INSTALLATION GUIDE
CURRENT MONITORING
TM
H606
TM
606
Split-Core Current Switch, Adjustable Trip Point
Installer’s Specifications
Amperage Range
1.25-50 A Continuous
External Supply Voltage
5-30 VDC
Insulation Class
600 VAC RMS (UL) 300 VAC RMS (CE)
Frequency
50/60 Hz
Temperature Range-15° to 60°C (5° to 140°F)
Humidity Range
10-90% RH non-condensing
Hysteresis
10% typical
Status Output Ratings
N.C. 0.1 [email protected] VDC polarity sensitive
Off State Resistance (max.)
34 µ[email protected] VDC; 200 µ[email protected] VDC
On State Voltage Drop
1.9 VDC (max.)@0.1 A
Terminal Block Max. Wire Size
14 AWG
Terminal Block Torque (nom.)
4 in-lbs (0.45 N-m)
Agency Approvals
UL508, E150462
Specification Note: For CE compliance, conductor shall be insulated according to IEC 61010‑1:2010,
Installation Category III or equivalent.
The unit design provides for basic insulation only.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
•
•
•
•
•
Follow safe electrical work practices. See NFPA 70E in the USA, or applicable local codes.
This equipment must only be installed and serviced by qualified electrical personnel.
Read, understand and follow the instructions before installing this product.
Turn off all power supplying equipment before working on or inside the equipment.
Use a properly rated voltage sensing device to confirm power is off.
DO NOT DEPEND ON THIS PRODUCT FOR VOLTAGE INDICATION
• Only install this product on insulated conductors.
Failure to follow these instructions will result in death or serious injury.
NOTICE
•
•
•
•
INSTALLATION
Disconnect and lock out power to the enclosure containing the
conductor to be monitored.
1. Locate a mounting surface for the removable mounting bracket that will allow
the monitored conductor to pass through the center window when it is installed
and that will keep the product at least 1/2” from any uninsulated conductors.
Determine cable routing for the controller connection, allowing wiring to reach
the mounting location.
2. Drill holes to mount the bracket to the chosen surface using the included screws.
This product is not intended for life or safety applications.
Do not install this product in hazardous or classified locations.
The installer is responsible for conformance to all applicable codes.
Mount this product inside a suitable fire and electrical enclosure.
WIRING EXAMPLE
3. Wire the output connections between the sensor and the controller (solid-state
contact) or external power supply.
4. Snap the sensor over the wire to be monitored and clip the assembly to the
mounting bracket.
5. Calibrate the sensor (see page 2) with the load running normally.
Insulated Conductor ONLY
CONTACTOR
6. Secure enclosure and reconnect power.
DIMENSIONS
DDC CONTROLLER
-
+
-
+ DI
Removable Mounting Bracket
0.6"
(16 mm)
1.2"
(31 mm)
0.7"
(18 mm)
2.1"
(54 mm)
0.5"
(13 mm)
+
2.1"
(54 mm)
5-30VDC
POWER SOURCE
Fan or Pump
0.4” x 0.2”
(10 mm x 5 mm)
Slot (2x)
Motor
Z201760-0E
PAGE 1
2.5" *
(64 mm)
1.0" *
(26 mm)
2.9"
(74 mm)
3.5"
(89 mm)
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
01121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
INSTALLATION GUIDE
H606
TM
OPERATION
CALIBRATION
The H606 is a current-sensitive switching device that monitors current (amperage) in
the conductor passing through it. A change in the conductor’s amperage that crosses
the adjustable switch threshold plus the hysteresis value causes the resistance of
the FET status output to change state, similar to the action of a mechanical switch.
In this model, the setpoint is adjustable through the action of a twenty (20) turn
potentiometer (see the CALIBRATION section). The status output is suitable for
connection to building controllers or other appropriate data acquisition equipment
operating at 5 to 30 volts. The H606 requires 5 to 30 VDC external power supply to
generate its output.
Before beginning calibration, establish normal load conditions.
NOTES
For load currents greater than sensor maximum rating:
Use a 5 Amp (H68xx series) Current Transformer (CT) as shown. This technique can be
combined with wrapping (see below) to add range for a low current load on a high
current source.
> 50A (Sensor max.)
240A
OK!
OK!
A
Then choose either A or B below.
A. To monitor under-current (belt loss, coupling shear, status)
!
STATUS
OK!
OK!
A
1. Turn setpoint screw
clockwise until Status Closed
LED turns on.
Status
Closed Setpoint
STOP
2. Slowly turn the screw counter‑clockwise until the Status Open LED just
turns on.
3. Turn the
Setpoint
Status
Setpoint Open
setpoint screw an
additional 1/4 turn
1/4 counter‑clockwise
for operational
STOP
margin.
+
300A:5A
S
RIE 23
USTon 972 56
4-85
IS IND
, Oreg 0-35
VER land 1-80
®
keye
Port
H68xx-5A CT
Haw
4A
B. To monitor over-current (mechanical problems, seized impeller)
STATUS
!
DANGER: 5A CTs can present hazardous voltages.
Install CTs in accordance with manufacturer's instructions.
Terminate the CT secondary before applying current.
CAUTION
RISK OF EQUIPMENT DAMAGE
• Derate the product’s maximum current for the number of turns
through the sensing window using the following formula.
OK!
OK!
A
Status
Setpoint Open
1. Turn setpoint screw
counter‑clockwise until Status
Open LED turns on.
STOP
2. Slowly turn the setpoint screw clockwise until the Status Closed LED
just turns on.
Rated Max. Amps ÷ Number of Turns = Max. monitored Amps
Status
Closed Setpoint
e.g. : 100A ÷ 4 Turns = 25 Amps max. in monitored conductor
• Failure to follow these instructions can result in overheating
and permanent equipment damage.
STOP
+
Setpoint
1/4
For load currents less than sensor minimum rating:
Wrap the monitored conductor through the center window and around the sensor
body to produce multiple turns. This increases the current measured by the
transducer.
< 1.25 A (Sensor Min.)
4x
0.5A
TROUBLESHOOTING
Problem
• Check sensor calibration (see above)
• Check for control voltage/current at sensor (<30V, <0.2A)
• Check for amperage in monitored conductor (> 1.25A)
• Check that at least 5 VDC are across the contacts.
• Assure that sensor core mating surfaces are clean and that
the core clamp is completely closed
Setpoint screw has no
stops
The setpoint screw has a slip-clutch at both ends of its travel to
avoid damage. Twenty turns CCW will reset the sensor to be
most sensitive. Repeat calibration above.
Both LEDs are lit
Setpoint screw is too far clockwise. See solution above.
ES 23
USTRI 972 56
4-85
gon
IS INDOre 0-35
VER tland, 1-80
®
Por
keye
PAGE 2
Solution
No Reading at Controller
Haw
Z201760-0E
3. Turn the
setpoint screw
an additional 1/4
turn clockwise
for operational
margin.
©2012 Veris Industries USA 800.354.8556 or +1.503.598.4564 / [email protected]
01121
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement