Carrier XPower Full DC Inverter VRF Technical Manual
The Carrier XPower Full DC Inverter is a variable refrigerant flow (VRF) system that offers a wide range of applications for residential, light commercial, and commercial buildings. It features modular outdoor units that can be combined to meet specific capacity requirements, with a maximum of 72HP achievable. The system also has a variety of indoor units, including ducted, cassette, high wall, and floor-mounted options. The units are designed for high efficiency and quiet operation, with a wide stable operation range. The XPower Full DC Inverter system has a variety of control options, including wireless remote controls and central management software.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
improve buildings
TM
VRF FULL DC INVERTER
Miraco
MISR REFRIGERATION & AIR CONDITIONING MFG. CO.
Technical Manual
VRF Outdoor Units the environmentally sound refrigerant
Smart Energy Saving Green Air Conditioning Solutions
For Large Scale Residential, Light Commercial & Commercial Applications
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Key Features
2
( Key Features )
14
( 1 )
Variety of
Applications
Residential
Light Commercial
Commercial
( 4 )
Wide
VRF Indoor Units
Lineup
1.8 kW to 56 kW
( 7 )
High
Efficiency
( 2 )
Advanced
Design
Modular outdoor units
Variety of indoor units
Type & Ranges
( 3 )
Wide
VRF Outdoor Units
Lineup
8 HP to 72 HP
( 8 )
Super
Quiet
( 5 )
Wide
Selection
Selection software provides flexibility of model selection
( 9 )
Enhanced
Comfort
( 6 )
Wide
Application Range
Wide Operation Range
Long Piping Length
High Height Difference
( 10 )
High
Reliability
( 11 )
High
Durability
( 12 )
Variety of
Controls
Individual Controls
Wireless Control
Wired Control
Central Controls
( 13 )
Variety of
Accessories
( 14 )
Easy
Installation
Service &
Maintenance
Variety of Applications
Carrier VRF Full DC Inverter Systems are Variable Refrigerant Flow R410A Heat Pump Systems.
Carrier VRF Full DC Inverter Systems are smart energy saving green - air conditioning
solutions for large scale residential, light commercial and commercial applications for
a wide range of environmental conditions.
Large Scale Residential & Light Commercial Applications
Luxury Apartments Villas
Restaurants
Large Scale Commercial Applications
Offices
Malls
Multiplexes
Hotels
Educational Institutions 3
4
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Advanced Design
Modular Outdoor Units - Design Layout
Top discharge
2 Pipe system
Modular design
6 basic modules 8HP - 10HP - 12HP - 14HP - 16HP - 18HP, which can be freely combined
in the installation site for wide range and large capacity for big sizes buildings.
2HP increment of capacity range, which meets customers needs accurately.
Outdoor unit includes all DC Inverter Compressor (s) + all DC fan motor (s)
Outdoor Unit
( Module )
8 HP
10 HP
12 HP
14 HP
16 HP
18 HP
DC Inverter Compressor (1)
1
1
1
1
1
1
Maximum capacity is 72 HP
Compressor Quantity
DC Inverter Compressor (2)
1
1
1
1
Maximum quantity of outdoor units is 4
Maximum quantity of indoor units is 64
Total capacity % range of indoor units is 50% ~ 130%
Outdoor DC Fan
Motor Quantity
1
1
2
2
2
2
56-72 HP
8-18 HP
20-36 HP
38-54 HP
Modular Outdoor Units - Model Identification
8 – 10 HP 12 –14 –16 HP 18 HP
Digital No.
Code
1, 2
Product Type
38 : Outdoor Unit
3, 4
Product Classification
VF: VRF FULL DC Inverter
5, 6, 7
Cooling Capacity
008 : 25.2 KW
010 : 28.0 KW
012 : 33.5 KW
014 : 40.0 KW
016 : 45.0 KW
018 : 50.0 KW
8
Application
H : Heat pump
C : Cool Only
9
Refrigerant
1 : R410A
10
Market
1 : Egypt & Export
11
Electrical Characteristics
9 : 380-415V-3PH-50HZ
12
Packing
0 : Standard packing
1 : Crate packing
13
Model Type
1 : Full DC Inverter
14
Model revision code
1 : Modular Type Tropical
1 2 3 4 5 6 7 8 9 10 11 12 13 14
3 8 V F 0 0 8 H 1 1 9 0 1 1
5
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Advanced Design
Modular Outdoor Units - Technical Specifications
6
Outdoor Unit Model
Power Supply
Cooling (1)
Cooling (2)
Heating (3)
Connected Indoor Units
DC Inverter
Scroll Compressor
Outdoor Fan Motor
Capacity
Input
EER
Capacity
Input
EER
Capacity
Input
COP
Total Capacity
Max Quantity
Quantity
V / Ph / Hz
W
Btu/h kW kW / kW
W
Btu/h kW kW / kW
W
W
W/W
%
8 – 10 HP 12 HP
38VF008H119011 38VF010H119011 38VF012H119011
380-415 / 3 / 50 380-415 / 3 / 50 380-415 / 3 / 50
25200 28000 33500
86000 95500 114300
5.875
4.29
23700
7.053
3.97
26300
8.793
3.81
30700
81000
6.37
3.72
27000
6150
4.39
50% ~ 130%
13
1
90000
7.64
3.45
31500
7554
4.17
50% ~ 130%
16
1
104000
11.25
2.73
37500
8993
4.17
50% ~ 130%
20
1 + 1
Model
Capacity
Input
Power supply
Operating frequency
Crankcase heater
Refrigerant oil
Quantity
Type
Model
Insulation class
Safe class
Input
Output
Rated current
Speed
W
W
31590
10340
31590
10340
31590 + 11800
10340 + 3665
V-Ph-Hz 380-415V~3Ph, 50Hz 380-415V~3Ph, 50Hz 380-415V~3Ph, 50Hz
Hz 40~200 40~200 40~200
W 27.6×2 27.6×2 27.6×2×2 ml
W
W
A r/min
FVC68D / 500
1
DC inverter
WZDK750-38G-4
E
IPX4
534
454
4.4
850
FVC68D / 500
1
DC inverter
WZDK750-38G-4
E
IPX4
534
454
4.4
850
FVC68D / 500 +
FVC68D / 500
2
DC inverter
WZDK450-38G
E
IPX4
450 × 2
360 × 2
3.5 × 2
1100 × 2
Modular Outdoor Units - Technical Specifications
Outdoor Unit Model
Power Supply
Cooling (1)
Cooling (2)
Heating (3)
Connected Indoor Units
DC Inverter
Scroll Compressor
Outdoor Fan Motor
14 –16 HP 18 HP
38VF014H119011 38VF016H119011 38VF018H119011
Capacity
Input
EER
Capacity
Input
EER
Capacity
Input
COP
Total Capacity
Max Quantity
Quantity
Model
Capacity
Input
Power supply
Operating frequency
Crankcase heater
Refrigerant oil
Quantity
Type
Model
Insulation class
Safe class
Input
Output
Rated current
Speed
V / Ph / Hz
W
Btu/h kW kW / kW
W
Btu/h kW kW / kW
W
W
W/W
%
380-415 / 3 / 50 380-415 / 3 / 50 380-415 / 3 / 50
40000 45000 50000
136500 153500 170500
11299
3.54
37600
12857
3.5
41240
14493
3.45
45830
129000
12240
3.07
45000
11194
4.02
50% ~ 130%
23
1+1
141000
16460
2.51
50000
12788
3.91
50% ~ 130%
26
1+1
156371
18550
2.47
56000
14396
3.89
50% ~ 130%
29
2
W
W
E655DHD-65D2YG+
E405DHD-36D2YG
31590+11800
10340+3665
E655DHD-65D2YG+
E405DHD-36D2YG E655DHD-65D2YG
31590+11800
10340+3665
31590+31590
10340+10340
V-Ph-Hz 380-415V~3Ph, 50Hz 380-415V~3Ph, 50Hz 380-415V~3Ph, 50Hz
Hz 40~200/48~230 40~200/48~230 40~200
W 27.6×2 27.6×2 27.6×2 ml
W
W
A r/min
FVC68D / 500 +
FVC68D / 500
2
DC motor
WZDK450-38G
E
IPX4
450×2
360×2
3.5×2
1100×2
FVC68D / 500 +
FVC68D / 500
2
DC motor
WZDK450-38G
E
IPX4
450×2
360×2
3.5×2
1100×2
FVC68D / 500 +
FVC68D / 500
2
DC motor
WZDK750-38G-4
E
IPX4
534x2
454x2
3.6×2
850×2 7
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Advanced Design
Modular Outdoor Units - Technical Specifications
8
Outdoor Unit Model
8 – 10 HP 12 HP
38VF008H119011 38VF010H119011 38VF012H119011
Outdoor Fan
Outdoor Coil
Outdoor Air Flow
External Static Pressure
Dimension ( D × H )
Vane Quantities
Number of rows
Tube pitch(a) × row pitch(b)
Tube outside diameter
Coil length×height
Number of circuits
Outdoor Sound Pressure Level (4)
Outdoor Unit
Quantity
Type
Material
Fin spacing
Fin type
Tube type
Packing (WxHxD)
Net / Gross weight
Charged refrigerant type and volume
Refrigerant control
Refrigerant Piping
Lines (5)
Dimension (WxHxD)
Excessive operating pressure
Liquid side
Gas side
Oil balance pipe mm mm mm mm mm m 3 /h
Pa dB(A) mm mm kg
Kg
MPa mm mm mm
1
Axial
Plastic
700 x 202
3
2
22 × 19
1.6
1985×1232
1
Axial
Plastic
700 x 202
3
2
22 × 19
1.6
Hydrophilic aluminum
ะค7.94
Inner-grooved
1985×1232
2
Axial
Plastic
560 x 189
3 + 4
2
22 × 19
1.6
2270×1232
22
11242
22
11242
0 ~ 20 ( Default )
20 ~ 40 ( Optional )
22
15620
57 57 59
960×1615×765 960×1615×765 1250×1615×765
1025×1790×830 1025×1790×830 1305×1790×820
212/220 212/220 288/300
R410A / 10 R410A / 10
Electronic Expansion Valves
R410A / 12
4.4/2.6
Ø 12.7
4.4/2.6
Ø 12.7
4.4/2.6
Ø 15.9
Ø 25.4
Ø 6.4
Ø 25.4
Ø 6.4
Ø 31.8
Ø 6.4
Notes:
1. Cooling conditions: indoor temp.: 27°C DB / 19°C WB; outdoor temp.: 35°C DB / 24°C WB
2. Cooling conditions: indoor temp.: 29°C DB / 19°C WB; outdoor temp.: 46°C DB / 24°C WB
3. Heating conditions: indoor temp.: 20°C DB/15°C WB outdoor temp.: 7°C DB / 6°C WB
4. Sound level: is measured in a semi-anechoic chamber conversion value, measured at a position 1 m in front of the unit
at a height of 1.3 m above the floor.
5. Inter connecting refrigerant piping length is 7.5m, level difference is zero.
6. Interconnecting refrigerant piping diameters are based on the condition that the total equivalent liquid line length is less than 90 meter.
When the total equivalent liquid line length is more than 90 meter, Please refer to the installation manual to choose interconnecting
refrigerant piping diameter.
Modular Outdoor Units - Technical Specifications
Outdoor Unit Model
14 –16 HP 18 HP
38VF014H119011 38VF016H119011 38VF018H119011
Outdoor Fan
Outdoor Coil
Outdoor Air Flow
External Static Pressure
Dimension ( D × H )
Vane Quantities
Number of rows
Tube pitch(a) × row pitch(b)
Tube outside diameter
Coil length×height
Number of circuits
Outdoor Sound Pressure Level (4)
Outdoor Unit
Quantity
Type
Material
Fin spacing
Fin type
Tube type
Packing (WxHxD)
Net / Gross weight
Charged refrigerant type and volume
Refrigerant control
Refrigerant Piping
Lines (5)
Dimension (WxHxD)
Excessive operating pressure
Liquid side
Gas side
Oil balance pipe mm mm mm mm mm m 3 /h
Pa dB(A) mm mm kg
Kg
MPa mm mm mm
2
Axial
Plastic
560 x 189
3+4
2
22 × 19
1.6
2270×1232
2
Axial
Plastic
560 x 189
3+4
2
22 × 19
1.6
Hydrophilic aluminum
ะค7.94
Inner-grooved
2270×1232
2
Axial
Plastic
560 x 189
3+4
2
22 × 19
1.6
2867×1232
22
15620
22
15620
0 ~ 20 ( Default )
20 ~ 40 ( Optional )
22
15770
61 62 62
1250×1615×765 1250×1615×765 1250×1615×765
1305×1790×820 1305×1790×820 1305×1790×820
288/308 288/308 310/330
R410A / 15 R410A / 15
Electronic Expansion Valves
R410A / 16
4.4/2.6
Ø 15.9
4.4/2.6
Ø 15.9
4.4/2.6
Ø 15.9
Ø 31.8
Ø 6.4
Ø 31.8
Ø 6.4
Ø 31.8
Ø 6.4
Notes:
1. Cooling conditions: indoor temp.: 27°C DB / 19°C WB; outdoor temp.: 35°C DB / 24°C WB
2. Cooling conditions: indoor temp.: 29°C DB / 19°C WB; outdoor temp.: 46°C DB / 24°C WB
3. Heating conditions: indoor temp.: 20°C DB/15°C WB outdoor temp.: 7°C DB / 6°C WB
4. Sound level: is measured in a semi-anechoic chamber conversion value, measured at a position 1 m in front of the unit
at a height of 1.3 m above the floor.
5. Inter connecting refrigerant piping length is 7.5m, level difference is zero.
6. Interconnecting refrigerant piping diameters are based on the condition that the total equivalent liquid line length is less than 90 meter.
When the total equivalent liquid line length is more than 90 meter, Please refer to the installation manual to choose interconnecting
refrigerant piping diameter.
9
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Advanced Design
Modular Outdoor Units - Dimensions
8 / 10 HP 12 / 14 / 16 / 18 HP
960 1250
10
Dimensions ( mm )
Modular Outdoor Units – Refrigerant Piping Connections
R: Pipe Connection
Size
HP
8
C
D
A
B
199
159
195
168
E
F
208
220
Liquide pipe OD Ø 12.7
Gas pipe OD Ø 25.4
10
199
159
195
168
208
220
OD Ø 12.7
OD Ø 25.4
A
B
Liquid side
Gauge point
Cooling only type without
Oil balancer
For parallel connect the modular units
Gas side
F E D
12
169
209
169
168
208
220
OD Ø 15.9
OD Ø 31.8
C
R Section View
14
169
209
169
168
208
220
OD Ø 15.9
OD Ø 31.8
Dimensions ( mm )
16
169
209
169
168
208
220
OD Ø 15.9
OD Ø 31.8
18
169
209
169
168
208
220
OD Ø 15.9
OD Ø 31.8
Wide VRF Outdoor Units Lineup
Single Outdoor Unit
8 HP 10 HP 12 HP 14 HP 16 HP 18 HP
Two Modular
Outdoor Units
Combination
Three Modular
Outdoor Units
Combination
Four Modular
Outdoor Units
Combination
20 HP
22 HP
24 HP
26 HP
28 HP
30 HP
32 HP
34 HP
36 HP
38 HP
40 HP
42 HP
44 HP
46 HP
48 HP
50 HP
52 HP
54 HP
56 HP
58 HP
60 HP
62 HP
64 HP
66 HP
68 HP
70 HP
72 HP
11
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Advanced Design
Wide VRF Outdoor Units Lineup
The Outdoor units capacity range is from 8HP up to 72HP in 2HP increment.
Maximum 4 ( four ) outdoor units can be connected in one VRF system with maximum
64 indoor units with capacity up to 130% of the total outdoor units capacity.
One Single Outdoor Unit
One Single Outdoor Unit of 18HP Maximum Capacity can be connected with maximum quantity of 29 indoor units
1 Outdoor Unit
18 HP Maximum Capacity
29 Indoor Units Maximum
12
One Single
Outdoor Unit
Total
Capacity
HP
8
10
12
14
16
18
8
HP
Combination Table
One Single Outdoor Unit
One Single Modular Outdoor unit
10
HP
12
HP
14
HP
16
HP
18
HP
Maximum
Quantity of
Indoor Units
13
16
20
23
26
29
Capacity ( kW )
Cooling
@ T1
Cooling
@ T3
Heating
25.2 23.7
27
28 26.3
31.5
33.5 30.7
37.5
40 37.6
45
45 41.24
50
50 45.83
56
Two Modular Outdoor Units Combination
Two Modular Outdoor Units of 36HP Maximum Capacity can be connected with maximum quantity of 59 indoor units
Master Slave
2 Modular Outdoor Units
36 HP Maximum Capacity
59 Indoor Units Maximum
Two Modular
Outdoor Units
Combination
Total
Capacity
HP
28
30
32
34
36
20
22
24
26
Combination Table
Two Modular Outdoor Units Combination
Recommended Two Modular Outdoor Units Combination Maximum
8
HP
10
HP
12
HP
14
HP
16
HP
18
HP
Quantity of
Indoor Units
33
46
50
53
56
59
36
39
43
Capacity ( kW )
Cooling
@ T1
Cooling
@ T3
Heating
56 52.60
63
61.5 57.00
69
68 63.90
76.5
73 67.54
81.5
78 72.13
87.5
85 78.84
95
90 83.43
101
95 87.07
106
100 91.66
112
13
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Advanced Design
Three Modular Outdoor Units Combination
Three Modular Outdoor Units of 54HP Maximum Capacity can be connected with maximum quantity of 64 indoor units
Master Slave ( 1 ) Slave ( 2 )
3 Modular Outdoor Units
54 HP Maximum Capacity
64 Indoor Units Maximum
14
Three Modular
Outdoor Units
Combination
Total
Capacity
HP
50
52
54
38
40
42
44
46
48
Combination Table
Three Modular Outdoor Units Combination
Recommended Three Modular Outdoor Units Combination Maximum
8
HP
10
HP
12
HP
14
HP
16
HP
18
HP
Quantity of
Indoor Units
63
64
64
Cooling
@ T1
Capacity ( kW )
Cooling
@ T3
106 98.43
113 105.14
120 108.78
Heating
119
126.5
135
64 123 113.37
137.5
64 128 117.96
143.5
64 135 124.67
151
64 140 129.26
157
64 145 132.90
162
64 150 137.49
168
Four Modular Outdoor Units Combination
Four Modular Outdoor Units of 72HP Maximum Capacity can be connected with maximum quantity of 64 indoor units
Master Slave ( 1 ) Slave ( 2 ) Slave ( 3 )
4 Modular Outdoor Units
72 HP Maximum Capacity
64 Indoor Units Maximum
Four Modular
Outdoor Units
Combination
Total
Capacity
HP
68
70
72
56
58
60
62
64
66
Combination Table
Four Modular Outdoor Units Combination
Recommended Four Modular Outdoor Units Combination Maximum
8
HP
10
HP
12
HP
14
HP
16
HP
18
HP
Quantity of
Indoor Units
Cooling
@ T1
Capacity ( kW )
Cooling
@ T3
Heating
64 156 144.26
175
64 163 150.97
182.5
64 168 155.56
188.5
64 173 159.20
193.5
64 178 163.79
199.5
64 185 170.50
207
64 190 175.09
213
64 195 178.73
218
64 200 183.32
224
15
16
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Advanced Design
Wide VRF Indoor Units Lineup - Types & Range
Ducted LSP Cassette 1 Way High Wall- S
1.8 - 2.2 - 2.8 - 3.6
4.5 - 5.6 - 7.1 Kw
Ducted MSP
1.8 - 2.2 - 2.8 - 3.6 - 4.5
5.6 - 7.1 Kw
Cassette 2 Way
2.2 - 2.8 - 3.6- 4.5 -5.6 Kw
High Wall - C
2.2 - 2.8 - 3.6 - 4.5 - 5.6 - 7.1 - 8.0
9.0 - 10.0 - 11.2 - 12.5 - 14.0 Kw
Ducted HSP
2.2 - 2.8 - 3.6 - 4.5
5.6 - 7.1 Kw
Cassette Compact 4 Way
2.2 - 2.8 - 3.6- 4.5 -5.6 Kw
High Wall - R
7.1 - 8.0 - 9.0 - 11.2 - 14.0
16.0 - 20.0 - 25.0 - 28.0 Kw
Ducted Big HSP
40.0 - 45.0 - 56.0 Kw
Fresh Air Unit
2.2 - 2.8 - 3.6 - 4.5 Kw
Cassette 4 Way
7.1 - 8.0 - 9.0 Kw
Console
2.8 - 3.6 - 4.5 - 5.6 - 7.1 - 8.0
9.0 - 10.0 - 11.2 - 12.5 - 14.0 Kw
2.2 - 2.8 - 3.6- 4.5 Kw
Floor - Ceiling
12.5 - 14.0 - 20.0
25.0 - 28.0 Kw
Concealed Floor Standing
3.6 - 4.5 - 5.6 - 7.1 - 8.0
9.0 - 11.2 - 14.0 Kw
Exposed Floor Standing
2.2 - 2.8 - 3.6 - 4.5
5.6 - 7.1 - 8.0 Kw
2.2 - 2.8 - 3.6 - 4.5 - 5.6
7.1 - 8.0 Kw
Wide VRF Indoor Units Lineup – Applications
Ducted
Cassette
High Wall Console
17
18
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Wide Selection
Carrier VRF Selection Software
Carrier selection software provides selection flexibility from wide range of Outdoor
and Indoor Units models depending upon load conditions & diversity required for
VRF projects.
Carrier selection software is used to design VRF systems which meets the consultants
and distributors requirements.
Carrier selection software provides a quick and convenient selection for users, which
supports multi-languages. Greatly improving the selection efficiency and simplifying
the selection procedures.
Multilanguage
Selection
Report
Output
Load
Calculation
Auto
Calculating
Drawing
Sketch
Project
It contains project information such as project name, location, etc.
Detailed meteorological data’s make the machines selected t for the local environment well.
A/C selection
There are different types and models of indoor units and all kinds of different power of outdoor units for choosing.
Controller selection
To select the right central controller for indoor unit and outdoor units; wireless or remote controller for indoor units.
Load calculation
It provides two calculation methods. Directly decide the room load or input the detailed parameters such as room area, estimated cooling / heating load index, heating capacity and cooling capacity.
Piping drawing
Piping drawing shows the detailed piping layout of VRF system including outdoor units, indoor units and parameters of piping and branch distributors.
Output report
It provides a total report of VRF project selection in word or PDF format.
19
20
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Wide Application Range
Wide Stable Operation Range
-20°C
-5°C
COOLING MODE
Outdoor Temperature
HEATING MODE
Outdoor Temperature 27°C
52°C
-20 -10 0 10 20 30 40 50 60
Outdoor temp. °C ( D.B )
Extra High Static Pressure – Max. 40Pa and Air Volume Increased by 10%
- Standard 0-20Pa function is equipped by default.
- High-static pressure propeller and optimized fan guard
can adapt to various installation environments.
- Carrier now offers up to 40 Pa external static pressure units
for customized applications.
* You need to consult Carrier sales team if you require
over 40Pa external static pressure.
40 Pa
Long Piping Length & Long Height Difference for Large Projects
The first indoor unit branch
Piping Installation Data
Actual Total Piping Length
Permitted value ( m )
1000 m *
Piping
Length
Actual longest piping length
Equivalent longest piping length
Height
Difference
Equivalent piping length from the farthest indoor unit to the first indoor unit branch
Height difference between outdoor unit and indoor unit
Outdoor Unit Up
Outdoor Unit Down
Height difference between indoor units
* Total pipe length is equal to two times pipe length plus pipe length.
* When the piping length from the farthest IDU to the first indoor branch joint is more than 40m,
It needs to meet the specific conditions according to the installation manual to achieve 90m.
175 m
200 m
40 m / 90 m *
70 m
110 m
30 m
21
22
VRF FULL DC INVERTER
VRF FULL DC INVERTER
High Efficiency
High Cooling EER / High Heating COP Values
VRF Full DC Inverter Outdoor Units series with all high efficiency DC Inverter scroll compressors, all high efficiency DC motor (s) and high efficiency outdoor coil, achieve the world’s top class Cooling Energy Efficiency Ratio ( EER ) and Heating Coefficient Of
Performance ( COP ).
Cooling EER
4.29
3.97 3.81
3.54 3.50 3.45
8 HP 10 HP 12 HP 14 HP 16 HP 18 HP
Heating COP
4.39 4.17 4.17 4.02 3.91 3.89
8 HP 10 HP 12 HP 14 HP 16 HP 18 HP
High Efficiency VRF Full DC Inverter Outdoor Unit
High Efficiency
Fan Housing & Outlet Grille
High Efficiency Outdoor Fan (s)
High Efficiency DC Fan Motor (s)
ODU
Size
8 HP
10 HP
12 HP
14 HP
16 HP
18 HP
DC Fan Motor
Qty.
1
1
2
2
2
2
High Efficiency
180° Sine-Wave DC Inverter
Control For Compressor Motor
High Efficiency Outdoor Coil
Precoated
Aluminum
Fins
Inner
Groove
Copper Tubes
12°C
Subcooling
High Efficiency
DC Inverter Scroll Compressor (s)
ODU
Size
8 HP
10 HP
12 HP
14 HP
16 HP
18 HP
Compressor
Qty.
1
1
1 + 1
1 + 1
1 + 1
1 + 1
23
VRF FULL DC INVERTER
VRF FULL DC INVERTER
High Efficiency
High Efficiency DC Inverter Scroll Compressor Technology
All compressor(s) are DC Inverter compressor type
8HP and 10HP outdoor units are equipped with one DC inverter scroll compressor
12, 14, 16, 18 HP outdoor units are equipped with two DC inverter scroll compressors
Suction Pipe
Discharge
Pipe
Oil even
Pipe
New structure enhances, mid frequency performance
Specially designed scroll profile for R410A
More compact, weight reduced by 50%
High IPLV
Advanced permanent magnet DC motor provide high torque and efficiencyand achieve 70% reduction in volume.
Wide operation range from 20Hz to 200Hz.
DC Inverter
Scroll Compressor
Compressor efficiency New DC motor-centralized winding
Common DC motor-distributing winding
Centralizing winding
Distributing winding
20 40 60 80 100
Rotor speed (s-1)
High Efficiency Smooth 180° Sine Wave DC Inverter Control
180° Sine Wave Inverter Control smoothes the rotation of the compressor motor, and improves compressor efficiency sharply than traditional sawtooth wave.
24 Common sawtooth wave 180° Sine Wave DC inverter
High Efficiency DC Fan Motor Technology
All outdoor fan motor(s) are DC motor type
8HP and 10HP outdoor units are equipped with one DC fan motor
12, 14, 16, 18 HP outdoor units are equipped with two DC fan motors
According to the running load and system pressure, the system speed control adjusts the
speed of DC fan motor to achieve the minimum power consumption and maximum efficiency.
DC fan motor
1000
800
600
400
200
DC inverter stepless adjustment
AC inverter multistep adjustment
System pressure
High Efficiency Outdoor Fan (s)
Optimum design of 3-dimensional turbo fan with patent aerodynamic new profile design of fan blades with sharp edge and little curve bigger diameter for maximum efficiency with maximum airflow.
Common design Carrier design
High Efficiency Fan Housing and Outlet Grille
Optimum design of fan housing and outlet grille for maximum airflow.
Efficient Air Management System (AMS) with uniform air circulation
over the complete coil surface at low velocity for maximum airflow
with minimum turbulence for minimum air resistance, smooth airflow
and efficient operation.
25
VRF FULL DC INVERTER
26
VRF FULL DC INVERTER
High Efficiency
High Efficiency Outdoor Coil Technology
High efficiency outdoor coil with large heat transfer surface, optimum coil circuiting design and efficient subcooling for maximum heat transfer, minimum electrical consumption and maximum efficiency.
Carrier design Common design
Windage & air flow
0.8
0.6
0.4
0.2
0
0
Reduce
28%
Common design
Carrier design
200 400 600 800 1000 Re
Frost contrast
High efficiency inner-threaded pipe, enhance heat transfer.
Hydrophilic film fins + inner-threaded pipes
0.8
0.6
0.4
0.2
0
0
Common design
0.2
0.4
Reduce
30%
Carrier design
0.6
0.8
Relative frosting rate
New patent design of window fins which enlarge the heat-transfer area , decrease the
air resistance, save more power and enhance heat transfer performance in cooling and
heating.
Hydrophilic aluminum fins and inner-groove copper tubes optimize heat transfer
efficiency.
Common Design
Gas Liquid
Carrier Design
Gas
Gas Gas Gas-Liquid Liquid
Liquid
Liquid
43 o C
75 o C
Common
Design
Increase the hot liquid rate in the condenser
Improve the heat-exchange efficiency
The outdoor coil can reach up to 12 o C subcooling,
reduces the system resistance and improves system efficiency and reliability.
37.1
o C
75 o C
Carrier
Sub-cooling
Technology
When the outdoor temperature is 35 o C, the refrigerant can be cooled down to 37.1
o C,
thus achieving high heat-transfer efficiency with only 2.1
o C temperature difference.
Multi solenoid valves control technology
Multi solenoid valves control technology in one system.
All the solenoid valves of the outdoor unit ensure precise temperature-control, steady and economic system running and economic to provide a comfortable environment.
Double EXV control technology
Each EXV, in the outdoor unit, achieves 480 pulse :
(1) to adjust refrigerant flow precisely.
(2) to ensure precise and steady temperature-control
to provide a comfortable environment.
High Pressure Sensor
Controls the discharge pressure of the compressor and to control the fan speed.
Always test the system pressure Every 20 seconds, compare the system pressure and the best pressure to adjust DC fan motor speed timely.
27
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Super Quiet
Super Quiet VRF Full DC Inverter Outdoor Unit
Super Quiet
Fan Housing & Outlet Grille
Super Quiet Outdoor Fan (s)
Super Quiet DC Fan Motor (s)
ODU
Size
8 HP
10 HP
12 HP
14 HP
16 HP
18 HP
DC Fan Motor
Qty.
1
1
2
2
2
2
Super Quiet
180° Sine-Wave DC Inverter
Control For Compressor Motor
28
Super Quiet
DC Inverter Scroll Compressor (s)
ODU
Size
8 HP
10 HP
12 HP
14 HP
16 HP
18 HP
Compressor
Qty.
1
1
1 + 1
1 + 1
1 + 1
1 + 1
Super Quiet DC Inverter Scroll Compressor Technology
Rubber isolators for compressor to absorb vibrations
at starting and running.
Optimum design of compressor suction and discharge tubing
to absorb vibrations and discharge gas pulsations.
DC Inverter
Scroll Compressor
Super Quiet DC Fan Motor Technology
Totally enclosed motor running with low speeds and minimum vibrations.
DC fan motor
Super Quiet Outdoor Fan (s)
Optimum design of 3-dimensional turbo fan with patent aerodynamic new profile design of fan blades with sharp edge and little curve bigger diameter for minimum airflow resistance, minimum sound and minimum vibrations.
Common design Carrier design
Super Quiet Fan Housing and Outlet Grille
Optimum design of fan housing and outlet grille for minimum airflow
resistance, minimum sound level and minimum vibrations.
Efficient Air Management System (AMS) with uniform air circulation
over the complete coil surface at low velocity for minimum sound level.
New Patent Fan Arrangement Technology for Sound Reduction
ODU
Capacity
Fan Qty.
8 / 10 HP
1
12 / 14 / 16 / 18 HP
1 + 1
Blades Qty.
3 3 + 4
29
30
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Enhanced Comfort
Smart Comfort Technology
For Quick Warm-up & Cool-down Design and Less Temperature Fluctuation
By utilizing the benefits of DC inverter compressor, the system can reach full load quickly and shorten the warm-up and cool-down times to provide an immediate and comfortable air solution.
Less temperature fluctuation will create a better living environment.
Temp
Time
1
2
Cooling operation
Inverter
Non-Inverter
Fluctuation of Room Temperature
Smart Soft Start Technology
Soft start function of VRF DC inverter compressor reduces strike to the electric network.
This kind of high-performance and low sound scroll compressor operates at a faster rate when starting, reducing start-up time. It helps the unitVRF system to bring the room temperature up to the set level quickly.
Starting current
( % )
600
500
400
300
200
100
1 2
Direct start
Y - โ Start
Start by Inverter
Comparison of start by inverter and by traditional methods
3 4 5 6
( Sec )
Smart Night Super Silent Operation Technology
Smart Night Super Silent Mode is easily set at site on the main board of the outdoor unit.
Smart Night Super Silent Mode has the following functions :
(1) Controls peak daytime operation ( X hours ) and non peak night time operation
( Y hours ) as per any one of the following modes :
Mode 1
Mode 2
Mode 3
Mode 4
X : 6 hours
X : 8 hours
X : 6 hours
X : 8 hours
,
,
,
,
Y : 10 hours
Y : 10 hours
Y : 12 hours
Y : 8 hours
Smart Night Super Silent Mode is activated X hours after peak day time operation
and it goes back to normal operation after Y hours of non peak night operation.
(2) Reduces sound level to minimum of 45 dB(A)
Peak value of ambient temp.
100
50
Sound
08:00 14:00 22:00 08:00
Mode 1→ X : 6 hours, Y : 10 hours
Smart Defrosting Technology - This function can be activated by setting at site.
- Temperature (load) curve shown in the graph is just an example.
Smart defrosting program has the following functions :
(1) Controls the defrosting time according the system real temperature.
(2) Reduces the heating loss by unnecessary defrosting and the indoor unit more comfortable.
(3) Shortens the defrosting time to 4 minutes due to the specialized defrosting valve.
Smart Defrosting
Usual Defrosting t min.
โt
Time 31
VRF FULL DC INVERTER
VRF FULL DC INVERTER
High Reliability
Smart Duty Cycling Function
In one combination of modular outdoor units, any outdoor unit can run as the master outdoor unit to equalize the service life of all outdoor units
Master
Outdoor unit
Slave (1)
Outdoor unit
Slave (2)
Outdoor unit
No. 1
No. 3
No. 2
No. 2
No. 1
No. 3
No. 3
No. 2
No. 1
INV INV INV INV INV INV
Smart Back-up Function
In one combination of modular outdoor units, when the master outdoor unit failed, any single slave outdoor unit can be set as the master unit, then the remaining outdoor units can keep on working. This can be set at field by DIP switch located on the main board of electrical control box of outdoor unit.
Master
Outdoor unit
Slave (1)
Outdoor unit
Slave (2)
Outdoor unit
32
INV INV INV INV
When the slave (1) outdoor unit failed and came into standby state, the left module still work.
INV INV
Smart & Presize 5 Stage Oil Control Technology
Smart & Presize 5 stage oil control technology ensures continuous safe oil level for every outdoor unit and every compressor to avoid compressor oil lack problem.
1st stage : Compressor internal oil separator
2nd stage : High efficiency oil separator (separation efficiency up to 99%)
3rd stage : Oil balance technology between compressors
4th stage : Oil balance technology between outdoor units modules
5th stage : Smart system oil return program
2nd stage 4th stage
1st stage
5th stage
3rd stage
Indoor Unit Quantity Monitoring
The quantity of indoor units should be exactly set on the outdoor main board, once some indoor units miscommunication with outdoor units during system running, the outdoor units will stop and display the fault code “H7”. This can prevent compressor from liquid hammer caused by dropped indoor units with EXV unclosed.
ENC3 S12
ON
Quantity setting switch
33
34
VRF FULL DC INVERTER
VRF FULL DC INVERTER
High Durability
Standard coated aluminum fins of outdoor
coil for coastal applications to protect
against corrosion.
Anti-rust, weather proof and long life outdoor unit sheet metal parts
made of chemically treated and zinc coated ( galvanized ) sheet metal.
Powder painted casing of outdoor unit with prefect adhesion of
highly resistant ployester paint 60-80 microns thick, which is
electro-statically applied and baked at a temperature of 220°C.
Easy Installation, Service and Maintenance
Compact Design for Effective Use of Space
Compact size and light weight design minimizes the installation footprint, reduces the installation floor load, and is easier for transportation.
For some projects the units can even be transported through the elevator or forklift, reduce access problem at the jobsite and reduce time and labor.
Easy Refrigerant Connections between Outdoor Units in One Combination
Two Modular Outdoor Units
Combination
W2 ( master )
W1 ( slave )
Liquid Line
VRF
INVERTER
Notes :
(1) Arrange modular outdoor units in a sequence
of Max HP to Min. HP i.e W2>W1
(2) The master outdoor unit W2 is the
maximum HP outdoor unit.
Gas Line
Oil Balance Line
VRF
INVERTER
Three Modular Outdoor Units
Combination
W3 ( master )
W2 ( slave )
W1 ( slave )
Liquid Line
VRF
INVERTER
VRF
INVERTER
VRF
INVERTER
Gas Line
Notes :
Oil Balance Line
(1) Arrange modular outdoor units in a sequence of Max HP to Min. HP i.e W3>W2>W1
(2) The master outdoor unit W3 is the maximum HP outdoor unit.
Four Modular Outdoor Units
Combination
W4 ( master )
W3 ( slave )
Liquid Line W2 ( slave )
VRF
INVERTER
W1 ( slave )
VRF
INVERTER
VRF
INVERTER
Gas Line
VRF
INVERTER
Notes :
Oil Balance Line
(1) Arrange modular outdoor units in a sequence of Max HP to Min. HP i.e W4>W3>W2>W1
(2) The master outdoor unit W4 is the maximum HP outdoor unit.
35
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Easy Installation, Service and Maintenance
Simple Signal Line Connection
Central control can be connected from indoor side or outdoor side ( X, Y, E terminal )
as you wish ( Reversible communication ).
Only one group of communication wires ( P, Q, E ) can connect outdoor unit,
indoor units and network
P Q E X Y E
X Y E
P Q E P Q E P Q E P Q E
Wireless controller can query and modify each indoor unit’s address.
36
Smart System Operation Parameters Checking For Start-Up & Commissioning
The reserved checking window on the electric control box of outdoor unit is used for easy checking of VRF system operation parameters status for start-up and commissioning.
4 bits digital tube
LED display
Smart Self Diagnostic Function For System Malfunctions Detection
The reserved checking window on the electrical control box of outdoor unit is also used for easy checking of error codes of
VRF system malfunctions.
4 bits digital tube
LED display
Auto Addressing of Indoor Units
Through Wireless Remote Control
Auto addressing of indoor units is done just by pressing button of
wireless remote control.
Wireless remote control and wired control can enquire and modify every
indoor unit address.
Through Outdoor Unit
Outdoor unit can automatically distribute the addresses to indoor units.
37
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Easy Installation, Service and Maintenance
Rotating Electric Control Box For 18 HP Outdoor Unit
The electronic control box can rotate in a wide angle to facilitate service and maintenance of pipeline system by reducing the disassembly time of the electrical control box.
W ide
Ro tatin g Angle
Rotating electrical control box
Outer layout compressor and simple pipe system
Easy Accessibility To Compressors & Valves
Compressors are located near the door, which simplifies checks and enables valves or compressors parts to be replaced easily.
38
Convenient electronic control check window. Can directly observe the operation status from the LED display, and directly press the FORCE
COOLING / CHECK button.
Integrated Solution for Control and Management
Carrier Intelligent Manager of designed specifically to control VRF systems, is based around a centralized format and dedicated to the complete control and monitoring of all the system’s functions. It can be used as a flexible multi-purpose system and applied to a variety of needs, according to the scale, purpose and control method of each building.
IMM
Software Login Interface Main Interface
Internet WLAN
Laptop
IP / Ethernet
PC
IMM Software
Fire Wall
PC
MAX : 4
IMM Software
M-INTERFACE
LAN
K1 K2 E
M-net
X Y E
MAX : 4
Outdoor Unit
39
VRF FULL DC INVERTER
VRF FULL DC INVERTER
Variety of Accessories
Branch Joints For Outdoor Unit
Description Appearance Branch Model Packing Size (mm) / Gross Weight (kg)
Two Modular
Outdoor Units
Combination
BJC-02-CM(i) 255 × 150 × 185 / 1.5
Three Modular
Outdoor Units
Combination
BJC-03-CM(i) 345 × 160 × 285 / 3.4
40
Four Modular
Outdoor Units
Combination
BJC-04-CM(i) 475 × 165 × 300 / 4.8
Detailed Dimensions of Branch Joints For Outdoor Unit
Branch model Gas side joints
BJC-02-CM(i)
0D:31.8
0D:31.8
ID:25.4
ID:25.4
Q2 Q2
ID:31.8
ID:31.8
ID:34.9
ID:34.9
0D:34.9
Q1
ID:31.8
ID:31.8
ID:25.4
ID:25.4
Q1
ID:31.8
ID:31.8
0D:31.8
0D:31.8
Q4 Q4 Q3 Q3
ID:38.1
ID:38.1
ID:34.9
ID:34.9
Liquid side joints
0D:15.9
0D:15.9
ID:12.7
ID:12.7
ID:15.9
ID:15.9
ID:19.1
ID:19.1
0D:19.1
Y2 Y2
Y6 Y6 Y3 Y3
ID:22.2
ID:22.2
Y1
ID:15.9
ID:15.9
Y1
ID:15.9
ID:15.9
0D:15.9
0D:15.9
ID:12.7
ID:12.7
ID:19.1
ID:19.1
Q2 Q2
Q1 Q1
Q7 Q7
Y2 Y2
Y1 Y1
Y6 Y6
BJC-03-CM(i)
Q5 Q5
Y7 Y7 Y4 Y4
Q1 Q1
Y1 Y1
BJC-04-CM(i)
41
www.miraco.com.eg
January 2016
Carrier is committed For continuous improvement of energy saving green products according to national and international standards to ensure the highest quality and reliability standards, and to meet market regulations and requirements.
All specifications subject to change without prior notice according to Carrier policy of continuous development.
advertisement
Key Features
- Modular outdoor units
- Wide stable operation range
- High efficiency
- Super quiet
- Enhanced comfort
- High reliability
- High durability
- Easy installation, service and maintenance
- Variety of accessories
- Variety of control options