VD550
Diesel Product Line
208-600 Volt
60 Hz / 1800 RPM
VD550-01
550 kWe / 510 kWe
Standby / Prime
Ratings
208V
240V
480V
600V
Phase
3
3
3
3
PF
0.8
0.8
0.8
0.8
Hz
60
60
60
60
Generator Model
572RSL4031
572RSL4031
572RSL4029
572RSS4272
Connection
12 LEAD WYE
12 LEAD DELTA
12 LEAD WYE
4 LEAD WYE
kWe
550
550
550
550
AMPS
1911
1656
828
662
Temp Rise
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
130˚C / 27˚C
kWe
510
510
510
510
AMPS
1772
1535
768
614
Temp Rise
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
105˚C / 40˚C
Standby
Prime
Standard Equipment
Generator
Engine
„„Radiator
Cooled Unit Mounted (50˚C)
Additional
„„Brushless
Single Bearing
„„Microprocessor
Voltage Regulator
„„Base
- Structural Steel
Line Circuit Breaker Mounted & Wired
„„Blower
Fan & Fan Drive
„„Automatic
„„Starter
& Alternator
„„±
.25% Voltage Regulation
„„Main
Pole, Rotating Field
Based Digital Control
„„Oil
Pump & Filter
„„4
„„Critical
Grade Silencer Mounted
„„Oil
Drain Extension w/Valve
„„130˚C
Standby Temperature Rise
„„Battery
Charger 24V 5 Amp
„„105˚C
Prime Temperature Rise
„„Jacket
of Rated Load - One Step
„„Governor
- Electronic Isochronous
„„24V
Battery System & Cables
„„100%
„„SAE
Flywheel Housing
„„5%
„„Air
Cleaner (Dry Single Stage)
„„Flexible
„„EPA
Fuel Connectors
Certified - Tier 2
Maximum Harmonic Content
„„NEMA
MG 1, IEEE and ANSI standards
compliance for temperature rise
Water Heater -20˚F 5000W 240V
w/Isolation Valves
„„Vibration
Isolation Mounts (Pad Type)
„„Radiator
Duct Flange (OPU Only)
„„Single
Source Supplier
„„2YR
/ 2000HR Standby Warranty
„„1YR
/ 1500HR Prime Warranty
„„Standard
VD550-01
Colors - White / Tan / Gray
1
Diesel Product Line
550 kWe / 510 kWe
Application Data
Engine
Manufacturer:
Volvo
Model:
TAD1642GE
Type:
Aspiration:
4-Cycle
Turbo Charged, Air to Air CAC
Cylinder Arrangement:
6 Cylinder Inline
Displacement - Cu. In. (lit):
Bore - in. (cm) x Stroke - in. (cm):
984 (16.12)
5.7 (14.4) x 6.5 (16.5)
Compression Ratio:
Rated RPM:
Max HP Stby (kWm):
16.5:1
1800
822 (613)
Exhaust System
Standby
Prime
Gas Temp. (Stack): °F (°C)
954 (512)
874 (468)
Gas Volume at Stack Temp: CFM (m³/min)
4,153 (118)
3,846 (109)
Maximum Allowable Exhaust Restriction: in. H2O (kPa)
40.2 (10.0)
32.1 (8.0)
Ambient Capacity of Radiator: °F (°C)
122 (50.0)
122 (50.0)
Maximum Allowable Static Pressure on Rad. Exhaust: in. H20 (kPa)
0.5 (0.12)
0.5 (0.12)
Water Pump Flow Rate: Gpm (lit/min)
122 (462)
122 (462)
Heat Rejection to Coolant: BTUM (kW)
14,104 (248)
12,397 (218)
Heat Rejection to CAC: BTUM (kW)
9,042 (158)
7,957 (139)
Heat Radiated to Ambient: BTUM (kW)
4,253 (74.4)
3,919 (68.6)
Aspirating: CFM (m³/min)
1,646 (46.6)
1,603 (45.4)
Air Flow Required for Rad. Cooled Unit: CFM (m³/min)
21,120 (598)
21,120 (598)
Cooling System
Air Requirements
Air Flow Required for Heat Exchanger/Rem. Rad. CFM (m³/min)
Consult Factory For Remote Cooled Applications
Fuel Consumption
At 100% of Power Rating: gal/hr (lit/hr)
39.9 (151.0)
35.9 (136.0)
At 75% of Power Rating: gal/hr (lit/hr)
28.8 (109.0)
26.0 (98.0)
At 50% of Power Rating: gal/hr (lit/hr)
19.1 (72.0)
17.5 (66.0)
Total Oil System: gal (lit)
12.7 (48.0)
12.7 (48.0)
Engine Jacket Water Capacity: gal (lit)
8.7 (33.0)
8.7 (33.0)
System Coolant Capacity: gal (lit)
15.9 (60.0)
15.9 (60.0)
Fluids Capacity
Deration Factors
Rated Power is available up to 4920 ft (1500 m) at ambient temperatures to 122˚F (50˚C).
Consult factory for site conditions above these parameters.
VD550-01
2
Diesel Product Line
550 kWe / 510 kWe
DGC-2020 Control Panel
Standard Features
„„Digital
Metering
„„Engine
Parameters
„„Generator
„„Engine
„„CAN
Protection Functions
Protection
Bus ECU Communications
„„Windows-Based
„„Multilingual
„„Remote
Software
Capability
Communications to RDP-110 Remote Annunciator
„„16
Programmable Contact Inputs
„„Up
to 15 Contact Outputs (7 standard)
„„UL
Recognized, CSA Certified, CE Approved
„„Event
„„IP
Recording
54 Front Panel Rating with Integrated Gasket
„„NFPA
110 Level 1 Compatible
Weights / Dimensions / Sound Data
LxWxH
Weight lbs
OPU
150 x 68 x 98 in
9575
Level 1
150 x 68 x 114 in
10,825
Level 2
150 x 68 x 125 in
11,475
Level 3
205 x 68 x 114 in
12,125
Height measured from bottom of base to exhaust stack.
No Load
Full Load
OPU
88 dBA
93 dBA
Level 1
83 dBA
88 dBA
Level 2
82 dBA
86 dBA
Level 3
72 dBA
76 dBA
Drawings based on standard open power 480 volt standby generator. Lengths may vary with other voltages. Subject to change without notice.
Sound data as measured at 23 feet (7 meters) in accordance with ISO 8528-10 at standby rating.
VD550-01
3
Diesel Product Line
550 kWe / 510 kWe
Optional Enclosures and Fuel Tanks
*Level 1 enclosures are 100 MPH Wind Rated as standard (up to 150 MPH available).
**Level 2 & 3 enclosures are 150 MPH Wind Rated as standard.
***Enclosure height does not include unit base or exhaust stack.
Double Wall UL 142 Listed Fuel Tanks
24 Hour (1250 Gallon)
48 Hour (2500 Gallon)
72 Hour (3750 Gallon)
A
B
C
A
B
C
A
B
C
OPU
175.00
68.00
36.00
315.00
68.00
36.00
460.00
68.00
36.00
Level 1
175.00
68.00
36.00
315.00
68.00
36.00
460.00
68.00
36.00
Level 2
175.00
68.00
36.00
315.00
68.00
36.00
460.00
68.00
36.00
Level 3
205.00
68.00
30.00
315.00
68.00
36.00
460.00
68.00
36.00
*All specification sheet dimensions are represented in inches.
**All enclosures and fuel tanks are based on the standard standby unit configuration. Any deviation can change dimensions.
***Level 1 enclosure not UL listed.
Materials and specifications subject to change without notice.
Distributed By:
Materials and specifications subject to change without notice.
Po
Powerdak Power Products LLC. | 3350 Jet Dr. Rapid City SD 57703 | Phone + 1 605-718-9960 |
VD550-01
Rev1.0
4
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement