this optional Manual
Control, use a screw driver (0.8x4mm). Push and turn it
90°, to lock it in position and keep the actuator in its operated state.
It is possible to rotate the screw multiple cycles. The unit
will toggle every 90° between “locked” (1) and “unlocked”
(0).
These options can be ordered together with the Control Module or as a kit to be mounted later.
Materials
- Push version
- Push & Lock version
: Red anodized aluminum
: Red anodized aluminum
Option ordering codes
For modules QC01, QC02, QC03, QC04 , QC30 and QC34
Code :
Description:
0
No Manual Control
1
Manual Control (Push)
2
Manual Control (Push&Lock)
Manual Control options
Top entry
Bottom entry
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.605.01 - Rev: B, Page 1 of 2
September, 2010
Date:
FieldQ
Pneumatic Module
Description:
The Pneumatic Module is the pneumatic interface between
the Control Module and the actual actuator. It controls the
incoming and outgoing airflow. These modules are available
in two basic executions:
- Single acting (for spring return actuators)
- Double acting
Manual Control
Exhausts
Valve block:
The Pneumatic Module contains a valve block with two or
four diaphragm/poppet valves (for single acting or double
acting executions) . The valves are operated by a pilot valve
in the Control Module.
To assure trouble-free operation, the valve block is equipped
with big ports. This enables a large air flow and to makes it
less sensitive for contamination of the internals. The large air
flow also enables it to be utilized for the entire FieldQ range.
Pneumatic
Module
-Push
- Push and lock
For more detailed information see data sheet 1.604.50
Options
Silencers and vents
The Pneumatic Module can
be equipped with either silencers or vents. Dedicated
IP65/NEMA4x rated vents
are available.
Air supply
Manual Control
For commissioning, emergency or maintenance purposes, the
FieldQ can be supplied with Manual Control options. These
options can operate the actuator when there is air pressure
available, but no control signal or power supply. Two versions
are available:
Breather Function:
The spring return models have standard a built in “Breather”
function. During the spring stroke, the exhaust air from the
center chamber is first fed to the spring chamber preventing
air from outside from being sucked into the spring chamber.
This reduces the possibility of internal corrosion and maximizes the actuators’ working life.
Speed Control
Two integrated speed control options are available:
1Speed control which throttles the air flow in one direction
(exhausted air).
2Speed control which
Ps = Pressure supply
throttles the air flow in
Ra =Exhaust
Rb =Exhaust
both directions (supplied
Pvv = Pilot valve vent
and exhausted air).
Opv= Over pressure vent
For more information on
speed control see sheet
Options:
1.605.02 page 2.
SC = Speed control
Speed
control
Double Acting
Pneumatic Plan
Single Acting (Spring
Return) Pneumatic Plan
MC=Manual Control
Breather
function
Pvv
Ps
Ra
SC
2/2 NC
Rb
SC
2/2 NO
2/2 NC
Pvv
Opv
2/2 NO
Pmo
Ps
Pneumatic
Module
Control
Module
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Ra
Rb
Opv
SC
2/2 NC
2/2 NO
Pmo
Product data sheet
Sheet No.: 1.605.01 - Rev: B, Page 2 of 2
September, 2010
Date:
FieldQ
Specification Pneumatic Module
Function
:Double or Single Acting (spring return)
“Breather” function:Standard for single acting actuators
Pressure range
- Double acting :2 to 8 bar g / 30 to 120psig
- Spring return
:6 to 8 bar g / 87 to 120psig with
maximum spring set.
:3 to 8 bar g / 43 to 120psig with
reduced spring set.
Enclosure
:IP65/NEMA4X
Air entry
:G1/4” or 1/4”NPT
Exhaust ports
:G1/4” or 1/4”NPT
Operating media
Air or inert gasses, filtered at 50 micrometer. The following
Control Modules require air filtered at 5 micrometer: QC03,
QC04, and QC34. See applicable data sheets 1.604.xx.
Temperature
Depends on the utilized Control Module. See applicable data
sheets 1.604.xxx.
Base Materials
Body
Aluminium
Valve housing
30% glass-filled Nylon
Finish
Polyester non-TGIC based powder coating
Valve seats
Buna-N
Membrane
Buna-N
Fasteners
Stainless Steel
Optional parts
1
Plug
2
Vents
3
Exhaust
4
6
1
4
5
NPT
Steel, zinc plated
BSP
Brass, nickel plated
Stainless Steel (AISI 303)
Base
Nylon
Cover
Zinc Nickel plated and transparent passivated
Option
Plastic silencer (nylon)
Speed Control
- Throttle
Stainless Steel (AISI 303)
- Nut Cover
Nylon PA6
5
Plug
Brass Nickel plated
6
Manual Control
2
- Plug
Brass Nickel plated
3
- Push
Red anodized aluminum
- Push & Lock
Red anodized aluminum
Maximum Flow rates of FieldQ pneumatic modules
- The maximum flow rates depends mainly on the flow rates
of the applied FieldQ pneumatic module
Pneumatic
Module
Double acting
Single acting
Stroke
Outward
Inward
Air
Spring
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
L/min.
350
365
350
240
Flow rates
KV =
4.7
4.9
4.7
3.2
Cv =
0.33
0.34
0.33
0.23
Product data sheet
Sheet No.: 1.605.02 - Rev: A Page 1 of 2
September, 2006
Date:
FieldQ
Pneumatic Module Options
Speed Control on FieldQ actuators
Speed control on spring return actuators
On spring return actuators only the
“central” air chamber is pressurized and
vented. Therefore both the “One-Way” or
the “Two-Way” throttles must be mounted
in the port for the central air chamber port
(1). Port (2) must be plugged.
Two integrated speed control options are available:
A “One-way” Speed control throttle
This throttle controls only the air flow exhausted from an air
chamber and as such limits the speed of the “Opening” or
“Closing” stroke (see table “Speed control configuration”).
It consists of :
1 Nut cover
2 Main throttle with set screw
3 Spring loaded counter part
1
1
2
2
Speed control on double acting actuators
On double acting actuators both the
“central-” and “end cap” air chambers are
pressurized and vented. Therefore both
the “One-Way” and “Two-Way” throttles
can be mounted in either ports (1) or (2).
B “Two-way” Speed control throttle
This throttle controls the air flow in and out of an air chamber
and as such limits the speed of the “Opening” and “Closing”
stroke simultaneously (see table “Speed control configuration”). It consists of :
1 Nut cover
2 Main throttle with set screw.
Note:
With the “Two-Way” speed control it is not possible to set both
the stroke cycle times to an equal time.
The actual stroke cycle times depend on the actual load on
the actuator during the different strokes.
CASTROL LMX or
FINA CERAN WR2
or equivalente
3
2
A
Ps = Pressure supply
Ra =Exhaust
Rb =Exhaust
Pvv = Pilot valve vent
Opv= Over pressure vent
Double Acting
Pneumatic Plan
Options:
SC = Speed Control
MC = Manual Control
2
B
1
1
Single Acting (Spring
Return) Pneumatic Plan
Breather
function
Pvv
Ps
Ra
SC
2/2 NC
Rb
SC
2/2 NO
2/2 NC
Pvv
Opv
2/2 NO
Pmo
Ps
Pneumatic
Module
Ra
Rb
Opv
SC
2/2 NC
2/2 NO
Control
Module
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Pmo
1
1
2
2
Product data sheet
Sheet No.: 1.605.02 - Rev: A Page 2 of 2
September, 2006
Date:
FieldQ
Speed control configuration (see table below)
As indicated, the throttles can be mounted in the port, for the
central air chamber(1) or the end cap air chambers(2).
How the actuator functions depends on
* the action (spring return or double acting)
* the assembly code (Spring to Close or Spring to Open)
* which throttle is applied (One way” or “Two way).
Please see the table below to select the required speed control configuration.
Central air chamber port
End cap air chambers port
“Opening” or “Closing” stroke
* Whether the speed of the “Opening” or “Closing” stroke is
limited, depends on the assembly code of the actuator.
Independently adjusting of the “Opening” or “Closing”
stroke speed
* The speed of the “opening” stroke and “closing” stroke on
double acting actuators with 2x “One-Way” throttles can be
set independently from each other.
Speed control and actuator sizing
Installing a Speed control option can result in a non-smooth
operation of the actuator (“Stick - Slip” behaviour). This behaviour can happen when the actuator size is to small for the
application. Selecting an actuator 1 size larger will solve this
“Stick - Slip” behaviour.
Speed control configuration
Option
code
QP
Q1
Q2
Q3
Q4
Plug
in air
chamber
port
Central
Plug
End cap
Throttle or Plug
“One way SC”
Central
Plug
End cap
“Two way SC”
Central
Plug
End cap
“One way SC”
Central
“One way SC”
End cap
Plug
Central
“One way SC”
End cap
Spring return actuators
Air Fail to Close
Air Fail to Open
(Code CW)
(Code CC)”
Standard”
No Speed Control
No Speed Control
Double acting actuators
(Code CW)
Standard
(Code CC)
No Speed Control
No Speed Control
Clock wise stroke Counter Clock wise Clock wise stroke
(closing)
stroke (opening)
(closing)
Both strokes simul- Both strokes simul- Both strokes simultaneously adjusttaneously adjusttaneously adjustable
able
able
Both strokes indeNot applicable
Not applicable
pendently adjustable
Counter Clock wise
Not applicable
Not applicable
stroke (opening)
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Counter Clock wise
stroke (opening)
Both strokes simultaneously adjustable
Both strokes independently adjustable
Clock wise stroke
(closing)
Product data sheet
Sheet No.: 1.606.01 - Rev: C Page 1 of 2
Date:
May 2014
FieldQ
FieldQ valve actuator
Parts and materials Actuator and Modules
Description
Body
Pinion
Upper pinion part
Guide band housing
Washer pinion
Bearing ring
Limit stop cam
Piston
End cap QS
End cap QD
Guide band piston
O-ring piston
O-ring end cap
O-ring upper pinion part
O-ring pinion top
O-ring pinion bottom
O-ring B-port
O-ring retainer bolt
O-ring limit stop bolt
Outer spring
Middle spring
Inner spring
Spring retainer
Washer spring pack
Spring pack retainer bolt
Washer
Nut
Nut cover
End cap screws
Retaining ring pinion large
Retaining ring pinion small
Limit stop screw
Indicator cap
Indicator arrow
Indicator insert
Type plate
Hammer drive
Insert
Qty. Description
1
Aluminum Alloy
1
Aluminum Alloy
1
Aluminum Alloy
2*
Nylatron
2*
CRMZX100
2*
Delrin®
1
Steel
2
Aluminum Alloy
2
Aluminum Alloy
2
Aluminum Alloy
2*
PTFE, Carbon filled
2*
Nitrile Rubber
2*
Nitrile Rubber
1*
Nitrile Rubber
1*
Nitrile Rubber
1*
Nitrile Rubber
2*
Nitrile Rubber
4*
Nitrile Rubber
2*
Nitrile Rubber
2
Carbon Spring Steel
2
Carbon Spring Steel
2
Carbon Spring Steel
2
Steel
2
Steel
2
Stainless Steel
4*Nylon
4
Stainless Steel
2
Polyethylene
8
Stainless Steel
1*
Carbon Spring Steel
1*
Carbon Spring Steel
1
Stainless Steel
1
Nylon
1
Nylon
1
Nylon
1
Stainless Steel
1
Stainless Steel
1
Aluminum Alloy
Specification
EN AC-AlSi10Mg (Cu)
EN AW 7075 T6
EN AW 7075 T6
PA6.6 + MoS2
-
POM
42CrMo4V
EN AC-AlSi7Mg
EN AC-AlSi7Mg
EN AC-AlSi7Mg
PTFE + 25% C
NBR
NBR
NBR
NBR
NBR
NBR
NBR
NBR
EN 10270-1 SH
EN 10270-1 SH
EN 10270-1 SH
St. DC01 EN10139
C35
AISI 304 (DIN W nr 1.4301)
PA6
AISI 304 (DIN W nr 1.4301)
PE
AISI 304 (DIN W nr 1.4301)
C45, DIN 17200
C45, DIN 17200
AISI 304 (DIN W nr 1.4301)
PA6
PA6
PA6
AISI 303 (DIN W nr 1.4305)
AISI 303 (DIN W nr 1.4305)
EN AW 6082 T5
Notes
1/5
2
2
6
1
1
3
3
3
4
4
3
3
5
Notes
1 See Corrosion protection below
2 Hard anodized.
3Deltatone® or Epoxy (black) coating.
4 Zinc plated and passivated.
5Anodized.
6Chromatized
Control & Pneumatic Modules
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
For material specification of
the Pneumatic Modules see
page 2
Corrosion protection
The applied paint system
has passed a 1000 hour salt
spray test as detailed by
ASTM B117. For a detailed
description of the Corrosion
protection system see data
sheet 1.606.05.
Temperature ranges
The temperature range
of FieldQ actuators with
NAMUR plates depends
on the O-ring seals and the
utilized grease.
For a detailed description of
posible temperature ranges
and applied parts, see data
sheet 1.605.03
Repair kit
Parts marked with an * are
included in the repair kit
Product data sheet
Sheet No.: 1.606.01 - Rev: C Page 2 of 2
Date:
May 2014
FieldQ
FieldQ valve actuator
Parts and materials Actuator and Modules
Modules QC01, 02, 03, 04
Modules QC41, QC42, QC43
QC11, QC12, QC13, QC14
QC30, QC31 and QC34
6
3
1
2
3
1
2
4
5
Base Materials
Body:Aluminium
Valve housing:
30% glass-filled Nylon
Finish:
Polyester non-TGIC based powder
coating
Valve seats:
Buna-N
Membrane:Buna-N
Fasteners:
Stainless Steel
External parts
1 Plug
NPT:
BSP:
2 Vents:
3 Exhaust
Base: Cover:
Option:
4 Speed Control:
- Throttle:
- Nut Cover:Nylon
5 Plug:
6 Manual Control:
- Plug: - Push:
- Push & Lock: Steel, zinc plated
Brass, nickel plated
Stainless Steel (AISI 303)
Nylon
Zinc Nickel plated and transparent passivated
Plastic silencer (nylon)
Stainless Steel (AISI 303)
PA6
Brass Nickel plated
4
Base Materials
Bodies:Aluminium
Finish:
2 Component with an epoxy primer and
polyurethane enamel top coating.
Pneumatic cartridge:
Aluminium
Valve seats
NBR
Pilot valve cartridge:
Housing: Nylon PA6
Switch cartridge:
Housing: Nylon PA6
Fasteners
Stainless Steel
External parts
1 Plug
2 Exhaust
NPT:
Base :
Cover:
Steel, Nickel plated
Nylon PA6
Zinc, Nickel plated and transparent passivated
Option: Plastic silencer (nylon)
3 Speed Control:
Stainless Steel (AISI 303)
4 Manual Control:
Red anodized aluminum
5 Nut Covers: Nylon PA6
Brass Nickel plated
Red anodized aluminum
Red anodized aluminum
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.606.07 - Rev: A
May, 2006
Date:
FieldQ
FieldQ valve actuator
Corrosion protection system
Description:
The corrosion protection system of FieldQ pneumatic valve
actuators consist of the following treatments or materials:
1Pretreatment
The actuator housings are anodized inside and outside, to
give them a durable and superb protection against wear and
corrosion.
The anodized base layer, takes care of excellent bonding
between the aluminum surface and the coating.
Additionally the pistons are chromatized to prevent the corrosion of the internals.
2De-greasing
All aluminum parts are de-greased before the powder coating
is applied by washing with an alkaline solution to assure the
best bonding between the aluminum surface and the coating.
3 Powder coating
- Polyester non-TGIC based powder coating for exterior use.
- The powder coating is applied cold using automatic electrostatic spray equipment and is cured at minimum 190°C
(374°F) offering excellent light and weather resistance.
- The powder coating thickness is 80 micrometer (3.1 mils).
- Good chemical resistance against most bases, acids, solvents, alkalis and oils at normal temperatures.
- Excellent exterior mechanical durability.
- The coating shows no decline of actuator functions after
1000 hours salt spray test.
- The powder coating is virtually solvent free, and therefore
environmentally friendly.
Technical data:
Coating
Thickness
Salt spray test
Color
Materials
:Polyester non-TGIC based powder coating
:80 to 160 micrometer (3.1 to 6.2 mils).
:1000h (DIN 50021 / ASTM B117)
:Yellow
:Housing :Anodized aluminium alloy
:Pistons :Chromatized
:Pinion
:High grade aluminum alloy,
hard anodized
:Fasteners :Stainless steel or alloy
steel with Deltatone treatment
:Tag plate :Stainless steel
Housing:
Anodized aluminium alloy,
polyester non-TGIC based
powder coating
Pinion:
High grade aluminum alloy,
hard anodized
4 High grade & hard anodized aluminum pinion
Actuators with high grade & hard anodized aluminum pinions,
passed a 1000 hours salt spray test.
5
Stainless steel or Deltatone® treated external steel
parts.
External parts are stainless steel or steel alloy with a Deltatone® treatment
6
Corrosion protected springs on Spring Return actuators
All the springs of spring return actuator are Deltatone® or
epoxy (black) coated to prevent the corrosion of the springs
and assure a long cycle life.
Stainless steel Fasteners
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Product data sheet
Sheet No.: 1.606.02 - Rev: C
May 2008
Date:
FieldQ
FieldQ valve actuator
Failure modes
Valve rotation
Closed
Valves are normally manufactured so that:
1 The valve is closed
2 The valve is open
*) = views from above
:after a clock wise rotation*
:after a counter clock wise rotation*
Open
Position after a failure
The position of the actuator after a failure depends on:
1 Principles of operation Spring Return or Double Acting
2 Actuator assembly code
See 1.606.03 for Double Acting
See 1.606.04 for Spring Return
3 Kind of failure See table.
Principle
of
operation:
Assembly
code :
CW
Double acting
actuator
CC
Single acting actuator
(Spring Return)
CW
CC
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
Kind
of
failure :
Pressure
not defined
Signal
Closed
Supply voltage
Closed
Pressure
not defined
Signal
Open
Supply voltage
Open
Pressure
Closed
Position :
Signal
Closed
Supply voltage
Closed
Pressure
Open
Signal
Open
Supply voltage
Open
Product data sheet
Sheet No.: 1.606.03 - Rev: C
November 2007
Date:
FieldQ
B
B
A
A
Actuator assembly codes
Double acting assembly codes
2
Standard assembly code:
1
CW
(= Clock Wise Rotation)
Visual indicator mounted:
Optional assembly code:
2
1
A
2
2
A
A
B
2
2
1
I
B
Position
indicator
B
CC
Visual indicator mounted:
(= for In line position indication
Pinion
B
2
(= Counter Clock Wise Rotation)
I
(= for In line position indication
A
2
1
2
2
B
1
1
2
2
B
A
A
Pistons
2
1
Optional assembly code:
A
2
2
2
1
2
1
A
A
B
B
2
2
2
1
- Central air chamber (1) pressurized
- End cap air chambers (2) pressurized
All views are from above. Pistons are shown in inner position
2
2
1
C
A
1
2
A= Pilot valve operated in Control Module B= Pilot valve
not operated in Control Module B
CC
(= Counter Clock Wise Rotation)
Visual indicator mounted:
B (= for Cross line position indication
C
2
A
2
Optional assembly code:
CW
(= Clock Wise Rotation)
A
Visual indicator mounted:
(= for CrossBline position indication
B
2
2
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
2
Product data sheet
Sheet No.: 1.606.04 - Rev: B
October 2006
Date:
FieldQ
B
B
A
A
Actuator assembly codes
Single acting (Spring Return) assembly codes
2
Standard assembly code:
2
CW
1
(= Clock Wise Rotation / Spring to Close)
Visual indicator mounted:
Optional assembly code:
I
(= for In line position indication
Visual indicator mounted:
(= for In line position indication
Pinion
B
B
2
I
A
A
B
2
2
2
B
2
1
1
2
A
B
CW
C
2
A
B
(= Counter Clock Wise Rotation/ Spring
to Open)
Visual indicator mounted:
(= for Cross line position indication
2
2
1
1
2
CC
CC
A
A
B
B
1
2
2
2
1
A
A=
Pilot valve operated in Control Module -
Central air chamber (1) pressurized
B
B= Pilot valve
not operated in Control Module - Spring stroke (2)
All views are from above. Pistons are shown in inner position
2
1
2
Optional assembly code:
B
2
A
2
1
(= Clock Wise Rotation / Spring to Close)
A
Visual indicator mounted:
(= for Cross line position indication
B
2
2
2
Optional assembly code:
2
21
1
Pistons
A
CC
B
Position
indicator
A
A
2 Spring
(= Counter Clock Wise 1Rotation/
to Open)
2
2
www.FieldQ .com
Copyright © Emerson Process Management. The information in this document is subject to change without notice. Updated data sheets can be obtained
from our web site www.Fieldq.com or from your nearest Valve Automation Center:
America’s: +1 281 477 4100 (fax 477 2809) Europe: +31 74 256 10 10 (fax +31 74 291 09 38) Asia/Pacific: +65 650 14 600 (fax +65 626 80 028)
2
World Area Configuration Centers (WACC) offer sales support,
service, inventory and commissioning to our global customers.
Choose the WACC or sales office nearest you:
NORTH & SOUTH AMERICA
MIDDLE EAST & AFRICA
19200 Northwest Freeway
Houston, TX 77065
T +1 281 477 4100
F +1 281 477 2809
Av. Hollingsworth,
325, Iporanga Sorocaba,
SP 18087-105
Brazil
T +55 15 3238 3788
F +55 15 3228 3300
P. O. Box 17033
Dubai
United Arab Emirates
T +971 4 811 8100
F +971 4 886 5465
ASIA PACIFIC
No. 9 Gul Road
#01-02 Singapore 629361
T +65 6501 4600
F +65 6268 0028
No.1 Lai Yuan Road
Wuqing Development Area
Tianjin 301700
P.R.China
T +86 22 8212 3300
F +86 22 8212 3308
P. O. Box 10305
Jubail 31961
Saudi Arabia
T +966 3 340 8650
F +966 3 340 8790
24 Angus Crescent
Longmeadow Business Estate
East P.O. Box 6908;
Greenstone; 1616
Modderfontein, Extension 5
South Africa
T +27 11 451 3700
F +27 11 451 3800
EUROPE
www.emersonprocess.com/fieldq
Asveldweg 11
7556 BR Hengelo (O)
The Netherlands
T +31 74 256 1010
F +31 74 291 0938
All Rights Reserved.
We reserve the right to modify or improve the designs or
specifications of the products mentioned in this manual at any time
without notice. Emerson Process Management does not assume
responsibility for the selection, use or maintenance of any product.
Responsibility for proper selection, use and maintenance of any
Emerson Process Management product remains solely with the
purchaser.
©2015 Emerson Electric Co.
For complete list of sales and manufacturing sites, please visit
www.emersonprocess.com/valveautomationlocations
Or contact us at [email protected]
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement