» Flexible Hose Technical Documentation

» Flexible Hose Technical Documentation
Flexible Hose
Application
The flex hose has been specially designed for operating conditions in heating
and air conditioning application coils.
Each hose is made up of several components and the special 12 point double
crimping on the ferrule under strict quality control gives this hose double
security against any leakage. The special EPDM core meets a fully defined
specification. Shore hardness, resistance to aging, mechanical resistance (elasticity, tensile fracture, stretching), ability to accept chemical agents in contact
with the elastomer and non-toxic. The elastomer is not sensitive to Glycol or
water treatment products.
Hoses meet 25/50 flammability and smoke development classification
requirements of codes and specifications when tested by ASTM E 84 method.
Technical Data
External Braiding
Crimping Ferrules
Connectors
Fiber Gasket
Core
All hoses are male NPT x female swivel NPSM male cone to male NPT adaptor.
stainless steel AISI 304
stainless steel AISI 304
machined brass
BA-U fiber washer
Formulated EPDM
On Installation: Avoid absolutely any tension due to stretching during the
course of tightening the connectors.
1. Install and tighten the fixed male connector (if applicable).
2. Install and tighten the union adaptor (if applicable).
3. Install and tighten the swivel nut. Use two spanners in order to screw in
the union: one to hold the hexagon of the adaptor and the other to tighten
the nut at the same time.
Operating & Burst Pressure Rating
1/2”
375 psi operating
1500 psi burst pressure
3/4”
300 psi operating
1200 psi burst pressure
1”
225 psi operating
900 psi burst pressure
1 1/4”
200 psi operating
800 psi burst pressure
1 1/2”
175 psi operating
600 psi burst pressure
2”
150 psi operating
500 psi burst pressure
Temperature Rating
5°F to 230°F (-15°C to 110°C)
Important: Do not re-screw the fixed connector or adaptor after tightening the
swivel nut; this will cause tensioning of the flexible hose with a risk of rapid
deterioration at this point. On removal, take the same precautions. If the
flexible hose incorporates two fixed connectors, at least one must be installed
on a counter-part fitted with a screw connector.
Temperature rating must adhere to the control valve and pipe package valve specs when
assembled to hoses.
Part Number
PHOSE1
PHOSE2
PHOSE3
PHOSE4
PHOSE5
PHOSE6
½”, 12” long male NPT X male NPT
½”, 24” long male NPT X male NPT
¾”, 12” long male NPT X male NPT
¾”, 24” long male NPT X male NPT
1”, 12” long male NPT X male NPT
1”, 24” long male NPT X male NPT
Cv Ratings
Cv
12” Length
18” Length
24” Length
36” Length
1/2”
3.3
3.2
3.1
3.0
3/4”
11.0
10.7
9.9
9.3
1”
20.9
20.3
19.5
18.2
1 1/4”
NA
37.9
36.9
34.7
1 1/2”
NA
64.4
61.0
55.0
2”
NA
NA
110.7
100.8
For calculated pressure drop across each hose, calculate P = (GPM
) . Cv rating is
Cv
supplied in the above chart.
2
Dimensions
Hose Size
12” [304.80] Length
24” [609.60] Length
½” [12.70]
½” [12.70]
Dimensions Inches [mm]
¾” [19.05]
1” [25.40]
¾” [19.05]
1” [25.40]
CUSTOM OPTION: The Flexible Hose set is also available in sizes 1 1/4” to 2”. Please
contact Customer Service for details at 800-543-9038.
Male NPT hose connection must mate with end connection of Union and Strainer (female
NPT must be selected for Strainer tallpiece and Union body if ordering hoses.)
800-543-9038 USA
14
866-805-7089 CANADA
203-791-8396 LATIN AMERICA
L30046 - 06/09 - Subject to change. © Belimo Aircontrols (USA), Inc.
NOTE: Every pipe package that is ordered with a flexible hose will have 2 hoses and will be