Crystal Plus Owner Manual English
Miraco
MISR REFRIGERATION & AIR CONDITIONING MFG. CO.
R22
220-240V ~ 50Hz 1Ph
PLUS
High Wall Split Air Conditioners
53KHFT 12-18-24 Cool Only
53QHFT 12-18-24 Heat Pump
O W NER’S M ANUAL
Carrier is committed to continuously improving its products according to national and international standards
to ensure the highest quality and reliability standards, and to meet market regulations and requirements.
All specifications subject to change without prior notice according to Carrier policy of continuous development.
03504165
Quality
Management System
Enviromental
Management System
Safety
Management System
ISO 9001 : 2008
ISO 14001 : 2004
BS OHSAS 18001 : 2007
Certificate No.: QS-5519HH
Certificate No : 12 104 30334 TMS
Certificate No : 12 116 30334 TMS
Rev. (0) - 2015
Miraco
MISR REFRIGERATION & AIR CONDITIONING MFG. CO.
R22
220V ~ 50Hz 1Ph
COOL EER
HEAT COP
PLUS
High Wall Split Systems
12K - 18K - 24K
Formaldehyde
Filter
IAQ
LE
Tropical
Compressor
Super
Quiet
Auto
Fan Speed
Timer
Functions
Easy Flexible
Installation
Efficient
AMS
Smart LCD
Wireless Control
Auto
Mode
Auto Restart
Function
Easy Fast Service
& Maintenance
Self Clean
Function
Efficient
Fans
Smart
Airflow
Independent Dehumidification
3
3 Minutes
Min. Time Delay
Fashion
Design
Efficient
Coils
Vertical Air flow
Auto Swing
Turbo
Function
Anti
Freezing
LCD
Display
Inner Groove
Copper Tubing
Horizontal Air flow
Manual Direction
Follow Me
Function
Self diagnostic
function
Efficient
Operation
Hydrophilic
Aluminum Fins
Louver Position
Memory Function
ECO
Function
Refrigerant
Leak Detection
Efficient
Anti-dust Filters
AMS
Auto
Anti-Freezing
Protection
Cleanable
Front Panel
Washable
Air Filter
PLUS
High Wall Split Systems
Wireless Remote Control
Control Buttons
DISPLAY OF SELECTED FUNCTIONS
1
MODE selection button
AUTO - COOL - DRY - HEAT - FAN
2
Decrease temperature button
Each time you press the button,
the temperature decreased by 1°C
3
Increase temperature button
Each time you press the button,
the temperature increased by 1°C
4
FAN selection button
High - Medium - Low - Auto fan speed
5
ON/OFF button
6
Vertical Air Flow Auto Swing
7
Horizontal Air Flow Auto Swing
8
ECO function button
9
TIMER ON function button
10
TIMER OFF function button
*
2
5
1
6
3
7
11
12
10
14
13
Self Clean function button
11
Fresh air function button
*
12
Follow Me function button
13
LED Display function button
14
TURBO function button
Note : * This function does not work with this product
but works with other products
4
8
9
PLUS
High Wall Split Systems
Wireless Remote Control
1
Signal transmission indicator
2
Operation MODE indicator
AUTO
COOL
DRY
HEAT
FAN
Display Of Remote Control
㪈
AUTO
Automatic
Cooling and dehumidification
Dehumidification only
㪉
SET TEMP.
FAN
COOL
HIGH
DRY
MED
HEAT
TIMER ON OFF
㪊
㪉
㪌
LOW
Heating
Ventilation (fan only)
3
ON / OFF indicator
4
SET TEMP. indicator
5
FAN SPEED indicator
HIGH
FAN SPEED indicator HIGH
MED
FAN SPEED indicator MED
LOW
FAN SPEED indicator LOW
㪋
㪍㪎 㪏
FAN SPEED indicator AUTO
6
TIMER ON function indicator
7
TIMER OFF function indicator
8
FOLLOW ME function indicator
Display Panel Of Indoor Unit
SET TEMP. indicator /
Error code in indicator
OPERATION indicator
TIMER function indicator
Cold Draft or Defrost indicator
( only with Heat Pump System )
Cool Only
Heat Pump
Thank you for selecting Carrier
Air Conditioner
Carrier
Split
is
the
optimum
air
conditioning
solution for places which require high wall installation, elegant
appearance and ultimate comfort combined with efficient, quiet
operation, optimum air distribution, and efficient Indoor Air
Quality (IAQ).
CONTENTS
PAGE NO.
1. GENERAL INFORMATION
1
2. SYSTEM SAFETY PROTECTIONS
2
3. TIPS OF ENERGY SAVING AND OPTIMUM COMFORT
3
4. SPLIT SYSTEM DESCRIPTION
5
5. CONSIDERATIONS FOR REMOTE CONTROL
6
6. EMERGENCY BUTTON
9
7. USE OF REMOTE CONTROL
10
8. AIR FILTERS CLEANING
25
9. INDOOR UNIT CLEANING
26
10. PERIODICAL CHECKS
27
11.
28
CONSIDERATIONS BEFORE A LONG SHUTDOWN PERIOD OF AIR CONDITIONER
12. OPERATION TIPS
29
13. TROUBLE SHOOTING TIPS
30
1. GENERAL INFORMATION
PRECAUTIONS
Installing and servicing of air conditioning equipment can be hazardous due to system
pressure and electrical components. Only trained and qualified service personnel should
install or service this equipment.
Untrained personnel can perform basic maintenance function such as cleaning coil and
filters. Trained service personnel should perform all other operations.
When working on air conditioning equipment, observe precautions in the literature, tags
and labels attached to the unit.
WARNINGS
•
The operating voltage of electrical power supply should be within the voltage mentioned on unit
nameplate data.
•
The capacity of electrical kWh counter should be larger than the operating currents required for
air conditioner(s) and any other electrical domestic appliances in use simultaneously from the
same supply.
•
The installation of electrical distribution box after the electrical KWH counter is necessary to
properly distribute the electrical loads. The electrical distribution box should be equipped with
circuit breakers according to the electrical loads. For each installed air conditioner, a separate
circuit breaker with its own overload should be installed on the electrical distribution box.
•
The installation of two-pole automatic circuit breaker is necessary to operate the air conditioner.
The circuit breaker must be installed to be far away from any flammable materials (curtains…etc.).
The circuit breaker size must be suitable for air conditioner.
•
Disconnect the electrical mains supply prior to any maintenance operations or prior to handling
any internal unit parts.
•
The manufacturer declines any liability for damage resulting from modifications or errors in the
electrical or refrigerant connections, made during the installation, or from the improper use of this
equipment. This will void the unit warranty immediately.
•
Failure to observe electrical safety codes may cause a fire hazard in case of short circuits.
•
This system will only work safety and correctly, if installed and tested by qualified personnel.
•
Do not open the electronic remote controller to avoid possible damage. In case of malfunction
contact a qualified service engineer.
•
The unit contains rotating equipment (fan). Ensure that this is out of reach for children.
•
Be conscious of the room temperature and general comfort, particularly when this is used near
children, senior or handicapped people.
•
For correct use, the air conditioner must operate within the temperature limits indicated in the
table “Operating Limits” included in the installation manual. Incorrect use of the system outside
these limits may cause malfunction and dripping water.
•
Controller batteries contain polluting elements. When exhausted, they must be disposed of in
accordance with local requirements.
•
Do not switch off the split system by disconnecting the electric power supply.
The system must always be switched off using the remote control.
(1 )
2. SYSTEM SAFETY PROTECTIONS
The air conditioner is equipped with complete safety protections to ensure safe
operation of air conditioner at different operating conditions :
2.1 Safety protections for Cool Only System
Auto Restart Feature with backup memory.
When the power failure is happened during the air conditioner operation, the microprocessor
of printed circuit board will memorize the operation setting. After the power is recovered, the
air conditioner operates automatically ( without remote control after elapse of compressor
time delay ), according to the previous operation settings.
3 (Three) minutes time delay between compressor turning off and turning on for compressor
protection against cycling.
Anti-freezing protection of indoor coil when the system is operating in cool mode with
excessive dirt on the indoor coil and / or clogged air filters and when the air conditioner is
operating in cool mode at low ambient temperature.
Smart self-diagnostic function for malfunctions detection for fast easy service and
maintenance.
Smart refrigerant leak detection by sensitive sensors mounted on the indoor and outdoor
coils for fast easy service and maintenance.
2.2 Safety protections for Heat Pump System
Auto Restart Feature with backup memory.
When the power failure is happened during the air conditioner operation, the microprocessor
of printed circuit board will memorize the operation setting. After the power is recovered, the
air conditioner operates automatically ( without remote control after elapse of compressor
time delay ), according to the previous operation settings.
3 (Three) minutes time delay between compressor turning off and turning on for compressor
protection against cycling.
Anti-freezing protection of indoor coil when the system is operating in cool mode with
excessive dirt on the indoor coil and / or clogged air filters and when the air conditioner is
operating in cool mode at low ambient temperature.
High temperature protection of outdoor coil when the air conditioner is operating in cool
mode.
Cold draft protection when the system is operating in heat mode.
When starting heat mode, the fan speed is regulated automatically from the lowest grade to
the preset level, according to the temperature rise of indoor coil. This function can prevent
cold air blowing out at the beginning of heat modem which avoids the discomfort to the
user.
High temperature protection of indoor coil when the air conditioner is operating in heat
mode.
Defrost protection of outdoor coil when the air conditioner is operating in heat mode
at very low ambient temperature.
Smart self-diagnostic function for malfunctions detection for fast easy service and
maintenance.
Smart refrigerant leak detection by sensitive sensors mounted on the indoor and outdoor
coils for fast easy service and maintenance.
(2 )
3. TIPS OF ENERGY SAVING AND OPTIMUM COMFORT
In Summer
•
Keep room temperature to comfort
levels.
• Don’t remain in direct contact
with cold air for a long period.
This is harmful to health.
• Don’t wait until it is too hot.
Turn the air conditioner for cooling
before that.
• Don’t exaggerate on the temperature
intensity, too cold.
Extreme temperatures are harmful to
your health and waste energy.
In Winter
•
•
•
•
Keep room temperature to comfort
levels.
Don’t remain in direct contact
with warm air for a long period.
This is harmful to health.
Don’t wait until it is too cold.
Turn the air conditioner for heating
before that.
Don’t exaggerate on the temperature
intensity, too hot.
Extreme temperatures are harmful to
your health and waste energy.
COOL mode
Keep doors, windows and any other
openings closed to prevent the
conditioned air from escaping and to
prevent un conditioned air from entering
the space to be air conditioned.
When in cooling, avoid direct sun in the
room to be air-conditioned, if possible
shut curtains or shades.
Keep doors, furniture or any other
obstructions away from blocking return
air and / or supply air of the indoor unit to
assure maximum efficiency and adequate
air circulation.
(3 )
HEAT mode
TIPS OF ENERGY SAVING AND OPTIMUM COMFORT (Cont.)
Use ECO function during sleep for
energy saving, comfortable and healthy
sleep during COOL mode or HEAT mode.
COOL mode
With ECO function
HEAT mode
With ECO function
Ensure a uniform air circulation in the
room to be air conditioned
(1) by using Swing ↕ function on the
remote control.
Deflector rod
For vertical Louver
(2) by manual adjustment of vertical
supply air louvers to right or left as
per the requirement.
Clean periodically air filters of indoor unit
every month to assure adequate air
Air Filters
circulation and maximum cooling and
heating efficiency.
Periodic service and maintenance of the
air conditioner or upon customer request
through Carrier or Carrier authorized
dealer to assure maximum cooling and
heating efficiency.
(4 )
4. SPLIT SYSTEM DESCRIPTION
High Wall Split Systems 12K – 18K – 24K
2
Indoor Unit Return Air
Outdoor Unit
8
7
3
1
9
11
4
Supply Air
10
1: Panel frame & Front panel
2: Chassis
3: Horizontal supply air louver
4: Vertical supply air louvers
5: Air filters
6: Manual control button
7: Power cord
8: Inter-connecting refrigerant piping and electrical cables between
indoor and outdoor units.
9: Drain hose
10: Wireless remote controller
11: Plastic holder of remote control
(5 )
5
6
5. CONSIDERATIONS FOR REMOTE CONTROL
5-1 HOW TO INSERT BATTERIES :
(a) Remove the cover of battery compartment at the
back of the remote control by pressing the tab
toward outside, in the direction of the arrow.
(b) Mount two batteries size AAA 1.5 Volt supplied with the
remote control.
Then close the cover of the battery component.
Note:
During mounting of batteries check battery symbols (+, -)
indicated in batteries compartment.
NOTES
1. The remote control uses two alkaline batteries (1.5 Volts) .
2. Do not use old batteries or batteries of different types, as this may cause the remote control to malfunction.
3. If you do not use the remote control for more than a few weeks, please remove the batteries.
Other wise battery leakage may damage the remote control.
4. The average battery life during normal use is approximately half a year.
5. Replace the batteries when there is no receiving beep coming from the indoor unit or transmission
indicator on the remote control fails to light.
6. Batteries should only be replaced after turning OFF the air conditioner.
5-2 INSTRUCTIONS OF USING WIRELESS REMOTE CONTROL
1- The remote control must be directed toward the receiver of indoor unit when pressing the buttons
of the desired functions. An acoustical acknowledgement sound (beep) will indicate that signal has
been received.
2- Avoid direct sunlight on the receiver of indoor unit, which may interfere with good signal reception
and the air conditioner may not work properly. Draw the curtains to avoid direct sunlight.
3- Avoid obstacles obstructions such as curtains, doors or other materials between the remote control
and the receiver of indoor unit to avoid blocking the signals from the remote control to the indoor unit.
4- The maximum operating distance for the remote control is approximately 8 meters.
5- Keep the remote control away from water. Do not let the remote control fall down.
6- Never use objects with sharp point to press the button on the remote control.
7- Prevent any liquid from falling into the remote control.
8- If other electric applications react to the remote control, move these applications.
8 meter
(6 )
CONSIDERATIONS FOR REMOTE CONTROL (Cont.)
5-3 Instruction for Remote Control
5-3-1 Cool Only or Heat Pump
ƒ
When you press Mode button and Fan button as the
same time more than 2 seconds, then the remote
covert to operate without Heat model to work with
indoor unit cool only.
5-3-2 Control function which do not work
with this product
( A ) Horizontal Air Flow Auto Swing
( B ) Fresh Function
(7 )
CONSIDERATIONS FOR REMOTE CONTROL (Cont.)
5-4 MOUNTING PLASTIC HOLDER OF REMOTE CONTROL
•
Fix the plastic holder of the remote control on the wall by using screws.
Screw
Plastic holder
(8 )
6. EMERGENCY FUNCTION
EMERGENCY FUNCTION
Emergency function can be used temporarily in case you cannot find the remote control or its batteries
are exhausted.
To perform Emergency function, follow below steps :
1. Open and lift the front panel up to an angle until
it remains fixed with a clicking sound.
2. Press manual control button ( AUTO / COOL )
until AUTO led illuminates on the display panel of
the indoor unit.
then the unit will work in forced AUTO mode
(the default setting temperature is 24°C).
Front panel
3. Close the panel firmly to its original position.
CAUTION
• Once you press the manual control button
( AUTO / COOL ), the operation mode is shifted
in an order as : AUTO → Forced COOL → OFF
• Push the manual control button to operate in forced
COOL mode, this is used for testing purposes only.
You had better not choose it.
• The Forced COOL mode is used only for testing
purposes by the installer and serviceman.
• To restore the remote control operation, use the remote
controller directly.
(9 )
7. USE OF REMOTE CONTROL
COOL MODE
START
1. Press " Mode " button to select COOL mode
on the remote control display.
2. Press " TEMP " buttons
or
to select the
desired set temperature on the remote control
display.
For Egyptian Market :
Set desired temp. between 20°C and 28°C.
For Export Markets :
Set desired temp. between 17°C and 30°C.
3. Press " Fan " button to select the desired
fan speed on the remote control display.
2
2
1
4
3
4. Press " On/Off " button to start
the air conditioner.
appears on the
ON symbol
remote control display.
OPERATION indicator
will illuminate
on the display panel of indoor unit.
COOL mode starts after approximately 3 minutes
STOP
If you want to stop the air conditioner,
Press " On/Off " button again.
NOTES
• If the room temperature is higher than
the selected temperature, the system will start COOL mode.
• If the room temperature is equal to or less than
the selected temperature, the system will stop COOL mode.
• If you use AUTO fan speed with COOL mode, the fan speed changes automatically
to low or medium or high speed based on the temperature difference between
setting temperature and room temperature.
(10 )
USE OF REMOTE CONTROL (Cont.)
HEAT MODE
START
1. Press " Mode " button to select HEAT mode
on the remote control display.
2. Press " TEMP " buttons
or
to select the
desired set temperature on the remote control
display.
For Egyptian Market :
Set desired temp. between 20°C and 28°C.
For Export Markets :
Set desired temp. between 17°C and 30°C.
3. Press " Fan " button to select the desired
fan speed on the remote control display.
4. Press " On/Off " button to start
the air conditioner.
2
2
1
4
3
ON symbol
appears on the
remote control display.
OPERATION indicator
will illuminate
on the display panel of indoor unit.
HEAT mode starts after approximately 3 minutes.
STOP
If you want to stop the air conditioner,
Press " On/Off " button again.
NOTES
• If the room temperature is lower than
the selected temperature, the system will start HEAT mode.
• If the room temperature is equal to or higher than
the selected temperature, the system will stop HEAT mode.
• If you use AUTO fan speed with HEAT mode, the fan speed changes automatically
to low or medium or high speed based on the temperature difference between
setting temperature and room temperature.
(11 )
USE OF REMOTE CONTROL (Cont.)
AUTO MODE
START
1. Press " Mode " button to select AUTO mode
on the remote control display.
2. Press " TEMP " buttons
or
to select
desired the set temperature on the remote control
display.
For Egyptian Market :
Set desired temp. between 20°C and 28°C.
For Export Markets :
Set desired temp. between 17°C and 30°C.
3. Press " On/Off " button to start
the air conditioner.
2
1
3
ON symbol
appears on the
remote control display.
OPERATION indicator
will illuminate
on the display panel of indoor unit.
AUTO mode starts after approximately 3 minutes.
STOP
If you want to stop the air conditioner,
Press " On/Off " button again.
NOTES
1. For Cool Only System
When Auto mode is activated, the air conditioner changes the operation mode automatically to
cool or fan only mode and also changes fan speed to auto speed by sensing the temperature
difference between room temperature and set temperature.
2. For Heat Pump System
When Auto mode is activated, the air conditioner changes the operation mode automatically to
cool or heat or fan only mode and also changes fan speed to auto speed by sensing the
temperature difference between room temperature and set temperature.
3. In the Auto mode, you cannot switch the fan speed. It has already been automatically controlled.
4. If the Auto mode is not comfortable for you, the desired mode can be selected manually.
(12 )
2
USE OF REMOTE CONTROL (Cont.)
DRY MODE
START
1. Press " Mode " button to select DRY mode
on the remote control display.
2. Press " TEMP " buttons
or
to select
desired the set temperature on the remote control
display.
For Egyptian Market :
Set desired temp. between 20°C and 28°C.
For Export Markets :
Set desired temp. between 17°C and 30°C.
2
1
3
3. Press " On/Off " button to start
the air conditioner.
ON symbol
appears on the
remote control display.
OPERATION indicator
will illuminate
on the display panel of indoor unit.
DRY mode starts after approximately 3 minutes.
STOP
If you want to stop the air conditioner,
Press ON/OFF button again.
NOTES
• In DRY mode, you can not switch the indoor fan speed.
The indoor fan speed will be automatically controlled.
• The DRY mode will automatically select the drying operation based on the
difference between the set temperature and the actual room temperature.
• The temperature is regulated while dehumidifying by repeating turning on
and off of the cooling operation or fan only.
(13 )
2
USE OF REMOTE CONTROL (Cont.)
FAN ONLY MODE
START
1. Press " Mode " button to select FAN mode
on the remote control display.
2. Press " Fan " button to select the desired
fan speed on the remote control display.
3. Press " On/Off " button to start
the air conditioner.
appears on the
ON symbol
remote control display.
OPERATION indicator
will illuminate
on the display panel of indoor unit.
Fan mode starts immediately.
STOP
If you want to stop the air conditioner,
Press ON/OFF button again.
NOTES
• Fan mode does not control temperature.
The setting temperature is not displayed on
the remote control display.
(14 )
1
3
2
USE OF REMOTE CONTROL (Cont.)
AIR FLOW DIRECTION CONTROL
‰
‰
‰
Air is supplied into the room through the supply air louvers located on the bottom of the indoor unit.
Air from the room is drawn into the indoor unit through the front panel and filters which are located
behind the front panel.
Make absolutely sure that the supply and return air flow of the indoor unit are not obstructed
(even partially).
•
Adjust supply air direction properly otherwise, it might
cause discomfort or cause uneven room temperatures.
•
Adjust the horizontal louver using the remote control.
•
Adjust the vertical louvers using manual.
CAUTION
•
The ↕ SWING button will be disabled when the air conditioner is not in operation
( including when the TIMER ON is set ).
•
Do not operate the air conditioner for long periods with the supply air direction set downward
in cooling or dry mode. Otherwise, condensation may occur on the surface of the horizontal
louver causing moisture to drop on to the floor or on furnishings.
•
Do not move the horizontal louver manually. Always use ↕ Swing button.
If you move horizontal louver manually, it may malfunction during operation.
If the louver malfunctions, stop the air conditioner once and restart it.
•
When the air conditioner is started immediately after it was stopped, the horizontal louver
might not move for approximately 10 seconds.
•
Open angle of the horizontal louver should not be set too small, as cooling performance may
be impaired due to too restricted air flow area.
•
Do not operate unit with horizontal louver in closed position.
•
When the air conditioner is connected to power (initial power), the horizontal louver may
generate a sound for 10 seconds, this is a normal operation.
(15 )
USE OF REMOTE CONTROL (Cont.)
↕ Swing Up and Down Function
To automatically ↕ Swing the horizontal louvers for the vertical supply
air direction ( Up- Down )
Perform this function while the air conditioner is in operation.
• Press ↕ Swing button on the remote control more than 2 seconds,
the louver will swing up and down automatically.
• Adjust the horizontal louvers automatically
Press ↕ Swing button on the remote control less than 2 seconds,
Used to stop or start horizontal louver movement or set the desired
up/down air flow direction. The louver changes 6 degree in angle for
each press
• To stop the function, press ↕ Swing button again.
Range
To set the horizontal supply air direction (left - right)
•
To set the horizontal air flow direction ( left - right ) move
the deflector rod manually to adjust the air flow in the
direction you prefer.
•
Adjust the vertical louvers manually using the lever on the
vertical louver arm.
•
Take care not to catch fingers on the fan, horizontal louver
or to damage vertical louvers.
When the air conditioner is in operation and the horizontal
louver is in a specific position, move the lever of vertical
louvers to right or left to adjust horizontal supply air.
(16 )
Deflector rod
For vertical Louver
USE OF REMOTE CONTROL (Cont.)
ECO Function
ECO function is useful when you go to sleep.
Carrier air conditioner automatically controls the selected temperature
and consequently controls the room temperature to avoid overcooling
or overheating and to have comfortable and healthy sleep.
ECO function with COOL Mode
If you want to operate ECO function with Cool mode to save energy and
maintain the most comfortable temperature during COOL mode,
apply the following steps :
Start:
Press ECO button to activate ECO function.
•
The fan speed will automatically change to low speed.
•
The set temperature will be automatically increased by 1°C
after 1 hour after COOL mode is selected.
•
Then the set temperature will be automatically increased by
another 1°C after additional 1 hour.
•
This new temperature will be maintained steady for the next
5 hours, after that the system will stop operation.
Stop:
If you want to cancel ECO function, press Mode button,
Fan button or On/Off button is pressed.
ECO function with COOL mode
ECO function with HEAT Mode
If you want to operate ECO function with Heat mode to save energy and
maintain the most comfortable temperature during HEAT mode,
apply the following steps :
Start:
Press ECO button to activate ECO function.
•
The fan speed will automatically change to low speed.
•
The set temperature will be automatically decreased by 1°C
after 1 hour after HEAT mode is selected.
•
Then the set temperature will be automatically decreased by
another 1°C after additional 1 hour.
•
This new temperature will be maintained steady for the next
5 hours, after that the system will stop operation.
Stop:
If you want to cancel ECO function, press Mode button,
Fan button or On/Off button is pressed.
(17 )
ECO function with HEAT mode
USE OF REMOTE CONTROL (Cont.)
TIMER ON Function
If you want to start automatically the air conditioner at the desired
time ( between 0 ~ 24 hrs ), use TIMER ON function
TIMER ON function is useful when you wake up in the morning
or when you return home.
TO SET TIMER ON TIME
1. Press the Timer button . The remote control shows TIMER ON, the
last Auto-on setting time and the signal " TIMER ON " will be
shown on the LCD display area. Now it is ready to reset the Auto-on
time to start the operation.
again to set desired Auto-on time.
2. Press the Timer button
Each time you press the button, the time increases by half
an hour between 0 and 10 hours and by one hour between 10
and 24 hours.
3. After setting the TIMER ON, there will be a one half second delay
before the remote control transmits the signal to the air conditioner.
Then after approximately another 2 seconds, the signal " TIMER
ON " will disappear and the set temperature will re-appear on the
LCD display of the remote control.
TIMER light of
appears on the display panel of the indoor unit.
TO CANCEL TIMER ON FUNCTION
Press Timer button
until the time setting is 0.0
EXAMPLE OF TIMER ON SETTING
To start automatically the air conditioner in 6 hours, apply the
following steps :
1. Press the Timer button , the last setting of starting operation
time and the signal " TIMER ON " will show on the display
of the remote control.
2. Press the Timer button
to display "6.0" on the TIMER ON
display of the remote control.
3. Wait for 0.5 second and the TIMER ON stops flashing and this
function is activated. The display of the remote control will
show the set temperature again.
Start
Off
Set
6 hours later
CAUTION
ƒ When you select the timer operation, the remote control automatically transmits the TIMER ON signal to the
indoor unit for the specified time.
Therefore, keep the remote control in a location where it can transmit the signal to the indoor unit properly.
ƒ The effective operation time set by the remote control for the TIMER ON function is limited to the following
settings: 0.0, 0.5, 1.0, 1.5, 2.0, 2.5, 3.0, 3.5, 4.0, 4.5, 5.0, 5.5, 6.0, 6.5, 7.0, 7.5, 8.0, 8.5, 9.0, 9.5, 10, 11, 12, 13, 14,
15, 16, 17, 18, 19, 20, 21, 22, 23, and 24.
(18 )
USE OF REMOTE CONTROL (Cont.)
TIMER OFF Function
If you want to stop automatically the air conditioner at the desired
time ( between 0 ~ 24 hrs ), use TIMER OFF function
TIMER OFF function is useful when you go to sleep.
TO SET TIMER OFF TIME
1. Press the Timer button
. The remote control shows TIMER OFF, the
last Auto-off setting time and the signal " TIMER OFF " will be shown
on the LCD display area. Now it is ready to reset the Auto-off time.
2. Press the Timer button
again to set desired Auto-off time. Each time
you press the button, the time increases by half an hour between 0 and
10 hours and by one hour between 10 and 24 hours.
3. After setting the TIMER OFF, there will be a one half second delay before
the remote control transmits the signal to the air conditioner. Then, after
approximately another 2 seconds, the signal " TIMER OFF " will
disappear and the set temperature will re-appear on the LCD display of
the remote control.
TIMER light of
appears on the display panel of the indoor unit.
TO CANCEL TIMER OFF FUNCTION
Press Timer button
until the time setting is 0.0
EXAMPLE OF TIMER OFF SETTING
To stop automatically the air conditioner in 10 hours.
1. Press the Timer button , the last setting of stopping
operation time and the signal " TIMER OFF " will show
on the display of the remote control.
to display "23" on the
2. Press the Timer button
TIMER OFF display of the remote controller.
3. Wait for 0.5 second and the TIMER OFF stops flashing and
this function is activated. The display of the remote
control will show the set temperature again.
Stop
On
Set
CAUTION
10 hours later
ƒ When you select the timer operation, the remote control automatically transmits the TIMER OFF signal to the
indoor unit for the specified time.
Therefore, keep the remote control in a location where it can transmit the signal where it can transmit the
signal to the indoor unit properly.
ƒ The effective operation time set by the remote control for the TIMER OFF function is limited to the following
settings: 0.0, 0.5, 1.0, 1.5, 2.0, 2.5, 3.0, 3.5, 4.0, 4.5, 5.0, 5.5, 6.0, 6.5, 7.0, 7.5, 8.0, 8.5, 9.0, 9.5, 10, 11, 12, 13, 14,
15, 16, 17, 18, 19, 20, 21, 22, 23, and 24.
(19 )
USE OF REMOTE CONTROL (Cont.)
COMBINATION OF ON TIMER AND OFF TIMER FUNCTIONS SIMULTANEOUSLY
ON TIMER → OFF TIMER ( Stop → Operation → Stop )
You can use this setting to automatically start the air conditioner when you wake up and automatically
stop it when you leave the house.
Example:
If you want to start the air conditioner automatically 2 hours after setting
and stop it automatically 5 hours after setting :
1. Set TIMER ON at 2 hours.
Start
Off
Stop
2. Set TIMER OFF at 5 hours.
Set
2 hours later
after setting
5 hours later
after setting
COMBINATION OF OFF TIMER AND ON TIMER FUNCTIONS SIMULTANEOUSLY
OFF TIMER → ON TIMER ( Operation → Stop → Operation )
You can use this setting to automatically stop the air conditioner after you go to sleep and start it
automatically again in the morning when you wake up or you return home.
Example:
If you want to stop the air conditioner automatically 2 hours after setting
and start it automatically again 10 hours after setting :
1. Set TIMER OFF at 2 hours.
Start
Stop
On
2. Set TIMER ON at 10 hours.
Set
2 hours later
after setting
10 hours later
after setting
CAUTION
ƒ If you want to cancel ON or OFF timer setting, press TIMER ON or TIMER OFF until the time is 0.0
ƒ The timer setting ( TIMER ON or TIMER OFF ) that in sequence occurs directly after the set time
will activated first.
ƒ The timer function (ON or OFF ) which in time is closest to the actual time will be activated first.
ƒ If the same time is set for both ON and OFF timers, no timer operation is performed.
The air conditioner may stop operating, either immediately or after approximately 10 minutes.
(20 )
USE OF REMOTE CONTROL (Cont.)
SELF CLEAN FUNCTION / FRESH FUNCTION
Self Clean function
ƒ Press this button less than 2 seconds will initiate Self Clean function
Then the symbol " SC " will appear on the front panel on the indoor unit
ƒ The air conditioner will automatically clean and dry the Evaporator and
keep it as fresh for the next operation.
Operate Self Clean function with Cool Only High Wall Split System
ƒ If you want to activate Self Clean function, Press Self Clean button less than
2 seconds Self Clean during unit ON and Self Clean will start operation.
Then the symbol " SC " will appear on the front panel on the indoor unit and the air conditioning works, respectively the
following steps :(1) Process fan only mode when low speed for 13 minutes
(2) Turn off Self Clean function
(3) Turn off air conditioner
Operate Self Clean function with Heat Pump High Wall Split System
ƒ If you want to activate Self Clean function, Press Self Clean button less than
2 seconds Self Clean during unit ON and Self Clean will start operation.
ƒ Then the symbol " SC " will appear on the front panel on the indoor unit and
the air conditioning works, respectively the following steps :(1) Process fan only mode when low speed for 13 minutes
(2) Process Heat mode for 1 minute
(3) Process fan only mode for 2 minutes
(4) Turn off Self Clean function
(5) Turn off air conditioner
START
If you want to activate Self Clean function,
Press Self Clean button less than 2 seconds Self Clean
during unit ON and Self Clean will start operation.
ƒ
STOP
ƒ
If you want to stop Self Clean function,
Press Self Clean button less than 2 seconds.
Fresh function
( Not available for this product )
(21 )
USE OF REMOTE CONTROL (Cont.)
FOLLOW ME FUNCTION
Follow Me function
ƒ
Press this button less than 2 seconds will initiate Follow Me function
ƒ
In Follow Me function, the remote control serves as a remote thermostat allowing for the precise
and comfortable temperature control when you stay close to the remote control. With this
technology, an efficient temperature sensor is built in the remote control.
ƒ
Follow Me function starts when the indoor unit receives the signal from the remote control and the
air conditioner is operated by the temperature information included in the signal and the set
temperature. In this mode, the return air temperature sensor in the indoor unit is inactive.
ƒ
When the indoor unit receives the signal, the buzzer in the indoor unit will sound once.
ƒ
When the Follow Me function is activated, the remote display is actual temperature at its location.
The remote control will send this signal to the air conditioner every 3 minutes interval until press the
Follow Me button again.
ƒ
The Follow Me function is not available under DRY and FAN mode.
ƒ
Switch the operation mode or turn off the unit will cancel the Follow
Me function automatically.
START
ƒ
If you want to activate Follow Me function, Press Follow Me button
Follow Me during unit ON and Follow Me will start operation. Then
will appear on the display of the
the led light of Follow Me function
remote control.
The remote control begins to detect the actual temperature as its location.
STOP
ƒ
If you want to stop Follow Me function,
Press Follow Me button less than 2 seconds.
(22 )
USE OF REMOTE CONTROL (Cont.)
LED FUNCTION
LED function
ƒ
Press this button less than 2 seconds will initiate
LED function
ƒ
Press this button to clear or light the display on
the indoor unit and display of wireless remote control.
(23 )
USE OF REMOTE CONTROL (Cont.)
TURBO FUNCTION
Turbo function
with COOL mode :
ƒ If you want faster cooling at super high airflow, super high fan speed
to reach the set temperature in the shortest time, Press TURBO button.
•
Turbo function will give faster cooling as super high fan speed for
about 20 minutes.
•
In this case TURBO powerful cooling will operate for about half an hour.
After half an hour, the fan speed will revert back to the previous
set fan speed.
NOTES:
• To cancel TURBO function, Press again TURBO button.
• In TURBO function, the fan speed can be adjusted.
• TURBO Function is not available with ECO function.
• TURBO function will cancel and indoor fan motor will
get back to the presetting speed
when one of following condition occur :
a. mode changed.
b. get into Force Cooling mode.
c. turn off the air conditioner.
(24 )
8. AIR FILTERS CLEANING
The air filters behind the front panel of the indoor unit should be checked and cleaned
every month. Clogged air filters will reduce cooling and heating efficiency.
WARNING:
It is necessary to stop the air conditioner and disconnect the power supply before
cleaning air filters.
Standard
Air
Filter
-
(1) Main air filters for dust removal
(2) Formaldehyde Filter for remove gases and odors to have healthy air always.
STEPS FOR CLEANING AIR FILTERS :
1. Lift the front panel of indoor unit with both hands
up to an angle until it stops with a clicking sound.
2. Take hold of the handle of the man air filter and
lift it up slightly to take ot out from the filter
holder then pull it downwards.
3. Remove Formaldehyde air filter
from its support frame as shown in the figure.
4. Clean the main filters with a vacuum cleaner or
water then dry it up in cool space.
Clean Formaldehyde air filter
with a vacuum cleaner.
5. Install Formaldehyde air filter
back into position.
6. Insert the upper portion of the main air filter back
into the unit taking care that the left and right edges
line up correctly and place filter into position.
NOTES
(1) To establish, how frequently the air filters should be cleaned, the operating conditions
must be taken in to account.
(2) The operating life of Formaldehyde air filter is two years.
(3)
Before operating the air conditioner, check that air filters are in their places inside unit.
(25 )
9. INDOOR UNIT CLEANING
Warning!
The indoor unit must be disconnected from the main supply before indoor unit cleaning.
Cleaning the indoor unit and remote controller
CAUTIONS
• Use a dry cloth to wipe the indoor unit and remote control.
• A cloth dampened with cold water may be used on the indoor unit if it is very dirty.
• The front panel of the indoor unit can be removed and cleaned with water.
Then wipe it with a dry cloth.
• Do not use water to clean inside the air conditioner exposure to water can destroy the electrical
insulation, leading to possible electric shock.
• Do not use a chemically treated cloth or duster to clean the unit.
• Never use water hotter than 40°C to clean the front panel, if could cause deformation of discoloration.
• Avoid any contact with heat sources as hot air which can damage the indoor unit casing.
• Do not use benzene, thinner, polishing powder, or similar solvents for cleaning.
These may cause the plastic surface to crack or deform.
(26 )
10. PERIODICAL CHECKS
WARNING:
It is necessary to stop the air conditioner and disconnect the power supply before
performing service and maintenance operations.
For a good operation of the air conditioner it is recommended to carry out periodic
service and maintenance of the air conditioner or upon customer request through
Carrier or Carrier authorized dealer.
Recommended service and maintenance works and intervals may vary depending on
the installation environment, e.g. dusty zones, etc. see below table :
Indoor Unit
Every Month
Clean air filters (3)
Every Year
●(1)
Clean front panel (2)
●
Clean indoor coil (2)
●
Clean drain pipe (2)
●
Change remote control batteries (4)
●
Outdoor Unit
Every Month
Every Year
Clean outdoor coil (2)
●
Blow air over electric parts (2)
●
Check electric connection tightening (2)
●
Clean fan wheel (2)
●
Check fan tightening (2)
●
Clean drain pan (2)
●
NOTES
(1)
(2)
(3)
(4)
Increase frequency in dusty zones.
Service and maintenance works to be carried out by qualified service personnel.
Cleaning air filters can be done by customer every month.
Changing batteries of remote control can be done by customer every year.
(27 )
11. CONSIDERATIONS BEFORE A LONG SHUTDOWN
PERIOD OF AIR CONDITIONER
Keep the indoor unit in operation for half
a day in the ventilation (fan only) mode
in order to dry all internal parts.
12h
Switch electric mains supply off.
Take batteries out of the remote control.
Clean indoor and outdoor units.
Clean the air filters and reposition them
in the unit.
Air Filters
(28 )
12. OPERATION TIPS
The following events may occur during normal operation of the air conditioner :
1. A slight white mist (water vapor)coming out from the indoor unit during COOL mode
ƒ A white mist may generate due to a large temperature difference between air inlet and air outlet on
COOL mode in an indoor environment that has a high relative humidity.
The cool air from the indoor unit is coming into contact with the room air.
ƒ A white mist may generate due to moisture generated from defrosting process when the air
conditioner restarts in HEAT mode operation after defrosting (only for heat pump system ).
2. Low noise of the air conditioner
ƒ You may hear a low hissing sound when the air conditioner is running or has just stopped running.
This sound is the sound of the refrigerant beginning to circulate or an adjustment of the refrigerant
pressures after stopping.
ƒ You can also hear a low short "squeak" when the indoor unit is in operation or when it has stopped.
These are generally due to the temperature changes on the plastic parts ( expansion or contraction ).
ƒ A noise may be heard due to louver restoring to its original position when power is first turned on.
3. Dust is blown out from the indoor unit.
This is a normal condition when the air conditioner has not been used for a long time or during first
use of the unit.
4. Unpleasant smells coming out from the indoor unit.
ƒ Unpleasant smells can be caused by substances accumulated in the air filters of indoor unit.
ƒ In this case, you must switch the system off and air filters must be cleaned.
ƒ Restart the indoor unit in ventilation ( fan only ) mode and open windows to change the room air.
5. The air conditioner turns to FAN only mode from COOL mode or HEAT mode.
When indoor temperature reaches the temperature setting on air conditioner, the compressor will
stop automatically, and the air conditioner turns to FAN only mode.
The compressor will start again when the indoor temperature rises on COOL mode or falls on HEAT
mode to the set point.
6. Dripping water may generate on the surface of the indoor unit during COOL mode
in a high relative humidity (higher than 80%).
Adjust the horizontal louvers to the maximum air outlet position and select HIGH fan speed.
7. Mist (water vapor) coming out from the outdoor unit during HEAT mode
It is normal in heat pump operation when defrost is automatically activated during heating operation
at very low ambient temperature ( only for heat pump system ).
8. Lightning or a car wireless telephone operating nearby may cause the system
to malfunction.
Disconnect the system with power and then re-connect the system with power again.
Press ON/OFF button on the remote control to restart operation.
(29 )
13. TROUBLE SHOOTING
If you have problems with your room air conditioner, check this trouble-shooting guide before contacting
Carrier or Carrier certified dealer.
If the abnormality persists and cannot be solved with the given instructions, turn off the air conditioner
and does not try to turn it on again, call Carrier or Carrier certified dealer.
TROUBLE
After batteries have
been placed into the
remote control, the
remote control cannot
operate the air
conditioner.
When pressing start
button, unit does not
acknowledge signal
with a beep.
POSSIBLE CAUSES
Batteries are exhausted or have the
wrong polarity.
Main switch is OFF.
Remote control batteries are exhausted.
Remote control has not been pointed
correctly to the receiver of unit.
SOLUTIONS
Replace batteries or check
polarity.
Switch it to ON position.
Replace batteries.
Turn remote control OFF and
repeat the operation in the
correct direction.
OR
There are obstacles (curtains, walls, etc.) Repeat the operation after having
between the remote control and the unit removed the obstacles.
When pressing stop
Receiver on the unit or the remote
Avoid direct sun on the unit, shut
button, unit does not control is under intense sun radiation.
curtains or shades.
acknowledge signal
Signal transmission is obstructed by
Avoid sending signals when
with a beep.
severe interference from an
computers or household
electromagnetic field.
appliances (Food processors,
coffee makers, etc.) are operating
close by cellular or cordless
telephones may also interfere
with the control.
Air conditioner will
Main supply switch is OFF
Switch to ON
not start.
Fuses or main switch are blown
Replace fuses
Protection against frequent compressor Wait for 3 minutes.
cycling is ON
Set temperature is higher than the room Correct set temperature.
temperature in the cool mode or lower
than the room temperature in heat mode.
Air conditioner does Air flow cannot circulate freely
Remove obstructions.
not cool the room
Dirty filters reduce air quantity
Clean air filters
adequately.
circulating.
Doors and/or windows are open.
Close doors and windows
Fan speed has been set to “Low”
Set fan speed at high speed.
Set temperature is high in the cool mode. Correct selected temperature.
Incidence of strong sun rays in the room Use shut curtains or shades
Unit wrongly selected for the room
Redefines adequate unit for the
room.
Air conditioner stops TIMER OFF function is working
Cancel TIMER OFF function
during cooling
Room temperature is lower than set
Normal operation
temperature
Ice or frost forms on Insufficient air circulation
Remove obstructions in front of
the indoor coil during
the unit
cooling
Dirty air filters
Clean air filters
(30 )
TROUBLE SHOOTING (Cont.)
TROUBLE
Air conditioner does
not heat the room
adequately.
POSSIBLE CAUSES
Air flow cannot circulate freely
Dirty filters reduce air quantity
circulating.
Doors and/or windows are open.
Fan speed has been set to “Low”
Set temperature is lower in heat
mode.
Unit wrongly selected for the room
Air conditioner stops
during heating
TIMER OFF function is working
Room temperature is high than set
temperature
A slight whistling
This is due to the refrigerant
noise is heard when is beginning to circulate or an
heard when the air
adjustment of the refrigerant
conditioner starts or pressures.
stops.
Unpleasant smells
Unpleasant smells can be caused
coming from the unit. by substances accumulated in the
air filter
SOLUTIONS
Remove obstructions.
Clean air filters
Close doors and windows
Set fan speed at high speed.
Correct selected temperature.
Redefines adequate unit for the room.
Cancel TIMER OFF function
Normal operation
Normal operation
Switch the system OFF and contact an
authorized service center to have the
filters cleaned.
Restart unit in the ventilation (fan only)
mode and open windows to change
room air.
Normal operation
Strange noises
Occasionally the unit can emit
coming from the unit. some strange short noises during
operation or when it has stopped.
These are generally due to the of
temperature changes on the plastic
parts.
Water dripping inside Clogged drain
Remove the obstructions from the
the room to be air
drain
conditioned.
Incorrect installation
Correct the installation as described in
installation manual
Malfunction appears Before contacting service center of If checks are OK, call service center
on the display panel & Carrier or one of Carrier authorized of Carrier or one of Carrier authorized
Error Code on indoor dealers, make the following checks: dealers.
unit.
ƒ Air filters are clean.
Leds status refers to
ƒ Air circulation of indoor unit is
malfunction.
not obstructed.
ƒ Air circulation of outdoor unit
is not obstructed.
(31 )