Johnson Controls TCS, TCL, TVS, TVL Fan Powered VAV Terminals Installation, Operation & Maintenance
Below you will find brief information for Fan Powered VAV Terminals TCS, Fan Powered VAV Terminals TCL, Fan Powered VAV Terminals TVS, Fan Powered VAV Terminals TVL. These are fan powered VAV terminals designed for safe and reliable operation when installed and operated within its’ design specification limits. The equipment is supplied with a rectangular discharge and comes in two configurations: parallel flow and series flow. The equipment should not make contact with any structure located above or below the equipment without appropriate isolation. They come with electric heaters (if supplied) that are always mounted on the unit discharge opening.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
FAN POWERED VAV TERMINALS
INSTALLATION, OPERATION & MAINTENANCE New Release Form 130.13-NOM3 (708)
MODELS TCS, TCL, TVS & TVL
LD13847
2
FORM 130.13-NOM3 (708)
TABLE OF CONTENTS
SAFETY CONSIDERATIONS ........................................................................................................................4
INSPECTION .................................................................................................................................................5
STORAGE .....................................................................................................................................................5
PRE-INSTALLATION INSPECTION ..............................................................................................................5
SEQUENCE OF OPERATION .......................................................................................................................6
Parallel Flow ...........................................................................................................................................6
Series Flow .............................................................................................................................................6
INSTALLATION .............................................................................................................................................6
Clearances .............................................................................................................................................7
Hanging and Mounting Equipment Overhead ....................................................................................7
Duct Connections ..................................................................................................................................7
Critically Sound Applications ...............................................................................................................7
Coil Connections ...................................................................................................................................8
Electrical .................................................................................................................................................8
OPERATION ..................................................................................................................................................8
Start-Up ..................................................................................................................................................8
Power Requirements ...........................................................................................................................8
Primary Air Damper and Fan Adjustment ...........................................................................................8
Series Flow, PSC Motor with SCR .......................................................................................................9
Parallel Flow, PSC Motor with SCR .....................................................................................................9
Series Flow ECM Motor Balancing ....................................................................................................10
Commissioning ....................................................................................................................................10
Balancing .............................................................................................................................................10
Manual Fan CFM Adjustment ............................................................................................................. 11
Remote Fan CFM Adjustment ............................................................................................................ 11
Status LED ........................................................................................................................................... 11
MAINTENANCE .......................................................................................................................................... 11
Factory Provided Damper Actuator ................................................................................................... 11
Damper Shaft ....................................................................................................................................... 11
Motor/Blower ........................................................................................................................................ 11
Cleaning ..........................................................................................................................................12
Replacement ...................................................................................................................................12
Coil ........................................................................................................................................................12
Cleaning ..........................................................................................................................................12
Replacement ...................................................................................................................................12
Electric Heat .........................................................................................................................................13
Replacement ...................................................................................................................................13
TROUBLESHOOTING GUIDELINES .........................................................................................................14
ECM SPECIFIC TROUBLESHOOTING GUIDELINES ...............................................................................15
Checking ECM Cables .........................................................................................................................15
VALVE CALIBRATION CHARTS ...............................................................................................................17
FAN CFM CALIBRATION CURVES - TABLE 3 ..........................................................................................18
IN-WARRANTY RETURN PROCEDURE ...................................................................................................19
SERIES FLOW TERMINAL UNIT WEIGHTS -TABLE 4 .............................................................................19
PARALLEL FLOW TERMINAL UNIT WEIGHTS - TABLE 5 ......................................................................20
REPLACEMENT PARTS LIST ....................................................................................................................20
JOHNSON CONTROLS
FORM 130.13-NOM3 (708)
SAFETY SYMBOLS
The following symbols are used in this document to alert the reader to areas of potential hazard:
DANGER indicates an im mi nent ly hazardous situation which, if not avoid ed, will re sult in death or se ri ous injury.
WARNING indicates a potentially haz ard ous sit u a tion which, if not avoid ed, could result in death or se-
ri ous in ju ry.
CAUTION identifi es a hazard which could lead to damage to the ma chine, damage to other equip ment and/or en vi ron men tal pollution. Usually an in struc tion will be given, together with a brief ex pla na tion.
NOTE is used to highlight ad di tion al information which may be helpful to you.
JOHNSON CONTROLS 3
SAFETY CONSIDERATIONS
The equipment covered in this manual is designed for safe and reliable operation when installed and operated within its’ design specifi cation limits. To avoid personal injury or damage to equipment or property while installing or operating this equipment, it is essential that qualifi ed, experience personnel familiar with local codes and regulations, perform these functions using good judgment and safe practices. See the following cautionary statements.
ELECTRICAL SHOCK HAZARDS
All power must be disconnected prior to installation and servicing this equipment. More then one source of power may be present. Disconnect, tag and lock out all power sources to avoid electrocution or shock hazards.
ROTATING EQUIPMENT HAZARD
Fans may start automatically. Disconnect all power and control circuits prior to servicing to avoid injury.
Caution should be exercised due to the possibility of fans “free wheeling” due to connected duct air movement.
HOT PARTS HAZARD
Electric heaters may start automatically. Disconnect all power and control circuits prior to servicing to avoid burns.
Check that rigging and lifting equipment can safely support the equipment assembly and component weights.
FORM 130.13-NOM3 (708)
All assemblies must be adequately secured during lifting and rigging by temporary supports and restraints until equipment is permanently fastened and set in its’ fi nal location per manufacturer’s guidelines.
All temporary and permanent equipment supports must be capable of safely supporting the equipment’s weight as well as any additional live, seismic or dead loads that may be encountered. All supports must be designed to meet applicable local codes and ordinances.
All fastening devices must be designed to mechanically lock the assembly in place without the capability of loosening or breaking away due to system operation and vibration.
Dampers may activate automatically.
Disconnect the control circuits or pneumatic control systems and secure all dampers when servicing damper, actuators or linkage to avoid injury.
Wear the appropriate personal protective equipment (gloves, safety glasses, leather closed toe shoes, etc) when handling this equipment recognizing that sheet metal components are being handled.
4 JOHNSON CONTROLS
INSPECTION
Upon receipt of equipment, carefully check all items against the bill of lading to ensure that all equipment has been received (including shipped loose items). Note any discrepancy on the bill of lading before signing. Note that “ship loose” items may be included with the base unit or shipped (bulk) on a separate pallet.
Inspect all equipment for any signs of damage caused during transit. On equipment with electric heat, make sure to check the coil fi ns and/or make sure that the resistance heat coils are not damaged. Note any visual damage on the bill of lading before signing.
Immediately report all visual and concealed damage to the carrier and fi le a claim with the carrier.
Locate the model number on the nameplate and check that the correct equipment has been received. Verify that all options have been included, such as controls, fi lters, heating coils, etc. Also check that equipment voltage agrees with the building parameters. If a discrepancy is discovered between what was ordered and received, contact your local Johnson Controls representative immediately.
Do not use fl ow sensor, connecting tubes, coil stubouts or damper shaft as a handle when lifting or moving equipment as damage may occur.
Do not handle by equipment’s heating elements, as permanent damage will occur.
Check assembly and component weights to be sure that the rigging equipment can handle them safely.
Note; also check the centers of gravity and any specifi c rigging instructions.
Check for adequate ventilation so fumes do not migrate through ductwork to occupied spaces when welding or cutting around the equipment.
FORM 130.13-NOM3 (708)
Do not work on damper until associated actuator is disconnected.
Never pressurize equipment above specifi ed test pressure.
Protect adjacent fl ammable materials when brazing. Use fl ame and heat protection barriers where need. Have a fi re extinguisher at hand and ready for immediate use.
STORAGE
If equipment is to be stored prior to installation, observe the following precautions:
1. Choose a dry storage site that is reasonably level and sturdy to prevent undue stress or permanent damage to the equipment. Set equipment off ground if in moisture prone areas.
2. Cover entire equipment with protective tarp or moisture proof cover. Extend cover under equipment if stored on ground. Secure cover with adequate tie downs. Be sure that piping connections have protective shipping caps installed.
3. Do not stack equipment any higher than how it was shipped. If equipment has been unpackaged since receipt from the factory, do not stack without equivalent support between units as was supplied from the factory.
PRE-INSTALLATION INSPECTION
Do not use fl ow sensor, connecting tubes, coil stubouts or damper shaft as a handle when lifting or moving equipment as damage may occur.
Do not handle by equipment’s heating elements, as permanent damage will occur.
JOHNSON CONTROLS 5
While viewing the damper from the discharge of the equipment, disengage the actuator by depressing the manual override button on the side of the actuator and rotate the shaft fully. The damper should close fully and there should be no gaps between the damper gasketing and the inside of the valve.
Units equipped with ECM or 1 horsepower motors will ship from the factory with a removable motor / wheel support installed in the fan housing. It is imperative that this shipping support be removed prior to equipment startup or damage may result to both the motor and the wheel. A label will be affi xed to the outside of the unit next to the power entry point, to identify the presence of this shipping insert.
Manually rotate the fan wheel to assure that there are no obstructions within the fan housing.
Equipment supplied with ECM motors, backward or reverse rotation of the blower is detrimental to the ECM motor.
SEQUENCE OF OPERATION
All fan-powered equipment is supplied with a rectangular discharge and comes in one of two confi gurations:
1. Parallel fl ow with hot water coils mounted on the plenum induction air opening.
2. Series fl ow with hot water coils mounted on the discharge opening.
Note that for either confi guration, electric heaters (if supplied) are always mounted on the unit discharge opening.
Parallel Flow
On parallel flow equipment, the primary air valve delivers cooled air to the equipment’s outlet. When the space temperature decreases beyond the control of the primary air valve, the fan is started along with the fi rst stage of heat. The fan delivers warm plenum air from the controlled space to the equipment’s outlet, which is mixed with the primary air prior to being delivered to the space.
FORM 130.13-NOM3 (708)
Either the primary air valve, fan or both can deliver airfl ow to the occupied space. A back draft damper is provided, when the fan is not operating. The effi ciency of this system is the same as standard single duct VAV equipment.
In a typical control sequence applied to parallel fl ow equipment, the air valve is closed to a zero minimum airfl ow before the fan is energized. After the fan has been energized, the reheat will be energized upon a further drop in space temperature. Therefore, little primary air is mixed with the heated air stream.
Series Flow
Fan must be energized prior to introduction of air through the primary air valve or the possibilities exist that the fan wheel will operate backwards
/ counter rotation.
On series fl ow equipment, the fan runs continuously whenever the central air handler is in operation.
In response to the space temperature, the air valve modulates the volume of primary air. The re-heat is typically off during the air valve’s modulation. Should the space temperature decrease to the point at which a decrease in primary air will not maintain the desired temperature, the reheat will be activated to increase the discharge air temperature.
INSTALLATION
Do not use fl ow sensor, connecting tubes, coil stubouts or damper shaft as a handle when lifting or moving equipment as damage may occur.
Do not handle by equipment’s heating elements, as permanent damage will occur.
6 JOHNSON CONTROLS
Terminal equipment with electric heat must be installed in a horizontal plane with respect to the air stream. Low height equipment can be fl ipped over in the fi eld to vary or change control section handing.
Consult factory for application utilizing mercury contactors.
Clearances
All equipment covered in this document, including those with electric heat, are ETL listed for 0.0” clearance to combustibles. Refer to NEC and/or local codes for minimum electrical clearances required for service. Equipment should not make contact with any structure located above or below the equipment without appropriate isolation. Equipment supplied with bottom access panels requires suffi cient clearance to remove access panels for service.
Hanging and Mounting Equipment Overhead
Johnson Controls strongly recommends that all equipment be suspended from the upper most ceiling or a structural element of the building, independent of the false ceiling grid. Suspension devices are fi eld supplied, sized and designed by others. Johnson Controls will not accept responsibility for equipment mounting supports.
Equipment must be installed in a level horizontal plane.
Failure to level equipment properly may prevent proper operation of controls. See Tables 3 and 4 for equipment weights.
When requested, equipment is supplied with optional hanger brackets for use with (up to) a 3/8” [10mm] diameter hanger rod. See submittal drawings for hanger bracket locations.
Hanger straps may be utilized as an alternate means of suspending the equipment. Do not secure hanger straps to electric heaters, coils or control enclosures. Hanger straps can be mounted directly to the sides and bottom of equipment casing, such that they do not interfere with working components or access panels using screws that are no longer than 1” [25mm].
When hanging equipment, always use the support method as prescribed for rectangular duct in the job specifi cations.
FORM 130.13-NOM3 (708)
Duct Connections
All duct connections should be confi gured and installed in accordance with SMACNA guidelines and all local code requirements. Check to see that duct fasteners are appropriate for the application and do not impinge any internal components. Pay particular attention to internal electrical components.
Fasten and seal all ductwork connections in accordance with project specifi cations.
Allow a minimum of 1½ duct diameters of straight duct prior to equipment inlet and after equipment discharge.
The diameter of the inlet duct for round valves must be equal to the listed size of the equipment. The round air valve inlet collar of the equipment is 1/8” smaller then listed size in order to allow the round ductwork to slip over the air valve inlet collar. DO NOT INSERT
DUCTWORK INTO AIR VALVE INLET COLLAR.
When making ductwork connection to air valve inlet collar and insulating air valve inlet, take caution not to damage or remove the fl ow sensor connections, which are vital to equipment control.
Provide insulation around entire inlet collar (all the way to the equipment casing).
Cut “slits” in the insulation for the fl ow tubes and secure with duct tape.
Permissible discharge duct connections are straight fl anged, slip and drive or drive and screw.
If equipment is to be installed in a location with high humidity, external insulation around the heating coil should be installed.
After all connections are made, check that the entire ductwork system is airtight. In some high-pressure systems, duct sealer may be necessary.
Sound Critical Applications
Flexible duct connectors are not recommended on equipment discharge. The sagging membrane of these fi ttings can cause turbulence and locally high air velocities that generate noise. Also, lightweight membrane material allows noise to breakout, which can increase sound levels in the space below.
JOHNSON CONTROLS 7
Coil Connections
Hot water and steam coils are male sweat connection.
Use appropriate brazing alloy for system temperature and pressure. Refer to equipment construction submittal drawing for specifi c connection size. MAXIMUM
HYDRONIC SYSTEM OPERATING PRESSURE
MUST NOT EXCEED 300 PSIG. MAXIMUM
STEAM SYSTEM PRESSURE MUST NOT
EXCEED 15 PSIG.
If necessary, you can change coil connection handing on one and two row coils from left-hand to right-hand (and vice-versa) by rotating the coil “like a steering wheel”
180° about its central axis when facing the fi ns. For three and four row coils, consult factory.
Electrical
All fi eld wiring must comply with NEC and all local codes. Electrical and control diagrams are affi xed to the interior of the control enclosure box.
Minimum circuit ampacity (MCA) designates the maximum operating load of the equipment for sizing wire feeders. Supply Circuit Protection designates the largest breaker in the electrical service panel that can be used to protect the equipment.
Use Copper conductors only.
OPERATION
Start-Up
Thorough safety precautions should always be taken when performing startup and service. Refer to safety considerations at the beginning of this Operation
Manual. Only qualifi ed individuals should perform these tasks.
Prior to start-up, the project control sequence/wiring diagram should be obtained and thoroughly understood.
If factory supplied analog or DDC controls are utilized, refer to the applicable Operation Manual for start-up and balancing information. Check that all electrical work is fi nished and properly terminated. Check that all electrical connections are tight and that the proper voltage is connected.
Check to make sure that heater elements are not damaged, free of all foreign material and proper control interlocks have been made before energizing the electric heater.
8
FORM 130.13-NOM3 (708)
Power Requirements
Three Phase AC power imbalance must not exceed 2%.
Be sure that the following guides are met:
1. AC power is within 10% of rated voltage at rated frequency. (See equipment nameplate for rat- ings)
2. AC power is within 5% of rated frequency at rated voltage.
3. A combined variation in the voltage and frequency of 10% (sum of absolute values) of rated values provided the frequency variation does not exceed
5% of rated frequency.
Primary Air Damper and Fan Adjustment
Unit should not be balanced until the incoming power supply is at the permanent voltage condition. All discharge ductwork must be connected. The minimum recommend discharge static pressure for all fanpowered equipment is 0.1” wg. and 0.2” on 3/4hp and larger. All foreign materials should be removed from the duct system. Optional fi lters should be installed as required.
Unless otherwise specifi ed, the fan motor has three speeds. Fan speed is selected in the electrical control enclosure by one of two methods. For units with dual motors, see Figure 1A showing how the fan speed is selected by placement of a factory supplied jumper wire on a terminal strip. Otherwise see Figure 1B which shows the wire to wire fan speed selection method. Simply insert the male quick connect (from control circuitry) into the female quick connect which corresponds to high (black), medium (blue), or low (red) motor speeds. Units are set to low speed at the factory as standard in order to optimize energy effi ciency. A three position rotary switch is optional.
ELECTRICAL SHOCK HAZARD
All power must be disconnected prior to changing jumper or serious injury or death will result.
All fan-power equipment is shipped with an electronic solid state fan speed controller (SCR) for PSC motors.
The SCR is located in the control enclosure. Using a 1/8” fl at blade screwdriver, adjusting the manual potentiometer clockwise will increase the motor speed; adjusting the potentiometer counterclockwise will decrease the motor speed.
JOHNSON CONTROLS
JUMPER
FIGURE 1A - FAN SPEED CONTROL WITH JUMPER
FORM 130.13-NOM3 (708)
5. If balancing dampers are present, adjust and set proportionally to desired position. To minimize noise levels, leave these dampers in the most open position possible.
6. If total airfl ow is too low, de-energize unit and move jumper to next higher speed.
7. Energize unit and adjust Fan Speed Control (SCR) for desired total airfl ow.
8. The maximum primary air balance may be checked using the optional radiated sound damper, or by suspending a sheet of notebook paper over the inlet using a small piece of tape. If the damper or notebook paper is blowing out of the unit, the primary maximum airfl ow is too high. If the paper or damper is being pulled into the unit, the maximum primary airfl ow is too low. Optimum balance is achieved when the damper or paper hangs straight down.
FIGURE 1B - WIRE TO WIRE FAN SPEED SELECTION
Series Flow, PSC Motor with SCR
1. Make sure that the motor speed is at maximum by turning the potentiometer located on the Fan Speed
Control (SCR) all the way clockwise.
2. Energize motor and let motor operate for a minimum of 15 minutes. During this run-in, check ductwork for any leaks and repair as necessary.
3. If remote balancing dampers are present set them to full open.
4. Attach a manometer or magnehelic to the differential pressure ports in the pneumatic tubing leading to the high and low side of the inlet air probe and measure the velocity pressure. Adjust and set the primary maximum airfl ow as necessary to meet job site requirements. See Table 2, Airfl ow vs.
Velocity Pressure chart. This chart, with different inlet sizes, is also located on the side of the equipment.
Parallel Flow, PSC Motor with SCR
1. Make sure that the motor speed is at maximum by turning the potentiometer located on the Fan Speed
Control (SCR) all the way clockwise.
2. With primary air valve in the closed position, energize motor and let motor operate for a minimum of 15 minutes. During this run-in, check ductwork for any leaks and repair as necessary.
3. If balancing dampers are present, adjust and set proportionally to desired position. To minimize noise levels, leave these dampers in the most open position possible.
4. If fan airfl ow is too low, de-energize unit and move jumper to next higher speed.
5. De-energize motor and perform minimum and maximum primary air balance. See Table 2, Air-
fl ow vs. Velocity Pressure chart. This chart, with different inlet sizes, is also located on the side of the equipment.
An extra jumper is required on units with 480 VAC motors. See wiring diagram attached to unit.
JOHNSON CONTROLS 9
24 volts A/C
15 A & B
24 volts AC
16 A & B
FORM 130.13-NOM3 (708)
Remote
Manual jumper
Analog input 2-10 VDC
VDC test loop
Common test loop
FIGURE 2 - ETPWM BOARD LAYOUT
Series Flow ECM Motor Balancing
Fan must be energized prior to introduction of air through the primary air valve or the possibility exists that the fan wheel will operate backward
(counter rotation). Reverse / counter rotation of the blower over a period of time will damage the ECM motor.
See Figure 2 for ETPWM Board Layout.
Commissioning
1. If remote balancing dampers are present set them to full open.
2. Make sure there are no obstructions in the discharge ductwork and/or at the plenum opening. If the unit has a radiated sound damper at the plenum opening, make sure it swings freely.
3. With unit de-energized, disable fan by disconnecting one of the wires leading to fan relay coil or contacts.
4. Energize unit.
5. Verify that there is 22 to 28 VAC across terminals
15 and 16 of ETPWM board.
6. Verify that there is 15 VDC across terminals G (+) and COM (-) of ETPWM board.
7. Connect voltmeter to wire loop VDC (+) and wire loop COM (-) of ETPWM board. Verify DC voltage is between 5.1 and 9.9 VDC.
8. De-energize unit and reconnect wire to fan relay removed in step 3. Make sure that all wires are reconnected per electrical schematic shipped with unit.
10
Manual speed adjustment
“G” activation line
Signal common
PWM output
LD13841
9. Energize unit and let motor operate for a minimum of 15 minutes. During this run-in, check ductwork for any leaks and repair as necessary.
Balancing
1. Adjust fan to the design CFM using either the
Manual or Remote Fan CFM Adjustment method listed below.
2. Attach a manometer or magnehelic to the differential pressure ports in the pneumatic tubing leading to the high and low side of the inlet air probe and measure the velocity pressure. Adjust and set the primary maximum airfl ow as necessary to meet job site requirements. See Table 2, Airfl ow vs.
Velocity Pressure chart. This chart, with different inlet sizes, is also located on the side of the equipment.
3. If balancing dampers are present, adjust and set proportionally to desired position. To minimize noise levels, and prevent premature ECM motor failure, leave these dampers in the most open position possible.
4. The maximum primary air balance may be checked using the optional radiated sound damper, or by suspending a sheet of notebook paper over the inlet using a small piece of tape. If the damper or notebook paper is blowing out of the unit, the primary maximum airfl ow is too high. If the paper or damper is being pulled into the unit, the maximum primary airfl ow is too low. Optimum balance is achieved when the damper or paper hangs straight down.
JOHNSON CONTROLS
Manual Fan CFM Adjustment
1. Verify that the jumper on ETPWM board is in the
“MAN” position (shipped from factory in Manual mode)
2. Connect voltmeter to wire loop VDC (+) and wire loop COM (-).
3. Determine the DC voltage for required airfl ow from the Fan Calibration Curve supplied on the side of the equipment. Use the bottom (5 to 10 volts DC) scale on the chart. An example Fan Calibration curve is shown in Table 3; however, the curve on the side of the equipment should be used in determining the voltage.
4. Using a 1/8” fl at bladed screwdriver, adjust the manual speed potentiometer, labeled SPD, to obtain the required voltage. Clockwise increases airfl ow, counterclockwise decreases airfl ow.
5. Do not set the voltage lower than 5.1 VDC or higher than 9.9 VDC or motor may experience starting problems.
6. Do not set the balance voltage outside limits of the voltage/CFM curve or erratic motor operation and eventual failure may result.
Remote Fan CFM Adjustment
1. Relocate the jumper on ETPWM board to the REM position.
2. Determine the DC voltage for required airfl ow from the Fan Calibration Curve supplied on the side of the equipment. Use the top (2 to 10 Analog Input
Volts DC) scale on the chart. An example Fan
Calibration curve is shown in Table 3; however, the curve on the side of the equipment should be used in determining the voltage.
3. Remotely adjust the external voltage source to the desired volts DC for required airfl ow.
4. Do not operate motor at control voltage lower than
2.1 VDC or higher than 9.9 VDC or motor may experience starting problems.
5. Do not operate motor at control voltage outside limits of the voltage/CFM curve or erratic motor operation, and eventual failure may result.
FORM 130.13-NOM3 (708)
Status LED
When the motor is running, the LED alternates between
CFM and RPM indications. In the RPM mode, LED turns on for a period of approximately 220 microseconds at a rate of 36 pulses per revolution. This mode lasts for ten seconds. Due to the rapid rate, LED will appear to be dimly lit, not fl ashing. As RPM is increased, brightness will increase. In the CFM mode, the LED will fl ash slowly, and at maximum brightness, once for every 100 CFM. Accuracy is +/- one fl ash. LED will then return to RPM mode, and cycle will repeat.
MAINTENANCE
Factory Provided Damper Actuator
Equipment may be supplied with a fi eld or factory mounted damper actuator.
If actuator is factory provided, see
ACT24 Floating-Point Control Direct
Coupled Actuator document. See
Table 1 for maximum wire lengths for control voltage.
TABLE 1 - MAXIMUM WIRE LENGTHS
WIRE SIZE MAX FEET
16 GA
18 GA
20 GA
22 GA
1225 FT
725 FT
400 FT
200FT
Damper Shaft
There is an indicator on the end of the damper shaft that can be used to determine the position on the damper blade. If the indicator is horizontal, the damper is completely open.
Motor/Blower
Fan powered terminal unit motors are equipped with permanently lubricated bearings and require little or no maintenance. The frequency of required cleaning is dependent on the operating hours of the system, fi lter maintenance and effi ciency as well as dirt load.
Periodically inspect the motor and blower-housing wheel for accumulation of dust and clean as necessary.
JOHNSON CONTROLS 11
Cleaning
1. Disconnect all electrical power to the equipment, tag and lock out power source.
2. Gain access to motor housing through access panel.
3. Use soft brush and vacuum to remove loose debris from motor housing.
4. Replace access panels and restore electrical power to equipment.
5. Use caution to assure that any contaminated material does not contact other areas of the equipment or building. Properly dispose of all contaminated materials.
Replacement
1. Disconnect all electrical power to the equipment, tag and lock out power source.
2. Remove bottoms access doors by removing the screws from the access door and then remove side rail screws to access to the motor.
3. Disconnect fan motor wiring.
4. Remove securing fan assembly to discharge
5. Loosen fan wheel set screw.
6. Remove nuts securing motor to housing and remove motor.
7. Remove fan cut off.
8. Remove fan wheel and clean as needed.
9. Reinstall wheel, cut off, motor, and housing.
Cleaning
1. Disconnect all electrical power to the equipment, tag and lock out power source.
2. Put on appropriate personal protective equipment.
3. Gain access to coil either through ductwork or optional coil access panel.
4. Use soft brush and vacuum to remove loose debris from sides of coil.
5. Straighten any coil fi ns that may have been damaged during cleaning process with fi n comb.
6. Replace ductwork or access panel and restore electrical power to equipment.
7. Use caution to assure that any contaminated material does not contact other areas of the equipment or building. Properly dispose of all contaminated materials.
Replacement
1. Disconnect all electrical power to the equipment, tag and lock out power source.
2. Disconnect all ductwork, if applicable.
3. Remove fi lter rails/ fi lter clips, if applicable.
4. Cut or un-braze water connection at coil.
5. Disconnect coil from equipment by removing screws on the exterior perimeter of the coil. Low height equipment only has mounting screws located on the sides of the equipment.
Coil
The frequency of required cleaning is dependent on the operating hours of the system, fi lter maintenance and effi ciency as well as dirt load.
Important: Coils may become externally fouled as result of normal operation. Dirt on the surface of the coil reduces its ability to transfer heat that can result in reduced performance and increased operating energy cost.
If the dirt on the surface of the coil becomes wet, microbial growth (mold) can result, possibly causing unpleasant odors and serious health related indoor air quality problems.
FORM 130.13-NOM3 (708)
Fin edges are sharp. Fins are fragile; care must be exercised to avoid damaging fi ns. Do not use solutions to clean coils; drain pans are not present to remove collected solution.
12 JOHNSON CONTROLS
FORM 130.13-NOM3 (708)
Electric Heat
Electric heat requires a minimum of
0.1” W.G. downstream static pressure for proper operation.
Electric heaters come equipped with a primary auto-reset limit switch to provide protection against overheating.
The primary auto-reset limit switch automatically cuts the heater off when overheating occurs, and turns the heater back on when the elements have cooled down.
Should the secondary one-time trip limit switch trip, they will need to be replaced with a limit switch that has the same trip temperature as the one-time trip limit switch originally supplied with the electric heater.
Optional secondary manual reset limit switches are available.
Electric heaters may be equipped with optional disconnect switch, fuses and airfl ow proving switch.
Replacement
1. Disconnect all electrical power to the equipment, tag and lock out power source.
2. Disconnect discharge ductwork from unit.
3. Remove electric heat assembly from equipment.
4. Before removing wires from the element rack
T-Plate, mark where the wires are connected so that they can be reconnected correctly on the new element rack.
5. Remove the wires and screws holding the heater
T-plate in the control enclosure and remove element rack.
6. Insert new element rack into control enclosure and replace screws to secure the element rack to control enclosure.
7. Replace wires.
8. Close control enclosure cover before turning on the power.
JOHNSON CONTROLS 13
FORM 130.13-NOM3 (708)
TROUBLESHOOTING GUIDELINES
PROBLEM POSSIBLE CAUSE
Blown fuse or open circuit breaker
CORRECTIVE ACTION
Replace fuse or reset circuit breaker; verify and correct source of overload.
Shipping Cardboard insert in fan wheel Remove insert and restart.
Improper wiring connections Check wiring with diagram supplied on unit.
Motor Fails to Start
Motor Overheats
Improper current supply
Compare actual supply power with motor nameplate recommendations. Contact power company for adjustments.
Check motor and confi rm rotates freely. Mechanical failure
Overloaded motor Reduce load or replace with a larger motor (refer factory).
Motor fan is clogged with dirt preventing proper ventilation
Remove fan cover, clean fan and replace cover. May be necessary to replace motor.
Lack of required external static pressure Add required external static pressure.
Excessive Motor
Noise
Motor mounting bolts loose
Fan wheel rubbing on fan housing
Loose fan wheel
Low Coil Capacity
Heater Does Not
Operate
Low or High Temperature Rise
Heater with SSR
Does Not Operate
SCR set too low
Incorrect airfl ow
Incorrect GPM
Dirty coil fi ns
Dirty fi lter (where applicable)
Incorrect water temperature
No Power
No Control Voltage
Blown Fuse
Open Limit (primary or secondary)
Airfl ow Incorrect Direction
Low External Static Pressure
Damaged elements
Incompatible Thermostat or Controller
Problems with Additional Stages
Incorrect CFM
Incorrect Signal Applied
Interface Board Fuse Blown
Tighten motor mounting bolts.
Align wheel in housing.
Align and tighten.
Select lower tap to Reduce motor speed and re-adjust fan SCR.
Check fan’s operating conditions.
Check water pumps, valves and lines for obstructions.
Clean coil Fins.
Replace fi lter.
Provide proper water temperature.
Check Disconnect.
Check transformer and transformer fusing (if applicable) replace if necessary.
Replace fuse.
Replace limits or reset as applicable.
Check for continuity across limit to determine if open, replace as necessary.
Check sensing tube, red tube = high and black tube = low, rotate if needed.
Increase airfl ow to obtain a minimum of .1 in. w.c. external static.
Check for open or damaged elements and replace as necessary.
Check Wiring.
Check for compatibility.
Check location of thermostat; might be installed in a
“too hot” or “too cold” location. Check heat outputs on controller.
Check contactors for open coil.
Check for damaged elements.
Check for blocked duct or location of heater.
Verify signal input.
Replace fuse.
14 JOHNSON CONTROLS
FORM 130.13-NOM3 (708)
ECM SPECIFIC TROUBLESHOOTING GUIDELINES
PROBLEM
Motor Fails to Start
Motor Surges
Excessive Motor
Noise
Poor Performance
POSSIBLE CAUSE CORRECTIVE ACTION
CFM Adjustment voltage above 9.9
VDC or below 5.1 VDC
Properly adjust CFM voltage.
ECM cables improperly seated at motor
Unplug cables from motor and re-install, making sure plugs on cables are fully seated in motor receptacles.
Replace cable(s). See section on checking cables below. ECM cables open or intermittent
Mechanical failure
Electrical failure
Check motor and confi rm it rotates freely.
Replace motor.
Fan Relay Contacts Oxidized/Sulfi dized Replace fan relay.
Fan CFM adjustment voltage outside range of Fan Calibration Curve
ESP (external static pressure) too high
Adjust voltage to value within range of Fan Calibration
Curve.
Verify balancing dampers as open as possible (at least one should be fully open). Verify radiated sound damper
(if supplied) swings freely. Verify plenum opening is unobstructed. Verify fi lter (if supplied) is not dirty and does not obstruct fl ow of plenum air.
Tighten motor mounting bolts.
Motor mounting bolts loose
Fan wheel rubbing on fan housing
Loose fan wheel
Align wheel in housing.
Align and tighten.
Lack of required external static pressure Add required external static pressure.
Wrong Program Contact Factory.
Motor Runs in
Reverse, Doesn’t
Respond to Speed
Adjustment
Motor Failure Replace.
Checking ECM Cables
Remove power from the unit. Unplug signal cable at motor, but leave quick connects attached to ETPWM board and fan relay or quick connect terminal block (see
Figure 3 and 4). Use ohmmeter to check continuity.
Repeat process for three wire power cable if signal cable does not appear to be defective (see Figure 3 and 5).
Only very light force is required when inserting meter probe into plug. Excess force will damage contacts.
JOHNSON CONTROLS 15
FORM 130.13-NOM3 (708)
FIGURE 3
Black wire to P3 (PWM) of ETPWM board
Green wire to P2 (Fan On/Off*) of Fan Relay or Curtis Block
Red wire to P6 (LED) of ETPWM board
9
10
11
12
13
14
15
16
5
6
7
8
1
2
3
4
FIGURE 4
White wire to P2 (COM) of ETPWM board
Blue wire to P7 (LCOM) of ETPWM board
LD13842
BLACK
WHITE
GREEN
RED
BLUE
LD13843
FIGURE 5
16
LD13844
JOHNSON CONTROLS
VALVE CALIBRATION CHARTS
Applicable calibration charts are affi xed to each unit.
TABLE 2
FORM 130.13-NOM3 (708)
JOHNSON CONTROLS
LD13845
17
18
FAN CFM CALIBRATION CURVES - TABLE 3
FORM 130.13-NOM3 (708)
Applied
Model
XX40
XX24
N/A
XX21
N/A
XX11
Where XX
Implies
Valve
Size
LD13846
JOHNSON CONTROLS
FORM 130.13-NOM3 (708)
IN-WARRANTY RETURN PROCEDURE
Refer to Johnson Controls Warranty Parts Policy.
SERIES FLOW TERMINAL UNIT WEIGHTS -TABLE 4
BASE UNIT WEIGHT
SIZE
SINGLE
WALL
1230
1430
1630
1440
1640
1644
1844
1218
1021
1221
1421
1224
1424
0506
0606
0806
0611
0811
1011
0818
1018
174
177
179
181
184
194
209
79
79
81
83
108
111
60
61
75
77
58
57
58
59
DOUBLE
WALL
38
39
39
40
40
42
46
17
17
18
18
24
24
14
14
16
17
13
13
13
13
21
21
21
21
21
21
21
9
9
7
9
11
11
5
5
7
7
5
5
1 ROW
5
5
TCS (22 GA)
ADDERS TO BASE UNIT WEIGHT
WATER COIL
2 ROW 3 ROW
7
7
10
10
7
7
7
7
11
11
10
10
10
10
16
16
11
11
11
11
23
23
42
42
42
42
42
42
42
63
63
63
63
63
63
63
16
16
16
16
34
34
84
84
84
84
84
84
84
22
22
22
22
45
45
4 ROW
13
13
13
13
13
13
22
22
ELEC.
HEAT
42
42
42
42
42
52
52
23
23
23
23
27
27
20
20
23
23
20
20
20
20
JOHNSON CONTROLS 19
FORM 130.13-NOM3 (708)
BASE UNIT WEIGHT
SIZE
SINGLE
WALL
10
12
14
16
6
8
4
5
85
87
118
120
44
44
46
48
PARALLEL FLOW TERMINAL UNIT WEIGHTS - TABLE 5
DOUBLE
WALL
PENDING
1 ROW
10
10
TVS (22 GA)
ADDERS TO BASE UNIT WEIGHT
WATER COIL
2 ROW 3 ROW
14
14
18
18
10
10
14
14
16
16
14
14
19
19
21
21
18
18
25
25
29
29
4 ROW
22
22
22
22
30
30
34
34
ELECTRIC
HEAT
27
31
26
31
18
18
18
20
REPLACEMENT PARTS LIST
SIZE
XX04
XX06
XX11
XX18
XX21
XX24
XX30
XX40
XX44
H/P
1/12
1/6
1/4
1/2
3/4
1
2 @ 1/2
2 @ 3/4
2 @ 1
SERIES FLOW TERMINALS
MOTORS AND BLOWERS, MODEL TCS
120
PM-02-1412
MOTOR
208/230 277
PM-02-1414
PM-02-0026
PM-02-0046
PM-02-1413
PM-02-0030
PM-02-0051
PM-02-0032
PM-02-0052
PM-02-0068
PM-02-0098
PM-02-0124
PM-02-0068
PM-02-0098
PM-02-0124
PM-02-0072
PM-02-0104
PM-02-0126
PM-02-0072
PM-02-0104
PM-02-0126
PM-02-0076
PM-02-0106
PM-02-0128
PM-02-0076
PM-02-0106
PM-02-0128
BLOWER
SIZE
5.75-7
9-4T
9-7T
9-9R
10-10T
10-9R
2 @ 9-9R
2 @ 10-10T
2 @ 10-9R
PART NO.
PM-06-0005
PM-06-0119
PM-06-0122
PM-06-0124
PM-06-0135
PM-06-0134
PM-06-0124
PM-06-0135
PM-06-0134
20 JOHNSON CONTROLS
FORM 130.13-NOM3 (708)
SIZE
XX06
XX08
XX10
XX19
SIZE
XX06
XX08
XX10
XX19
SIZE
XX04
XX06
XX11
XX18
XX21
XX24
SIZE
XX11
XX18
XX19
XX21
XX24
XX40
H/P
1/3
1/2
1/2
3/4
1
2 @ 1/2
ECM MOTOR OPTION FOR MODELS TCS
MOTOR
120/240
PM-02-1334
277
PM-02-1302
PM-02-1335
PM-02-1335
PM-02-1336
PM-02-1337
PM-02-1335
PM-02-1303
PM-02-1303
PM-02-1304
PM-02-1305
PM-02-1303
H/P
1/6
1/4
1/4
2 @ 1/4
H/P
1/3
1/3
1/2
2 @1/3
H/P
1/12
1/6
1/4
1/2
3/4
1
MOTORS AND BLOWERS, MODEL TCL
MOTOR
120
PM-02-0026
208/230
PM-02-0030
277
PM-02-0032
PM-02-1404
PM-02-1404
PM-02-1404
PM-02-1403
PM-02-1403
PM-02-1403
PM-02-1402
PM-02-1402
PM-02-1402
ECM MOTOR OPTIONS FOR MODEL TCL
MOTOR
120/240
PM-02-1405
277
PM-02-1406
PM-02-1405
PM-02-1407
PM-02-1405
PM-02-1406
PM-02-1408
PM-02-1406
PARALLEL FLOW TERMINALS
MOTORS AND BLOWERS, MODEL TVS
120
PM-02-1412
PM-02-0026
PM-02-0046
MOTOR
208/230
PM-02-1413
PM-02-0030
PM-02-0051
PM-02-0072
277
PM-02-1414
PM-02-0032
PM-02-0052
PM-02-0068
PM-02-0098
PM-02-0124
PM-02-0104
PM-02-0126
PM-02-0076
PM-02-0106
PM-02-0128
BLOWER
SIZE
9-4R
10-4R
10-5R
2 @ 10-4R
BLOWER
SIZE
5.75-7
9-4T
9-7T
10-9T
10-10T
10-9R
PART NO.
PM-06-0118
PM-06-0145
PM-06-01
PM-06-0145
PART NO.
PM-06-0005
PM-06-0119
PM-06-0122
PM-06-0133
PM-06-0135
PM-06-0134
JOHNSON CONTROLS 21
22
SIZE
XX06
XX11
XX18
XX21
XX24
SIZE
XX04
XX09
XX15
AMPS
25
30
35
40
50
FORM 130.13-NOM3 (708)
H/P
1/3
1/2
1/2
3/4
1
ECM MOTOR OPTIONS FOR MODEL TVS
MOTOR
120/240
PM-02-1334
277
PM-02-1302
PM-02-1335
PM-02-1335
PM-02-1336
PM-02-1337
PM-02-1303
PM-02-1303
PM-02-1304
PM-02-1305
MOTORS AND BLOWERS, MODEL TVL
MOTOR
120
PM-02-0001
208/230
PM-02-0003
277
PM-02-0005
PM-02-1367
PM-02-1376
PM-02-1368
PM-02-1377
PM-02-1369
PM-02-1378
BLOWER
PART NO.
PM-06-00148
PM-06-00148
PM-06-00150
H/P
1/8
1/4
1/2
# OF POLES
2
3
3
1
2
3
1
2
3
1
3
1
2
1
2
MAGNETIC CONTACTORS
COIL VOLTAGE
24
PE-05-1251
120
PE-05-1252
240
PE-05-1256
PE-05-2251
N/A
PE-05-1301
PE-05-2301
PE-05-2252
N/A
PE-05-1302
PE-05-2302
PE-05-2256
N/A
PE-05-1306
PE-05-2306
PE-05-3301
N/A
PE-05-2351
PE-05-3351
PE-05-1401
PE-05-2401
PE-05-3401
PE-05-1501
PE-05-2501
PE-05-3501
PE-05-3302
N/A
PE-05-2352
PE-05-3352
PE-05-1402
PE-05-2402
PE-05-3402
N/A
PE-05-2502
PE-05-3502
PE-05-3306
N/A
PE-05-2356
PE-05-3356
PE-05-1406
PE-05-2406
PE-05-3406
PE-05-1506
PE-05-2506
PE-05-3506
277
PE-05-1255
PE-05-2255
N/A
PE-05-1305
PE-05-2305
PE-05-3305
N/A
PE-05-2355
PE-05-3355
PE-05-1405
PE-05-2405
PE-05-3405
N/A
PE-05-2505
PE-05-3505
480
PE-05-1257
PE-05-2257
N/A
PE-05-1307
PE-05-2307
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
N/A
JOHNSON CONTROLS
FORM 130.13-NOM3 (708)
AMPS
35
50
# OF POLES
1
2
3
1
2
3
MERCURY CONTACTORS
COIL VOLTAGE
24
PE-26-1351
PE-26-2351
120
PE-26-1352
PE-26-2352
240
PE-26-1356
PE-26-2356
PE-26-3351
PE-26-1501
PE-26-2501
PE-26-3501
PE-26-3352
PE-26-1502
PE-26-2502
PE-26-3502
PE-26-3356
PE-26-1506
PE-26-2506
PE-26-3506
277
PE-26-1355
PE-26-2355
PE-26-3355
PE-26-1505
PE-26-2505
PE-26-3505
480
PE-26-1357
PE-26-2357
PE-26-3357
PE-26-1507
PE-26-2507
PE-26-3507
4
5
µf
3
6
7.5
10
12.5
15
20
3
VA
50
75
TYPE CC
600 VOLT
MINI
CAPACITORS
PART #
PE-12-0499
PE-12-0500
PE-12-0501
PE-12-0502
PE-12-0503
PE-12-0504
PE-12-0505
PE-12-0506
PE-12-0508
PE-12-0509
VOLTAGE
370
370
370
370
370
370
370
370
370
440
120
TO 24 VAC
PE-10-2105
PE-10-2107
TRANSFORMERS
208/240 277
TO 24 VAC
PE-10-6105
PE-10-6107
TO 24 VAC
PE-10-5105
PE-10-5107
6
10
15
20
25
30
AMPS
1
2
3
4
5
FUSES
STANDARD
PE-06-0001
PE-06-0002
PE-06-0003
PE-06-0004
PE-06-0005
PE-06-0006
PE-06-0010
PE-06-0015
PE-06-0020
PE-06-0025
PE-06-0030
TIME DELAY
N/A
PE-06-0035
PE-06-0037
PE-06-0039
PE-06-0040
PE-06-0041
PE-06-0044
PE-06-0046
PE-06-0047
PE-06-0048
PE-06-0049
480
TO 24 VAC
PE-10-7105
PE-10-7107
575
TO 24 VAC
PE-10-9105
PE-10-9107
JOHNSON CONTROLS 23
©2008 Johnson Controls, Inc. P.O. Box 423, Milwaukee, WI 53203 www.johnsoncontrols.com
Printed in USA 130.13-NOM3 (708)
New Release
advertisement
Key Features
- Parallel flow
- Series flow
- Electric Heat
- ECM Motor
- PSC Motor
- Factory Mounted Damper Actuator
Frequently Answers and Questions
What are the configurations available for the Fan Powered VAV Terminals?
Where should the equipment be installed?
What are the key features of the Fan Powered VAV Terminals?
Related manuals
advertisement
Table of contents
- 1 Form 130.13-NOM3 (708)
- 2 TABLE OF CONTENTS
- 4 SAFETY CONSIDERATIONS
- 5 INSPECTION
- 5 STORAGE
- 5 PRE-INSTALLATION INSPECTION
- 6 SEQUENCE OF OPERATION
- 6 Parallel Flow
- 6 Series Flow
- 6 INSTALLATION
- 7 Clearances
- 7 Hanging and Mounting Equipment Overhead
- 7 Duct Connections
- 7 Sound Critical Applications
- 8 Coil Connections
- 8 Electrical
- 8 OPERATION
- 8 Start-Up
- 8 Power Requirements
- 8 Primary Air Damper and Fan Adjustment
- 9 Series Flow, PSC Motor with SCR
- 9 Parallel Flow, PSC Motor with SCR
- 10 Series Flow ECM Motor Balancing
- 11 Manual Fan CFM Adjustment
- 11 Remote Fan CFM Adjustment
- 11 Status LED
- 11 MAINTENANCE
- 11 Factory Provided Damper Actuator
- 11 Damper Shaft
- 11 Motor/Blower
- 12 Coil
- 13 Electric Heat
- 14 TROUBLESHOOTING GUIDELINES
- 15 ECM SPECIFIC TROUBLESHOOTING GUIDELINES
- 15 Checking ECM Cables
- 17 VALVE CALIBRATION CHARTS
- 18 FAN CFM CALIBRATION CURVES
- 19 IN-WARRANTY RETURN PROCEDURE
- 19 SERIES FLOW TERMINAL UNIT WEIGHTS
- 20 PARALLEL FLOW TERMINAL UNIT WEIGHTS
- 20 REPLACEMENT PARTS LIST