Benson ECA Gas Cabinet Heater Installation Commissioning Servicing User Instructions
Below you will find brief information for Gas Cabinet Heater ECA. The ECA is a gas-fired forced convection heater available in a range of sizes from approximately 29.3 kW to 381.0 kW. The heater can be used for both ducted and free blowing applications. It is fitted with a forced draught burner, which has been test fired and pre-set before it is shipped. The controls are located on a removable panel that can be repositioned for remote operation.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
41
BENSON ECA CABINET HEATER (GAS F I R E D) INSTALLATI ON COMMISSI ONING SERVICING USER INSTRUCTIONS November 2005 Issue 1 PART NO 20-45-363 1 ~ CONTENTS ~ SECTION 1 1.0 Compliance Notices 1.1 Certificates of Conformity 1.2 General Product Information 1.3 General Requirements 1.4 Delivery & Pre-installation Checks 1.5 Warranty 4 5 5 5 6 6 2.0 Location & Positioning 2.1 Gas Supply 2.2 Electrical Supply 2.3 Air Supply 2.4 Minimum Space Requirements 2.5 Air Distribution System 2.6 Flue System 7 9 9 9 10 10 11 3.0 Installation 3.1 Packaging & Siting 3.2 Flooring 3.3 Minimum Clearances 3.4 Assembly 3.5 Flue Installation 3.6 Gas Installation and Connection 3.7 Electrical Installation & Connection 3.8 Air Distribution Installation 3.9 Warm Air Registers 3.10 Heater Control Installation 15 15 15 15 15 15 16 16 16 16 17 4.0 Commissioning 4.1 Pre-Test 4.2 Ignition 4.3 Air Delivery System 4.4 Hand Over 17 17 18 20 20 5.0 Servicing 5.1 Planned Servicing 5.2 Servicing Procedure - Major Component Parts 5.3 Servicing - Re-commissioning 6.0 Fault Diagnosis By Flow Charts 7.0 Wiring Diagrams by Model and Burner Type 8.0 Technical Data Net Efficiency Calculations 8.1 Benson Cabinet Range Data 21 21 21 24 25 27 33 34 9.0 Reference Documents Standards, Codes of Practice 9.1 Parts Listing 37 38 2 SECTION 2 10.0 Introduction 10.1 Commissioning/hand over 10.2 Servicing 10.3 Start up procedure 10.4 Stop procedure 10.5 Shutdown procedure 10.6 Ventilation only 10.7 Lockout situations 10.8 Contact Information ILLUSTRATIONS Page No 8 12-14 22 25 27 Exploded view Flue Systems Fan and Motor Configurations Fault Diagnosis Flow Charts Wiring Diagrams Any reference made to Laws, Standards, Directives , Codes of Practice or other recommendations governing the application and installation of heating appliances and which may be referred to in Brochures, Specifications, Quotations, and Installation, Operation and Maintenance manuals is done so for information and guidance purposes only and should only be considered valid at the time of the publication. Benson Heating cannot be held responsible from any matters arising from the revision to or introduction of new Laws, Standards, Directives, Codes of Practice or other recommendations. 3 1.0 Compliance notices The Benson Gas fired Cabinet Heaters detailed herewith are manufactured by Benson Heating Within a strictly controlled quality environment within the parameters of ISO 9001. These instructions are only valid if the following country code is on the appliance GB. IE. If this code is not present on the appliance, it is necessary to refer to the technical instructions which will provide the necessary information concerning the modification of then appliance to the conditions of use for the country. The Benson range has been tested and assessed for compliance with the following European Directives. Gas Appliance Directive (90/396/ EEC) Machinery Directive (89/392/EEC) Low Voltage Directive (73/23/EEC) & (93/68/EEC) Electromagnetic Compatibility Directive (89/336/EEC & 91/31/EEC) Where proprietary items are incorporated into Benson Heating products, detailed information and instructions are also provided as part of the information pack. It is the responsibility of the installer, owner, user, or hirer, of such products supplied by Benson Heating, to ensure that they are familiar with the appropriate information/ manuals, supplied by the manufacturer, and that they are suitably aware of the purpose of the manuals and the safety instructions. In addition, operators must be suitably trained in the use of the appliance so as to ensure its continued safe and efficient use. Benson Heating has a commitment to continuous improvement, and therefore reserves the right to amend or change the specification of the Cabinet Heater range subject to compliance with the appropriate European, national, and local regulations. Contained within the text of the manual, the words 'Caution' and 'Warning' are used to highlight certain points. Product Liability Directive (65/374/EEC) The manufacturer has taken reasonable and practical steps to ensure that Benson Cabinet Heaters are safe and without risk when properly used. These heaters should therefore only be used in the manner and purpose for which they were intended, and in accordance with the recommendations detailed herewith. The heaters have been designed, manufactured, assembled, inspected, and tested, with safety and quality in mind, there are certain basic precautions which the installer and user should be aware of, and they are strongly advised to read the appropriate sections of the information pack accompanying the heater, prior to installation or use. Benson Heating supports all new products being supplied to their customers with a comprehensive information pack; this clearly defines mandatory instructions for the safe installation, use, and maintenance, of the appliance(s). 4 Caution is used when failure to follow or implement the instruction (s) can lead to premature failure or damage to the heater or its component parts. Warning is used when failure to heed or implement the instruction (s) can lead to not only component damage, but also to a hazardous situation being created where there is a risk of personal injury. NOTE THE WARRANTY REGISTRATION CARD SUPPLIED WITH THE HEATER MUST BE COMPLETED AND RETURNED IN THE PRE–PAID ENVELOPE TO BENSON HEATING ON COMPLETION OF COMMISSIONING Warranty claims made without this condition being fulfilled will not be processed The Benson range of Gas fired Cabinet Heaters conform to the following harmonised standards; BS EN 1020 Requirements for non domestic gas fired forced convection air heaters for space heating incorporating a fan to assist transportation of combustion air and/or combustion products. BS EN 292 - Part 1 : 1991 Safety of Machinery - Basic Concepts, General Principles for Design Basic terminology, methodology BS EN 292 - Part 2 : 1991 Safety of Machinery - Basic Concepts, General Principles for Design Technical Principles and Specifications BS EN 60204 - Part 1 : 1993 Safety of Machinery - Electrical Equipment for Machines Specification for General Requirements or be used as free blowing units, but each heater must be connected to its own individual open flue. Each heater is fitted with a forced draught burner which has been test fired and pre-set prior to despatch. The safety functions of the burner are by way of a fully sequential control box fitted to the burner. Note Neither asbestos nor soft soldered joints are used in the construction or manufacture of the Benson range of Cabinet Heaters. The materials selected for use can withstand the mechanical, chemical, and thermal stresses which they will be subject to during foreseen normal use when installed in accordance with the manufacturers recommendations. 1.3 General requirements BS EN 60335 - Part 1 : 1988 Safety of Household and Similar Electrical Appliances General Requirements Caution Before installation, check that the local distribution conditions, nature of gas and BS EN 55014 - 1993 pressure, and the current state adjustment of Limits and methods of measurement of radio the appliance are compatible. disturbance characteristics of electrical motor-operated and thermal appliances for Installation, commissioning, and servicing household and similar purposes, electrical must only be carried out by appropriately tools and similar electric apparatus qualified and competent persons. BS EN 50165 - 1995 Electrical Equipment of non-electric heating appliances for household and similar purposes, safety requirements 1.1 Certificates of conformity Certificates are available from the Quality Control Department at Benson Heating. Notified body Pin reference is 63AQ0533. Warning Unauthorised modifications to the appliance, or departure from the manufacturers guidance on intended use, or, installation contrary to the manufacturers recommendations may constitute a hazard. Note To ignore the warning and caution notices, and to ignore the advice from the manufacturer on installation, commissioning, 1.2 General product information servicing, or use, will jeopardise any applicable warranty, moreover, such a The Benson range of indirect gas fired forced situation could also compromise the safe and convection heaters have an output range efficient running of the appliance itself, and from approximately 29.3 kW to 381.0 kW and thereby constitute a hazard. are available in a configuration that will allow for down flow, horizontal, floor mounting, or The installation of the appliance must meet above ground level on purpose built steel all the relevant European, national, and local supports. criteria. (See sections 3 and 9). Prior to installation the following points The units can suit either ducted applications, should be considered; 5 a) The position of the heater for the optimum efficient distribution and circulation of warm air b) The position of the heater relative to the route of the flue c) The position of the heater relative to the supply of gas d) The position of the heater relative to the electrical services, and if appropriate, any additional controls. e) The position of the heater relative to the supply of fresh air insurance criteria 1.5 Warranty The heater is supplied with a 2 year warranty made up as follows; first year covering parts and labour, and second year covering parts only. In addition to this there is also a 10 year time related warranty on the combustion chamber/heat exchanger. The warranty commences from the date of despatch from the manufacturer, and is subject to the terms detailed within the Benson Heating 'conditions of business'. f) The height if applicable at which the heater is to be mounted and potential stratification / Note (i) circulation problems. The warranty may be invalidated if g) The position of the heater relative to service and maintenance requirements a) The warranty registration/commissioning card has not been completed and returned to Caution Benson Heating The heater must not be installed within an area where the conditions are unsuitable, e. b) The installation is not in accordance with g. where the atmosphere is highly corrosive, the general requirements of this manual has a high degree of salinity, or where high wind velocities may affect burner operation. c) The flue arrangement and air supply for Suitable protection should be provided for the heater are not in accordance with the the appliance when it is located in a position manufacturers where it may be susceptible to external recommendations, codes of practice, or mechanical damage from; for example, fork similar standards lift trucks, overhead cranes etc. 1.4 Delivery and pre-installation checks The heater is supplied wrapped in heavy duty protective polythene. On receipt of the heater, the following checks should be carried out; a) The model is as per order d) Air flow through the heater is not in accordance with the manufacturers technical specifications e) Internal wiring on the heater has been tampered with or unauthorised service/ repairs undertaken f) The main electrical supply input to the heater has been interrupted during the heating mode b) That it is undamaged c) That it is suitable for the fuel supply d) That it is suitable for the electrical supply If any of these points are not satisfied then contact should be made with the Sales Office at Benson Heating as soon as possible by telephoning 01547-528534. In the case of claims for damage, this must be signed for as damaged and reported in writing within 24 hours of delivery, in order to comply with 6 g) The heater has been subject to and affected by the ingress of water in any form h) The heater is not operated at the rating(s) laid down in the manufacturers technical specifications i) The heater has not been operated or used within the normal scope of its intended application j) The manufacturer's recommended minimum service requirements have not been complied with Note (ii) All warranty claims must contain the following information to enable processing to take place; (1) Heater model (2) Heater serial number (3) Order reference/date of order, together with full installation details (name and address) (4) Details or symptoms of fault (5) Installers name and address. Indirect fired heaters must not be located in hazardous areas, however, it is permissible for the heater to supply air to such areas. The heater must not be installed within an environment where there is a high concentration of chlorides, fluorides, salts, or other aggressive or volatile chemicals / compounds. Nor should the heater be positioned where the burner could be adversely affected by high winds or draughts. The location chosen for the heater must allow for the fitting of an effective flue system. Faulty parts must be returned to the Knighton The location must also allow for adequate Spares Department, the address of which is clearance for the air supply, return air circulation, oil supply, electrical supply, whilst provided in Section 2 of this manual. Any also providing good and safe working such parts will undergo inspection to verify the claim. Replacement parts supplied prior access. The heater must be installed on a to this may be charged, and a credit supplied flat and level surface made from noncombustible material, which is sufficiently upon subsequent validation of the warranty robust to withstand the weight of the heater claim. and any ancillary equipment. Any Consumable items are specifically not combustible material adjacent to the heater included within the scope of the warranty. or flue system must be so placed or shielded so that its surface temperature does not Note (iii) Notification is required immediately a fault is exceed 65oC. suspected. In areas where it is proposed that more than The manufacturer will not accept responsibility for any additional damage that one heater is to be installed, a general scheme of circulation should be drawn up has been caused, expense incurred, or consequential loss resulting from any failure and maintained, thereby offering the best heat distribution. of the heater(s). All Benson Heaters are fitted with a pressure relief facility, this is incorporated into the design of the flue gas exit duct. Care should Warning All of the basic criteria must be satisfied prior therefore be taken in siting service connections and controls well away from the to commencing installation and pressure relief vent. commissioning, additionally, the Cabinet Heater must be positioned and installed so as to comply with all the relevant standards Warning and guide lines (see section 9.0), as well as Under no circumstances must the pressure relief be restricted, blocked, or have the free meeting national and local fire regulations exit of exhaust gas impaired or re-directed. and insurance criteria, especially if it is proposed that the heater is to be installed within a special risk area (e.g. proximity to where petrol engined vehicles are stored or parked, where cellulose spraying takes place, where woodworking machinery is operated, etc,). 2.0 Location /positioning 7 8 2.1 Gas supply - general The Benson range of gas fired cabinet heaters are all manufactured and pre-set for use with natural gas classified under the following categories, based upon the destination of the heater I2H , I2L, I2Es , I2E(R)B , I2Esi , The heater must be compatible with the gas supply, and each heater must be installed with a separate approved isolating gas cock positioned adjacent to and upstream of the union between the service pipe and the heater. The gas supplier should have been contacted to confirm that the supply feed (pipework and metering) is capable of delivering the required dynamic volume of gas, thereby ensuring that the minimum burner pressure can be achieved. Consideration should have also been given to the pressure drop on single and multiple heater installations, and the affect that such installations will have upon other plant sharing the gas supply. electrical isolation of the heater, furthermore, in the case of a unit wired for a three phase supply, the supply should only be used to serve the heater itself and no other plant or equipment. The position of the isolation switch must be such that it is adjacent to the heater and easily accessible at all times. In addition, the isolator itself must have a contact separation of not less than 3mm as per BS5991 clause 20.2. The Control Fuse ratings are detailed on the appliance data plate. Warning Ensure that the electric and gas supplies are turned off before any electrical work is carried out on the heater. Ensure that wiring cannot make contact with any surfaces liable to be subject to high temperatures or where the insulation of the wiring could be impaired as a result of such contact. All Cabinet Heaters must be earthed. Caution The main electrical supply must not be switched off or disconnected as a method for stopping the heater, the exception to this is in If it is necessary to fit a gas booster, the controls must include a low pressure cut-off an emergency, or during servicing, when the heat exchanger has been allowed to cool switch which must be fitted on the supply sufficiently to prevent any damage from side of the booster. It is also a requirement that the gas supplier is contacted prior to the occurring. Claims for damage will not be considered if they have resulted from fitting of the unit. incorrect wiring or the incorrect use of the heater. Note Reference to the Institute of Gas Engineers 2.3 Air supply publication UP-1 and UP-2 together with BS6891 is strongly advised. Consideration must be given to the provision Service and Installation pipework must be of of air for the purposes of combustion and a diameter equal to or greater than the inlet ventilation of the heated space, plant room or enclosure where heaters are to be installed connection on the heater, all joints must be sealed using an approved sealing compound, and the system purged and Note tested for soundness. It is strongly recommended that BS 6230 : 2005 is referred to for further information concerning ventilation requirements 2.2 Electrical supply Where mechanical ventilation is used it is a Wiring external to the cabinet heater must be requirement that the inlet is of the mechanical type, and the outlet is either installed in accordance with any local, national, and European regulations, as well mechanical or natural. as meeting the appropriate requirements of IEE regulations. The means of connection to the main electrical supply must allow for complete 9 The table in the next column provides specific data for each heater model as 2.3.1 Heaters installed within the heated space Where heaters are installed within the space to be heated (I.e. not a plant room or enclosure Combustion air or heater related ventilation air Will not be required if The design air change rate of the heated space is 0.5 air changes per hour or greater The design air change rate may be satisfied by natural infiltration or by mechanical ventilation Combustion and General ventilation will be required if The design air change rate of the heated space is less than 0.5 air changes per hour Where the heated space has an air change rate of less than 0.5 air changes per hour then it will be necessary to provide either natural ventilation openings to the heated space (section 2.3.1.1. refers) or the mechanical ventilation of the heated space (section 2.3.1.2. refers) MODEL 120 220 370 560 770 1020 2.3.1.2 Mechanical Ventilation to the Heated Space In the event that the heated space has a design air change of less than 0.5 air changes per hour and that installer prefers to mechanically ventilate the heated space rather than provide ventilation openings then - 2.3.1.1 Natural Ventilation Openings to the Heated Space • If the heated space design air change rate is less than 0.5 air changes per hour then provision for low level natural ventilation openings will only be necessary The minimum free area of the low level • natural ventilation opening shall be • 2cm2 for each kW of rated heat input The low level natural ventilation opening • should be situated on an external wall and be within 1000 mm of floor level for natural gas and ideally at floor level for l.p.g gas • installations but in any event no higher than 250 mm. 10 Minimum Free Area of ventilation opening The heated space needs to be mechanically ventilated so that the design air change is 0.5 air changes or greater. It is a requirement that the mechanical ventilation shall be of the ’input’ type with either natural or mechanical extraction. Systems of mechanical extraction with a natural inlet shall not be used It is necessary to provide an automatic means to safely inhibit heater(s) operation should mechanical air supply fail for any reason Mechanical ventilation systems where fitted must be provided with safety interlocks to prevent heater operation in case of air flow failure 2.4.3 Ventilation openings and Grilles Ventilation openings and grilles must communicate directly with the outside air, be of negligible resistance and shall be sited so that they cannot easily be blocked or flooded 2.5 Air distribution system Where the combustion air intake is not ducted to atmosphere heater installed in flue only configuration then ventilation can be via a permanent ventilation opening / grille situated at both Low level (Inlet) and high Level (Outlet) and with the free area of such grilles as :- All materials used within the construction of the delivery and return air ducts must not represent a fire hazard and should be made from thermally inert materials. The selection of materials must take account of the environment into which the heater and its air delivery system is expected to work, it must also take account of the stresses and loadings placed upon it during its normal working life Where interjoist spaces are used to route ducting these must be lined with fire resistant insulation material. Low level (Inlet) For heaters with a rated input of less than 60 kW — 9.0 cm2 per kW of heat input For heaters with a rated input of more than 60 kW — 540 cm2 plus for each kW of rated input over the 60 kW threshold an additional 4.5 cm2 High Level (Outlet) For heaters with a rated input of less than 60 kW — 4.5 cm2 per kW of heat input For heaters with a rated input of more than 60 kW — 270 cm2 plus for each kW of rated input over the 60 kW threshold an additional 2.25 cm2 Alternatively mechanical input (not extract) ventilation may be used in association with either mechanical or natural extract , and with a ventilation flow rate of 3.24m3/h per kW of total rated input Where mechanical extract is used to complement the above then the extract rate shall be 2.06m3/h per kW of rated heat input 11 In installations where forced recirculation is a feature, a full and unobstructed return air path to the heater(s) must be provided, with return air grilles connected by ducting directly to the return air inlet on the heater. The limit for recirculation should not be greater than 85% recirculated air to 15% fresh air. Where the heater is installed within a compartment or plant room the return air and discharge air arrangement must be such that the air circulation fan does not interfere with the operation of the flue. The return air intake and warm air outlet should therefore be fully ducted to and from the heater, respectively, within the compartment or plant room. If the inlet air is ducted to the outside, then the lowest edge of the inlet air duct must be at least 500 mm above the outside floor or ground level, it must also be fitted with an access point (s) to allow for cleaning and servicing to occur. The openings in the structure of the plant room, through which the ductwork passes must be of fire resistant material and constructed to prevent the likelihood of any fire from spreading. Provision must be made for the disconnection of the flue for inspection and service requirements, and it is strongly advised that where bends are fitted inspection covers are included. The materials from which the flue is constructed must be non-combustible, resistant to internal and external corrosion, and be capable of withstanding the stresses and loadings associated with normal use. Warm air outlets on ducted applications must When designing the flue system the prevention of the formation and entrapment be such that they cannot be closed or become blocked, which again would lead to of condensation must be a key consideration. an increase in static pressure and nuisance Twin wall or insulated systems are recommended as they tend to inhibit the shutdown. formation of condensates. The outlets must not be sited so that warm Where condensation is unavoidable traps air can be discharged onto combustible materials, if necessary, guard rails should be should be included to encourage the condensates to flow freely to a point from used to ensure that effected areas are kept clear. Return air intakes must not be located which they may be released, preferably into a gully. The condensate pipe from the flue to so that potentially harmful or hazardous the disposal point must be made from contaminated air can be drawn into the corrosion resistant pipe of not less than system. 25 mm internal diameter. In ducted applications the ductwork must be designed so as to give a static pressure within the limits stated in section 8 of this manual. It should be noted that if the static pressure is too high, nuisance shut-down will occur when the heater goes out on the overheat limit thermostat, if the static pressure is too low, then damage can be caused to the fan motor. 2.6 Flue system It is essential that the products of combustion are flued to the outside of the building. Each heater must have its own separate flue, with a flue diameter of not less than is detailed in section 8 within this manual. the minimum vertical length of flue must not be less than 3m. The flue should rise vertically, and the number of bends should be kept to a minimum. Flue pipe should be supported at intervals not exceeding 1.8mtrs Flue pipes below a height of 2 m should be guarded against the possibility of being accidentally touched when hot by personnel It is strongly advised that BS 5854; 1980, and BS 5440; parts 1 and 2, are used as consultative documents when considering flue requirements. Care should be taken to ensure that the flue terminal is not situated in a high pressure area, the proximity of buildings and other obstacles which will influence this must be taken into account, preferably at the design stage. See figures 2-12. 12 If the flue passes through a wall, ceiling, or roof made from combustible material then it has to be sleeved so as to provide a minimum of a 25 mm void between the exterior of the flue and the internal wall of the sleeve. The maximum permitted temperature of any adjacent combustible material is 65oC. The position of the flue and its terminal should be such that it does not impair the combustion process. It should terminate in an exposed position so as to allow the escape and dissipation of flue gases without risk of their re-entering the property through windows, ventilation ports, etc,. The flue should extend to at least 1m above the height of any object within 3,5m of the terminal. Flue terminals should be fitted on all flues with a diameter of 200 mm or less. The terminal must be of the approved type, and have outlet grilles on all sides giving a total free area of at least double that of the flue. Caution It is imperative that the flue should be properly sealed where it passes through the roof, this can best be achieved by using the approved method of roof flashing plate and cravat. Note It should be noted that claims made under warranty and attributed to the ingress of water may not be considered especially if an approved method of sealing has not been used, or if the design of the flue has not made provision for possible condensation problems. 13 1RWOHVVWKDQ PP 1RWOHVVWKDQ PP 3DUDSHW *UHDWHUWKDQPP Flat roof with parapet 1RWOHVVWKDQ PP H1 H2 /HVVWKDQK2 /HVVWKDQK1 *UHDWHUWKDQPP Flat roof envelope method H2 1RWOHVVWKDQ PP 6WUXFWXUH 6WUXFWXUH 2 H1 *UHDWHUWKDQK1 Flat roof where the flue height is more than 10 Heights (H) away from all structures 1RWOHVVWKDQ PP 6WUXFWXUH /HVVWKDQPP Flat roof with flue close to parapet 14 1RWOHVVWKDQ PP 1RWOHVVWKDQ PP Flat roof with no parapet 1RWOHVVWKDQ PP 6WUXFWXUH /HVVWKDQ PP Flat roof with structure close to flue outlet 1RWOHVVWKDQ PP 1RWJUHDWHUWKDQ ° Pitched roof not greater than 45° 15 1RWOHVVWKDQ PP 2.4 Minimum space requirements The minimum space requirements for single and multiple heater applications are detailed in section 3.3 later within this manual. 16 2.7 Flue Installation 3.3 Minimum clearances An integral flue spigot is fitted to all Cabinet Heaters thereby allowing the flue to connect The following minimum clearances (in directly to the heater. The design of the flue millimeters) must be observed when must ensure that it can be disconnected to installing the heater. allow for cleaning and servicing, furthermore, all of the flue section joint sockets must face upwards, and the seal between the sections Model Size Front Rear Lhs achieved through mechanical joints or 120 500 1,000 150 through the use of approved caulking string and grout. It is strongly advised that BS 5854 220 600 1,200 150 and BS 5440 parts 1 and 2 are referred to, 370 600 1,500 150 see also figs 2-12. Where condensation is likely to be a problem provision should be made preferably at the design stage (see section 2.5). Rhs 150 150 150 560 900 1,500 150 150 770 900 2,000 400 400 1020 900 2,000 500 500 3.0 Installation 3.4 Assembly It is strongly advised that the installer reads Section 2 and Section 3 of this manual prior to starting any installation work. It is a requirement that only qualified and competent personnel may undertake installation, commissioning, and servicing. Warning Always ensure that the appropriate personal protective equipment is used. 3.1 Packaging/siting The following sub-assembly parts should be assembled to allow installation to continue. (a) Vertical Nozzled Models For free blowing applications it will be necessary to complete the final assembly before continuing with the installation. The bonnet top with nozzle spigots should be attached to the heater and secured. The nozzles should then be pushed home on the spigots and positioned to provide the desired airflow. Ensure louvres are adjusted outwards and ensure blades are not resonating The nozzles should be securely fixed in their desired position on completion of commissioning. The heater will usually be supplied wrapped in heavy gauge polythene, non assembled parts will be supplied separately. Prior to installation, the assembly of the heater should be completed, it is advisable that this is undertaken in the area where the heater is (b) Horizontal Nozzled Models scheduled to be sited. Remove packaging and secure the 90o Duct Outlet to the outlet on the heater using the Caution bolts supplied. It is strongly advised that when positioning Secure the nozzle spigot plate to the duct the heater the lifting eyes are used, thereby outlet using the bolts and prevailing torque reducing the risk of inadvertent damage nuts provided. Fit the securing brackets to being occasioned to the heater. each of the outlet nozzles, and lift the complete heater assembly and position on 3.2 Flooring the pre-sited purpose built supports. Finish off the assembly by fitting and securing the The heater must be installed on a level non outlet nozzles to the spigots by way of combustible surface capable of supporting previously fitted brackets. the weight of the heater and any ancillary equipment. 17 3.5 Gas Installation/Connection Service pipework must terminate at an approved gas cock, and be adjacent to the position of the heater. The connection to the heater can be made by way of either an approved flexible coupling, or rigid connection. Threaded connections must comply with ISO288/1 of ISO 7/1, further information concerning the accepted practice in European countries is detailed in the June 1995 version of prEN 1020 annex A7 The diameter of the pipework from the cock to the burner connection must not be less than the diameter of the burner connection inlet. (see section 8 ) The installation must be purged and tested for soundness prior to commissioning. Always ensure that the appropriate personal protective equipment is used. 3.6 Electrical Installation/Connection Benson cabinet heaters are available either for 415V 50Hz 3PH or 230V 50Hz 1PH supplies depending upon the model specified. It is recommended that reference is made to the wiring diagrams contained within section 7 of this manual prior to installation or connection to the supply. The electrical supply must be as specified and suitable for the heater, and must be run within conduit to a point adjacent to the heater, and be terminated to provide an isolation point that will prevent remote or inadvertent activation. Cables, conduit, and fittings that are used to make the connection between the isolator and the heater must conform to the appropriate IEE regulations. Warning Always isolate from mains electrical supply before commencing work on the heater. Always ensure that the appropriate personal protective equipment is used. 3.7 Air Distribution Installation The materials selected must be of low heat capacity, and it is preferable that all warm air ductwork is thermally insulated. Where ducting may be subject to deterioration from exposure to moisture or high humidity material selection and insulation are prime considerations. Joints and seams must be airtight and fastened securely and designed to remain so, even when operating at high temperatures. Adequate support must be designed into the layout of the ductwork to ensure that the integrity of the seams and joints is maintained. The support must be independent and separate from the heater and the ducting, to allow for free movement during expansion and contraction. Where ducting passes through walls or partitions sufficient clearance must be left, irrespective of any fire stop requirement, to allow for expansion and contraction Failure to adhere to these latter two points can result in the generation and transmission of excess noise. Where ducting is installed in concrete flooring a permanent membrane must be used to isolate the ducting from the corrosive effect of the alkaline salts within the concrete. Care should be taken to ensure that soft insulation material does not become compressed and thereby lose its effectiveness. All heaters are supplied fused and pre-wired, all must be earthed. 3.8 Warm Air Registers Final connections for any additional external controls must be completed on site, and must be carried out according to IEE regulations. Separate user information is provided for the time control unit and the burner, and forms part of the product information pack which accompanies every heater when despatched. 18 In order that vertical temperature gradients are minimal thereby providing a more even heat distribution, it is preferable to install warm air registers at low wall levels or at floor level, with the size, number, and position commensurate with the requirement of the application. To minimise noise levels the registers should be set away from corners, additionally, a good seal between the register frame and the wall is important, particularly on high level positions, if unsightly staining through warm air/ particulate deposition is to be avoided. mean that on site commissioning is less important than might otherwise be the case. Note It is strongly recommended that equipment used for the sampling and analysis of flue gases is accurate to within +/- 0.1% and maintained so that it is regularly calibrated. 3.9 Heater Control Installation 4.1 Commissioning - Pretest Check to ensure electrical safety, and Warning Isolate heater from mains before undertaking inspect and check the installation, testing for leaks. any electrical work. (a) Ensure that the electrical supply is turned off. All Cabinet Heaters from are manufactured and supplied with a CP4 Optimised Control (b) Ensure that the gas supply is turned off. as standard . Set CP4 Control as per Basic Setting Guide Instruction Sheet Supplied (c) Check that all panels and fasteners are secure and in place. The controls are located on a removable panel which when separated from the heater can be re-positioned so as to offer a remote facility. However, to facilitate this, it is necessary to order and fit an electrical panel cover and front panel blanking plate to the heater in place of the control unit. (d) Check that the heater is installed so that it is square and that the support is adequate. The controls for Horizontal Cabinets are supplied as remote option. 4.0 Commissioning It is a requirement that only suitably qualified and competent personnel are allowed to undertake the commissioning of the heater. It is also strongly recommended that prior to commissioning the engineer familiarises himself with; the information contained within the information pack that accompanies the heater, the heater itself, and with the specific requirements of the installation /application. (e) Ensure that warm air delivery outlets are open and that ducting is adequately supported. (f) Ensure that if filter assemblies are fitted that they are secure and correctly located. (g) Check that air inlets are clear and that return air paths are adequate. (h) Ensure that the flue is secure, adequately supported, and that the various joints are properly sealed. (i) Check that condensate trap and drain facilities are adequate. (j) Check that there is provision for flue gas sampling and that this sample point can be plugged and sealed after commissioning. (k) Check that fan and limit stat settings have not been disturbed and are as follows 120/560 770/1020 Range Warning Fan on 60oC Fan on 50oC All Cabinet Heaters undergo a rigorous test o C programme prior to being despatched, whilst Overheat limit -100oC Overheat limit -100 o Fan off 30oC Fan off 30 C such a programme does involve precommissioning and setting up the heater to operate efficiently and well within its designed operational limits, this does not 19 Also check that the white button (automatic) is pulled outward and that the red button (reset) is pushed inwards to the reset position. See fig 15. Interval 1 <5s (l) Remove lower panel and check motor and fan drive system for integrity of joints, check 2 <40s pulley alignment, fan rotation, and belt tension (see section 5.2 and figs 17 and 18). (m) Ensure that the burner is securely attached to the heater. Operand Combustion air damper actuated, burner fan motor initiates purge cycle... Pilot valve opens ignition transformer provides spark for pilot ignition... -------- E I T H E R -------- 3 >40s Ignition failure caused by gas (n) Test for electrical earth continuity starvation resulting in burner lockbetween the heater, oil pipe work, and mains out/shut-down... supply. CP4 Control Press FAN /Enter The fan will start enabling fan direction etc to be verified. Reset on/standby switch to standby position (h) Clear burner lockout using burner reset function. (p) Turn mains electrical supply to off, replace and secure lower louvered panel covering fan and motor assembly. (j) Open gas supply cocks Repeat steps 4.2 c,e,f. (i) Set heater on/standby switch to standby position ----------- O R ---------3 >40s Pilot ignition... Burner ignition... 4 <60s Burner ignition cycle complete Note 4.2 Commissioning - Ignition It is strongly recommended that the separate manual concerning the operational details of Warning the burner supplied with the heater as part of Do not proceed with commissioning unless the information package is studied prior to all the criteria detailed within sections 4.0 commissioning. and 4.1 have been satisfied. Time intervals within the ignition sequence (a) Ensure that the electrical supply is turned will vary slightly from one model to another. off. Warning (b) Ensure that the gas supply is turned off. If burner ignition is not satisfactorily accomplished, commissioning must not (c) Select the following switch settings on the proceed until the reason or fault has been identified and rectified, if necessary by heater reference to the separate burner information or to section 6 of this manual. (d) Turn on main electrical supply. (q) Set controls to demand settings (e) Prog 0000 Enter 1TEMP key in an operating temp and Enter Press RUN 3 times to return to main screen Press OVER button Select 1 OVERIDE then select 1 and key in 01 hour override this will allow enough time to commission the heater safely (f) Check for the following burner sequence 20 ( j ) Repeat steps 4.2 (k) Re-check all connections and joints for gas soundness using an approved leak detection fluid. (l) Remove burner cover and attach manometers to check burner pressure settings. (m) Repeat steps 4.2 d,e,f, allowing the (iii) Check integrity of unit, ensuring that neither the bi-metallic strip nor its casing is (n) Check burner pressure settings are in line damaged. with the data as per section 8.1 (if (s) Undertake flue gas analysis using adjustment is necessary refer to separate approved and calibrated analysing burner information within section B) equipment recording data on the Note (i) commissioning card, ie, CO, CO2, net and The figures quoted in section B are gross flue temperatures. Record mains gas, independent test figures based upon zero and burner head pressure, ambient flue resistance. temperature, barometric pressure, and complete percentage efficiency calculation (o) Adjust room thermostat to its highest using the formula detailed in section 8. setting, and allow the heater to continue to fire. Note (ii) (p) Gradually reduce the temperature setting The burner air and gas pressure settings on the room thermostat until the burner shuts should be only very finely adjusted to achieve a CO2 reading of 9.3% (+/- 0.1%). down, (@ < ambient) and then gradually increase the temperature setting on the thermostat until heat is called for, Note (iii) (@ > ambient) and the burner automatically The net efficiency must not be lower than 79% for heaters fitted with a modulating or re-fires. hi / lo burner. In other cases the net efficiency level must (q) Re-set time clock to a minimum off period, checking that the burner shuts down, not be lower than 84% and then automatically re-lights once the minimum off period has elapsed (Separate Note (iv) All Cabinet Heaters are test fired and preinformation on the time clock is contained within the information package supplied with commissioned as part of the manufacturing process, if however, during on site the heater). commissioning the data are found to be not in accordance with the manufacturers data, (r) Check fan and limit stat by depressing and holding in the fan motor overload re-set then the following action is recommended. button, located on the heater electrical panel. * Re-check all readings and calculations. * Adjust burner as per manufacturers The time between the fan stopping and burner shut down should be noted, once the instructions. * Consult Benson Heating Technical burner has shut down the overload on the Department. motor should be released. (t) Complete commissioning card and If the time interval between fan stop and burner shut down is greater than 90 seconds provide operating instructions for the user, high-light the fact that the manufacturer further checks should be made. recommends that in the interests of safety These are as follows: and efficiency the heater is serviced on a regular basis only by qualified and competent (i) Check settings on fan and limit stat are persons. correct, ie, fan on 60oC, fan off 30oC, limit 100oC. The completed commissioning card must be returned to Benson Heating Service On completion delete any override settings on optimised control and return temperature Department immediately after the satisfactory completion of commissioning, settings to customer requirements failure to do so can invalidate any subsequent warranty claim. (ii) Check that the position of the unit is correct, ie, equi-distant between heat exchanger body and heat shield panel. (u) Set all controls to the requirements of the heater to reach thermal equilibrium. 21 user. For setting information See Fan belt section page 23 4.3 Commissioning - air delivery system On free blowing applications the integrity of the fastenings on the heater top and outlet nozzles must be checked . Final adjustment for the direction of the air flow from the nozzle hoods should be made. Ensure louvres are adjusted outwards and ensure blades are not resonating and the hoods should be secured in the required position by drilling through the two holes provided in the hood outer ring and fastened in place using self tapping screws . Caution On ducted applications it is necessary that the system is balanced in order to optimise the efficiency of the heater and the air distribution and delivery system. Failure to balance the system can result in fan motor overloading and premature component failure, it can also result in an inefficient heating/ventilation system. (a) Check that the amount of fan produced air volume is in accordance with the heater specification, if the volume is too great the fan can be overloaded. Ensure that the running current is as per that stated on the heater data plate. Alternatively, the static pressure should be measured at the start of the ductwork to confirm that it is within the permissible tolerance. (b) If the current drawn is greater than the stated running current, in most probability this will be caused by insufficient static pressure within the ductwork, in which case system resistance should be increased through the introduction of a damper placed as close to the start of the ductwork as possible, thereby resulting in a reduction in drawn current. The damper should be adjusted until the current is in accordance with that stated on the data plate. (c) If the current drawn is too low the duct outlet grilles will require opening to reduce static pressure and increase air volume, if this is not the case overheat cut outs can be caused. On Completion of commissioning the fan belts should checked for the correct tension 22 4.4 Commissioning - hand over (a) Upon full and satisfactory completion of commissioning, a record of commissioning information (contact, date, etc) should be left with the heater, a copy of which must also be forwarded to Benson Heating Service Dept. (b) The commissioning engineer must ensure that the user is familiar with the safe and efficient use of the heater, detailing the function of all controls and main components. (c) The user should be made aware of the following in particular (i) Lighting, shutdown, and operational information. (ii) Safety features, data plate, and labeling. (iii) The requirement for regular inspection especially if the heater is within a more demanding environment - and the need for regular servicing carried out by competent and qualified persons. (d) Section 2 'User Instructions' should be left with the customer upon satisfactory completion of the commissioning and handover. Caution After approximately 100 hours of running, the tension of the fan belts must be checked to ensure that they are correct and that they have not stretched. See section 5.2 for further instructions 5.0 Servicing Warning Servicing must be carried out on a regular basis, the maximum interval between services being 1 year. It is a requirement that only suitably qualified and competent persons are allowed to undertake servicing. Before any maintenance or servicing work is carried out the heater must be shut down and allowed to cool, and have the gas and electric supplies to it turned off at the gas cock and isolator respectively. Caution Certain component parts are factory sealed and are designed so as to be tamper proof. Usually such items do not require servicing, and therefore should not be tampered with. Failure to comply with this can invalidate any warranty, and can also lead to premature failure. The following parts fall within this category: room thermostat, time clock, frost thermostat, sequential controller, and fan and motor. Additionally, the fan and limit stat has been factory set, and must not be re-set without formal consent from the manufacturer. Reference should be made to the separate information covering the operational details of the burner and timer. Only approved spare/replacement parts can be fitted, failure to comply with this can compromise the safe and efficient running of the heater, and can also invalidate any warranty claim. 5.2 Servicing Procedure - Major Component Parts Flue A visual inspection should be carried out to ensure that the flue remains adequately supported, both internally as well as externally, and that the various joints are effectively sealed. Inspection covers, where fitted, should be removed and the flue checked to see whether cleaning is required If inspection covers are not fitted the flue gas exit duct and flue spigot will provide not only an indication of the cleanliness of the flue, but will also enable access for cleaning. The presence of the flue terminal should be checked. If a condensate trap and drain facility is fitted this should be checked to ensure that it continues to function correctly, and the drainage of condensates is not impaired. Main Fan Motor 5.1 Planned Servicing Remove access panel, dust and other In order to maintain the efficient operation of foreign matter should be cleaned by blowing over with compressed air and through the the heater it is recommended that the following planned servicing and preventative use of a soft bristle brush and cloth. Solvent wipes may be used to remove heavy soiling maintenance programme is adopted by the from the motor casing. user. Traces of surplus lubricants spreading from Quarterly Inspection the bearings should also be cleaned away. (a) Visual inspection of the burner Where motors are fitted with grease nipples (b) Clean and check ionisation probes (c) Check overheat safety is operational bearings should be lubricated with the correct grade of lubricant. motors which do not have grease nipples feature sealed Bi-Annual Inspection bearings which are lubricated during (a) As per quarterly inspection, plus... manufacture for their life. (b) Combustion check The electrical connections should be checked as follows. Annual Inspection The cover to the terminal box should be (a) As per half year inspection, plus. removed by undoing the screws which (b) Heat exchanger and cleaning secure it. (c) Electrical connections Check connections for signs of corrosion, (d) Main fan motor tightness, and ensure that there are no stray (e) Main fan assembly strands which could form a short circuit. (f) Pulleys Clean, tighten, and replace as necessary. (g) Fan belts Replace cover and secure (h) Gas supply (i) Burner (j) Air delivery system (k) Flue (l) Report 23 Motorised Fan Assembly 120-220 Fan and Motor Assembly 370-560 Fan and Motor Assembly 770-1020 24 Main Fan Remove dust and other foreign matter by blowing off with compressed air or through the use of a soft bristle brush. Check that the bearings do not show signs of excessive wear. It should be noted that these bearings do not require lubricating. If the bearings require replacing the following procedure should be followed. (a) Remove belt(s). (b) Loosen setscrew on eccentric collar and tap collar in the opposite direction to fan rotation. (c) Remove collar and bearing. (d) Check shaft for alignment and straightness. (e) Locate the bearing in its seat and place on the shaft with the cam facing outwards. (f) Fit the eccentric collar and engage the cams. (g) Tighten initially by rotating, and then by tapping in the direction of the fan rotation. (h) Replace fasteners and secure. (i) Turn by hand to ensure free fan rotation. Fan Belts Check belts for signs of wear. Frayed or split belts must be replaced using belts with a common batch code. Belt tension must be checked, and if on multi-belt units it is found that one belt contains more slack than its accompanying belts, then all the belts on the unit must be replaced, again using a common batch code. Replacement and tensioning is carried out as follows. Note The maximum displacement at the mid point of the top edge of the belt must not be greater than 16mm per metre of span, when a force of 3kg is applied in a plane perpendicular to the belt. (a) Loosen fan motor securing bolts on chassis. (b) Loosen fan motor slide adjustment bolt. (c) Slide fan towards fan to slacken belts. (d) Replace belts, pull fan motor away from fan until belts are tight. (e) Tighten adjustment bolt to hold motor. (f) Tighten fan securing bolts ensuring that the fan is square and the pulleys aligned. Pulleys Check pulleys for alignment using a straight (g) Check belt tension, making final edge, if necessary reposition either or both of adjustments as necessary. (h) Tighten and clamp fasteners to hold fan the pulleys and the fan motor. Check for motor in position. excessive wear within the root and sides of the grooves, and check for any other signs of Heat Exchanger wear or damage, if necessary replace the The heat exchanger requires a visual pulley as follows. inspection at least once per year, this should (a) Release tension on belts and remove. (b) Release the taper locks by slackening the be accompanied by cleaning. securing screws by several complete turns. It is recommended that a flue brush and vacuum cleaner are used to facilitate this. (c) Fully remove one screw from the taper Access to the heat exchanger is gained lock, and having oiled it, insert into the through the removal of the rear upper panel threaded jacking point. (d) Tighten screw until the taper lock is free. and heat shield. Servicing and cleaning should be performed (e) Remove taper lock and pulley. as follows. (f) Fit taper lock in new pulley, and provisionally position on the shaft. (g) Remove the screw from the jacking point, (a) Remove brass nuts and cover from heat exchanger end assembly to expose heat and tighten both screws in their clamping points until the pulley can just be moved on exchanger tubes. (b) Remove any accumulated deposits from the shaft by hand. the tubes by pushing through the full length (h) Align pulleys using a straight edge, and by gradual alternate tightening of the screws with a flue brush. (c) The flue brush should be withdrawn so as clamp in position. to pull any deposits back into the bottom of (i) Refit belts and check for the correct the flue box where they can then be removed amount of tension. 25 by using a vacuum cleaner. (d) Particular attention should be paid to the upper internal surfaces of the tubes, where through convection heavier deposition is likely to occur. (e) Any deposits which may have accumulated within the combustion chamber can be removed with a vacuum cleaner once the burner is removed. manufacturer. Note It is most important that the burner is serviced regularly and in accordance with the manufacturers instructions. Air Delivery System A visual inspection should be undertaken to ensure that the air delivery system is in good order, and that it remains adequately supported and that the various joints are effectively sealed. Note It is most important that a build up of deposits is not allowed to occur as this can have an adverse effect upon the efficiency of Report the heater and reduce the life of the heat A full and detailed service report should be exchanger. prepared, it is advised that the report is not completed until the heater has been re(f) The heat exchanger and combustion commissioned, where upon the completed chamber should be visually inspected for report can then be run through with the user. signs of splits, cracks, and distortion (g) All gaskets should be checked to ensure that they continue to provide a gas tight seal, 5.3 Service Re-commissioning if there is an element of doubt then they The heater should be re-commissioned as should be replaced. follows, as per section 4.1 through to section 4.4 inclusive. If the condition of the heat exchanger gives cause for concern the Service Department at This must be regarded as a necessary part Benson Heating should be advised pending of the heater service by the servicing engineer. a more detailed examination. Electrical Supply All connections must be checked to ensure that they are secure, and free from corrosion. Terminals and connections should also be checked to ensure that no stray strands are bridging terminals. Electrical continuity should also be checked. Gas Supply The gas supply pipework, and fittings should all be inspected to ensure that they are free from corrosion, and to ensure that where brackets have been fitted these remain secure and offer adequate support. The system should be soundness tested in accordance with Institute of Gas Engineers recommendations detailed in UP-1 and UP-2. Burner Service requirements for the burner fitted to the cabinet heater are covered in the separate manual prepared by the burner 26 Check On/Off Switch Check Isolator No Power Check Fuses Burner fails to Run Check for Lockout Check Thermostat No Demand Check Timer Check Overheat Check Voltage Check Control Box and Burner Check Gas Supply Ensure Gas Cock is Open Fan Starts but Burner goes to Lockout Air in Gas Feed Faulty Air Pressure Switch Ignition Failure Check Air Pressure Switch Check Flame Probe Check Burner Motor Ensure start Gas Valve Opens Purge Air Check as per Burner Manual Check Control Box Faulty Ignition Transformer Faulty Electrode Control Box Fault 27 Check HT Lead and Connector Check Gap Check Insulation Check Gas supply Excess Air Check that flue Gas CO is as advised Adjust damper to suit Burner lights on start gas but fails to establish main flame Check Flame Probe Low Gas Pressure Signal Check Inlet Gas Pressure Check Main Burner Gas Pressure Position Check Controls Check Burner Check Control Insufficient air passing over Heat Exchanger Burner starts but excess temperature shuts down the burner on overheat lockout Check air to inlet is not restricted Resistance too high Check Low Flame Switch is On Check Slow Acting Valve Remove Obstruction Clean Filters Check Outlet Grilles are Open Check Nozzles are Open High Return (inlet ) Air Temperature Fan Belt Slipping Adjust and or replace Belts Impellor Slipping Tighten Couplings Faulty or incorrectly set Fan Limit Control Check for warm air short circuit to Air Inlet Reset Fan Limit Control 28 Reset Nozzles away from adjacent walls Drawing 20-45-311 Riello ON / OFF Gas or Oil Fired Burner 230v/1ph/50Hz CP4 Control 29 Drawing No 20-45-312 Riello ON / OFF Gas or Oil Fired Burner 230v/1ph/50Hz CP4 Control 30 Drawing No 20-45-313 Riello ON/OFF Gas or Oil Fired Burner 415v/3ph/50Hz CP4 Control 31 32 8.0 Technical Data Formulae for calculating efficiency are detailed as follows: where q1 is the heat of the dry products of combustion (% of heat released per unit volume of gas) q2 is the heat of the water vapour contained in the products of combustion ( % of heat released per unit volume of gas) c1 is the mean specific heat of the dry products of combustion (in MJ / m3 K) t1 is the average combustion air temperature (in 0 C) t2 is the average temperature of the products of combustion (in 0 C) Hi is the net calorific value of the gas at 1013 mbar and 150 C , dry (in MJ / m3) Hs is the gross calorific value of the gas at 1013 mbar and 150 C , dry (in MJ / m3) Vf is the volume of dry products of combustion per unit volume of gas (in m3) Vf is calculated from the volume of CO2(V CO2) produced by the combustion of 1m3 of gas (see table below), and from the CO2 content of the products of combustion (V CO2,M) V CO2 Vf = ------------------ x 100 V CO2 M Ref. Gas V CO2 G110 0.26 G120 0.32 G20 1 G25 0.86 The net efficiency E (net) (in %) is given by: where t2 - t1 q1 = C1 x Vf ------------ x 100 Hi G30 G31 4 3 E (net) = 100 - ( q1+ q2 ) and Hs - Hi q2 = 0.077 ------------ (t2 - t1 ) Hi Note The required net efficiency must not be less than 84% On heaters that are fitted with modulating or Hi / Lo burners the testing is carried out with the appliance adjusted to give the minimum rate, and the following formula is used. Qn 10 ( Qn - Qmin ) ---------------------- in % Qn is the nominal heat input Qmin is the minimum obtainable heat input Emin > E n - En is the net efficiency determined by the Notified Body Note The minimum net efficiency for appliances fitted with modulating or Hi / Lo burners must not be less than 79%. 33 8.1Technical Data Range MODEL 120 220 370 HEAT OUTPUT kW/hr Btu/hr 35.35 120,545 63.15 215,468 108.73 370,978 HEAT INPUT (GROSS) KW/hr Btu/hr 43.05 146,900 76.73 261,800 131.71 449,394 GAS CONSUMPTION M3/hr Ft3/hr 145.8 258 441 BURNER TYPE RIELLO GS5 GS10 GS20 BURNER GAS PRESSURE (zero resistance cover fitted) Mbar 2.7 4.1 3.1 MINIMUM GAS INLET PRESSURE Mbar Ins WG 17.5 7 17.5 7 17.5 7 HEAD SETTING (zero flue resistance) Number 1.5 AIR SHUTTER SET (zero flue resistance) Number 3 GAS CONNECTION RC½ RC½ RC¾ AVAILABLE OUTLET PRESSURE Pascals Ins WG 100 0.4 100 0.4 150 0.6 NOZZLE DISCHARGE VELOCITY M/sec Ft/min 4.53 888 5.91 1159 6.98 1369 AIR THROW (APPROX) Mtrs Ft 14 45 17.1 55 20.2 65 AIR DELIVERY M3/sec Ft3/min 0.71 1500 1.39 2950 2.65 5620 TEMPERATURE RISE THROUGH HEATER Deg C Deg F 50.3 122 49.8 122 44.5 112 EFFICIENCY NET % 91.18 91.38 91.68 SOUND LEVEL Dba 69 72 76 COMBUSTION CHAMBER (press) Mbar 0.21 0.34 0.88 FLUE RESISTANCE Min Mbar Max Mbar -0.2 0.6 -0.2 0.6 -0.2 0.6 FLUE DIAMETER Mm 125 175 175 ELECTRICAL SUPPLY Standard 230/1/50 230/1/50 415/3/50 RATED INPUT KW 0.55 0.99 2.2 FUSED ISOLATOR SIZE Amps 16 20 16 RUNNING CURRENT Amps 4.8 7.2 5.2 ELECTRICAL SUPPLY Optional N/A 415/3/50 230/1/50 RATED INPUT KW N/A 0.99 2.2 FUSED ISOLATOR SIZE Amps N/A 16 40 RUNNING CURRENT Amps N/A 2.2 14 WEIGHT Kg 196 243 332 AIR NOZZLE SIZE Ins 9.4 9.4 11 NOZZLE AMOUNT No 2 3 4 209 200 194 FLUE TEMPERATURE (GROSS) 0 @ 20 C Ambient 34 Technical Data Range MODEL 560 770 1020 HEAT OUTPUT kW/hr Btu/hr 163.39 557,486 225.60 769,747 300.21 1,024,317 HEAT INPUT (GROSS) KW/hr Btu/hr 196.80 671,480 274.91 938.000 366.01 1,248,826 GAS CONSUMPTION M3/hr Ft3/hr 662 927 1230 BURNER TYPE RIELLO GS20 RS28.1 RS38.1 BURNER GAS PRESSURE (zero resistance cover fitted) Mbar 5.8 8.2 5.7 Mbar Ins WG 17.5 7 17.5 7 17.5 7 3.5 5 4 6.5 3.5 4 RC1¼ RC1¼ RC2 MINIMUM GAS INLET PRESSURE HEAD SETTING (zero flue resistance) Number AIR SHUTTER SET (zero flue resistance) Number GAS CONNECTION AVAILABLE OUTLET PRESSURE (STD) Pascals Ins WG 188 0.75 175 0.7 250 1 NOZZLE DISCHARGE VELOCITY M/sec Ft/min 6.71 1315 7.39 1445 8.49 1665 AIR THROW (APPROX) Mtrs Ft 21.7 70 24.8 80 31.1 100 AIR DELIVERY(STD) M3/sec Ft3/min 3.4 7200 4.86 10,300 6.88 14,680 TEMPERATURE RISE THROUGH HEATER Deg C Deg F 49.2 120 48 118 45 113 EFFICIENCY NET % 92.2 91.13 91.09 SOUND LEVEL Dba 78 81 81 COMBUSTION CHAMBER (press) Mbar 0.62 0.92 0.9 FLUE RESISTANCE Min Mbar Max Mbar -0.4 1.6 -0.4 1.6 -0.4 1.6 FLUE DIAMETER Mm 200 225 250 ELECTRICAL SUPPLY Standard 415/3/50 415/3/50 415/3/50 RATED INPUT KW 3 5.5 7.5 FUSED ISOLATOR SIZE Amps 25 32 64 RUNNING CURRENT Amps 6.5 11 24 ELECTRICAL SUPPLY Optional N/A 646 1090 RATED INPUT KW N/A 14.6 18.5 FUSED ISOLATOR SIZE Amps N/A 4 4 RUNNING CURRENT Amps N/A 340 300 WEIGHT Kg 540 330 332 AIR NOZZLE SIZE Ins 12.6 11 11 NOZZLE AMOUNT No 4 3 4 175 207 206 FLUE TEMPERATURE GROSS 0 @ 20 C Ambient 35 9.0 Reference Information Doc/Ref BS EN 1020 :1998 BS EN 292 Title/Subject Non Domestic Gas Fired Forced Convection Air Heaters For Space Heating Parts 1 and 2; 1992 Safety of Machinery BS EN 60204 Part 1; 1993 Safety of Machinery - Electrical BS EN 60335 Part 1; 1988 Safety of Electrical Appliances BS EN 55014 1993 Electromagnetic Compatibility BS EN 50165 1995 Safety of Electrical Equipment BS 5854 1980 Code of Practice - Flues/Flue Structures BS 6891 1988 Installation of Pipework < 28mm BS 5991 1989 Indirect Gas Fired Heaters < 2 MW BS 715 1993 Metal Flue Pipes and Fittings BS 5440 Part 1 ; 1990 Specification/Installation of Flues BS 5440 Part 2 ; 1989 Ventilation Requirements Gas Appliances ISO 7/1 (see also BS21 ) ISO 228/1 See also BS 2779 and BS 5380) Pipe Threads Seals and Couplings Specification for Metric Pipe Threads UP/1 (Replaces IM/5 & IM/16 ) Installation of Gas Appliances UP/2 (Replaces IM/7 ) Installation of Gas Appliances 36 Parts list DESCRIPTION 120 220 Heat Exchanger Assy 31-28-128 20-45-154 Stackbox Assy 31-28-078 31-27-123 Front Lower Inlet Panel 31-28-075 20-45-144 Front Top Panel 31-28-126 20-45-143 Back Top Panel 31-28-083 20-45-137 Heatshield Front Panel 31-28-124 20-45-140 Heatshield Back Panel 31-28-123 20-45-141 Flue Box Cover Assy 31-28-115 20-45-094 Rear Lower Inlet Panel 31-20-107 20-45-139 Fan/Limit Thermostat 28-60-023 28-60-021 Fan/ limit Stat Gasket 20-33-549 20-33-549 Burner Plate Gasket 31-28-080 30—40-156 Pressure Relief Gasket 31-27-121 31-27-121 Sight Glass 20-30-151 20-30-151 Sight Glass Holder 20-30-061 20-30-061 Sight Glass Gasket 31-28-084 31-24-084 Fuse 1ph 28-07-049 28-07-049 Nozzle Outlet Assy 31-30-167(2) Tray Spigot Assy 31-30-176 Motorised Fan 1ph 28-09-049 Fan Restrictor 28-09-002 N/A Burner c/w Gas Train 29-99-445 Control panel CP4 37 29-99-446 DESCRIPTION 370 560 Heat Exchanger Assy 20-46-283 20-46-355 Stackbox Assy 31-27-123 20-46-307 Front Lower Inlet Panel 20-46-311 20-46-327 Front Top Panel 20-46-312 20-46-332 Back Top Panel 20-46-289 20-46-338 Heatshield Front Panel 20-46-291 20-46-336 Heatshield Back Panel 20-46-290 20-46-335 Flue Box Cover Assy 20-45-094 20-46-310 Rear Lower Inlet Panel 20-46-315 20-46-326 Overload 28-11-056 28-11-055 Contactor 28-11-057 21-11-057 Fan/Limit Thermostat 28-60-021 28-60-021 Fan/ limit Stat Gasket 20-33-549 20-33-549 Burner Plate Gasket 31-27-121 31-29-046 Pressure Relief Gasket 31-27-121 20-46-354 Sight Glass 20-30-151 20-30-151 Sight Glass Holder 20-30-061 20-30-061 Sight Glass Gasket 31-28-084 31-28-084 Fuse 1ph N/A N/A Fuse 3ph 28-07-048 28-07-048 Nozzle Outlet Assy 31-30-159(4) 31-30-157(4) Motorised Fan 1ph N/A N/A Fan 28-09-003 28-09-004 Fan Pulley 28-65-096 28-65-105 Motor 28-10-015 28-10-120 Motor Pulley 28-65-063 28-65-072 09-16-110(2) 09-06-126(2) 29-99-448 29-99-450 N/A 30-10-145 Belt Burner Air Head 38 DESCRIPTION 770 DESCRIPTION 1020 Heat Exchanger Assy 20-47-405 Rear Panel 20-27-013 Stackbox Assy 20-47-425 Top Rear Heat Shield 20-27-011 Front Lower Inlet Panel 20-47-021 Bottom Rear Heat Shield 20-27-010 Front Top Panel 20-47-426 Heat Exchanger Assy 20-27-946 Back Top Panel 20-47-429 Gas Exit Duct Assy V 20-27-090 Heatshield Front Panel 20-47-430 Gas Exit Duct Assy H 20-27-092 Heatshield Back Panel 20-47-431 Outlet Assy (Nozzled) V 20-27-094 Flue Box Cover Assy 20-46-310 Outlet Assy (Nozzled) H 20-27-148 Rear Lower Inlet Panel 20-47-022 Outlet Assy (Ducted) 20-27-028 Side Lower Inlet Panel 20-47-039 Nozzle Outlet Assy (4) V 20-27-034 Overload 28-11-111 Contactor 28-11-057 Fan/Limit Thermostat 28-60-023 Fan/ limit Stat Gasket 20-33-549 Fan Drive Assy (Nozzled) 20-27-526 Burner Plate Gasket 31-29-046 Fan Drive Assy (Ducted) 20-27-527 Pressure Relief Gasket 20-46-354 Motor (Nozzled) 28-10-024 Sight Glass 20-30-151 Motor (Ducted) 28-10-025 Sight Glass Holder 20-30-061 Drive Pulley (Nozzled) 28-65-047 Sight Glass Gasket 31-28-084 Drive Pulley (Ducted) 28-65-053 Fuse Holder 28-07-050 Driven Pulley (Nozzled) 28-65-049 Fuse 3ph 28-07-048 Driven Pulley (Ducted) 28-65-054 Nozzle Outlet Assy 20-47-402 Taper lock Drive (Nozzled) 28-66-013 Tray Spigot Assy 20-47-403 Taper lock Drive (Ducted) 28-66-042 Fan 28-09-043 Taper lock Driven (Nozzled) 28-66-013 Fan Pulley 28-65-043 Taper lock Driven (Ducted) 28-66-019 Fan Taper lock 28-66-136 V Belt (3) 09-16-126 Motor 28-65-043 Burner c/w Gas Train 29-99-476 Motor Pulley 28-65-042 Air Head 30-10-146 Motor Taper lock 28-66-028 V Belt (3) 09-16-112 Burner c/w Gas Train 29-99-450 Air Head 30-10-145 39 10.1 Commissioning and hand over SECTION 2 BASIC USER INSTRUCTIONS 10.0 Introduction The following information is relevant to the Gas fired Cabinet Heater range manufactured by Benson Heating. These heaters are manufactured within a strictly controlled quality system to ISO 9001. Warning As part of the commissioning programme, the commissioning engineer must go through the following with the operator. (i) Lighting, shutdown, and operational information. (ii) Safety features, data plate, and labeling. (iii) The requirement for regular inspection especially if the heater is within a more demanding environment - and the need for regular servicing, carried out by competent and qualified engineers. All Benson Heating gas fired Cabinet Heaters are CE marked, having been found to satisfy the essential requirements of the following European Directives. Machinery Directive (89/392/EEC) Low Voltage Directive (73/23/EEC & 93/68/ EEC) Electromagnetic Compatibility Directive (89/336/EEC & 91/31/EEC) Product Liability Directive (65/374/EEC) Caution After approximately 100 hours of running, the tension on the fan belts must be checked to ensure that it is correct, and that the belts have not stretched. It is strongly advised that this is undertaken by the commissioning engineer, and not the operator Benson Heating support all new products being supplied to their customers with a comprehensive information pack, and it is the responsibility of the owner, user, or hirer, of such products supplied by Benson Heating to ensure that operators are provided with the operator manual, and that they are suitably instructed regarding the purpose of the manual and safety instructions. In addition to this, operators must also be suitably and adequately trained in the use of the product. Warning Servicing must be carried out on a regular basis, the maximum interval between services being one year. It is a requirement that only suitably qualified and competent persons are allowed to undertake the servicing. Contained within the text of this manual, the words 'Caution' and 'Warning' are used to highlight certain points. Caution is used when failure to follow or implement the instruction(s) can lead to a premature failure or damage being occasioned to the heater or its component parts. Warning is used when failure to heed or implement the instruction(s) can lead not only to component damage, but can also lead to a hazardous situation being created where there is a risk of personal injury or death 40 10.2 Servicing Benson Heating advise that the planned service schedule as detailed in section 5.1 of the Installation, Commissioning and Servicing Manual is adopted by the user. Further details are available from either Benson Heating or from the commissioning engineer. 10.3 Start up procedure CP4 OPTION (a) Ensure that the gas cocks are open, and that the mains electrical supply is turned on (b) Ensure that the CP4 has been correctly programmed (c) Ensure programme is displaying Heat On setting ANALOGUE OPTION (d) Ensure On Standby switch ON (e) Ensure heat vent switch is set for ‘heat’ (f) Check for the following burner sequence interval 10.6 Ventilation only CP4 OPTION (a) Select FAN /Enter to confirm ANALOGUE OPTION (b) Set heat/ventilate switch to 'ventilate'. operand 10.7 Lockout situations 1 2 3 4 <5s Combustion air damper actuated fan motor initiates purge cycle... <40s Pilot valve opens ignition transformer provides spark for Pilot ignition and flame detection <40s Pilot ignition and Burner ignition If either the burner or the fan and limit stat go to lockout, the lockout must be cleared manually before the ignition sequence can be re-initiated. <60s Burner ignition start cycle complete Caution Repeated or frequent lockouts must be investigated and their cause determined by a qualified and competent engineer. Note The time intervals within the ignition sequence may vary slightly between models. (f) The burner will continue to fire until heat is no longer demanded. 10.4 Stop procedure CP4 OPTION (a) Select standby , option 2 standby (b) The fan motor will continue to run until heat dissipation allows the fan and limit stat to shut down the fan. Stop procedure Analogue OPTION a) Set switch to standby' position. (b) The fan motor will continue to run until heat dissipation allows the fan and limit stat to shut down the fan. Caution Do not use the main electrical isolator to turn off the heater, to do so can cause damage to the heat exchanger and combustion chamber and thereby invalidate the warranty. 10.8 Contact information Further information is available from :- Benson Heating Ludlow Road Knighton Powys LD7 1LP Telephone 01547 528534 Facsimile 01547 520399 10.5 Shut down procedure (a) Follow steps 10.4 (a) and (b), when fan stops turn main electrical isolator off, and shut gas cocks 41 Benson Heating is a Division of Benson Climate Systems Ltd
advertisement
Key Features
- Gas fired
- Forced convection
- Ducted and free blowing applications
- Range of sizes from 29.3 kW to 381.0 kW
- Forced draught burner
- Removable control panel
- Remote operation
Frequently Answers and Questions
What is the warranty on the Benson ECA Gas Cabinet Heater?
The heater is supplied with a 2 year warranty, first year covering parts and labour, and second year covering parts only. In addition to this there is also a 10 year time related warranty on the combustion chamber/heat exchanger.
What are the minimum clearance requirements for installing the Benson ECA Gas Cabinet Heater?
The minimum space requirements for single and multiple heater applications are detailed in section 3.3 later within this manual.
What are the requirements for the flue system for the Benson ECA Gas Cabinet Heater?
It is essential that the products of combustion are flued to the outside of the building. Each heater must have its own separate flue, with a flue diameter of not less than is detailed in section 8 within this manual.