PROFI-8855 spec eng

PROFI-8855 spec eng
PROFIBUS Remote I/O Unit with 8 Expansion Slots
PROFI-8855
The PROFI-8855 Remote I/O Unit is specially designed for the slave device of PROFIBUS DP
protocol. It supports up to 8 slots for ICPDAS I-8k series, I-87k Low Profile series, and I-87k High
Profiles series I/O modules. In addition, we also provide hot-swap function for I-87k High Profiles
series I/O modules. To setup network, users can choose and configure I/O modules by using the GSD
file without any other setting tools.
Pin Assignments
Protocol& hierarchy: DP-V0 Slave
Detect transmission rate (9.6 ~ 12000 kbps)
automatically
Support all I-8k & I-87k I/O Module
Support Device-Related & Channel-Related Diagnosis
Address 0~126 set by rotary switches or SSA-Telegram
Support Hot-Swap for I-87k High-Profile Modules
Network Isolation Protection
3000 VDC isolation protection on PROFIBUS side
4 kV ESD Protection (contacting for any terminal)
Design Flowchart
Hot-Swap & Auto-configuration
Copy GSD file to
Configuration Tool
Select Module(s) &
Parameter Setting
Diagnostic message report when module pulls.
Auto-Reconfiguration issue when module plugs.
Programming &
Running though I/O
Object
1/2
Generate Object that
map from the I/O
Module.
Hardware
CPU
SRAM/Flash/EEPROM
80186, 80 MHz or compatible
512 KB / 512 KB / 2 KB
Watchdog IC
CPU built-in
8 slots
4 kV class A
Watchdog
Expansion Slot
ESD Protection
PROFIBUS Interface
Profichip VPC3+C
Controller
Transceiver
Connector
Baud Rate (bps)
Transmission Distance (m)
Isolation
Protocol
ADI ADM2486
9-pin female D-Sub
9.6 k, 19.2 k, 45.45 k, 93.75 k, 187.5 k, 500 k, 1.5 M, 3 M, 6 M, 12 M
Depend on baud rate (for example, max. 1200 m at 9.6 kbps )
3000 VDC for DC-to-DC, 2500 Vrms for bus-to-logic
DP-V0
UART Interface
COM
RS-232 (For updating firmware)
LED
Round LED
PWR LED, RUN LED, ERR LED
Power
Power supply
Protection
Power Consumption
Unregulated +10 ~ +30 VDC
Power reverse polarity protection, Over-voltage brown-out protection
5.5 W
Mechanism
Installation
Dimensions
DIN-Rail or Wall Mounting
312 mm x 91 mm x 132 mm (W x L x H)
Environment
-25 ~ 75 ℃
-40 ~ 80 ℃
5 ~ 95% RH, non-condensing
Operating Temp.
Storage Temp.
Humidity
Application
Diagram
Ordering Information
PROFI-8855
PROFIBUS Remote I/O Unit with 8 Expansion Slots
PROFI-8855 CR
PROFIBUS Remote I/O Unit with 8 Expansion Slots(RoHS)