WhisperPower M-SQ 8, 10, 12, 16 Marine Diesel Generating Set Installation Manual

WhisperPower M-SQ 8, 10, 12, 16 Marine Diesel Generating Set Installation Manual
Add to My manuals

Below you will find brief information for Marine Diesel Generating Set M-SQ 8, Marine Diesel Generating Set M-SQ 10, Marine Diesel Generating Set M-SQ 12, Marine Diesel Generating Set M-SQ 16. This manual provides instructions on how to install the WhisperPower M-SQ series marine diesel generator, including information on location, ventilation, fuel supply, cooling, exhaust, and electrical connections. It also includes specifications for the various models and accessories.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

WhisperPower M-SQ 8, M-SQ 10, M-SQ 12, M-SQ 16 Installation Manual | Manualzz

INSTALLATION MANUAL

M-SQ8 / 10 / 12 / 16

- 1500 RPM -

Marine diesel generating set 230V / 50Hz

Digital Diesel Control

WHISPER POWER BV

Kelvinlaan 82

9207 JB Drachten

The Netherlands

Tel.: +31-512-571550

Fax.: +31-512-571599 www.whisperpower.eu

V1. September 2010

CONTENTS

CONTENTS:

1 INSTALLATION ........................................................................................................................................................ 3

1.1

General ....................................................................................................................................................... 3

1.2

Location ...................................................................................................................................................... 3

1.3

Instructions for optimal sound and vibration insulation ................................................................................... 3

1.4

Ventilation ................................................................................................................................................... 4

1.5

Connections ................................................................................................................................................ 4

1.5.1

Fuel supply .................................................................................................................................. 8

1.5.2

Cooling........................................................................................................................................ 9

1.5.3

Exhaust system ..........................................................................................................................13

1.5.4

Digital Diesel Control system (12 Volt) .........................................................................................16

1.5.5

AC power system (230 Volt) ........................................................................................................18

2 INSTALLATION SPECIFICATIONS .........................................................................................................................20

2.1

General ......................................................................................................................................................20

2.2

Commission table .......................................................................................................................................20

2.3

Installation specifications ............................................................................................................................21

2.4

Specification of the accessories ..................................................................................................................21

2.5

Installation materials ...................................................................................................................................22

3 DIAGRAMS & DRAWINGS ......................................................................................................................................30

3.1

DC wiring M-SQ8, 10 and 12 .......................................................................................................................30

3.2

DC wiring M-SQ16 ......................................................................................................................................32

3.3

Wiring diagram electronic governor (M-SQ10 only) ......................................................................................34

3.4

AC wiring diagram 230V / 50Hz ...................................................................................................................35

3.5

Remote control panel drawings ...................................................................................................................36

3.6

Dimensions M-SQ8 and 10 .........................................................................................................................37

3.7

Dimensions M-SQ12 ...................................................................................................................................38

3.8

Dimensions M-SQ16 ...................................................................................................................................39

2

September 2010 / M-SQ8/10/12/16 / EN

1 INSTALLATION

1.1 GENERAL

This installation manual is valid for the following models:

Part number

Description

41106005 M-SQ8 230V 1500rpm

41106006 M-SQ8 230V 1500rpm -ungrounded

41109005 M-SQ10 230V 1500rpm

41109006 M-SQ10 230V 1500rpm -ungrounded

41107005 M-SQ12 230V 1500rpm

41107006 M-SQ12 230V 1500rpm -ungrounded

41108005 M-SQ16 230V 1500rpm

41108006 M-SQ16 230V 1500rpm -ungrounded

For other models see our website: www.whisperpower.eu.

To ensure reliability and durability of the equipment, it is very important that the installation is carried out with the utmost care and attention. To avoid problems, such as temperature problems, noise levels, vibration, etc. the instructions set out in this manual must be followed and all installation work must be carried out professionally.

1.2 LOCATION

Since Whisper generating sets have extremely compact dimensions, they can be installed in tight locations. Please consider that even almost maintenance-free machinery must still remain accessible.

When selecting the location area in which to mount the generating set, make sure there is sufficient room to carry out any maintenance work. The unit must be easily accessible on the service side and on the distribution side to have access to the V-belt

Please also note that in spite of the automatic oil pressure sensor it is still essential that the oil level is checked regularly.

INSTALLATION

1.3 INSTRUCTIONS FOR OPTIMAL SOUND

AND VIBRATION INSULATION

Position the generating set as low as possible in the vessel. As the generating set is already secured to the base frame by means of flexible engine mountings, the frame must be mounted directly, without additional vibration dampers, to the vessel ’s main structure.

Whisper generating sets are standard equipped with a sound cover. The canopy has been designed to give effective sound insulation. For optimum sound and vibration dampening, the following factors should be considered.

1 Most important is the structure on which the generator is places to be stiff. Directly below the rubber mountings the structure should be supported vertically to the superstructure of the ship.

2 Avoid mounting the generating set in close proximity to thin walls or floors that may cause resonance.

3 Sound dampening is extremely poor if the generating set is mounted on a light weight flimsy surface such as plywood which will only amplify vibrations. If mounting on a thinner surface cannot be avoided, this should be at least be reinforced with stiffening struts or ribbing. If possible, holes should be drilled or cut through the surface to help reduce the resonance.

Covering the surrounding walls and floors with a heavy coating plus foam will certainly improve the situation.

4 Never connect the base of the generating set directly to bulkheads or tanks.

Figure 1: Mounting of the Whisper generating set. X = wrong, V = OK

EN / M-SQ8/10/12/16 / September 2010

3

INSTALLATION

1.4 VENTILATION

The generating set normally draws air from the engine room. Engine rooms with natural ventilation must have vent openings of adequate size and location to enable the generating set to operate without overheating. To allow an ample supply of air within the temperature limits of the generating set an opening of at least 100 cm2 is required.

A "sealed" engine compartment must have a good extraction ventilator to maintain reasonable engine room temperatures. High temperature of intake air reduces engine performance and increases engine coolant temperatures. Air temperatures above 40°C reduce the engine power by 2% for each 5°C of rise. To minimise these effects the engine room temperature must not be more than 15ºC above the outside ambient air temperature.

Apply a combination of ventilators, blowers and air intake ducting to meet the temperature limit. The air inlet ducts should run to the bottom of the engine room to clear fumes from the bilge and to circulate fresh air. Air outlets should be at the top of the engine room to remove the hottest air.

An engine room blower should be used as an extraction ventilator to remove air from the engine room.

In cases where it is impossible to meet the above mentioned temperature limit by using machine room ventilation, connections are to be made for an air inlet directly to the enclosure. With these connections the generating set can be directly connected to an air duct.

Air inlets should be louvered, where appropriate, to protect the engine room and to protect the generating set from water spray. As an extra precaution, the fitting of a cowl ventilator with a cover box located as high as possible, is recommended.

1.5 CONNECTIONS

The generating set comes supplied with all supply lines and output cable (i.e. electric cables, cooling water connections, exhaust, fuel lines etc.) already connected to the engine and generator. The supply lines are fed through the capsule

’s front base. The connections are marked as shown in figures 2 till 4

All electrical connections, cable types and sizes must comply with the appropriate national regulations. Supplied cables are rated for ambient temperatures up to 70°C. If the cables are required to meet higher temperature requirements, they must be run through conduits.

ATTENTION!

Before working (installation) on the system read the section safety instructions.

4

September 2010 / M-SQ8/10/12/16 / EN

Fig. 2a Connections M-SQ8 / 10

INSTALLATION

01 Bypass cooling water in

Ø19mm (3/4")

02 Bypass cooling water out

Ø19mm (3/4")

03 Expansion tank Ø8mm

04 Exhaust hose Ø51mm

10 Remote control

11 AC power output

05 Battery NEG (

–) 25mm2

06 Battery POS (+) 25mm2

07 Raw water inlet Ø19mm

08 Fuel in Ø8mm

09 Fuel out Ø8mm

Fig. 2b Connections M-SQ8 / 10

EN / M-SQ8/10/12/16 / September 2010

5

INSTALLATION

Fig. 3a Connections M-SQ12

01 Expansion tank Ø8mm

02 Bypass cooling water out

Ø19mm (3/4")

03 Bypass cooling water in

Ø19mm (3/4")

04 Exhaust hose Ø51mm

05 Remote control

06 AC power output

07 Battery NEG (

–) 25mm2

08 Battery POS (+) 25mm2

09 Raw water inlet Ø19mm

10 Fuel in Ø8mm

11 Fuel out Ø8mm

Fig. 3b Connections M-SQ12

6

September 2010 / M-SQ8/10/12/16 / EN

Fig. 4a Connections M-SQ16

Fig. 4b Connections M-SQ16

EN / M-SQ8/10/12/16 / September 2010

INSTALLATION

01 Battery NEG (

–) 35mm2

02 Fuel out Ø8mm

03 Fuel in Ø8mm

04 Battery POS (+) 35mm2

05 Raw water inlet Ø25.4mm

06 Expansion tank Ø8mm

07 Bypass cooling water out

Ø25.4mm

08 Bypass cooling water in

Ø25.4mm

09 Exhaust hose Ø51mm

10 Remote control

11 AC power output

7

INSTALLATION

1.5.1 Fuel supply

1 FUEL TANK

Fuel tanks should be made of appropriate material such as

(stainless) steel or plastic. Steel tanks should not be galvanised or painted inside. Condensation can occur in metal tanks when temperature changes. Therefore, water accumulates at the bottom of the tank and provisions should be made for the drainage of this water.

The tank will need a filling connection, a return connection and an air ventilation connection which will require protection against water entry.

Some official regulations do not allow connection points at the base of the fuel tank; in this instance connections are to be made at the top of the tank with internal tubing down to a few cm above the bottom of the tank.

Fig. 5 Fuel supply (fuel tank is above the generating set)

1 Fuel return

2 Fuel supply

3 Prefilter / Water separator (optional)

5 Fuel Tank

1

5

A

4

3

Fig. 6 Fuel supply (fuel tank is below the generating set)

1 Fuel return

2 Fuel supply

3 Prefilter / Water separator (optional)

8

2

4 Extra fuel lift pump (optional)

5 Fuel tank

September 2010 / M-SQ8/10/12/16 / EN

2 FUEL LIFT PUMP

The generating set itself is equipped with a fuel lift pump; therefore the tank can be installed at a lower level than the generating set. The maximum suction height is 1 m.

If the pump has to lift the fuel higher than one meter an external fuel lift pump must be installed. The control board is already prepared to connect an extra fuel pump.

3 FUEL PIPES

When the tank is above the generating set we recommend ending the return line on the top of the tank.

When the return is on the top - in case of a leakage the return line cannot overflow because of siphoning. One will only need a fuel cock in the fuel supply line. When the tank is below the generating set we recommend ending the return line on the bottom of the tank (A) below the inlet of the supply line.

Both supply and return fuel pipe lines should be appropriate material and 8 mm outer diameter tubing. The quality of the tubing of fuel pipes could be submitted to local regulations depending on the application of the vessel.

The fuel pipes can be plumbed to the flexible hoses which are on the generating set and have a connection to fit to 8 mm pipe. This fuel lines fulfils CE standards and are according to ISO 7840 A2.

It is important to avoid bends in the pipes, as they could trap air bubbles. The return pipe should never be connected to the suction pipe. Other consumers of diesel fuel, such as the propulsion engine and heaters, have to be connected to separate suction and return pipes

4 FUEL FILTERS

A fine fuel filter is installed which requires maintenance.

WhisperPower advises to install an extra fuel filter/ water fuel separator near the fuel tank.

Before starting your generating set for the first time follow the fuel system bleeding procedure in the users manual.

INSTALLATION

1.5.2 Cooling

Intercooling is based on a raw water pump, heat exchanger and water-injected exhaust. Cooling liquid in the internal cooling system is cooled in a heatexchanger by outboard water (raw water or seawater). After the raw water is warmed up in the heatexchanger it is dumped overboard by injecting it in the exhaust.

The generating set should have its own sea water (coolant water) inlet and should not be connected to any other engine systems. A properly installed cooling system is critical to keep engine temperatures within an acceptable range. Ensure that the installation complies to the following installation instructions.

1 THE INTERNAL COOLING SYSTEM

The internal cooling system should be filled with cooling liquid. (Refer to the users manual 2.5.12) When the engine becomes hot the liquid expands and the system is pressurised. After the pressure becomes too high the release valve in the filling cap on the manifold opens and the expanding liquid is pressed into the expansion tank that is in the delivery. Also the air in the system that is collected at the top of the manifold is released in this way.

When the liquid cools down there will be under-pressure.

Another valve opens and the liquid is sucked into the manifold again. This system works only when there is enough liquid initially. This has to be checked when commissioning the generator set. By filling up the expansion tank when necessary there will always be enough liquid in the system. The hose that is in the delivery has to be connected to the connection on the side of the filling cap. This hose is made of heat resistant plastic and is not sensitive for kinks.

The hose goes through a hole that has to be drilled in the lower part of the canopy close to the place where the tank is mounted.

MAX.

EN / M-SQ8/10/12/16 / September 2010

Fig.7: Expansion tank placement

9

INSTALLATION

The tank has to be placed close to the generator. When it is mounted above the top of the manifold the liquid in the tank will be drained when the cap on the manifold is taken off. When keel cooling or radiator cooling is applied the system will not be pressurised. A cap without release valve should be applied. Refer to the special manual for these applications.

2 RAW WATER SUPPLY

For raw water supply the following installation materials are required: -a skin fitting - a sea cock - a water strainer - hoses and clamps. In order to keep the suction resistance in the line at a minimum, the sea water intake system (i.e. sea cock, tru-hull fitting, inlet filter, etc.) must have the following inner diameter at least:

1

2

4

Max.

60"

150cm

Min.

24"

60cm

Min.

24"

60cm

5

3

Model

M-SQ8, 10, 12

M-SQ16

Minimum inner diameter

19 mm (3/4")

25.4 mm (1")

The suction hose should be kept as short as possible.

Raw water plumbing should avoid bends as much as possible.

Restriction of raw water flow, caused by kinked hoses, undersized pipes or connections, will reduce the engine cooling capability. This is the main cause for overheating of an engine.

After running the generating set for the first time, check the coolant flow rate using a stopwatch and by holding a pail of a known volume under the wet-exhaust outlet. The flow rate should be according to the data in the users manual.

6

2"

5cm

7

Fig. 8. Internal cooling system

1 Water level;

2 Water/exhaust separator;

3 Seacock;

4 Waterlock;

5 Air vent;

6 Water strainer;

7 Seacock.

10

September 2010 / M-SQ8/10/12/16 / EN

3 INSTALLATION OF THROUGH HULL FITTING

It is good practice for yachts to use a hull inlet fitting with an integrated strainer (water scoop). For propulsion engines in motorboats the water scoop is often mounted against the sailing direction to induce more water intake for cooling.

This should not be done in the case of a generating set! When sailing at higher speeds, water will be forced into the inlet and your generating set will overflow!

SAILING DIRECTION

INSTALLATION

5 SIPHON BREAKER (AIR VENT)

When the point of water injection is below the waterline, then -when the engine is stopped -there is a risk that the cooling water may enter the engine as a result of siphoning. To avoid this happening, the generating set is designed to accommodate a siphon breaker (air vent). In the standard delivery the connections are bypassed. See figure 10

FLOW DIRECTION

SAILING DIRECTION

FLOW DIRECTION

Fig. 9 Installing water intake

On motorboats and on sailing boats the water scoop for a generating set should be fitted with the opening faced backwards to prevent water being forced in during sailing.

4 WATER STRAINER

Use an appropriate water strainer with connections of the following dimensions:

Model Inner dimensions

M-SQ8, 10, 12

M-SQ16

19 mm (3/4")

25.4 mm (1")

Install the water strainer in a well accessible position,

(refer to fig. 8, ref. 6) 5 cm above the waterline.

EN / M-SQ8/10/12/16 / September 2010

Fig. 10: Bypassed siphon breaker connections

Hoses with the following inner diameter should be used:

Model Inner dimensions

M-SQ8, 10, 12

M-SQ16

19 mm (3/4")

25.4 mm (1")

If the generating set cannot be mounted such that the bottom of the generating set is placed above the waterline, an air vent must be installed. See figure 11

Extend the water hose of the by-pass 60 cm above waterline and install an air vent. Ideally, the air vent should be mounted above the yacht keel center line (i.e. to minimize the influence of swaying on the water intake).

Fast motorboats will lay deeper when sailing at large speed and can cause pressure on the waterinlet. This should be avoided to prevent fleeding the engine.

If the air vent is clogged the water hoses will not be vented when the generating set has stopped and water can be forced into the engine. This leads to immediate engine problems and eventually severe damage!

DAMAGE CAUSED BY THE INGRESS OF WATER IN

THE ENGINE IS NOT COVERED BY GUARANTEE

11

INSTALLATION

Siphon breaker

OPEN

Fig.11 siphon breaker connected

On the valve is a little hose to drain a little water that could be spilled from the valve. This hose should go down and may not end under water, because it should ventilate air into the valve to break the siphoning.

OPEN

Fig. 13 WhisperPower siphon breaker

Fig 12: Wrong siphon breaker hose routing

Check the air vent at regular intervals. Open, clean and lubricate the valve as required.

12

September 2010 / M-SQ8/10/12/16 / EN

1.5.3 Exhaust system

Water is injected in the exhaust system of the generating set. In this way the cooling water that has passed the heat exchanger is mixed with the exhaust gases. Temperature and volume of the gases are thereby reduced considerably, so that a rubber exhaust hose can be used and the level of noise is reduced as well.

1 STANDARD EXHAUST SYSTEM INSTALLATION

The generating set exhaust system must remain completely independent and separate from the exhaust system of any other engine on board. A water lock prevents the generating set from being flooded by cooling water and should be installed as close to the generating set as possible. The lock must be large enough to hold the entire water volume held in the hose from the top of the goose neck to the water lock. The water lock must be installed at the lowest point of the exhaust system (ref. to fig. 14, ref. 1). The exhaust hose must have an inner

INSTALLATION diameter of 51 mm no less, no more-. The exhaust system must be installed so that the back pressure inside the exhaust does not exceed 0.07 bar (1psi – 70 cm watercolumn) and total length from the genearot to the top of the goose neck or or water/separator does not exceed

3m (10 ft.). (Refer to paragraph 5.4.3 of the users manual).

The exhaust hose descends from the capsule to the water lock. Then the hose rises via the "goose neck" to the through-hull exhaust outlet, situated minimum 50 mm above the water line (ref. to fig. 14, ref. 5.) The "goose neck" must be vertical and situated preferable along the ship

’s keel center line. If the generating set is mounted less than 60 cm (24") above the waterline, a "goose neck" must be installed to prevent the engine from overflowing. It is recommended to install an extra muffler close to the through-hull fitting. .

A

4

HOSE ROUTE A- B MAX. 10ft (3m)

B

3

2

3

1

5

6

Fig. 14: Standard exhaust system

1 Exhaust water lock;

2 Exhaust outlet muffler;

3 Exhaust line Ø 51 mm (2

”);

4 Goose neck

5 Through-hull exhaust outlet Ø 51 mm (2 ”);

6 Water level.

EN / M-SQ8/10/12/16 / September 2010

13

INSTALLATION

2 SUPER SILENT" EXHAUST SYSTEM

In order to reduce the noise level of the generating set to a minimum, an option to reduce the exhaust noise further

(especially exhaust water splashing) is an exhaust/water separator. The exhaust/water separator allows the cooling water to be ejected through a line (A) separate from the exhaust fumes and also functions as a goose neck to prevent water from flooding the engine. If the exhaust/water separator is mounted more than 600 mm above the water level an additional goose neck is not required.

Fig.16: Water trap in exhaust system

Fig. 15 Super silent exhaust system

If the through-hull exhaust outlet has to be mounted far from the generating set (total length of the exhaust piping from generator to top of goose neck (water separator) is more than 3 m.), an exhaust/water separator must definitely be installed (see figure 18). The sea water from the separator must then run down along the shortest possible path to the through-hull outlet.

However watertraps should be avoided as the fumes still contains water and this should not accumulate in bents

(refer to fig 16 and 17). An additional outlet exhaust muffler close to the hull outlet will help further to reduce noise emission.

Fig.17: Water trap in exhaust system

14

September 2010 / M-SQ8/10/12/16 / EN

INSTALLATION

Fig.18.

If the generating set and the exhaust system have been installed correctly, neighbouring boats will not be disturbed by generating set noise. With the "super silent" exhaust system, generating set noises are almost inaudible. For optimal noise reduction, the sea water outlet from the exhaust/water separator (centre outlet on the unit) should be installed below the water level to eliminate noisy splashing of the effluent sea water.

The through-hull outlet for the exhaust fumes should not direct the fumes directly toward the water surface as this will cause excessive noise (ref. to fig. 19).

Do not direct the outlet directly toward the water surface.

Fig. 19. Outlet direction

EN / M-SQ8/10/12/16 / September 2010

15

INSTALLATION

1.5.4 Digital Diesel Control system (12 Volt)

1 DIGITAL DIESEL CONTROL SYSTEM

The electrical control system is standard in 12 Volt with negative earth. Non- earth return is available as an option for aluminium vessels to prevent corrosion.

All electrical wiring has been prepared on the generating set to the control panel prior to despatch from the factory.

The engine is controlled by a very advanced microprocessor based system: Digital Diesel Control.

The “black box” containing the microprocessor is located on top of the alternator.

A local control panel is on the generating set.

Remote control

A remote control panel also containing a microprocessor is in the delivery. A 15 m intermediate 8-pole communication cable is in the standard supply as well (refer to fig. 20). If necessary an optional longer (up to 30m / 100ft) intermediate cable can be connected if the standard length does not suit the required distance. When a longer distance than 30m / 100ft is required, consult the

WhisperPower service department for advice.

One can mount the control panel after drilling a hole in the dashboard using the plastic cover. Refer to the dimensional drawing in paragraph 3.5. The panel without the plastic cover fits the Mastervision modular panel system.

More remote control panels (slave panels) can be put in parallel by using the modular connectors on the back of the units. As a slave one can use the same panel offering all functions again. It is also possible to use an old or new type slave panel only to start and stop the generator.

Old type remote panels and system panels (like the

System Manager AC + Whisper or the CSCP4) can be connected by means of the green connector.

Pay attention to the colour codes as indicated in fig. 21 when fitting cable to the green connector. Some software versions in old system panels (supplied before May 2004) could conflict with the software in the DDC and an update of the software of the system panel could be necessary.

When this is the case consult to the WhisperPower service department for advice.

When using the factory settings, installation is very simple: just plug the remote cable into the remote and the generator is ready to use. Refer to fig. 21.

REMOTE CABLE

Fig. 20 Remote control cable

Whisper Remote Panel

Fig. 21 Remote box terminals

REMOTE CABLE

7

8

9

10

11

12

3

4

1

2

5

6

WIRING COLOURS

RED

GREEN

BROWN

YELLOW

PINK

PURPLE

BLUE

WHITE

RED/BLUE

GREY/PINK

GREY

BLACK

SENSE BAT. 2

WARNING RELAY

MAX. 150 mA

16

September 2010 / M-SQ8/10/12/16 / EN

Acoustic alarm or warning lamp

One can connect an external max.150 mA relay to generate an acoustic warning or applying a warning lamp etc. Be aware of polarity as some relays has a diode inside and should be connected plus to plus en minus to minus as indicated. Refer to fig. 21.

Connection for emergency stop / fire alarm switch

To connect an emergency stop button or to stop the generator automatically in case of a fire alarm, you can use the bypass connection between fastons J7 and J18 on the backside of the local control panel. See fi g. 22. To do so, remove this bypass connection and then replace it by an emergency switch or a potential free fire alarm switch with normally closed contacts

Remove bypass between J7 - J18 local control panel

(rear view)

Normal operation

Alarm / emergency

Fig. 22: Connection for emergency stop / fire alarm switch

Automatic start/stop

WhisperPower cannot be held responsible for damage caused by the unattended running generator using the auto-start/stop mode or interval mode

Using the auto-start/stop (interval) mode the generator can start unexpectedly. When working on the electrical system, the 3 Amp fuse must be removed from the control panel and the battery plus cable must be removed from the battery.

In the delivery are warning stickers to stick on several parts of the electric installation

(transfer switch, distribution box, etc.) to warn for automatic start)

EN / M-SQ8/10/12/16 / September 2010

INSTALLATION

The Digital Diesel Control system offers several options for automatic starting and stopping.

Access to this menu and other menus could be blocked.

For blocking and setting up this options refer to the

APPENDIX of the DDC users manual.

One of these options is to monitor a second battery (not being the starter battery) to start the generator automatically when the voltage of this battery drops below a certain setting.

Other names for this second battery are

“auxiliary battery”,

“service battery”, ”users battery” or “consumers battery”.

We will refer to this battery as

“the second battery”(BAT2).

In some menus the starter battery could be indicated as

“the first battery” (BAT1).

A sense wire to monitor the second battery should be connected (attention polarity!) to the connector on the back of the remote panel. Refer to fig. 21. The sense wires must be connected directly on the second battery before a main switch and be protected by a 3 Amps fuse.

(Monitoring the generator starter battery does not require an extra sense connection)

Settings

When one want to apply other settings than the factory settings refer to the DDC users manual, especially to the

APPENDIX.

2 STARTER BATTERY

For starting, the Whisper requires a 12V starter battery with the following capacity:

Model Minimum capacity

M-SQ8, 10, 12

M-SQ16

70Ah

120Ah

The generating set can be connected with the main engine battery or have its own battery.

We strongly recommend the use of a separate battery for the generating set and to keep the wiring system for the propulsion engine and the domestic DC supply system completely separate and individually connected to separate batteries.

230VAC

IVO 12/10

A

B

+

12V

-

Fig. 23 Starter battery

17

INSTALLATION

However, the negative of all the batteries on the vessel should be interconnected (when on earth) to avoid difference in the voltage level of the earth on different places causing trouble to electronic devices which might be in the system.

The above recommendation is not valid for ships having the starter battery of the propulsion engine or other auxiliary equipment positive grounded. When this is the case an expert should be consulted.

A battery switch may be used to interrupt the positive connection.

The starter battery is charged by the alternator on the engine. An additional battery charger will help to keep the battery in good condition when the generating set is not used. A battery charger is not included in the standard supply. A high efficiency battery charging unit can be ordered from WhisperPower which is able to charge both the ship ’s main battery and the starter battery. Also a small charger can be used to charge the starter battery only, such as the IVO SMART 12/10. A battery switch and a charger are included in the battery installation kits, art. no.

50230210 (70Ah) or 50230220 (160Ah)

3 OTHER RECOMMENDATIONS AND WARNINGS

The battery should be secured for seagoing conditions and the terminals should be insulated. For extra safety the battery can be enclosed in a wooden, plastic, fiberglas etc.

(non metal) box. Even when the earth return system is applied a negative battery cable should be used and the vessel should not to be used as a conductor.

The battery cables are supplied in a standard length of 1.5 m, if longer cables are required a larger cross sectional area should be considered to compensate for voltage reduction.

When two batteries are used in series to provide a 24 Volt supply system, never take off 12 Volt (starting) power from one of these batteries. This will result in severe damage to both batteries within a short time.

Disconnect the battery leads if electrical welding is to be carried out, otherwise damage will be caused to the diodes of the alternator.

As explosive hydrogen gases may be discharged during charging, the battery should be located in a well ventilated room.

Ensure that the supplied battery cable connectors are properly fitted and never remove during or shortly after charging as sparking can occur, which may ignite the hydrogen gasses.

1.5.5 AC power system (230 Volt)

Before working (installation) on the system read the sections on safety in the users manual.

Be sure that all electrical installations (including all safety systems) comply with all required regulations of the local authorities. All electrical safety/shutdown and circuit breaking systems have to be installed onboard as the generating set itself cannot be equipped with such equipment for every possible variation.

The vessel

’s power supply system should be suitable and safe for the AC voltage which is applied and the power that will be generated. Special attention has to be paid on dividing the system in branches which are fused individually.

It is absolutely essential that each and every circuit in the on-board electrical system is properly installed by a qualified electrician.

1 FUSE

An output fuse (from the generating set to the system) should be installed to protect the installed electrical system. The following maximum single phase output current applies:

Model

M-SQ8

M-SQ10

M-SQ12

M-SQ16

Maximum single phase output current

35A

43A

52A

70A

The fuses must be of the slow reacting type. For electrical motors connected to the system, a motor protection switch must be installed.

18

September 2010 / M-SQ8/10/12/16 / EN

2 GROUNDING

The AC alternator windings are not grounded.

The housing of the alternator and all other metal parts are grounded

To make a connection between

“neutral” and “ground” is necessary as part of a specific insulation failure protection system.

Small pleasure craft in Europe (length up to 24 meter) is submitted to The Recreational Craft Directive 94/25/EC.

The guidelines of this directive refer to (ISO 13297).

When the installation comply to this standard the

“neutral” and “ground” should be connected on the generating set by connecting the blue (neutral) wire with the terminal on which the yellow/green wire is connected.

A Ground Fault Circuit Interrupter (GFCI) or similar device must be applied

WARNING

In all situations the transfer switches between shore, inverter and generator should switch all connections, the phase line (L) as wel as neutral (N).

Be aware that insulation protection systems can be different for different applications and even within the ship there could be different standards for different spaces. We did refer to the Recreational Craft Directive that applies to pleasure craft up to 24 m of length. Sometimes one has to comply with other standards such as the rules of certification societies like Lloyds Register of Shipping or

Veritas, regulations for the protection of personal, building legislation, etc. It is of the greatest importance to have expert advice on this issue.

For safety reasons connect the main ships ground to negative point of the generating set start battery. When a ungrounded DC system or positive grounded DC system is applied the battery negative should not be connected to the main ships ground.

INSTALLATION

3 CABLE

For the power cable we recommend the use of 3 wire single phase or 5 wire tri-phase oil resistant cable with a sufficient cross sectional area. One wire for earth is included. For long cables it is recommended to apply cables with a larger cross section (refer to ISO 13297 annex A)

4 TRANSFER SWITCH

A power source selector switch much be installed between the generating set and the ship

’s electrical supply system.

This switch must ensure that all AC consumers can be switched off at once. This switch should also be installed to keep the generating set and shore (grid) power systems separate.

Transfer switches - to switch over from shore to ship or from generating set to inverter - should be well designed to switch over all wires including neutral (and not only phases or line) and there should be provisions with the aid of timers to prevent relays from clattering.

WhisperPower recommends the installation of a Mass

Systemswitch as the power source selector. This works automatically when the generating set is not running the input remains in the shore position and as soon as the generating set is running the Mass Systemswitch switches automatically after 10 seconds delay time over to the generating set position.

EN / M-SQ8/10/12/16 / September 2010

19

INSTALLATION SPECIFICATIONS

2 INSTALLATION SPECIFICATIONS

2.1 GENERAL

1 Mount the generating set directly, without additional vibration dampers, on a solid surface.

2 Connect the (sea) water inlet to the strainer.

3 Connect exhaust system.

4 Connect a siphon breaker or

‘air vent’ into the cooling circuit, if necessary.

5 Connect

‘fuel supply line’ to the water separator/ fuel filter.

6 Connect

‘fuel return line’ to the fuel tank.

7 Connect remote panel (just plug in).

8 Connect the AC cable from the AC box to the power source selector (or Mass Systemswitch).

9 Connect plus and minus from the 12V starter battery to the battery cables.

10 Install a WhisperPower battery charger. (optional)

2.2 COMMISSION TABLE

1 Check if a siphon breaker (air vent) is necessary and has been installed

2 Open the seawater inlet valve and check all water connections. Check if the strainer is installed on or just above the seawater level.

3 Check if the exhaust system is properly installed.

Check maximum length of exhaust hose, diameter of exhaust hose, position of the water lock, maximum lift.

Also check the minimum required height of 60 cm above sea level of the exhaust loop (goose neck).

4 Open the seawater outlet valve and check all water connections.

5 Check the AC cables and the grounding.

6 Check if an AC breaker is installed before or after the power source selector. When there is only a circuit breaker, use it to disconnect the generating set from the grid.

7 Check all DC connections, check if the battery switch/ circuit breaker is closed.

8 Open the fuel valve. Check if there are no air leaks in the fuel supply line, and check if the lift of the fuel is less than 1 meter. Check if there is no air in the water fuel separator.

9 Check if the air intake in the canopy is not blocked.

10 Check the oil level and colour of the oil. Check the coolant level

11 To bleed the fuel system:

·

M-SQ8, 10, and 12: push the

“Start” button on the local control (not on the remote panel) and hold at least 5 seconds and as long as necessary to bleed the system.

·

M-SQ16: use the manual pump by turning the cap loose and pumping as long as necessary to bleed the system. See chapter 4.2.2 of the user

’s manual.

12 Start the engine by pushing the start button

13 Check when the generating set is running, the delay of 5 to 10 seconds in the power source selector transfer.

14 Check voltage and frequency under

‘no load’ conditions.

15 Check voltage and frequency under

‘full load’ conditions.

16 Check if the battery charger of the generating set is working (max. 14.5 Volt).

17 Close the sound shield and check the noise level.

18 Stop the generating set and check the engine again for leakages of oil, fuel or water.

Installation checklist available on our website: www.whisperpower.eu.

Commissioning form available on our website: www.whisperpower.eu.

20

September 2010 / M-SQ8/10/12/16 / EN

INSTALLATION SPECIFICATIONS

2.3 INSTALLATION SPECIFICATIONS

TECHNICAL DATA

Model

Dimensions lxwxh.

