SP1763 EIPM 2 10

SP1763 EIPM 2 10
Anybus X-gateway - EtherNet/IP™ Scanner Interface
Product Overview
Network Installation Sheet
LED Indicators
The EtherNet/IP Scanner interface can only be mounted in the top slot
of the Anybus X-gateway.
LED
Indication
GW Status
See Gateway Installation Sheet
LA
Top view
IP Address Configuration Switches
EtherNet/IP Connector (X1)
IP Address Configuration Switches
MS
Power Connector (X3)
1 2 3 4 5 6 7 8
ON
NS
Front view
Meaning
Green
Link established
Green (flashing)
Receiving/transmitting data
Off
Link not detected
Green
Normal operation
Green (flashing)
Standby, not yet configured
Red
Major fault, unrecoverable
Red (flashing)
Minor fault, recoverable
Red/green (alternating)
Hardware self test
Off
No power
Green
EtherNet/IP connection(s) OK
Green (flashing)
No EtherNet/IP connections
Red
Duplicate IP address
Red (flashing)
Connection timeout
Red/green (alternating)
Hardware self test
Off
No power or no IP address set
Sets the binary value of the last byte of the IP address within subnet
192.168.0.1–254 (netmask 255.255.255.0). To use a different subnet,
set all switches to OFF and configure via the Anybus IPconfig tool.
1
OFF
OFF
OFF
ON
ON
2
OFF
OFF
OFF
ON
ON
3
OFF
OFF
OFF
ON
ON
Switch position
4
5
6
OFF OFF OFF
OFF OFF OFF
OFF OFF ON
ON
ON
ON
ON
ON
ON
7
OFF
OFF
OFF
ON
ON
1 2 3 4 5 6 7 8
8
OFF
ON
OFF
OFF
ON
IP address
(example)
Set by software
192.168.0.1
192.168.0.2
192.168.0.254
(Not valid)
= 192.168.0.1
ON
Accessories Checklist
The following items are required for installation:
•
EtherNet/IP configuration tool (optional, not included)
•
USB cable (included)
•
EDS file for EtherNet/IP (see www.anybus.com)
•
LAN cable (not included)
Installation and Startup Summary
GW Status
LA
MS
NS
(Depending on your setup, some steps may not be required.)
1. Connect the gateway to the EtherNet/IP network
2. Set a valid IP address for the EtherNet/IP interface
(contact your network administrator for information)
3. Connect a PC to the gateway via USB
4. Power up and configure the gateway
5. Install the EDS file in the EtherNet/IP configuration tool
Status LED:s
EtherNet/IP (RJ45) Connector
USB Connector (X4)
1
8
Pin
Signal
1
TD+
2
TD-
3
RD+
4, 5, 7, 8
Termination to PE
6
RD-
Technical Support
Technical support, documentation and software downloads are
available at www.anybus.com.
Technical questions regarding the EtherNet/IP fieldbus system should
be addressed to ODVA at www.odva.org.
ODVA™ and EtherNet/IP™ are trademarks of ODVA, Inc.
SP1763, rev. 2.10, Sep 2015
www.anybus.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement