Carrier XPower Full DC Inverter VRF Technical Manual

Carrier XPower Full DC Inverter VRF Technical Manual

The Carrier XPower Full DC Inverter is a variable refrigerant flow (VRF) system that offers a wide range of applications for residential, light commercial, and commercial buildings. It features modular outdoor units that can be combined to meet specific capacity requirements, with a maximum of 72HP achievable. The system also has a variety of indoor units, including ducted, cassette, high wall, and floor-mounted options. The units are designed for high efficiency and quiet operation, with a wide stable operation range. The XPower Full DC Inverter system has a variety of control options, including wireless remote controls and central management software.

advertisement

Assistant Bot

Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.

Carrier XPower Full DC Inverter Technical Manual | Manualzz

improve buildings

TM

VRF FULL DC INVERTER

Miraco

MISR REFRIGERATION & AIR CONDITIONING MFG. CO.

Technical Manual

VRF Outdoor Units the environmentally sound refrigerant

Smart Energy Saving Green Air Conditioning Solutions

For Large Scale Residential, Light Commercial & Commercial Applications

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Key Features

2

( Key Features )

14

( 1 )

Variety of

Applications

Residential

Light Commercial

Commercial

( 4 )

Wide

VRF Indoor Units

Lineup

1.8 kW to 56 kW

( 7 )

High

Efficiency

( 2 )

Advanced

Design

Modular outdoor units

Variety of indoor units

Type & Ranges

( 3 )

Wide

VRF Outdoor Units

Lineup

8 HP to 72 HP

( 8 )

Super

Quiet

( 5 )

Wide

Selection

Selection software provides flexibility of model selection

( 9 )

Enhanced

Comfort

( 6 )

Wide

Application Range

Wide Operation Range

Long Piping Length

High Height Difference

( 10 )

High

Reliability

( 11 )

High

Durability

( 12 )

Variety of

Controls

Individual Controls

Wireless Control

Wired Control

Central Controls

( 13 )

Variety of

Accessories

( 14 )

Easy

Installation

Service &

Maintenance

Variety of Applications

Carrier VRF Full DC Inverter Systems are Variable Refrigerant Flow R410A Heat Pump Systems.

Carrier VRF Full DC Inverter Systems are smart energy saving green - air conditioning

solutions for large scale residential, light commercial and commercial applications for

a wide range of environmental conditions.

Large Scale Residential & Light Commercial Applications

Luxury Apartments Villas

Restaurants

Large Scale Commercial Applications

Offices

Malls

Multiplexes

Hotels

Educational Institutions 3

4

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Advanced Design

Modular Outdoor Units - Design Layout

Top discharge

2 Pipe system

Modular design

6 basic modules 8HP - 10HP - 12HP - 14HP - 16HP - 18HP, which can be freely combined

in the installation site for wide range and large capacity for big sizes buildings.

2HP increment of capacity range, which meets customers needs accurately.

Outdoor unit includes all DC Inverter Compressor (s) + all DC fan motor (s)

Outdoor Unit

( Module )

8 HP

10 HP

12 HP

14 HP

16 HP

18 HP

DC Inverter Compressor (1)

1

1

1

1

1

1

Maximum capacity is 72 HP

Compressor Quantity

DC Inverter Compressor (2)

1

1

1

1

Maximum quantity of outdoor units is 4

Maximum quantity of indoor units is 64

Total capacity % range of indoor units is 50% ~ 130%

Outdoor DC Fan

Motor Quantity

1

1

2

2

2

2

56-72 HP

8-18 HP

20-36 HP

38-54 HP

Modular Outdoor Units - Model Identification

8 – 10 HP 12 –14 –16 HP 18 HP

Digital No.

Code

1, 2

Product Type

38 : Outdoor Unit

3, 4

Product Classification

VF: VRF FULL DC Inverter

5, 6, 7

Cooling Capacity

008 : 25.2 KW

010 : 28.0 KW

012 : 33.5 KW

014 : 40.0 KW

016 : 45.0 KW

018 : 50.0 KW

8

Application

H : Heat pump

C : Cool Only

9

Refrigerant

1 : R410A

10

Market

1 : Egypt & Export

11

Electrical Characteristics

9 : 380-415V-3PH-50HZ

12

Packing

0 : Standard packing

1 : Crate packing

13

Model Type

1 : Full DC Inverter

14

Model revision code

1 : Modular Type Tropical

1 2 3 4 5 6 7 8 9 10 11 12 13 14

3 8 V F 0 0 8 H 1 1 9 0 1 1

5

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Advanced Design

Modular Outdoor Units - Technical Specifications

6

Outdoor Unit Model

Power Supply

Cooling (1)

Cooling (2)

Heating (3)

Connected Indoor Units

DC Inverter

Scroll Compressor

Outdoor Fan Motor

Capacity

Input

EER

Capacity

Input

EER

Capacity

Input

COP

Total Capacity

Max Quantity

Quantity

V / Ph / Hz

W

Btu/h kW kW / kW

W

Btu/h kW kW / kW

W

W

W/W

%

8 – 10 HP 12 HP

38VF008H119011 38VF010H119011 38VF012H119011

380-415 / 3 / 50 380-415 / 3 / 50 380-415 / 3 / 50

25200 28000 33500

86000 95500 114300

5.875

4.29

23700

7.053

3.97

26300

8.793

3.81

30700

81000

6.37

3.72

27000

6150

4.39

50% ~ 130%

13

1

90000

7.64

3.45

31500

7554

4.17

50% ~ 130%

16

1

104000

11.25

2.73

37500

8993

4.17

50% ~ 130%

20

1 + 1

Model

Capacity

Input

Power supply

Operating frequency

Crankcase heater

Refrigerant oil

Quantity

Type

Model

Insulation class

Safe class

Input

Output

Rated current

Speed

W

W

31590

10340

31590

10340

31590 + 11800

10340 + 3665

V-Ph-Hz 380-415V~3Ph, 50Hz 380-415V~3Ph, 50Hz 380-415V~3Ph, 50Hz

Hz 40~200 40~200 40~200

W 27.6×2 27.6×2 27.6×2×2 ml

W

W

A r/min

FVC68D / 500

1

DC inverter

WZDK750-38G-4

E

IPX4

534

454

4.4

850

FVC68D / 500

1

DC inverter

WZDK750-38G-4

E

IPX4

534

454

4.4

850

FVC68D / 500 +

FVC68D / 500

2

DC inverter

WZDK450-38G

E

IPX4

450 × 2

360 × 2

3.5 × 2

1100 × 2

Modular Outdoor Units - Technical Specifications

Outdoor Unit Model

Power Supply

Cooling (1)

Cooling (2)

Heating (3)

Connected Indoor Units

DC Inverter

Scroll Compressor

Outdoor Fan Motor

14 –16 HP 18 HP

38VF014H119011 38VF016H119011 38VF018H119011

Capacity

Input

EER

Capacity

Input

EER

Capacity

Input

COP

Total Capacity

Max Quantity

Quantity

Model

Capacity

Input

Power supply

Operating frequency

Crankcase heater

Refrigerant oil

Quantity

Type

Model

Insulation class

Safe class

Input

Output

Rated current

Speed

V / Ph / Hz

W

Btu/h kW kW / kW

W

Btu/h kW kW / kW

W

W

W/W

%

380-415 / 3 / 50 380-415 / 3 / 50 380-415 / 3 / 50

40000 45000 50000

136500 153500 170500

11299

3.54

37600

12857

3.5

41240

14493

3.45

45830

129000

12240

3.07

45000

11194

4.02

50% ~ 130%

23

1+1

141000

16460

2.51

50000

12788

3.91

50% ~ 130%

26

1+1

156371

18550

2.47

56000

14396

3.89

50% ~ 130%

29

2

W

W

E655DHD-65D2YG+

E405DHD-36D2YG

31590+11800

10340+3665

E655DHD-65D2YG+

E405DHD-36D2YG E655DHD-65D2YG

31590+11800

10340+3665

31590+31590

10340+10340

V-Ph-Hz 380-415V~3Ph, 50Hz 380-415V~3Ph, 50Hz 380-415V~3Ph, 50Hz

Hz 40~200/48~230 40~200/48~230 40~200

W 27.6×2 27.6×2 27.6×2 ml

W

W

A r/min

FVC68D / 500 +

FVC68D / 500

2

DC motor

WZDK450-38G

E

IPX4

450×2

360×2

3.5×2

1100×2

FVC68D / 500 +

FVC68D / 500

2

DC motor

WZDK450-38G

E

IPX4

450×2

360×2

3.5×2

1100×2

FVC68D / 500 +

FVC68D / 500

2

DC motor

WZDK750-38G-4

E

IPX4

534x2

454x2

3.6×2

850×2 7

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Advanced Design

Modular Outdoor Units - Technical Specifications

8

Outdoor Unit Model

8 – 10 HP 12 HP

38VF008H119011 38VF010H119011 38VF012H119011

Outdoor Fan

Outdoor Coil

Outdoor Air Flow

External Static Pressure

Dimension ( D × H )

Vane Quantities

Number of rows

Tube pitch(a) × row pitch(b)

Tube outside diameter

Coil length×height

Number of circuits

Outdoor Sound Pressure Level (4)

Outdoor Unit

Quantity

Type

Material

Fin spacing

Fin type

Tube type

Packing (WxHxD)

Net / Gross weight

Charged refrigerant type and volume

Refrigerant control

Refrigerant Piping

Lines (5)

Dimension (WxHxD)

Excessive operating pressure

Liquid side

Gas side

Oil balance pipe mm mm mm mm mm m 3 /h

Pa dB(A) mm mm kg

Kg

MPa mm mm mm

1

Axial

Plastic

700 x 202

3

2

22 × 19

1.6

1985×1232

1

Axial

Plastic

700 x 202

3

2

22 × 19

1.6

Hydrophilic aluminum

ะค7.94

Inner-grooved

1985×1232

2

Axial

Plastic

560 x 189

3 + 4

2

22 × 19

1.6

2270×1232

22

11242

22

11242

0 ~ 20 ( Default )

20 ~ 40 ( Optional )

22

15620

57 57 59

960×1615×765 960×1615×765 1250×1615×765

1025×1790×830 1025×1790×830 1305×1790×820

212/220 212/220 288/300

R410A / 10 R410A / 10

Electronic Expansion Valves

R410A / 12

4.4/2.6

Ø 12.7

4.4/2.6

Ø 12.7

4.4/2.6

Ø 15.9

Ø 25.4

Ø 6.4

Ø 25.4

Ø 6.4

Ø 31.8

Ø 6.4

Notes:

1. Cooling conditions: indoor temp.: 27°C DB / 19°C WB; outdoor temp.: 35°C DB / 24°C WB

2. Cooling conditions: indoor temp.: 29°C DB / 19°C WB; outdoor temp.: 46°C DB / 24°C WB

3. Heating conditions: indoor temp.: 20°C DB/15°C WB outdoor temp.: 7°C DB / 6°C WB

4. Sound level: is measured in a semi-anechoic chamber conversion value, measured at a position 1 m in front of the unit

at a height of 1.3 m above the floor.

5. Inter connecting refrigerant piping length is 7.5m, level difference is zero.

6. Interconnecting refrigerant piping diameters are based on the condition that the total equivalent liquid line length is less than 90 meter.

When the total equivalent liquid line length is more than 90 meter, Please refer to the installation manual to choose interconnecting

refrigerant piping diameter.

Modular Outdoor Units - Technical Specifications

Outdoor Unit Model

14 –16 HP 18 HP

38VF014H119011 38VF016H119011 38VF018H119011

Outdoor Fan

Outdoor Coil

Outdoor Air Flow

External Static Pressure

Dimension ( D × H )

Vane Quantities

Number of rows

Tube pitch(a) × row pitch(b)

Tube outside diameter

Coil length×height

Number of circuits

Outdoor Sound Pressure Level (4)

Outdoor Unit

Quantity

Type

Material

Fin spacing

Fin type

Tube type

Packing (WxHxD)

Net / Gross weight

Charged refrigerant type and volume

Refrigerant control

Refrigerant Piping

Lines (5)

Dimension (WxHxD)

Excessive operating pressure

Liquid side

Gas side

Oil balance pipe mm mm mm mm mm m 3 /h

Pa dB(A) mm mm kg

Kg

MPa mm mm mm

2

Axial

Plastic

560 x 189

3+4

2

22 × 19

1.6

2270×1232

2

Axial

Plastic

560 x 189

3+4

2

22 × 19

1.6

Hydrophilic aluminum

ะค7.94

Inner-grooved

2270×1232

2

Axial

Plastic

560 x 189

3+4

2

22 × 19

1.6

2867×1232

22

15620

22

15620

0 ~ 20 ( Default )

20 ~ 40 ( Optional )

22

15770

61 62 62

1250×1615×765 1250×1615×765 1250×1615×765

1305×1790×820 1305×1790×820 1305×1790×820

288/308 288/308 310/330

R410A / 15 R410A / 15

Electronic Expansion Valves

R410A / 16

4.4/2.6

Ø 15.9

4.4/2.6

Ø 15.9

4.4/2.6

Ø 15.9

Ø 31.8

Ø 6.4

Ø 31.8

Ø 6.4

Ø 31.8

Ø 6.4

Notes:

1. Cooling conditions: indoor temp.: 27°C DB / 19°C WB; outdoor temp.: 35°C DB / 24°C WB

2. Cooling conditions: indoor temp.: 29°C DB / 19°C WB; outdoor temp.: 46°C DB / 24°C WB

3. Heating conditions: indoor temp.: 20°C DB/15°C WB outdoor temp.: 7°C DB / 6°C WB

4. Sound level: is measured in a semi-anechoic chamber conversion value, measured at a position 1 m in front of the unit

at a height of 1.3 m above the floor.

5. Inter connecting refrigerant piping length is 7.5m, level difference is zero.

6. Interconnecting refrigerant piping diameters are based on the condition that the total equivalent liquid line length is less than 90 meter.

When the total equivalent liquid line length is more than 90 meter, Please refer to the installation manual to choose interconnecting

refrigerant piping diameter.

9

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Advanced Design

Modular Outdoor Units - Dimensions

8 / 10 HP 12 / 14 / 16 / 18 HP

960 1250

10

Dimensions ( mm )

Modular Outdoor Units – Refrigerant Piping Connections

R: Pipe Connection

Size

HP

8

C

D

A

B

199

159

195

168

E

F

208

220

Liquide pipe OD Ø 12.7

Gas pipe OD Ø 25.4

10

199

159

195

168

208

220

OD Ø 12.7

OD Ø 25.4

A

B

Liquid side

Gauge point

Cooling only type without

Oil balancer

For parallel connect the modular units

Gas side

F E D

12

169

209

169

168

208

220

OD Ø 15.9

OD Ø 31.8

C

R Section View

14

169

209

169

168

208

220

OD Ø 15.9

OD Ø 31.8

Dimensions ( mm )

16

169

209

169

168

208

220

OD Ø 15.9

OD Ø 31.8

18

169

209

169

168

208

220

OD Ø 15.9

OD Ø 31.8

Wide VRF Outdoor Units Lineup

Single Outdoor Unit

8 HP 10 HP 12 HP 14 HP 16 HP 18 HP

Two Modular

Outdoor Units

Combination

Three Modular

Outdoor Units

Combination

Four Modular

Outdoor Units

Combination

20 HP

22 HP

24 HP

26 HP

28 HP

30 HP

32 HP

34 HP

36 HP

38 HP

40 HP

42 HP

44 HP

46 HP

48 HP

50 HP

52 HP

54 HP

56 HP

58 HP

60 HP

62 HP

64 HP

66 HP

68 HP

70 HP

72 HP

11

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Advanced Design

Wide VRF Outdoor Units Lineup

The Outdoor units capacity range is from 8HP up to 72HP in 2HP increment.

Maximum 4 ( four ) outdoor units can be connected in one VRF system with maximum

64 indoor units with capacity up to 130% of the total outdoor units capacity.

One Single Outdoor Unit

One Single Outdoor Unit of 18HP Maximum Capacity can be connected with maximum quantity of 29 indoor units

1 Outdoor Unit

18 HP Maximum Capacity

29 Indoor Units Maximum

12

One Single

Outdoor Unit

Total

Capacity

HP

8

10

12

14

16

18

8

HP

Combination Table

One Single Outdoor Unit

One Single Modular Outdoor unit

10

HP

12

HP

14

HP

16

HP

18

HP

Maximum

Quantity of

Indoor Units

13

16

20

23

26

29

Capacity ( kW )

Cooling

@ T1

Cooling

@ T3

Heating

25.2 23.7

27

28 26.3

31.5

33.5 30.7

37.5

40 37.6

45

45 41.24

50

50 45.83

56

Two Modular Outdoor Units Combination

Two Modular Outdoor Units of 36HP Maximum Capacity can be connected with maximum quantity of 59 indoor units

Master Slave

2 Modular Outdoor Units

36 HP Maximum Capacity

59 Indoor Units Maximum

Two Modular

Outdoor Units

Combination

Total

Capacity

HP

28

30

32

34

36

20

22

24

26

Combination Table

Two Modular Outdoor Units Combination

Recommended Two Modular Outdoor Units Combination Maximum

8

HP

10

HP

12

HP

14

HP

16

HP

18

HP

Quantity of

Indoor Units

33

46

50

53

56

59

36

39

43

Capacity ( kW )

Cooling

@ T1

Cooling

@ T3

Heating

56 52.60

63

61.5 57.00

69

68 63.90

76.5

73 67.54

81.5

78 72.13

87.5

85 78.84

95

90 83.43

101

95 87.07

106

100 91.66

112

13

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Advanced Design

Three Modular Outdoor Units Combination

Three Modular Outdoor Units of 54HP Maximum Capacity can be connected with maximum quantity of 64 indoor units

Master Slave ( 1 ) Slave ( 2 )

3 Modular Outdoor Units

54 HP Maximum Capacity

64 Indoor Units Maximum

14

Three Modular

Outdoor Units

Combination

Total

Capacity

HP

50

52

54

38

40

42

44

46

48

Combination Table

Three Modular Outdoor Units Combination

Recommended Three Modular Outdoor Units Combination Maximum

8

HP

10

HP

12

HP

14

HP

16

HP

18

HP

Quantity of

Indoor Units

63

64

64

Cooling

@ T1

Capacity ( kW )

Cooling

@ T3

106 98.43

113 105.14

120 108.78

Heating

119

126.5

135

64 123 113.37

137.5

64 128 117.96

143.5

64 135 124.67

151

64 140 129.26

157

64 145 132.90

162

64 150 137.49

168

Four Modular Outdoor Units Combination

Four Modular Outdoor Units of 72HP Maximum Capacity can be connected with maximum quantity of 64 indoor units

Master Slave ( 1 ) Slave ( 2 ) Slave ( 3 )

4 Modular Outdoor Units

72 HP Maximum Capacity

64 Indoor Units Maximum

Four Modular

Outdoor Units

Combination

Total

Capacity

HP

68

70

72

56

58

60

62

64

66

Combination Table

Four Modular Outdoor Units Combination

Recommended Four Modular Outdoor Units Combination Maximum

8

HP

10

HP

12

HP

14

HP

16

HP

18

HP

Quantity of

Indoor Units

Cooling

@ T1

Capacity ( kW )

Cooling

@ T3

Heating

64 156 144.26

175

64 163 150.97

182.5

64 168 155.56

188.5

64 173 159.20

193.5

64 178 163.79

199.5

64 185 170.50

207

64 190 175.09

213

64 195 178.73

218

64 200 183.32

224

15

16

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Advanced Design

Wide VRF Indoor Units Lineup - Types & Range

Ducted LSP Cassette 1 Way High Wall- S

1.8 - 2.2 - 2.8 - 3.6

4.5 - 5.6 - 7.1 Kw

Ducted MSP

1.8 - 2.2 - 2.8 - 3.6 - 4.5

5.6 - 7.1 Kw

Cassette 2 Way

2.2 - 2.8 - 3.6- 4.5 -5.6 Kw

High Wall - C

2.2 - 2.8 - 3.6 - 4.5 - 5.6 - 7.1 - 8.0

9.0 - 10.0 - 11.2 - 12.5 - 14.0 Kw

Ducted HSP

2.2 - 2.8 - 3.6 - 4.5

5.6 - 7.1 Kw

Cassette Compact 4 Way

2.2 - 2.8 - 3.6- 4.5 -5.6 Kw

High Wall - R

7.1 - 8.0 - 9.0 - 11.2 - 14.0

16.0 - 20.0 - 25.0 - 28.0 Kw

Ducted Big HSP

40.0 - 45.0 - 56.0 Kw

Fresh Air Unit

2.2 - 2.8 - 3.6 - 4.5 Kw

Cassette 4 Way

7.1 - 8.0 - 9.0 Kw

Console

2.8 - 3.6 - 4.5 - 5.6 - 7.1 - 8.0

9.0 - 10.0 - 11.2 - 12.5 - 14.0 Kw

2.2 - 2.8 - 3.6- 4.5 Kw

Floor - Ceiling

12.5 - 14.0 - 20.0

25.0 - 28.0 Kw

Concealed Floor Standing

3.6 - 4.5 - 5.6 - 7.1 - 8.0

9.0 - 11.2 - 14.0 Kw

Exposed Floor Standing

2.2 - 2.8 - 3.6 - 4.5

5.6 - 7.1 - 8.0 Kw

2.2 - 2.8 - 3.6 - 4.5 - 5.6

7.1 - 8.0 Kw

Wide VRF Indoor Units Lineup – Applications

Ducted

Cassette

High Wall Console

17

18

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Wide Selection

Carrier VRF Selection Software

Carrier selection software provides selection flexibility from wide range of Outdoor

and Indoor Units models depending upon load conditions & diversity required for

VRF projects.

Carrier selection software is used to design VRF systems which meets the consultants

and distributors requirements.

Carrier selection software provides a quick and convenient selection for users, which

supports multi-languages. Greatly improving the selection efficiency and simplifying

the selection procedures.

Multilanguage

Selection

Report

Output

Load

Calculation

Auto

Calculating

Drawing

Sketch

Project

It contains project information such as project name, location, etc.

Detailed meteorological data’s make the machines selected t for the local environment well.

A/C selection

There are different types and models of indoor units and all kinds of different power of outdoor units for choosing.

Controller selection

To select the right central controller for indoor unit and outdoor units; wireless or remote controller for indoor units.

Load calculation

It provides two calculation methods. Directly decide the room load or input the detailed parameters such as room area, estimated cooling / heating load index, heating capacity and cooling capacity.

Piping drawing

Piping drawing shows the detailed piping layout of VRF system including outdoor units, indoor units and parameters of piping and branch distributors.

Output report

It provides a total report of VRF project selection in word or PDF format.

19

20

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Wide Application Range

Wide Stable Operation Range

-20°C

-5°C

COOLING MODE

Outdoor Temperature

HEATING MODE

Outdoor Temperature 27°C

52°C

-20 -10 0 10 20 30 40 50 60

Outdoor temp. °C ( D.B )

Extra High Static Pressure – Max. 40Pa and Air Volume Increased by 10%

- Standard 0-20Pa function is equipped by default.

- High-static pressure propeller and optimized fan guard

can adapt to various installation environments.

- Carrier now offers up to 40 Pa external static pressure units

for customized applications.

* You need to consult Carrier sales team if you require

over 40Pa external static pressure.

40 Pa

Long Piping Length & Long Height Difference for Large Projects

The first indoor unit branch

Piping Installation Data

Actual Total Piping Length

Permitted value ( m )

1000 m *

Piping

Length

Actual longest piping length

Equivalent longest piping length

Height

Difference

Equivalent piping length from the farthest indoor unit to the first indoor unit branch

Height difference between outdoor unit and indoor unit

Outdoor Unit Up

Outdoor Unit Down

Height difference between indoor units

* Total pipe length is equal to two times pipe length plus pipe length.

* When the piping length from the farthest IDU to the first indoor branch joint is more than 40m,

It needs to meet the specific conditions according to the installation manual to achieve 90m.

175 m

200 m

40 m / 90 m *

70 m

110 m

30 m

21

22

VRF FULL DC INVERTER

VRF FULL DC INVERTER

High Efficiency

High Cooling EER / High Heating COP Values

VRF Full DC Inverter Outdoor Units series with all high efficiency DC Inverter scroll compressors, all high efficiency DC motor (s) and high efficiency outdoor coil, achieve the world’s top class Cooling Energy Efficiency Ratio ( EER ) and Heating Coefficient Of

Performance ( COP ).

Cooling EER

4.29

3.97 3.81

3.54 3.50 3.45

8 HP 10 HP 12 HP 14 HP 16 HP 18 HP

Heating COP

4.39 4.17 4.17 4.02 3.91 3.89

8 HP 10 HP 12 HP 14 HP 16 HP 18 HP

High Efficiency VRF Full DC Inverter Outdoor Unit

High Efficiency

Fan Housing & Outlet Grille

High Efficiency Outdoor Fan (s)

High Efficiency DC Fan Motor (s)

ODU

Size

8 HP

10 HP

12 HP

14 HP

16 HP

18 HP

DC Fan Motor

Qty.

1

1

2

2

2

2

High Efficiency

180° Sine-Wave DC Inverter

Control For Compressor Motor

High Efficiency Outdoor Coil

Precoated

Aluminum

Fins

Inner

Groove

Copper Tubes

12°C

Subcooling

High Efficiency

DC Inverter Scroll Compressor (s)

ODU

Size

8 HP

10 HP

12 HP

14 HP

16 HP

18 HP

Compressor

Qty.

1

1

1 + 1

1 + 1

1 + 1

1 + 1

23

VRF FULL DC INVERTER

VRF FULL DC INVERTER

High Efficiency

High Efficiency DC Inverter Scroll Compressor Technology

All compressor(s) are DC Inverter compressor type

8HP and 10HP outdoor units are equipped with one DC inverter scroll compressor

12, 14, 16, 18 HP outdoor units are equipped with two DC inverter scroll compressors

Suction Pipe

Discharge

Pipe

Oil even

Pipe

New structure enhances, mid frequency performance

Specially designed scroll profile for R410A

More compact, weight reduced by 50%

High IPLV

Advanced permanent magnet DC motor provide high torque and efficiencyand achieve 70% reduction in volume.

Wide operation range from 20Hz to 200Hz.

DC Inverter

Scroll Compressor

Compressor efficiency New DC motor-centralized winding

Common DC motor-distributing winding

Centralizing winding

Distributing winding

20 40 60 80 100

Rotor speed (s-1)

High Efficiency Smooth 180° Sine Wave DC Inverter Control

180° Sine Wave Inverter Control smoothes the rotation of the compressor motor, and improves compressor efficiency sharply than traditional sawtooth wave.

24 Common sawtooth wave 180° Sine Wave DC inverter

High Efficiency DC Fan Motor Technology

All outdoor fan motor(s) are DC motor type

8HP and 10HP outdoor units are equipped with one DC fan motor

12, 14, 16, 18 HP outdoor units are equipped with two DC fan motors

According to the running load and system pressure, the system speed control adjusts the

speed of DC fan motor to achieve the minimum power consumption and maximum efficiency.

DC fan motor

1000

800

600

400

200

DC inverter stepless adjustment

AC inverter multistep adjustment

System pressure

High Efficiency Outdoor Fan (s)

Optimum design of 3-dimensional turbo fan with patent aerodynamic new profile design of fan blades with sharp edge and little curve bigger diameter for maximum efficiency with maximum airflow.

Common design Carrier design

High Efficiency Fan Housing and Outlet Grille

Optimum design of fan housing and outlet grille for maximum airflow.

Efficient Air Management System (AMS) with uniform air circulation

over the complete coil surface at low velocity for maximum airflow

with minimum turbulence for minimum air resistance, smooth airflow

and efficient operation.

25

VRF FULL DC INVERTER

26

VRF FULL DC INVERTER

High Efficiency

High Efficiency Outdoor Coil Technology

High efficiency outdoor coil with large heat transfer surface, optimum coil circuiting design and efficient subcooling for maximum heat transfer, minimum electrical consumption and maximum efficiency.

Carrier design Common design

Windage & air flow

0.8

0.6

0.4

0.2

0

0

Reduce

28%

Common design

Carrier design

200 400 600 800 1000 Re

Frost contrast

High efficiency inner-threaded pipe, enhance heat transfer.

Hydrophilic film fins + inner-threaded pipes

0.8

0.6

0.4

0.2

0

0

Common design

0.2

0.4

Reduce

30%

Carrier design

0.6

0.8

Relative frosting rate

New patent design of window fins which enlarge the heat-transfer area , decrease the

air resistance, save more power and enhance heat transfer performance in cooling and

heating.

Hydrophilic aluminum fins and inner-groove copper tubes optimize heat transfer

efficiency.

Common Design

Gas Liquid

Carrier Design

Gas

Gas Gas Gas-Liquid Liquid

Liquid

Liquid

43 o C

75 o C

Common

Design

Increase the hot liquid rate in the condenser

Improve the heat-exchange efficiency

The outdoor coil can reach up to 12 o C subcooling,

reduces the system resistance and improves system efficiency and reliability.

37.1

o C

75 o C

Carrier

Sub-cooling

Technology

When the outdoor temperature is 35 o C, the refrigerant can be cooled down to 37.1

o C,

thus achieving high heat-transfer efficiency with only 2.1

o C temperature difference.

Multi solenoid valves control technology

Multi solenoid valves control technology in one system.

All the solenoid valves of the outdoor unit ensure precise temperature-control, steady and economic system running and economic to provide a comfortable environment.

Double EXV control technology

Each EXV, in the outdoor unit, achieves 480 pulse :

(1) to adjust refrigerant flow precisely.

(2) to ensure precise and steady temperature-control

to provide a comfortable environment.

High Pressure Sensor

Controls the discharge pressure of the compressor and to control the fan speed.

Always test the system pressure Every 20 seconds, compare the system pressure and the best pressure to adjust DC fan motor speed timely.

27

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Super Quiet

Super Quiet VRF Full DC Inverter Outdoor Unit

Super Quiet

Fan Housing & Outlet Grille

Super Quiet Outdoor Fan (s)

Super Quiet DC Fan Motor (s)

ODU

Size

8 HP

10 HP

12 HP

14 HP

16 HP

18 HP

DC Fan Motor

Qty.

1

1

2

2

2

2

Super Quiet

180° Sine-Wave DC Inverter

Control For Compressor Motor

28

Super Quiet

DC Inverter Scroll Compressor (s)

ODU

Size

8 HP

10 HP

12 HP

14 HP

16 HP

18 HP

Compressor

Qty.

1

1

1 + 1

1 + 1

1 + 1

1 + 1

Super Quiet DC Inverter Scroll Compressor Technology

Rubber isolators for compressor to absorb vibrations

at starting and running.

Optimum design of compressor suction and discharge tubing

to absorb vibrations and discharge gas pulsations.

DC Inverter

Scroll Compressor

Super Quiet DC Fan Motor Technology

Totally enclosed motor running with low speeds and minimum vibrations.

DC fan motor

Super Quiet Outdoor Fan (s)

Optimum design of 3-dimensional turbo fan with patent aerodynamic new profile design of fan blades with sharp edge and little curve bigger diameter for minimum airflow resistance, minimum sound and minimum vibrations.

Common design Carrier design

Super Quiet Fan Housing and Outlet Grille

Optimum design of fan housing and outlet grille for minimum airflow

resistance, minimum sound level and minimum vibrations.

Efficient Air Management System (AMS) with uniform air circulation

over the complete coil surface at low velocity for minimum sound level.

New Patent Fan Arrangement Technology for Sound Reduction

ODU

Capacity

Fan Qty.

8 / 10 HP

1

12 / 14 / 16 / 18 HP

1 + 1

Blades Qty.

3 3 + 4

29

30

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Enhanced Comfort

Smart Comfort Technology

For Quick Warm-up & Cool-down Design and Less Temperature Fluctuation

By utilizing the benefits of DC inverter compressor, the system can reach full load quickly and shorten the warm-up and cool-down times to provide an immediate and comfortable air solution.

Less temperature fluctuation will create a better living environment.

Temp

Time

1

2

Cooling operation

Inverter

Non-Inverter

Fluctuation of Room Temperature

Smart Soft Start Technology

Soft start function of VRF DC inverter compressor reduces strike to the electric network.

This kind of high-performance and low sound scroll compressor operates at a faster rate when starting, reducing start-up time. It helps the unitVRF system to bring the room temperature up to the set level quickly.

Starting current

( % )

600

500

400

300

200

100

1 2

Direct start

Y - โˆ† Start

Start by Inverter

Comparison of start by inverter and by traditional methods

3 4 5 6

( Sec )

Smart Night Super Silent Operation Technology

Smart Night Super Silent Mode is easily set at site on the main board of the outdoor unit.

Smart Night Super Silent Mode has the following functions :

(1) Controls peak daytime operation ( X hours ) and non peak night time operation

( Y hours ) as per any one of the following modes :

Mode 1

Mode 2

Mode 3

Mode 4

X : 6 hours

X : 8 hours

X : 6 hours

X : 8 hours

,

,

,

,

Y : 10 hours

Y : 10 hours

Y : 12 hours

Y : 8 hours

Smart Night Super Silent Mode is activated X hours after peak day time operation

and it goes back to normal operation after Y hours of non peak night operation.

(2) Reduces sound level to minimum of 45 dB(A)

Peak value of ambient temp.

100

50

Sound

08:00 14:00 22:00 08:00

Mode 1→ X : 6 hours, Y : 10 hours

Smart Defrosting Technology - This function can be activated by setting at site.

- Temperature (load) curve shown in the graph is just an example.

Smart defrosting program has the following functions :

(1) Controls the defrosting time according the system real temperature.

(2) Reduces the heating loss by unnecessary defrosting and the indoor unit more comfortable.

(3) Shortens the defrosting time to 4 minutes due to the specialized defrosting valve.

Smart Defrosting

Usual Defrosting t min.

โˆ†t

Time 31

VRF FULL DC INVERTER

VRF FULL DC INVERTER

High Reliability

Smart Duty Cycling Function

In one combination of modular outdoor units, any outdoor unit can run as the master outdoor unit to equalize the service life of all outdoor units

Master

Outdoor unit

Slave (1)

Outdoor unit

Slave (2)

Outdoor unit

No. 1

No. 3

No. 2

No. 2

No. 1

No. 3

No. 3

No. 2

No. 1

INV INV INV INV INV INV

Smart Back-up Function

In one combination of modular outdoor units, when the master outdoor unit failed, any single slave outdoor unit can be set as the master unit, then the remaining outdoor units can keep on working. This can be set at field by DIP switch located on the main board of electrical control box of outdoor unit.

Master

Outdoor unit

Slave (1)

Outdoor unit

Slave (2)

Outdoor unit

32

INV INV INV INV

When the slave (1) outdoor unit failed and came into standby state, the left module still work.

INV INV

Smart & Presize 5 Stage Oil Control Technology

Smart & Presize 5 stage oil control technology ensures continuous safe oil level for every outdoor unit and every compressor to avoid compressor oil lack problem.

1st stage : Compressor internal oil separator

2nd stage : High efficiency oil separator (separation efficiency up to 99%)

3rd stage : Oil balance technology between compressors

4th stage : Oil balance technology between outdoor units modules

5th stage : Smart system oil return program

2nd stage 4th stage

1st stage

5th stage

3rd stage

Indoor Unit Quantity Monitoring

The quantity of indoor units should be exactly set on the outdoor main board, once some indoor units miscommunication with outdoor units during system running, the outdoor units will stop and display the fault code “H7”. This can prevent compressor from liquid hammer caused by dropped indoor units with EXV unclosed.

ENC3 S12

ON

Quantity setting switch

33

34

VRF FULL DC INVERTER

VRF FULL DC INVERTER

High Durability

Standard coated aluminum fins of outdoor

coil for coastal applications to protect

against corrosion.

Anti-rust, weather proof and long life outdoor unit sheet metal parts

made of chemically treated and zinc coated ( galvanized ) sheet metal.

Powder painted casing of outdoor unit with prefect adhesion of

highly resistant ployester paint 60-80 microns thick, which is

electro-statically applied and baked at a temperature of 220°C.

Easy Installation, Service and Maintenance

Compact Design for Effective Use of Space

Compact size and light weight design minimizes the installation footprint, reduces the installation floor load, and is easier for transportation.

For some projects the units can even be transported through the elevator or forklift, reduce access problem at the jobsite and reduce time and labor.

Easy Refrigerant Connections between Outdoor Units in One Combination

Two Modular Outdoor Units

Combination

W2 ( master )

W1 ( slave )

Liquid Line

VRF

INVERTER

Notes :

(1) Arrange modular outdoor units in a sequence

of Max HP to Min. HP i.e W2>W1

(2) The master outdoor unit W2 is the

maximum HP outdoor unit.

Gas Line

Oil Balance Line

VRF

INVERTER

Three Modular Outdoor Units

Combination

W3 ( master )

W2 ( slave )

W1 ( slave )

Liquid Line

VRF

INVERTER

VRF

INVERTER

VRF

INVERTER

Gas Line

Notes :

Oil Balance Line

(1) Arrange modular outdoor units in a sequence of Max HP to Min. HP i.e W3>W2>W1

(2) The master outdoor unit W3 is the maximum HP outdoor unit.

Four Modular Outdoor Units

Combination

W4 ( master )

W3 ( slave )

Liquid Line W2 ( slave )

VRF

INVERTER

W1 ( slave )

VRF

INVERTER

VRF

INVERTER

Gas Line

VRF

INVERTER

Notes :

Oil Balance Line

(1) Arrange modular outdoor units in a sequence of Max HP to Min. HP i.e W4>W3>W2>W1

(2) The master outdoor unit W4 is the maximum HP outdoor unit.

35

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Easy Installation, Service and Maintenance

Simple Signal Line Connection

Central control can be connected from indoor side or outdoor side ( X, Y, E terminal )

as you wish ( Reversible communication ).

Only one group of communication wires ( P, Q, E ) can connect outdoor unit,

indoor units and network

P Q E X Y E

X Y E

P Q E P Q E P Q E P Q E

Wireless controller can query and modify each indoor unit’s address.

36

Smart System Operation Parameters Checking For Start-Up & Commissioning

The reserved checking window on the electric control box of outdoor unit is used for easy checking of VRF system operation parameters status for start-up and commissioning.

4 bits digital tube

LED display

Smart Self Diagnostic Function For System Malfunctions Detection

The reserved checking window on the electrical control box of outdoor unit is also used for easy checking of error codes of

VRF system malfunctions.

4 bits digital tube

LED display

Auto Addressing of Indoor Units

Through Wireless Remote Control

Auto addressing of indoor units is done just by pressing button of

wireless remote control.

Wireless remote control and wired control can enquire and modify every

indoor unit address.

Through Outdoor Unit

Outdoor unit can automatically distribute the addresses to indoor units.

37

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Easy Installation, Service and Maintenance

Rotating Electric Control Box For 18 HP Outdoor Unit

The electronic control box can rotate in a wide angle to facilitate service and maintenance of pipeline system by reducing the disassembly time of the electrical control box.

W ide

Ro tatin g Angle

Rotating electrical control box

Outer layout compressor and simple pipe system

Easy Accessibility To Compressors & Valves

Compressors are located near the door, which simplifies checks and enables valves or compressors parts to be replaced easily.

38

Convenient electronic control check window. Can directly observe the operation status from the LED display, and directly press the FORCE

COOLING / CHECK button.

Integrated Solution for Control and Management

Carrier Intelligent Manager of designed specifically to control VRF systems, is based around a centralized format and dedicated to the complete control and monitoring of all the system’s functions. It can be used as a flexible multi-purpose system and applied to a variety of needs, according to the scale, purpose and control method of each building.

IMM

Software Login Interface Main Interface

Internet WLAN

Laptop

IP / Ethernet

PC

IMM Software

Fire Wall

PC

MAX : 4

IMM Software

M-INTERFACE

LAN

K1 K2 E

M-net

X Y E

MAX : 4

Outdoor Unit

39

VRF FULL DC INVERTER

VRF FULL DC INVERTER

Variety of Accessories

Branch Joints For Outdoor Unit

Description Appearance Branch Model Packing Size (mm) / Gross Weight (kg)

Two Modular

Outdoor Units

Combination

BJC-02-CM(i) 255 × 150 × 185 / 1.5

Three Modular

Outdoor Units

Combination

BJC-03-CM(i) 345 × 160 × 285 / 3.4

40

Four Modular

Outdoor Units

Combination

BJC-04-CM(i) 475 × 165 × 300 / 4.8

Detailed Dimensions of Branch Joints For Outdoor Unit

Branch model Gas side joints

BJC-02-CM(i)

0D:31.8

0D:31.8

ID:25.4

ID:25.4

Q2 Q2

ID:31.8

ID:31.8

ID:34.9

ID:34.9

0D:34.9

Q1

ID:31.8

ID:31.8

ID:25.4

ID:25.4

Q1

ID:31.8

ID:31.8

0D:31.8

0D:31.8

Q4 Q4 Q3 Q3

ID:38.1

ID:38.1

ID:34.9

ID:34.9

Liquid side joints

0D:15.9

0D:15.9

ID:12.7

ID:12.7

ID:15.9

ID:15.9

ID:19.1

ID:19.1

0D:19.1

Y2 Y2

Y6 Y6 Y3 Y3

ID:22.2

ID:22.2

Y1

ID:15.9

ID:15.9

Y1

ID:15.9

ID:15.9

0D:15.9

0D:15.9

ID:12.7

ID:12.7

ID:19.1

ID:19.1

Q2 Q2

Q1 Q1

Q7 Q7

Y2 Y2

Y1 Y1

Y6 Y6

BJC-03-CM(i)

Q5 Q5

Y7 Y7 Y4 Y4

Q1 Q1

Y1 Y1

BJC-04-CM(i)

41

www.miraco.com.eg

January 2016

Carrier is committed For continuous improvement of energy saving green products according to national and international standards to ensure the highest quality and reliability standards, and to meet market regulations and requirements.

All specifications subject to change without prior notice according to Carrier policy of continuous development.

advertisement

Key Features

  • Modular outdoor units
  • Wide stable operation range
  • High efficiency
  • Super quiet
  • Enhanced comfort
  • High reliability
  • High durability
  • Easy installation, service and maintenance
  • Variety of accessories
  • Variety of control options

Frequently Answers and Questions

What is the maximum capacity of the XPower Full DC Inverter system?
The maximum capacity of the XPower Full DC Inverter system is 72HP.
How many outdoor units can be connected in one VRF system?
A maximum of four outdoor units can be connected in one VRF system.
What types of indoor units are available with the XPower Full DC Inverter system?
The XPower Full DC Inverter system offers a variety of indoor units, including ducted, cassette, high wall, and floor-mounted options.
What is the maximum piping length and height difference for the XPower Full DC Inverter system?
The maximum piping length is 175 meters, and the maximum height difference between the outdoor unit and indoor units is 110 meters down and 70 meters up.
What is the maximum quantity of indoor units that can be connected to one outdoor unit?
The maximum quantity of indoor units that can be connected to one outdoor unit is 29.