Weight including sound shield

Max. operation angle

Remote panel 15 m cable

Battery capacity min.

Fuel consumption

Model fuel pump

Max lift fuel pump

Cooling

Cooling pump

Model cooling pump

Minimum water supply

Alternator

Voltage regulation

Output power at 50Hz power factor cos phi = 1

Battery charger

M-SQ8

90 x 58 x 63 cm

335 kg

25°

M-SQ10

90 x 58 x 63 cm

335 kg

25°

M-SQ12 M-SQ16

106 x 58 x 63 cm 116 x 58 x 70 cm

380 kg

25°

440kg

25°

Digital Diesel Control System

12V / 70Ah 12V / 70Ah

1,5 – 4 l/hr, load dependent

Electrical driven

12V

1m

Indirect

Electrical driven

12V

1m

Indirect capacitor (+ optional: AVR )

8 kW 10 kW

12V / 70Ah

Electrical driven

12V

1m

Indirect

12V / 120Ah

Mechanical driven

Manual priming

1m

Indirect

WhisperPower self priming raw water impeller pump, PTO driven

M12 M12 M12 M16

18-22 l/min 18-22 l/min 18-22 l/min synchronous brushless, maintenance free water cooled

20-25 l/min

12 kW 16 kW alternator including regulator (50 Amps)

2.4 SPECIFICATION OF THE ACCESSORIES

Model:

Water scoop

Inlet valve

Water strainer

Air vent

Inlet suction hose

Fuel filter/water separator

Fuel inlet and return

Exhaust hose

Water lock

Water/gas separator

Anti shock mounts

Battery charger (optional)

M-SQ8

M-SQ10

M-SQ12

3/4

” = 19 mm

3/4 ” in / 19 mm out

19 mm in / 19 mm out

19 mm

19 mm

30 micron

M-SQ16

1

” = 25.4 mm

1 ” in / 25.4 mm out

25.4 mm in / 25.4 mm out

25.4 mm

25.4 mm

30 micron

8 mm

Ø 51 mm inner

Ø 51 mm

Ø 51 – 40 – 51 mm

8 mm

Ø 51 mm inner

Ø 51 mm

Ø 51 – 40 – 51 mm

Included Included

IVO SMART 12/10; 12V / 10 Amps, 230V/50Hz

EN / M-SQ8/10/12/16 / September 2010

21

INSTALLATION SPECIFICATIONS

2.5 INSTALLATION MATERIALS

2

3

4

5

WATER INLET KIT 3/4 ” (20 mm) for M-SQ8, 10 and 12 no

1 qty

1 article no

50230052 description

Intake strainer

1

1

4

3

50230042

50221004

50221502

50220056

Lever operated ball valve FF

Male hose connection

Hose clamps

Outboard cooling water hose

6

7

2

1

8

TOTAL

1

50221007

50230060

50230067

50230211

Male hose connection

Nickel plated brass intake strainer

Mounting bracket waterstrainer

WATER INLET KIT 20 mm

WATER INLET KIT 1 ” (25 mm) for M-SQ16 no

4

5

11

12

13

14

15

4

5

6

7 no

1

2

3 qty article no

1

1

1

4

3

2

1

50230053

50230043

50221010

50221503

50220050

50221008

50230061 description

Intake strainer

Lever operated ball valve FF

Male hose connection

Hose clamps

Outboard cooling water hose

Male hose connection

Nickel plated brass intake strainer

TOTAL 50230221 WATER INLET KIT 25 mm

AIR VENT KIT 3/4 ” (20 mm) for M-SQ8, 10 and 12 qty article no

7 50221502

3

2

1

1

1

1

50220056

50221031

50221042

50230001

50221001

50221521 description

Hose clamps

Outboard cooling water hose

Bend male type with hose connection

TEE fittings

Syphon breaker valve

Male hose connection

Hose clamps

16

TOTAL

1,5 50220055

50230212

AIR VENT KIT 1 ” (25 mm) for M-SQ16

Outboard cooling water hose

AIR VENT KIT 20 mm no

4

5

11 qty article no

7

3

2

50221503

50220050

50221083 description

Hose clamps

Outboard cooling water hose

Bend male type with hose connection

12

12

13

11

1

1

1

2

50221043

50221102

50230001

50221008

14

15

1

1

50221001

50221521

16

TOTAL

1,5 50220055

50230222

TEE fittings

Straight reducer

Syphon breaker valve

Male hose connection

Male hose connection

Hose clamps

Outboard cooling water hose

SYPHON BREAKER KIT 25 mm

22

September 2010 / M-SQ8/10/12/16 / EN dimensions

3/4

3/4

3/4x20

19-29 mm

20x28 mm

1/2x20

1/2 dimensions

1

1 ”

1 ”x25

26-38 mm

25x33 mm

3/4x25

3/4 dimensions

19-29 mm

20x28 mm

1/2x20

1/2

1/2

3/8x13

12-20 mm

12x18.2 mm dimensions

26 - 38 mm

25 x 33 mm

3/4

3/4

3/4 x 1/2

1/2

3/4 x 25

3/8x13

12-20 mm

12x18.2 mm

INSTALLATION SPECIFICATIONS

Fig. 24: Installation materials water inlet and air vent

* Hose drain should go downwards. Water must flow out freely. Refer to installation manual for proper installation air-vent kit.

Faulty installation can cause serious problems

EN / M-SQ8/10/12/16 / September 2010

23

INSTALLATION SPECIFICATIONS

EXHAUST KIT 51 mm no qty article no

22

23

5

3

50221541

50220035

24

25

1

1

26

TOTAL

1

50230072

50230034

50221024

50230213 description

Hose clamps

Marine exhaust hose

Waterlock

Brass through hull fitting

Female hose connector

EXHAUST KIT 51 mm

OPTIONAL INSTALLATION MATERIALS no qty article no description

21A

22

1

2

50230077

50221541

WATER SEPARATOR KIT 51 mm

Elbow 90° adapter exhaust hose

Hose clamps HD no

21

22

23

40

31

32

33

34

35

36

37

38

39

TOTAL

8

8

1

4

4

4 qty article no

2 50221506

2 50221541

2.5 50220035

1.5 50220033

1 50221015

1

1

50230044

50230033

50230081

50201121

50211152

50211465

50211405

50211445

50230214 description

Hose clamps

Hose clamps HD

Marine exhaust hose

Marine exhaust hose

Male hose connection

Lever operated ball valve FF

Brass through hull fitting

Water exhaust fumes separator

Vibration mounting

Bolt

Nut

Washer

Lock washer

WATER SEPARATOR KIT 51 mm dimensions

55-62 mm

51 mm inner

51 mm

1 ½ x 70

1 ½ x 5 dimensions

51 mm

55-62 mm dimensions

44-56 mm

55-62 mm

51 mm inw

40 mm inw

1 1/4 x 40

1 1/4

1/1/4x70

51-40-51

25x30 mm M8

M8x16

M8

M8

M8

24

September 2010 / M-SQ8/10/12/16 / EN

INSTALLATION SPECIFICATIONS

Fig. 25: Installation materials exhaust M-SQ8, 10 and 12.

EN / M-SQ8/10/12/16 / September 2010

25

INSTALLATION SPECIFICATIONS

WHISPER 16ULTRA

M-SQ16

Fig. 26: Installation materials exhaust M-SQ16.

26

September 2010 / M-SQ8/10/12/16 / EN

FUEL KIT no qty article no

41

42

2

1

50221203

50230090

43

44

45

46

2

2

2

2

50221618

50221644

50221615

50221616 description

Straight coupling

Fuel strainer/water separator

Parallel male stud coupling

Reducing male nipple

Hose connection

Nut coupling

47

48

1

4

49

TOTAL

2

50221252

50221522

50221632

50230205

Nipple hose pipe

Hose clamps

Gasket ring

FUEL KIT

OPTIONAL INSTALLATION MATERIALS no qty article no description

50

51

1

1

50222020

50220063 copper fuel pipe fuel hose

BATTERY INSTALLATION KIT 70 Ah for M-SQ8, 10 and 12 no

51

52

53

54

55

56

57 qty article no

1

1

1

1

1

1

1

62000700

43011000

68060100

68060200

68456902

68456914

79009005 description

WhisperPower AGM Battery 12V/70Ah battery charger IVO SMART 12/10 battery terminal + battery terminal

– isolation cap isolation cap battery switch

58

TOTAL

4 6503002508

50230210 cable connectors

BATTERY INSTALLATION KIT 70 Ah

BATTERY INSTALLATION KIT 160 Ah for M-SQ16 no

51 qty article no

1 62001600 description

WhisperPower AGM Battery 12V/160Ah

52

53

54

55

56

57

1

1

58

TOTAL

4

1

1

1

1

43011000

68060100

68060200

68456902

68456914

79009005

6503003508

50230220 battery charger IVO SMART 12/10 battery terminal + battery terminal – isolation cap isolation cap battery switch cable connectors

BATTERY INSTALLATION KIT 160 Ah

INSTALLATION SPECIFICATIONS dimensions

8 mm

M14x1.5 mm

M14 - 8 mm

M14-M16 60 gr.

8 mm

M16x1.5 mm

8 mm

10-16 mm

14x20x1.5 mm dimensions

6x8 mm

8x16 mm dimensions

70Ah

M8

M8

250 Amp

M8x25 dimensions

160Ah

M8

M8

250 Amp

M8x35

EN / M-SQ8/10/12/16 / September 2010

27

INSTALLATION SPECIFICATIONS

Fig. 27: Installation materials battery and fuel M-SQ8, 10 and 12

Included are all fittings to fit copper pipes 8 mm outer diameter or rubber fuel hoses 8 mm inner diameter, or both.

28

September 2010 / M-SQ8/10/12/16 / EN

WHISPER 16ULTRA

M-SQ16

INSTALLATION SPECIFICATIONS

Fig. 28: Installation materials battery and fuel M-SQ16

Included are all fittings to fit copper pipes 8 mm outer diameter or rubber fuel hoses 8 mm inner diameter, or both.

EN / M-SQ8/10/12/16 / September 2010

29

DIAGRAMS & DRAWINGS

3 DIAGRAMS & DRAWINGS

3.1 DC WIRING M-SQ8, 10 AND 12

Fig. 29: DC wiring diagram M-SQ8, 10 and 12

30

September 2010 / M-SQ8/10/12/16 / EN

Wiring colours M-SQ8, 10 and 12 battery > starter motor starter motor > DDC starter motor > LCP battery > ground ground > LCP ground (GND)

DDC > glow plugs

DDC > starter solenoid

LCP > fuel lift pump +

LCP > fuel lift pump -

DDC > LCD

DDC > oil pressure switch

LCP > oil pressure switch

DDC > water temperature switch

LCP >water temperature switch

DDC > exhaust temperature switch

LCP > exhaust temperature switch

DDC > fuel solenoid (hold)

DDC > fuel solenoid (pull)

DDC > fuel solenoid (com.)

B+ terminal alternator > starter motor

DDC >R terminal alternator

DDC > L terminal alternator

DDC > current measuring transformer

DDC >current measuring transformer

DDC > LCP

DDC > LCP

DDC > LCP

DDC > generator AC output

DDC > generator AC output

DIAGRAMS & DRAWINGS

12

14

16

33

18

19

11

11

33

9

20

17

21

7

7

8

8

15

5

6

6

2

3

4

5

Cable code number

1

13 blue blue/black blue/green blue/rose green pink black red wit orange black red black red red/green brown blue colour red red red black black brown yellow brown black grey purple purple/black

1 mm2

1 mm2

1 mm2

1 mm2

1,5 mm2

1,5 mm2

1,5 mm2

6 mm2

1,5 mm2

1,5 mm2

1 mm2

1 mm2

1,5 mm2

1,5 mm2

1,5 mm2

1 mm2

1 mm2 cross section

25 mm2

6 mm2

2,5 mm2

25 mm2

4 mm2

4 mm2

2,5 mm2

1,5 mm2

1,5 mm2

1,5 mm2

1 mm2

1 mm2

EN / M-SQ8/10/12/16 / September 2010

31

DIAGRAMS & DRAWINGS

3.2 DC WIRING M-SQ16

Fig. 30: DC wiring diagram M-SQ16

32

September 2010 / M-SQ8/10/12/16 / EN

Wiring colours M-SQ16 battery > starter motor starter motor > DDC starter motor > LCP battery > ground ground > LCP ground (GND)

DDC > glow plugs

DDC > starter solenoid

DDC > LCD

DDC > oil pressure switch

LCP > oil pressure switch

DDC > water temperature switch

LCP >water temperature switch

DDC > exhaust temperature switch

LCP > exhaust temperature switch

DDC > fuel solenoid (hold)

DDC > fuel solenoid (pull)

DDC > fuel solenoid (com.)

B+ terminal alternator > starter motor

DDC >R terminal alternator

DDC > L terminal alternator

DDC > current measuring transformer

DDC >current measuring transformer

DDC > LCP

DDC > LCP

DDC > LCP

DDC > generator AC output

DDC > generator AC output

DDC=Digital Diesel Control Unit

11

11

12

14

16

33

33

17

21

18

19

8

8

9

20

6

6

7

7

2

3

4

5

Cable code number

1

13

LCP=Local Control Panel blue/green blue/rose green pink black red wit orange black red black red red/green brown blue colour red red red black black brown yellow grey purple purple/black blue blue/black

DIAGRAMS & DRAWINGS

1 mm2

1 mm2

1,5 mm2

2,5 mm2

2,5 mm2

6 mm2

1,5 mm2

1,5 mm2

1 mm2

1 mm2

1,5 mm2

1,5 mm2

1,5 mm2

1 mm2

1 mm2 cross section

35 mm2

6 mm2

2,5 mm2

35 mm2

4 mm2

4 mm2

2,5 mm2

1,5 mm2

1 mm2

1 mm2

1 mm2

1 mm2

EN / M-SQ8/10/12/16 / September 2010

33

DIAGRAMS & DRAWINGS

3.3 WIRING DIAGRAM ELECTRONIC GOVERNOR (M-SQ10 ONLY)

Fig. 31: Electronic governer.

The M-SQ10 is equipped with an electronic governor in addition to the mechanical governor that is on other

Whisper models. A governor keeps the speed

(RPM=Rotations Per Minute) of the engine at a fixed value. The RPM of the engine correlates with the frequency of the electrical output (1500 RPM =50 Hz) of the alternator.

Under full load the RPM of the other Whisper models that have only a mechanical governor can drop 75 RPM (=2.5

Hz) at full load and will go further down or collapse when further loaded. However the engines with the electronic governor will keep the RPM and frequency at the set value. As the voltage is related to the frequency, the voltage will be more stable as well.

The RPM represents power and the alternator performs better as well on a higher speed. Whisper models with an electronic governor will bring more power.

So the electronic governor offers three advantages: a more stable frequency and voltage and more power.

The electronic governor system contains two parts:

1 The actuator controls the engine speed. This actuator replaces the standard hold solenoid that is on all other mechanical controlled Whisper engines. The actuator controls the RPM directly on the fuel rack inside the fuel pump without levers and other mechanical transmissions.

2 A microprocessor keeps the speed at the set value by controlling the actuator. The microprocessor is programmed at the WhisperPower factory and many parameters are set to perform well. It should not be necessary to make adjustments. When adjustments are necessary this can only be done with the help of an interface to a computer and special software to get access to the microprocessor.

The electronic governor does not need a pickup device in the flywheel housing that counts the passing tooth of the flywheel and determines the exact RPM of the engine, because the processor uses the 50 Hz of the AC output voltage as a reference.

Note: When this manual was not supplied with the generator and there is a pick up on your generator than you have another model than referred to in this manual.

Refer to our website for the correct manual.

34

September 2010 / M-SQ8/10/12/16 / EN

3.4 AC WIRING DIAGRAM 230V / 50HZ

STATOR

GREEN (1)

EXCITATION

WINDING

GREEN (2)

ROTOR

CAPACITOR

DIAGRAMS & DRAWINGS

RED (3)

MAIN WINDING

EARTH AND NEUTRAL NOT CONNECTED

230V / 50Hz

RED (11) BLACK (11)

DDC/ct-1

BROWN L1

BLACK (4)

RED (3) YELLOW/GREEN

PE

BLUE N

MAIN WINDING

DDC/AC-1

BLACK (4)

YELLOW/GREEN

Fig. 32: AC wiring diagram

EARTH AND NEUTRAL CONNECTED

EN / M-SQ8/10/12/16 / September 2010

35

DIAGRAMS & DRAWINGS

3.5 REMOTE CONTROL PANEL DRAWINGS

Fig. 33: Whisper remote panel

The remote panel comes in a carton that can be used as a template to drill the mounting hole.

36

September 2010 / M-SQ8/10/12/16 / EN

3.6 DIMENSIONS M-SQ8 AND 10

DIAGRAMS & DRAWINGS

Fig. 34: Outer dimensions (mm) M-SQ8 and 10

CONNECTIONS M-SQ8 / 10:

• exhaust:

• fuel hose:

• sea water in:

• air vent connection:

• battery +:

• battery -:

51 mm

8 mm

19 mm

19 mm

25 mm2

25 mm2

POWERCABLES ISO 13297 annex A

• 3x6 mm2 (not included)

REMOTE CONTROL:

• 15 meter 8 wire communication cable (included)

BOX DIMENSIONS M-SQ8 / 10

• length

• width

• height

• weight

900 mm

575 mm

635 mm

335 kg

EN / M-SQ8/10/12/16 / September 2010

37

DIAGRAMS & DRAWINGS

3.7 DIMENSIONS M-SQ12

Fig. 35: Outer dimensions (mm) M-SQ12

CONNECTIONS M-SQ12:

• exhaust:

• fuel hose:

• sea water in:

• air vent connection:

• battery +:

• battery -:

51 mm

8 mm

POWERCABLES ISO 13297 annex A

• 3x10 mm2 (not included)

REMOTE CONTROL:

• 15 meter 8 wire communication cable (included)

19 mm

19 mm

25 mm2

25 mm2

BOX DIMENSIONS M-SQ12

• length

• width

• height

• weight

1060 mm

575 mm

635 mm

380 kg

38

September 2010 / M-SQ8/10/12/16 / EN

3.8 DIMENSIONS M-SQ16

DIAGRAMS & DRAWINGS

Fig. 36: Outer dimensions (mm) M-SQ16

CONNECTIONS M-SQ16:

• exhaust:

• fuel hose:

• sea water in:

• air vent connection:

• battery +:

• battery -:

POWERCABLES ISO 13297 annex A

• 3x16 mm2 (not included)

REMOTE CONTROL:

• 15 meter 8 wire communication cable (included)

51 mm

8 mm

25.4 mm

25.4 mm

35 mm2

35 mm2

BOX DIMENSIONS M-SQ16

• length

• width

• height

• weight

1160 mm

675 mm

700 mm

440 kg

EN / M-SQ8/10/12/16 / September 2010

39

Kelvinlaan 82, 9207 JB Drachten, The Netherlands

Tel : + 31-512-571550 / Fax : + 31-512-571599 www.whisperpower.eu / [email protected]

advertisement

Key Features

  • Compact dimensions
  • Digital Diesel Control system
  • Remote control panel
  • Automatic start/stop
  • Super silent exhaust system
  • Seawater cooled
  • 1500 RPM
  • 230V / 50Hz
  • 12 Volt DC System

Frequently Answers and Questions

What are the minimum battery capacities required for the different models?
The minimum battery capacities are: M-SQ8, 10, 12: 70Ah, M-SQ16: 120Ah.
What is the maximum lift height for the fuel pump?
The maximum lift height for the fuel pump is 1 meter.
What is the minimum required height of the exhaust loop (goose neck) above sea level?
The minimum required height of the exhaust loop (goose neck) above sea level is 60 cm.
What is the maximum length of the exhaust hose?
The maximum length of the exhaust hose is 3 meters (10 feet).
How do I bleed the fuel system for the M-SQ8, 10, and 12 models?
To bleed the fuel system for the M-SQ8, 10, and 12 models, push the "Start" button on the local control (not on the remote panel) and hold for at least 5 seconds, or as long as necessary to bleed the system.

Related manuals